CARTER HEALTHCARE SPANISH SPRINGS - …€¦ · carter healthcare code analysis drawing index ......
11
A000 COVER SHEET & DESIGN CRITERIA A NEW TENANT BUILDOUT FOR: CARTER HEALTHCARE DRAWING INDEX CODE ANALYSIS AN 1,800 SQUARE FOOT INTERIOR MERCANTILE TENANT BUILD-OUT REMODELED TO AN OFFICE TENANT SPACE. SCOPE OF WORK ARCHITECTURAL A000 COVER SHEET, CODE ANALYSIS, GENERAL BUILDING INFORMATION A100 DEMOLITION PLAN, RENOVATION PLAN, LIFE SAFETY PLAN AND FINISH SCHEDULE A101 REFLECTED CEILING PLAN, DOOR SCHEDULE, WALL PARTITIONS, AND INTERIOR ELEVATIONS PLUMBING P001 PLUMBING - SCHEDULES, NOTES, AND DETAILS P101 PLUMBING FLOOR PLAN - WASTE/VENT AND WATER SUPPLY MECHANICAL M001 MECHANICAL - SCHEDULES, NOTES, AND DETAILS M101 MECHANICAL FLOOR PLAN - HVAC ELECTRICAL E001 ELECTRICAL - SCHEDULES AND DETAILS E002 ELECTRICAL - NOTES EPS101 ELECTRICAL FLOOR PLAN - POWER/SYSTEMS EL101 ELECTRICAL FLOOR PLAN - LIGHTING CONTROL JOINT HOSE BIB FLOOR DRAIN FD HB CJ ELECTRIC WATER COOLER EWC HC HANDICAPPED ROOF DRAIN RD STL. STRUCT. WWF STEEL STRUCTURAL WOVEN WIRE FABRIC NOT IN CONTRACT NIC NOT TO SCALE NTS VCT VINYL COMPOSITION TILE CARPET CPT CT CERAMIC TILE DF DRINKING FOUNTAIN EJ EXPANSION JOINT VENT THROUGH ROOF VTR SIM SIMILAR ALUMINUM ACOUSTIC ABOVE FINISH FLOOR CONTINUOUS ROOF LEADER/DOWNSPOUT DIAMETER FIRE EXTINGUISHER CEILING CLG. FE CONT. RL DIAM. COL. COLUMN ACOUS. A.F.F. ALUM. EXHAUST EXISTING EXTERIOR INSULATION MAXIMUM HOLLOW METAL GYPSUM BOARD EXT. MIN MAX JST. H.M. GYP. BD. INSUL. GA MINIMUM JOIST GAUGE EXH EXIST. EQ. EQUAL UNLESS NOTED OTHERWISE U.N.O. FEC FIRE EXTINGUISHER CABINET CONC. CONCRETE CMU CONCRETE MASONRY UNIT DBL. DOUBLE GALV. GALVANIZED FLR. FLOOR THRU THROUGH FIRE DEPT. CONNECTION FHA FIRE HYDRANT ASSEMBLY SYMBOLS 01 FD ABBREVIATIONS CODE ANALYSIS BUSINESS - B OCCUPANCY TYPE: CONSTRUCTION TYPE: CONSTRUCTION II-B (EXISTING / SPRINKLERED) INTERIOR WALL AND CEILING FINISH REQUIREMENTS FBC 803.9: GROUP B - BUSINESS - SPRINKLERED VERTICAL EXITS & PASSAGEWAYS EXIT CORRIDORS ROOMS AND ENCLOSED SPACES B C C APPROVED AUTOMATIC SPRINKLER SYSTEM IS PROVIDED THROUGHOUT THIS OCCUPANCY. FIRE PROTECTION SYSTEMS FBC 903: EXIT ACCESS TRAVEL DISTANCE FBC 1016.1: BUSINESS: MAXIMUM TRAVEL DISTANCE WITH A SPRINKLER SYSTEM SHALL BE 300'-0". MAXIMUM TRAVEL DISTANCE PROVIDED: 43'-8" CORRIDORS FBC 1018.1: BUSINESS: A FIRE RESISTANCE RATING IS NOT REQUIRED FOR CORRIDORS IN AN OCCUPANCY IN GROUP B WHICH IS SPRINKLERED MINIMUM NUMBER OF EXITS FBC 1021: OCCUPANT LOAD 1-500, MINIMUM # OF EXITS SHALL BE 2. NUMBER OF EXITS PROVIDED: 2 MINIMUM NUMBER OF PLUMBING FACILITIES (FROM TABLE P403.1) GROUP B - SPRINKLERED FLOOR AREA SF/OCCUPANT TOTAL OCCUPANT LOAD FLOOR AREA GROUP B - BUSINESS- SPRINKLERED STAIRWAYS OCCUPANT LOAD OTHER EGRESS COMPONENT EGRESS WIDTH FBC 1005.1: 0.3 PER OCCUPANT 18 PERSONS 0.2 PER OCCUPANT 5.4 REQUIRED 3.6 INCHES N/A PROVIDED 35 INCHES OCCUPANT LOAD FBC 1004: INTERIOR WALL AND CEILING FINISHES FLAME SPREAD AND SMOKE-DEVELOPED INDEXES AS PER ASTM E 84: CLASS A: FLAME SPREAD 0-25; SMOKE-DEVELOPED 0-450 CLASS B: FLAME SPREAD 26-75; SMOKE-DEVELOPED 0-450 CLASS C: FLAME SPREAD 76-200; SMOKE DEVELOPED 0-450 A FIRE ALARM AND DETECTION SYSTEM IS NOT REQUIRED FOR THIS PROJECT. FIRE ALARM AND DETECTION SYSTEMS FBC 907: 1 PROJECT LOCATION NOT TO SCALE N N (PLAN NORTH) P1 3 A201 3 A401 A A 1 1/A401 3 A501 3 A301 3 A102 DETAIL OR ENLARGED PLAN DETAIL ROOM NAME INTERIOR ELEVATION WALL SECTION BUILDING SECTION ELEVATION STRUCTURAL GRID CENTER LINE WINDOW TYPE TAG DOOR NUMBER TAG PARTITION TYPE TAG ROOM NAME ROOM NO. DETAIL OR SECTION NUMBER VIEW DIRECTION SHEET NUMBER DETAIL OR SECTION NUMBER SHEET NUMBER DETAIL OR SECTION NUMBER SHEET NUMBER ELEVATION NUMBER SHEET NUMBER DETAIL NUMBER SHEET NUMBER COLUMN GRID DESIGNATION GRID LINE DETAIL OR SECTION NUMBER SHEET NUMBER WINDOW NUMBER DOOR NUMBER WALL PARTITION NUMBER THIS PROJECT IS DESIGNED TO MEET THE REQUIREMENTS OF: 2014, 5th EDITION FLORIDA BUILDING CODE 2014, 5th EDITION FLORIDA PLUMBING CODE 2014, 5th EDITION FLORIDA MECHANICAL CODE 2014, 5th EDITION FLORIDA ENERGY CODE 2014, 5th EDITION FLORIDA EXISTING BUILDING CODE FLORIDA FIRE PREVENTION CODE 5th EDITION, 2012 ALL WORK SHALL CONFORM TO THESE CODES AND ALL OTHER APPLICABLE CODES, STANDARDS, AND ORDINANCES. WORK AREA COMPLIANCE METHOD ALTERATION LEVEL 3 XX/A401 DETAIL (MINOR) DETAIL NUMBER SHEET NUMBER REVISION TAG REVISION NUMBER THE VILLAGES, FLORIDA 32159 980 DEL MAR DRIVE B / FIRST FLOOR = 100 18 PERSONS 1,800 SF 18 PERSONS SCHEMATIC DESIGN/BUILD FIRE SPRINKLER SYSTEM MODIFICATIONS SHALL BE DESIGNED BY A LICENSED FIRE SPRINKLER CONTRACTOR. THE FIRE SPRINKLER CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL DOCUMENTATION TO THE AUTHORITIES HAVING JURISDICTION AS REQUIRED FOR PERMITTING. PLANS AND SPECIFICATIONS ISSUED BY FIRE PROTECTION CONTRACTOR SHALL BE SUBMITTED TO LANDLORD FOR WRITTEN APPROVAL. ALL WORK SHALL CONFORM TO LANDLORDS INSURANCE UNDERWRITERS AND CODE REQUIREMENTS AND ALL OTHER GOVERNING AUTHORITIES. PROVIDE ALL CONNECTIONS AND TURN-DOWN HEADS TO EXISTING FIRE PROTECTION SPRINKLER LINE, GRID AND UPRIGHT HEADS. SPRINKLER HEADS MUST BE CONCEALED OR SEMI-RECESSED MOUNTED HEADS. THE SPACING OF SPRINKLERS AND SIZES OF PIPES SHALL CONFORM TO THE REQUIREMENTS OF N.F.P.A. SYSTEM SHALL BE TESTED IN ACCORDANCE TO N.F.P.A. IN LOCATING SPRINKLERS AND PIPING, CONTRACTOR SHALL COORDINATE THE SPRINKLER LAYOUT WITH THE LIGHTING AND MECHANICAL DEVICE LAYOUT. PIPE SUPPORTS: HANGERS, CLAMPS, RODS AND OTHER ACCESSORIES OF AN APPROVED TYPE AND IN SUFFICIENT NUMBER TO PROPERLY SUPPORT ALL PIPING. REFER TO ARCHITECTURAL DOCUMENTS FOR LOCATIONS OF ALL SMOKE AND/OR FIRE WALLS MAINTAINING THE INTEGRITY OF THE SMOKE/FIRE WALLS WITH A TESTED ASSEMBLY FIRE SPRINKLER CONTRACTOR SHALL MAKE CONNECTION TO EXISTING FIRE MAIN BY PROVIDING AND INSTALLING VICTAULIC CONNECTIONS. G.C. TO NOTIFY TENANT COORDINATOR 48 HOURS IN ADVANCE OF WORK OR INSPECTIONS ON FIRE PROTECTION SYSTEM. FIRE SPRINKLER SYSTEM NOTE PROJECT LOCATION SERVICE SINKS F LAVS DRINKING FOUNTAINS 1:100 OCCUPANCY M BUSINESS 18 PERSONS WATER CLOSETS 1:25 1st 50 1:50 > 50 1 1 1 1 REQUIRED 1 1 HI/LO 2 2 PROVIDED 1 1:40 1st 80 1:80 > 80 REVISIONS ISSUE DATE JOB # SHEET TITLE SHEET NO. A NEW TENANT BUILDOUT FOR CARTER HEALTH SPANISH SPRINGS 980 DEL MAR DRIVE THE VILLAGES, FL 32159 05.27.2016 1636 936 E. FT. KING STREET OCALA, FLORIDA 34471 3 ) FL LIC# AA26001291 SPANISH SPRINGS
AN 1,800 SQUARE FOOT INTERIOR MERCANTILE TENANTBUILD-OUT REMODELED TO AN OFFICE TENANT SPACE.
