TEHNIČKO UPUTSTVO / TECHNICAL MANUALTEHNIČNA NAVODILA
za montažu, upotrebu i održavanje akumulacijskog spremnika /for instalation, use and maintenance of the water accumulation tanks /za montažo, uporabo in vzdrževanje akumulacijskega rezervoarja
TUCAS1-08/2017
CAS; -S; -B; -BS
HEATING TECHNIQUE
Centrometal d.o.o. - Glavna 12, 40306 Macinec, Croatia, tel: 040 372 600, fax: 040 372 611
HR EN SLO
2 Tehničko uputstvo CAS, CAS-B, CAS-S i CAS-BS
Dimenzije i osnovni dijelovi akumulacijskog spremnika
CAS CAS-S
Termometar
Termometar
Toplinskaizolacija
Mjesto za temp. osjetnik
Mjesto za temp. osjetnik
F
DC
B
A
Priključak (unut.nav.) *
Termometar
Termometar
Postolje spremnika
Priključak (unut.nav.) *
Priključak (unut.nav.) *
Mjesto za temp. osjetnik
Mjesto za temp. osjetnik
Priključak (unut.nav.) *
E
Tijelo spremnika
Cijevni izmjenjivač(umutarnji navoj 5/4")
CAS CAS-S
90
°
90
°
G
H
Priključak (unut.nav.) *
Priključak (unutarnji navoj) *
Mjesto za temp. osjetnik
Cijevni izmjenjivač(umutarnji navoj 5/4")
Priključak (unutarnji navoj) *
Priključak 1/2" za termometar
Cijevni izmjenjivač(unutarnji navoj 5/4")
Cijevni izmjenjivač(unutarnji navoj 5/4")
Priključak (unutarnji navoj) *
* - Priključak 6/4" (CAS 501 - 2001), 2" (CAS 3001 - 4001) (unutarnji navoj)
HR
3Tehničko uputstvo CAS, CAS-B, CAS-S i CAS-BS
Dimenzije i osnovni dijelovi akumulacijskog spremnika
CAS-BS
90
°
90
°
Priključak 1/2" za termometar
Otvor za osjetnik
Cirkulacija (unutarnji navoj 3/4")
Topla sanitarna voda(unutarnji navoj 3/4")
Priključak 6/4’’(unut.nav.)
Hladna sanitarna voda(unutarnji navoj 3/4")
Cijevni izmjenjivač(umutarnji navoj 5/4")
Mjesto za temp. osjetnik
Hladna sanitarna voda(unutarnji navoj 3/4")
Topla sanitarna voda(unutarnji navoj 3/4")
Priključak 6/4’’(unut.nav.)
Priključak 6/4”(unutarnji navoj)
Cirkulacija(unutarnji navoj 3/4")
CAS-B
CAS-BSCAS-B
Termometar
Termometar
Termometar
Mjesto za temp. osjetnik
Mjesto za temp. osjetnik
Cijevniizmjenivač(unutarnji
navoj 5/4'')
Inox bojler PTV
Priključak 6/4” (unutarnji navoj)
Priključak 6/4’’(unut.nav.)
Toplinskaizolacija
Termometar
Priključak 6/4’’(unut.nav.)
Priključak 6/4’’(unut.nav.)
Mjesto za temp. osjetnik
Priključak 6/4’’(unut.nav.)
Mjesto za temp. osjetnik
Postolje spremnika
Cijevni izmjenjivač(unutarnji navoj 5/4")
Cijevni izmjenjivač(unutarnji navoj 5/4")
Poklopac otvora zareviziju PTV
Poklopac otvora zareviziju PTV
Tijelo spremnika
Otvor za osjetnik
HR
4 Tehničko uputstvo CAS, CAS-B, CAS-S i CAS-BS
Tehnički podaci
Tip1001 2001501 801
0,8 1,0 2,0 3,0 4,0
2
3
4
5
6
8
10
20
30
40
Slika 1. Otpor protoka CAS
Količina protoka u m /h3
Otp
or
pro
tok
a u
mb
ar
CAS1001501 801
CAS-S1001501 801
CAS-BS1501
Volumen
Promjer tijela sprem. G
Vanjski promjer H
Ukupna visina F
Priključci
Max. radni tlak
Max. radna temp.
Min. visina prostorije
Masa pr. tijela spr.
Masa praznog spremnika
Volumen sprem. PTV
Max. radni tlak spr. PTV
Priključci PTV
Ogrj. površina spirale
Volumen ogrj. spirale
Toplinska izolacija
Visina A
Visina B
Visina C
Visina D
Visina E
(lit.)(mm)(mm)(mm)
(R)(bar)(°C)
(mm)(kg)(kg)(lit.)
(bar)(R)
2(m )(lit.)
(mm)(mm)(mm)(mm)(mm)(mm)
475650850
16706/4''
3100
18707584-----
100230610
-10001380
740790990
17506/4''
3100
195099112
-----
100320670
-10201370
940790990
21506/4''
3100
2350149164
-----
100320800
-12901770
21801200140021806/4''
3100
2435245265
-----
100335800
-12701735
475650850
16706/4''
3100
1870100109
---
1,910,5100230610630
10001380
940790990
21506/4''
3100
2350185201
---
3,217,5100320800970
12901770
740790990
17506/4''
3100
1950135150
---
2,614
100320670870
10201370
475650850
16706/4''
3100
1870120129125
63/4"1,9
10,5100230610630
10001380
740790990
17506/4''
3100
1950175190170
63/4"2,614
100320670870
10201370
940790990
21506/4''
3100
2350215230170
63/4"3,2
17,5100320800970
12901770
14501000120021006/4''
3100
2300185204
-----
100320785
-12551720
3001
2960125014502695
2"3
1002915321
-----
100370
1000-
16302260
4001
3820140016002790
2"3
1003015380
-----
100420
1050-
16802310
501
CAS-B
801 1001
940790990
21506/4''
3100
2350176191170
63/4"
--
100320800
-12901770
740790990
17506/4''
3100
1950137150170
63/4"
--
100320670
-10201370
475650850
16706/4''
3100
1870105114125
63/4"
--
100230610
-10001380
HR
27Tehničko uputstvo CentroMini 5Tehničko uputstvo CAS, CAS-B, CAS-S i CAS-BS
1.0. PREDSTAVLJANJE
Predstavljanje, namjena, stanje kod isporuke
Akumulacijski spremnici CAS, CAS-B, CAS-S i CAS-BS tvrtke Centrometal d.o.o. proizvedeni su najsuvremenijom tehnologijom zavarivanja od kvalitetnog čelika. Izrađuju se u 7 volumena (475, 740, 940, 1450, 2180, 2960 i 3820 litara) i 4 izvedbe: kao akumulacijski spremnik (CAS), sa ugrađenim inox bojlerom za pripremu potrošne tople vode (CAS-B), sa ugrađenim cijevnim izmjenjivačem za spajanje solarnih kolektora (CAS-S) te sa ugrađenim inox bojlerom i cijevnim izmjenjivačem (CAS-BS). Pridržavanjem tehničkih uputa, koja pojašnjavaju konstrukciju, način rada, priključivanje i održavanje akumulacijskog spremnika, zagarantiran Vam je nesmetan i ekonomičan rad proizvoda.
