A000 COVER SHEET & DESIGN CRITERIA A NEW TENANT BUILDOUT FOR: CARTER HEALTHCARE DRAWING INDEX CODE ANALYSIS AN 1,800 SQUARE FOOT INTERIOR MERCANTILE TENANT BUILD-OUT REMODELED TO AN OFFICE TENANT SPACE. SCOPE OF WORK ARCHITECTURAL A000 COVER SHEET, CODE ANALYSIS, GENERAL BUILDING INFORMATION A100 DEMOLITION PLAN, RENOVATION PLAN, LIFE SAFETY PLAN AND FINISH SCHEDULE A101 REFLECTED CEILING PLAN, DOOR SCHEDULE, WALL PARTITIONS, AND INTERIOR ELEVATIONS PLUMBING P001 PLUMBING - SCHEDULES, NOTES, AND DETAILS P101 PLUMBING FLOOR PLAN - WASTE/VENT AND WATER SUPPLY MECHANICAL M001 MECHANICAL - SCHEDULES, NOTES, AND DETAILS M101 MECHANICAL FLOOR PLAN - HVAC ELECTRICAL E001 ELECTRICAL - SCHEDULES AND DETAILS E002 ELECTRICAL - NOTES EPS101 ELECTRICAL FLOOR PLAN - POWER/SYSTEMS EL101 ELECTRICAL FLOOR PLAN - LIGHTING CONTROL JOINT HOSE BIB FLOOR DRAIN FD HB CJ ELECTRIC WATER COOLER EWC HC HANDICAPPED ROOF DRAIN RD STL. STRUCT. WWF STEEL STRUCTURAL WOVEN WIRE FABRIC NOT IN CONTRACT NIC NOT TO SCALE NTS VCT VINYL COMPOSITION TILE CARPET CPT CT CERAMIC TILE DF DRINKING FOUNTAIN EJ EXPANSION JOINT VENT THROUGH ROOF VTR SIM SIMILAR ALUMINUM ACOUSTIC ABOVE FINISH FLOOR CONTINUOUS ROOF LEADER/DOWNSPOUT DIAMETER FIRE EXTINGUISHER CEILING CLG. FE CONT. RL DIAM. COL. COLUMN ACOUS. A.F.F. ALUM. EXHAUST EXISTING EXTERIOR INSULATION MAXIMUM HOLLOW METAL GYPSUM BOARD EXT. MIN MAX JST. H.M. GYP. BD. INSUL. GA MINIMUM JOIST GAUGE EXH EXIST. EQ. EQUAL UNLESS NOTED OTHERWISE U.N.O. FEC FIRE EXTINGUISHER CABINET CONC. CONCRETE CMU CONCRETE MASONRY UNIT DBL. DOUBLE GALV. GALVANIZED FLR. FLOOR THRU THROUGH FIRE DEPT. CONNECTION FHA FIRE HYDRANT ASSEMBLY SYMBOLS 01 FD ABBREVIATIONS CODE ANALYSIS BUSINESS - B OCCUPANCY TYPE: CONSTRUCTION TYPE: CONSTRUCTION II-B (EXISTING / SPRINKLERED) INTERIOR WALL AND CEILING FINISH REQUIREMENTS FBC 803.9: GROUP B - BUSINESS - SPRINKLERED VERTICAL EXITS & PASSAGEWAYS EXIT CORRIDORS ROOMS AND ENCLOSED SPACES B C C APPROVED AUTOMATIC SPRINKLER SYSTEM IS PROVIDED THROUGHOUT THIS OCCUPANCY. FIRE PROTECTION SYSTEMS FBC 903: EXIT ACCESS TRAVEL DISTANCE FBC 1016.1: BUSINESS: MAXIMUM TRAVEL DISTANCE WITH A SPRINKLER SYSTEM SHALL BE 300'-0". MAXIMUM TRAVEL DISTANCE PROVIDED: 43'-8" CORRIDORS FBC 1018.1: BUSINESS: A FIRE RESISTANCE RATING IS NOT REQUIRED FOR CORRIDORS IN AN OCCUPANCY IN GROUP B WHICH IS SPRINKLERED MINIMUM NUMBER OF EXITS FBC 1021: OCCUPANT LOAD 1-500, MINIMUM # OF EXITS SHALL BE 2. NUMBER OF EXITS PROVIDED: 2 MINIMUM NUMBER OF PLUMBING FACILITIES (FROM TABLE P403.1) GROUP B - SPRINKLERED FLOOR AREA SF/OCCUPANT TOTAL OCCUPANT LOAD FLOOR AREA GROUP B - BUSINESS- SPRINKLERED STAIRWAYS OCCUPANT LOAD OTHER EGRESS COMPONENT EGRESS WIDTH FBC 1005.1: 0.3 PER OCCUPANT 18 PERSONS 0.2 PER OCCUPANT 5.4 REQUIRED 3.6 INCHES N/A PROVIDED 35 INCHES OCCUPANT LOAD FBC 1004: INTERIOR WALL AND CEILING FINISHES FLAME SPREAD AND SMOKE-DEVELOPED INDEXES AS PER ASTM E 84: CLASS A: FLAME SPREAD 0-25; SMOKE-DEVELOPED 0-450 CLASS B: FLAME SPREAD 26-75; SMOKE-DEVELOPED 0-450 CLASS C: FLAME SPREAD 76-200; SMOKE DEVELOPED 0-450 A FIRE ALARM AND DETECTION SYSTEM IS NOT REQUIRED FOR THIS PROJECT. FIRE ALARM AND DETECTION SYSTEMS FBC 907: 1 PROJECT LOCATION NOT TO SCALE N N (PLAN NORTH) P1 3 A201 3 A401 A A 1 1/A401 3 A501 3 A301 3 A102 DETAIL OR ENLARGED PLAN DETAIL ROOM NAME INTERIOR ELEVATION WALL SECTION BUILDING SECTION ELEVATION STRUCTURAL GRID CENTER LINE WINDOW TYPE TAG DOOR NUMBER TAG PARTITION TYPE TAG ROOM NAME ROOM NO. DETAIL OR SECTION NUMBER VIEW DIRECTION SHEET NUMBER DETAIL OR SECTION NUMBER SHEET NUMBER DETAIL OR SECTION NUMBER SHEET NUMBER ELEVATION NUMBER SHEET NUMBER DETAIL NUMBER SHEET NUMBER COLUMN GRID DESIGNATION GRID LINE DETAIL OR SECTION NUMBER SHEET NUMBER WINDOW NUMBER DOOR NUMBER WALL PARTITION NUMBER THIS PROJECT IS DESIGNED TO MEET THE REQUIREMENTS OF: 2014, 5th EDITION FLORIDA BUILDING CODE 2014, 5th EDITION FLORIDA PLUMBING CODE 2014, 5th EDITION FLORIDA MECHANICAL CODE 2014, 5th EDITION FLORIDA ENERGY CODE 2014, 5th EDITION FLORIDA EXISTING BUILDING CODE FLORIDA FIRE PREVENTION CODE 5th EDITION, 2012 ALL WORK SHALL CONFORM TO THESE CODES AND ALL OTHER APPLICABLE CODES, STANDARDS, AND ORDINANCES. WORK AREA COMPLIANCE METHOD ALTERATION LEVEL 3 XX/A401 DETAIL (MINOR) DETAIL NUMBER SHEET NUMBER REVISION TAG REVISION NUMBER THE VILLAGES, FLORIDA 32159 980 DEL MAR DRIVE B / FIRST FLOOR = 100 18 PERSONS 1,800 SF 18 PERSONS SCHEMATIC DESIGN/BUILD FIRE SPRINKLER SYSTEM MODIFICATIONS SHALL BE DESIGNED BY A LICENSED FIRE SPRINKLER CONTRACTOR. THE FIRE SPRINKLER CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL DOCUMENTATION TO THE AUTHORITIES HAVING JURISDICTION AS REQUIRED FOR PERMITTING. PLANS AND SPECIFICATIONS ISSUED BY FIRE PROTECTION CONTRACTOR SHALL BE SUBMITTED TO LANDLORD FOR WRITTEN APPROVAL. ALL WORK SHALL CONFORM TO LANDLORDS INSURANCE UNDERWRITERS AND CODE REQUIREMENTS AND ALL OTHER GOVERNING AUTHORITIES. PROVIDE ALL CONNECTIONS AND TURN-DOWN HEADS TO EXISTING FIRE PROTECTION SPRINKLER LINE, GRID AND UPRIGHT HEADS. SPRINKLER HEADS MUST BE CONCEALED OR SEMI-RECESSED MOUNTED HEADS. THE SPACING OF SPRINKLERS AND SIZES OF PIPES SHALL CONFORM TO THE REQUIREMENTS OF N.F.P.A. SYSTEM SHALL BE TESTED IN ACCORDANCE TO N.F.P.A. IN LOCATING SPRINKLERS AND PIPING, CONTRACTOR SHALL COORDINATE THE SPRINKLER LAYOUT WITH THE LIGHTING AND MECHANICAL DEVICE LAYOUT. PIPE SUPPORTS: HANGERS, CLAMPS, RODS AND OTHER ACCESSORIES OF AN APPROVED TYPE AND IN SUFFICIENT NUMBER TO PROPERLY SUPPORT ALL PIPING. REFER TO ARCHITECTURAL DOCUMENTS FOR LOCATIONS OF ALL SMOKE AND/OR FIRE WALLS MAINTAINING THE INTEGRITY OF THE SMOKE/FIRE WALLS WITH A TESTED ASSEMBLY FIRE SPRINKLER CONTRACTOR SHALL MAKE CONNECTION TO EXISTING FIRE MAIN BY PROVIDING AND INSTALLING VICTAULIC CONNECTIONS. G.C. TO NOTIFY TENANT COORDINATOR 48 HOURS IN ADVANCE OF WORK OR INSPECTIONS ON FIRE PROTECTION SYSTEM. FIRE SPRINKLER SYSTEM NOTE PROJECT LOCATION SERVICE SINKS F LAVS DRINKING FOUNTAINS 1:100 OCCUPANCY M BUSINESS 18 PERSONS WATER CLOSETS 1:25 1st 50 1:50 > 50 1 1 1 1 REQUIRED 1 1 HI/LO 2 2 PROVIDED 1 1:40 1st 80 1:80 > 80 REVISIONS ISSUE DATE JOB # SHEET TITLE SHEET NO. A NEW TENANT BUILDOUT FOR CARTER HEALTH SPANISH SPRINGS 980 DEL MAR DRIVE THE VILLAGES, FL 32159 05.27.2016 1636 936 E. FT. KING STREET OCALA, FLORIDA 34471 3 ) FL LIC# AA26001291 SPANISH SPRINGS

CARTER HEALTHCARE SPANISH SPRINGS - …€¦ · carter healthcare code analysis drawing index ... gwb1 - 5/8" gypsum board p1 - (2) coat interior latex paint finish gcb1 - gyp brd

  • Upload
    ngotu

  • View
    216

  • Download
    0

Embed Size (px)

Citation preview

A000

COVER SHEET&

DESIGN CRITERIA

A NEW TENANT BUILDOUT FOR:

CARTER HEALTHCARE

DRAWING INDEXCODE ANALYSIS

AN 1,800 SQUARE FOOT INTERIOR MERCANTILE TENANTBUILD-OUT REMODELED TO AN OFFICE TENANT SPACE.

SCOPE OF WORK

ARCHITECTURALA000 COVER SHEET, CODE ANALYSIS, GENERAL BUILDING INFORMATIONA100 DEMOLITION PLAN, RENOVATION PLAN, LIFE SAFETY PLAN AND FINISH SCHEDULEA101 REFLECTED CEILING PLAN, DOOR SCHEDULE, WALL PARTITIONS,

AND INTERIOR ELEVATIONS

PLUMBINGP001 PLUMBING - SCHEDULES, NOTES, AND DETAILS

P101 PLUMBING FLOOR PLAN - WASTE/VENT AND WATER SUPPLY

MECHANICALM001 MECHANICAL - SCHEDULES, NOTES, AND DETAILSM101 MECHANICAL FLOOR PLAN - HVAC

ELECTRICALE001 ELECTRICAL - SCHEDULES AND DETAILSE002 ELECTRICAL - NOTES

EPS101 ELECTRICAL FLOOR PLAN - POWER/SYSTEMSEL101 ELECTRICAL FLOOR PLAN - LIGHTING

CONTROL JOINT HOSE BIB

FLOOR DRAIN

FD

HBCJ

ELECTRIC WATER COOLEREWC

HC HANDICAPPED

ROOF DRAINRD

STL.

STRUCT.

WWF

STEEL

STRUCTURAL

WOVEN WIRE FABRIC

NOT IN CONTRACTNIC

NOT TO SCALENTS

VCT VINYL COMPOSITION TILE

CARPETCPT

CT CERAMIC TILE

DF

DRINKING FOUNTAIN

EJ EXPANSION JOINT

VENT THROUGH ROOFVTR

SIM SIMILAR

ALUMINUM

ACOUSTIC

ABOVE FINISH FLOOR

CONTINUOUS

ROOF LEADER/DOWNSPOUT

DIAMETER

FIRE EXTINGUISHER

CEILINGCLG.

FE

CONT.

RL

DIAM.

COL. COLUMN

ACOUS.

A.F.F.

ALUM.

EXHAUST

EXISTING

EXTERIOR

INSULATION

MAXIMUM

HOLLOW METAL

GYPSUM BOARD

EXT.

MIN

MAX

JST.

H.M.

GYP. BD.

INSUL.

GA

MINIMUM

JOIST

GAUGE

EXH

EXIST.

EQ. EQUAL

UNLESS NOTED OTHERWISEU.N.O.

FEC FIRE EXTINGUISHER CABINET

CONC. CONCRETE

CMU CONCRETE MASONRY UNIT

DBL. DOUBLE

GALV. GALVANIZED

FLR. FLOOR

THRU THROUGH

FIRE DEPT. CONNECTION

FHA FIRE HYDRANT ASSEMBLY

SYMBOLS

01

FD

ABBREVIATIONS CODE ANALYSIS

BUSINESS - B

OCCUPANCY TYPE:

CONSTRUCTION TYPE:

CONSTRUCTION II-B (EXISTING / SPRINKLERED)

INTERIOR WALL AND CEILING FINISH REQUIREMENTS FBC 803.9:

GROUP B - BUSINESS - SPRINKLERED

VERTICAL EXITS &PASSAGEWAYS

EXIT CORRIDORSROOMS AND

ENCLOSED SPACESB C C

APPROVED AUTOMATIC SPRINKLER SYSTEM IS PROVIDED THROUGHOUT THIS OCCUPANCY.

FIRE PROTECTION SYSTEMS FBC 903:

EXIT ACCESS TRAVEL DISTANCE FBC 1016.1:BUSINESS: MAXIMUM TRAVEL DISTANCE WITH A SPRINKLER SYSTEM SHALL BE 300'-0".MAXIMUM TRAVEL DISTANCE PROVIDED: 43'-8"

CORRIDORS FBC 1018.1:BUSINESS: A FIRE RESISTANCE RATING IS NOT REQUIRED FOR CORRIDORS IN ANOCCUPANCY IN GROUP B WHICH IS SPRINKLERED

MINIMUM NUMBER OF EXITS FBC 1021:OCCUPANT LOAD 1-500, MINIMUM # OF EXITS SHALL BE 2.NUMBER OF EXITS PROVIDED: 2

MINIMUM NUMBER OF PLUMBING FACILITIES(FROM TABLE P403.1)

GROUP B - SPRINKLERED

FLOOR AREA SF/OCCUPANT TOTAL OCCUPANT LOADFLOOR AREA

GROUP B - BUSINESS- SPRINKLERED

STAIRWAYSOCCUPANT LOADOTHER EGRESSCOMPONENT

EGRESS WIDTH FBC 1005.1:

0.3 PER OCCUPANT18 PERSONS 0.2 PER OCCUPANT

5.4REQUIRED 3.6 INCHES

N/APROVIDED 35 INCHES

OCCUPANT LOAD FBC 1004:

INTERIOR WALL AND CEILING FINISHES FLAME SPREAD ANDSMOKE-DEVELOPED INDEXES AS PER ASTM E 84:

CLASS A: FLAME SPREAD 0-25; SMOKE-DEVELOPED 0-450CLASS B: FLAME SPREAD 26-75; SMOKE-DEVELOPED 0-450CLASS C: FLAME SPREAD 76-200; SMOKE DEVELOPED 0-450

A FIRE ALARM AND DETECTION SYSTEM IS NOT REQUIRED FOR THIS PROJECT.

FIRE ALARM AND DETECTION SYSTEMS FBC 907:

1PROJECT LOCATIONNOT TO SCALE

N

N(PLAN NORTH)

P1

3

A201

3

A401

A

A

1

1/A401

3

A501

3

A301

3

A102

DETAIL ORENLARGEDPLAN

DETAIL

ROOMNAME

INTERIORELEVATION

WALLSECTION

BUILDINGSECTION

ELEVATION

STRUCTURALGRID

CENTER LINE

WINDOWTYPE TAG

DOORNUMBER TAG

PARTITIONTYPE TAG

ROOM NAME

ROOM NO.

DETAIL OR SECTIONNUMBER

VIEW DIRECTION

SHEET NUMBER

DETAIL OR SECTIONNUMBER

SHEET NUMBER

DETAIL OR SECTIONNUMBER

SHEET NUMBER

ELEVATION NUMBER

SHEET NUMBER

DETAIL NUMBER

SHEET NUMBER

COLUMN GRIDDESIGNATION

GRID LINE

DETAIL ORSECTIONNUMBER

SHEETNUMBER

WINDOW NUMBER

DOOR NUMBER

WALL PARTITIONNUMBER

THIS PROJECT IS DESIGNED TO MEET THE REQUIREMENTS OF:2014, 5th EDITION FLORIDA BUILDING CODE2014, 5th EDITION FLORIDA PLUMBING CODE2014, 5th EDITION FLORIDA MECHANICAL CODE2014, 5th EDITION FLORIDA ENERGY CODE2014, 5th EDITION FLORIDA EXISTING BUILDING CODEFLORIDA FIRE PREVENTION CODE 5th EDITION, 2012

ALL WORK SHALL CONFORM TO THESE CODES AND ALL OTHER APPLICABLE CODES,STANDARDS, AND ORDINANCES.

WORK AREA COMPLIANCE METHOD ALTERATION LEVEL 3

XX/A401DETAIL(MINOR)

DETAIL NUMBER

SHEET NUMBER

REVISION TAG REVISION NUMBER

THE VILLAGES, FLORIDA 32159

980 DEL MAR DRIVE

B / FIRST FLOOR = 100 18 PERSONS1,800 SF

18 PERSONS

SCHEMATIC DESIGN/BUILD FIRE SPRINKLER SYSTEM MODIFICATIONS SHALL BE DESIGNED BY A LICENSED FIRESPRINKLER CONTRACTOR. THE FIRE SPRINKLER CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALLDOCUMENTATION TO THE AUTHORITIES HAVING JURISDICTION AS REQUIRED FOR PERMITTING.

PLANS AND SPECIFICATIONS ISSUED BY FIRE PROTECTION CONTRACTOR SHALL BE SUBMITTED TO LANDLORD FORWRITTEN APPROVAL.

ALL WORK SHALL CONFORM TO LANDLORDS INSURANCE UNDERWRITERS AND CODE REQUIREMENTS AND ALL OTHERGOVERNING AUTHORITIES.

PROVIDE ALL CONNECTIONS AND TURN-DOWN HEADS TO EXISTING FIRE PROTECTION SPRINKLER LINE, GRID ANDUPRIGHT HEADS.

SPRINKLER HEADS MUST BE CONCEALED OR SEMI-RECESSED MOUNTED HEADS. THE SPACING OF SPRINKLERS ANDSIZES OF PIPES SHALL CONFORM TO THE REQUIREMENTS OF N.F.P.A. SYSTEM SHALL BE TESTED IN ACCORDANCE TON.F.P.A.

IN LOCATING SPRINKLERS AND PIPING, CONTRACTOR SHALL COORDINATE THE SPRINKLER LAYOUT WITH THELIGHTING AND MECHANICAL DEVICE LAYOUT.

PIPE SUPPORTS: HANGERS, CLAMPS, RODS AND OTHER ACCESSORIES OF AN APPROVED TYPE AND IN SUFFICIENTNUMBER TO PROPERLY SUPPORT ALL PIPING.

REFER TO ARCHITECTURAL DOCUMENTS FOR LOCATIONS OF ALL SMOKE AND/OR FIRE WALLS MAINTAINING THE

INTEGRITY OF THE SMOKE/FIRE WALLS WITH A TESTED ASSEMBLY

FIRE SPRINKLER CONTRACTOR SHALL MAKE CONNECTION TO EXISTING FIRE MAIN BY PROVIDING AND INSTALLINGVICTAULIC CONNECTIONS.

G.C. TO NOTIFY TENANT COORDINATOR 48 HOURS IN ADVANCE OF WORK OR INSPECTIONS ON FIRE PROTECTIONSYSTEM.

FIRE SPRINKLER SYSTEM NOTE

PROJECTLOCATION

SERVICESINKS

F LAVSDRINKINGFOUNTAINS

1:100

OCCUPANCY

MBUSINESS18 PERSONS

WATERCLOSETS

1:25 1st 501:50 > 50

1111REQUIRED

11 HI/LO22PROVIDED

11:40 1st 801:80 > 80

REVISIONS

ISSUE DATE

JOB #

SHEET TITLE

SHEET NO.

A N

EW T

ENA

NT

BU

ILD

OU

T FO

R

CA

RTE

R H

EALT

HSPA

NIS

H S

PRIN

GS

98

0 D

EL M

AR D

RIV

E

TH

E V

ILLA

GES

, FL

32

15

9

05.27.2016

1636

936 E. FT. KING STREETOCALA, FLORIDA 34471

P 352.629.3867 F 352.629.3866

FL LIC# AA26001291

SPANISH SPRINGS

100

WAITING/RECEPTION

P01

101

OFFICE102

OFFICE

103

WORK AREA

104

CONFERENCEROOM

108

BREAK AREA

105

IT

106

HCP RR

107

HCP RR

10'-4"

19'-4"

10'-4"

10'-4"

8'-0"

12'-3" 5'-0" 12'-3"

3'-0"

2'-0"

3'-0"

4'-7"

3'-0" 11'-6" 14'-10"

6'-7" 5'-0" 3'-0"

4'-6"

10'-0"

4'-6"

RECONFIGURECOMMODE ANDLAVATORY FOR ADACOMPLIANCE

NEW HCPDRINKINGFOUNTAINS

NEWMOPSINK

12'-8"5'-4"1'-0"MIN

D01

EXISTING 3070SF DOOR TOREMAIN AS IS

EXISTING 4050FG TO REMAIN

AS IS

EXISTING2-4050 FG TOREMAIN AS IS

EXISTING 3070HM DOOR TOREMAIN AS IS

EXISTING 3068SC DOOR TOREMAIN AS IS

EXISTING 3068SC DOOR TOREMAIN AS IS

D02

D03

D04

D05

4068 COW/ DRYWALL

RETRUNS

2A101

W1W1

TYPICAL

P01

TYPICAL

7'-7"

7'-4"

T-SHAPED SPACE PERADA 304.3.2 WITH KNEESPACE COMPLYING W/ADA 306

4'-6"5'-3"

D06

3'-4"

7'-4"

REF W/ICEMAKER

BACK WALLFINISHED W/PLYWOOD

FRAMELESSGLASS WALL

SYSTEM

FRAMELESSGLASS WALL

SYSTEM

DOOR DESIGNATION TAG -SEE DOOR SCHEDULE

XXXX

000

000WINDOW DESIGNATION TAG -SEE WINDOW SCHEDULE

ROOM NAME ANDDESIGNATION TAG

0

000INTERIOR / EXTERIORELEVATION TAG

ELEVATION NUMBER

SHEET NUMBER

WALL AND PARTITION TAG -SEE WALL TYPES THIS SHEET

ROOM NAME

ROOM NUMBER

FLOOR PLAN LEGEND

FE

EGRESS DISTANCE CALCULATIONSTARTING POINT

EGRESS PATH OF TRAVEL

FEC

EXISTING WALL MOUNTED2A10BC FIRE EXTINGUISHER

2A10BC FIRE EXTINGUISHER INSEMI-RECESSED CABINET

INTERNALLY ILLUMINATED LED EXITLIGHT WITH DIRECTIONAL ARROWAND BATTERY BACKUP

EMERGENCY LIGHT (2 LAMP) WITHBATTERY BACKUP

INTERNALLY ILLUMINATED LED

EMERGENCY EXIT LIGHT / EMERGENCYLIGHT COMBO WITH BATTERY BACKUP

SD SMOKE DETECTOR WITH FIXEDTEMPERATURE HEAT DETECTOR

EXISTING WALLS TO REMAIN

ITEM TO BE DEMOLISHED

NEW PARTITION

GENERAL FLOOR PLAN NOTES

1. ALL WORK SHALL SHALL MEET OR EXCEED THE FLORIDA BUILDINGCODE 5th EDITION (2014), FLORIDA FIRE PREVENTION CODE,NATIONAL ELECTRIC CODE, AMERICANS WITH DISABILITIES ACT, ANDALL CURRENT APPLICABLE LOCAL, STATE, AND FEDERAL CODES ANDORDINANCES.

2. ALL DIMENSIONS ARE TAKEN FROM FACE OF EXISTING GYPSUMBOARD, FACE OF EXISTING MASONRY OR FACE OF NEW METALSTUDS.

3. ALL STORAGE SHELVING, MERCHANDISE DISPLAY RACKS ANDEQUIPMENT, AND POINT OF SALE CABINETRY AND EQUIPMENTSHOWN ON FLOOR PLAN SHALL BE SIZED AND DESIGNED BY OTHERS.LOCATIONS AND SIZES DENOTED ON PLANS ARE PROPOSED FOR THEINTENT OF SPACE PLANNING AND ARCHITECTURAL DESIGN ONLYAND MUST BE VERIFIED.

4. EXISTING STOREFRONT DOOR AND WINDOW ASSEMBLIES TOREMAIN. GC TO CLEAN AND REPAIR TO 'LIKE-NEW' CONDITION ASREQUIRED.

5. ALL FURNITURE TO BE SUPPLIED BY OWNER.

CEILING REMARKS

CEI

LIN

G H

EIG

HT

ROOM FINISH SCHEDULE

BASEWALLS

WAITING/RECEPTION

ROOM FLOOR

DESCRIPTION

100

RO

OM

TA

G

SURFACE FINISH

GW

B1

- 5

/8

" G

YPSU

M B

OA

RD

P1

- (2

) C

OA

T IN

TERIO

R L

ATE

X P

AIN

T FI

NIS

H

GC

B1

- G

YP B

RD

WIT

H P

AIN

T FI

NIS

H

10'-0"

OFFICE101

OFFICE102

WPT1

- W

OO

D P

LAN

K T

ILE

GW

B2

- 5

/8

" M

OIS

TURE

RES

ISTA

NT

GW

B

CPT1

- C

ARPET

VB1

-

3"

VIN

YL

CO

VE

BA

SE

P2

- (2

) C

OA

T EP

OX

Y P

AIN

T FI

NIS

H

CPT1

WPT1

VB1

VB1

GWB1

GWB2 P2

GWB1 P1

WORK AREA103

VCT1 VB1

GWB1

GCB1

CONFERENCE ROOM104

IT CLOSET105

HCP RR106

HCP RR107

BREAK AREA108

VC

T1 -

VIN

YL

CO

MPO

SIT

E TI

LE

VCT1

VCT1

CPT1

CPT1

CPT1

TB1

-

TILE

BA

SE

TB1

VB1

VB1

VB1

VB1

VB1

GWB2

GWB1

GWB1

GWB1

GWB1

P2

P1

P1

P1

P1

P1

P1

GCB1

AC

T1 -

AC

OU

STI

CA

L C

EILI

NG

TIL

E

ACT1

ACT1

ACT1

ACT1

ACT1

ACT1

ACT1

10'-0"

10'-0"

10'-0"

10'-0"

10'-0"

10'-0"

10'-0"

10'-0"

W/ O

RA

NG

E PEE

L TE

XTU

RE

W/ O

RA

NG

E PEE

L TE

XTU

RE

VCT1

ROOM FINISH SPECIFICATIONSFLOOR FINISHES

6x24 WOOD PLANK TILE FLOORING

MANUFACTURER = TRINITY SURFACES

WPT1 =

STYLE = ENGLISH PINE

COLOR = TBD

LATEX INTERIOR PAINT (FIELD COLOR)

MANUFACTURER = KELLY-MOORE

COLOR/FINISH = SPANISH SAND #231 (EGGSHELL)

PAINT SPECIFICATIONP1 =

NOTE 1 = PROVIDE (2) FINISH COATS

NOTE 1 = STAGGER PLANKS IN ASHLAR PATTERN

EPOXY INTERIOR PAINT (FIELD COLOR, WET AREAS)P2 =

NOTE 1 = PROVIDE (2) FINISH COATS

12x12 VINYL COMPOSITION TILE

MANUFACTURER = ARMSTRONG FLOORING

STYLE = IMPERIAL TEXTURE - STANDARD EXCELON

VCT1 =

COLOR = 51836 SHELTER WHITE

24" x 24" CARPET TILE

MANUFACTURER = MANNINGTON

CPT1 =

STYLE = SUBTLETY COLLECTION

COLOR = DELICATE (13113)

3x24 WOOD PLANK TILE BASE

BASE TRIMTB1 = 3" RUBBER BASE

MANUFACTURER = ROPPE

STYLE = PINNACLE

COLOR = 193 BLACK BROWN

VB1 =

MANUFACTURER = TRINITY SURFACES

STYLE = ENGLISH PINE

COLOR = TBD

NOTE 1 = STAGGER PLANKS IN ASHLAR PATTERN

2x2 ACOUSTICAL CEILING TILE AND GRID

MANUFACTURER = ARMSTRONG

STYLE = CIRRUS, FINE TEXTURE, TEGULAR EDGE

CEILING FINISH

COLOR = #584 WHITE

ACT1 =

GRID = 15/16" WHITE

NOTE: ALL DOOR TRIM TO BE PAINTED

MANUFACTURER = KELLY-MOORE

COLOR/FINISH = SPANISH SAND #231 (SATIN)

COUNTERTOP LAMINATE

MANUFACTURER = WILSONART

COLOR/FINISH = WILLOW SPRINGS 4906-38

LAMINATE SPECIFICATIONCOUNTER= CABINET LAMINATECABINET=

NOTE 1 = FINEGRAIN FINISH WITH AEON

MANUFACTURER = WILSONART

COLOR/FINISH = NEPAL TEAK 7209K-78

NOTE 1 = FINE VELVET TEXTURE FINISH

PRIMARY EXIT: EXISTING3070 SF DOOR = 175

OCCUPANTS

MAXIMUM DISTANCETO EGRESS = 50'-0"

MAXIMUM DISTANCETO EGRESS = 47'-2"

SECONARY EXIT: EXISTING3070 HM DOOR = 175

OCCUPANTS

5'-0"

1'-0"MIN

EXISTING

EXISTINGEXISTINGFE

EXISTINGFE

5'-0"

01

0101

02

03

03

03

03

03

01

01

01

04

04

04

04

05

04

EXIS

TIN

G 1

HR T

ENA

NT

SEP

ARA

TIO

NW

ALL

TO

REM

AIN

AS IS

EXIS

TIN

G 1

HR T

ENA

NT

SEP

ARA

TIO

NW

ALL

TO

REM

AIN

AS IS

DEMOLITION PLAN NOTES

REMOVE EXISTING WALL ASSEMBLY, INCLUDING FRAMING, BRACING, SHEATHING, WALLBOARD, TRIM, AND CASEWORK AND ALL ASSOCIATED ELECTRICAL, TELECOMMUNICATION,

SECURITY, AUDIO/VISUAL, FIRE ALARM, AND HVAC EQUIPMENT AND FIXTURES.01

REMOVE EXISTING DOOR ASSEMBLY, INCLUDING DOOR SLAB, FRAME,AND ALL ASSOCIATED HARDWARE.