SCOPE OF WORK
ARCHITECTURALA000 COVER SHEET, CODE ANALYSIS, GENERAL BUILDING INFORMATIONA100 DEMOLITION PLAN, RENOVATION PLAN, LIFE SAFETY PLAN AND FINISH SCHEDULEA101 REFLECTED CEILING PLAN, DOOR SCHEDULE, WALL PARTITIONS,
AND INTERIOR ELEVATIONS
PLUMBINGP001 PLUMBING - SCHEDULES, NOTES, AND DETAILS
P101 PLUMBING FLOOR PLAN - WASTE/VENT AND WATER SUPPLY
MECHANICALM001 MECHANICAL - SCHEDULES, NOTES, AND DETAILSM101 MECHANICAL FLOOR PLAN - HVAC
ELECTRICALE001 ELECTRICAL - SCHEDULES AND DETAILSE002 ELECTRICAL - NOTES
EPS101 ELECTRICAL FLOOR PLAN - POWER/SYSTEMSEL101 ELECTRICAL FLOOR PLAN - LIGHTING
CONTROL JOINT HOSE BIB
FLOOR DRAIN
FD
HBCJ
ELECTRIC WATER COOLEREWC
HC HANDICAPPED
ROOF DRAINRD
STL.
STRUCT.
WWF
STEEL
STRUCTURAL
WOVEN WIRE FABRIC
NOT IN CONTRACTNIC
NOT TO SCALENTS
VCT VINYL COMPOSITION TILE
CARPETCPT
CT CERAMIC TILE
DF
DRINKING FOUNTAIN
EJ EXPANSION JOINT
VENT THROUGH ROOFVTR
SIM SIMILAR
ALUMINUM
ACOUSTIC
ABOVE FINISH FLOOR
CONTINUOUS
ROOF LEADER/DOWNSPOUT
DIAMETER
FIRE EXTINGUISHER
CEILINGCLG.
FE
CONT.
RL
DIAM.
COL. COLUMN
ACOUS.
A.F.F.
ALUM.
EXHAUST
EXISTING
EXTERIOR
INSULATION
MAXIMUM
HOLLOW METAL
GYPSUM BOARD
EXT.
MIN
MAX
JST.
H.M.
GYP. BD.
INSUL.
GA
MINIMUM
JOIST
GAUGE
EXH
EXIST.
EQ. EQUAL
UNLESS NOTED OTHERWISEU.N.O.
FEC FIRE EXTINGUISHER CABINET
CONC. CONCRETE
CMU CONCRETE MASONRY UNIT
DBL. DOUBLE
GALV. GALVANIZED
FLR. FLOOR
THRU THROUGH
FIRE DEPT. CONNECTION
FHA FIRE HYDRANT ASSEMBLY
SYMBOLS
01
FD
ABBREVIATIONS CODE ANALYSIS
BUSINESS - B
OCCUPANCY TYPE:
CONSTRUCTION TYPE:
CONSTRUCTION II-B (EXISTING / SPRINKLERED)
INTERIOR WALL AND CEILING FINISH REQUIREMENTS FBC 803.9:
GROUP B - BUSINESS - SPRINKLERED
VERTICAL EXITS &PASSAGEWAYS
EXIT CORRIDORSROOMS AND
ENCLOSED SPACESB C C
APPROVED AUTOMATIC SPRINKLER SYSTEM IS PROVIDED THROUGHOUT THIS OCCUPANCY.
FIRE PROTECTION SYSTEMS FBC 903:
EXIT ACCESS TRAVEL DISTANCE FBC 1016.1:BUSINESS: MAXIMUM TRAVEL DISTANCE WITH A SPRINKLER SYSTEM SHALL BE 300'-0".MAXIMUM TRAVEL DISTANCE PROVIDED: 43'-8"
CORRIDORS FBC 1018.1:BUSINESS: A FIRE RESISTANCE RATING IS NOT REQUIRED FOR CORRIDORS IN ANOCCUPANCY IN GROUP B WHICH IS SPRINKLERED
MINIMUM NUMBER OF EXITS FBC 1021:OCCUPANT LOAD 1-500, MINIMUM # OF EXITS SHALL BE 2.NUMBER OF EXITS PROVIDED: 2
MINIMUM NUMBER OF PLUMBING FACILITIES(FROM TABLE P403.1)
GROUP B - SPRINKLERED
FLOOR AREA SF/OCCUPANT TOTAL OCCUPANT LOADFLOOR AREA
GROUP B - BUSINESS- SPRINKLERED
STAIRWAYSOCCUPANT LOADOTHER EGRESSCOMPONENT
EGRESS WIDTH FBC 1005.1:
0.3 PER OCCUPANT18 PERSONS 0.2 PER OCCUPANT
5.4REQUIRED 3.6 INCHES
N/APROVIDED 35 INCHES
OCCUPANT LOAD FBC 1004:
INTERIOR WALL AND CEILING FINISHES FLAME SPREAD ANDSMOKE-DEVELOPED INDEXES AS PER ASTM E 84:
CLASS A: FLAME SPREAD 0-25; SMOKE-DEVELOPED 0-450CLASS B: FLAME SPREAD 26-75; SMOKE-DEVELOPED 0-450CLASS C: FLAME SPREAD 76-200; SMOKE DEVELOPED 0-450
A FIRE ALARM AND DETECTION SYSTEM IS NOT REQUIRED FOR THIS PROJECT.
FIRE ALARM AND DETECTION SYSTEMS FBC 907:
1PROJECT LOCATIONNOT TO SCALE
N
N(PLAN NORTH)
P1
3
A201
3
A401
A
A
1
1/A401
3
A501
3
A301
3
A102
DETAIL ORENLARGEDPLAN
DETAIL
ROOMNAME
INTERIORELEVATION
WALLSECTION
BUILDINGSECTION
ELEVATION
STRUCTURALGRID
CENTER LINE
WINDOWTYPE TAG
DOORNUMBER TAG
PARTITIONTYPE TAG
ROOM NAME
ROOM NO.
DETAIL OR SECTIONNUMBER
VIEW DIRECTION
SHEET NUMBER
DETAIL OR SECTIONNUMBER
SHEET NUMBER
DETAIL OR SECTIONNUMBER
SHEET NUMBER
ELEVATION NUMBER
SHEET NUMBER
DETAIL NUMBER
SHEET NUMBER
COLUMN GRIDDESIGNATION
GRID LINE
DETAIL ORSECTIONNUMBER
SHEETNUMBER
WINDOW NUMBER
DOOR NUMBER
WALL PARTITIONNUMBER
THIS PROJECT IS DESIGNED TO MEET THE REQUIREMENTS OF:2014, 5th EDITION FLORIDA BUILDING CODE2014, 5th EDITION FLORIDA PLUMBING CODE2014, 5th EDITION FLORIDA MECHANICAL CODE2014, 5th EDITION FLORIDA ENERGY CODE2014, 5th EDITION FLORIDA EXISTING BUILDING CODEFLORIDA FIRE PREVENTION CODE 5th EDITION, 2012
ALL WORK SHALL CONFORM TO THESE CODES AND ALL OTHER APPLICABLE CODES,STANDARDS, AND ORDINANCES.
WORK AREA COMPLIANCE METHOD ALTERATION LEVEL 3
XX/A401DETAIL(MINOR)
DETAIL NUMBER
SHEET NUMBER
REVISION TAG REVISION NUMBER
THE VILLAGES, FLORIDA 32159
980 DEL MAR DRIVE
B / FIRST FLOOR = 100 18 PERSONS1,800 SF
18 PERSONS
SCHEMATIC DESIGN/BUILD FIRE SPRINKLER SYSTEM MODIFICATIONS SHALL BE DESIGNED BY A LICENSED FIRESPRINKLER CONTRACTOR. THE FIRE SPRINKLER CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALLDOCUMENTATION TO THE AUTHORITIES HAVING JURISDICTION AS REQUIRED FOR PERMITTING.
PLANS AND SPECIFICATIONS ISSUED BY FIRE PROTECTION CONTRACTOR SHALL BE SUBMITTED TO LANDLORD FORWRITTEN APPROVAL.
ALL WORK SHALL CONFORM TO LANDLORDS INSURANCE UNDERWRITERS AND CODE REQUIREMENTS AND ALL OTHERGOVERNING AUTHORITIES.
PROVIDE ALL CONNECTIONS AND TURN-DOWN HEADS TO EXISTING FIRE PROTECTION SPRINKLER LINE, GRID ANDUPRIGHT HEADS.
SPRINKLER HEADS MUST BE CONCEALED OR SEMI-RECESSED MOUNTED HEADS. THE SPACING OF SPRINKLERS ANDSIZES OF PIPES SHALL CONFORM TO THE REQUIREMENTS OF N.F.P.A. SYSTEM SHALL BE TESTED IN ACCORDANCE TON.F.P.A.
IN LOCATING SPRINKLERS AND PIPING, CONTRACTOR SHALL COORDINATE THE SPRINKLER LAYOUT WITH THELIGHTING AND MECHANICAL DEVICE LAYOUT.
PIPE SUPPORTS: HANGERS, CLAMPS, RODS AND OTHER ACCESSORIES OF AN APPROVED TYPE AND IN SUFFICIENTNUMBER TO PROPERLY SUPPORT ALL PIPING.
REFER TO ARCHITECTURAL DOCUMENTS FOR LOCATIONS OF ALL SMOKE AND/OR FIRE WALLS MAINTAINING THE
INTEGRITY OF THE SMOKE/FIRE WALLS WITH A TESTED ASSEMBLY
FIRE SPRINKLER CONTRACTOR SHALL MAKE CONNECTION TO EXISTING FIRE MAIN BY PROVIDING AND INSTALLINGVICTAULIC CONNECTIONS.