Akumulacijski spremnici CAS, CAS-B, CAS-S i CAS-BS namijenjeni su akumuliranju energije (npr. u sustavima centralnog grijanja uz kotlove na kruto gorivo radi akumuliranja toplinske energije) te osiguravaju ekonomičniji i efikasniji rad samog sustava u koji su ugrađeni. Više izvedbi ovih spremnika omogućuju istodobno korištenje više obnovljivih izvora energije, što ih čini ekološki i energetski vrlo prihvatljivim.
2.0. NAMJENA
3.0. STANJE KOD ISPORUKE
Akumulacijski spremnici CAS, CAS-B, CAS-S i CAS-BS se zbog lakšeg transporta i lakšeg postavljanja ne isporučuju s montiranom toplinskom izolacijom već zasebno:- tijelo akumulacijskog spremnika na drvenoj paleti- toplinska izolacija upakirana u zaštitnu PVC foliju- termometar (4 kom.), tuljac za termometar (4 kom.), rozete (crne) upakirano u PVC vrečicu
HR
6 Tehničko uputstvo CAS, CAS-B, CAS-S i CAS-BS
4.0. POSTAVLJANJE
Akumulacijski spremnici CAS, CAS-B, CAS-S i CAS-BS dolaze isporučeni na drvenoj paleti. Prije postavljanja akumulacijskog spremnika na predviđeno mjesto u kotlovnici potrebno ga je skinuti s drvene palete. Postavljanje i sastavljanje akumulacijskog spremnika te ugradnja dodatne opreme na spremnik mora biti izvedeno od strane stučne osobe. Akumulacijski spremnik je potrebno postaviti na horizontalnu čvrstu podlogu predviđenu za opterećenje koje uzrokuje masa punog spremnika. Kotlovnica mora biti sigurna od smrzavanja. Spremnik je potrebno postaviti tako da je njegovo spajanje moguće korektno izvesti, a da ujedno bude omogućeno nadziranje u toku rada. Za montažu toplinske izolacije na akumulacijski spremnik vidi ‘’Tehničko uputstvo za montažu toplinske izolacije akumulacijskog spremnika CAS; -S; -B; -BS’’ koje se isporučuje sa spremnikom (uz jamstveni list).
6.0. PRIKLJUČENJE AKUMULACIJSKOG SPREMNIKA NA INSTALACIJU
CENTRALNOG GRIJANJA
Priključenje spremnika na instalaciju centralnog grijanja izvesti prema preporukama i shemi proizvođača kotla (izvora topline), a u skladu sa ovim tehničkim uputama i pravilima struke.
5.0. NATPISNA PLOČICA S OSNOVNIM PODACIMA O PROIZVODU
Max. radni pretlak sprem. (bar):
Volumen spremnika (lit.):
Tvornički broj:
Godina proizvodnje:
Tip sprem.: CAS
2010.
d.o.o.40306 MACINEC, GLAVNA 12 - HRVATSKA
Proizvođač: Centrometal d.o.o.
AKUMULACIJSKI SPREMNIK
Volumen spremnika PTV (lit.):
Max. radni pretl. sp. PTV (bar):
Masa spremnika (kg):
Max. radni pretlak sprem. (bar):
Volumen spremnika (lit.):
Tvornički broj:
Godina proizvodnje:
Tip sprem.: CAS
2010.
d.o.o.40306 MACINEC, GLAVNA 12 - HRVATSKA
Proizvođač: Centrometal d.o.o.
AKUMULACIJSKI SPREMNIK
Volumen spremnika PTV (lit.):
Max. radni pretl. sp. PTV (bar):
Masa spremnika (kg):
Natpisna p loč ica akumulaci jskog spremnika nalazi se pričvršćena na njegovo postolje i prekrivena je toplinskom izolacijom. Kako bi se došlo do natpisne pločice potrebno je povući patentni zatvarač toplinske izolacije prema gore (otvoriti) cca. 50 cm te je razmaknuti (vidi sliku 2.).
Slika 2. Položaj natpisne pločice na akumulacijskom spremniku
cc
a.