REMOVE EXISTING SLAT WALL SYSTEM.

REMOVE EXISTING PLUMBING FIXTURE, CAP OR RECONFIGUREPLUMBING FOR NEW LAYOUT.

02

03

04

REMOVE EXISTING TILE @ ENTRY.05

-REMOVE ALL EXISTING LAMINATE/VINYL FLOORING.-REMOVE ALL EXISTING ACOUSTICAL CEILING TILES.

-REMOVE ALL EXISTING LIGHTING AND HVAC GRILLES, COORD. W/ MEP DRAWINGS.

A100

FLOOR PLAN - DEMOLITION,FLOOR PLAN - RENOVATION,FLOOR PLAN - LIFE SAFETY,

ANDFINISH SCHEDULE

REVISIONS

ISSUE DATE

JOB #

SHEET TITLE

SHEET NO.

A N

EW T

ENA

NT

BU

ILD

OU

T FO

R

CA

RTE

R H

EALT

HSPA

NIS

H S

PRIN

GS

980 D

EL M

AR D

RIV

E

TH

E V

ILLA

GES

, FL

32159

05.27.2016

1636

936 E. FT. KING STREETOCALA, FLORIDA 34471

P 352.629.3867 F 352.629.3866FL LIC# AA26001291

2FLOOR PLAN - RENOVATION1/4" = 1'-0"

3FLOOR PLAN - LIFE SAFETY PLAN1/4" = 1'-0"

1FLOOR PLAN - DEMOLITION1/4" = 1'-0"

10-0

EXTG

EXTG

REFLECTED CEILING PLAN LEGEND

GYPSUM BOARD CEILING OR SOFFIT WITHINDICATED HEIGHT FROM FINISH FLOOR

SUSPENDED 2x2 ACOUSTICAL CEILINGTILE SET IN GRID SYSTEM (WITHINDICATED HEIGHT FORM FINISH FLOOR)

0-0

EMERGENCY LIGHT (2 LAMP) WITHBATTERY BACKUP

INTERNALLY ILLUMINATED LED EXIT LIGHT /EMERGENCY LIGHTING COMBINATION WITHDIRECTIONAL ARROW AND BATTERY BACKUP

0-0

REFLECTED CEILING PLAN NOTES-SEE ELECTRICAL AND MECHANICAL ENGINEERED DRAWINGS FOR ALLLIGHTING AND MECHANICAL LOCATIONS AND SPECIFICATIONS.

REMARKS

DOOR SCHEDULE

ELEVATIONTHKHEIGHT

DOOR

DOOR TYPEMARK

FRAME

WIDTHRATING

THSHLD

SIZE

MATERIAL GLAZING ELEVATIONMATERIALJAMBHEAD

DETAIL

RATINGLOCKSET

FINISHFINISH FACE

01 (OFFICE) PANELED SWING 3'-0" 6'-8" 1-3/4" D1 WOOD PAINT N/A HM 4-7/8" 2" F1

TYPE

KD PAINT H1 J1

THROAT /DEPTH

NAN/A L1

3'-0" 1-3/4" D1 WOOD PAINT N/A HM 4-7/8" 2" F1KD PAINT H1 J1 NAN/A L1

04 (IT) 1-3/4" D1 WOOD PAINT N/A HM 4-7/8" 2" F1KD PAINT H1 J1 NAN/A L3

N/A

N/A

N/A

SCHEDULE KEY

LOCKSET KEYL1 = OFFICEL2 = PRIVACYL3 = STOREROOM

HARDWARE KEYH1 = SURFACE MOUNTED DOOR CLOSERH2 = METAL FRAME DOOR SILENCERSH3 = MOP PLATEH4 = BATHROOM SIGN WITH BRAILLE LETTERING

HARDWARE

H1,H2

H2,H3

PANELED SWING

PANELED SWING

1. ALL DOOR HARDWARE TO BE COMMERCIAL GRADE AND COMPLY WITH ADA GUIDELINES AND ALL OTHERAPPLICABLE CODES.

2. ALL LATCH SETS ARE TO BE ADA COMPLIANT LEVER-TYPE.

3. VERIFY ALL DOOR HARDWARE STYLES AND FINISHES WITH OWNER BEFORE PURCHASE.

4. VERIFY ALL FRAME ROUGH OPENINGS WITH DOOR MANUFACTURER.

5. COORDINATE ALL DOOR AND FRAME INSTALLATION AND HARDWARE SPECIFICATIONS WITH SECURITYSYSTEM COMPONENT INSTALLATION REQUIREMENTS AND ENSURE ALL ELECTRICAL AND HARDWARE NEEDSARE ADDRESSED.

6. VERIFY ALL KEYING REQUIREMENTS WITH OWNER.

7. DOORSTOPS SHALL BE FURNISHED FOR ALL DOORS TO PREVENT DAMAGE TO DOORS OR HARDWAREFROM STRIKING ADJACENT WALLS OR FIXTURES. WALL BUMPERS ARE PREFERRED, BUT WHERE NOT PRACTICALFURNISH FLOOR STOPS. WHERE CONDITIONS PROHIBIT THE USE OF EITHER WALL OR FLOOR TYPE STOPS,FURNISH SURFACE MOUNTED OVERHEAD STOPS.

8. DOOR CLOSERS SHALL BE FURNISHED WITH PARALLEL ARM MOUNTED ON ALL DOORS OPENING INTOCORRIDORS OR OTHER PUBLIC SPACES AND SHALL BE MOUNTED TO PERMIT 180 DEGREES DOOR SWINGWHEREVER WALL CONDITIONS PERMIT. FURNISH WITH NON-HOLD OPEN ARMS UNLESS OTHERWISEINDICATED.

9. THE FOLLOWING SCHEDULE IS FURNISHED FOR WHATEVER ASSISTANCE IT MAY AFFORD THE CONTRACTOR;DO NOT CONSIDER IT AS ENTIRELY INCLUSIVE. SHOULD ANY PARTICULAR DOOR OR ITEM BE OMITTED IN ANYSCHEDULED HARDWARE GROUP, PROVIDE DOOR OR ITEM WITH HARDWARE SAME AS REQUIRED FOR SIMILARPURPOSES.

DOOR SCHEDULE GENERAL NOTES

02 (OFFICE) H1,H2

05 (JANITOR) 1-3/4" D1 WOOD PAINT N/A HM 4-7/8" 2" F1KD PAINT H1 J1 NAN/A L3N/A H2,H3PANELED SWING

(2) 3'-0" 1-3/4" D2 WOOD PAINT N/A HM 4-7/8" 2" F1KD PAINT H1 J1 NAN/A L1N/APANELED SWING03 (CONF) H1,H2

3'-0"

3'-0"

6'-8"

6'-8"

6'-8"

6'-8"

NOTE: ALL NEW DOORS TO MATCH EXISTING DOOR, MATERIAL, FINISH, PANEL STYLE, AND HEIGHT.

3'-0" 1-3/4" D1 WOOD PAINT N/A HM 4-7/8" 2" F1KD PAINT H1 J1 NAN/A L1N/APANELED SWING06 (CORRIDOR) H1,H26'-8"

180° SWING

SOLID CORE WOODPANELED (PAINTED)PANEL DESIGN TOMATCH EXISTING

D21/2" = 1'-0"

SOLID CORE WOOD (DOUBLE DOOR)

AS S

CH

EDU

LED

AS SCHEDULED

2" HOLLOW METAL KDFRAME

SOLID CORE WOODPANELED (PAINTED)PANEL DESIGN TOMATCH EXISTING

D11/2" = 1'-0"

SOLID CORE WOOD

AS S

CH

EDU

LED

AS SCHEDULED

2" HOLLOW METALKD FRAME

H11-1/2" = 1'-0"

DOOR HEAD DETAIL - HOLLOW METAL FRAME

METAL STUDS AT 16" O.C.

GYP. BD.

HOLLOW METAL FRAME

LIGHTGAUGE MTL. HEADER

SOUND ATTENUATTING BATTS

GYP. BD.

SCHEDULED DOOR

2 42x4 WOOD BUCK

1/2" 1/2"

J11-1/2" = 1'-0"

DOOR JAMB DETAIL - HOLLOW METAL FRAME

METAL STUDS AT 16" O.C.

STUD ANCHORS

GYP. BD.

1/2" 1/2"INTERSECTING WALL LINE

2"

SCHEDULED DOOR

HOLLOW METAL FRAME

LIGHTGAUGE MTL. JAMB

SOUND ATTENUATTING BATTS

GYP. BD.

2 4 2x4 WOOD BUCK

3" = 1'-0"

PARTITION WALL DETAIL

UNFACED, FULL DEPTH,FRICTION-FIT, FIBER-GLASSSOUND ATTENUATING BATTS;TYP.

METAL STUD TRACK

1/4" GROOVE

CONTINUOUS BEADACOUSTICAL SEALANT

(1) LAYER 5/8" GYP. BD. EA.SIDE

BRACE TO STRUCTUREAT 48" O.C.ALTERNATING

3-5/8"x 20 GA. GALV. MTL.STUDS AT 16" O.C.

FINISHED CEILING

METAL STUD TRACK

P01

2"

AS S

CH

EDU

LED

AS

SCHEDULED

2"

2"

OPEN

A101

H1

A101

J1

F11/2" = 1'-0"

HOLLOW METAL FRAME

6'-8"

MA

TCH

AD

JAC

ENT

DO

ORS

W11/2" = 1'-0"

INTERIOR FIXED GLASS WALL SYSTEM

CR LAURENCE (OR EQUAL)FRAMELESS GLASS WALL

OFFICE SYSTEM(COORDINATE DIVISIONS

W/ GLASS WALL MANUF.)

11'-11" (V.I.F. PRIOR TO ORDERING)

CEILING LINE

(T3)

FLOOR MTDHCP WC

(T5) TOWELDISPENSER

WALL MTDHCP LAV

(T4)

FINISH FLOOR

NOTE 1. WC FLUSH CONTROL TO BEAUTOMATIC OR HAND-OPERATED (HANDOPERATED TO BE LOCATED ON OPEN SIDEOF WATER CLOSET.

NOTE 2. GRAB BARS TO BE 1-1/2"O.D. SS.

NOTE 3. PROVIDE INSULATION TO ALLEXPOSED HOT WATER LINES.

1'-6"

2'-0"

1'-6"

2'-10"

24"x36"MIRROR

(T2)

1'-6"

2'-10"

3'-4"4'-0"

36" SS GRAB BAR (T1)

SCALE: 1/2" = 1'-0"

INTERIOR ELEVATIONTYPICAL RESTROOM

5'-0" CLEAR ADA COMPLIANT HI-LOWELECTRIC WATER COOLERS

3'-0"

MA

X

3'-6"

MA

X

1'-4"

1'-10"

3'-6"

MA

X

3'-0"

MA

X

6"

8"

FRONT VIEW SIDE VIEW

3'-10" CLEAR

SCALE: 1/2" = 1'-0"

INTERIOR ELEVATIONHI-LOW WATER COOLER

FINISH FLOOR

REF SPACE

2'-6"2'-3"

2'-10"

2'-2"

2'-0"

2'-3"3'-0"

12"D UPPER

2'-3"

2'-3"

12"D UPPER

BASE BASE BASE

FINISHEDEND PANEL

LAMINATEBACKSPLASH

LAMINATECOUNTERTOP WITHBULL NOSE EDGE

LAMINATE WALLCABINETS WITHADJUSTABLE SHELVING

2'-6"

2'-2"

2'-0"

6'-0"

1'-0"

12"D UPPER12"D UPPER

A101

REFLECTED CEILING PLAN,DOOR SCHEDULE,WALL PARTITIONS,

ANDINTERIOR ELEVATIONS

REVISIONS

ISSUE DATE

JOB #

SHEET TITLE

SHEET NO.

A N

EW T

ENA

NT

BU

ILD

OU

T FO

R

CA

RTE

R H

EALT

HSPA

NIS

H S

PRIN

GS

980 D

EL M

AR D

RIV

E

TH

E V

ILLA

GES

, FL

32159

05.27.2016

1636

936 E. FT. KING STREETOCALA, FLORIDA 34471

P 352.629.3867 F 352.629.3866FL LIC# AA26001291

1REFLECTED CEILING PLAN1/4" = 1'-0"

2BREAK AREA INTERIOR ELEVATION1/2" = 1'-0"

PLUMBING NOTES

PLUMBING INDEX

SHEET TITLESHEET NUMBER

PLUMBING SYMBOL LEGEND

SYMBOL DESCRIPTION

GENERAL:

SUBMITTALS:

COORDINATION OF WORK:

PRODUCTS:

TESTING AND STERLIZATION:

WARRANTY:

FIREWALL AND FLOOR PENETRATION DETAIL

P.001

PLUMBINGSCHEDULES,

NOTES, DETAILS

REVISIONS

ISSUE DATE

JOB #

SHEET TITLE

SHEET NO.

05.27.16

1636

A N

EW T

ENA

NT

BU

ILD

OU

T FO

R

THE

VIL

LAG

ES, FL

32

15

9

MPEMILLER PROFESSIONAL

ENGINEERING, LLC

P.O. BOX 4246OCALA, FLORIDA [email protected]

MILLER PROFESSIONAL

CERTIFICATE OF AUTH. #30872

98

0 D

EL M

AR D

RIV

E

CA

RTE

R H

EALT

H

PARTIN ARCHITECTURE

P A

936 E. FT. KING STREETOCALA, FLORIDA 34471

P 352.629.3867 F 352.629.3866

FL LIC# AA26001291

ENGINEERING, LLC

.

...