G.C. TO NOTIFY TENANT COORDINATOR 48 HOURS IN ADVANCE OF WORK OR INSPECTIONS ON FIRE PROTECTIONSYSTEM.
FIRE SPRINKLER SYSTEM NOTE
PROJECTLOCATION
SERVICESINKS
F LAVSDRINKINGFOUNTAINS
1:100
OCCUPANCY
MBUSINESS18 PERSONS
WATERCLOSETS
1:25 1st 501:50 > 50
1111REQUIRED
11 HI/LO22PROVIDED
11:40 1st 801:80 > 80
REVISIONS
ISSUE DATE
JOB #
SHEET TITLE
SHEET NO.
A N
EW T
ENA
NT
BU
ILD
OU
T FO
R
CA
RTE
R H
EALT
HSPA
NIS
H S
PRIN
GS
98
0 D
EL M
AR D
RIV
E
TH
E V
ILLA
GES
, FL
32
15
9
05.27.2016
1636
936 E. FT. KING STREETOCALA, FLORIDA 34471
P 352.629.3867 F 352.629.3866
FL LIC# AA26001291
SPANISH SPRINGS
100
WAITING/RECEPTION
P01
101
OFFICE102
OFFICE
103
WORK AREA
104
CONFERENCEROOM
108
BREAK AREA
105
IT
106
HCP RR
107
HCP RR
10'-4"
19'-4"
10'-4"
10'-4"
8'-0"
12'-3" 5'-0" 12'-3"
3'-0"
2'-0"
3'-0"
4'-7"
3'-0" 11'-6" 14'-10"
6'-7" 5'-0" 3'-0"
4'-6"
10'-0"
4'-6"
RECONFIGURECOMMODE ANDLAVATORY FOR ADACOMPLIANCE
NEW HCPDRINKINGFOUNTAINS
NEWMOPSINK
12'-8"5'-4"1'-0"MIN
D01
EXISTING 3070SF DOOR TOREMAIN AS IS
EXISTING 4050FG TO REMAIN
AS IS
EXISTING2-4050 FG TOREMAIN AS IS
EXISTING 3070HM DOOR TOREMAIN AS IS
EXISTING 3068SC DOOR TOREMAIN AS IS
EXISTING 3068SC DOOR TOREMAIN AS IS
D02
D03
D04
D05
4068 COW/ DRYWALL
RETRUNS
2A101
W1W1
TYPICAL
P01
TYPICAL
7'-7"
7'-4"
T-SHAPED SPACE PERADA 304.3.2 WITH KNEESPACE COMPLYING W/ADA 306
4'-6"5'-3"
D06
3'-4"
7'-4"
REF W/ICEMAKER
BACK WALLFINISHED W/PLYWOOD
FRAMELESSGLASS WALL
SYSTEM
FRAMELESSGLASS WALL
SYSTEM
DOOR DESIGNATION TAG -SEE DOOR SCHEDULE
XXXX
000
000WINDOW DESIGNATION TAG -SEE WINDOW SCHEDULE
ROOM NAME ANDDESIGNATION TAG
0
000INTERIOR / EXTERIORELEVATION TAG
ELEVATION NUMBER
SHEET NUMBER
WALL AND PARTITION TAG -SEE WALL TYPES THIS SHEET
ROOM NAME
ROOM NUMBER
FLOOR PLAN LEGEND
FE
EGRESS DISTANCE CALCULATIONSTARTING POINT
EGRESS PATH OF TRAVEL
FEC
EXISTING WALL MOUNTED2A10BC FIRE EXTINGUISHER
2A10BC FIRE EXTINGUISHER INSEMI-RECESSED CABINET
INTERNALLY ILLUMINATED LED EXITLIGHT WITH DIRECTIONAL ARROWAND BATTERY BACKUP
EMERGENCY LIGHT (2 LAMP) WITHBATTERY BACKUP
INTERNALLY ILLUMINATED LED
EMERGENCY EXIT LIGHT / EMERGENCYLIGHT COMBO WITH BATTERY BACKUP
SD SMOKE DETECTOR WITH FIXEDTEMPERATURE HEAT DETECTOR
EXISTING WALLS TO REMAIN
ITEM TO BE DEMOLISHED
NEW PARTITION
GENERAL FLOOR PLAN NOTES
1. ALL WORK SHALL SHALL MEET OR EXCEED THE FLORIDA BUILDINGCODE 5th EDITION (2014), FLORIDA FIRE PREVENTION CODE,NATIONAL ELECTRIC CODE, AMERICANS WITH DISABILITIES ACT, ANDALL CURRENT APPLICABLE LOCAL, STATE, AND FEDERAL CODES ANDORDINANCES.
2. ALL DIMENSIONS ARE TAKEN FROM FACE OF EXISTING GYPSUMBOARD, FACE OF EXISTING MASONRY OR FACE OF NEW METALSTUDS.
3. ALL STORAGE SHELVING, MERCHANDISE DISPLAY RACKS ANDEQUIPMENT, AND POINT OF SALE CABINETRY AND EQUIPMENTSHOWN ON FLOOR PLAN SHALL BE SIZED AND DESIGNED BY OTHERS.LOCATIONS AND SIZES DENOTED ON PLANS ARE PROPOSED FOR THEINTENT OF SPACE PLANNING AND ARCHITECTURAL DESIGN ONLYAND MUST BE VERIFIED.
4. EXISTING STOREFRONT DOOR AND WINDOW ASSEMBLIES TOREMAIN. GC TO CLEAN AND REPAIR TO 'LIKE-NEW' CONDITION ASREQUIRED.
HARDWARE KEYH1 = SURFACE MOUNTED DOOR CLOSERH2 = METAL FRAME DOOR SILENCERSH3 = MOP PLATEH4 = BATHROOM SIGN WITH BRAILLE LETTERING
HARDWARE
H1,H2
H2,H3
PANELED SWING
PANELED SWING
1. ALL DOOR HARDWARE TO BE COMMERCIAL GRADE AND COMPLY WITH ADA GUIDELINES AND ALL OTHERAPPLICABLE CODES.
2. ALL LATCH SETS ARE TO BE ADA COMPLIANT LEVER-TYPE.
3. VERIFY ALL DOOR HARDWARE STYLES AND FINISHES WITH OWNER BEFORE PURCHASE.
4. VERIFY ALL FRAME ROUGH OPENINGS WITH DOOR MANUFACTURER.
5. COORDINATE ALL DOOR AND FRAME INSTALLATION AND HARDWARE SPECIFICATIONS WITH SECURITYSYSTEM COMPONENT INSTALLATION REQUIREMENTS AND ENSURE ALL ELECTRICAL AND HARDWARE NEEDSARE ADDRESSED.
6. VERIFY ALL KEYING REQUIREMENTS WITH OWNER.
7. DOORSTOPS SHALL BE FURNISHED FOR ALL DOORS TO PREVENT DAMAGE TO DOORS OR HARDWAREFROM STRIKING ADJACENT WALLS OR FIXTURES. WALL BUMPERS ARE PREFERRED, BUT WHERE NOT PRACTICALFURNISH FLOOR STOPS. WHERE CONDITIONS PROHIBIT THE USE OF EITHER WALL OR FLOOR TYPE STOPS,FURNISH SURFACE MOUNTED OVERHEAD STOPS.
8. DOOR CLOSERS SHALL BE FURNISHED WITH PARALLEL ARM MOUNTED ON ALL DOORS OPENING INTOCORRIDORS OR OTHER PUBLIC SPACES AND SHALL BE MOUNTED TO PERMIT 180 DEGREES DOOR SWINGWHEREVER WALL CONDITIONS PERMIT. FURNISH WITH NON-HOLD OPEN ARMS UNLESS OTHERWISEINDICATED.
9. THE FOLLOWING SCHEDULE IS FURNISHED FOR WHATEVER ASSISTANCE IT MAY AFFORD THE CONTRACTOR;DO NOT CONSIDER IT AS ENTIRELY INCLUSIVE. SHOULD ANY PARTICULAR DOOR OR ITEM BE OMITTED IN ANYSCHEDULED HARDWARE GROUP, PROVIDE DOOR OR ITEM WITH HARDWARE SAME AS REQUIRED FOR SIMILARPURPOSES.
PLUMBING CONTRACTOR SHALL COMPLETELY FAMILIARIZE HIMSELF/HERSELF WITH ALL CONDITIONS
AutoCAD SHX Text
AFFECTING HIS/HER WORK INCLUDING VISIT TO THE SITE BEFORE PREPARING PROPOSAL. ALL
AutoCAD SHX Text
WORK IS TO BE PERFORMED IN ACCORDANCE WITH ALL APPLICABLE CODES AND STANDARDS
AutoCAD SHX Text
FROM ALL AUTHORITIES HAVING JURISDICTION OVER THE WORK. WHERE CONFLICT EXISTS
AutoCAD SHX Text
BETWEEN THE APPLICABLE CODES AND STANDARDS OR THE PLANS AND SPECIFICATIONS, THE
AutoCAD SHX Text
MOST STRINGENT AS DETERMINED BY THE ENGINEER SHALL APPLY. CONTRACTOR SHALL NOTIFY
AutoCAD SHX Text
ENGINEER OF CONFLICTING CONDITIONS AFFECTING HIS/HER WORK AND ADVISE ENGINEER FOR
AutoCAD SHX Text
CLARIFICATION. LOCAL CODES IN EFFECT FOR THIS PROJECT INCLUDE BUT ARE NOT LIMITED TO
AutoCAD SHX Text
THE FOLLOWING:
AutoCAD SHX Text
2014 FLORIDA BUILDING CODE
AutoCAD SHX Text
2014 FLORIDA BUILDING CODE - MECHANICAL
AutoCAD SHX Text
2014 FLORIDA BUILDNG CODE - PLUMBING
AutoCAD SHX Text
2014 FLORIDA BUILDING CODE - GAS
AutoCAD SHX Text
2011 NFPA 70 "NATIONAL ELECTRIC CODE"
AutoCAD SHX Text
SUBMISSION OF BID INDICATES CONTRACTOR'S ACKNOWLEDGEMENT THAT THEY ARE PROVIDING TO
AutoCAD SHX Text
THE OWNER A COMPLETE AND OPERATING SYSTEM. ANY CONTRACTOR UNCERTAINTIES OR
AutoCAD SHX Text
MISSING INFORMATION CONCERNS TO BE SUBMITTED IN WRITING PRIOR TO SUBMISSION OF BID
AutoCAD SHX Text
SO THAT ENGINEER MAY PROVIDE PROPER CLARIFICATION.