50
cm
Postavljanje, natpisna pločica, priključenje na instalaciju grijanjaHR
Shema 1. Primjer ugradnje akumulacijskog spremnika CAS-BS na vodovodnu instalaciju
1 - Akumulacijski spremnik CAS-B/CAS-BS2 - Ekspanzijska posuda za sanitarnu vodu3 - Sigurnosni ventil s tlakom otvaranja 6 bar4 - Nepovratni ventil5 - Regulator tlaka6 - Zaporni ventil7 - Topla sanitarna voda8 - Cirkulacija9 - Hladna sanitarna voda10 - 3-putni termostatski mješajući ventil za sanitarnu vodu11 - Otvor za osjetnik12 - Priključak 6/4" (unutarnji navoj)
* potrebno je ugraditi ako je tlak ulazne vode veći od 4 bar-a
*
**
** preporuka
90°
9
7
10**
Ulaz hladne sanitarne vode
2
4 *5 6
1
8
11
12 11
7 9
8
12
3
27Tehničko uputstvo CentroMini 7Tehničko uputstvo CAS, CAS-B, CAS-S i CAS-BS
Priključenje na vodovodnu instalaciju
7.0. PRIKLJUČENJE AKUMULACIJSKOG SPREMNIKA CAS-B I CAS-BS
NA VODOVODNU INSTALACIJU
Priključenje inox bojlera u akumulacijskom spremniku CAS-B/CAS-BS na vodovodnu instalaciju mora se izvesti prema važećim tehničkim normama, od strane stručne osobe (Shema 1.). Dovod hladne sanitarne vode priključuje se na priključak (9) (Shema 1.) (kolčak 3/4''), a priključak (7) (Shema 1.) (kolčak 3/4'') služi za odvod tople sanitarne vode. Priključak cirkulacijskog voda (8) (kolčak 3/4'') nalazi se s desne strane priključka hladne vode.Na ulaz hladne sanitarne vode u bojler obavezna je ugradnja: - ekspanzijske posude za sanitarnu vodu; - sigurnosnog ventila sa tlakom otvaranja 6 bar-a; - redukcijskog ventila koji smanjuje tlak ulazne hladne sanitarne vode na 4 bar-a (ukoliko je njezin tlak veći); - nepovratnog ventila.
HR
Potrebno je provesti (prekontrolirati, ako su već izvedene) sve radnje u skladu sa točkama 1.0. do 7.0. ovih uputa.
Maksimalni radni tlak u spremniku spojenom na instalaciju centralnog grijanja mora biti ograničen ugrađenim sigurnosnim ventilom s tlakom otvaranja max. 3 bar-a.
8.0. PUŠTANJE U POGON
8.1. PUŠTANJE U POGON - CAS / -S 501, CAS / -S 801, CAS / -S 1001, CAS / -S 1501,
CAS / -S 2001, CAS - 3001, CAS - 4001
8.2. PUŠTANJE U POGON - CAS-B / -BS 501, CAS-B / -BS 801, CAS-B / -BS 1001,
CAS-B / -BS 1501, CAS-B / -BS 2001
Potrebno je provesti (prekontrolirati, ako su već izvedene) sve radnje u skladu sa točkama 1.0. do 7.0. ovih uputa.
Maksimalni radni tlak u spremniku spojenom na instalaciju centralnog grijanja mora biti ograničen ugrađenim sigurnosnim ventilom s tlakom otvaranja max. 3 bar-a.
Maksimalni radni tlak u inox bojleru za sanitarnu vodu spojenom na vodovodnu instalaciju mora biti ograničen ugrađenim sigurnosnim ventilom s tlakom otvaranja max. 6 bar-a.
Prije punjenja akumulacijskog spremnika izvedbe CAS-B i CAS-BS kotlovskom vodom (strana sustava grijanja), mora se napuniti inox bojler PTV (sanitarna voda) na tlak minimalno 1,5 bar-a.
8 Tehničko uputstvo CAS, CAS-B, CAS-S i CAS-BS
Akumulacijski spremnik CAS, CAS-B, CAS-S i CAS-BS čistiti prema potrebi pražnjenjem posude. Prije svakog punjenja akumulacijskog spremnika izvedbe CAS-B i CAS-BS kotlovskom vodom (strana sustava grijanja), mora se napuniti inox bojler PTV (sanitarna voda) na tlak minimalno 1,5 bar-a. Iznos minimalnog tlaka od 1,5 bar-a u inox bojleru PTV (sanitarna voda) održavati i tokom rada.
9.0. KORIŠTENJE, ČIŠĆENJE I ODRŽAVANJE
Puštanje u pogon, korištenje, čišćenje i održavanjeHR
27Tehničko uputstvo CentroMini 9Tehničko uputstvo CAS, CAS-B, CAS-S i CAS-BS
Karakteristike akumulacijskih spremnika
10.0. KARAKTERISTIKE AKUMULACIJSKIH SPREMNIKA CAS, CAS-B, CAS-S i CAS-BS
Izrađeni su iz atestiranog čeličnog lima u skladu s normom ISO 9001/2000.Dobra toplinska izolacija (100 mm) obložena oblogom od skaja.Moguće povezivanje više spremnika zajedno u svrhu povećanja ukupne akumulacije.Izrađuju se u 7 volumena i 4 izvedbe:- CAS 501 (475 litara), CAS 801 (740 litara), CAS 1001 (940 litara), CAS 1501 (1450 litara) i CAS 2001 (2160 litara), CAS 3001 (2960 litara) i CAS 4001 (3820 litara) - akumulacijski spremnik- CAS-S 501 (475 litara), CAS-S 801 (740 litara), CAS-S 1001 (940 litara) - akumul. spremnik sa cijevnim izmjenjivačem- CAS-B 501 (475 litara), CAS-B 801 (740 litara), CAS-B 1001 (940 litara) - akumul. spremnik sa inox bojlerom za san. vodu- CAS-BS 501 (475 litara), CAS-BS 801 (740 litara), CAS-BS 1001 (940 litara) - akumul. sprem. sa inox bojlerom i cijev. izmjenj.