SPA

NIS

H S

PRIN

GS

AutoCAD SHX Text
PLUMBING - SCHEDULES, NOTES, DETAILS
AutoCAD SHX Text
P.001
AutoCAD SHX Text
BALL VALVE INSTALLED ON VERTICAL SUPPLY PIPE
AutoCAD SHX Text
X" VTR
AutoCAD SHX Text
VENT THRU ROOF
AutoCAD SHX Text
BALL VALVE
AutoCAD SHX Text
TEE - OUTLET DOWN
AutoCAD SHX Text
ELBOW - TURNED UP
AutoCAD SHX Text
TEE - OUTLET UP
AutoCAD SHX Text
COLD WATER PIPING
AutoCAD SHX Text
ELBOW - TURNED DOWN
AutoCAD SHX Text
HOT/TEMPERED WATER PIPING
AutoCAD SHX Text
X" S.
AutoCAD SHX Text
X" V.
AutoCAD SHX Text
SANITARY WASTE/SOIL PIPING
AutoCAD SHX Text
VENT PIPING
AutoCAD SHX Text
ABOVE GRADE WASTE/SOIL PIPE
AutoCAD SHX Text
BELOW GRADE WASTE/SOIL PIPE
AutoCAD SHX Text
PLUMBING FLOOR PLAN - WASTE/VENT
AutoCAD SHX Text
P.101
AutoCAD SHX Text
PLUMBING CONTRACTOR SHALL COMPLETELY FAMILIARIZE HIMSELF/HERSELF WITH ALL CONDITIONS
AutoCAD SHX Text
AFFECTING HIS/HER WORK INCLUDING VISIT TO THE SITE BEFORE PREPARING PROPOSAL. ALL
AutoCAD SHX Text
WORK IS TO BE PERFORMED IN ACCORDANCE WITH ALL APPLICABLE CODES AND STANDARDS
AutoCAD SHX Text
FROM ALL AUTHORITIES HAVING JURISDICTION OVER THE WORK. WHERE CONFLICT EXISTS
AutoCAD SHX Text
BETWEEN THE APPLICABLE CODES AND STANDARDS OR THE PLANS AND SPECIFICATIONS, THE
AutoCAD SHX Text
MOST STRINGENT AS DETERMINED BY THE ENGINEER SHALL APPLY. CONTRACTOR SHALL NOTIFY
AutoCAD SHX Text
ENGINEER OF CONFLICTING CONDITIONS AFFECTING HIS/HER WORK AND ADVISE ENGINEER FOR
AutoCAD SHX Text
CLARIFICATION. LOCAL CODES IN EFFECT FOR THIS PROJECT INCLUDE BUT ARE NOT LIMITED TO
AutoCAD SHX Text
THE FOLLOWING:
AutoCAD SHX Text
2014 FLORIDA BUILDING CODE
AutoCAD SHX Text
2014 FLORIDA BUILDING CODE - MECHANICAL
AutoCAD SHX Text
2014 FLORIDA BUILDNG CODE - PLUMBING
AutoCAD SHX Text
2014 FLORIDA BUILDING CODE - GAS
AutoCAD SHX Text
2011 NFPA 70 "NATIONAL ELECTRIC CODE"
AutoCAD SHX Text
SUBMISSION OF BID INDICATES CONTRACTOR'S ACKNOWLEDGEMENT THAT THEY ARE PROVIDING TO
AutoCAD SHX Text
THE OWNER A COMPLETE AND OPERATING SYSTEM. ANY CONTRACTOR UNCERTAINTIES OR
AutoCAD SHX Text
MISSING INFORMATION CONCERNS TO BE SUBMITTED IN WRITING PRIOR TO SUBMISSION OF BID
AutoCAD SHX Text
SO THAT ENGINEER MAY PROVIDE PROPER CLARIFICATION.
AutoCAD SHX Text
PROVIDE ADEQUATE NUMBER OF SKILLED WORKMEN WHO ARE THOROUGHLY TRAINED AND
AutoCAD SHX Text
EXPERIENCED IN THE NECESSARY CRAFTS AND WHO ARE COMPLETELY FAMILIAR WITH THE
AutoCAD SHX Text
SPECIFIED REQUIREMENTS AND THE METHODS NEEDED FOR PROPER PERFORMANCE OF THE
AutoCAD SHX Text
WORK.
AutoCAD SHX Text
CONTRACTOR TO PREPARE SUBMITTALS AND SHOP DRAWINGS FOR ALL PLUMBING WORK AS
AutoCAD SHX Text
REQUIRED BY THE CONSTRUCTION DOCUMENTS FOR ENGINEER'S REVIEW NOT MORE THAN 35
AutoCAD SHX Text
CALENDAR DAYS AFTER CONTRACTOR HAS RECEIVED THE OWNER'S NOTICE TO PROCEED.
AutoCAD SHX Text
CONTRACTOR TO PROVIDE STERILIZATION "CERTIFICATE OF PERFORMANCE" UPON COMPLETION OF
AutoCAD SHX Text
WATER LINE STERILIZATION.
AutoCAD SHX Text
CONTRACTOR TO PROVIDE SUFFICIENT DATA INDICATING THAT WRAPPING OF STEEL PIPING HAS
AutoCAD SHX Text
BEEN TESTED AND MEETS THE SPECIFIED REQUIREMENTS. INDICATE DATE OF INSPECTION,
AutoCAD SHX Text
VOLTAGES USED, AND NAME/ADDRESS OF THE INSPECTOR.
AutoCAD SHX Text
UPON COMPLETION OF WORK, CONTRACTOR TO PROVIDE TWO COPIES OF AN OPERATION AND
AutoCAD SHX Text
MAINTENANCE MANUAL. INCLUDE IN EACH MANUAL A COPY OF THE PROJECT RECORD
AutoCAD SHX Text
DOCUMENTS.
AutoCAD SHX Text
ENGINEER'S DRAWINGS AND CONSTRUCTION DOCUMENTS ARE DIAGRAMMATIC. CONTRACTOR OF
AutoCAD SHX Text
THIS WORK TO COORDINATE WITH ALL WORK OF CONTRACTORS OF ALL TRADES AND GENERAL
AutoCAD SHX Text
CONTRACTOR. CONTRACTORS TO FIELD MEASURE PRIOR TO FABRICATION OF ANY WORK.
AutoCAD SHX Text
CONTRACTOR OF WORK OF THIS TRADE TO COMMUNICATE WITH GENERAL CONTRACTOR AND
AutoCAD SHX Text
CONTRACTORS OF OTHER TRADES AND PREPARE DRAWINGS, SKETCHES, AND PROVIDE
AutoCAD SHX Text
INFORMATION AS NEEDED TO COMMUNICATE WITH OTHER TRADES FOR CONSTRUCTION OF
AutoCAD SHX Text
COMPLETE AND OPERATING SYSTEM WITHOUT ADDITIONAL COST TO OWNER. PRIOR TO BEGINNING
AutoCAD SHX Text
WORK OF THIS TRADE, CONTRACTOR OF THIS TRADE TO CONDUCT COORDINATION MEETING WITH
AutoCAD SHX Text
OTHER AFFECTED CONTRACTORS OF OTHER TRADES AND GENERAL CONTRACTOR FOR PURPOSES
AutoCAD SHX Text
OF COORDINATION. CONTRACTOR'S FAILURES TO COORDINATE WILL NOT BE CAUSE FOR
AutoCAD SHX Text
RECOVERY OF ADDITIONAL COMPENSATION FOR CORRECTION OR MODIFICATION WORK WHICH IN
AutoCAD SHX Text
THE SOLE OPINION OF THE ENGINEER IS NOT WELL COORDINATED.
AutoCAD SHX Text
LAYOUT THE PLUMBING SYSTEM IN CAREFUL COORDINATION WITH THE DRAWINGS, DETERMINING
AutoCAD SHX Text
PROPER ELEVATIONS FOR ALL COMPONENTS OF THE SYSTEM USING ONLY THE MINIMUM NUMBER
AutoCAD SHX Text
OF BENDS TO PRODUCE A SATISFACTORILY FUNCTIONING SYSTEM. FOLLOW THE GENERAL LAYOUT
AutoCAD SHX Text
SHOWN ON THE DRAWINGS IN ALL CASES EXCEPT WHERE OTHER WORK MAY INTERFERE.
AutoCAD SHX Text
ALL MATERIALS TO BE OF DOMESTIC MANUFACTURER UNLESS OTHERWISE DIRECTED.
AutoCAD SHX Text
PIPE:
AutoCAD SHX Text
DRAIN, WASTE, AND VENT SYSTEM:
AutoCAD SHX Text
BELOW THE FLOOR AND OUTSIDE UNDERGROUND PIPING AND FITTINGS TO BE SCHEDULE 40 PVC.
AutoCAD SHX Text
ABOVE GROUND PIPING AND FITTINGS TO BE SCHEDULE 40 PVC.
AutoCAD SHX Text
WATER SYSTEM (DOMESTIC HOT/COLD):
AutoCAD SHX Text
ABOVE GROUND PIPING TO BE TYPE 'L' COPPER WITH SILVER SOLDER SWEATED CONNECTIONS
AutoCAD SHX Text
BELOW GROUND PIPING TO BE TYPE 'K' COPPER WITH SILVER SOLDER SWEATED CONNECTIONS.
AutoCAD SHX Text
PIPING FROM WATER SOURCE TO THE MAIN VALVE AND GREATER THAN 5' FROM THE BUILDING
AutoCAD SHX Text
ENVELOPE MAY BE SCHEDULE 40 PVC.
AutoCAD SHX Text
PROVIDE THRUST BLOCKS AND TRACING WIRE IN A MANNER CONSISTENT WITH MANUFACTURER'S
AutoCAD SHX Text
RECOMMENDATIONS.
AutoCAD SHX Text
ALL COPPER PIPING INSTALLED IN CONCRETE OR UNDERGROUND TO BE INSTALLED IN SEAMLESS
AutoCAD SHX Text
POLYETHYLENE SLEEVE.
AutoCAD SHX Text
FIXTURE TRIM AND ESCUTCHEONS:
AutoCAD SHX Text
ALL FIXTURE TRIM TO BE CHROME PLATED UNLESS ALTERNATE FINISH IS SPECIFIED.
AutoCAD SHX Text
WHERE PIPING PENETRATES THROUGH WALLS, FLOORS, OR SLABS, INSTALL CAST BRASS
AutoCAD SHX Text
ESCUTCHONS. SECURE TIGHT TO WALL WITH SET SCREW.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
LAYOUT PIPES TO FALL WITHIN PARTITION WALL, ROOF OR CEILING CAVITIES, AND TO NOT
AutoCAD SHX Text
REQUIRE FURRING OTHER THAN AS SHOWN ON THE DRAWINGS.
AutoCAD SHX Text
ALL WATER SUPPLY PIPING WITHIN THE BUILDING TO BE ROUTED OVERHEAD CONCEALED BY
AutoCAD SHX Text
CEILING CONSTRUCTION EXCEPT FOR DROPS TO PLUMBING FIXTURES. NO PIPING IS PERMITTED
AutoCAD SHX Text
TO BE ROUTED EXPOSED UNLESS OTHERWISE PERMITTED BY THE DRAWINGS.
AutoCAD SHX Text
TRENCHING AND BACKFILLING TO BE PERFORMED IN STRICT ACCORDANCE WITH THESE NOTES.
AutoCAD SHX Text
CUT BOTTOM OF TRENCHES TO GRADE. MAKE TRENCHES 12" WIDER THAN THE GREATEST
AutoCAD SHX Text
DIMENSION OF THE PIPE. INSTALL PIPING PROMPTLY AFTER TRENCHING. KEEP TRENCHES OPEN
AutoCAD SHX Text
AS SHORT A TIME AS PRACTICAL. FOR TRENCHES UNDER THE BUILDING, INSTALL PIPES ON A
AutoCAD SHX Text
6" BED OF DAMP SAND. BACK FILL TO BOTTOM OF SLAB WITH DAMP SAND. FOR TRENCHES
AutoCAD SHX Text
OUTSIDE THE BUILDING, INSTALL UNDERGROUND PIPING ON A 6" BED OF DAMP SAND. BACKFILL
AutoCAD SHX Text
TO WITHIN 12" OF FINISH GRADE WITH DAMP SAND. BACKFILL REMAINDER WITH NATIVE SOIL.
AutoCAD SHX Text
DO NOT BACKFILL UNTIL INSTALLATION HAS BEEN APPROVED AND UNTIL PROJECT RECORD
AutoCAD SHX Text
DOCUMENTS HAVE BEEN PROPERLY ANNOTATED.
AutoCAD SHX Text
THOROUGHLY CLEAN ITEMS BEFORE INSTALLATION. CAP PIPE OPENINGS TO EXCLUDE DIRT UNTIL
AutoCAD SHX Text
FIXTURES ARE INSTALLED AS FINAL CONNECTIONS HAVE BEEN MADE.
AutoCAD SHX Text
CUT PIPE ACCURATELY, AND WORK INTO PLACE WITHOUT SPRINGING OR FORCING, PROPERLY
AutoCAD SHX Text
CLEARING WINDOWS, DOORS, AND OTHER OPENINGS. EXCESSIVE CUTTING OR OTHER WAKENING
AutoCAD SHX Text
OF THE BUILDING WILL NOT BE PERMITTED.
AutoCAD SHX Text
SHOW NO TOOL MARKS OR THREADS ON EXPOSED PLATED, POLISHED, OR ENAMELED
AutoCAD SHX Text
CONNECTIONS FROM FIXTURES. TAPE ALL FINISHED SURFACES TO PREVENT DAMAGE DURING
AutoCAD SHX Text
CONSTRUCTION.
AutoCAD SHX Text
MAKE CHANGES IN DIRECTIONS WITH FITTINGS. MAKE CHANGES IN MAIN SIZES WITH ECCENTRIC
AutoCAD SHX Text
REDUCING FITTINGS. UNLESS OTHERWISE NOTED, INSTALL WATER SUPPLY AND RETURN PIPING
AutoCAD SHX Text
WITH STRAIGHT SIDE OF ECCENTRIC FITTINGS AT TOP OF THE PIPE.
AutoCAD SHX Text
ROUTE HORIZONTAL SANITARY AND STORM DRAINAGE PIPING AT A UNIFORM GRADE OF 0.25" PER
AutoCAD SHX Text
FOOT, UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
ROUTE HORIZONTAL WATER SUPPLY PIPING WITH AN ADEQUATE PITCH UPWARDS IN DIRECTION OF
AutoCAD SHX Text
FLOW TO ALLOW COMPLETE DRAINAGE.
AutoCAD SHX Text
SECURELY BOLT ALL EQUIPMENT, ISOLATORS, HANGERS AND SIMILAR ITEMS IN PLACE.
AutoCAD SHX Text
SUPPORT EACH ITEM INDEPENDENTLY FROM OTHER PIPES. DO NOT USE WIRE FOR HANGING OR
AutoCAD SHX Text
STRAPPING PIPES.
AutoCAD SHX Text
PROVIDE COMPLETE DIELECTRIC ISOLATION BETWEEN FERROUS AND NON-FERROUS METALS.
AutoCAD SHX Text
PROVIDE UNION AND SHUT OFF VALVES SUITABLY LOCATED TO FACILITATE MAINTENANCE AND
AutoCAD SHX Text
REMOVAL OF EQUIPMENT AND APPARATUS.
AutoCAD SHX Text
INSTALL PIPING, EQUIPMENT, AND ACCESSORIES TO PERMIT ACCESS FOR MAINTENANCE.
AutoCAD SHX Text
RELOCATE ITEMS AS NECESSARY TO PROVIDE SUCH ACCESS, AND WITHOUT ADDITIONAL COST TO
AutoCAD SHX Text
THE OWNER.
AutoCAD SHX Text
FOR COPPER TUBING PIPE JOINTS, CUT SQUARE, REMOVE BURRS, AND CLEAN INSIDE OF FEMALE
AutoCAD SHX Text
FILLING TO BRIGHT FINISH. APPLY SOLDER FLUX WITH BRUSH TO TUBING. REMOVE INTERNAL
AutoCAD SHX Text
PARTS OF SOLDER-END VALVES PRIOR TO SOLDERING. PROVIDE DIELECTRIC UNIONS AT POINTS
AutoCAD SHX Text
OF CONNECTION OF COPPER TUBING TO FERROUS PIPING AND EQUIPMENT. FOR JOINING
AutoCAD SHX Text
COPPER TUBING, USE 95-5 SOLDER FOR WATER PIPING 3" AND SMALLER, USE "SIL-FOS"
AutoCAD SHX Text
BRAZING FOR WATER PIPING LARGER THAN 3" AND ALL PIPING LOCATED UNDERGROUND.
AutoCAD SHX Text
FOR SCREWED PIPE JOINTS, DEBURR CUTS. DO NOT REAM EXCEEDING INTERNAL DIAMETER OF
AutoCAD SHX Text
THE PIPE. THREAD TO REQUIREMENTS OF ANSI B2.1. USE TEFLON TAPE ON MALE THREAD
AutoCAD SHX Text
PRIOR TO JOINING OTHER SERVICES. USE LITHARGE AND GLYCERIN ON JOINT PRIOR TO
AutoCAD SHX Text
CLEANING FOR AIR AND OIL PIPING.
AutoCAD SHX Text
FOR PVC PIPE JOINTS, THOROUGHLY CLEAN AND DEBURR CUTS. FITTINGS TO PVC JOINTS ARE
AutoCAD SHX Text
TO BE IN ACCORDANCE WITH ASTM D2855, PRIMED THEN SOLVENT WELDED WITH ASTM D2564
AutoCAD SHX Text
SOLVENT CEMENT.
AutoCAD SHX Text
FOR LEAKY JOINTS, REMAKE WITH NEW MATERIAL. REMOVE LEAKING SECTION AND/OR FITTING
AutoCAD SHX Text
AS DIRECTED. DO NOT USE THREAD CEMENT OR SEALANT TO TIGHTEN JOINT.
AutoCAD SHX Text
ALL EXISTING PIPING INSTALLED THROUGH TENANTS SPACE TO BE PROVIDED WITH UL FIRE RATED
AutoCAD SHX Text
ASSEMBLY AS REQUIRED BY AUTHORITY HAVING JURISDICTION (AHJ).
AutoCAD SHX Text
INSULATION:
AutoCAD SHX Text
GENERAL:
AutoCAD SHX Text
INSULATE WATER SYSTEM (DOMESTIC HOT/COLD) AS LISTED BELOW AND TO VALUES NOT LESS
AutoCAD SHX Text
THAN THOSE REQUIRED BY THE MOST CURRENT EDITION OF THE FLORIDA ENERGY EFFICIENCY
AutoCAD SHX Text
CODE FOR BUILDING CONSTRUCTION.
AutoCAD SHX Text
SEE "HANDICAPPED INSULATION" SECTION BELOW FOR ADDITIONAL REQUIREMENTS.
AutoCAD SHX Text
INSULATION TO BE CLOSED CELL ELASTOMERIC FOAM WITH THERMAL CONDUCTIVITY OF NOT MORE
AutoCAD SHX Text
THAN 0.28 BTU*IN/HR*FT*FT*°F AT 75°F MEAN TEMPERATURE, AP ARMAFLEX AS MANUFACTURED
AutoCAD SHX Text
BY ARMSTRONG OR EQUAL.
AutoCAD SHX Text
INSTALL 0.010 INCH EMBOSSED ALUMINUM JACKET LAGGING OVER ALL INSULATED PIPING WHERE
AutoCAD SHX Text
EXPOSED TO THE WEATHER. INCLUDE PREFABRICATED JACKETING AT ALL FITTINGS. UV COATED
AutoCAD SHX Text
PAINTING NOT PERMITTED UNLESS SPECIFICALLY NOTED.
AutoCAD SHX Text
COLD WATER:
AutoCAD SHX Text
FOR FIXTURE TURNOUTS, 3/8" THICK INSULATION MINIMUM
AutoCAD SHX Text
FOR PIPING 2" AND LESS, 3/8" THICK INSULATION MINIMUM
AutoCAD SHX Text
FOR PIPING 2.5" AND GREATER, 1/2" THICK INSULATION MINIMUM
AutoCAD SHX Text
HOT WATER:
AutoCAD SHX Text
FOR FIXTURE TURNOUTS, 1/2" THICK INSULATION MINIMUM
AutoCAD SHX Text
FOR PIPING 2" AND LESS, 1" THICK INSULATION MINIMUM
AutoCAD SHX Text
FOR PIPING 2.5" AND GREATER, 1.5" THICK INSULATION MINIMUM
AutoCAD SHX Text
PIPE WRAPPING:
AutoCAD SHX Text
FOR STEEL PIPING IN CONCRETE OR UNDERGROUND, WRAP AND PROVIDE 50%%% OVERLAP ON
AutoCAD SHX Text
TAPE WELD RUBBER COATING.
AutoCAD SHX Text
SECURE INSPECTION AND TESTING BY AN INDEPENDENT AGENCY APPROVED IN ADVANCE,
AutoCAD SHX Text
DEMONSTRATE PROTECTION BY PASSING 600V HOLIDAY TEST AFTER WRAPPING.
AutoCAD SHX Text
SLEEVES:
AutoCAD SHX Text
WHERE PIPES PASS THROUGH CONCRETE, MASONRY, OR STUD WALLS, OR PASS THROUGH
AutoCAD SHX Text
CEILINGS, PROVIDE RUST-PROOF SLEEVE OF THE SIZE REQUIRED.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
SET PIPE SLEEVES IN PLACE BEFORE CONCRETE IS PLACED.
AutoCAD SHX Text
FOR UNINSULATED PIPE, PROVIDE SLEEVES TWO PIPE SIZES LARGER THAN THE PIPE PASSING
AutoCAD SHX Text
THROUGH, OR PROVIDE A MINIMUM OF 0.5" CLEARANCE BETWEEN INSIDE AND OUTSIDE OF THE
AutoCAD SHX Text
PIPE.
AutoCAD SHX Text
FOR INSULATED PIPE, PROVIDE SLEEVES OF ADEQUATE SIZE TO ACCOMMODATE THE FULL
AutoCAD SHX Text
THICKNESS OF PIPE COVERING, WITH CLEARANCE FOR PACKING AND CAULKING.
AutoCAD SHX Text
CAULK THE SPACE BETWEEN SLEEVE AND PIPE OR PIPE COVERING, USING A NON-COMBUSTIBLE,
AutoCAD SHX Text
PERMANENTLY PLASTIC, WATERPROOF, NON-STAINING COMPOUND WHICH LEAVES A SMOOTH
AutoCAD SHX Text
FINISHED APPEARANCE, OR PACK WITH NONCOMBUSTIBLE ROPE, OR FIBERGLASS TO WITHIN 1/2"
AutoCAD SHX Text
OF BOTH WALL FACES, AND PROVIDE THE WATERPROOF COMPOUNT DESCRIBED ABOVE.
AutoCAD SHX Text
FOR FINISH AND ESCUTCHEONS, SMOOTH UP ROUGH EDGES AROUND SLEEVES WITH PLASTER OR
AutoCAD SHX Text
SPACKLING COMPOUND. PROVIDE 1" WIDE CHROME OR NICKEL PLATED ESCUTCHEONS ON ALL
AutoCAD SHX Text
PIPES EXPOSED TO VIEW WHERE PASSING THROUGH WALL, FLOORS, PARTITIONS, CEILING, AND
AutoCAD SHX Text
SIMILAR LOCATIONS. SIZE THE ESCUTCHEONS TO FIT PIPE AND A COVERING. HOLD
AutoCAD SHX Text
ESCUTCHEONS IN PLACE WITH SET SCREW.
AutoCAD SHX Text
VALVES:
AutoCAD SHX Text
CHECK VALVES:
AutoCAD SHX Text
FOR PIPING 3" AND SMALLER, BRONZE, SCREWED, Y-PATTERN, #200 WOG, SWING CHECK TYPE
AutoCAD SHX Text
PRESSURE REGULATORS:
AutoCAD SHX Text
ALL BRONZE WITH BRASS STRAINER UPSTREAM OF REGULATOR
AutoCAD SHX Text
PARTITION STOP VALVES:
AutoCAD SHX Text
ALL BRONZE, LOOSE KEY TYPE
AutoCAD SHX Text
ALL FIXTURES TO BE FURNISHED WITH CHROMED BRONZE STOP.
AutoCAD SHX Text
ALL VALVES LARGER THAN 3" TO BE FLANGED.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
PROVIDE VALVES IN WATER SUPPLY PIPING SYSTEMS.
AutoCAD SHX Text
IN ADDITION TO THE LOCATIONS SHOWN ON THE FLOOR PLANS, INSTALL VALVES IN LOCATIONS
AutoCAD SHX Text
THAT PERMIT FLUSHING AND STERILIZATION OF THE SYSTEM AS WELL AS PERMIT FOR EASY
AutoCAD SHX Text
ACCESSIBILITY AND MAINTENANCE.
AutoCAD SHX Text
HANGERS:
AutoCAD SHX Text
DRAIN WASTE AND VENT SYSTEM:
AutoCAD SHX Text
ADJUSTABLE RING HANGERS WITH SUPPORTING RODS AND ISOLATORS.
AutoCAD SHX Text
INSTALL RISER CLAMPS AT EACH FLOOR AND AS REQUIRED.
AutoCAD SHX Text
WATER SYSTEM (DOMESTIC HOT/COLD):
AutoCAD SHX Text
SPLIT RING HANGERS WITH SUPPORTING RODS AND ISOLATORS.
AutoCAD SHX Text
INSTALL RISER CLAMPS AT EACH FLOOR AND AS REQUIRED.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
SPACE HANGERS AND SUPPORT FOR HORIZONTAL COPPER TUBING ACCORDING TO THE
AutoCAD SHX Text
FOLLOWING SCHEDULE:
AutoCAD SHX Text
PIPE SIZE
AutoCAD SHX Text
1" AND SMALLER
AutoCAD SHX Text
1-1/4" TO 1-1/2"
AutoCAD SHX Text
2" AND LARGER
AutoCAD SHX Text
SPACE HANGERS AND SUPPORT FOR HORIZONTAL PVC PIPING ACCORDING TO THE FOLLOWING
AutoCAD SHX Text
SCHEDULE:
AutoCAD SHX Text
PIPE SIZE
AutoCAD SHX Text
1" AND SMALLER:
AutoCAD SHX Text
1-1/2" TO 3"
AutoCAD SHX Text
PROVIDE SUPPORT WITHIN 12" OF EACH HORIZONTAL ELBOW.
AutoCAD SHX Text
PROVIDE SWAY BRACING ON ALL HANGERS LONGER THAN 18" IN LENGTH.
AutoCAD SHX Text
SUPPORT VERTICAL PIPING WITH RISER CLAMPS SECURED TO THE PIPING AND RESTING ON THE
AutoCAD SHX Text
BUILDING STRUCTURE. PROVIDE AT EACH FLOOR UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
PROVIDE INSULATION CONTINUOUS THROUGH HANGERS AND ROLLERS. PROTECT INSULATION BY
AutoCAD SHX Text
GALVANIZED STEEL SHIELDS OF SUFFICIENT AREA TO PREVENT MORE THAN 10%%% REDUCTION IN
AutoCAD SHX Text
THICKNESS OF INSULATION.
AutoCAD SHX Text
ARRANGE PIPE SUPPORTS TO PREVENT EXCESSIVE DEFLECTION, AND TO AVOID EXCESSIVE
AutoCAD SHX Text
BENDING STRESS.
AutoCAD SHX Text
SUPPORT PIPING FROM INSERTS OR ANCHORS IN CONCRETE SLABS. PROVIDE THE INSERTS AND
AutoCAD SHX Text
ARRANGE FOR THE PLACING WITH OTHER TRADES.
AutoCAD SHX Text
FOR HUBLESS PIPING, PROVIDE HANGERS ON THE PIPING AT EACH SIDE OF, AND WITHIN 6" OF,
AutoCAD SHX Text
HUBLESS PIPE COUPLING SO THE COUPLING WILL BEAR NO WEIGHT. DO NOT PROVIDE HANGERS
AutoCAD SHX Text
ON COUPLINGS. PROVIDE HANGERS ADEQUATE TO MAINTAIN ALIGNMENT AND TO PREVENT
AutoCAD SHX Text
SAGGING OF THE PIPING, MAKING ADEQUATE PROVISION TO PREVENT SHEARING AND TWISTING OF
AutoCAD SHX Text
THE PIPE AND THE JOINT.
AutoCAD SHX Text
CLEANOUTS:
AutoCAD SHX Text
FLOORS:
AutoCAD SHX Text
PROVIDE AS SCHEDULED ON THE DRAWINGS.
AutoCAD SHX Text
IN FINISHED ROOM FLOORS, PROVIDE ROUND NICKEL-BRONZE TOP.
AutoCAD SHX Text
IN UNFINISHED ROOM FLOORS, PROVIDE ROUND CAST IRON TOP.
AutoCAD SHX Text
IN FLOORS WITH WATERPROOFING MEMBRANE, PROVIDE "FLUSH WITH FLOOR" WITH ADJUSTABLE
AutoCAD SHX Text
WATERTIGHT COVERS AND INTEGRAL ANCHORING FLANGE WITH CLAMPING COVER.
AutoCAD SHX Text
FINISHED WALLS:
AutoCAD SHX Text
PROVIDE AS SCHEDULED ON THE DRAWINGS WITH ROUND CHROME PLATED OR STAINLESS STEEL
AutoCAD SHX Text
ACCESS PLATE AND SCREW.
AutoCAD SHX Text
PROVIDE CLEANOUT PLUGS OF EXTRA HEAVY BRONZE.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
SECURE THE ARCHITECT OR ENGINEER'S APPROVAL OF LOCATIONS FOR CLEANOUTS IN FINISHED
AutoCAD SHX Text
AREAS PRIOR TO INSTALLATION.
AutoCAD SHX Text
PROVIDE CLEANOUTS OF SAME NOMINAL SIZE AS THE PIPES THEY SERVE EXCEPT WHERE
AutoCAD SHX Text
CLEANOUTS ARE REQUIRED IN PIPES 4" AND LARGER, PROVIDE 4" CLEANOUTS.
AutoCAD SHX Text
ALL CLEANOUTS TO BE ACCESSIBLE. AFTER PRESSURE TESTS ARE MADE AND APPROVED,
AutoCAD SHX Text
THOROUGHLY GRAPHITE THE CLEANOUT THREADS.
AutoCAD SHX Text
TRAPS:
AutoCAD SHX Text
ALL TRAPS TO BE CAST BRASS WITH BRASS NUTS AND CHROMED FINISH.
AutoCAD SHX Text
WATER HAMMER ARRESTORS:
AutoCAD SHX Text
PROVIDE STAINLESS STEEL TYPE AS SCHEDULED ON THE DRAWINGS FOR HOT WATER AND COLD
AutoCAD SHX Text
WATER SUPPLY LINES.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
INSTALL ARRESTORS IN UPRIGHT POSITION AT ALL QUICK CLOSING VALVES, SOLENOIDS, ISOLATED
AutoCAD SHX Text
PLUMBING FIXTURES, AND SUPPLY HEADERS AT PLUMBING FIXTURE GROUPS.
AutoCAD SHX Text
IN ADDITION TO LOCATIONS SHOWN ON PLANS, PROVIDE WATER HAMMER ARRESTORS IN
AutoCAD SHX Text
ACCORDANCE WITH PLUMBING AND DRAINAGE INSTITUTE STANDARD WH-201.
AutoCAD SHX Text
INSTALL WATER HAMMER ARRESTORS BEHIND ACCESS PANELS WHERE THEY ARE NOT ACCESSIBLE
AutoCAD SHX Text
BY REMOVABLE CEILING TILES.
AutoCAD SHX Text
WHERE FIXTURES ARE NOT PROTECTED BY WATER HAMMER ARRESTOR, PROVIDE 24" HIGH AIR
AutoCAD SHX Text
CHAMBERS ON EACH WATER SUPPLY, PROPERLY DESIGNED AND SIZED FOR MAINTENANCE AND
AutoCAD SHX Text
DRAINAGE.
AutoCAD SHX Text
BACKFLOW PREVENTERS:
AutoCAD SHX Text
IN FINISHED SPACES, PROVIDE CHROMIUM PLATED FINISH.
AutoCAD SHX Text
FOR FLUSH VALVES, PROVIDE DIAPHRAGM TYPE WITH APPROVED VACUUM BREAKER.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
INSTALL BACKFLOW PREVENTER OR VACUUM BREAKER AT ALL PLUMBING FIXTURES, FAUCETS WITH
AutoCAD SHX Text
HOSE CONNECTIONS, AND ON FIXTURES AS NECESSARY TO PREVENT POSSIBLE BACK-SIPHONAGE,
AutoCAD SHX Text
INCLUDING BUT NOT LIMITED TO HOSE BIBS, SERVICE SINKS, AND AS OTHERWISE INDICATED ON
AutoCAD SHX Text
THE DRAWINGS.
AutoCAD SHX Text
ARRANGE FOR TESTING OF BACKFLOW DEVICES AS REQUIRED BY THE GOVERNMENTAL AGENCIES
AutoCAD SHX Text
HAVING JURISDICTION.
AutoCAD SHX Text
HANDICAPPED INSULATION:
AutoCAD SHX Text
PROVIDE WHERE SHOWN ON THE DRAWINGS AND/OR AS REQUIRED BY GOVERNMENTAL AGENCIES
AutoCAD SHX Text
HAVING JURISDICTION, AT LAVATORIES FOR HANDICAPPED PERSONS PIPE PROTECTION AS
AutoCAD SHX Text
REQUIRED BY CODE, OR AS OTHERWISE INDICATED ON THE DRAWINGS.
AutoCAD SHX Text
PROVIDE TRAP WRAP ON ALL EXPOSED PIPING UNDER LAVATORIES AT LOCATIONS WHERE PIPING
AutoCAD SHX Text
IS EXPOSED.
AutoCAD SHX Text
FIXTURES AND EQUIPMENT:
AutoCAD SHX Text
GENERAL:
AutoCAD SHX Text
PROVIDE FIXTURES AS SCHEDULED ON THE DRAWINGS.
AutoCAD SHX Text
FIXTURES TO MEET OR EXCEED THE REQUIREMENTS OF CSA, ICC/ANSI, OBC, AND ALL OTHER
AutoCAD SHX Text
APPLICABLE STANDARDS/CODES.
AutoCAD SHX Text
WATER CLOSETS:
AutoCAD SHX Text
PROVIDE FIXTURE AND VALVE AS INDICATED ON THE DRAWINGS.
AutoCAD SHX Text
LAVATORY:
AutoCAD SHX Text
PROVIDE FIXTURE AND FAUCET AS INDICATED ON THE DRAWINGS. UNLESS OTHERWISE NOTED,
AutoCAD SHX Text
FURNISH FIXTURE WITH AERATOR, P-TRAP, AND STOPS.
AutoCAD SHX Text
WATER HEATING SYSTEM:
AutoCAD SHX Text
PROVIDE COMPLETE SYSTEM IN A MANNER CONSISTENT WITH THE DRAWINGS, INCLUDING BUT NOT
AutoCAD SHX Text
LIMITED TO WATER HEATER, PUMPS, CONTROLS, AND SUPPLEMENTARY ACCESSORIES
AutoCAD SHX Text
RECOMMENDED BY THE MANUFACTURER.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
FIXTURES TO BE LEVEL AND IN PROPER ALIGNMENT WITH RESPECT TO WALLS, FLOORS, AND
AutoCAD SHX Text
WITH FIXTURES EQUALLY SPACED.
AutoCAD SHX Text
FIXTURE WATER SUPPLIES TO BE IN ALIGNMENT WITH EACH OTHER AND THE FIXTURE. PIPING
AutoCAD SHX Text
TO BE INSTALLED LEVEL AND IN PROPER ALIGNMENT WITH RESPECT TO WALLS AND FLOORS AND
AutoCAD SHX Text
WITHOUT VERTICAL OR HORIZONTAL OFFSETS.
AutoCAD SHX Text
GROUT WALL AND FLOOR MOUNTED FIXTURES WATERTIGHT WHERE THE FIXTURES ARE IN CONTACT
AutoCAD SHX Text
WITH WALLS AND FLOORS.
AutoCAD SHX Text
CAULK DECK-MOUNTED TRIM AT THE TIME OF ASSEMBLY, INCLUDING FIXTURE AND CASEWORK
AutoCAD SHX Text
MOUNTED. CAULK SELF-RIMMING SINKS INSTALLED IN CASEWORK.
AutoCAD SHX Text
ALL COLD AND HOT WATER SUPPLY PIPING TO BE TESTED TO NOT LESS THAN 125 PSI
AutoCAD SHX Text
HYDROSTATIC PRESSURE AND HELD FOR NOT LESS THAN 48 HOURS. PROVIDE CHART RECORD
AutoCAD SHX Text
DURING TEST PERIOD FROM CALIBRATED AND SEALED RECORDING METER. ADVISE ENGINEER 48
AutoCAD SHX Text
HOURS PRIOR TO START OF TESTING.
AutoCAD SHX Text
DISINFECT ALL WATER SUPPLY PIPING BY METHOD APPROVED BY ENGINEER. SECURE AND SUBMIT
AutoCAD SHX Text
STERILIZATION CERTIFICATE OF PERFORMANCE STATING SYSTEM CAPACITY, DISINFECTANT APPLIED,
AutoCAD SHX Text
AND RESULTANT RESIDUALS IN PPM AT COMPLETION. AFTER FINAL FLUSHING, SECURE
AutoCAD SHX Text
INDEPENDENT ANALYSIS BY STATE LICENSED LABORATORY OF WATER SAMPLES FROM THE SYSTEM
AutoCAD SHX Text
SHOWING SUITABILITY OF POTABLE WATER SUPPLY, INCLUDING NEGATIVE TEST FOR
AutoCAD SHX Text
COLI-AEROGENE ORGANISMS. PROVIDE A TOTAL PLATE COUNT OF LESS THAN 100 BACTERIA PER
AutoCAD SHX Text
CC, OR EQUAL TO THE CONTROL SAMPLE. IF ANALYSIS RESULTS ARE NOT SATISFACTORY,
AutoCAD SHX Text
REPEAT THE DISINFECTION PROCEDURES AND RETEST UNTIL SPECIFIED STANDARDS ARE
AutoCAD SHX Text
ACHIEVED.
AutoCAD SHX Text
CONTRACTOR TO WARRANTY ALL MATERIALS, WORKMANSHIP, AND SYSTEM PERFORMANCE FOR A
AutoCAD SHX Text
PERIOD OF NOT LESS THAN ONE YEAR FROM TIME OF SUBSTSANTIAL COMPLETION. WHERE
AutoCAD SHX Text
MANUFACTURER'S STANDARD WRITTEN WARRANTIES OR WARRANTY REQUIREMENTS STATED
AutoCAD SHX Text
ELSEWHERE IN THE DRAWINGS ARE OF A PERIOD OF GREATER THAN ONE YEAR, CONTRACTOR OR
AutoCAD SHX Text
MANUFACTURER ARE TO PROVIDE WARRANTY OF LONGER DURATION.
AutoCAD SHX Text
MAXIMUM SPACING ON CENTERS
AutoCAD SHX Text
6'-0"
AutoCAD SHX Text
7'-0"
AutoCAD SHX Text
8'-0"
AutoCAD SHX Text
MAXIMUM SPACING ON CENTERS
AutoCAD SHX Text
3'-0"
AutoCAD SHX Text
4'-0"
AutoCAD SHX Text
ACCESS BOXES:
AutoCAD SHX Text
WALLS:
AutoCAD SHX Text
IN TILE WALLS, PROVIDE WITH POLISHED CHROME PLATE FACE.
AutoCAD SHX Text
IN OTHER FINISHED ROOMS, PROVIDE WITH BONDERIZED PRIME-COATED STEEL FACE AND WITH
AutoCAD SHX Text
ALLEN LOCK.
AutoCAD SHX Text
CEILINGS:
AutoCAD SHX Text
PROVIDE WITH BONDERIZED PRIME-COATED STEEL FACE WITH ALLEN LOCK.
AutoCAD SHX Text
FLOORS:
AutoCAD SHX Text
PROVIDE WITH PLAIN ALUMINUM OR NICKEL-BRONZE NON-SKID TOP.
AutoCAD SHX Text
MIN 2.75" THICK PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING ON ONE SIDE OF WALL AS A PERMANENT FORM
AutoCAD SHX Text
3.75" LIGHTWEIGHT CONCRETE
AutoCAD SHX Text
PIPE MATERIAL AS SCHEDULED
AutoCAD SHX Text
OPTIONAL METALLIC SLEEVE 10" DIA. MAX.; SCH. 5 MIN.; CAST OR GROUTED IN PLACE
AutoCAD SHX Text
3/8" DIAMETER MIN BEAD ALL AROUND
AutoCAD SHX Text
SEALANT OR PUTTY; MIN 1" APPLIED WITHIN ANNULAR SPACE. FLUSH WITH WALL SURFACE. APPLY 3/8" DIA MIN BEAD OF FILL MATERIAL AT PENETRANT/CONCRETE OR PENETRANT/SLEEVE INTERFACE
AutoCAD SHX Text
SECTION VIEW
AutoCAD SHX Text
UL SEALANT OR PUTTY
AutoCAD SHX Text
MINERAL WOOL PACKING MATERIAL
AutoCAD SHX Text
PIPE MATERIAL AS SCHEDULED
AutoCAD SHX Text
OPTIONAL STEEL SLEEVE
AutoCAD SHX Text
THROUGH PENETRATION - CONCRETE WALL OR SLAB UL SYSTEM NO: W-J-1108
AutoCAD SHX Text
PIPE MATERIAL AS SCHEDULED
AutoCAD SHX Text
1/4" MINIMUM CAULK TYPICAL ALL AROUND AND BOTH SIDES. ADDITIONAL FILL MATERIAL TO BE INSTALLED SUCH THAT A MIN 1/4" CROWN IS FORMED AROUND THE PENETRATING ITEM AND LAPPING 1/2" BEYOND THE PERIPHERY OF THE OPENING.
AutoCAD SHX Text
FIRE RATED WALL CONSTRUCTION BY OTHERS
AutoCAD SHX Text
SECTION VIEW
AutoCAD SHX Text
PIPE MATERIAL AS SCHEDULED
AutoCAD SHX Text
ANNULAR SPACE TO BE 1/8" MIN, 1/4" MAX.
AutoCAD SHX Text
THROUGH PENETRATION - FRAME WALL UL SYSTEM NO: W-L-1033
AutoCAD SHX Text
MIN 1" THICK 4 PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING. PACKING MATERIAL TO BE RECESSED FROM BOTH SURFACES OF WALL. TYPICAL ALL AROUND BOTH SIDES.
AutoCAD SHX Text
PLUMBING FLOOR PLAN - WATER SUPPLY
AutoCAD SHX Text
2014 FLORIDA BUILDNG CODE - ENERGY CONSERVATION
AutoCAD SHX Text
2014 FLORIDA BUILDING CODE - EXISTING BUILDING
AutoCAD SHX Text
BALL VALVES: PRESSURE RATING 250 PSI, FULL PORT, BRONZE TRIM BLOWOUT PROOF STEM, LEVER HANDLE, DEZINCIFICATION RESISTANT.
AutoCAD SHX Text
OR PRO-PRESS CONNECTION SYSTEM.
AutoCAD SHX Text
OR PRO-PRESS CONNECTION SYSTEM.

PROJECT NOTES-PLUMBING

DEMO NOTES-PLUMBING

PLUMBING FIXTURE SCHEDULE

DESCRIPTIONSYMBOL MANUFACTURER MODEL NUMBER

CONN SIZE (IN)

NOTESEQUAL MFG. CW HW

FLOW

RATEDRAIN

PLAN NOTES-WASTE/VENT

PLAN NOTES-WATER SUPPLY

WATER HEATER ON WALL BRACKET INSTALLATION

EXIS

TIN

G 1

HR T

ENA

NT

SEP

ARA

TIO

NW

ALL

TO

REM

AIN

AS IS

EXIS

TIN

G 1

HR T

ENA

NT

SEP

ARA

TIO

NW

ALL

TO

REM

AIN

AS IS

104

ROOMCONFERENCE

105

IT

107

HCP RR

108

BREAK AREA

106

HCP RR

EXIS

TIN

G 1

HR T

ENA

NT

SEP

ARA

TIO

NW

ALL

TO

REM

AIN

AS IS

EXIS

TIN

G 1

HR T

ENA

NT

SEP

ARA

TIO

NW

ALL

TO

REM

AIN

AS IS

104

ROOMCONFERENCE

105

IT

107

HCP RR

108

BREAK AREA

106

HCP RR

P.101

PLUMBINGFLOOR PLANS

WASTE/VENTWATER SUPPLY

PLUMBING FLOOR PLAN - WATER SUPPLY

SCALE: 1/4" = 1'-0"

N

PLUMBING FLOOR PLAN - WASTE/VENT

SCALE: 1/4" = 1'-0"

N

ISOMETRIC DIAGRAM - WATER SUPPLY

NOT TO SCALE

ISOMETRIC DIAGRAM - WASTE/VENT

NOT TO SCALE

REVISIONS

ISSUE DATE

JOB #

SHEET TITLE

SHEET NO.

05.27.16

1636

A N

EW T

ENA

NT

BU

ILD

OU

T FO

R

THE

VIL

LAG

ES, FL

32

15

9

MPEMILLER PROFESSIONAL

ENGINEERING, LLC

P.O. BOX 4246OCALA, FLORIDA [email protected]

MILLER PROFESSIONAL

CERTIFICATE OF AUTH. #30872

98

0 D

EL M

AR D

RIV

E

CA

RTE

R H

EALT

H

PARTIN ARCHITECTURE

P A

936 E. FT. KING STREETOCALA, FLORIDA 34471

P 352.629.3867 F 352.629.3866

FL LIC# AA26001291

ENGINEERING, LLC

.

...