AutoCAD SHX Text
PROVIDE ADEQUATE NUMBER OF SKILLED WORKMEN WHO ARE THOROUGHLY TRAINED AND
AutoCAD SHX Text
EXPERIENCED IN THE NECESSARY CRAFTS AND WHO ARE COMPLETELY FAMILIAR WITH THE
AutoCAD SHX Text
SPECIFIED REQUIREMENTS AND THE METHODS NEEDED FOR PROPER PERFORMANCE OF THE
AutoCAD SHX Text
WORK.
AutoCAD SHX Text
CONTRACTOR TO PREPARE SUBMITTALS AND SHOP DRAWINGS FOR ALL PLUMBING WORK AS
AutoCAD SHX Text
REQUIRED BY THE CONSTRUCTION DOCUMENTS FOR ENGINEER'S REVIEW NOT MORE THAN 35
AutoCAD SHX Text
CALENDAR DAYS AFTER CONTRACTOR HAS RECEIVED THE OWNER'S NOTICE TO PROCEED.
AutoCAD SHX Text
CONTRACTOR TO PROVIDE STERILIZATION "CERTIFICATE OF PERFORMANCE" UPON COMPLETION OF
AutoCAD SHX Text
WATER LINE STERILIZATION.
AutoCAD SHX Text
CONTRACTOR TO PROVIDE SUFFICIENT DATA INDICATING THAT WRAPPING OF STEEL PIPING HAS
AutoCAD SHX Text
BEEN TESTED AND MEETS THE SPECIFIED REQUIREMENTS. INDICATE DATE OF INSPECTION,
AutoCAD SHX Text
VOLTAGES USED, AND NAME/ADDRESS OF THE INSPECTOR.
AutoCAD SHX Text
UPON COMPLETION OF WORK, CONTRACTOR TO PROVIDE TWO COPIES OF AN OPERATION AND
AutoCAD SHX Text
MAINTENANCE MANUAL. INCLUDE IN EACH MANUAL A COPY OF THE PROJECT RECORD
AutoCAD SHX Text
DOCUMENTS.
AutoCAD SHX Text
ENGINEER'S DRAWINGS AND CONSTRUCTION DOCUMENTS ARE DIAGRAMMATIC. CONTRACTOR OF
AutoCAD SHX Text
THIS WORK TO COORDINATE WITH ALL WORK OF CONTRACTORS OF ALL TRADES AND GENERAL
AutoCAD SHX Text
CONTRACTOR. CONTRACTORS TO FIELD MEASURE PRIOR TO FABRICATION OF ANY WORK.
AutoCAD SHX Text
CONTRACTOR OF WORK OF THIS TRADE TO COMMUNICATE WITH GENERAL CONTRACTOR AND
AutoCAD SHX Text
CONTRACTORS OF OTHER TRADES AND PREPARE DRAWINGS, SKETCHES, AND PROVIDE
AutoCAD SHX Text
INFORMATION AS NEEDED TO COMMUNICATE WITH OTHER TRADES FOR CONSTRUCTION OF
AutoCAD SHX Text
COMPLETE AND OPERATING SYSTEM WITHOUT ADDITIONAL COST TO OWNER. PRIOR TO BEGINNING
AutoCAD SHX Text
WORK OF THIS TRADE, CONTRACTOR OF THIS TRADE TO CONDUCT COORDINATION MEETING WITH
AutoCAD SHX Text
OTHER AFFECTED CONTRACTORS OF OTHER TRADES AND GENERAL CONTRACTOR FOR PURPOSES
AutoCAD SHX Text
OF COORDINATION. CONTRACTOR'S FAILURES TO COORDINATE WILL NOT BE CAUSE FOR
AutoCAD SHX Text
RECOVERY OF ADDITIONAL COMPENSATION FOR CORRECTION OR MODIFICATION WORK WHICH IN
AutoCAD SHX Text
THE SOLE OPINION OF THE ENGINEER IS NOT WELL COORDINATED.
AutoCAD SHX Text
LAYOUT THE PLUMBING SYSTEM IN CAREFUL COORDINATION WITH THE DRAWINGS, DETERMINING
AutoCAD SHX Text
PROPER ELEVATIONS FOR ALL COMPONENTS OF THE SYSTEM USING ONLY THE MINIMUM NUMBER
AutoCAD SHX Text
OF BENDS TO PRODUCE A SATISFACTORILY FUNCTIONING SYSTEM. FOLLOW THE GENERAL LAYOUT
AutoCAD SHX Text
SHOWN ON THE DRAWINGS IN ALL CASES EXCEPT WHERE OTHER WORK MAY INTERFERE.
AutoCAD SHX Text
ALL MATERIALS TO BE OF DOMESTIC MANUFACTURER UNLESS OTHERWISE DIRECTED.
AutoCAD SHX Text
PIPE:
AutoCAD SHX Text
DRAIN, WASTE, AND VENT SYSTEM:
AutoCAD SHX Text
BELOW THE FLOOR AND OUTSIDE UNDERGROUND PIPING AND FITTINGS TO BE SCHEDULE 40 PVC.
AutoCAD SHX Text
ABOVE GROUND PIPING AND FITTINGS TO BE SCHEDULE 40 PVC.
AutoCAD SHX Text
WATER SYSTEM (DOMESTIC HOT/COLD):
AutoCAD SHX Text
ABOVE GROUND PIPING TO BE TYPE 'L' COPPER WITH SILVER SOLDER SWEATED CONNECTIONS
AutoCAD SHX Text
BELOW GROUND PIPING TO BE TYPE 'K' COPPER WITH SILVER SOLDER SWEATED CONNECTIONS.
AutoCAD SHX Text
PIPING FROM WATER SOURCE TO THE MAIN VALVE AND GREATER THAN 5' FROM THE BUILDING
AutoCAD SHX Text
ENVELOPE MAY BE SCHEDULE 40 PVC.
AutoCAD SHX Text
PROVIDE THRUST BLOCKS AND TRACING WIRE IN A MANNER CONSISTENT WITH MANUFACTURER'S
AutoCAD SHX Text
RECOMMENDATIONS.
AutoCAD SHX Text
ALL COPPER PIPING INSTALLED IN CONCRETE OR UNDERGROUND TO BE INSTALLED IN SEAMLESS
AutoCAD SHX Text
POLYETHYLENE SLEEVE.
AutoCAD SHX Text
FIXTURE TRIM AND ESCUTCHEONS:
AutoCAD SHX Text
ALL FIXTURE TRIM TO BE CHROME PLATED UNLESS ALTERNATE FINISH IS SPECIFIED.
AutoCAD SHX Text
WHERE PIPING PENETRATES THROUGH WALLS, FLOORS, OR SLABS, INSTALL CAST BRASS
AutoCAD SHX Text
ESCUTCHONS. SECURE TIGHT TO WALL WITH SET SCREW.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
LAYOUT PIPES TO FALL WITHIN PARTITION WALL, ROOF OR CEILING CAVITIES, AND TO NOT
AutoCAD SHX Text
REQUIRE FURRING OTHER THAN AS SHOWN ON THE DRAWINGS.
AutoCAD SHX Text
ALL WATER SUPPLY PIPING WITHIN THE BUILDING TO BE ROUTED OVERHEAD CONCEALED BY
AutoCAD SHX Text
CEILING CONSTRUCTION EXCEPT FOR DROPS TO PLUMBING FIXTURES. NO PIPING IS PERMITTED
AutoCAD SHX Text
TO BE ROUTED EXPOSED UNLESS OTHERWISE PERMITTED BY THE DRAWINGS.
AutoCAD SHX Text
TRENCHING AND BACKFILLING TO BE PERFORMED IN STRICT ACCORDANCE WITH THESE NOTES.
AutoCAD SHX Text
CUT BOTTOM OF TRENCHES TO GRADE. MAKE TRENCHES 12" WIDER THAN THE GREATEST
AutoCAD SHX Text
DIMENSION OF THE PIPE. INSTALL PIPING PROMPTLY AFTER TRENCHING. KEEP TRENCHES OPEN
AutoCAD SHX Text
AS SHORT A TIME AS PRACTICAL. FOR TRENCHES UNDER THE BUILDING, INSTALL PIPES ON A
AutoCAD SHX Text
6" BED OF DAMP SAND. BACK FILL TO BOTTOM OF SLAB WITH DAMP SAND. FOR TRENCHES
AutoCAD SHX Text
OUTSIDE THE BUILDING, INSTALL UNDERGROUND PIPING ON A 6" BED OF DAMP SAND. BACKFILL
AutoCAD SHX Text
TO WITHIN 12" OF FINISH GRADE WITH DAMP SAND. BACKFILL REMAINDER WITH NATIVE SOIL.
AutoCAD SHX Text
DO NOT BACKFILL UNTIL INSTALLATION HAS BEEN APPROVED AND UNTIL PROJECT RECORD
AutoCAD SHX Text
DOCUMENTS HAVE BEEN PROPERLY ANNOTATED.
AutoCAD SHX Text
THOROUGHLY CLEAN ITEMS BEFORE INSTALLATION. CAP PIPE OPENINGS TO EXCLUDE DIRT UNTIL
AutoCAD SHX Text
FIXTURES ARE INSTALLED AS FINAL CONNECTIONS HAVE BEEN MADE.
AutoCAD SHX Text
CUT PIPE ACCURATELY, AND WORK INTO PLACE WITHOUT SPRINGING OR FORCING, PROPERLY
AutoCAD SHX Text
CLEARING WINDOWS, DOORS, AND OTHER OPENINGS. EXCESSIVE CUTTING OR OTHER WAKENING
AutoCAD SHX Text
OF THE BUILDING WILL NOT BE PERMITTED.