HR
10 Technical manual CAS, CAS-B, CAS-S i CAS-BS
F
DC
B
A
E
Dimensions and the basic parts of the accumulation tank
Connection (female thread) *
Accumulation tank body
Connection (female thread) *
Tube for temp.sensor
Connection (female thread) *
Tube exchanger(female thread 5/4'')
Connection (female thread) *
Tube exchanger(female thread 5/4'')
Connection (female thread)*
Accumulation tank foundation
Tube exchanger(female thread 5/4'')
Thermal insulation
Thermometer
Thermometer
Thermometer
Thermometer
Tube for temp.sensor
Tube for temp.sensor
Tube for temp.sensor
CAS CAS-S
CAS CAS-S
90
°
90
°
G
H
Connection 1/2'' for thermometer
Connection (female thread)*
Connection (female thread)*
Tube exchanger(female thread 5/4'')
Connection (female thread)*
Tube for temp.sensor
* Connection 6/4'' (cas 501- 2001), 2" (CAS 3001- 4001) (female thread)
EN
11Technical manual CAS, CAS-B, CAS-S i CAS-BS
Dimensions and the basic parts of the accumulation tank
CAS-BSCAS-B
Thermometer
Thermal insulation
Accumulation tank body
Steinless steel DHW tank
Connection 6/4'' (female thread)
Connection 6/4'' (female thread)
Tube for temp.sensor
Connection 6/4''(female thread)
Tube exchanger(female thread 5/4'')
Connection 6/4''(female thread)
Tube exchanger(female thread 5/4'')
Connection 6/4''(female thread)
Accumulation tank foundation
Tube exchanger(female thread 5/4'')
Thermometer
Thermometer
Thermometer
Tube for temp.sensor
Tube for temp.sensor
Tube for temp.sensor
CAS-BS
90
°
90
°
CAS-B
Visual control opening cover DHW
Connection 1/2'' for thermometer
Opening for sensor Circulation(female thread 3/4'')
Connection 6/4'' (female thread)
Tube exchanger(female thread 5/4'')
Connection 6/4''(female thread)
Connection 6/4'' (female thread)Circulation(female thread 3/4'')
Visual controlopening cover DHW
Opening for sensor
Cold sanitary water(female thread 3/4'')
Hot sanitary water(female thread 3/4'')
Hot sanitary water(female thread 3/4'')
Cold sanitary water(female thread 3/4'')
Tube for temp.sensor
EN
12 Technical manual CAS, CAS-B, CAS-S i CAS-BS
Technical data
0,8 1,0 2,0 3,0 4,0
2
3
4
5
6
8
10
20
30
40
Pict. 1. Flow resistance of CAS
Flo
w r
es
ista
nc
e i
n m
ba
r
3Amount of flow in m /h
Tip1001 2001501 801
CAS
1001501 801
CAS-S
1001501 801
CAS-BS
1501
Volume
Tank body diameter G
Outer diameter H
Total height F
Connections
Max. operating press.
Max. operating temp.
Min. height of the room
Empty acc. body weight
Empty acc. tank weight
DHW tank capacity
Max. oper. press. DHW tank
DHW connections
Heat exchanger surface
Heat exchanger volume
Thermal insulation
Height A
Height B
Height C
Height D
Height E
(lit.)
(mm)
(mm)
(mm)
(R)
(bar)
(°C)
(mm)
(kg)
(kg)
(lit.)
(bar)
(R)2
(m )
(lit.)
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
475650850
16706/4''
3100
18707584-----
100230610
-10001380
740790990
17506/4''
3100
195099112
-----
100320670
-10201370
940790990
21506/4''
3100
2350149164
-----
100320800
-12901770
21801200140021806/4''
3100
2435245265
-----
100335800
-12701735
475650850
16706/4''
3100
1870100109
---
1,910,5100230610630
10001380
940790990
21506/4''
3100
2350185201
---
3,217,5100320800970
12901770
740790990
17506/4''
3100
1950135150
---
2,614
100320670870
10201370
475650850
16706/4''
3100
1870120129125
63/4"1,9
10,5100230610630
10001380
740790990
17506/4''
3100
1950175190170
63/4"2,614
100320670870
10201370
940790990
21506/4''
3100
2350215230170
63/4"3,2
17,5100320800970
12901770
14501000120021006/4''
3100
2300185204
-----
100320785
-12551720
3001
2960125014502695
2"3
1002915321
-----
100370
1000-
16302260
4001
3820140016002790
2"3
1003015380
-----
100420
1050-
16802310
501
CAS-B
801 1001
940790990
21506/4''
3100
2350176191170
63/4"
--
100320800
-12901770
740790990
17506/4''
3100
1950137150170
63/4"
--
100320670
-10201370
475650850
16706/4''
3100
1870105114125
63/4"
--
100230610
-10001380
EN
2713Technical manual CAS, CAS-B, CAS-S i CAS-BS
Presentation, use, status at delivery
1.0. PRESENTATION
Water accumulation tanks CAS, CAS-B, CAS,S and CAS-BS are manufactured with the most modern welding technology, made from high quality steel. They are made in seven different volumes (475, 740, 940, 1450, 2160, 2960 and 3820 litres) and four different versions: water accumulation tank (CAS), with inbuilt stainless steel domestic hot water (DHW) tank (CAS-B), with inbuilt tube heat exchanger for solar collector connection (CAS-S) and with inbuilt stainless steel DHW tank and tube heat exchanger (CAS-BS). We highly recommend You to follow our technical manual with attention which brighten the construction, operation, instalation and maintenance of the water accumulation tank in order to assure a long life and proper operation condition of the product.
2.0. USE
Accumulation tanks CAS, CAS-B, CAS-S and CAS-BS are intended for accumulation of energy (for example in the central heating systems with solid fuel boilers for accumulation of thermal energy) and provide more economical and efficient operation of the system in which they are installed. Lot of versions of the water accumulation enables simultaneously use of more renewable energy sources what makes them ecologically and energetic very acceptable.
3.0. STATUS AT DELIVERY
For easier transport and positioning into boiler room, accumulation tanks CAS, CAS-B, CAS-S i CAS-BS are not supplied with built-in thermal insulation but separately as follows:- accumulation tank body- thermal insulation packed in a protective PVC foil- thermometer (4 pcs.), rosette (4 pcs. red, 3 pcs. blue and 4 pcs. black) packed in PVC bag
EN
Connection of the accumulation tank to central heating system should be done by recommendation and schematic drawing from boiler (heat source) manufacturer, according to this technical manual and good technical practice.
14
Max. radni pretlak sprem. (bar):
Volumen spremnika (lit.):
Tvornički broj:
Godina proizvodnje:
Tip sprem.:
Proizvođač:
AKUMULACIJSKI SPREMNIK
Volumen spremnika PTV (lit.):
Max. radni pretl. sp. PTV (bar):
Masa spremnika (kg):
Max. radni pretlak sprem. (bar):
Volumen spremnika (lit.):
Tvornički broj:
Godina proizvodnje:
Tip sprem.: CAS
2010.
d.o.o.40306 MACINEC, GLAVNA 12 - HRVATSKA
Proizvođač: Centrometal d.o.o.
AKUMULACIJSKI SPREMNIK
Volumen spremnika PTV (lit.):
Max. radni pretl. sp. PTV (bar):
Masa spremnika (kg):
cc
a.