SPA

NIS

H S

PRIN

GS

AutoCAD SHX Text
1.
AutoCAD SHX Text
COORDINATE ANY REQUIRED ROOFING WORK WITH VILLAGES SELECTED ROOFING CONTRACTOR. ANY ROOF PENETRATIONS THAT MAY BECOME NECESSARY ARE TO BE PERFORMED BY THIS CONTRACTOR AT GENERAL CONTRACTOR'S EXPENSE.
AutoCAD SHX Text
REMOVE ALL FIXTURES, DEVICES, AND PIPING WITHIN AREA OF WORK AS NECESSARY TO PREPARE FOR ACCOMMODATION OF RENOVATED/NEW SYSTEMS AS SHOWN ON THESE PLANS.
AutoCAD SHX Text
ALL EXISTING PIPING SERVING FIXTURES BEING REMOVED OR RELOCATED ARE TO BE REMOVED. BRANCH PIPING TO BE REMOVED AND CAPPED AT MAIN PIPING CONNECTION. DO NOT REMOVE ANY PIPING SECTION THAT WOULD AFFECT SERVICE FOR ADJACENT FIXTURES THAT WILL REMAIN.
AutoCAD SHX Text
NOTE: EXISTING SYSTEMS CONNECTION POINTS ARE BASED UPON BEST AVAILABLE INFORMATION DURING DESIGN, LIMITED ONLY TO ITEMS THAT ARE CLEARLY VISIBLE PRE-DEMOLITION. CONTRACTOR TO COORDINATE EXACT EXISTING SYSTEMS LOCATIONS AFTER COMMENCEMENT OF DEMOLITION AND PRIOR TO ANY ROUGH-IN WORK. ADVISE ENGINEER IF UTILITY CONNECTION POINTS DIFFER.
AutoCAD SHX Text
2.
AutoCAD SHX Text
ALL SLAB PENETRATIONS TO BE TERMITE TREATED BY LANDLORD'S PREFERRED TREATMENT SERVICE AT TENANT'S EXPENSE TO MAINTAIN EXISTING WARRANTIES.
AutoCAD SHX Text
CO
AutoCAD SHX Text
ZURN
AutoCAD SHX Text
Z1400-BZ
AutoCAD SHX Text
FURNISH WITH TOP TO MATCH
AutoCAD SHX Text
FLOOR COVERING OR SATIN
AutoCAD SHX Text
FINISHED BRONZE.
AutoCAD SHX Text
JOSAM
AutoCAD SHX Text
WATTS
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
LVWH
AutoCAD SHX Text
FAUCET
AutoCAD SHX Text
LAVATORY
AutoCAD SHX Text
PROTECTION
AutoCAD SHX Text
PIPE
AutoCAD SHX Text
KOHLER
AutoCAD SHX Text
K-2035
AutoCAD SHX Text
K-2057
AutoCAD SHX Text
0.5
AutoCAD SHX Text
COLOR TO BE WHITE
AutoCAD SHX Text
DELTA
AutoCAD SHX Text
CHICAGO
AutoCAD SHX Text
AMER STD
AutoCAD SHX Text
BRIGGS
AutoCAD SHX Text
-
AutoCAD SHX Text
0.5
AutoCAD SHX Text
2
AutoCAD SHX Text
0.5 GPM
AutoCAD SHX Text
COLOR TO BE WHITE
AutoCAD SHX Text
FURNISH WITH 1-1/4" CHROMED
AutoCAD SHX Text
BRASS TRAP AND STRAINER.
AutoCAD SHX Text
FINISH TO BE CHROME BRASS. FURNISH W/0.5 GPM AERATOR
AutoCAD SHX Text
T&S
AutoCAD SHX Text
B-2711
AutoCAD SHX Text
KOHLER
AutoCAD SHX Text
LAVATORY- ADA COMPLIANT WALL HUNG
AutoCAD SHX Text
CLEANOUT
AutoCAD SHX Text
EWC
AutoCAD SHX Text
ELKAY
AutoCAD SHX Text
LZSTL8C
AutoCAD SHX Text
FURNISH WITH TOP TO MATCH
AutoCAD SHX Text
FLOOR COVERING OR SATIN
AutoCAD SHX Text
FINISHED BRONZE.
AutoCAD SHX Text
HALSEY
AutoCAD SHX Text
OASIS
AutoCAD SHX Text
0.5
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
0.75 GPM
AutoCAD SHX Text
TAYLOR
AutoCAD SHX Text
8.0 GPH
AutoCAD SHX Text
ELECTRIC WATER COOLER WALL HUNG, HI/LO ADA COMPLIANT
AutoCAD SHX Text
WCPH
AutoCAD SHX Text
SEAT
AutoCAD SHX Text
WATER CLOSET
AutoCAD SHX Text
K-4731-C
AutoCAD SHX Text
-
AutoCAD SHX Text
AMER STD
AutoCAD SHX Text
0.5
AutoCAD SHX Text
-
AutoCAD SHX Text
3
AutoCAD SHX Text
1.4 GPF
AutoCAD SHX Text
K-3493
AutoCAD SHX Text
COLOR TO BE WHITE
AutoCAD SHX Text
COLOR TO BE WHITE
AutoCAD SHX Text
KOHLER
AutoCAD SHX Text
WATER CLOSET- ADA COMPLIANT FLUSH TANK PRESSURE ASSIST ELONGATED 1.4 GPF
AutoCAD SHX Text
KOHLER
AutoCAD SHX Text
BEMIS
AutoCAD SHX Text
AMER STD
AutoCAD SHX Text
JSS
AutoCAD SHX Text
FAUCET
AutoCAD SHX Text
SINK
AutoCAD SHX Text
B-0655-BSTP
AutoCAD SHX Text
BRIGGS
AutoCAD SHX Text
AMER STD
AutoCAD SHX Text
0.5
AutoCAD SHX Text
0.5
AutoCAD SHX Text
3
AutoCAD SHX Text
5.0 GPM
AutoCAD SHX Text
ZURN
AutoCAD SHX Text
MSB2424
AutoCAD SHX Text
FIAT
AutoCAD SHX Text
COLOR TO BE WHITE
AutoCAD SHX Text
T&S
AutoCAD SHX Text
CHICAGO
AutoCAD SHX Text
FINISH TO BE CHROME BRASS
AutoCAD SHX Text
JANITOR SERVICE SINK 3" NPTF TRAP AND STRAINER
AutoCAD SHX Text
EWH-1
AutoCAD SHX Text
EXPANSION
AutoCAD SHX Text
HEATER
AutoCAD SHX Text
ST-5
AutoCAD SHX Text
STATE
AutoCAD SHX Text
RHEEM
AutoCAD SHX Text
0.75
AutoCAD SHX Text
0.75
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
BY DOMESTIC
AutoCAD SHX Text
ENJ-30
AutoCAD SHX Text
A.O. SMITH
AutoCAD SHX Text
-
AutoCAD SHX Text
AMTROL
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
-
AutoCAD SHX Text
ELECTRIC WATER HEATER 30 GALLON 4.5 KW 208V, 1 HEIGHT = 31" EF = 0.95
AutoCAD SHX Text
TANK
AutoCAD SHX Text
(INCLUDED WITH K-2035)
AutoCAD SHX Text
BS
AutoCAD SHX Text
FAUCET
AutoCAD SHX Text
LAVATORY
AutoCAD SHX Text
B-2866-05
AutoCAD SHX Text
JUST
AutoCAD SHX Text
KOHLER
AutoCAD SHX Text
0.5
AutoCAD SHX Text
0.5
AutoCAD SHX Text
2
AutoCAD SHX Text
1.8 GPM
AutoCAD SHX Text
CHICAGO
AutoCAD SHX Text
DLR171610PD
AutoCAD SHX Text
ELKAY
AutoCAD SHX Text
FINISH TO BE STAINLESS STEEL
AutoCAD SHX Text
T&S
AutoCAD SHX Text
DELTA
AutoCAD SHX Text
FINISH TO BE CHROME BRASS
AutoCAD SHX Text
BREAK SINK 17"x16"x10"D 3 FAUCET HOLES
AutoCAD SHX Text
IMB
AutoCAD SHX Text
IPS CORP
AutoCAD SHX Text
BIM875
AutoCAD SHX Text
1/2" COPPER SUPPLY
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
BY DOMESTIC
AutoCAD SHX Text
0.5
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
ICE MACHINE BOX RECESSED 20 GA GALVANIZED 1/4 TURN VALVE
AutoCAD SHX Text
LVWH
AutoCAD SHX Text
WCPH
AutoCAD SHX Text
WCPH
AutoCAD SHX Text
LVWH
AutoCAD SHX Text
EWC
AutoCAD SHX Text
BS
AutoCAD SHX Text
EWH-1
AutoCAD SHX Text
2
AutoCAD SHX Text
JSS
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
0.75"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
0.75"
AutoCAD SHX Text
0.75"
AutoCAD SHX Text
1"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
1
AutoCAD SHX Text
IMB
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
LVWH
AutoCAD SHX Text
WCPH
AutoCAD SHX Text
WCPH
AutoCAD SHX Text
LVWH
AutoCAD SHX Text
JSS
AutoCAD SHX Text
BS
AutoCAD SHX Text
2" V.
AutoCAD SHX Text
2" V.
AutoCAD SHX Text
2" V.
AutoCAD SHX Text
2" V.
AutoCAD SHX Text
2" S.
AutoCAD SHX Text
3" S.
AutoCAD SHX Text
3" S.
AutoCAD SHX Text
2" S.
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
EWC
AutoCAD SHX Text
2
AutoCAD SHX Text
2" S.
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
4
AutoCAD SHX Text
4
AutoCAD SHX Text
CONNECT NEW 3" SANITARY SEWER PIPING TO EXISTING 4" MAIN SANITARY SEWER PIPING IN TENANT SPACE WITHIN 10' OF THIS LOCATION.
AutoCAD SHX Text
1
AutoCAD SHX Text
3
AutoCAD SHX Text
CONNECT NEW 2" VENT PIPING TO EXISTING CONNECTION IN TENANT SPACE WITHIN 10' OF THIS LOCATION.
AutoCAD SHX Text
PROVIDE FIXTURE WITH INTEGRAL TRAP CLEANOUT.
AutoCAD SHX Text
4
AutoCAD SHX Text
CONNECT NEW 2" SANITARY SEWER PIPING TO EXISTING 4" MAIN SANITARY SEWER PIPING IN TENANT SPACE WITHIN 10' OF THIS LOCATION.
AutoCAD SHX Text
2
AutoCAD SHX Text
CONNECT NEW 1" COLD WATER SUPPLY PIPING TO EXISTING MAIN WATER SUPPLY ABOVE CEILING SERVING TENANT SPACE WITHIN 10' OF THIS LOCATION.
AutoCAD SHX Text
1
AutoCAD SHX Text
EWH-1 TO BE MOUNTED ON WALL BRACKET ATTACHED TO EXTERIOR WALL, ABOVE JANITOR SERVICE SINK.
AutoCAD SHX Text
2
AutoCAD SHX Text
30" MAX.
AutoCAD SHX Text
INSTALL 1/4" MIN. DIAMETER ASTM A-36 STEEL ANCHORS TO PROVIDE MINIMUM PULLOUT RESISTANCE OF 800 LBS IN WALL SUBSTRATE (TYPICAL OF 3).
AutoCAD SHX Text
2-1/2" x 2-1/2" x 1/4" ANGLE BRACKET. TWO REQUIRED 30" APART MAXIMUM.
AutoCAD SHX Text
3-1/2" x 3/16" STEEL BAR GRATING WITH SPACER BARS NOT MORE THAN 4" O.C.
AutoCAD SHX Text
3" MAX.
AutoCAD SHX Text
12"
AutoCAD SHX Text
45°
AutoCAD SHX Text
3/8"
AutoCAD SHX Text
3/8"
AutoCAD SHX Text
3/8"
AutoCAD SHX Text
2-1/2" x 2-1/2" x 1/4" ANGLE FRAME.
AutoCAD SHX Text
ALL STEEL TO BE ASTM A-36. ALL WELD METAL TO HAVE MINIMUM STRENGTH OF 60 KPSI (EXX). WALL BRACKET TO BE MOUNTED ABOVE CEILING.
AutoCAD SHX Text
NOTE:
AutoCAD SHX Text
WATER HEATER
AutoCAD SHX Text
0.75" DRAIN PIPE DISCHARGE TO ADJACENT JANITOR SINK INDIRECTLY VIA AIR GAP
AutoCAD SHX Text
PRESSURE AND TEMPERATURE RELIEF VALVE. 0.75" DRAIN PIPE DISCHARGE TO ADJACENT JANITOR SINK INDIRECTLY VIA AIR GAP
AutoCAD SHX Text
COLD WATER
AutoCAD SHX Text
HOT WATER
AutoCAD SHX Text
WCPH
AutoCAD SHX Text
WCPH
AutoCAD SHX Text
LVWH
AutoCAD SHX Text
LVWH
AutoCAD SHX Text
EWC
AutoCAD SHX Text
JSS
AutoCAD SHX Text
BS
AutoCAD SHX Text
3" S.
AutoCAD SHX Text
2" S.
AutoCAD SHX Text
3" S.
AutoCAD SHX Text
2" V.
AutoCAD SHX Text
2" V.
AutoCAD SHX Text
2" V.
AutoCAD SHX Text
2" S.
AutoCAD SHX Text
2" S.
AutoCAD SHX Text
2" V.
AutoCAD SHX Text
3" S.
AutoCAD SHX Text
3" S.
AutoCAD SHX Text
2" V.
AutoCAD SHX Text
2" S.
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
4
AutoCAD SHX Text
4
AutoCAD SHX Text
1
AutoCAD SHX Text
IMB
AutoCAD SHX Text
ON WALL BRACKET
AutoCAD SHX Text
EWH-1
AutoCAD SHX Text
ABOVE CEILING
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
0.75"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
1"
AutoCAD SHX Text
1"
AutoCAD SHX Text
1"
AutoCAD SHX Text
0.75"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
0.75"
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
NO WORK THIS AREA UNLESS OTHERWISE NOTED
AutoCAD SHX Text
NO WORK THIS AREA UNLESS OTHERWISE NOTED

MECHANICAL NOTES

MECHANICAL ABBREVIATIONS

SYMBOL DESCRIPTION

MECHANICAL SYMBOL LEGEND

DESCRIPTIONSYMBOL

MECHANICAL INDEX

SHEET TITLESHEET NUMBER

GENERAL:

SUBMITTALS:

COORDINATION OF WORK:

PRODUCTS:

TEST AND BALANCE:

WARRANTY:

M.001

MECHANICALSCHEDULES,

NOTES, DETAILS

REVISIONS

ISSUE DATE

JOB #

SHEET TITLE

SHEET NO.

05.27.16

1636

A N

EW T

ENA

NT

BU

ILD

OU

T FO

R

THE

VIL

LAG

ES, FL

32

15

9

MPEMILLER PROFESSIONAL

ENGINEERING, LLC

P.O. BOX 4246OCALA, FLORIDA [email protected]

MILLER PROFESSIONAL

CERTIFICATE OF AUTH. #30872

98

0 D

EL M

AR D

RIV

E

CA

RTE

R H

EALT

H

PARTIN ARCHITECTURE

P A

936 E. FT. KING STREETOCALA, FLORIDA 34471

P 352.629.3867 F 352.629.3866

FL LIC# AA26001291

ENGINEERING, LLC

.

...

SPA

NIS

H S

PRIN

GS

AutoCAD SHX Text
BHP
AutoCAD SHX Text
BTUH
AutoCAD SHX Text
AHU
AutoCAD SHX Text
AFF
AutoCAD SHX Text
EF
AutoCAD SHX Text
DX
AutoCAD SHX Text
DB
AutoCAD SHX Text
CU
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text
AIR HANDLING UNIT
AutoCAD SHX Text
BRAKE HORSEPOWER
AutoCAD SHX Text
BRITISH THERMAL UNIT PER HOUR
AutoCAD SHX Text
HP
AutoCAD SHX Text
GA
AutoCAD SHX Text
FPM
AutoCAD SHX Text
%%DF
AutoCAD SHX Text
DIRECT EXPANSION
AutoCAD SHX Text
DRYBULB
AutoCAD SHX Text
DEGREES FAHRENHEIT
AutoCAD SHX Text
EXHAUST FAN
AutoCAD SHX Text
CONDENSING UNIT
AutoCAD SHX Text
SD
AutoCAD SHX Text
RS
AutoCAD SHX Text
NATIONAL ELECTRIC CODE (NFPA-70)
AutoCAD SHX Text
KILOWATTS
AutoCAD SHX Text
RPM
AutoCAD SHX Text
RH
AutoCAD SHX Text
REQD
AutoCAD SHX Text
RELATIVE HUMIDITY
AutoCAD SHX Text
REQUIRED
AutoCAD SHX Text
NEC
AutoCAD SHX Text
MIN
AutoCAD SHX Text
MAX
AutoCAD SHX Text
MAXIMUM
AutoCAD SHX Text
MINIMUM
AutoCAD SHX Text
KW
AutoCAD SHX Text
FEET PER MINUTE
AutoCAD SHX Text
GAUGE
AutoCAD SHX Text
HORSEPOWER
AutoCAD SHX Text
SUPPLY AIR DIFFUSER
AutoCAD SHX Text
REMOTE TEMPERATURE SENSOR
AutoCAD SHX Text
REVOLUTIONS PER MINUTE
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
STAINLESS STEEL
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
SS
AutoCAD SHX Text
EAG
AutoCAD SHX Text
EXHAUST AIR GRILLE
AutoCAD SHX Text
EOG
AutoCAD SHX Text
EXHAUST OUTLET GRILLE
AutoCAD SHX Text
RAG
AutoCAD SHX Text
RETURN AIR GRILLE
AutoCAD SHX Text
SL
AutoCAD SHX Text
SLR
AutoCAD SHX Text
SLOT DIFFUSER SUPPLY
AutoCAD SHX Text
SLOT RETURN
AutoCAD SHX Text
T
AutoCAD SHX Text
THERMOSTAT
AutoCAD SHX Text
FD
AutoCAD SHX Text
FIRE DAMPER
AutoCAD SHX Text
SUPPLY AIR DIFFUSER (SD) - 1 WAY
AutoCAD SHX Text
SUPPLY AIR DIFFUSER (SD) - 2 WAY
AutoCAD SHX Text
SUPPLY AIR DIFFUSER (SD) - 2 WAY
AutoCAD SHX Text
SUPPLY AIR DIFFUSER (SD) - 3 WAY
AutoCAD SHX Text
SUPPLY AIR DIFFUSER (SD) - 4 WAY
AutoCAD SHX Text
RETURN AIR DEVICE (RAG) EXHAUST AIR GRILL (EAG)
AutoCAD SHX Text
REMOTE TEMPERATURE SENSOR (RS)
AutoCAD SHX Text
THERMOSTAT (T). NUMBER INDICATES SYSTEM
AutoCAD SHX Text
FIRE DAMPER (FD)
AutoCAD SHX Text
SLOT DIFFUSER (SL)
AutoCAD SHX Text
LISTED IN INCHES UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
DUCT SIZE. (WIDTH/DEPTH). ALL DUCT SIZES
AutoCAD SHX Text
24/20
AutoCAD SHX Text
SUPPLY DUCTWORK, ROUND OR RECTANGULAR AS NOTED.
AutoCAD SHX Text
SPIN-IN WITH DAMPER
AutoCAD SHX Text
RETURN DUCTWORK, ROUND OR RECTANGULAR AS NOTED.
AutoCAD SHX Text
DUCT SIZE. (WIDTH/DEPTH). ALL DUCT SIZES LISTED IN INCHES UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
24/20
AutoCAD SHX Text
FLEXIBLE DUCT.
AutoCAD SHX Text
DUCT TRANSITION - RECT. TO ROUND.
AutoCAD SHX Text
T
AutoCAD SHX Text
101
AutoCAD SHX Text
RS
AutoCAD SHX Text
101
AutoCAD SHX Text
MECHANICAL - SCHEDULES, NOTES, DETAILS
AutoCAD SHX Text
M.001
AutoCAD SHX Text
MECHANICAL FLOOR PLAN - HVAC
AutoCAD SHX Text
M.101
AutoCAD SHX Text
FCU
AutoCAD SHX Text
FAN COIL UNIT
AutoCAD SHX Text
MECHANICAL CONTRACTOR SHALL COMPLETELY FAMILIARIZE HIMSELF/HERSELF WITH ALL CONDITIONS
AutoCAD SHX Text
AFFECTING HIS/HER WORK INCLUDING VISIT TO THE SITE BEFORE PREPARING PROPOSAL. ALL WORK
AutoCAD SHX Text
IS TO BE PERFORMED IN ACCORDANCE WITH ALL APPLICABLE CODES AND STANDARDS FROM ALL
AutoCAD SHX Text
AUTHORITIES HAVING JURISDICTION OVER THE WORK. WHERE CONFLICT EXISTS BETWEEN THE
AutoCAD SHX Text
APPLICABLE CODES AND STANDARDS OR THE PLANS AND SPECIFICATIONS, THE MOST STRINGENT AS
AutoCAD SHX Text
DETERMINED BY THE ENGINEER SHALL APPLY. CONTRACTOR SHALL NOTIFY ENGINEER OF
AutoCAD SHX Text
CONFLICTING CONDITIONS AFFECTING HIS/HER WORK AND ADVISE ENGINEER FOR CLARIFICATION.
AutoCAD SHX Text
LOCAL CODES IN EFFECT FOR THIS PROJECT INCLUDE BUT ARE NOT LIMITED TO THE FOLLOWING:
AutoCAD SHX Text
2014 FLORIDA BUILDING CODE
AutoCAD SHX Text
2014 FLORIDA BUILDING CODE - MECHANICAL
AutoCAD SHX Text
2014 FLORIDA BUILDNG CODE - PLUMBING
AutoCAD SHX Text
2014 FLORIDA BUILDING CODE - GAS
AutoCAD SHX Text
2011 NFPA 70 "NATIONAL ELECTRIC CODE"
AutoCAD SHX Text
NFPA 90A "INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS"
AutoCAD SHX Text
NFPA 90B "INSTALLATION OF WARM AIR HEATING AND AIR CONDITIONING SYSTEMS"
AutoCAD SHX Text
SUBMISSION OF BID INDICATES CONTRACTOR'S ACKNOWLEDGEMENT THAT THEY ARE PROVIDING TO THE
AutoCAD SHX Text
OWNER A COMPLETE AND OPERATING SYSTEM. ANY CONTRACTOR UNCERTAINTIES OR MISSING
AutoCAD SHX Text
INFORMATION CONCERNS TO BE SUBMITTED IN WRITING PRIOR TO SUBMISSION OF BID SO THAT
AutoCAD SHX Text
ENGINEER MAY PROVIDE PROPER CLARIFICATION.
AutoCAD SHX Text
PROVIDE ADEQUATE NUMBER OF SKILLED WORKMEN WHO ARE THOROUGHLY TRAINED AND
AutoCAD SHX Text
EXPERIENCED IN THE NECESSARY CRAFTS AND WHO ARE COMPLETELY FAMILIAR WITH THE SPECIFIED
AutoCAD SHX Text
REQUIREMENTS AND THE METHODS NEEDED FOR PROPER PERFORMANCE OF THE WORK.
AutoCAD SHX Text
CONTRACTOR TO PREPARE SUBMITTALS AND SHOP DRAWINGS FOR ALL MECHANICAL WORK AS
AutoCAD SHX Text
REQUIRED BY THE CONSTRUCTION DOCUMENTS FOR ENGINEER'S REVIEW NOT MORE THAN 35
AutoCAD SHX Text
CALENDAR DAYS AFTER CONTRACTOR HAS RECEIVED THE OWNER'S NOTICE TO PROCEED.
AutoCAD SHX Text
CONTRACTOR TO SUBMIT REFRIGERANT PIPING DIAGRAMS/SHOP DRAWINGS PROVIDED BY EQUIPMENT
AutoCAD SHX Text
MANUFACTUER WITH EQUIPMENT SUBMITTTAL FOR SITE SPECIFIC INSTALLATION.
AutoCAD SHX Text
CONTRACTOR TO SUBMIT NAME AND QUALIFICATIONS OF TEST AND BALANCE COMPANY BEING
AutoCAD SHX Text
PROPOSED BY CONTRACTOR FOR TEST AND BALANCE WORK, INCLUDING DOCUMENTATION OF
AutoCAD SHX Text
EXPERIENCE AND CONTRACTOR'S ENGINEERING CORPORATION LICENSE SHOWING NAME OF QUALIFYING
AutoCAD SHX Text
REGISTERED PROFESSIONAL ENGINEER AND QUALIFYING PROFESSIONAL ENGINEER'S CURRENT LICENSE.
AutoCAD SHX Text
UPON COMPLETION OF WORK, CONTRACTOR TO PROVIDE TWO COPIES OF AN OPERATION AND
AutoCAD SHX Text
MAINTENANCE MANUAL. INCLUDE IN EACH MANUAL A COPY OF THE PROJECT RECORD DOCUMENTS.
AutoCAD SHX Text
ENGINEER'S DRAWINGS AND CONSTRUCTION DOCUMENTS ARE DIAGRAMMATIC. CONTRACTOR OF THIS
AutoCAD SHX Text
WORK TO COORDINATE WITH ALL WORK OF CONTRACTORS OF ALL TRADES AND GENERAL
AutoCAD SHX Text
CONTRACTOR. CONTRACTORS TO FIELD MEASURE PRIOR TO FABRICATION OF ANY WORK.
AutoCAD SHX Text
CONTRACTOR OF WORK OF THIS TRADE TO COMMUNICATE WITH GENERAL CONTRACTOR AND
AutoCAD SHX Text
CONTRACTORS OF OTHER TRADES AND PREPARE DRAWINGS, SKETCHES, AND PROVIDE INFORMATION
AutoCAD SHX Text
AS NEEDED TO COMMUNICATE WITH OTHER TRADES FOR CONSTUCTION OF COMPLETE AND OPERATING
AutoCAD SHX Text
SYSTEM WITHOUT ADDITIONAL COST TO OWNER. PRIOR TO BEGINNING WORK OF THIS TRADE,
AutoCAD SHX Text
CONTRACTOR OF THIS TRADE TO CONDUCT COORDINATION MEETING WITH OTHER AFFECTED
AutoCAD SHX Text
CONTRACTORS OF OTHER TRADES AND GENERAL CONTRACTOR FOR PURPOSES OF COORDINATION.
AutoCAD SHX Text
CONTRACTORS' FAILURES TO COORDINATE WILL NOT BE CAUSE FOR RECOVERY OF ADDITIONAL
AutoCAD SHX Text
COMPENSATION FOR CORRECTION OR MODIFICATION WORK WHICH IN THE SOLE OPINION OF THE
AutoCAD SHX Text
ENGINEER IS NOT WELL COORDINATED.
AutoCAD SHX Text
LAYOUT THE MECHANICAL SYSTEM IN CAREFUL COORDINATION WITH THE DRAWINGS, DETERMINING
AutoCAD SHX Text
PROPER ELEVATIONS FOR ALL COMPONENTS OF THE SYSTEM USING ONLY THE MINIMUM NUMBER OF
AutoCAD SHX Text
BENDS TO PRODUCE A SATISFACTORILY FUNCTIONING SYSTEM. FOLLOW THE GENERAL LAYOUT SHOWN
AutoCAD SHX Text
ON THE DRAWINGS IN ALL CASES EXCEPT WHERE OTHER WORK MAY INTERFERE.
AutoCAD SHX Text
ALL MATERIALS TO BE OF DOMESTIC MANUFACTURER UNLESS OTHERWISE DIRECTED.
AutoCAD SHX Text
FIRE DAMPERS:
AutoCAD SHX Text
FIRE DAMPERS TO BE INSTALLED UNLESS OTHERWISE NOTED IN ALL RATED FLOOR AND WALL
AutoCAD SHX Text
PENETRATIONS AND/OR IN ACCORDANCE WITH THE MOST CURRENT REQUIREMENTS OF NFPA 90, 90A,
AutoCAD SHX Text
OR 90B. FIRE DAMPERS TO BE INSTALLED AS SHOWN ON THE DETAILS AND IN ACCORDANCE WITH
AutoCAD SHX Text
THE MOST CURRENT SMACNA STANDARDS.
AutoCAD SHX Text
INSTALL FIRE DAMPERS IN SLEEVES AND SEAL BETWEEN SLEEVE AND FLOOR CUT WITH UL APPROVED
AutoCAD SHX Text
FIRESTOP SEALANT.
AutoCAD SHX Text
ALL FIRE DAMPERS TO HAVE FULL FLOW CROSS SECTION, TYPE B.
AutoCAD SHX Text
FURNISH DYNAMIC FIRE DAMPERS IN SYSTEMS WHOSE BLOWERS DO NOT SHUT DOWN UPON
AutoCAD SHX Text
INITIATION OF FIRE ALARM SYSTEM. STATIC FIRE DAMPERS ARE PERMITTED FOR USE WITH SYSTEMS
AutoCAD SHX Text
WHOSE BLOWERS SHUT DOWN ON INITIATION OF FIRE ALARM SYSTEM.
AutoCAD SHX Text
AIR FILTERS:
AutoCAD SHX Text
UNLESS OTHERWISE NOTED, ALL FILTERS TO BE ASHRAE MERV 8 PLEATED FILTER MEDIA.
AutoCAD SHX Text
INSTALL TEMPORARY AIR FILTERS FOR USE DURING CONSTRUCTION AT TIME FILTER RACKS ARE
AutoCAD SHX Text
INSTALLED. IF SYSTEMS ARE OPERATING DURING CONSTRUCTION, FILTERS ARE TO BE REPLACED
AutoCAD SHX Text
MONTHLY AND DUCT CLEANING IS TO BE PERFORMED JUST PRIOR TO REQUEST FOR SUBSTANTIAL
AutoCAD SHX Text
COMPLETION AND BEFORE BEGINNING OF TEST AND BALANCE WORK.
AutoCAD SHX Text
PRIOR TO CONTRACTORS REQUEST FOR SUBSTANTIAL COMPLETION INSPECTION, CONTRACTOR TO
AutoCAD SHX Text
PROVIDE INDEPENDENT TEST AND BALANCE BY FIRM WITH NOT LESS THAN 10 YEARS
AutoCAD SHX Text
DEMONSTRATABLE EXPERIENCE SPECIALIZING IN TEST AND BALANCE WORK. TEST AND BALANCE TO
AutoCAD SHX Text
BE PERFORMED IN ACCORDANCE WITH THE WRITTEN PROCEDURES OF SMACNA, AABC, OR NEBB AND
AutoCAD SHX Text
COMPANY CERTIFIED BY AABC OR NEBB. ALL TEST AND BALANCE WORK TO BE PERFORMED UNDER
AutoCAD SHX Text
THE SUPERVISION OF A LICENSED PROFESSIONAL ENGINEER AND ALL REPORTS TO BEAR THE
AutoCAD SHX Text
ORIGINAL SEAL AND SIGNATURE OF LICENSED PROFESSIONAL ENGINEER.
AutoCAD SHX Text
TEST AND ADJUST EACH PIECE OF EQUIPMENT AND EACH SYSTEM AS REQURIED TO ASSURE PROPER
AutoCAD SHX Text
BALANCE AND OPERATION. TEST AND REGULATE VENTILATION AND AIR CONDITIONING SYSTEMS TO
AutoCAD SHX Text
CONFORM TO THE AIR VOLUMES SHOWN ON THE APPROVED DESIGN DRAWINGS. MAKE TESTS AND
AutoCAD SHX Text
ADJUSTMENTS IN APPARATUS AND DUCTS FOR SECURING THE PROPER VOLUME AND FACE
AutoCAD SHX Text
DISTRIBUTION OF AIR FOR EACH GRILLE AND CEILING OUTLET. WHERE REQUIRED, PROVIDE PULLEYS
AutoCAD SHX Text
FOR FANS AT NO ADDITIONAL COST TO THE OWNER, AND SET TO DRIVE THE FANS AT THE SPEED
AutoCAD SHX Text
NEEDED TO GIVE THE INDICATED VOLUME.
AutoCAD SHX Text
FOR EACH SYSTEM, TAKE THE FOLLOWING DATA IN TABULATED FORM:
AutoCAD SHX Text
AIR VOLUMES AT ALL SUPPLY, RETURN, AND EXHAUST OUTLETS
AutoCAD SHX Text
TOTAL CFM SUPPLIED, MEASURED AT RTU
AutoCAD SHX Text
TOTAL CFM RETURNED, MEASURED AT RTU
AutoCAD SHX Text
TOTAL CFM OUTDOOR AIR AT MULTIPLE DAMPER SETTINGS WHERE REQUIRED, MEASURED AT RTU
AutoCAD SHX Text
TOTAL CFM EXHAUST AT MULTIPLE SETTINGS WHERE REQUIRED, MEASURED AT RTU
AutoCAD SHX Text
DRY BULB AND WET BULB TEMPERATURES AT OUTDOOR AIR INTAKES, RETURN AIR, MIXED
AutoCAD SHX Text
RETURN/OUTDOOR AIR, AND SUPPLY AIR
AutoCAD SHX Text
SYSTEM COOLING CAPACITY
AutoCAD SHX Text
TOTAL, RETURN, AND SUPPLY STATIC PRESSURE AT EACH FAN AND AT EACH SYSTEM
AutoCAD SHX Text
MOTOR SPEED, FAN SPEED, AND INPUT AMPERE RATING FOR EACH FAN
AutoCAD SHX Text
THERMOSTAT AND TEMPERATURE SENSOR CALIBRATIONS
AutoCAD SHX Text
AIR FLOW TRAVERSES AT ALL AIR HANDLING SIDES OF ALL HEATING AND COOLING EQUIPMENT
AutoCAD SHX Text
INCLUDING BUT NOT LIMITED TO COMPLETE TRAVERSES AND MULTIPLE OUTDOOR AIR DAMPER
AutoCAD SHX Text
SETTINGS FOR TOTAL SUPPLY, TOTAL RETURN, AND TOTAL OUTDOOR AIR.
AutoCAD SHX Text
CONTRACTOR TO INCLUDE IN TEST AND BALANCE WORK THE FOLLOWING ADJUSTMENT SERVICES
AutoCAD SHX Text
DURING THE FIRST 18 MONTHS FROM THE DATE OF SUBSTANTIAL COMPLETION AS WELL AS THOSE
AutoCAD SHX Text
INDICATED ABOVE FOR THE PURPOSES OF PERFORMANCE CONFIRMATION, COMFORT BALANCING, AND
AutoCAD SHX Text
OTHER SYSTEM ADJUSTMENT:
AutoCAD SHX Text
NOT LESS THAN THREE (3) SEPARATE VISITS TO BE ATTENDED BY COMPOSITE CREW INCLUDING
AutoCAD SHX Text
MECHANICAL CONTRACTOR, CONTROLS CONTRACTOR, GENERAL CONTRACTOR, OWNER'S
AutoCAD SHX Text
REPRESENTATIVE, AND INDEPENDENT TEST AND BALANCE COMPANY OF NOT LESS THAN FOUR HOUR
AutoCAD SHX Text
DURATION AS REQUESTED BY ENGINEER. CREW TO BE COMPLETELY CAPABLE OF OPERATING,
AutoCAD SHX Text
ADJUSTING, AND SERVICING ALL MECHANICAL EQUIPMENT AND CONTROLS ASSOCIATED WITH THE
AutoCAD SHX Text
PROJECT AT TIME OF SITE VISIT. SCHEDULE TO BE SUBMITTED TO OWNER'S REPRESENTATIVE AT
AutoCAD SHX Text
TIME OF BUILDING ACCEPTANCE AND WILL BE REVIEWED AND APPROVED PRIOR TO RETURNING TO
AutoCAD SHX Text
CONTRACTOR.
AutoCAD SHX Text
CONTRACTOR TO WARRANTY ALL MATERIALS, WORKMANSHIP, AND SYSTEM PERFORMANCE FOR A
AutoCAD SHX Text
PERIOD OF NOT LESS THAN ONE YEAR FROM TIME OF SUBSTSANTIAL COMPLETION. WHERE
AutoCAD SHX Text
MANUFACTURER'S STANDARD WRITTEN WARRANTIES OR WARRANTY REQUIREMENTS STATED ELSEWHERE
AutoCAD SHX Text
IN THE DRAWINGS ARE OF A PERIOD OF GREATER THAN ONE YEAR, CONTRACTOR OR MANUFACTURER
AutoCAD SHX Text
ARE TO PROVIDE WARRANTY OF LONGER DURATION.
AutoCAD SHX Text
CONTRACTOR TO NOTIFY OWNER'S REPRESENTATIVE OF DATE OF SUBSTANTIAL COMPLETION AT TIME
AutoCAD SHX Text
OF SUBSTANTIAL COMPLETION.
AutoCAD SHX Text
DUCTWORK:
AutoCAD SHX Text
GENERAL:
AutoCAD SHX Text
ALL DIMENSIONS SHOWN ON THE PLANS ARE CLEAR INSIDE DIMENSIONS.
AutoCAD SHX Text
DUCT MATERIALS, INDOOR LOCATIONS:
AutoCAD SHX Text
PROVIDE G-60 GALVANIZED STEEL UNLESS OTHERWISE NOTED. DUCTWORK WITHIN 10' OF EXTERIOR
AutoCAD SHX Text
BUILDING PENETRATIONS TO BE G-90 GALVANIZED STEEL.
AutoCAD SHX Text
IN ALL EXPOSED INTERIOR LOCATIONS, PROVIDE NOT LESS THAN TWO GAGES HEAVIER THAN THE
AutoCAD SHX Text
MINIMUM GAUGE REQUIRED BY THE APPLICABLE SMACNA STANDARD AND JOINED WITH FOUR BOLT
AutoCAD SHX Text
CONNECTION AS MANUFACTURED BY DUCTMATE.
AutoCAD SHX Text
FLEXIBLE DUCTWORK TO HAVE NOT LESS THAN R-6 INSULATION RATING, ATCO UPC #036 OR EQUAL
AutoCAD SHX Text
BY SCHULLER. FLEX DUCT TO HAVE FLAME SPREAD RATING LESS THAN 25 AND SMOKE DEVELOPED
AutoCAD SHX Text
RATING OF LESS THAN 50.
AutoCAD SHX Text
DUCT MATERIALS, OUTDOOR LOCATIONS:
AutoCAD SHX Text
PROVIDE G-90 GALVANIZED STEEL.
AutoCAD SHX Text
DUCTWORK INSULATION:
AutoCAD SHX Text
GENERAL:
AutoCAD SHX Text
ALL EXTERNAL DUCTWORK WRAP TO BE SCHULLER R-SERIES MICROLITE FIBERGLASS DUCT WRAP
AutoCAD SHX Text
WITH FSK FACING OR EQUAL BY OCF.
AutoCAD SHX Text
ALL INTERNAL DUCT LINER TO BE SCHULLER PERMACOTE LINACOUSTIC WITH FACTORY APPLIED
AutoCAD SHX Text
ANTI-MICROBIAL TREATMENT.
AutoCAD SHX Text
INSULATION AND DUCT LINER TO HAVE FLAME SPREAD RATING LESS THAN 25 AND SMOKE
AutoCAD SHX Text
DEVELOPED RATING OF LESS THAN 50.
AutoCAD SHX Text
ALL INSULATION IS TO BE APPLIED WITH ADHESIVE AND MECHANICAL FASTENERS IN ACCORDANCE
AutoCAD SHX Text
WITH THE MOST CURRENT WRITTEN RECOMMENDATIONS OF SMACNA.
AutoCAD SHX Text
SUPPLY AND RETURN DUCTWORK:
AutoCAD SHX Text
NOT LESS THAN R-6 INSTALLED RATING UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
EXHAUST AND OUTDOOR AIR DUCTWORK:
AutoCAD SHX Text
NOT LESS THAN R-4 INSTALLED RATING UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
INSTALLATION:
AutoCAD SHX Text
ALL DUCTWORK TO BE CONSTRUCTED IN A MANNER CONSISTENT WITH THE MOST CURRENT DUCT
AutoCAD SHX Text
CONSTRUCTION STANDARDS OF SMACNA.
AutoCAD SHX Text
NO PLENUM-TYPE CONNECTIONS OF ANY KIND ARE PERMITTED UNLESS OTHERWISE NOTED OR
AutoCAD SHX Text
PERMITTED BY ENGINEER FOR SPECIAL CONDITION.
AutoCAD SHX Text
ALL DUCTWORK TO BE SMACNA SEAL CLASS "C" UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
TURNING VANES ARE TO BE INSTALLED IN ALL BRANCH CONNECTIONS OF ALL RECTANGULAR
AutoCAD SHX Text
DUCTWORK.
AutoCAD SHX Text
MANUAL VOLUME DAMPERS ARE TO BE INSTALLED IN ALL BRANCH DUCTWORK CONNECTIONS OR AS
AutoCAD SHX Text
OTHERWISE NOTED OR SHOWN, WITH THE EXCEPTION OF IN GREASE LADEN DUCTWORK. VOLUME
AutoCAD SHX Text
DAMPERS ARE TO BE 2" STAND-OFF TYPE.
AutoCAD SHX Text
EXPOSED DUCTWORK TO BE PAINTED CONSISTENT WITH THE REQUIREMENTS LISTED IN THE
AutoCAD SHX Text
ARCHITECTURAL DOCUMENTS. IF REQUIREMENTS ARE NOT FOUND IN ARCHITECTURAL DOCUMENTS,
AutoCAD SHX Text
PROVIDE ONE COAT OF PRIMER AND TWO COATS OF OIL BASED ENAMEL AS MANUFACTURED BY PPG
AutoCAD SHX Text
OR SHERWIN WILLIAMS APPLIED IN STRICT ACCORDANCE WITH MANUFACTURER'S WRITTEN
AutoCAD SHX Text
INSTRUCTIONS. COLOR TO BE AS SELECTED BY ARCHITECT OR ENGINEER.
AutoCAD SHX Text
COORDINATE WITH TRUSS MANUFACTURER AS MAY BE REQUIRED IN ORDER TO PROVIDE REQUIRED
AutoCAD SHX Text
CLEARANCES AND TRUSS SPACE AS NEEDED FOR INSTALLATION OF THE DUCTWORK.
AutoCAD SHX Text
WHERE DUCTWORK PENETRATES DRAFT STOPS OR OTHER CONTINUOUS WALLS OR OTHER BARRIERS IN
AutoCAD SHX Text
THE CONSTRUCTION, SEAL DUCTWORK AROUND PENETRATION IN A MANNER CONSISTENT WITH LEVEL
AutoCAD SHX Text
OF PROTECTION OF DRAFT STOP, WALL, OR OTHER BARRIER.
AutoCAD SHX Text
PROVIDE DUCT ACCESS DOOR AT ALL DUCT SMOKE DETECTOR LOCATIONS.
AutoCAD SHX Text
ALL EXISTING DUCTWORK PASSING THROUGH NEW FIRE RATED CONSTRUCTIONS TO BE
AutoCAD SHX Text
RECONSTRUCTED ACCORDING TO AN APPROVED UL RATED ASSEMBLY AS REQUIRED BY THE
AutoCAD SHX Text
AUTHORITY HAVING JURISDICTION (AHJ).
AutoCAD SHX Text
2014 FLORIDA BUILDNG CODE - ENERGY CONSERVATION
AutoCAD SHX Text
2014 FLORIDA BUILDING CODE - EXISTING BUILDING
AutoCAD SHX Text
ALL FILTERS TO BE LABELED WITH THE DATE OF INSTALLATION.
AutoCAD SHX Text
HEATING, VENTILATING, AND AIR CONDITIONING EQUIPMENT:
AutoCAD SHX Text
GENERAL:
AutoCAD SHX Text
EACH ROOFTOP UNIT, CONDENSING UNIT, HEAT PUMP, AND AIR HANDLING UNIT TO BE FURNISHED
AutoCAD SHX Text
WITH ENGRAVED PLASTIC LABEL WITH THE FOLLOWING INFORMATION:
AutoCAD SHX Text
UNIT NUMBER
AutoCAD SHX Text
PANEL AND CIRCUIT BREAKER NUMBER
AutoCAD SHX Text
HEATING COIL SIZE