AutoCAD SHX Text
SHOW NO TOOL MARKS OR THREADS ON EXPOSED PLATED, POLISHED, OR ENAMELED
AutoCAD SHX Text
CONNECTIONS FROM FIXTURES. TAPE ALL FINISHED SURFACES TO PREVENT DAMAGE DURING
AutoCAD SHX Text
CONSTRUCTION.
AutoCAD SHX Text
MAKE CHANGES IN DIRECTIONS WITH FITTINGS. MAKE CHANGES IN MAIN SIZES WITH ECCENTRIC
AutoCAD SHX Text
REDUCING FITTINGS. UNLESS OTHERWISE NOTED, INSTALL WATER SUPPLY AND RETURN PIPING
AutoCAD SHX Text
WITH STRAIGHT SIDE OF ECCENTRIC FITTINGS AT TOP OF THE PIPE.
AutoCAD SHX Text
ROUTE HORIZONTAL SANITARY AND STORM DRAINAGE PIPING AT A UNIFORM GRADE OF 0.25" PER
AutoCAD SHX Text
FOOT, UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
ROUTE HORIZONTAL WATER SUPPLY PIPING WITH AN ADEQUATE PITCH UPWARDS IN DIRECTION OF
AutoCAD SHX Text
FLOW TO ALLOW COMPLETE DRAINAGE.
AutoCAD SHX Text
SECURELY BOLT ALL EQUIPMENT, ISOLATORS, HANGERS AND SIMILAR ITEMS IN PLACE.
AutoCAD SHX Text
SUPPORT EACH ITEM INDEPENDENTLY FROM OTHER PIPES. DO NOT USE WIRE FOR HANGING OR
AutoCAD SHX Text
STRAPPING PIPES.
AutoCAD SHX Text
PROVIDE COMPLETE DIELECTRIC ISOLATION BETWEEN FERROUS AND NON-FERROUS METALS.
AutoCAD SHX Text
PROVIDE UNION AND SHUT OFF VALVES SUITABLY LOCATED TO FACILITATE MAINTENANCE AND
AutoCAD SHX Text
REMOVAL OF EQUIPMENT AND APPARATUS.
AutoCAD SHX Text
INSTALL PIPING, EQUIPMENT, AND ACCESSORIES TO PERMIT ACCESS FOR MAINTENANCE.
AutoCAD SHX Text
RELOCATE ITEMS AS NECESSARY TO PROVIDE SUCH ACCESS, AND WITHOUT ADDITIONAL COST TO
AutoCAD SHX Text
THE OWNER.
AutoCAD SHX Text
FOR COPPER TUBING PIPE JOINTS, CUT SQUARE, REMOVE BURRS, AND CLEAN INSIDE OF FEMALE
AutoCAD SHX Text
FILLING TO BRIGHT FINISH. APPLY SOLDER FLUX WITH BRUSH TO TUBING. REMOVE INTERNAL
AutoCAD SHX Text
PARTS OF SOLDER-END VALVES PRIOR TO SOLDERING. PROVIDE DIELECTRIC UNIONS AT POINTS
AutoCAD SHX Text
OF CONNECTION OF COPPER TUBING TO FERROUS PIPING AND EQUIPMENT. FOR JOINING
AutoCAD SHX Text
COPPER TUBING, USE 95-5 SOLDER FOR WATER PIPING 3" AND SMALLER, USE "SIL-FOS"
AutoCAD SHX Text
BRAZING FOR WATER PIPING LARGER THAN 3" AND ALL PIPING LOCATED UNDERGROUND.
AutoCAD SHX Text
FOR SCREWED PIPE JOINTS, DEBURR CUTS. DO NOT REAM EXCEEDING INTERNAL DIAMETER OF
AutoCAD SHX Text
THE PIPE. THREAD TO REQUIREMENTS OF ANSI B2.1. USE TEFLON TAPE ON MALE THREAD
AutoCAD SHX Text
PRIOR TO JOINING OTHER SERVICES. USE LITHARGE AND GLYCERIN ON JOINT PRIOR TO
AutoCAD SHX Text
CLEANING FOR AIR AND OIL PIPING.
AutoCAD SHX Text
FOR PVC PIPE JOINTS, THOROUGHLY CLEAN AND DEBURR CUTS. FITTINGS TO PVC JOINTS ARE
AutoCAD SHX Text
TO BE IN ACCORDANCE WITH ASTM D2855, PRIMED THEN SOLVENT WELDED WITH ASTM D2564
AutoCAD SHX Text
SOLVENT CEMENT.
AutoCAD SHX Text
FOR LEAKY JOINTS, REMAKE WITH NEW MATERIAL. REMOVE LEAKING SECTION AND/OR FITTING
AutoCAD SHX Text
AS DIRECTED. DO NOT USE THREAD CEMENT OR SEALANT TO TIGHTEN JOINT.
AutoCAD SHX Text
ALL EXISTING PIPING INSTALLED THROUGH TENANTS SPACE TO BE PROVIDED WITH UL FIRE RATED
AutoCAD SHX Text
ASSEMBLY AS REQUIRED BY AUTHORITY HAVING JURISDICTION (AHJ).
AutoCAD SHX Text
INSULATION:
AutoCAD SHX Text
GENERAL:
AutoCAD SHX Text
INSULATE WATER SYSTEM (DOMESTIC HOT/COLD) AS LISTED BELOW AND TO VALUES NOT LESS
AutoCAD SHX Text
THAN THOSE REQUIRED BY THE MOST CURRENT EDITION OF THE FLORIDA ENERGY EFFICIENCY
AutoCAD SHX Text
CODE FOR BUILDING CONSTRUCTION.
AutoCAD SHX Text
SEE "HANDICAPPED INSULATION" SECTION BELOW FOR ADDITIONAL REQUIREMENTS.
AutoCAD SHX Text
INSULATION TO BE CLOSED CELL ELASTOMERIC FOAM WITH THERMAL CONDUCTIVITY OF NOT MORE
AutoCAD SHX Text
THAN 0.28 BTU*IN/HR*FT*FT*°F AT 75°F MEAN TEMPERATURE, AP ARMAFLEX AS MANUFACTURED
AutoCAD SHX Text
BY ARMSTRONG OR EQUAL.
AutoCAD SHX Text
INSTALL 0.010 INCH EMBOSSED ALUMINUM JACKET LAGGING OVER ALL INSULATED PIPING WHERE
AutoCAD SHX Text
EXPOSED TO THE WEATHER. INCLUDE PREFABRICATED JACKETING AT ALL FITTINGS. UV COATED
AutoCAD SHX Text
PAINTING NOT PERMITTED UNLESS SPECIFICALLY NOTED.
AutoCAD SHX Text
COLD WATER:
AutoCAD SHX Text
FOR FIXTURE TURNOUTS, 3/8" THICK INSULATION MINIMUM
AutoCAD SHX Text
FOR PIPING 2" AND LESS, 3/8" THICK INSULATION MINIMUM
AutoCAD SHX Text
FOR PIPING 2.5" AND GREATER, 1/2" THICK INSULATION MINIMUM
AutoCAD SHX Text
HOT WATER:
AutoCAD SHX Text
FOR FIXTURE TURNOUTS, 1/2" THICK INSULATION MINIMUM
AutoCAD SHX Text
FOR PIPING 2" AND LESS, 1" THICK INSULATION MINIMUM
AutoCAD SHX Text
FOR PIPING 2.5" AND GREATER, 1.5" THICK INSULATION MINIMUM
AutoCAD SHX Text
PIPE WRAPPING:
AutoCAD SHX Text
FOR STEEL PIPING IN CONCRETE OR UNDERGROUND, WRAP AND PROVIDE 50%%% OVERLAP ON
AutoCAD SHX Text
TAPE WELD RUBBER COATING.
AutoCAD SHX Text
SECURE INSPECTION AND TESTING BY AN INDEPENDENT AGENCY APPROVED IN ADVANCE,
AutoCAD SHX Text
DEMONSTRATE PROTECTION BY PASSING 600V HOLIDAY TEST AFTER WRAPPING.
AutoCAD SHX Text
SLEEVES:
AutoCAD SHX Text
WHERE PIPES PASS THROUGH CONCRETE, MASONRY, OR STUD WALLS, OR PASS THROUGH
AutoCAD SHX Text
CEILINGS, PROVIDE RUST-PROOF SLEEVE OF THE SIZE REQUIRED.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
SET PIPE SLEEVES IN PLACE BEFORE CONCRETE IS PLACED.
AutoCAD SHX Text
FOR UNINSULATED PIPE, PROVIDE SLEEVES TWO PIPE SIZES LARGER THAN THE PIPE PASSING
AutoCAD SHX Text
THROUGH, OR PROVIDE A MINIMUM OF 0.5" CLEARANCE BETWEEN INSIDE AND OUTSIDE OF THE
AutoCAD SHX Text
PIPE.
AutoCAD SHX Text
FOR INSULATED PIPE, PROVIDE SLEEVES OF ADEQUATE SIZE TO ACCOMMODATE THE FULL
AutoCAD SHX Text
THICKNESS OF PIPE COVERING, WITH CLEARANCE FOR PACKING AND CAULKING.
AutoCAD SHX Text
CAULK THE SPACE BETWEEN SLEEVE AND PIPE OR PIPE COVERING, USING A NON-COMBUSTIBLE,
AutoCAD SHX Text
PERMANENTLY PLASTIC, WATERPROOF, NON-STAINING COMPOUND WHICH LEAVES A SMOOTH
AutoCAD SHX Text
FINISHED APPEARANCE, OR PACK WITH NONCOMBUSTIBLE ROPE, OR FIBERGLASS TO WITHIN 1/2"
AutoCAD SHX Text
OF BOTH WALL FACES, AND PROVIDE THE WATERPROOF COMPOUNT DESCRIBED ABOVE.
AutoCAD SHX Text
FOR FINISH AND ESCUTCHEONS, SMOOTH UP ROUGH EDGES AROUND SLEEVES WITH PLASTER OR
AutoCAD SHX Text
SPACKLING COMPOUND. PROVIDE 1" WIDE CHROME OR NICKEL PLATED ESCUTCHEONS ON ALL
AutoCAD SHX Text
PIPES EXPOSED TO VIEW WHERE PASSING THROUGH WALL, FLOORS, PARTITIONS, CEILING, AND
AutoCAD SHX Text
SIMILAR LOCATIONS. SIZE THE ESCUTCHEONS TO FIT PIPE AND A COVERING. HOLD
AutoCAD SHX Text
ESCUTCHEONS IN PLACE WITH SET SCREW.