50
cm
Technical manual CAS, CAS-B, CAS-S i CAS-BS
Installation, plate, installation to heating system
4.0. INSTALATION
5.0. PLATE WITH BASIC INFORMATION ABOUT THE PRODUCT
Picture 2. Position of the plate on the accumulation tank
Plate of accumulation tank is attached to its foundation and covered with insulation. In order to reach the plate the zipper must pulled up (open) approx. 50 cm and separate thermal insulation (see Picture 2).
2010.
d.o.o.40306 MACINEC, GLAVNA 12 - CROATIA
Centrometal d.o.o.
WATER ACCUMULATORTANK
Weight of the tank (kg):
Volume of the DHW tank (lit.):
Max. operating pressure (bar):
Volume of the tank (lit.):
Product No.:
Year of production:
Type:
Manufacturer:
Max. operating pressure of the DHW tank (bar):
6.0. INSTALLATION OF THE ACCUMULATION TANK TO CENTRAL
HEATING SYSTEM
Accumulation tanks CAS, CAS-B, CAS-S and CAS-BS are delivered on a wooden pallet. Before placing the accumulation tank in the boiler room it needs to be removed from the wooden pallet. Installation and assembly of accumulation tank and installation of additional equipment on the tank must be performed by a qualified person. Accumulation tank need to be placed on a horizontal solid foundation for the anticipated load that causes the full weight of the accumulation tank. Boiler room must be protected from freezing. Accumulation tank has to be positioned so that it can be properly connected and simultaneously, enabling tending of accumulation tank control during operation. For mounting of thermal insulation on the accumulation tank see ''Technical instructions for installation of thermal insulation and jacket for accumulation tank CAS, S-,-B,-BS'' which are delivered with thermal insulation of the tank.
EN
1 - Accumulation tank CAS-B / CAS-BS2 - Expansion vessel for sanitary water3 - Safety valve with opening pressure 6 bar4 - Non-return valve5 - Pressure reducing valve6 - Stop valve7 - Hot sanitary water8 - Circulation9 - Cold sanitary water10 - Thermal 3-way mixing valve for sanitary water11 - Sensor tube12 - Connection 6/4'' (female thread)
*
**
90°
9
7
10**
2
4 *5 6
1
8
11
1211
7 9
8
123
27Tehničko uputstvo CentroMini 15Technical manual CAS, CAS-B, CAS-S i CAS-BS
Connection to water supply installation
7.0. CONNECTION OF THE ACCUMULATION TANK CAS-B AND CAS-BS
TO WATER SUPPLY INSTALLATION
Connection of stainless steel domestic hot water (DHW) tank positioned in the accumulation tank CAS-B / CAS-BS to water supply installation has to be done by an expert professional and all installation works have to be performed in accordance with available technical standards (Scheme 1.). Cold sanitary water supply line has to be connected to connection (9) (Scheme 1) (connection 3/4'') and the connection (7) (Schema 1) (connection 3/4'') is intended for disposal of hot sanitary water. Connection for circulation line (8) (connection 3/4'') is located on the right side of the cold water connection. The following has to be installed at the entry of supply line of cold sanitary water in DHW tank:
- expansion vessel for sanitary water;
- safety valve with opening pressure of 6 bar;- reducing valve which reduces cold sanitary water pressure to 4 bar (if its pressure is higher);- non-return valve.
Inlet coldsanitary water
Scheme 1. Example of installation accumulation tank CAS-BS to water supply system
* It should be built in if inlet water pressure is over 4 bars.
** recommendation
EN
16 Technical manual CAS, CAS-B, CAS-S i CAS-BS
8.0. START UP
It is necessary to perform (check, if you have already performed) all actions in accordance with points 1.0. to 7.0. these instructions.Max. working pressure in the accumulation tank connected to the installation of central heating must be limited with built in safety valve with max. openning pressure 3 bar.
9.0. USE, CLEANING AND MAINTENANCE
The water accumulation tank CAS, CAS-B, CAS-S and CAS-BS have to be cleaned as needed, by discharge the accumulation tank.Before filling the tank CAS-B and CAS-BS with boiler water (heating system side), you must fill sanitary water heater tank on pressure min. 1,5 bar. Min. pressure of 1,5 bar inside the sanitary water heater tank should be kept during the usual work.
8.1. START UP - CAS / -S 501, CAS / -S 801, CAS / -S 1001, CAS / -S 1501,
CAS / -S 2001, CAS - 3001, CAS - 4001
8.2. START UP - CAS / -S 501, CAS / -S 801, CAS / -S 1001, CAS / -S 1501,
CAS / -S 2001
It is necessary to perform (check, if you have already performed) all actions in accordance with points 1.0. to 7.0. these instructions.Max. working pressure in the accumulation tank connected to the installation of central heating must be limited with built in safety valve with max. openning pressure 3 bar.Max. working pressure in the stainless steel DHW water tank connected to water supply system must be limited with built in safety valve with max. openning pressure 6 bar.Before filling the tank CAS-B and CAS-BS with boiler water (heating system side), you must fill sanitary water heater tank DHW on pressure min. 1,5 bar.
Start up, use, cleaning and maintenanceEN
10.0. CHARACTERISTICS OF ACCUMULATION TANKS CAS, CAS-B, CAS-S i CAS-BS
They are manufactured from certificated metal sheet in compliance with the ISO 9001/2000 norm.They are very good thermal insulated (100 mm), the outer cover is made of artificial leather.It is possible to connect the tanks mutually in order to increase total accumulation of the system.They are produced in six different volumes and four version:- CAS 501 (475 lit.), CAS 801 (740 lit.), CAS 1001 (940 lit.), CAS 1501 (1450 lit.) and CAS 2001 (2160 lit.), CAS 3001 (2960 lit.) i CAS 4001 (3820 lit.) - water accumulation tank- CAS-S 501 (475 lit.), CAS-S 801 (740 lit.), CAS-S 1001 (940 lit.) - wat. acc. tank with inbuilt solar tube heat exchanger- CAS-B 501 (475 lit.), CAS-B 801 (740 lit.), CAS-B 1001 (940 lit.) - wat. acc. tank with inbuilt stainless steel DHW wat. tank- CAS-BS 501 (475 lit.), CAS-BS 801 (740 lit.), CAS-BS 1001 (940 lit.) - wat. acc. tank with inbuilt DHW wat. tank and heat exch.