EXIS

TIN

G 1

HR T

ENA

NT

SEP

ARA

TIO

NW

ALL

TO

REM

AIN

AS IS

EXIS

TIN

G 1

HR T

ENA

NT

SEP

ARA

TIO

NW

ALL

TO

REM

AIN

AS IS

100

RECEPTIONWAITING/

101

OFFICE

102

OFFICE

103

WORK AREA

104

ROOMCONFERENCE

105

IT

106

HCP RR

107

HCP RR

108

BREAK AREA

A/C & HEATING EQUIPMENT SCHEDULE

RTU-4

(EXISTING TO REMAIN)

FAN SCHEDULE

AIR DISTRIBUTION DEVICE SCHEDULE

NECK SIZE FACE SIZE MAX CFM MAX NC MAX SP RUN OUT SIZETHROW

EF-1 EF-2 EF-3

PLAN NOTES-MECHANICAL

PROJECT NOTES-MECHANICAL

SEQUENCE OF OPERATION

DEMO NOTES-MECHANICAL

M.101

MECHANICALFLOOR PLAN

HVAC

MECHANICAL FLOOR PLAN - HVAC

SCALE: 1/4" = 1'-0"

N

REVISIONS

ISSUE DATE

JOB #

SHEET TITLE

SHEET NO.

05.27.16

1636

A N

EW T

ENA

NT

BU

ILD

OU

T FO

R

THE

VIL

LAG

ES, FL

32

15

9

MPEMILLER PROFESSIONAL

ENGINEERING, LLC

P.O. BOX 4246OCALA, FLORIDA [email protected]

MILLER PROFESSIONAL

CERTIFICATE OF AUTH. #30872

98

0 D

EL M

AR D

RIV

E

CA

RTE

R H

EALT

H

PARTIN ARCHITECTURE

P A

936 E. FT. KING STREETOCALA, FLORIDA 34471

P 352.629.3867 F 352.629.3866

FL LIC# AA26001291

ENGINEERING, LLC

.

...

SPA

NIS

H S

PRIN

GS

AutoCAD SHX Text
20/14
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
EF-1
AutoCAD SHX Text
EF-3
AutoCAD SHX Text
SD1-25
AutoCAD SHX Text
SD1-25
AutoCAD SHX Text
(75 CFM)
AutoCAD SHX Text
(75 CFM)
AutoCAD SHX Text
SD1-75
AutoCAD SHX Text
SD3-125
AutoCAD SHX Text
SD3-125
AutoCAD SHX Text
RAG4-125
AutoCAD SHX Text
RAG4-125
AutoCAD SHX Text
SD3-125
AutoCAD SHX Text
SD3-125
AutoCAD SHX Text
SD3-125
AutoCAD SHX Text
SD3-125
AutoCAD SHX Text
SD4-225
AutoCAD SHX Text
SD4-225
AutoCAD SHX Text
SD3-150
AutoCAD SHX Text
SD3-150
AutoCAD SHX Text
SD3-150
AutoCAD SHX Text
RAG6-450
AutoCAD SHX Text
RAG6-335(x2)
AutoCAD SHX Text
RAG5-250
AutoCAD SHX Text
10"%%C
AutoCAD SHX Text
16/14
AutoCAD SHX Text
8"%%C
AutoCAD SHX Text
12/14
AutoCAD SHX Text
10"%%C
AutoCAD SHX Text
10"%%C
AutoCAD SHX Text
12/10
AutoCAD SHX Text
SD1-25
AutoCAD SHX Text
6/10
AutoCAD SHX Text
8"%%C
AutoCAD SHX Text
EF-2
AutoCAD SHX Text
(75 CFM)
AutoCAD SHX Text
8"%%C
AutoCAD SHX Text
1
AutoCAD SHX Text
24/14
AutoCAD SHX Text
10"%%C
AutoCAD SHX Text
12"%%C
AutoCAD SHX Text
8"%%C
AutoCAD SHX Text
24/14
AutoCAD SHX Text
RS
AutoCAD SHX Text
4
AutoCAD SHX Text
2
AutoCAD SHX Text
RS
AutoCAD SHX Text
4
AutoCAD SHX Text
2
AutoCAD SHX Text
T
AutoCAD SHX Text
2
AutoCAD SHX Text
4
AutoCAD SHX Text
18/14
AutoCAD SHX Text
10/14
AutoCAD SHX Text
12"%%C
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
AREA SERVED
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
208/3
AutoCAD SHX Text
VOLTAGE/PHASE
AutoCAD SHX Text
26.6
AutoCAD SHX Text
MCA (A) (FAN+HEAT)
AutoCAD SHX Text
30
AutoCAD SHX Text
MOCP (A) (FAN+HEAT)
AutoCAD SHX Text
BALANCE INFORMATION
AutoCAD SHX Text
1800
AutoCAD SHX Text
SUPPLY CFM (MIN/MAX)
AutoCAD SHX Text
1620
AutoCAD SHX Text
RETURN CFM (MIN/MAX)
AutoCAD SHX Text
180
AutoCAD SHX Text
OUTDOOR AIR CFM (MIN/MAX)
AutoCAD SHX Text
-
AutoCAD SHX Text
EXHAUST AIR CFM (MIN/MAX)
AutoCAD SHX Text
EXISTING PACKAGED ROOFTOP UNIT TO REMAIN. BALANCE SYSTEM TO REQUIREMENTS LISTED ABOVE. ADVISE ENGINEER IF ANY VALUES ARE NOT OBTAINABLE.
AutoCAD SHX Text
PACKAGED ROOFTOP UNIT
AutoCAD SHX Text
CARRIER
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
50TFF006
AutoCAD SHX Text
MODEL NUMBER
AutoCAD SHX Text
PERFORMANCE
AutoCAD SHX Text
60.0
AutoCAD SHX Text
TOTAL COOLING CAPACITY (BTUH)
AutoCAD SHX Text
45.0
AutoCAD SHX Text
SENSIBLE COOLING CAPACITY (MBTUH)
AutoCAD SHX Text
7.5
AutoCAD SHX Text
HEATING CAPACITY (KW)
AutoCAD SHX Text
AREA SERVED
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
MODEL NUMBER
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
CFM
AutoCAD SHX Text
RPM
AutoCAD SHX Text
BHP
AutoCAD SHX Text
ESP (IN-H20)
AutoCAD SHX Text
MOTOR HP
AutoCAD SHX Text
VOLTAGE/PHASE
AutoCAD SHX Text
INTERLOCK WITH
AutoCAD SHX Text
ACCESSORIES
AutoCAD SHX Text
ACCESSORIES:
AutoCAD SHX Text
1
AutoCAD SHX Text
VARIABLE SPEED CONTROLLER
AutoCAD SHX Text
2
AutoCAD SHX Text
INTEGRAL DISCONNECT SWITCH
AutoCAD SHX Text
3
AutoCAD SHX Text
BACKDRAFT DAMPER
AutoCAD SHX Text
4
AutoCAD SHX Text
OUTLET SCREEN
AutoCAD SHX Text
5
AutoCAD SHX Text
VIBRATION ISOLATION
AutoCAD SHX Text
ACCEPTABLE EQUAL MANUFACTURERS INCLUDE COOK AND TWIN CITY, OR WHERE APPROVED BY ENGINEER PRIOR TO SUBMISSION OF BID.
AutoCAD SHX Text
UNISEX RR #102
AutoCAD SHX Text
ACCEPTABLE EQUAL MANUFACTURERS FOR AIR DISTRIBUTION DEVICES TO INCLUDE TITUS, PRICE, OR NAILOR, OR WHERE APPROVED BY ENGINEER PRIOR TO SUBMISSION OF BID.
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
5700 AL
AutoCAD SHX Text
SD1
AutoCAD SHX Text
SD2
AutoCAD SHX Text
SD3
AutoCAD SHX Text
SD4
AutoCAD SHX Text
100
AutoCAD SHX Text
175
AutoCAD SHX Text
175
AutoCAD SHX Text
275
AutoCAD SHX Text
<15
AutoCAD SHX Text
<15
AutoCAD SHX Text
<15
AutoCAD SHX Text
<15
AutoCAD SHX Text
0.030
AutoCAD SHX Text
0.043
AutoCAD SHX Text
0.027
AutoCAD SHX Text
0.040
AutoCAD SHX Text
SD5
AutoCAD SHX Text
400
AutoCAD SHX Text
<15
AutoCAD SHX Text
0.058
AutoCAD SHX Text
SD6
AutoCAD SHX Text
550
AutoCAD SHX Text
<15
AutoCAD SHX Text
0.064
AutoCAD SHX Text
METALAIRE
AutoCAD SHX Text
SUPPLY DIFFUSER
AutoCAD SHX Text
RH
AutoCAD SHX Text
12/12
AutoCAD SHX Text
RAG1
AutoCAD SHX Text
12/12
AutoCAD SHX Text
RAG2
AutoCAD SHX Text
12/12
AutoCAD SHX Text
RAG3
AutoCAD SHX Text
22/22
AutoCAD SHX Text
RAG4
AutoCAD SHX Text
14/14
AutoCAD SHX Text
14/14
AutoCAD SHX Text
14/14
AutoCAD SHX Text
24/24
AutoCAD SHX Text
200
AutoCAD SHX Text
300
AutoCAD SHX Text
400
AutoCAD SHX Text
200
AutoCAD SHX Text
19
AutoCAD SHX Text
19
AutoCAD SHX Text
20
AutoCAD SHX Text
19
AutoCAD SHX Text
0.031
AutoCAD SHX Text
0.025
AutoCAD SHX Text
0.020
AutoCAD SHX Text
0.031
AutoCAD SHX Text
12/12, 8" ID
AutoCAD SHX Text
12/12, 10" ID
AutoCAD SHX Text
12/12, 12" ID
AutoCAD SHX Text
22/22, 8" ID
AutoCAD SHX Text
22/22
AutoCAD SHX Text
RAG5
AutoCAD SHX Text
24/24
AutoCAD SHX Text
300
AutoCAD SHX Text
19
AutoCAD SHX Text
0.025
AutoCAD SHX Text
22/22, 10" ID
AutoCAD SHX Text
22/22
AutoCAD SHX Text
RAG6
AutoCAD SHX Text
24/24
AutoCAD SHX Text
400
AutoCAD SHX Text
20
AutoCAD SHX Text
0.020
AutoCAD SHX Text
22/22, 12" ID
AutoCAD SHX Text
METALAIRE
AutoCAD SHX Text
RETURN AIR GRILLE
AutoCAD SHX Text
22/22
AutoCAD SHX Text
RAG7
AutoCAD SHX Text
24/24
AutoCAD SHX Text
800
AutoCAD SHX Text
23
AutoCAD SHX Text
0.025
AutoCAD SHX Text
22/22, 16" ID
AutoCAD SHX Text
22/22
AutoCAD SHX Text
RAG8
AutoCAD SHX Text
24/24
AutoCAD SHX Text
1000
AutoCAD SHX Text
27
AutoCAD SHX Text
0.035
AutoCAD SHX Text
22/22, 18" ID
AutoCAD SHX Text
COLOR OF ALL DEVICES TO BE SELECTED FROM MANUFACTURER'S STANDARD COLORS. ALL DEVICES TO HAVE TRIM AS MANUFACTURER FOR ADJACENT CONSTRUCTIONS. ALL AIR DISTRIBUTION DEVICES TO HAVE FULL FACE FRAMES. ALL DEVICES IN HARD CEILINGS ARE TO BE PROVIDED WITH TRIM RING FOR PLASTER AND SHEET ROCK CEILINGS TO ALLOW DEVICES TO BE LAY-IN. NO EXPOSED SCREW FASTENERS ARE PERMITTED. PAINT DEVICES TO MATCH ADJACENT FINISHES USING PAINTING CRITERIA IN ARCHITECTURAL DOCUMENTS AS WELL AS ANY REFERENCED STANDARDS.
AutoCAD SHX Text
3-5-7
AutoCAD SHX Text
4-7-10
AutoCAD SHX Text
1-3-9
AutoCAD SHX Text
1-3-9
AutoCAD SHX Text
1-3-11
AutoCAD SHX Text
2-4-13
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
6" ID
AutoCAD SHX Text
8" ID
AutoCAD SHX Text
8" ID
AutoCAD SHX Text
10" ID
AutoCAD SHX Text
12" ID
AutoCAD SHX Text
14" ID
AutoCAD SHX Text
6" ID
AutoCAD SHX Text
8" ID
AutoCAD SHX Text
8" ID
AutoCAD SHX Text
10" ID
AutoCAD SHX Text
12" ID
AutoCAD SHX Text
14" ID
AutoCAD SHX Text
12/12
AutoCAD SHX Text
12/12
AutoCAD SHX Text
24/24
AutoCAD SHX Text
24/24
AutoCAD SHX Text
24/24
AutoCAD SHX Text
24/24
AutoCAD SHX Text
ZONE LOAD CALC INFO
AutoCAD SHX Text
APPROXIMATE AREA (SF)
AutoCAD SHX Text
SIZING METHOD
AutoCAD SHX Text
OUTDOOR SUMMER DB/WB (%%DF)
AutoCAD SHX Text
OUTDOOR WINTER DB/WB (%%DF)
AutoCAD SHX Text
GRAINS WATER DIFFERENCE
AutoCAD SHX Text
TOTAL SENSIBLE GAIN (MBH)
AutoCAD SHX Text
TOTAL LATENT GAIN (MBH)
AutoCAD SHX Text
AHSRAE TRANSFER
AutoCAD SHX Text
29/24
AutoCAD SHX Text
69.6
AutoCAD SHX Text
45.6
AutoCAD SHX Text
9.3
AutoCAD SHX Text
1800
AutoCAD SHX Text
95/78
AutoCAD SHX Text
INDOOR DB (%%DF)
AutoCAD SHX Text
74
AutoCAD SHX Text
60
AutoCAD SHX Text
RELATIVE HUMIDITY (%%%)
AutoCAD SHX Text
54.9
AutoCAD SHX Text
TOTAL COOLING (W/OA)
AutoCAD SHX Text
18.0
AutoCAD SHX Text
TOTAL HEATING (W/OA)
AutoCAD SHX Text
FUNCTION METHOD
AutoCAD SHX Text
GREENHECK
AutoCAD SHX Text
SP-B90
AutoCAD SHX Text
DIRECT DRIVE
AutoCAD SHX Text
75
AutoCAD SHX Text
700
AutoCAD SHX Text
0.06
AutoCAD SHX Text
0.25
AutoCAD SHX Text
49.7 WATTS
AutoCAD SHX Text
120/1
AutoCAD SHX Text
LIGHT SWITCH
AutoCAD SHX Text
1,2,3,4,5
AutoCAD SHX Text
UNISEX RR #102
AutoCAD SHX Text
GREENHECK
AutoCAD SHX Text
SP-B90
AutoCAD SHX Text
DIRECT DRIVE
AutoCAD SHX Text
75
AutoCAD SHX Text
700
AutoCAD SHX Text
0.06
AutoCAD SHX Text
0.25
AutoCAD SHX Text
49.7 WATTS
AutoCAD SHX Text
120/1
AutoCAD SHX Text
LIGHT SWITCH
AutoCAD SHX Text
1,2,3,4,5
AutoCAD SHX Text
VIA BLOCK
AutoCAD SHX Text
LOAD SOFTWARE
AutoCAD SHX Text
JANITOR
AutoCAD SHX Text
GREENHECK
AutoCAD SHX Text
SP-B90
AutoCAD SHX Text
DIRECT DRIVE
AutoCAD SHX Text
75
AutoCAD SHX Text
700
AutoCAD SHX Text
0.06
AutoCAD SHX Text
0.25
AutoCAD SHX Text
49.7 WATTS
AutoCAD SHX Text
120/1
AutoCAD SHX Text
LIGHT SWITCH
AutoCAD SHX Text
1,2,3,4,5
AutoCAD SHX Text
1.
AutoCAD SHX Text
CONNECT NEW 8" EXHAUST AIR DUCTWORK TO EXISTING CAPPEDEXHAUST AIR DUCTWORK ABOVE CEILING LEVEL WITHIN 10' OF THIS LOCATION.
AutoCAD SHX Text
1
AutoCAD SHX Text
COORDINATE ANY REQUIRED ROOFING WORK WITH VILLAGES SELECTED ROOFING CONTRACTOR. ANY ROOF PENETRATIONS THAT MAY BECOME NECESSARY ARE TO BE PERFORMED BY THIS CONTRACTOR AT GENERAL CONTRACTOR'S EXPENSE.
AutoCAD SHX Text
LOCATE RTU CONTROLS IN THIS LOCATION. EXTEND CIRCUITRY AS NEEDED WITHIN TENANT SPACE IF EXISTING CIRCUITRY PROVIDED IN SHELL CONSTRUCTION IS NOT OF ADEQUATE LENGTH. INTERLOCK TWO EXISTING UNITS INTO COMMON THERMOSTAT. INTERFACE NEW REMOTE TEMPERATURE SENSORS (RS) TO THIS THERMOSTAT FOR TEMPERATURE AVERAGING BETWEEN THERMOSTAT AND REMOTE SENSOR READINGS.
AutoCAD SHX Text
2
AutoCAD SHX Text
2.
AutoCAD SHX Text
ROUTE DUCTWORK AS TIGHT TO THE UNDERSIDE OF THE STRUCTURE AS POSSIBLE TO ACCOMMODATE CEILING HEIGHT AND DOWNLIGHT FIXTURE DEPTH. ROUTE SMALLER BRANCH DUCT TAPS UP THROUGH JOIST ELEMENT OPENINGS AT LOCATIONS OF DUCT CROSSES AS MAY BE NEEDED. COORDINATE DUCT ROUTING WITH LIGHT FIXTURE AND CEILING ELEVATION PRIOR TO FABRICATION AND ROUGH-IN OF ANY DUCTWORK.
AutoCAD SHX Text
CONNECT NEW 20/14 SUPPLY AIR DUCTWORK TO EXISTING SUPPLY DUCTWORK DROP WITHIN 10' OF THIS LOCATION. CONVERGE OR EXPAND DUCT AS NEEDED TO MATCH SUPPLY DROP SIZE AT CONNECTION POINT.
AutoCAD SHX Text
3
AutoCAD SHX Text
CONNECT NEW 24/14 RETURN AIR DUCTWORK TO EXISTING RETURN DUCTWORK DROP WITHIN 10' OF THIS LOCATION. CONVERGE OR EXPAND DUCT AS NEEDED TO MATCH RETURN DROP SIZE AT CONNECTION POINT. ELBOW CONNECTION TO BE MADE BELOW DROP. NO PLENUM TYPE FITTINGS PERMITTED UNLESS OTHERWISE SHOWN OR NOTED.
AutoCAD SHX Text
4
AutoCAD SHX Text
SYSTEM TO OPERATE ON OWNER'S TIME OF DAY SCHEDULING OR
AutoCAD SHX Text
MANUAL OVERRIDE.
AutoCAD SHX Text
DURING OCCUPIED PERIODS, SYSTEMS TO RUN AT OCCUPIED
AutoCAD SHX Text
SETPOINT TEMPERATURE WITH BLOWER RUNNING CONTINUOUSLY
AutoCAD SHX Text
AND HEATING/COOLING CYCLES OPERATING ON SPACE
AutoCAD SHX Text
TEMPERATURE DEMAND. DURING UNOCCUPIED PERIODS, SYSTEMS
AutoCAD SHX Text
TO RUN AT UNOCCUPIED SETPOINT TEMPERATURE WITH BLOWER
AutoCAD SHX Text
AND HEATING/COOLING STAGES OPERATING ON SPACE
AutoCAD SHX Text
TEMPERATURE DEMAND.
AutoCAD SHX Text
OUTDOOR AIR DAMPER TO OPEN TO MAXIMUM SETPOINT POSITION
AutoCAD SHX Text
WHEN SYSTEM IS IN OCCUPIED PERIODS.
AutoCAD SHX Text
OUTDOOR AIR DAMPER TO CLOSE WHEN THE SYSTEM BLOWER IS
AutoCAD SHX Text
OFF AND IN UNOCCUPIED PERIODS.
AutoCAD SHX Text
INTERFACE NEW REMOTE TEMPERATURE SENSORS TO EXISTING
AutoCAD SHX Text
THERMOSTAT. AVERAGE REMOTE TEMPERATURE SENSOR READINGS.
AutoCAD SHX Text
REMOVE ALL DEVICES, AIR DISTRIBUTION, DUCTWORK, ETC WITHIN AREA OF WORK AS NECESSARY TO PREPARE FOR ACCOMMODATION OF RENOVATED/NEW SYSTEMS AS SHOWN ON THESE PLANS.
AutoCAD SHX Text
NOTE: EXISTING SYSTEMS CONNECTION POINTS ARE BASED UPON BEST AVAILABLE INFORMATION DURING DESIGN, LIMITED ONLY TO ITEMS THAT ARE CLEARLY VISIBLE PRE-DEMOLITION. CONTRACTOR TO COORDINATE EXACT EXISTING SYSTEMS LOCATIONS AFTER COMMENCEMENT OF DEMOLITION AND PRIOR TO ANY ROUGH-IN WORK. ADVISE ENGINEER IF UTILITY CONNECTION POINTS DIFFER.
AutoCAD SHX Text
NO WORK THIS AREA UNLESS OTHERWISE NOTED

ELECTRICAL ABBREVIATIONS

SYMBOL DESCRIPTION

ELECTRICAL SYMBOL LEGEND

DESCRIPTIONSYMBOL

ELECTRICAL INDEX

SHEET TITLESHEET NUMBER

MOUNTINGDESCRIPTIONSYMBOL

ELECTRICAL DEVICE SCHEDULE

MOUNTINGDESCRIPTIONSYMBOL

COMMUNICATIONS DEVICE SCHEDULE

FIRE ALARM SCHEDULE

DESCRIPTIONSYMBOL MANUFACTURER MODEL NUMBER NOTES

CONTROL PANEL AND ACCESSORIES

INITIATING DEVICES

NOTIFICATION/RESPONSE DEVICES

FIRE ALARM RISER NOT TO SCALE

FIRE ALARM CONDUCTOR SIZES

WIRE TYPEDESCRIPTION WIRE COLOR

MFGTAG DESCRIPTION LAMP(S)MODEL NUMBER NOTEVOLT EQUAL MFG.