AutoCAD SHX Text
VALVES:
AutoCAD SHX Text
CHECK VALVES:
AutoCAD SHX Text
FOR PIPING 3" AND SMALLER, BRONZE, SCREWED, Y-PATTERN, #200 WOG, SWING CHECK TYPE
AutoCAD SHX Text
PRESSURE REGULATORS:
AutoCAD SHX Text
ALL BRONZE WITH BRASS STRAINER UPSTREAM OF REGULATOR
AutoCAD SHX Text
PARTITION STOP VALVES:
AutoCAD SHX Text
ALL BRONZE, LOOSE KEY TYPE
AutoCAD SHX Text
ALL FIXTURES TO BE FURNISHED WITH CHROMED BRONZE STOP.
AutoCAD SHX Text
ALL VALVES LARGER THAN 3" TO BE FLANGED.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
PROVIDE VALVES IN WATER SUPPLY PIPING SYSTEMS.
AutoCAD SHX Text
IN ADDITION TO THE LOCATIONS SHOWN ON THE FLOOR PLANS, INSTALL VALVES IN LOCATIONS
AutoCAD SHX Text
THAT PERMIT FLUSHING AND STERILIZATION OF THE SYSTEM AS WELL AS PERMIT FOR EASY
AutoCAD SHX Text
ACCESSIBILITY AND MAINTENANCE.
AutoCAD SHX Text
HANGERS:
AutoCAD SHX Text
DRAIN WASTE AND VENT SYSTEM:
AutoCAD SHX Text
ADJUSTABLE RING HANGERS WITH SUPPORTING RODS AND ISOLATORS.
AutoCAD SHX Text
INSTALL RISER CLAMPS AT EACH FLOOR AND AS REQUIRED.
AutoCAD SHX Text
WATER SYSTEM (DOMESTIC HOT/COLD):
AutoCAD SHX Text
SPLIT RING HANGERS WITH SUPPORTING RODS AND ISOLATORS.
AutoCAD SHX Text
INSTALL RISER CLAMPS AT EACH FLOOR AND AS REQUIRED.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
SPACE HANGERS AND SUPPORT FOR HORIZONTAL COPPER TUBING ACCORDING TO THE
AutoCAD SHX Text
FOLLOWING SCHEDULE:
AutoCAD SHX Text
PIPE SIZE
AutoCAD SHX Text
1" AND SMALLER
AutoCAD SHX Text
1-1/4" TO 1-1/2"
AutoCAD SHX Text
2" AND LARGER
AutoCAD SHX Text
SPACE HANGERS AND SUPPORT FOR HORIZONTAL PVC PIPING ACCORDING TO THE FOLLOWING
AutoCAD SHX Text
SCHEDULE:
AutoCAD SHX Text
PIPE SIZE
AutoCAD SHX Text
1" AND SMALLER:
AutoCAD SHX Text
1-1/2" TO 3"
AutoCAD SHX Text
PROVIDE SUPPORT WITHIN 12" OF EACH HORIZONTAL ELBOW.
AutoCAD SHX Text
PROVIDE SWAY BRACING ON ALL HANGERS LONGER THAN 18" IN LENGTH.
AutoCAD SHX Text
SUPPORT VERTICAL PIPING WITH RISER CLAMPS SECURED TO THE PIPING AND RESTING ON THE
AutoCAD SHX Text
BUILDING STRUCTURE. PROVIDE AT EACH FLOOR UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
PROVIDE INSULATION CONTINUOUS THROUGH HANGERS AND ROLLERS. PROTECT INSULATION BY
AutoCAD SHX Text
GALVANIZED STEEL SHIELDS OF SUFFICIENT AREA TO PREVENT MORE THAN 10%%% REDUCTION IN
AutoCAD SHX Text
THICKNESS OF INSULATION.
AutoCAD SHX Text
ARRANGE PIPE SUPPORTS TO PREVENT EXCESSIVE DEFLECTION, AND TO AVOID EXCESSIVE
AutoCAD SHX Text
BENDING STRESS.
AutoCAD SHX Text
SUPPORT PIPING FROM INSERTS OR ANCHORS IN CONCRETE SLABS. PROVIDE THE INSERTS AND
AutoCAD SHX Text
ARRANGE FOR THE PLACING WITH OTHER TRADES.
AutoCAD SHX Text
FOR HUBLESS PIPING, PROVIDE HANGERS ON THE PIPING AT EACH SIDE OF, AND WITHIN 6" OF,
AutoCAD SHX Text
HUBLESS PIPE COUPLING SO THE COUPLING WILL BEAR NO WEIGHT. DO NOT PROVIDE HANGERS
AutoCAD SHX Text
ON COUPLINGS. PROVIDE HANGERS ADEQUATE TO MAINTAIN ALIGNMENT AND TO PREVENT
AutoCAD SHX Text
SAGGING OF THE PIPING, MAKING ADEQUATE PROVISION TO PREVENT SHEARING AND TWISTING OF
AutoCAD SHX Text
THE PIPE AND THE JOINT.
AutoCAD SHX Text
CLEANOUTS:
AutoCAD SHX Text
FLOORS:
AutoCAD SHX Text
PROVIDE AS SCHEDULED ON THE DRAWINGS.
AutoCAD SHX Text
IN FINISHED ROOM FLOORS, PROVIDE ROUND NICKEL-BRONZE TOP.
AutoCAD SHX Text
IN UNFINISHED ROOM FLOORS, PROVIDE ROUND CAST IRON TOP.
AutoCAD SHX Text
IN FLOORS WITH WATERPROOFING MEMBRANE, PROVIDE "FLUSH WITH FLOOR" WITH ADJUSTABLE
AutoCAD SHX Text
WATERTIGHT COVERS AND INTEGRAL ANCHORING FLANGE WITH CLAMPING COVER.
AutoCAD SHX Text
FINISHED WALLS:
AutoCAD SHX Text
PROVIDE AS SCHEDULED ON THE DRAWINGS WITH ROUND CHROME PLATED OR STAINLESS STEEL
AutoCAD SHX Text
ACCESS PLATE AND SCREW.
AutoCAD SHX Text
PROVIDE CLEANOUT PLUGS OF EXTRA HEAVY BRONZE.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
SECURE THE ARCHITECT OR ENGINEER'S APPROVAL OF LOCATIONS FOR CLEANOUTS IN FINISHED
AutoCAD SHX Text
AREAS PRIOR TO INSTALLATION.
AutoCAD SHX Text
PROVIDE CLEANOUTS OF SAME NOMINAL SIZE AS THE PIPES THEY SERVE EXCEPT WHERE
AutoCAD SHX Text
CLEANOUTS ARE REQUIRED IN PIPES 4" AND LARGER, PROVIDE 4" CLEANOUTS.
AutoCAD SHX Text
ALL CLEANOUTS TO BE ACCESSIBLE. AFTER PRESSURE TESTS ARE MADE AND APPROVED,
AutoCAD SHX Text
THOROUGHLY GRAPHITE THE CLEANOUT THREADS.
AutoCAD SHX Text
TRAPS:
AutoCAD SHX Text
ALL TRAPS TO BE CAST BRASS WITH BRASS NUTS AND CHROMED FINISH.
AutoCAD SHX Text
WATER HAMMER ARRESTORS:
AutoCAD SHX Text
PROVIDE STAINLESS STEEL TYPE AS SCHEDULED ON THE DRAWINGS FOR HOT WATER AND COLD
AutoCAD SHX Text
WATER SUPPLY LINES.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
INSTALL ARRESTORS IN UPRIGHT POSITION AT ALL QUICK CLOSING VALVES, SOLENOIDS, ISOLATED
AutoCAD SHX Text
PLUMBING FIXTURES, AND SUPPLY HEADERS AT PLUMBING FIXTURE GROUPS.
AutoCAD SHX Text
IN ADDITION TO LOCATIONS SHOWN ON PLANS, PROVIDE WATER HAMMER ARRESTORS IN
AutoCAD SHX Text
ACCORDANCE WITH PLUMBING AND DRAINAGE INSTITUTE STANDARD WH-201.
AutoCAD SHX Text
INSTALL WATER HAMMER ARRESTORS BEHIND ACCESS PANELS WHERE THEY ARE NOT ACCESSIBLE
AutoCAD SHX Text
BY REMOVABLE CEILING TILES.
AutoCAD SHX Text
WHERE FIXTURES ARE NOT PROTECTED BY WATER HAMMER ARRESTOR, PROVIDE 24" HIGH AIR
AutoCAD SHX Text
CHAMBERS ON EACH WATER SUPPLY, PROPERLY DESIGNED AND SIZED FOR MAINTENANCE AND
AutoCAD SHX Text
DRAINAGE.
AutoCAD SHX Text
BACKFLOW PREVENTERS:
AutoCAD SHX Text
IN FINISHED SPACES, PROVIDE CHROMIUM PLATED FINISH.
AutoCAD SHX Text
FOR FLUSH VALVES, PROVIDE DIAPHRAGM TYPE WITH APPROVED VACUUM BREAKER.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
INSTALL BACKFLOW PREVENTER OR VACUUM BREAKER AT ALL PLUMBING FIXTURES, FAUCETS WITH
AutoCAD SHX Text
HOSE CONNECTIONS, AND ON FIXTURES AS NECESSARY TO PREVENT POSSIBLE BACK-SIPHONAGE,
AutoCAD SHX Text
INCLUDING BUT NOT LIMITED TO HOSE BIBS, SERVICE SINKS, AND AS OTHERWISE INDICATED ON
AutoCAD SHX Text
THE DRAWINGS.
AutoCAD SHX Text
ARRANGE FOR TESTING OF BACKFLOW DEVICES AS REQUIRED BY THE GOVERNMENTAL AGENCIES
AutoCAD SHX Text
HAVING JURISDICTION.
AutoCAD SHX Text
HANDICAPPED INSULATION:
AutoCAD SHX Text
PROVIDE WHERE SHOWN ON THE DRAWINGS AND/OR AS REQUIRED BY GOVERNMENTAL AGENCIES
AutoCAD SHX Text
HAVING JURISDICTION, AT LAVATORIES FOR HANDICAPPED PERSONS PIPE PROTECTION AS
AutoCAD SHX Text
REQUIRED BY CODE, OR AS OTHERWISE INDICATED ON THE DRAWINGS.