Characteristic of accumulation tanks
27Tehničko uputstvo CentroMini 17Technical manual CAS, CAS-B, CAS-S i CAS-BS
EN
18 Tehnična navodila CAS, CAS-B, CAS-S i CAS-BS
Dimenzije in osnovni deli akumulacijskega rezervoarja
CAS CAS-S
Termometer
Termometer
Toplotnaizolacija
Prostor za temp.tipalo
Prostor za temp.tipalo
F
DC
B
A
Priključek (notranji navoj) *
Termometer
Termometer
Podnožje rezervoarja
Priključek (notranji navoj) *
Priključek (notranji navoj) *
Prostor za temp.tipalo
Mjesto za temp. osjetnik
Priključek (notranji navoj)*
E
Telo rezervoarja
Cevni izmenjevalnik(notranji navoj 5/4")
CAS CAS-S
90
°
90
°
G
H
Priključek (notranji navoj) *
Priključek (notranji navoj) *
Prostor za temp.tipalo
Cevni izmenjevalnik(notranji navoj 5/4")
Priključek (notranji navoj) *
Priključek 1/2" za termometer
Cevni izmenjevalnik(notranji navoj 5/4")
Cevni izmenjevalnik(notranji navoj 5/4")
Priključek (notranji navoj) *
* - Priključek 6/4" (CAS 501 - 2001), 2" (CAS 3001 - 4001) (notranji navoj)
SLO
19
Dimenzije in osnovni deli akumulacijskega rezervoarja
CAS-BS
90
°
90
°
Priključek 1/2" za termometer
Otvor za osjetnik
Cirkulacija (notranji navoj 3/4")
Topla sanitarna voda(notranji navoj 3/4")
Priključek 6/4’’(notranji navoj)
Hladna sanitarna voda(notranji navoj 3/4")
Cevni izmenjevalnik(notranji navoj 5/4")
Prostor za temp.tipalo
Hladna sanitarna voda(notranji navoj 3/4")
Topla sanitarna voda(notranji navoj 3/4")
Priključek 6/4’’(notranji navoj)
Priključek 6/4”(notranji navoj)
Cirkulacija(unutarnji navoj 3/4")
CAS-B
CAS-BSCAS-B
Termometar
Termometar
Termometar
Prostor za temperaturnotipalo
Prostor za temp.tipalo
Cijevniizmjenivač(unutarnji
navoj 5/4'')
Inox bojler PTV
Priključek 6/4” (notranji navoj)
Priključek 6/4’’(notranji navoj)
Toplinskaizolacija
Termometar
Priključek 6/4’’(not.nav.)
Priključek 6/4’’(notranji)
Prostor za temp.tipalo
Priključak 6/4’’(unut.nav.)
Prostor za temperaturnotipalo
Podnožje rezervoarja
Cevni izmenjevalnik(notranji navoj 5/4")
Cevni izmenjevalnik(notranji navoj 5/4")
Poklopec odprtineza reviziju PTV
Poklopec odprtine za reviziju PTV
Telo rezervoarja
Odprtina za tipalo
Tehnična navodila CAS, CAS-B, CAS-S i CAS-BS
SLO
20
Tehnički podatki
Tip1001 2001501 801
0,8 1,0 2,0 3,0 4,0
2
3
4
5
6
8
10
20
30
40
Slika 1. Otpor protoka CAS
Količina pretoka v m /h3
Up
or
pre
toka v
mb
ar
CAS
1001501 801
CAS-S
1001501 801
CAS-BS
1501
Prostornina
Premer telesa rezervoarja G
Zunanji premer H
Skupna višina F
Priključki
Max. delovni tlak
Max. delovna temp.
Min. višina prostora
Masa prazneg telesa rezerv.
Masa prazneg rezervoarja
Prostornina rezervoarja PTV
Max. delovni tlak PTV
Priključki PTV
Ogrevalna površina spirale
Prostornina ogrevalne spirale
Toplotna izolacija
Višina A
Višina B
Višina C
Višina D
Višina E
(lit.)(mm)(mm)(mm)
(R)(bar)(°C)
(mm)(kg)(kg)(lit.)
(bar)(R)
2(m )(lit.)
(mm)(mm)(mm)(mm)(mm)(mm)
3001 4001
Tehnična navodila CAS, CAS-B, CAS-S i CAS-BS
501
CAS-B
801 1001
475650850
16706/4''
3100
18707584-----
100230610
-10001380
740790990
17506/4''
3100
195099112
-----
100320670
-10201370
940790990
21506/4''
3100
2350149164
-----
100320800
-12901770
21801200140021806/4''
3100
2435245265
-----
100335800
-12701735
475650850
16706/4''
3100
1870100109
---
1,910,5100230610630
10001380
940790990
21506/4''
3100
2350185201
---
3,217,5100320800970
12901770
740790990
17506/4''
3100
1950135150
---
2,614
100320670870
10201370
475650850
16706/4''
3100
1870120129125
63/4"1,9
10,5100230610630
10001380
740790990
17506/4''
3100
1950175190170
63/4"2,614
100320670870
10201370
940790990
21506/4''
3100
2350215230170
63/4"3,2
17,5100320800970
12901770
14501000120021006/4''
3100
2300185204
-----
100320785
-12551720
2960125014502695
2"3
1002915321
-----
100370
1000-
16302260
3820140016002790
2"3
1003015380
-----
100420
1050-
16802310
940790990
21506/4''
3100
2350176191170
63/4"
--
100320800
-12901770
740790990
17506/4''
3100
1950137150170
63/4"
--
100320670
-10201370
475650850
16706/4''
3100
1870105114125
63/4"
--
100230610
-10001380
SLO
2721
1.0. PREDSTAVITEV
Predstavljanje, namen, stanje pri dobavi
Akumulacijski rezervoarji CAS, CAS-B, CAS-S i CAS-BS podjetja Centrometal d.o.o. so izdelani s pomočjo najsodobnejše tehnologije varjenja iz kvalitetnega jekla. Izdelujejo se v 7 prostorninah (475, 740, 940, 1450, 2160, 2960 in 3820 litrov) in v 4 izvedbah: kot akumulacijski rezervoar (CAS), z vgrajenim inox bojlerjem za pripravo tople sanitarne vode (CAS-B), z vgrajenim cevnim izmenjevalnikom za priključitev sončnih kolektorjev (CAS-S) in z vgrajenim inox bojlerjem ter cevnim izmenjevalnikom (CAS-BS). Če boste upoštevali tehnična navodila, ki pojasnjujejo konstrukcijo, način dela, priključitev in vzdrževanje akumulacijskega rezervoarja, vam je zagotovljeno nemoteno in ekonomično delovanje izdelka.