LIGHTING FIXTURE SCHEDULE

MTG HEIGHT

AA

A/A1

EX

B

A/A1

ALT

E.001

ELECTRICALSCHEDULES AND

DETAILS

REVISIONS

ISSUE DATE

JOB #

SHEET TITLE

SHEET NO.

05.27.16

1636

A N

EW T

ENA

NT

BU

ILD

OU

T FO

R

THE

VIL

LAG

ES, FL

32

15

9

MPEMILLER PROFESSIONAL

ENGINEERING, LLC

P.O. BOX 4246OCALA, FLORIDA [email protected]

MILLER PROFESSIONAL

CERTIFICATE OF AUTH. #30872

98

0 D

EL M

AR D

RIV

E

CA

RTE

R H

EALT

H

PARTIN ARCHITECTURE

P A

936 E. FT. KING STREETOCALA, FLORIDA 34471

P 352.629.3867 F 352.629.3866

FL LIC# AA26001291

ENGINEERING, LLC

.

...

SPA

NIS

H S

PRIN

GS

AutoCAD SHX Text
MLO
AutoCAD SHX Text
G
AutoCAD SHX Text
EWC
AutoCAD SHX Text
C
AutoCAD SHX Text
CKT
AutoCAD SHX Text
AHU
AutoCAD SHX Text
AFF
AutoCAD SHX Text
MAIN LOUG ONLY
AutoCAD SHX Text
CIRCUIT
AutoCAD SHX Text
CONDUIT
AutoCAD SHX Text
ABOVE FINISH FLOOR
AutoCAD SHX Text
AIR HANDLING UNIT
AutoCAD SHX Text
GROUND FAULT CIRCUIT INTERRUPTER
AutoCAD SHX Text
ELECTRIC WATER COOLER
AutoCAD SHX Text
WEATHERPROOF
AutoCAD SHX Text
UNLESS OTHERWISE NOTED
AutoCAD SHX Text
TELEPHONE TERMINAL BOARD
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
PULL BOX
AutoCAD SHX Text
UNO
AutoCAD SHX Text
WP
AutoCAD SHX Text
PB
AutoCAD SHX Text
TTB
AutoCAD SHX Text
PNL
AutoCAD SHX Text
FLOOR MOUNTED
AutoCAD SHX Text
FL
AutoCAD SHX Text
CEILING
AutoCAD SHX Text
CLG
AutoCAD SHX Text
WEATHERPROOF GCFI
AutoCAD SHX Text
WPG
AutoCAD SHX Text
WALL MOUNTED
AutoCAD SHX Text
W
AutoCAD SHX Text
W
AutoCAD SHX Text
TELEPHONE/FAX/DATA DUPLEX OUTLET
AutoCAD SHX Text
TELEPHONE OUTLET
AutoCAD SHX Text
WALL MOUNTED TELEPHONE OUTLET
AutoCAD SHX Text
TELEPHONE/FAX/DATA/MODEM QUAD OUTLET
AutoCAD SHX Text
CATV OUTLET
AutoCAD SHX Text
TELEPHONE TERMINAL BOARD
AutoCAD SHX Text
4
AutoCAD SHX Text
(X)
AutoCAD SHX Text
S
AutoCAD SHX Text
3
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
2
AutoCAD SHX Text
S
AutoCAD SHX Text
SINGLE RECEPTACLE
AutoCAD SHX Text
DUPLEX WEATHERPROOF GFCI RECEPTACLE
AutoCAD SHX Text
FL
AutoCAD SHX Text
WPG
AutoCAD SHX Text
CEILING MOUNTED RECEPTACLE
AutoCAD SHX Text
DUPLEX RECEPTACLE
AutoCAD SHX Text
DUPLEX GFCI RECEPTACLE
AutoCAD SHX Text
G
AutoCAD SHX Text
CLG
AutoCAD SHX Text
DUPLEX RECEPTACLE
AutoCAD SHX Text
FLOOR MOUNTED DUPLEX RECEPTACLE
AutoCAD SHX Text
DISCONNECT SWITCH
AutoCAD SHX Text
JUNCTION BOX
AutoCAD SHX Text
TWO (2) DUPLEX RECEPTACLES
AutoCAD SHX Text
TWO (2) DUPLEX RECEPTACLES
AutoCAD SHX Text
SINGLE POLE SWITCH
AutoCAD SHX Text
THREE WAY TOGGLE SWITCH
AutoCAD SHX Text
DOUBLE POLE SWITCH
AutoCAD SHX Text
120/208 VOLT PANEL
AutoCAD SHX Text
WALL/CEILING MOUNTED EMERGENCY LIGHT
AutoCAD SHX Text
UNIVERSAL MOUNTED EXIT LIGHT
AutoCAD SHX Text
MOTOR RATED SWITCH
AutoCAD SHX Text
DIMMER SWITCH
AutoCAD SHX Text
SURFACE MOUNTED FLUORESCENT
AutoCAD SHX Text
INCANDESCENT OR COMPACT FLUORESCENT
AutoCAD SHX Text
FOUR WAY TOGGLE SWITCH
AutoCAD SHX Text
CONDUIT RUN EXPOSED ON WALL OR CEILING
AutoCAD SHX Text
CONDUIT CONCEALED IN WALL OR IN CEILING
AutoCAD SHX Text
# OF ARROWS INDICATES HOMERUN CIRCUIT
AutoCAD SHX Text
CONDUITS UNDERGROUND OR IN SLAB
AutoCAD SHX Text
J
AutoCAD SHX Text
CONCEALED IN CEILING
AutoCAD SHX Text
M
AutoCAD SHX Text
S
AutoCAD SHX Text
D
AutoCAD SHX Text
RECESSED DOWN LIGHT
AutoCAD SHX Text
RECESSED FLUORESCENT
AutoCAD SHX Text
INCANDESCENT OR COMPACT FLUORESCENT
AutoCAD SHX Text
WALL MOUNTED DOWN LIGHT
AutoCAD SHX Text
TO DESIGNATED PANEL
AutoCAD SHX Text
ELECTRICAL - SCHEDULES AND DETAILS
AutoCAD SHX Text
E.001
AutoCAD SHX Text
ELECTRICAL FLOOR PLAN - POWER/SYSTEMS
AutoCAD SHX Text
EPS.101
AutoCAD SHX Text
ELECTRICAL FLOOR PLAN - LIGHTING
AutoCAD SHX Text
EL.101
AutoCAD SHX Text
MOUNT 18" AFF TO CENTERLINE OF DEVICE
AutoCAD SHX Text
MOUNT 18" AFF TO CENTERLINE OF DEVICE
AutoCAD SHX Text
MOUNT 18" AFF TO CENTERLINE OF DEVICE
AutoCAD SHX Text
MOUNT 2" ABOVE COUNTER OR PER ARCH PLANS
AutoCAD SHX Text
MOUNT 18" AFF TO CENTERLINE OF DEVICE
AutoCAD SHX Text
MOUNT 18" AFF TO CENTERLINE OF DEVICE
AutoCAD SHX Text
MOUNT 2" ABOVE COUNTER OR PER ARCH PLANS
AutoCAD SHX Text
DUPLEX RECEPTACLE 125 VOLT, 20 AMP, NEMA 5-20R LEVITON #16352
AutoCAD SHX Text
18" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
CEILING SECURE TO STRUCTURE ABOVE
AutoCAD SHX Text
DUPLEX RECEPTACLE 125 VOLT, 20 AMP, NEMA 5-20R LEVITON #16352
AutoCAD SHX Text
CEILING MOUNTED VACANCY SENSOR (PIR/ACTIVE ULTRASONIC) LEVITON #O3C20-MDW; 2000 SF COVERAGE, WHITE HOUSING FURNISH COMPLETE WITH 20A POWER PACKS AND 15A ADD-A-RELAY AS NEEDED OR SHOWN
AutoCAD SHX Text
48" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
CEILING SECURE TO STRUCTURE ABOVE
AutoCAD SHX Text
VACANCY SENSING SWITCH (PIR/ACTIVE ULTRASONIC) LEVITON #OSSMT-GT SET TO 30 MINUTES SEQUENCE OF OPERATION: MANUAL ON, MANUAL/SENSOR OFF
AutoCAD SHX Text
VS
AutoCAD SHX Text
S
AutoCAD SHX Text
CLG
AutoCAD SHX Text
DUPLEX RECEPTACLE 125 VOLT, 20 AMP, NEMA 5-20R LEVITON #16352, SPLIT WIRED FOR SWITCHED CONTROL
AutoCAD SHX Text
18" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
DUPLEX GROUND FAULT RECEPTACLE 125 VOLT, 20 AMP, NEMA 5-20R LEVITON #6899
AutoCAD SHX Text
18" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
G
AutoCAD SHX Text
DUPLEX GROUND FAULT RECEPTACLE 125 VOLT, 20 AMP, NEMA 5-20R LEVITON #6899 W/LEVITON #T5979 IN-USE COVER
AutoCAD SHX Text
26" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
WPG
AutoCAD SHX Text
48" AFF OR 2" ABOVE COUNTER/BACKSPLASH
AutoCAD SHX Text
(2) DUPLEX RECEPTACLES 125 VOLT, 20 AMP, NEMA 5-20R (2) LEVITON #16352
AutoCAD SHX Text
18" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
DUPLEX RECEPTACLE 125 VOLT, 20 AMP, NEMA 5-20R LEVITON #16352
AutoCAD SHX Text
(2) DUPLEX RECEPTACLES 125 VOLT, 20 AMP, NEMA 5-20R (2) LEVITON #16352
AutoCAD SHX Text
48" AFF OR 2" ABOVE COUNTER/BACKSPLASH
AutoCAD SHX Text
FLOOR BOX STEEL CITY 667SC SERIES WITH FEED THROUGH CABLE IN-USE COVER PROVIDE RECEPTACLE COUNT AS SHOWN ON FLOOR PLAN. PROVIDE CONDUIT COUNT AS SHOWN IN DEVICE SCHEDULES
AutoCAD SHX Text
FL
AutoCAD SHX Text
FL
AutoCAD SHX Text
FL
AutoCAD SHX Text
FL
AutoCAD SHX Text
FL
AutoCAD SHX Text
FLUSH SECURE TO STRUCTURE
AutoCAD SHX Text
TWO GANG WALL BOX WITH (3) 0.75" SYSTEMS CONDUITS TO CEILING (1) POWER RECEPTACLE, (1) 4-PORT MULTI-INSERT COVER, LEVITON #41644 (1) CAT6 JACK, LEVITON #61110 (1) F-CONNECTOR, LEVITON #40831 (2) BLANKS, LEVITON #41084 ALL DEVICES UNDER COMMON FACEPLATE
AutoCAD SHX Text
84" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
48" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
TOGGLE SWITCH SINGLE POLE/SINGLE THROW, 20 AMP LEVITON #5621-2
AutoCAD SHX Text
S
AutoCAD SHX Text
48" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
TOGGLE SWITCH DOUBLE POLE/SINGLE THROW, 20 AMP LEVITON #5622-2
AutoCAD SHX Text
S
AutoCAD SHX Text
2
AutoCAD SHX Text
48" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
TOGGLE SWITCH THREE WAY, 20 AMP LEVITON #5623-2
AutoCAD SHX Text
S
AutoCAD SHX Text
3
AutoCAD SHX Text
48" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
TOGGLE SWITCH THREE WAY, 20 AMP LEVITON #5624-2
AutoCAD SHX Text
S
AutoCAD SHX Text
4
AutoCAD SHX Text
48" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
VACANCY SENSING MULTI-WAY SWITCH (PIR/ACTIVE ULTRASONIC) LEVITON #OSSMT SERIES, SET TO 30 MINUTES SEQUENCE OF OPERATION: MANUAL ON, MANUAL/SENSOR OFF
AutoCAD SHX Text
S
AutoCAD SHX Text
3
AutoCAD SHX Text
48" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
VACANCY SENSING DUAL RELAY SWITCH (PIR/ACTIVE ULTRASONIC) LEVITON #OSSMT SERIES, 10 MIN. DELAY OFF ON FAN CIRCUIT SEQUENCE OF OPERATION: MANUAL ON, MANUAL/SENSOR OFF
AutoCAD SHX Text
S
AutoCAD SHX Text
F
AutoCAD SHX Text
48" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
DIMMER PRESET WITH LED LOCATOR, 1000 WATT MINIMUM LEVITON #ILLUMATECH
AutoCAD SHX Text
D
AutoCAD SHX Text
VS
AutoCAD SHX Text
VS
AutoCAD SHX Text
48" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
MOTOR RATED SWITCH SQUARE D CLASS 2510 WITH ENCLOSURE
AutoCAD SHX Text
S
AutoCAD SHX Text
M
AutoCAD SHX Text
MEASUREMENTS ARE TO THE CENTERLINE OF THE DEVICE. DEVICES ARE TO BE MOUNTED IN VERTICAL POSITION UNLESS OTHERWISE NOTED. RECEPTACLES MOUNTED VERTICALLY TO BE MOUNTED WITH GROUND CONTACT IN THE UP POSITION. GFCI RECEPTACLE CIRCUITS MAY BE PROTECTED BY SINGLE GFCI RECEPTACLE AT BEGINNING OF CIRCUIT. RECEPTACLES SERVING ELECTRIC WATER COOLERS TO BE FURNISHED WITH GFCI PROTECTION. DEVICE AND DEVICE PLATE COLORS ARE TO BE WHITE AS SELECTED BY TENANT.
AutoCAD SHX Text
DUPLEX DATA OUTLET BLANK TELCO JUNCTION BOX. STUB (1) 3/4"C. W/90° BENDS AND BUSHINGS INTO ACCESSIBLE CEILING.PROVIDE PULL STRING.
AutoCAD SHX Text
QUAD DATA OUTLET BLANK TELCO JUNCTION BOX. STUB (1) 3/4"C. W/90° BENDS AND BUSHINGS INTO ACCESSIBLE CEILING. PROVIDEPULL STRING AND 4-11/16" BACK BOX.
AutoCAD SHX Text
18" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
18" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
18" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
SIMPLEX DATA OUTLET BLANK TELCO JUNCTION BOX. STUB (1) 3/4"C. W/90° BENDS AND BUSHINGS INTO ACCESSIBLE CEILING.PROVIDE PULL STRING.
AutoCAD SHX Text
CATV OUTLET. PROVIDE 3/4" C. TO TTB. PROVIDE PULL STRING.
AutoCAD SHX Text
REFER TO DRAWINGS
AutoCAD SHX Text
'TTB'
AutoCAD SHX Text
TELEPHONE TERMINAL BOARD 4'x8x0.75" EXTERIOR PLYWOOD WITH 2 COATS OF GRAY FIRE RETARDANT PAINT. PROVIDE #6 CU GROUND TO MAIN ELECTRICAL SERVICE GROUND W/6' SLACK AT BOARD.
AutoCAD SHX Text
18" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
MEASUREMENTS ARE TO CENTER LINE OF DEVICE. CABLE ASSOCIATED WITH CATV SHALL BE #F6SSVV 75 OHM DROP CABLECATV (ETL) AS MANUFACTURED BY COMMSCOPE OR EQUAL. PROVIDE SURGE SUPPRESSION ON ALL LOW VOLTAGE CONDUCTORS ENTERING OR EXITING THE BUILDING, INCLUDING BUT NOT LIMITED TO, VOICE/DATA/CATV/CCTV. DEVICE AND DEVICE PLATE COLORS ARE TO BE WHITE AS SELECTED BY TENANT.
AutoCAD SHX Text
48" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
DIMMER 0-10V LOW VOLTAGE MATCHED TO CONTROL LIGHT FIXTURES ASSOCIATED WITH RESPECTIVE CONTROL DEVICE
AutoCAD SHX Text
D
AutoCAD SHX Text
L
AutoCAD SHX Text
-
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text
FIRE ALARM CONTROL PANEL
AutoCAD SHX Text
FACP
AutoCAD SHX Text
.
AutoCAD SHX Text
-
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text
FIRE ALARM ANNUNCIATOR PANEL
AutoCAD SHX Text
FAAP
AutoCAD SHX Text
.
AutoCAD SHX Text
DOUBLE ACTION UL LISTED FIRE ALARM PULL STATION
AutoCAD SHX Text
.
AutoCAD SHX Text
DUCT SMOKE DETECTOR HOUSING WITH PHOTOELECTRIC DETECTOR AND SAMPLING TUBES (300-4000 FPM VELOCITY). PROVIDE RELAY FOR AHU BLOWER SHUTDOWN
AutoCAD SHX Text
.
AutoCAD SHX Text
STROBE W/LOW PROFILE WHITE HOUSING W/CONCEALED MOUNTING SCREWS W/MINIMUM 75 cd RATING (80-96" AFF)
AutoCAD SHX Text
.
AutoCAD SHX Text
F
AutoCAD SHX Text
75 cd
AutoCAD SHX Text
COMBINATION HORN/STROBE WITH WHITE HOUSING, FIELD SELECTABLE CANDELA SETTING 75 cd RATING CEILING MOUNTED
AutoCAD SHX Text
.
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
75 cd
AutoCAD SHX Text
CLG
AutoCAD SHX Text
NOTE: SEE FLOOR PLANS FOR SPECIFIC DEVICE QUANTITIES AND LOCATIONS.
AutoCAD SHX Text
FACP
AutoCAD SHX Text
FAAP
AutoCAD SHX Text
FASU
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
...
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
...
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
...
AutoCAD SHX Text
...
AutoCAD SHX Text
...
AutoCAD SHX Text
...
AutoCAD SHX Text
AUTO DIALER TO TELEPHONE LINE
AutoCAD SHX Text
TO 120V POWER CIRCUIT
AutoCAD SHX Text
CONTRACTOR TO PROVIDE ANY AND ALL SHOP DRAWINGS, WORKING DRAWINGS, AND DETAILS AS REQUIRED BY LOCAL, STATE, AND NATIONAL AUTHORITIES HAVING JURISDICTION FOR PERFORMANCE OF THE WORK OF THIS FIRE ALARM SYSTEM AS REQUIRED FOR ANY AND ALL SPECIAL PERMITTING. CONTRACTOR TO SUBMIT THESE DRAWINGS AND ALL SYSTEM COMPONENT CUTSHEETS AND DATA FOR ENGINEER'S REVIEW AND COMMENT.
AutoCAD SHX Text
FIRE ALARM SYSTEM PLANS INCLUDED HEREIN ARE DIAGRAMMATIC. CONTRACTOR TO PROVIDE COMPLETE AND OPERATING FIRE ALARM SYSTEM IN MANNER CONSISTENT WITH THESE DOCUMENTS AND NFPA 72 NATIONAL FIRE ALARM CODE.
AutoCAD SHX Text
1.
AutoCAD SHX Text
2.
AutoCAD SHX Text
18/2
AutoCAD SHX Text
ADDRESSIBLE CIRCUIT
AutoCAD SHX Text
RED JACKET BLACK AND RED
AutoCAD SHX Text
14/2
AutoCAD SHX Text
24V DC POWER
AutoCAD SHX Text
WHITE AND BLACK
AutoCAD SHX Text
14/2
AutoCAD SHX Text
STROBE SIGNAL
AutoCAD SHX Text
RED AND BLUE
AutoCAD SHX Text
14/2
AutoCAD SHX Text
MISC. UNDERGROUND
AutoCAD SHX Text
WHITE AND BLACK
AutoCAD SHX Text
FURNISH IN ACCORDANCE WITH THIS SCHEDULE UNLESS OTHERWISE NOTED. ALL WIRES ARE TO BE COPPER, FPL, OR FPLR FOR RISERS UNLESS OTHERWISE NOTED. ALL INITIATING AND SIGNAL CIRCUITS TO BE INSTALLED IN 0.5" METAL CONDUIT.
AutoCAD SHX Text
WORK OF THIS SYSTEM TO BE PERFORMED BY OWNER'S DESIGNATED FIRE ALARM SERVICE CONTRACTOR.
AutoCAD SHX Text
3.
AutoCAD SHX Text
MATCH EXISTING SYSTEM TO GREATEST EXTENT POSSIBLE
AutoCAD SHX Text
MATCH EXISTING SYSTEM TO GREATEST EXTENT POSSIBLE
AutoCAD SHX Text
MATCH EXISTING SYSTEM TO GREATEST EXTENT POSSIBLE
AutoCAD SHX Text
MATCH EXISTING SYSTEM TO GREATEST EXTENT POSSIBLE
AutoCAD SHX Text
...
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
...
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
...
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
...
AutoCAD SHX Text
INTERCEPT EXISTING LOCAL INITIATION AND NOTIFICATION CIRCUITS AND EXTEND TO NEW APPLIANCES. VERIFY AVAILABLE CIRCUIT AND BATTERY CAPACITY PRIOR TO INTERCONNECTION. PROVIDE NEW INITIATION AND NOTIFICATION CIRCUITRY IF EXISTING CIRCUIT IS NOT ADEQUATE.
AutoCAD SHX Text
(NEW)
AutoCAD SHX Text
(NEW)
AutoCAD SHX Text
(NEW)
AutoCAD SHX Text
(NEW)
AutoCAD SHX Text
CLG
AutoCAD SHX Text
CLG
AutoCAD SHX Text
VERIFY ALL REQUIREMENTS WITH LOCAL FIRE MARSHAL PRIOR TO BID. ISSUANCE OF BID INDICATES THIS COORDINATION.
AutoCAD SHX Text
4.
AutoCAD SHX Text
CEILING MOUNTED DEVICES IN ACOUSTIC TILE CEILINGS TO BE MOUNTED IN CENTER OF TILE.
AutoCAD SHX Text
5.
AutoCAD SHX Text
CEILING MOUNTED OCCUPANCY SENSOR (PIR/ACTIVE ULTRASONIC) LEVITON #OSC20-MOW; 2000 SF COVERAGE, WHITE HOUSING FURNISH COMPLETE WITH 20A POWER PACKS AND 15A ADD-A-RELAY AS NEEDED OR SHOWN
AutoCAD SHX Text
CEILING SECURE TO STRUCTURE ABOVE
AutoCAD SHX Text
OS
AutoCAD SHX Text
ELECTRICAL - NOTES
AutoCAD SHX Text
E.002
AutoCAD SHX Text
FURNISHED
AutoCAD SHX Text
120
AutoCAD SHX Text
-
AutoCAD SHX Text
EXIT LIGHT SINGLE FACE LED UNIVERSAL MOUNT/ARROWS THERMOPLASTIC, WHITE, RED LETTERS SELF DIAGNOSTICS
AutoCAD SHX Text
CHLORIDE
AutoCAD SHX Text
CXXL3RW
AutoCAD SHX Text
LIGHTALARMS
AutoCAD SHX Text
DUALITE
AutoCAD SHX Text
MCPHILBEN
AutoCAD SHX Text
COOPER
AutoCAD SHX Text
120/277
AutoCAD SHX Text
-
AutoCAD SHX Text
2-LAMP 2x4 3" DEEP 12 CELL PARABOLIC LOW IRIDESCENT SEMI-SPECULAR LOUVER, MULTI-VOLT PROGRAMMED START BALLAST A1: 1400 LUMEN EMERGENCY BALLAST
AutoCAD SHX Text
DAYBRITE
AutoCAD SHX Text
WILLIAMS
AutoCAD SHX Text
COOPER
AutoCAD SHX Text
COLUMBIA
AutoCAD SHX Text
A: 2LP3GS232-26AL-UNV
AutoCAD SHX Text
(2) 32W
AutoCAD SHX Text
T8
AutoCAD SHX Text
CEILING MOUNTED
AutoCAD SHX Text
120
AutoCAD SHX Text
-
AutoCAD SHX Text
(3) 100W A-LAMP
AutoCAD SHX Text
REPLACEMENT
AutoCAD SHX Text
WALL MOUNTED
AutoCAD SHX Text
CREE
AutoCAD SHX Text
MED BASE, 2700K
AutoCAD SHX Text
COORDINATE WITH
AutoCAD SHX Text
ARCH ELEVATIONS
AutoCAD SHX Text
-
AutoCAD SHX Text
SELECTED BY ARCHITECT OR OWNER PURCHASED AND INSTALLED BY CONTRACTOR $350 ALLOWANCE FOR PURCHASE PER FIXTURE
AutoCAD SHX Text
WALL MOUNTED OVER THE MIRROR LIGHT LED RETROFIT LAMP (CONFIRM EXACT LAMP REQUIREMENTS WITH FIXTURE SELECTED)
AutoCAD SHX Text
A1: 2LP3GS232-26AL-UNV-E5
AutoCAD SHX Text
120/277
AutoCAD SHX Text
1
AutoCAD SHX Text
2x4 LED TROFFER WITH ROOM SIDE HEAT SINK, 5400 LUMEN, 3500K A1: EMERGENCY BATTERY
AutoCAD SHX Text
DAYBRITE
AutoCAD SHX Text
WILLIAMS
AutoCAD SHX Text
COOPER
AutoCAD SHX Text
COLUMBIA
AutoCAD SHX Text
A: 2EVG54L835-4-D-UNV
AutoCAD SHX Text
55W
AutoCAD SHX Text
LED
AutoCAD SHX Text
CEILING MOUNTED
AutoCAD SHX Text
A1: 2EVG54L835-4-D-UNV-
AutoCAD SHX Text
NOTES:
AutoCAD SHX Text
IN LIEU OF THE SPECIFIED TYPE 'A' AND 'A1' FIXTURE IN THE LIGHTING FIXTURE SCHEDULE, PROVIDE ALTERNATE PRICING FOR SUBSTITUTION OF FIXTURE 'A-ALT' AND 'A1-ALT', RESPECTIVELY. AS PART OF ALTERNATE PRICING, INCLUDE REPLACEMENT OF STANDARD SWITCHES SHOWN ON SHEET EL.101 WITH LOW VOLTAGE SWITCH MATCHED TO FIXTURE 'A-ALT' IF NEEDED FOR COMPATIBILITY.
AutoCAD SHX Text
1.
AutoCAD SHX Text
EMLED
AutoCAD SHX Text
WALL MOUNTED
AutoCAD SHX Text
CEILING MOUNTED
AutoCAD SHX Text
CREE
AutoCAD SHX Text
120
AutoCAD SHX Text
-
AutoCAD SHX Text
6x48 LED SURFACE MOUNT LINEAR PRISMATIC ACRYLIC LENS, 4000 LUMENS 3500K
AutoCAD SHX Text
DAYBRITE
AutoCAD SHX Text
OWL440L835-UNV
AutoCAD SHX Text
53W
AutoCAD SHX Text
LED
AutoCAD SHX Text
WALL MOUNTED
AutoCAD SHX Text
CREE
AutoCAD SHX Text
COOPER
AutoCAD SHX Text
COLUMBIA
AutoCAD SHX Text
CEILING MOUNTED

ELECTRICAL NOTES

GENERAL:

SUBMITTALS:

COORDINATION OF WORK:

PRODUCTS:

TELEPHONE, SIGNAL, AND COMMUNICATION SYSTEMS:

WARRANTY:

E.002

ELECTRICALNOTES

REVISIONS

ISSUE DATE

JOB #

SHEET TITLE

SHEET NO.

05.27.16

1636

A N

EW T

ENA

NT

BU

ILD

OU

T FO

R

THE

VIL

LAG

ES, FL

32

15

9

MPEMILLER PROFESSIONAL

ENGINEERING, LLC

P.O. BOX 4246OCALA, FLORIDA [email protected]

MILLER PROFESSIONAL

CERTIFICATE OF AUTH. #30872

98

0 D

EL M

AR D

RIV

E

CA

RTE

R H

EALT

H

PARTIN ARCHITECTURE

P A

936 E. FT. KING STREETOCALA, FLORIDA 34471

P 352.629.3867 F 352.629.3866

FL LIC# AA26001291

ENGINEERING, LLC

.