AutoCAD SHX Text
PROVIDE TRAP WRAP ON ALL EXPOSED PIPING UNDER LAVATORIES AT LOCATIONS WHERE PIPING
AutoCAD SHX Text
IS EXPOSED.
AutoCAD SHX Text
FIXTURES AND EQUIPMENT:
AutoCAD SHX Text
GENERAL:
AutoCAD SHX Text
PROVIDE FIXTURES AS SCHEDULED ON THE DRAWINGS.
AutoCAD SHX Text
FIXTURES TO MEET OR EXCEED THE REQUIREMENTS OF CSA, ICC/ANSI, OBC, AND ALL OTHER
AutoCAD SHX Text
APPLICABLE STANDARDS/CODES.
AutoCAD SHX Text
WATER CLOSETS:
AutoCAD SHX Text
PROVIDE FIXTURE AND VALVE AS INDICATED ON THE DRAWINGS.
AutoCAD SHX Text
LAVATORY:
AutoCAD SHX Text
PROVIDE FIXTURE AND FAUCET AS INDICATED ON THE DRAWINGS. UNLESS OTHERWISE NOTED,
AutoCAD SHX Text
FURNISH FIXTURE WITH AERATOR, P-TRAP, AND STOPS.
AutoCAD SHX Text
WATER HEATING SYSTEM:
AutoCAD SHX Text
PROVIDE COMPLETE SYSTEM IN A MANNER CONSISTENT WITH THE DRAWINGS, INCLUDING BUT NOT
AutoCAD SHX Text
LIMITED TO WATER HEATER, PUMPS, CONTROLS, AND SUPPLEMENTARY ACCESSORIES
AutoCAD SHX Text
RECOMMENDED BY THE MANUFACTURER.
AutoCAD SHX Text
INSTALLATION REQUIREMENTS:
AutoCAD SHX Text
FIXTURES TO BE LEVEL AND IN PROPER ALIGNMENT WITH RESPECT TO WALLS, FLOORS, AND
AutoCAD SHX Text
WITH FIXTURES EQUALLY SPACED.
AutoCAD SHX Text
FIXTURE WATER SUPPLIES TO BE IN ALIGNMENT WITH EACH OTHER AND THE FIXTURE. PIPING
AutoCAD SHX Text
TO BE INSTALLED LEVEL AND IN PROPER ALIGNMENT WITH RESPECT TO WALLS AND FLOORS AND
AutoCAD SHX Text
WITHOUT VERTICAL OR HORIZONTAL OFFSETS.
AutoCAD SHX Text
GROUT WALL AND FLOOR MOUNTED FIXTURES WATERTIGHT WHERE THE FIXTURES ARE IN CONTACT
AutoCAD SHX Text
WITH WALLS AND FLOORS.
AutoCAD SHX Text
CAULK DECK-MOUNTED TRIM AT THE TIME OF ASSEMBLY, INCLUDING FIXTURE AND CASEWORK
AutoCAD SHX Text
MOUNTED. CAULK SELF-RIMMING SINKS INSTALLED IN CASEWORK.
AutoCAD SHX Text
ALL COLD AND HOT WATER SUPPLY PIPING TO BE TESTED TO NOT LESS THAN 125 PSI
AutoCAD SHX Text
HYDROSTATIC PRESSURE AND HELD FOR NOT LESS THAN 48 HOURS. PROVIDE CHART RECORD
AutoCAD SHX Text
DURING TEST PERIOD FROM CALIBRATED AND SEALED RECORDING METER. ADVISE ENGINEER 48
AutoCAD SHX Text
HOURS PRIOR TO START OF TESTING.
AutoCAD SHX Text
DISINFECT ALL WATER SUPPLY PIPING BY METHOD APPROVED BY ENGINEER. SECURE AND SUBMIT
AutoCAD SHX Text
STERILIZATION CERTIFICATE OF PERFORMANCE STATING SYSTEM CAPACITY, DISINFECTANT APPLIED,
AutoCAD SHX Text
AND RESULTANT RESIDUALS IN PPM AT COMPLETION. AFTER FINAL FLUSHING, SECURE
AutoCAD SHX Text
INDEPENDENT ANALYSIS BY STATE LICENSED LABORATORY OF WATER SAMPLES FROM THE SYSTEM
AutoCAD SHX Text
SHOWING SUITABILITY OF POTABLE WATER SUPPLY, INCLUDING NEGATIVE TEST FOR
AutoCAD SHX Text
COLI-AEROGENE ORGANISMS. PROVIDE A TOTAL PLATE COUNT OF LESS THAN 100 BACTERIA PER
AutoCAD SHX Text
CC, OR EQUAL TO THE CONTROL SAMPLE. IF ANALYSIS RESULTS ARE NOT SATISFACTORY,
AutoCAD SHX Text
REPEAT THE DISINFECTION PROCEDURES AND RETEST UNTIL SPECIFIED STANDARDS ARE
AutoCAD SHX Text
ACHIEVED.
AutoCAD SHX Text
CONTRACTOR TO WARRANTY ALL MATERIALS, WORKMANSHIP, AND SYSTEM PERFORMANCE FOR A
AutoCAD SHX Text
PERIOD OF NOT LESS THAN ONE YEAR FROM TIME OF SUBSTSANTIAL COMPLETION. WHERE
AutoCAD SHX Text
MANUFACTURER'S STANDARD WRITTEN WARRANTIES OR WARRANTY REQUIREMENTS STATED
AutoCAD SHX Text
ELSEWHERE IN THE DRAWINGS ARE OF A PERIOD OF GREATER THAN ONE YEAR, CONTRACTOR OR
AutoCAD SHX Text
MANUFACTURER ARE TO PROVIDE WARRANTY OF LONGER DURATION.
AutoCAD SHX Text
MAXIMUM SPACING ON CENTERS
AutoCAD SHX Text
6'-0"
AutoCAD SHX Text
7'-0"
AutoCAD SHX Text
8'-0"
AutoCAD SHX Text
MAXIMUM SPACING ON CENTERS
AutoCAD SHX Text
3'-0"
AutoCAD SHX Text
4'-0"
AutoCAD SHX Text
ACCESS BOXES:
AutoCAD SHX Text
WALLS:
AutoCAD SHX Text
IN TILE WALLS, PROVIDE WITH POLISHED CHROME PLATE FACE.
AutoCAD SHX Text
IN OTHER FINISHED ROOMS, PROVIDE WITH BONDERIZED PRIME-COATED STEEL FACE AND WITH
AutoCAD SHX Text
ALLEN LOCK.
AutoCAD SHX Text
CEILINGS:
AutoCAD SHX Text
PROVIDE WITH BONDERIZED PRIME-COATED STEEL FACE WITH ALLEN LOCK.
AutoCAD SHX Text
FLOORS:
AutoCAD SHX Text
PROVIDE WITH PLAIN ALUMINUM OR NICKEL-BRONZE NON-SKID TOP.
AutoCAD SHX Text
MIN 2.75" THICK PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING ON ONE SIDE OF WALL AS A PERMANENT FORM
AutoCAD SHX Text
3.75" LIGHTWEIGHT CONCRETE
AutoCAD SHX Text
PIPE MATERIAL AS SCHEDULED
AutoCAD SHX Text
OPTIONAL METALLIC SLEEVE 10" DIA. MAX.; SCH. 5 MIN.; CAST OR GROUTED IN PLACE
AutoCAD SHX Text
3/8" DIAMETER MIN BEAD ALL AROUND
AutoCAD SHX Text
SEALANT OR PUTTY; MIN 1" APPLIED WITHIN ANNULAR SPACE. FLUSH WITH WALL SURFACE. APPLY 3/8" DIA MIN BEAD OF FILL MATERIAL AT PENETRANT/CONCRETE OR PENETRANT/SLEEVE INTERFACE
AutoCAD SHX Text
SECTION VIEW
AutoCAD SHX Text
UL SEALANT OR PUTTY
AutoCAD SHX Text
MINERAL WOOL PACKING MATERIAL
AutoCAD SHX Text
PIPE MATERIAL AS SCHEDULED
AutoCAD SHX Text
OPTIONAL STEEL SLEEVE
AutoCAD SHX Text
THROUGH PENETRATION - CONCRETE WALL OR SLAB UL SYSTEM NO: W-J-1108
AutoCAD SHX Text
PIPE MATERIAL AS SCHEDULED
AutoCAD SHX Text
1/4" MINIMUM CAULK TYPICAL ALL AROUND AND BOTH SIDES. ADDITIONAL FILL MATERIAL TO BE INSTALLED SUCH THAT A MIN 1/4" CROWN IS FORMED AROUND THE PENETRATING ITEM AND LAPPING 1/2" BEYOND THE PERIPHERY OF THE OPENING.
AutoCAD SHX Text
FIRE RATED WALL CONSTRUCTION BY OTHERS
AutoCAD SHX Text
SECTION VIEW
AutoCAD SHX Text
PIPE MATERIAL AS SCHEDULED
AutoCAD SHX Text
ANNULAR SPACE TO BE 1/8" MIN, 1/4" MAX.
AutoCAD SHX Text
THROUGH PENETRATION - FRAME WALL UL SYSTEM NO: W-L-1033
AutoCAD SHX Text
MIN 1" THICK 4 PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING. PACKING MATERIAL TO BE RECESSED FROM BOTH SURFACES OF WALL. TYPICAL ALL AROUND BOTH SIDES.
AutoCAD SHX Text
PLUMBING FLOOR PLAN - WATER SUPPLY
AutoCAD SHX Text
2014 FLORIDA BUILDNG CODE - ENERGY CONSERVATION
AutoCAD SHX Text
2014 FLORIDA BUILDING CODE - EXISTING BUILDING
AutoCAD SHX Text
BALL VALVES: PRESSURE RATING 250 PSI, FULL PORT, BRONZE TRIM BLOWOUT PROOF STEM, LEVER HANDLE, DEZINCIFICATION RESISTANT.
COORDINATE ANY REQUIRED ROOFING WORK WITH VILLAGES SELECTED ROOFING CONTRACTOR. ANY ROOF PENETRATIONS THAT MAY BECOME NECESSARY ARE TO BE PERFORMED BY THIS CONTRACTOR AT GENERAL CONTRACTOR'S EXPENSE.