Akumulacijski rezervoarji CAS, CAS-B, CAS-S i CAS-BS so namenjeni akumuliranju energije (npr. v centralnih ogrevalnih sistemih poleg kotlov na trdo gorivo z namenom akumuliranja toplotne energije) ter zagotavljajo bolj ekonomično in učinkovito delovanje samega sistema, v katerega so vgrajeni. Več izvedb teh rezervoarjev omogočajo istočasno uporabo več obnovljivih virov energije, zaradi česar so ekološko in energijsko sprejemljivejši.
2.0. NAMEN
3.0. STANJE OB DOBAVI
Akumulacijski rezervoarji CAS, CAS-B, CAS-S i CAS-BS se zaradi lažjega transporta in lažjega postavljanja ne dobavljajo z montirano toplotno izolacijo, temveč posebej:- telo akumulacijskega rezervoarja na leseni paleti- toplotna izolacija zapakirane v zaščitno PVC folijo- termometer (4 kosi), tulec za termometer (4 kosi), rozete (črne) zapakirane v PVC vrečko
Tehnična navodila CAS, CAS-B, CAS-S i CAS-BS
SLO
22
4.0. POSTAVITEV
Akumulacijski rezervoarji CAS, CAS-B, CAS-S in CAS-BS se dobavljajo na leseni paleti. Pred postavljanjem akumulacijskega rezervoarja na predvideno mesto v kotlovnici ga morate sneti z lesene palete. Postavljanje in sestavljanje akumulacijskega rezervoarja in vgradnja dodatne opreme na rezervoar mora biti izpeljana s strani strokovne osebe. Akumulacijski rezervoar morate postaviti na horizontalno trdno površino, ki je predvidena za prenašanje obremenitev, ki jih povzroča masa polnega rezervoarja. Kotlovnica mora biti zaščitena pred zamrzovanjem. Rezervoar morate postaviti tako, da je njegovo priključitev možno izvesti korektno, vendar da je hkrati ob tem omogočen nadzor med delom. Za montažo toplotne izolacije na akumulacijski rezervoar glejte ''Tehnična navodila za montažo toplotne izolacije akumulacijskega rezervoarja CAS, -S; -B; -BS'', ki so priložena rezervoarju (priložen je tudi garancijski list).
6.0. PRIKLJUČITEV AKUMULACIJSKEGA REZERVOARJA NA
CENTRALNO OGREVALNO NAPELJAVO
Priključitev rezervoarja na centralno ogrevalno napeljavo morate izvesti po priporočilih in shemi proizvajalca kotla (toplotni vir) in hkrati v skladu s temi tehničnimi navodili in strokovnimi pravili.
5.0. NAPISNA PLOŠČICA Z OSNOVNIMI PODATKI O PROIZVODU
Max. radni pretlak sprem. (bar):
Volumen spremnika (lit.):
Tvornički broj:
Godina proizvodnje:
Tip sprem.: CAS
2010.
d.o.o.40306 MACINEC, GLAVNA 12 - HRVATSKA
Proizvođač: Centrometal d.o.o.
AKUMULACIJSKI SPREMNIK
Volumen spremnika PTV (lit.):
Max. radni pretl. sp. PTV (bar):
Masa spremnika (kg):
Max. radni pretlak sprem. (bar):
Volumen spremnika (lit.):
Tvornički broj:
Godina proizvodnje:
Tip sprem.: CAS
2010.
d.o.o.40306 MACINEC, GLAVNA 12 - HRVATSKA
Proizvođač: Centrometal d.o.o.
AKUMULACIJSKI SPREMNIK
Volumen spremnika PTV (lit.):
Max. radni pretl. sp. PTV (bar):
Masa spremnika (kg):
Napisna ploščica akumulacijskegarezervoarja je pritrjena na podnožju rezervoarja in prekrita s toplotno izolacijo. Če želite dostopati do napisne ploščice, morate patentno zapiralo toplotne izolacije povleči navzgor (odpreti) za cca. 50 cm in jo razmakniti (glejte sliko 2.).
Slika 2. Položaj napisne ploščice na akumulacijskem rezervoarju
cc
a.
50
cm
Postavitev, napisna ploščica, priključitev na instalacijo ogrevanja
Tehnična navodila CAS, CAS-B, CAS-S i CAS-BS
SLO
Shema 1. Primer vgradnje akumulacijskega rezervoarja CAS-BS na vodovodno napeljavo
1 - Akumulacijski rezervoar CAS-B/CAS-BS2 - Ekspanzijska posoda za sanitarno vodo3 - Varnostni ventil s tlakom odpiranja 6 barov4 - Nepovratni ventil5 - Regulator tlaka6 - Zaporni ventil7 - Topla sanitarna voda8 - Cirkulacija9 - Hladna sanitarna voda10 - 3-potni termostatski mešalni ventil za sanitarno vodo11 - Odprtina za tipalo12 - Priključek 6/4" (notranji navoj)
* potrebno je vgraditi, če je tlak vhodne vode večji od 4 bare
*
**
** priporočilo
90°
9
7
10**
Vhod za hladno sanitarno vodo
2
4 *5 6
1
8
11
12 11
7 9
8
12
3
2723
Priključitev na vodovodnu napeljavu
7.0. PRIKLJUČITEV AKUMULACIJSKEGA REZERVOARJA CAS- B IN
CAS- BS NA VODOVODNO NAPELJAVO
Priključitev inox bojlerja v akumulacijskem rezervoarju CAS-B/CAS-BS na vodovodno napeljavo mora v skladu z veljavnimi tehničnimi standardi izpeljatistrokovna oseba (Shema 1.). Dovod hladne sanitarne vode je potrebno priključiti na priključek 9 (Shema 1.) (objemka 3/4''), priključek 7 (Shema 1.) (objemka 3/4'') pa se uporablja za odvod tople sanitarne vode. Priključek cirkulacijskega voda 8 (objemka 3/4'') se nahaja na desni strani priključka za hladno vodo.Na vhod hladne sanitarne vode v bojler je obvezna vgradnja: - ekspanzijske posode za sanitarno vodo; - varnostnega ventila s tlakom odpiranja 6 barov; - redukcijskega ventila, ki znižuje tlak vhodne hladne sanitarne vode na 4 bare (če je njen tlak večji); - nepovratnega ventila.