...

SPA

NIS

H S

PRIN

GS

AutoCAD SHX Text
ELECTRICAL CONTRACTOR SHALL COMPLETELY FAMILIARIZE HIMSELF/HERSELF WITH ALL CONDITIONS AFFECTING HIS/HER
AutoCAD SHX Text
WORK INCLUDING VISIT TO THE SITE BEFORE PREPARING PROPOSAL. ALL WORK IS TO BE PERFORMED IN ACCORDANCE
AutoCAD SHX Text
WITH ALL APPLICABLE CODES AND STANDARDS FROM ALL AUTHORITIES HAVING JURISDICTION OVER THE WORK. WHERE
AutoCAD SHX Text
CONFLICT EXISTS BETWEEN THE APPLICABLE CODES AND STANDARDS OR THE PLANS AND SPECIFICATIONS, THE MOST
AutoCAD SHX Text
STRINGENT AS DETERMINED BY THE ENGINEER SHALL APPLY. CONTRACTOR SHALL NOTIFY ENGINEER OF CONFLICTING
AutoCAD SHX Text
CONDITIONS AFFECTING HIS/HER WORK AND ADVISE ENGINEER FOR CLARIFICATION. LOCAL CODES IN EFFECT FOR THIS
AutoCAD SHX Text
PROJECT INCLUDE BUT ARE NOT LIMITED TO THE FOLLOWING:
AutoCAD SHX Text
2014 FLORIDA BUILDING CODE
AutoCAD SHX Text
2014 FLORIDA BUILDING CODE - MECHANICAL
AutoCAD SHX Text
2014 FLORIDA BUILDING CODE - PLUMBING
AutoCAD SHX Text
2014 FLORIDA BUILDING CODE - GAS
AutoCAD SHX Text
2011 NFPA 70 "NATIONAL ELECTRIC CODE"
AutoCAD SHX Text
NFPA 90A "INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS"
AutoCAD SHX Text
NFPA 90B "INSTALLATION OF WARM AIR HEATING AND AIR CONDITIONING SYSTEMS"
AutoCAD SHX Text
SUBMISSION OF BID INDICATES CONTRACTOR'S ACKNOWLEDGEMENT THAT THEY ARE PROVIDING TO THE OWNER A
AutoCAD SHX Text
COMPLETE AND OPERATING SYSTEM. ANY CONTRACTOR UNCERTAINTIES OR MISSING INFORMATION CONCERNS TO BE
AutoCAD SHX Text
SUBMITTED IN WRITING PRIOR TO SUBMISSION OF BID SO THAT ENGINEER MAY PROVIDE PROPER CLARIFICATION.
AutoCAD SHX Text
PROVIDE ADEQUATE NUMBER OF SKILLED WORKMEN WHO ARE THOROUGHLY TRAINED AND EXPERIENCED IN THE
AutoCAD SHX Text
NECESSARY CRAFTS AND WHO ARE COMPLETELY FAMILIAR WITH THE SPECIFIED REQUIREMENTS AND THE METHODS
AutoCAD SHX Text
NEEDED FOR PROPER PERFORMANCE OF THE WORK.
AutoCAD SHX Text
ALL WORK IS TO BE PERFORMED IN ACCORDANCE WITH NECA "STANDARD OF INSTALLATION" AND IN ACCORDANCE WITH
AutoCAD SHX Text
THE MANUFACTURER'S WRITTEN INSTRUCTIONS AND RECOMMENDATIONS.
AutoCAD SHX Text
CONTRACTOR TO PREPARE SUBMITTALS AND SHOP DRAWINGS FOR ALL ELECTRICAL WORK AS REQUIRED BY THE
AutoCAD SHX Text
CONSTRUCTION DOCUMENTS FOR ENGINEER'S REVIEW NOT MORE THAN 35 CALENDAR DAYS AFTER CONTRACTOR HAS
AutoCAD SHX Text
RECEIVED THE OWNER'S NOTICE TO PROCEED.
AutoCAD SHX Text
UPON COMPLETION OF WORK, CONTRACTOR TO PROVIDE TWO COPIES OF AN OPERATION AND MAINTENANCE MANUAL.
AutoCAD SHX Text
INCLUDE IN EACH MANUAL A COPY OF THE PROJECT RECORD DOCUMENTS.
AutoCAD SHX Text
ENGINEER'S DRAWINGS AND CONSTRUCTION DOCUMENTS ARE DIAGRAMMATIC. CONTRACTOR OF THIS WORK TO
AutoCAD SHX Text
COORDINATE WITH ALL WORK OF CONTRACTORS OF ALL TRADES AND GENERAL CONTRACTOR. CONTRACTORS TO FIELD
AutoCAD SHX Text
MEASURE PRIOR TO FABRICATION OF ANY WORK. CONTRACTOR OF WORK OF THIS TRADE TO COMMUNICATE WITH
AutoCAD SHX Text
GENERAL CONTRACTOR AND CONTRACTORS OF OTHER TRADES AND PREPARE DRAWINGS, SKETCHES, AND PROVIDE
AutoCAD SHX Text
INFORMATION AS NEEDED TO COMMUNICATE WITH OTHER TRADES FOR CONSTRUCTION OF COMPLETE AND OPERATING
AutoCAD SHX Text
SYSTEM WITHOUT ADDITIONAL COST TO OWNER. PRIOR TO BEGINNING WORK OF THIS TRADE, CONTRACTOR OF THIS
AutoCAD SHX Text
TRADE TO CONDUCT COORDINATION MEETING WITH OTHER AFFECTED CONTRACTORS OF OTHER TRADES AND GENERAL
AutoCAD SHX Text
CONTRACTOR FOR PURPOSES OF COORDINATION. CONTRACTOR'S FAILURES TO COORDINATE WILL NOT BE CAUSE FOR
AutoCAD SHX Text
RECOVERY OF ADDITIONAL COMPENSATION FOR CORRECTION OR MODIFICATION WORK WHICH IN THE SOLE OPINION OF
AutoCAD SHX Text
THE ENGINEER IS NOT WELL COORDINATED.
AutoCAD SHX Text
LAYOUT THE ELECTRICAL SYSTEM IN CAREFUL COORDINATION WITH THE DRAWINGS, DETERMINING PROPER ELEVATIONS FOR
AutoCAD SHX Text
ALL COMPONENTS OF THE SYSTEM USING ONLY THE MINIMUM NUMBER OF BENDS TO PRODUCE A SATISFACTORILY
AutoCAD SHX Text
FUNCTIONING SYSTEM. FOLLOW THE GENERAL LAYOUT SHOWN ON THE DRAWINGS IN ALL CASES EXCEPT WHERE OTHER
AutoCAD SHX Text
WORK MAY INTERFERE.
AutoCAD SHX Text
IN ADDITION TO PROVIDING TEMPORARY POWER AS NEEDED FOR CONSTRUCTION PROVIDE AND PAY THE COSTS FOR
AutoCAD SHX Text
INSTALLING PERMANENT POWER, ELECTRICAL METERS, AND METERING ACCESSORIES AS REQUIRED. CONTRACTOR TO
AutoCAD SHX Text
COORDINATE AS NEEDED WITH THE LOCAL UTILITY TO INCLUDE ALL COSTS ASSOCIATED WITH THE INSTALLATION OF
AutoCAD SHX Text
PERMANENT ELECTRICAL SERVICES AS SHOWN ON THE DRAWINGS. WHEN PERMANENT METERING IS IN PLACE AND
AutoCAD SHX Text
PERMANENTLY CONNECTED, THE OWNER WILL PAY THE COSTS FOR ELECTRICAL POWER CHARGED AGAINST THE METER OR
AutoCAD SHX Text
METERS.
AutoCAD SHX Text
ALL MATERIALS TO BE OF DOMESTIC MANUFACTURER UNLESS OTHERWISE DIRECTED.
AutoCAD SHX Text
WHERE UNDERWRITER'S LABORATORY, INC. (UL) HAVE ESTABLISHED STANDARDS FOR SUCH MATERIALS, PROVIDE ONLY
AutoCAD SHX Text
MATERIALS BEARING THE UL LABEL.
AutoCAD SHX Text
CONDUIT:
AutoCAD SHX Text
ALL CONDUCTORS TO BE INSTALLED IN EMT, IMC, OR RMC IN LOCATIONS AS DESCRIBED IN THE CONSTRUCTION
AutoCAD SHX Text
DOCUMENTS. METALLIC CONDUIT IS TO PROVIDE A REDUNDANT GROUNDING PATH.
AutoCAD SHX Text
BURIED IN EARTH UNDER SLAB LOCATIONS TO BE INTERMEDIATE CONDUIT WITH RIGID METALLIC FITTINGS.
AutoCAD SHX Text
SWEEPS FROM BELOW EARTH PENETRATING SLAB INTO EXPOSED LOCATIONS TO BE RIGID METAL CONDUIT OR BETTER
AutoCAD SHX Text
COATED WITH TWO APPLICATIONS OF HEAVY FIBRATED COAL TAR MASTIC.
AutoCAD SHX Text
OUTDOOR LOCATIONS ABOVE GRADE, SLAB ABOVE GRADE, WET, OR DAMP LOCATIONS TO BE INTERMEDIATE METAL
AutoCAD SHX Text
CONDUIT.
AutoCAD SHX Text
DRY CONCEALED OR EXPOSED LOCATIONS TO BE ELECTRICAL METAL TUBING WITH COMPRESSION OR SCREW FITTINGS.
AutoCAD SHX Text
DRY LOCATION BRANCH CIRCUITRY FINAL CONNECTIONS AT LIGHT FIXTURES, MOTORIZED EQUIPMENT, AND OTHER SPECIFIC
AutoCAD SHX Text
VIBRATING EQUIPMENT TO BE FLEXIBLE METAL CONDUIT, LIMITED TO LENGTHS OF 6' MAXIMUM AND USED FOR AND ONLY
AutoCAD SHX Text
FOR FINAL CONNECTIONS. FLEXIBLE METAL CONDUIT TO BE OF INTERLOCKED STEEL CONSTRUCTION.
AutoCAD SHX Text
WET LOCATION BRANCH CIRCUITRY FINAL CONNECTIONS AT LIGHT FIXTURES, MOTORIZED EQUIPMENT, AND OTHER SPECIFIC
AutoCAD SHX Text
VIBRATING EQUIPMENT TO BE LIGHT LIQUID TIGHT FLEXIBLE METAL CONDUIT. LIQUID TIGHT FLEXIBLE METAL CONDUIT TO
AutoCAD SHX Text
BE OF STEEL CONSTRUCTION WITH PVC JACKET AND IS TO ONLY BE USED IN DAMP, WET, AND OUTDOOR LOCATIONS
AutoCAD SHX Text
AND LISTED AS SUITABLE GROUNDING CONDUCTOR WITH SMIILARLY LISTED FITTINGS.
AutoCAD SHX Text
FITTINGS AND CONDUIT BODIES TO BE OF SAME MATERIAL AS ADJACENT CONDUIT.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
CONDUIT TO BE ROUTED PARALLEL AND PERPENDICULAR TO WALLS EXCEPT UNDER SLAB WHERE ROUTING IS TO BE
AutoCAD SHX Text
FROM POINT TO POINT.
AutoCAD SHX Text
WHERE CONDUIT IS EXPOSED, ROUTE PARALLEL TO OR AT RIGHT ANGLE WITH LINES OF THE BUILDING. MAKE BENDS
AutoCAD SHX Text
WITH STANDARD CONDUIT ELBOWS OR CONDUIT BENT TO NOT LESS THAN THE SAME RADIUS. MAKE BENDS FREE FROM
AutoCAD SHX Text
DENTS AND FLATTENING.
AutoCAD SHX Text
SECURELY AND RIGIDLY SUPPORT CONDUITS THROUGHOUT THE WORK.
AutoCAD SHX Text
PROVIDE NECESSARY SLEEVES AND CHASES WHERE CONDUITS PASS THROUGH FLOORS AND WALLS, AND PROVIDE OTHER
AutoCAD SHX Text
NECESSARY OPENINGS AND SPACE, ARRANGING FOR IN PROPER TIME TO PREVENT UNNECESSARY CUTTING IN
AutoCAD SHX Text
CONNECTION WITH THE WORK. PERFORM CUTTING AND PATCHING IN ACCORDANCE WITH THE PROVISIONS FOR THE
AutoCAD SHX Text
ORIGINAL WORK.
AutoCAD SHX Text
WHERE CONDUITS PIERCE THE ROOF, PROVIDE 24 GAUGE GALVANIZED IRON ROOF JACKS AND FLASHING COLLAR BRAZED
AutoCAD SHX Text
ONTO THE CONDUITS AND COVERING THE TOP OF THE ROOF JACKS.
AutoCAD SHX Text
INSTALL NO MORE THAN THE EQUIVALENT OF THREE (3) 90 DEGREE BENDS BETWEEN BOXES IN CONDUIT RUNS.
AutoCAD SHX Text
ALL EXISTING CONDUIT INSTALLED THROUGH TENANTS SPACE TO BE PROVIDED WITH UL FIRE RATED ASSEMBLY AS
AutoCAD SHX Text
REQUIRED BY AUTHORITY HAVING JURISDICTION (AHJ).
AutoCAD SHX Text
CONDUCTORS:
AutoCAD SHX Text
ALL CONDUCTORS ARE TO BE COPPER UNLESS SPECIFICALLY NOTED OTHERWISE.
AutoCAD SHX Text
ALL CONDUCTOR INSULATION TO BE 600 VOLT RATED THWN/THHN UNLESS OTHERWISE SPECIFICALLY NOTED.
AutoCAD SHX Text
MINIMUM CONDUCTOR SIZE IS TO BE NOT LESS THAN #12 AWG.
AutoCAD SHX Text
FOR CONDUCTORS #8 AND SMALLER, PROVIDE SOLID WIRE.
AutoCAD SHX Text
FOR CONDUCTORS LARGER THAN #8, PROVIDE STRANDED WIRE.
AutoCAD SHX Text
ALL 20 AMP CIRCUITS GREATER THAN 75' FROM FEEDING PANELBOARD TO FIRST DEVICE IN CIRCUIT TO BE NOT LESS
AutoCAD SHX Text
THAN #10 AWG WITH #10 GROUND.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
CONDUCTORS TO BE PULLED INTO RACEWAY AT THE SAME TIME USING SUITABLE WIRE PULLING LUBRICANT FOR WIRE
AutoCAD SHX Text
SIZES GREATER THAN #4 AWG. CLEAN CONDUCTOR SURFACES BEFORE INSTALLING LUGS AND CONNECTORS AND MAKE
AutoCAD SHX Text
TERMINATION TO CARRY FULL CURRENT RATING OF CIRCUIT WITH NO PERCEPTIBLE TEMPERATURE RISE.
AutoCAD SHX Text
PROVIDE CODE SIZE CONDUIT FOR NUMBER AND SIZE WIRES SHOWN OR REQUIRED WITHOUT WIRE AMPACITY DERATING,
AutoCAD SHX Text
UNLESS A LARGER SIZE CONDUIT AND/OR CONDUCTOR IS SHOWN ON THE DRAWINGS.
AutoCAD SHX Text
USE IDENTIFIED (WHITE) NEUTRALS AND COLOR CODED PHASE WIRES FOR ALL BRANCH CIRCUIT WIRING.
AutoCAD SHX Text
PROVIDE SEPARATE INSULATED EQUIPMENT GROUNDING CONDUCTOR WITHIN EACH FEEDER AND BRANCH CIRCUIT RACEWAY
AutoCAD SHX Text
TERMINATED ON EACH END WITH A SUITABLE LUG, BUS, OR BUSHING.
AutoCAD SHX Text
MAKE SPLICES ELECTRICALLY AND MECHANICALLY SECURE WITH PRESSURE TYPE CONNECTORS, OR BY SOLDERING.
AutoCAD SHX Text
TAPE ALL JOINTS WITH RUBBER TAPE 1.5 TIMES THE THICKNESS OF THE CONDUCTOR INSULATION, THEN COVER WITH
AutoCAD SHX Text
FRICTION TAPE OR VINYL-PLASTIC ELECTRICAL TAPE.
AutoCAD SHX Text
THE DRAWINGS INDICATE THE GENERAL DIRECTION OF HOME RUNS. CONTINUE ALL SUCH HOME RUNS TO THE PANEL
AutoCAD SHX Text
AS THOUGH THE ROUTES WERE SHOWN COMPLETELY.
AutoCAD SHX Text
CLEAN CONDUCTOR SURFACES BEFORE INSTALLING LUGS AND CONNECTORS.
AutoCAD SHX Text
PANELBOARDS:
AutoCAD SHX Text
EQUIPMENT TO BE AS NOTED ON THE DRAWINGS WHERE MANUFACTURED BY SQUARE D, SIEMENS, OR CUTLER HAMMER.
AutoCAD SHX Text
PROVIDE AS SHOWN ON THE DRAWING, WITH CIRCUIT BREAKERS AND SIMILAR COMPONENTS AS SHOWN ON THE
AutoCAD SHX Text
DRAWINGS OR REQUIRED FOR PROPER COMPLETION.
AutoCAD SHX Text
PANELBOARDS TO HAVE COPPER BUS.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
INSTALL PANELBOARDS PLUMB AND LEVEL.
AutoCAD SHX Text
PROVIDE FIVE SPARE 1" CONDUITS FROM EACH RECESSED PANELBOARD TO AN ACCESSIBLE LOCATION ABOVE THE
AutoCAD SHX Text
CEILING AND LABEL AS SPARE.
AutoCAD SHX Text
ALL MULTI-WIRE BRANCH CIRCUIT DISCONNECTING MEANS TO BE PROVIDED WITH MULTI-POLE CIRCUIT BREAKER AT THE
AutoCAD SHX Text
POINT WHERE THE BRANCH CIRCUIT ORIGINATES. ALL MULTI-WIRE BRANCH CIRCUITS GROUNDED AND UN-GROUNDED
AutoCAD SHX Text
CONDUCTORS TO BE GROUPED BY WIRE TIES WITHIN THE PANELBOARD OR OTHER POINT OF ORIGINATION.
AutoCAD SHX Text
INSPECT EACH DEVICE FOR DEFECTS IN MANUFACTURER AND OPERATE EACH SWITCHING DEVICE WITH CIRCUIT ENERGIZED
AutoCAD SHX Text
TO VERIFY PROPER OPERATION.
AutoCAD SHX Text
IDENTIFY EACH ELECTRICAL DISTRIBUTION AND CONTROL EQUIPMENT ENCLOSURE WITH ENGRAVED THREE LAYER PLASTIC
AutoCAD SHX Text
RED NAMEPLATE WITH 1/4" WHITE LETTERS. IDENTIFY FEEDER CIRCUITS ON PANELBOARDS WITH SIMILAR LABEL.
AutoCAD SHX Text
PROVIDE TYPED CIRCUIT DIRECTORY FOR EACH PANELBOARD. REVISE DIRECTORY AS NEEDED TO REFLECT CIRCUITRY
AutoCAD SHX Text
CHANGES MADE DURING CONSTRUCTION TO BALANCE PHASE LOADS.
AutoCAD SHX Text
THOROUGHLY CLEAN ALL PANELBOARD SURFACES BEFORE TURNING WORK OVER TO THE OWNER. VACUUM AND WIPE
AutoCAD SHX Text
INSIDE OF ENCLOSURES.
AutoCAD SHX Text
SAFETY SWITCHES:
AutoCAD SHX Text
EQUIPMENT TO BE AS NOTED ON THE DRAWINGS WHERE MANUFACTURED BY SQUARE D, SIEMENS, OR CUTLER HAMMER.
AutoCAD SHX Text
PROVIDE HEAVY DUTY TYPE, HORSEPOWER RATED, QUICK-MATE AND QUICK-BREAK DESIGN, EXTERNALLY OPERATED WITH
AutoCAD SHX Text
PROVISION FOR PADLOCKING, FUSIBLE, OR NON-FUSIBLE AS SHOWN ON THE DRAWINGS.
AutoCAD SHX Text
PROVIDE ENCLOSURE CLEARLY MARKED FOR MAXIMUM VOLTAGE, CURRENT, AND HORSEPOWER RATING (INDOOR: NEMA
AutoCAD SHX Text
TYPE 1, OUTDOOR: NEMA TYPE 3R, RAINTIGHT).
AutoCAD SHX Text
INSTALL FUSES IN SWITCHES.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
INSTALL SAFETY SWITCHES AND ENCLOSURES PLUMB AND LEVEL.
AutoCAD SHX Text
INSPECT EACH DEVICE FOR DEFECTS IN MANUFACTURER AND OPERATE EACH SWITCHING DEVICE WITH CIRCUIT ENERGIZED
AutoCAD SHX Text
TO VERIFY PROPER OPERATION.
AutoCAD SHX Text
IDENTIFY EACH ENCLOSURE WITH ENGRAVED THREE LAYER PLASTIC RED NAMEPLATE WITH 1/4" WHITE LETTERS.
AutoCAD SHX Text
THOROUGHLY CLEAN ALL SAFETY SWITCH SURFACES BEFORE TURNING WORK OVER TO THE OWNER. VACUUM AND WIPE
AutoCAD SHX Text
INSIDE OF ENCLOSURES.
AutoCAD SHX Text
BOXES AND ENCLOSURES:
AutoCAD SHX Text
ALL BOXES TO BE GALVANIZED METAL.
AutoCAD SHX Text
INDOOR LOCATION BOXES TO BE SHEET METAL.
AutoCAD SHX Text
OUTDOOR, DAMP, OR WET LOCATION BOXES TO BE CAST BOXES.
AutoCAD SHX Text
FLOOR BOXES TO BE FULLY ADJUSTABLE, CAST, ROUND, 1-1/2 INCH DEEP WITH FLOOR TRIM TO ACCOMMODATE
AutoCAD SHX Text
ADJACENT FLOOR FINISH.
AutoCAD SHX Text
ALL CABINETS AND ENCLOSURES TO BE STEEL CONSTRUCTION WITH METAL MOUNTING PANEL. FINISH TO BE
AutoCAD SHX Text
MANUFACTURER'S STANDARD ENAMEL FINISH. WHERE HINGED ENCLOSURE IS REQUIRED USE CONTINUOUS HINGES WITH
AutoCAD SHX Text
LOCKING MEANS.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
INSTALL BOXES AND ENCLOSURES PLUMB AND LEVEL.
AutoCAD SHX Text
RECEPTACLES AND SWITCHES/DIMMERS:
AutoCAD SHX Text
RECEPTACLES, SWITCHES, AND DIMMERS TO BE AS NOTED ON THE DRAWINGS.
AutoCAD SHX Text
DEVICES TO BE RATED NOT LESS THAN THEIR BRANCH CIRCUIT WITH A MINIMUM OF 20 AMP RATING. VOLTAGE RATING
AutoCAD SHX Text
TO BE NOT LESS THAN BRANCH CIRCUIT VOLTAGE.
AutoCAD SHX Text
COLOR OF ALL DEVICES AND DEVICE COVER PLATES TO BE AS SELECTED BY OWNER UNLESS SPECIFICALLY NOTED IN
AutoCAD SHX Text
THE DRAWINGS.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
INSTALL RECEPTACLES, SWITCHES, AND DIMMERS PLUMB AND LEVEL.
AutoCAD SHX Text
MOUNTING HEIGHTS OF ALL WALL SWITCHES AND RECEPTACLES TO BE COORDINATED WITH MILLWORK SHOP DRAWINGS,
AutoCAD SHX Text
FURNITURE LOCATIONS, AND/OR INTERIOR ELEVATIONS.
AutoCAD SHX Text
SEE DEVICE SCHEDULE OR NOTES ON PLANS FOR MOUNTING HEIGHTS.
AutoCAD SHX Text
AFFORD OWNER, ARCHITECT, AND/OR ENGINEER THE OPPORTUNITY TO RELOCATE DEVICES WITHIN THE SAME ROOM AT
AutoCAD SHX Text
TIME OF ROUGH-IN INSPECTION PRIOR TO COVERING UP WALLS AT NO ADDITIONAL COST TO OWNER.
AutoCAD SHX Text
INSPECT EACH DEVICE FOR DEFECTS IN MANUFACTURER AND OPERATE EACH SWITCHING DEVICE WITH CIRCUIT ENERGIZED
AutoCAD SHX Text
TO VERIFY PROPER OPERATION.
AutoCAD SHX Text
VERIFY THAT EACH RECEPTACLE IS ENERGIZED WITH PROPER POLARITY.
AutoCAD SHX Text
PERFORM GFCI TEST FOR EACH GFCI RECEPTACLE OR CIRCUIT BREAKER.
AutoCAD SHX Text
THOROUGHLY CLEAN ALL RECEPTACLE, SWITCH, AND DIMMER SURFACES BEFORE TURNING WORK OVER TO THE OWNER.
AutoCAD SHX Text
LIGHT FIXTURES:
AutoCAD SHX Text
LIGHT FIXTURES TO BE AS NOTED ON THE DRAWINGS AND ARE TO BE PROVIDED COMPLETE WITH ATTACHED PULL BOX
AutoCAD SHX Text
AND UL LABEL.
AutoCAD SHX Text
PROVIDE FLUORESCENT FIXTURES WITH ELECTRONIC PROGRAMMED START BALLAST, RATED FOR TEMPERATURES DOWN TO
AutoCAD SHX Text
0 DEGREES FAHRENHEIT WHERE APPLICABLE.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
INSTALL LIGHT FIXTURES STRAIGHT AND TRUE WITH REFERENCE TO WALLS IN ACCORDANCE WITH THE MANUFACTURER'S
AutoCAD SHX Text
WRITTEN INSTRUCTIONS.
AutoCAD SHX Text
USE CLIPS FOR RECESSED LIGHT FIXTURES IN GRID CEILINGS.
AutoCAD SHX Text
INSTALL LIGHT FIXTURES, INCLUDING THOSE MOUNTED IN CONTINUOUS ROWS, SO THAT THE WEIGHT OF THE FIXTURE IS
AutoCAD SHX Text
SUPPORTED, EITHER DIRECTLY OR INDIRECTLY, BY A SOUND AND SAFE STRUCTURAL MEMBER OF THE BUILDING, USING
AutoCAD SHX Text
ADEQUATE NUMER AND TYPE OF FASTENERS TO ASSURE SAFE INSTALLATION. SCREWED FASTENINGS AND TOGGLE BOLTS
AutoCAD SHX Text
THROUGH CEILING MATERIAL OR WALL PANELING ARE NOT ACCEPTABLE. DO NOT SUPPORT FROM SUB-PURLINS OF
AutoCAD SHX Text
PANELIZED ROOF SYSTEMS.
AutoCAD SHX Text
LIGHT FIXTURES 2'X4' AND LARGER RECESSED IN SUSPENDED CEILINGS TO BE SUSPENDED INDEPENDENT OF THE
AutoCAD SHX Text
CEILING GRID.
AutoCAD SHX Text
AIM AND ADJUST LIGHT FIXTURES AS INDICATED OR DIRECTED.
AutoCAD SHX Text
INSPECT EACH DEVICE FOR DEFECTS IN MANUFACTURER AND OPERATE EACH SWITCHING DEVICE WITH CIRCUIT ENERGIZED
AutoCAD SHX Text
TO VERIFY PROPER OPERATION.
AutoCAD SHX Text
CHECK EACH LIGHT FIXTURE FOR PROPER OPERATION FOR A PERIOD OF TWO HOURS.
AutoCAD SHX Text
UPON COMPLETION OF THE PROJECT REPLACE ALL FAILED LAMPS, FAILED BALLASTS, AND CRACKED LENSES.
AutoCAD SHX Text
THOROUGHLY CLEAN ALL LIGHT FIXTURE SURFACES BEFORE TURNING WORK OVER TO THE OWNER.
AutoCAD SHX Text
PROVIDE OUTLET DEVICE BACKBOXES AND CONDUIT RUNS AS DESCRIBED ON THE DRAWINGS. PROVIDE ONE (1) 3/4"
AutoCAD SHX Text
CONDUIT WITH PULLSTRING FROM EACH SIMPLEX OR DUPLEX COMMUNICATIONS OUTLET UP TO ACCESSIBLE CEILING.
AutoCAD SHX Text
PROVIDE TWO (2) 3/4" CONDUITS WITH PULLSTRING FROM EACH QUAD COMMUNICATIONS OUTLET UP TO ACCESSIBLE
AutoCAD SHX Text
CEILING.
AutoCAD SHX Text
PROVIDE BUSHING AT 90 DEGREE BEND ABOVE CEILING.
AutoCAD SHX Text
CONTRACTOR TO WARRANTY ALL MATERIALS, WORKMANSHIP, AND SYSTEM PERFORMANCE FOR A PERIOD OF NOT LESS
AutoCAD SHX Text
THAN ONE YEAR FROM TIME OF SUBSTSANTIAL COMPLETION. WHERE MANUFACTURER'S STANDARD WRITTEN WARRANTIES
AutoCAD SHX Text
OR WARRANTY REQUIREMENTS STATED ELSEWHERE IN THE DRAWINGS ARE OF A PERIOD OF GREATER THAN ONE YEAR,
AutoCAD SHX Text
CONTRACTOR OR MANUFACTURER ARE TO PROVIDE WARRANTY OF LONGER DURATION.
AutoCAD SHX Text
2014 FLORIDA BUILDING CODE - ENERGY CONSERVATION
AutoCAD SHX Text
2014 FLORIDA BUILDING CODE - EXISTING BUILDING
AutoCAD SHX Text
ALL LED LIGHTING AND LAMPING TO BE LABELED WITH THE DATE OF INSTALLATION.

EXIS

TIN

G 1

HR T

ENA

NT

SEP

ARA

TIO

NW

ALL

TO

REM

AIN

AS IS

EXIS

TIN

G 1

HR T

ENA

NT

SEP

ARA

TIO

NW

ALL

TO

REM

AIN

AS IS

100

RECEPTIONWAITING/

101

OFFICE

102

OFFICE

103

WORK AREA

104

ROOMCONFERENCE

105

IT

106

HCP RR

107

HCP RR

108

BREAK AREA

'F' PANEL SCHEDULE (EXISTING)

POWER RISER DIAGRAM NOTES

MINIMUM CONDUCTOR SIZES

CURRENT CARRYINGOVERCURRENT RATING GROUND CONDUCTOR

AND NEUTRAL CONDUCTOR

MINIMUM CONDUIT SIZE

4W+G 3W+G 2W+G

PLAN NOTES-POWER/SYSTEMS

PROJECT NOTES-POWER/SYSTEMS

DEMO NOTES-ELECTRICAL

EPS.101

ELECTRICALFLOOR PLAN

POWER/SYSTEMS

ELECTRICAL FLOOR PLAN - POWER/SYSTEMS

SCALE: 1/4 = 1'-0"

N

REVISIONS

ISSUE DATE

JOB #

SHEET TITLE

SHEET NO.

05.27.16

1636

A N

EW T

ENA

NT

BU

ILD

OU

T FO

R

THE

VIL

LAG

ES, FL

32

15

9

MPEMILLER PROFESSIONAL

ENGINEERING, LLC

P.O. BOX 4246OCALA, FLORIDA [email protected]

MILLER PROFESSIONAL

CERTIFICATE OF AUTH. #30872

98

0 D

EL M

AR D

RIV

E

CA

RTE

R H

EALT

H

PARTIN ARCHITECTURE

P A

936 E. FT. KING STREETOCALA, FLORIDA 34471

P 352.629.3867 F 352.629.3866

FL LIC# AA26001291

ENGINEERING, LLC

.

...

SPA

NIS

H S

PRIN

GS

AutoCAD SHX Text
TTB
AutoCAD SHX Text
G
AutoCAD SHX Text
G
AutoCAD SHX Text
G
AutoCAD SHX Text
G
AutoCAD SHX Text
G
AutoCAD SHX Text
+
AutoCAD SHX Text
'F'
AutoCAD SHX Text
+60"
AutoCAD SHX Text
G
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
75 cd
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
75 cd
AutoCAD SHX Text
F
AutoCAD SHX Text
15 cd
AutoCAD SHX Text
F
AutoCAD SHX Text
15 cd
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
S
AutoCAD SHX Text
M
AutoCAD SHX Text
3
AutoCAD SHX Text
F-31:33
AutoCAD SHX Text
4
AutoCAD SHX Text
4
AutoCAD SHX Text
4
AutoCAD SHX Text
4
AutoCAD SHX Text
4
AutoCAD SHX Text
4
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
75 cd
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
75 cd
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
75 cd
AutoCAD SHX Text
ON WALL BRACKET
AutoCAD SHX Text
EWH-1
AutoCAD SHX Text
ABOVE CEILING
AutoCAD SHX Text
F-8,10,12
AutoCAD SHX Text
8
AutoCAD SHX Text
12
AutoCAD SHX Text
F-2,4,6
AutoCAD SHX Text
6
AutoCAD SHX Text
2
AutoCAD SHX Text
F-15,17,19
AutoCAD SHX Text
17
AutoCAD SHX Text
F-7,9
AutoCAD SHX Text
9
AutoCAD SHX Text
15
AutoCAD SHX Text
F-11,13
AutoCAD SHX Text
11
AutoCAD SHX Text
8.2
AutoCAD SHX Text
8.7
AutoCAD SHX Text
4.9
AutoCAD SHX Text
9.3
AutoCAD SHX Text
9.4
AutoCAD SHX Text
VOLTAGE/PHASE:
AutoCAD SHX Text
LIGHTS-EXTERIOR
AutoCAD SHX Text
0.50
AutoCAD SHX Text
1.73
AutoCAD SHX Text
0.83
AutoCAD SHX Text
6.0
AutoCAD SHX Text
1.1
AutoCAD SHX Text
0.7
AutoCAD SHX Text
1.1
AutoCAD SHX Text
20
AutoCAD SHX Text
20
AutoCAD SHX Text
20
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1.08
AutoCAD SHX Text
1.26
AutoCAD SHX Text
0.36
AutoCAD SHX Text
0.36
AutoCAD SHX Text
0.36
AutoCAD SHX Text
0.36
AutoCAD SHX Text
0.90
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
2.2
AutoCAD SHX Text
2.2
AutoCAD SHX Text
0.18
AutoCAD SHX Text
TOTAL CONNECTED KVA:
AutoCAD SHX Text
DESC
AutoCAD SHX Text
C
AutoCAD SHX Text
B
AutoCAD SHX Text
2
AutoCAD SHX Text
A
AutoCAD SHX Text
#
AutoCAD SHX Text
4
AutoCAD SHX Text
8
AutoCAD SHX Text
6
AutoCAD SHX Text
P
AutoCAD SHX Text
A
AutoCAD SHX Text
C
AutoCAD SHX Text
12
AutoCAD SHX Text
10
AutoCAD SHX Text
18
AutoCAD SHX Text
16
AutoCAD SHX Text
14
AutoCAD SHX Text
20
AutoCAD SHX Text
24
AutoCAD SHX Text
22
AutoCAD SHX Text
30
AutoCAD SHX Text
28
AutoCAD SHX Text
26
AutoCAD SHX Text
KVA
AutoCAD SHX Text
CK
AutoCAD SHX Text
BRKR
AutoCAD SHX Text
A
AutoCAD SHX Text
P
AutoCAD SHX Text
A
AutoCAD SHX Text
1
AutoCAD SHX Text
#
AutoCAD SHX Text
C
AutoCAD SHX Text
B
AutoCAD SHX Text
3
AutoCAD SHX Text
7
AutoCAD SHX Text
5
AutoCAD SHX Text
A
AutoCAD SHX Text
9
AutoCAD SHX Text
11
AutoCAD SHX Text
19
AutoCAD SHX Text
17
AutoCAD SHX Text
15
AutoCAD SHX Text
13
AutoCAD SHX Text
21
AutoCAD SHX Text
23
AutoCAD SHX Text
29
AutoCAD SHX Text
25
AutoCAD SHX Text
27
AutoCAD SHX Text
DESC
AutoCAD SHX Text
TOTALS:
AutoCAD SHX Text
BRKR
AutoCAD SHX Text
KVA
AutoCAD SHX Text
CK
AutoCAD SHX Text
B
AutoCAD SHX Text
PHASE TOTAL
AutoCAD SHX Text
31
AutoCAD SHX Text
33
AutoCAD SHX Text
35
AutoCAD SHX Text
41
AutoCAD SHX Text
37
AutoCAD SHX Text
39
AutoCAD SHX Text
32
AutoCAD SHX Text
36
AutoCAD SHX Text
42
AutoCAD SHX Text
40
AutoCAD SHX Text
38
AutoCAD SHX Text
20
AutoCAD SHX Text
20
AutoCAD SHX Text
20
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
20
AutoCAD SHX Text
20
AutoCAD SHX Text
20
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
20
AutoCAD SHX Text
20
AutoCAD SHX Text
20
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
30
AutoCAD SHX Text
20
AutoCAD SHX Text
"
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
"
AutoCAD SHX Text
AMPS/MAIN:
AutoCAD SHX Text
MOUNTING:
AutoCAD SHX Text
NO. CIRCUITS:
AutoCAD SHX Text
ENCLOSURE:
AutoCAD SHX Text
208/120 VOLT, 3 PHASE, 4 WIRE
AutoCAD SHX Text
225/MLO (200A MCB UPSTREAM)
AutoCAD SHX Text
FLUSH
AutoCAD SHX Text
42
AutoCAD SHX Text
NEMA 1
AutoCAD SHX Text
TOTAL DEMAND KVA:
AutoCAD SHX Text
AIC RATING (AMPS):
AutoCAD SHX Text
24.7
AutoCAD SHX Text
25.4 (70.6 AMPS)
AutoCAD SHX Text
10K
AutoCAD SHX Text
"
AutoCAD SHX Text
"
AutoCAD SHX Text
3.19
AutoCAD SHX Text
3.19
AutoCAD SHX Text
3.19
AutoCAD SHX Text
30
AutoCAD SHX Text
"
AutoCAD SHX Text
"
AutoCAD SHX Text
3
AutoCAD SHX Text
"
AutoCAD SHX Text
"
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
MANUFACTURER:
AutoCAD SHX Text
SQUARE D
AutoCAD SHX Text
STYLE:
AutoCAD SHX Text
NQOD
AutoCAD SHX Text
RECEPTS
AutoCAD SHX Text
RECEPTS
AutoCAD SHX Text
RECEPTS
AutoCAD SHX Text
RECEPTS
AutoCAD SHX Text
RECEPTS
AutoCAD SHX Text
RECEPTS
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
"
AutoCAD SHX Text
"
AutoCAD SHX Text
SURGE SUPPRESSOR
AutoCAD SHX Text
20
AutoCAD SHX Text
20
AutoCAD SHX Text
20
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
20
AutoCAD SHX Text
20
AutoCAD SHX Text
20
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
20
AutoCAD SHX Text
20
AutoCAD SHX Text
20
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
20
AutoCAD SHX Text
"
AutoCAD SHX Text
"
AutoCAD SHX Text
3
AutoCAD SHX Text
"
AutoCAD SHX Text
"
AutoCAD SHX Text
0.90
AutoCAD SHX Text
0.54
AutoCAD SHX Text
0.90
AutoCAD SHX Text
0.18
AutoCAD SHX Text
0.18
AutoCAD SHX Text
0.18
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
1
AutoCAD SHX Text
#12
AutoCAD SHX Text
#12
AutoCAD SHX Text
21-30 AMPS
AutoCAD SHX Text
31-40 AMPS
AutoCAD SHX Text
41-50 AMPS
AutoCAD SHX Text
FURNISH CONDUCTORS IN ACCORDANCE WITH THIS SCHEDULE UNLESS OTHERWISE NOTED. ALL WIRES ARE TO BE COPPER, THHN, UNLESS OTHERWISE NOTED. SEE ELECTRICAL NOTES FOR ADDITIONAL CONDUIT AND WIRE INSULATION REQUIREMENTS.
AutoCAD SHX Text
0-20 AMPS
AutoCAD SHX Text
#10
AutoCAD SHX Text
#10
AutoCAD SHX Text
#8
AutoCAD SHX Text
#10
AutoCAD SHX Text
#8
AutoCAD SHX Text
#10
AutoCAD SHX Text
51-60 AMPS
AutoCAD SHX Text
#6
AutoCAD SHX Text
#10
AutoCAD SHX Text
61-70 AMPS
AutoCAD SHX Text
#4
AutoCAD SHX Text
#8
AutoCAD SHX Text
71-80 AMPS
AutoCAD SHX Text
#4
AutoCAD SHX Text
#8
AutoCAD SHX Text
81-90 AMPS
AutoCAD SHX Text
#3
AutoCAD SHX Text
#8
AutoCAD SHX Text
91-100 AMPS
AutoCAD SHX Text
#3
AutoCAD SHX Text
#8
AutoCAD SHX Text
0.75"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
0.75"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
1"
AutoCAD SHX Text
0.75"
AutoCAD SHX Text
-
AutoCAD SHX Text
1.25"
AutoCAD SHX Text
1"
AutoCAD SHX Text
-
AutoCAD SHX Text
1.25"
AutoCAD SHX Text
1"
AutoCAD SHX Text
-
AutoCAD SHX Text
1.25"
AutoCAD SHX Text
1"
AutoCAD SHX Text
-
AutoCAD SHX Text
1.25"
AutoCAD SHX Text
1.25"
AutoCAD SHX Text
-
AutoCAD SHX Text
1"
AutoCAD SHX Text
0.75"
AutoCAD SHX Text
-
AutoCAD SHX Text
1.25"
AutoCAD SHX Text
1.25"
AutoCAD SHX Text
-
AutoCAD SHX Text
2
AutoCAD SHX Text
EXISTING 200 AMP FUSES IN EXISTING NEMA 3R ENCLOSURE TO REMAIN.
AutoCAD SHX Text
UTILITY TRANSFORMER
AutoCAD SHX Text
S/N
AutoCAD SHX Text
METER
AutoCAD SHX Text
1 SET OF (4) 3/0 CU THHN/THWN
AutoCAD SHX Text
MAIN ELECTRIC COURTYARD
AutoCAD SHX Text
METER
AutoCAD SHX Text
METER
AutoCAD SHX Text
(EXISTING)
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
'F'
AutoCAD SHX Text
MAIN
AutoCAD SHX Text
208/120V
AutoCAD SHX Text
3%%C, 4W
AutoCAD SHX Text
METER
AutoCAD SHX Text
CARTER HEALTH CARE
AutoCAD SHX Text
+ #6 CU GND IN 3.0"C.
AutoCAD SHX Text
G
AutoCAD SHX Text
F
AutoCAD SHX Text
E
AutoCAD SHX Text
D
AutoCAD SHX Text
TVSS
AutoCAD SHX Text
1
AutoCAD SHX Text
METER
AutoCAD SHX Text
METER
AutoCAD SHX Text
METER
AutoCAD SHX Text
G
AutoCAD SHX Text
J VIA K
AutoCAD SHX Text
K.J.
AutoCAD SHX Text
METER
AutoCAD SHX Text
H-1
AutoCAD SHX Text
200A
AutoCAD SHX Text
208/3
AutoCAD SHX Text
LIGHTS-INTERIOR
AutoCAD SHX Text
LIGHTS-INTERIOR
AutoCAD SHX Text
RECEPTS
AutoCAD SHX Text
RECEPTS
AutoCAD SHX Text
RECEPTS
AutoCAD SHX Text
RECEPTS
AutoCAD SHX Text
RECEPTS
AutoCAD SHX Text
RECEPTS
AutoCAD SHX Text
RECEPTS
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
EWH-1
AutoCAD SHX Text
"
AutoCAD SHX Text
RECEPTS-RTU
AutoCAD SHX Text
RTU-4
AutoCAD SHX Text
TIMECLOCK
AutoCAD SHX Text
34
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
20
AutoCAD SHX Text
20
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
20
AutoCAD SHX Text
1
AutoCAD SHX Text
-
AutoCAD SHX Text
EXISTING 200 AMP PANELBOARD 'F' TO REMAIN.
AutoCAD SHX Text
2
AutoCAD SHX Text
DISCONNECT
AutoCAD SHX Text
PNL 'H-1'
AutoCAD SHX Text
METER
AutoCAD SHX Text
C
AutoCAD SHX Text
METER
AutoCAD SHX Text
B
AutoCAD SHX Text
METER
AutoCAD SHX Text
A
AutoCAD SHX Text
*
AutoCAD SHX Text
NEW LOAD TO BE CONNECTED TO EXISTING CIRCUIT BREAKER MADE
AutoCAD SHX Text
AVAILABLE BY DEMOLITION WORK OF THIS PROJECT.
AutoCAD SHX Text
**
AutoCAD SHX Text
NEW PANEL-MATCHING CIRCUIT BREAKER INSTALLED IN AVAILABLE
AutoCAD SHX Text
CIRCUIT BREAKER SPACE FOR NEW LOAD.
AutoCAD SHX Text
~
AutoCAD SHX Text
EXISTING LOAD ON PANEL/SERVICE TO REMAIN UNCHANGED.
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
**
AutoCAD SHX Text
1.
AutoCAD SHX Text
ALL ELECTRICAL DEVICE AND DEVICE PLATE COVERS TO BE AS SELECTED BY TENANT AND APPROVED BY LANDLORD.
AutoCAD SHX Text
2.
AutoCAD SHX Text
UNIT MOUNTED POWER RECEPTACLES ADJACENT TO RTU-4 TO REMAIN.
AutoCAD SHX Text
3.
AutoCAD SHX Text
PROVIDE PUDDY PACK FOR ANY NEW DEVICES BEING MOUNTED IN FIRE RATED WALL ASSEMBLY.
AutoCAD SHX Text
4.
AutoCAD SHX Text
COORDINATE ANY REQUIRED ROOFING WORK WITH VILLAGES SELECTED ROOFING CONTRACTOR. ANY ROOF PENETRATIONS THAT MAY BECOME NECESSARY ARE TO BE PERFORMED BY THIS CONTRACTOR AT TENANT'S EXPENSE.
AutoCAD SHX Text
EXISTING PANELBOARD 'F' TO REMAIN.
AutoCAD SHX Text
1
AutoCAD SHX Text
ELECTRIC WATER HEATER EWH-1: MOTOR RATED SWITCH PROVIDE 3-#10 CU + GND IN 0.75" CONDUIT FROM DISCONNECT TO NEW PANEL-MATCHING CIRCUIT BREAKER. PROVIDE ENGRAVED TAG ON CEILING INDICATING:
AutoCAD SHX Text
3
AutoCAD SHX Text
"WATER HEATER DISCONNECTING MEANS ABOVE"
AutoCAD SHX Text
ALL EXISTING DEVICES IN WALLS BEING REMOVED AS PART OF THIS PROJECT ARE TO BE REMOVED INCLUDING ALL ASSOCIATED ABOVE SLAB BRANCH CIRCUIT CONDUITS AND CONDUCTORS (BACK TO FIRST UPSTREAM JUNCTION BOX). IF REMOVAL OF DEVICE BREAKS THE CIRCUIT TO DOWNSTREAM DEVICES INTERCEPT AND EXTEND AS REQUIRED TO EXTEND CIRCUIT. PROVIDE ANY ASSOCIATED SYSTEM APPURTENANCES AS NEEDED. IF ALL DEVICES AND FIXTURES ON A PARTICULAR CIRCUIT ARE REMOVED, REMOVE ALL CONDUIT AND CONDUCTORS BACK TO BRANCH CIRCUIT BREAKER IN PANELBOARD (TURNING CIRCUIT BREAKER TO 'OFF' POSITION). IF EXISTING UNDER SLAB CONDUITS OBSTRUCT ROUTING OF NEW UTILITY SERVICE OF ANY KIND, EXISTING CONDUIT TO BE REMOVED. DO NOT REMOVE ANY SYSTEM COMPONENT THAT WOULD AFFECT ANY SERVICE FOR ADJACENT SPACES.
AutoCAD SHX Text
NOTE: EXISTING SYSTEMS CONNECTION POINTS ARE BASED UPON BEST AVAILABLE INFORMATION DURING DESIGN, LIMITED ONLY TO ITEMS THAT ARE CLEARLY VISIBLE PRE-DEMOLITION. CONTRACTOR TO COORDINATE EXACT EXISTING SYSTEMS LOCATIONS AFTER COMMENCEMENT OF DEMOLITION AND PRIOR TO ANY ROUGH-IN WORK. ADVISE ENGINEER IF UTILITY CONNECTION POINTS DIFFER.
AutoCAD SHX Text
REMOVE ALL FIXTURES, DEVICES, AND RACEWAYS WITHIN AREA OF WORK AS NECESSARY TO PREPARE FOR ACCOMMODATION OF RENOVATED/NEW SYSTEMS AS SHOWN ON THESE PLANS.
AutoCAD SHX Text
INTERCEPT AND EXTEND EXISTING COMMUNICATIONS CONDUITS WITHIN THIS TENANT SPACE TO NEW TELEPHONE TERMINAL BOARD (TTB) LOCATION SHOWN ON THIS PLAN.
AutoCAD SHX Text
2
AutoCAD SHX Text
EXISTING FIRE ALARM NOTIFICATION AND/OR INITIATION APPLIANCE TO REMAIN. REMOVE AND RE-INSTALL IN SAME LOCATION IF NEEDED TO ACCOMMODATE NEW WALL FINISHES.
AutoCAD SHX Text
4
AutoCAD SHX Text
NO WORK THIS AREA UNLESS OTHERWISE NOTED

EXIS

TIN

G 1

HR T

ENA

NT

SEP

ARA

TIO

NW

ALL

TO

REM

AIN

AS IS

EXIS

TIN

G 1

HR T

ENA

NT

SEP

ARA

TIO

NW

ALL

TO

REM

AIN

AS IS

100

RECEPTIONWAITING/

101

OFFICE

102

OFFICE

103

WORK AREA

104

ROOMCONFERENCE

105

IT

106

HCP RR

107

HCP RR

108

BREAK AREA

FIREWALL AND FLOOR PENETRATION DETAIL - 2-HOUR

OCCUPANCY/VACANCY CONTROL LIGHTING WIRING DIAGRAM

SYMBOL LEGEND

DESCRIPTIONSYMBOL

SEQUENCE OF OPERATION

PLAN NOTES-LIGHTING

PROJECT NOTES-LIGHTING

DEMO NOTES-ELECTRICAL

EL.101

ELECTRICALFLOOR PLAN

LIGHTING

ELECTRICAL FLOOR PLAN - LIGHTING

SCALE: 1/4" = 1'-0"

N

REVISIONS

ISSUE DATE

JOB #

SHEET TITLE

SHEET NO.

05.27.16

1636

A N

EW T

ENA

NT

BU

ILD

OU

T FO

R

THE

VIL

LAG

ES, FL

32

15

9

MPEMILLER PROFESSIONAL

ENGINEERING, LLC

P.O. BOX 4246OCALA, FLORIDA [email protected]

MILLER PROFESSIONAL

CERTIFICATE OF AUTH. #30872

98

0 D

EL M

AR D

RIV

E

CA

RTE

R H

EALT

H

PARTIN ARCHITECTURE

P A

936 E. FT. KING STREETOCALA, FLORIDA 34471

P 352.629.3867 F 352.629.3866

FL LIC# AA26001291

ENGINEERING, LLC

.

...

SPA

NIS

H S

PRIN

GS

AutoCAD SHX Text
A
AutoCAD SHX Text
EF
AutoCAD SHX Text
AA
AutoCAD SHX Text
AA
AutoCAD SHX Text
EF
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
2
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
VS
AutoCAD SHX Text
S
AutoCAD SHX Text
3
AutoCAD SHX Text
S
AutoCAD SHX Text
VS
AutoCAD SHX Text
S
AutoCAD SHX Text
F
AutoCAD SHX Text
S
AutoCAD SHX Text
F
AutoCAD SHX Text
S
AutoCAD SHX Text
3
AutoCAD SHX Text
VS
AutoCAD SHX Text
VS
AutoCAD SHX Text
EX
AutoCAD SHX Text
EX
AutoCAD SHX Text
A
AutoCAD SHX Text
A1
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A1
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A1
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A1
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
A1
AutoCAD SHX Text
B
AutoCAD SHX Text
S
AutoCAD SHX Text
F
AutoCAD SHX Text
B
AutoCAD SHX Text
EX
AutoCAD SHX Text
EX
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
EF
AutoCAD SHX Text
EM
AutoCAD SHX Text
EM
AutoCAD SHX Text
F-3,5
AutoCAD SHX Text
'F'
AutoCAD SHX Text
5
AutoCAD SHX Text
MIN 2.75" THICK PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING ON ONE SIDE OF WALL AS A PERMANENT FORM
AutoCAD SHX Text
3.75" LIGHTWEIGHT CONCRETE
AutoCAD SHX Text
PIPE MATERIAL AS SCHEDULED
AutoCAD SHX Text
OPTIONAL METALLIC SLEEVE 10" DIA. MAX.; SCH. 5 MIN.; CAST OR GROUTED IN PLACE
AutoCAD SHX Text
3/8" DIAMETER MIN BEAD ALL AROUND
AutoCAD SHX Text
SEALANT OR PUTTY; MIN 1" APPLIED WITHIN ANNULAR SPACE. FLUSH WITH WALL SURFACE. APPLY 3/8" DIA MIN BEAD OF FILL MATERIAL AT PEENTRANT/CONCRETE OR PEENTRANT/SLEEVE INTERFACE
AutoCAD SHX Text
SECTION VIEW
AutoCAD SHX Text
UL SEALANT OR PUTTY
AutoCAD SHX Text
MINERAL WOOL PACKING MATERIAL
AutoCAD SHX Text
PIPE MATERIAL AS SCHEDULED
AutoCAD SHX Text
OPTIONAL STEEL SLEEVE
AutoCAD SHX Text
THROUGH PENETRATION - CONCRETE WALL OR SLAB UL SYSTEM NO: W-J-1106
AutoCAD SHX Text
PIPE MATERIAL AS SCHEDULED
AutoCAD SHX Text
1/4" MINIMUM CAULK TYPICAL ALL AROUND AND BOTH SIDES. ADDITIONAL FILL MATERIAL TO BE INSTALLED SUCH THAT A MIN 1/4" CROWN IS FORMED AROUND THE PENETRATING ITEM AND LAPPING 1/2" BEYOND THE PERIPHERY OF THE OPENING.
AutoCAD SHX Text
FIRE RATED WALL CONSTRUCTION BY OTHERS
AutoCAD SHX Text
SECTION VIEW
AutoCAD SHX Text
PIPE MATERIAL AS SCHEDULED
AutoCAD SHX Text
ANNULAR SPACE TO BE 1/8" MIN, 1/4" MAX.
AutoCAD SHX Text
THROUGH PENETRATION - FRAME WALL UL SYSTEM NO: W-L-1033
AutoCAD SHX Text
MIN 1" THICK 4 PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING. PACKING MATERIAL TO BE RECESSED FROM BOTH SURFACES OF WALL. TYPICAL ALL AROUND BOTH SIDES.
AutoCAD SHX Text
TO LOAD
AutoCAD SHX Text
PPR
AutoCAD SHX Text
D
AutoCAD SHX Text
CR
AutoCAD SHX Text
CR
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
CR
AutoCAD SHX Text
S
AutoCAD SHX Text
TO LOAD
AutoCAD SHX Text
CR
AutoCAD SHX Text
S
AutoCAD SHX Text
TO LOAD
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
TO LOAD
AutoCAD SHX Text
TO CIRCUIT
AutoCAD SHX Text
TO LOAD
AutoCAD SHX Text
PPR
AutoCAD SHX Text
S
AutoCAD SHX Text
CR
AutoCAD SHX Text
VS
AutoCAD SHX Text
VS
AutoCAD SHX Text
VS
AutoCAD SHX Text
CEILING MOUNTED PIR/ULTRASONIC VACANCY SENSOR
AutoCAD SHX Text
D
AutoCAD SHX Text
ON/OFF SWITCH
AutoCAD SHX Text
DIMMER
AutoCAD SHX Text
LOW VOLTAGE POWER PACK WITH RELAY
AutoCAD SHX Text
CONTROL RELAY; ADD-A-RELAY
AutoCAD SHX Text
ALL SPACE LIGHTING ZONES TO BE CONTROLLED BY AN OCCUPANCY OR VACANCY CONTROL SYSTEM. COMMON SIGNAL FOR MULTIPLE OCCUPANCY AND/OR VACANCY SENSORS TO SYSTEM RELAYS TO ENABLE ALL SWITCHING AND DIMMING FUNCTIONS IN ALL SPACE ZONES FOR USE, OPERATION, AND ADJUSTMENT BY USER. OCCUPANCY AND/OR VACANCY SENSING CIRCUIT TO HAVE 10 TO 60 MINUTE ADJUSTABLE INTERVAL. ALL RELAYS FOR POWER AND ZONING REQUIREMENTS TO BE FURNISHED BY OCCUPANCY AND/OR VACANCY SENSOR. SYSTEM TO BE AS MANUFACTURED BY WATTSTOPPER, LEVITON, OR LUTRON. DEFAULT SEQUENCE OF OPERATION TO BE ON BY MANUAL SWITCH, OFF BY MANUAL SWITCH OR OCCUPANCY/VACANCY SENSOR SIGNAL UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
CEILING MOUNTED PIR/ULTRASONIC OCCUPANCY SENSOR
AutoCAD SHX Text
1.
AutoCAD SHX Text
ALL ELECTRICAL DEVICE AND DEVICE PLATE COVER COLORS TO BE AS SELECTED BY TENANT AND APPROVED BY LANDLORD.
AutoCAD SHX Text
2.
AutoCAD SHX Text
UNIT MOUNTED SERVICE LIGHTS ADJACENT TO RTU-4 TO REMAIN.
AutoCAD SHX Text
3.
AutoCAD SHX Text
PROVIDE PUDDY PACK FOR ANY NEW DEVICES BEING MOUNTED IN FIRE RATED WALL ASSEMBLY.
AutoCAD SHX Text
4.
AutoCAD SHX Text
ALL EMERGENCY AND EXIT LIGHT FIXTURES TO BE CONNECTED TO LOCAL LIGHT CIRCUIT AHEAD OF ANY SWITCH OR RELAY UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
LANDLORD PROVIDED TENANT SIGNAGE TO BE CONNECTED TO AVAILABLE SPARE CIRCUIT BREAKER IN EXISTING PANEL 'F' VIA LANDLORD PROVIDED JUNCTION BOX ABOVE ACCESSIBLE CEILING. EXTEND JUNCTION BOX FROM EXTERIOR WALL TO EDGE OF GYPSUM SOFFIT TO MAINTAIN CODE REQUIRED ACCESSIBILITY. CIRCUIT THROUGH HOUSE EXTERIOR LIGHTING CONTROLS VIA LANDLORD PROVIDED JUNCTION BOX AND CONDUIT.
AutoCAD SHX Text
1
AutoCAD SHX Text
EXISTING EXTERIOR LIGHTING CIRCUITED TO HOUSE PANEL TO REMAIN.
AutoCAD SHX Text
2
AutoCAD SHX Text
ALL EXISTING DEVICES IN WALLS BEING REMOVED AS PART OF THIS PROJECT ARE TO BE REMOVED INCLUDING ALL ASSOCIATED ABOVE SLAB BRANCH CIRCUIT CONDUITS AND CONDUCTORS (BACK TO FIRST UPSTREAM JUNCTION BOX). IF REMOVAL OF DEVICE BREAKS THE CIRCUIT TO DOWNSTREAM DEVICES INTERCEPT AND EXTEND AS REQUIRED TO EXTEND CIRCUIT. PROVIDE ANY ASSOCIATED SYSTEM APPURTENANCES AS NEEDED. IF ALL DEVICES AND FIXTURES ON A PARTICULAR CIRCUIT ARE REMOVED, REMOVE ALL CONDUIT AND CONDUCTORS BACK TO BRANCH CIRCUIT BREAKER IN PANELBOARD (TURNING CIRCUIT BREAKER TO 'OFF' POSITION). IF EXISTING UNDER SLAB CONDUITS OBSTRUCT ROUTING OF NEW UTILITY SERVICE OF ANY KIND, EXISTING CONDUIT TO BE REMOVED. DO NOT REMOVE ANY SYSTEM COMPONENT THAT WOULD AFFECT ANY SERVICE FOR ADJACENT SPACES.
AutoCAD SHX Text
NOTE: EXISTING SYSTEMS CONNECTION POINTS ARE BASED UPON BEST AVAILABLE INFORMATION DURING DESIGN, LIMITED ONLY TO ITEMS THAT ARE CLEARLY VISIBLE PRE-DEMOLITION. CONTRACTOR TO COORDINATE EXACT EXISTING SYSTEMS LOCATIONS AFTER COMMENCEMENT OF DEMOLITION AND PRIOR TO ANY ROUGH-IN WORK. ADVISE ENGINEER IF UTILITY CONNECTION POINTS DIFFER.
AutoCAD SHX Text
REMOVE ALL FIXTURES, DEVICES, AND RACEWAYS WITHIN AREA OF WORK AS NECESSARY TO PREPARE FOR ACCOMMODATION OF RENOVATED/NEW SYSTEMS AS SHOWN ON THESE PLANS.
AutoCAD SHX Text
EXISTING EXIT SIGN TO REMAIN. RE-CIRCUIT TO LOCAL 120V LIGHTING CIRCUIT AHEAD OF ANY SWITCH.
AutoCAD SHX Text
3
AutoCAD SHX Text
NO WORK THIS AREA UNLESS OTHERWISE NOTED