Tehnična navodila CAS, CAS-B, CAS-S i CAS-BS
SLO
Potrebno je izpeljati (preveriti, če so že bila izpeljana) vsa dela v skladu s točkama od 1.0. do 7.0., ki sta navedeni v teh navodilih. Maksimalni delovni tlak v rezervoarju, priključenem na centralno ogrevalno napeljavo mora biti omejen z vgrajenim varnostnim ventilom s tlakom odpiranja maks. 3 bare.
8.0. ZAGON
8.1. ZAGON - CAS / -S 501, CAS / -S 801, CAS / -S 1001, CAS / -S 1501,
CAS / -S 2001, CAS - 3001, CAS - 4001
8.2. ZAGON - CAS-B / -BS 501, CAS-B / -BS 801, CAS-B / -BS 1001,
CAS-B / -BS 1501, CAS-B / -BS 2001
Potrebno je izpeljati (preveriti, če so že bila izpeljana) vsa dela v skladu s točkama od 1.0. do 7.0., ki sta navedeni v teh navodilih. Maksimalni delovni tlak v rezervoarju, priključenem na centralno ogrevalno napeljavo mora biti omejen z vgrajenim varnostnim ventilom s tlakom odpiranja maks. 3 bare.
Maksimalni delovni tlak v inox bojlerju za sanitarno vodo, priključenem na vodovodno napeljavo omejen z vgrajenim varnostnim ventilom s tlakom odpiranja
maks. 6 barov. Pred polnjenjem akumulacijskega rezervoarja izvedbe CAS-B i CAS-BS s kotlovno vodo (stran ogrevalnega sistema), se mora najprej napolniti inox bojler PTV (sanitarna voda) na tlak minimalno 1,5 bara.
24
Akumulacijski rezervoar CAS, CAS-B, CAS-S in CAS-BS je treba čistiti potrebi
tako, da izpraznite posodo. Vsakič preden napolnite akumulacijski rezervoar v izvedbah CAS-B in CAS-BS s kotlovno vodo (stran ogrevalnega sistema), morate napolniti najprej inox bojler PTV (sanitarna voda) s tlakom minimalno 1,5 barov. Minimalni tlak naj znaša 1,5 barov v inox bojlerju PTV (sanitarna voda) in ga ohranjujte med delovanjem.
9.0. UPORABA, ČIŠČENJE IN VZDRŽEVANJE
Zagon, uporaba, čiščenje in vzdrževanje
Tehnična navodila CAS, CAS-B, CAS-S i CAS-BS
SLO
2725
Karakteristike akumulacijskih rezervoarjev
10.0. KARAKTERISTIKE AKUMU. REZERVOARJEV CAS, CAS-B, CAS-S in CAS-BS
Izdelani so iz atestirane jeklene pločevine v skladu s standardom ISO 9001/2000.Dobra toplotna izolacija (100 mm) obložena z oblogo iz skaja.Možno je povezovanje več rezervoarjev skupaj z namenom povečanja skupne akumulacije.Izdelujejo se v 7 prostorninah in 4 izvedbah:- CAS 501 (475 litrov), CAS 801 (740 litrov), CAS 1001 (940 litrov), CAS 1501 (1450 litrov) in CAS 2001 (2160 litrov), CAS 3001 (2960 litrov) in CAS 4001 (3820 litrov) - akumulacijski rezervoar - CAS-S 501 (475 litrov), CAS-S 801 (740 litrov), CAS-S 1001 (940 litrov) - akumul. rezervoar s cevnim izmenjevalnikom- CAS-B 501 (475 litrov), CAS-B 801 (740 litrov), CAS-B 1001 (940 litrov) - akumul. rezervoar z inox bojlerjem za san. vodo- CAS-BS 501 (475 litrov), CAS-BS 801 (740 litrov), CAS-BS 1001 (940 litrov) - akumul. rezerv. z inox bojlerjem in cev . izmenj.
Tehnična navodila CAS, CAS-B, CAS-S i CAS-BS
SLO
HEATING TECHNIQUE
www.centrometal.hre-mail: [email protected]
Centrometal d.o.o. Glavna 12, 40306 Macinec, Croatia
central tel: +385 40 372 600, fax: +385 40 372 611service tel: +385 40 372 622, fax: +385 40 372 621
Centrometal d.o.o. shall not be responsible for possible incorrect data caused by printing errors or error made in transcription and all figures and diagrams are for explanatory purposes only and relevant adjustment have to be made at the spot. In any case, it reserves the right to modify its products as deemed to be required and useful without any prior notification.
Tvrtka Centrometal d.o.o. ne preuzima odgovornost za moguće netočnosti u ovoj brošuri, nastale tiskanim greškama ili prepisivanjem, u svakom slučaju pridržava si pravo unositi vlastitim proizvodima one izmjene koje smatra potrebnim i korisnim.
Podjetje Centrometal d.o.o. ne prevzema odgovornosti za možne napake v teh tehničnih navodilih, ki bi nastale zaradi tiskarskih napak pri prepisovanju ali prevajanju. Vse slike in sheme so približne in vsako je treba prilagoditi resničnemu stanju na terenu. V vsakem primeru si podjetje pridržuje pravico, da v svoje lastne proizvode vnese spremembe, za katere meni, da so potrebne.