AutoCAD SHX Text
REMOVE ALL FIXTURES, DEVICES, AND PIPING WITHIN AREA OF WORK AS NECESSARY TO PREPARE FOR ACCOMMODATION OF RENOVATED/NEW SYSTEMS AS SHOWN ON THESE PLANS.
AutoCAD SHX Text
ALL EXISTING PIPING SERVING FIXTURES BEING REMOVED OR RELOCATED ARE TO BE REMOVED. BRANCH PIPING TO BE REMOVED AND CAPPED AT MAIN PIPING CONNECTION. DO NOT REMOVE ANY PIPING SECTION THAT WOULD AFFECT SERVICE FOR ADJACENT FIXTURES THAT WILL REMAIN.
AutoCAD SHX Text
NOTE: EXISTING SYSTEMS CONNECTION POINTS ARE BASED UPON BEST AVAILABLE INFORMATION DURING DESIGN, LIMITED ONLY TO ITEMS THAT ARE CLEARLY VISIBLE PRE-DEMOLITION. CONTRACTOR TO COORDINATE EXACT EXISTING SYSTEMS LOCATIONS AFTER COMMENCEMENT OF DEMOLITION AND PRIOR TO ANY ROUGH-IN WORK. ADVISE ENGINEER IF UTILITY CONNECTION POINTS DIFFER.
AutoCAD SHX Text
2.
AutoCAD SHX Text
ALL SLAB PENETRATIONS TO BE TERMITE TREATED BY LANDLORD'S PREFERRED TREATMENT SERVICE AT TENANT'S EXPENSE TO MAINTAIN EXISTING WARRANTIES.
AutoCAD SHX Text
CO
AutoCAD SHX Text
ZURN
AutoCAD SHX Text
Z1400-BZ
AutoCAD SHX Text
FURNISH WITH TOP TO MATCH
AutoCAD SHX Text
FLOOR COVERING OR SATIN
AutoCAD SHX Text
FINISHED BRONZE.
AutoCAD SHX Text
JOSAM
AutoCAD SHX Text
WATTS
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
LVWH
AutoCAD SHX Text
FAUCET
AutoCAD SHX Text
LAVATORY
AutoCAD SHX Text
PROTECTION
AutoCAD SHX Text
PIPE
AutoCAD SHX Text
KOHLER
AutoCAD SHX Text
K-2035
AutoCAD SHX Text
K-2057
AutoCAD SHX Text
0.5
AutoCAD SHX Text
COLOR TO BE WHITE
AutoCAD SHX Text
DELTA
AutoCAD SHX Text
CHICAGO
AutoCAD SHX Text
AMER STD
AutoCAD SHX Text
BRIGGS
AutoCAD SHX Text
-
AutoCAD SHX Text
0.5
AutoCAD SHX Text
2
AutoCAD SHX Text
0.5 GPM
AutoCAD SHX Text
COLOR TO BE WHITE
AutoCAD SHX Text
FURNISH WITH 1-1/4" CHROMED
AutoCAD SHX Text
BRASS TRAP AND STRAINER.
AutoCAD SHX Text
FINISH TO BE CHROME BRASS. FURNISH W/0.5 GPM AERATOR
AutoCAD SHX Text
T&S
AutoCAD SHX Text
B-2711
AutoCAD SHX Text
KOHLER
AutoCAD SHX Text
LAVATORY- ADA COMPLIANT WALL HUNG
AutoCAD SHX Text
CLEANOUT
AutoCAD SHX Text
EWC
AutoCAD SHX Text
ELKAY
AutoCAD SHX Text
LZSTL8C
AutoCAD SHX Text
FURNISH WITH TOP TO MATCH
AutoCAD SHX Text
FLOOR COVERING OR SATIN
AutoCAD SHX Text
FINISHED BRONZE.
AutoCAD SHX Text
HALSEY
AutoCAD SHX Text
OASIS
AutoCAD SHX Text
0.5
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
0.75 GPM
AutoCAD SHX Text
TAYLOR
AutoCAD SHX Text
8.0 GPH
AutoCAD SHX Text
ELECTRIC WATER COOLER WALL HUNG, HI/LO ADA COMPLIANT
AutoCAD SHX Text
WCPH
AutoCAD SHX Text
SEAT
AutoCAD SHX Text
WATER CLOSET
AutoCAD SHX Text
K-4731-C
AutoCAD SHX Text
-
AutoCAD SHX Text
AMER STD
AutoCAD SHX Text
0.5
AutoCAD SHX Text
-
AutoCAD SHX Text
3
AutoCAD SHX Text
1.4 GPF
AutoCAD SHX Text
K-3493
AutoCAD SHX Text
COLOR TO BE WHITE
AutoCAD SHX Text
COLOR TO BE WHITE
AutoCAD SHX Text
KOHLER
AutoCAD SHX Text
WATER CLOSET- ADA COMPLIANT FLUSH TANK PRESSURE ASSIST ELONGATED 1.4 GPF
AutoCAD SHX Text
KOHLER
AutoCAD SHX Text
BEMIS
AutoCAD SHX Text
AMER STD
AutoCAD SHX Text
JSS
AutoCAD SHX Text
FAUCET
AutoCAD SHX Text
SINK
AutoCAD SHX Text
B-0655-BSTP
AutoCAD SHX Text
BRIGGS
AutoCAD SHX Text
AMER STD
AutoCAD SHX Text
0.5
AutoCAD SHX Text
0.5
AutoCAD SHX Text
3
AutoCAD SHX Text
5.0 GPM
AutoCAD SHX Text
ZURN
AutoCAD SHX Text
MSB2424
AutoCAD SHX Text
FIAT
AutoCAD SHX Text
COLOR TO BE WHITE
AutoCAD SHX Text
T&S
AutoCAD SHX Text
CHICAGO
AutoCAD SHX Text
FINISH TO BE CHROME BRASS
AutoCAD SHX Text
JANITOR SERVICE SINK 3" NPTF TRAP AND STRAINER
AutoCAD SHX Text
EWH-1
AutoCAD SHX Text
EXPANSION
AutoCAD SHX Text
HEATER
AutoCAD SHX Text
ST-5
AutoCAD SHX Text
STATE
AutoCAD SHX Text
RHEEM
AutoCAD SHX Text
0.75
AutoCAD SHX Text
0.75
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
BY DOMESTIC
AutoCAD SHX Text
ENJ-30
AutoCAD SHX Text
A.O. SMITH
AutoCAD SHX Text
-
AutoCAD SHX Text
AMTROL
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
-
AutoCAD SHX Text
ELECTRIC WATER HEATER 30 GALLON 4.5 KW 208V, 1 HEIGHT = 31" EF = 0.95
AutoCAD SHX Text
TANK
AutoCAD SHX Text
(INCLUDED WITH K-2035)
AutoCAD SHX Text
BS
AutoCAD SHX Text
FAUCET
AutoCAD SHX Text
LAVATORY
AutoCAD SHX Text
B-2866-05
AutoCAD SHX Text
JUST
AutoCAD SHX Text
KOHLER
AutoCAD SHX Text
0.5
AutoCAD SHX Text
0.5
AutoCAD SHX Text
2
AutoCAD SHX Text
1.8 GPM
AutoCAD SHX Text
CHICAGO
AutoCAD SHX Text
DLR171610PD
AutoCAD SHX Text
ELKAY
AutoCAD SHX Text
FINISH TO BE STAINLESS STEEL
AutoCAD SHX Text
T&S
AutoCAD SHX Text
DELTA
AutoCAD SHX Text
FINISH TO BE CHROME BRASS
AutoCAD SHX Text
BREAK SINK 17"x16"x10"D 3 FAUCET HOLES
AutoCAD SHX Text
IMB
AutoCAD SHX Text
IPS CORP
AutoCAD SHX Text
BIM875
AutoCAD SHX Text
1/2" COPPER SUPPLY
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
BY DOMESTIC
AutoCAD SHX Text
0.5
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
ICE MACHINE BOX RECESSED 20 GA GALVANIZED 1/4 TURN VALVE
AutoCAD SHX Text
LVWH
AutoCAD SHX Text
WCPH
AutoCAD SHX Text
WCPH
AutoCAD SHX Text
LVWH
AutoCAD SHX Text
EWC
AutoCAD SHX Text
BS
AutoCAD SHX Text
EWH-1
AutoCAD SHX Text
2
AutoCAD SHX Text
JSS
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
0.75"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
0.75"
AutoCAD SHX Text
0.75"
AutoCAD SHX Text
1"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
1
AutoCAD SHX Text
IMB
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
LVWH
AutoCAD SHX Text
WCPH
AutoCAD SHX Text
WCPH
AutoCAD SHX Text
LVWH
AutoCAD SHX Text
JSS
AutoCAD SHX Text
BS
AutoCAD SHX Text
2" V.
AutoCAD SHX Text
2" V.
AutoCAD SHX Text
2" V.
AutoCAD SHX Text
2" V.
AutoCAD SHX Text
2" S.
AutoCAD SHX Text
3" S.
AutoCAD SHX Text
3" S.
AutoCAD SHX Text
2" S.
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
3
AutoCAD SHX Text
3
AutoCAD SHX Text
EWC
AutoCAD SHX Text
2
AutoCAD SHX Text
2" S.
AutoCAD SHX Text
3
AutoCAD SHX Text
4
AutoCAD SHX Text
4
AutoCAD SHX Text
4
AutoCAD SHX Text
CONNECT NEW 3" SANITARY SEWER PIPING TO EXISTING 4" MAIN SANITARY SEWER PIPING IN TENANT SPACE WITHIN 10' OF THIS LOCATION.
AutoCAD SHX Text
1
AutoCAD SHX Text
3
AutoCAD SHX Text
CONNECT NEW 2" VENT PIPING TO EXISTING CONNECTION IN TENANT SPACE WITHIN 10' OF THIS LOCATION.
AutoCAD SHX Text
PROVIDE FIXTURE WITH INTEGRAL TRAP CLEANOUT.
AutoCAD SHX Text
4
AutoCAD SHX Text
CONNECT NEW 2" SANITARY SEWER PIPING TO EXISTING 4" MAIN SANITARY SEWER PIPING IN TENANT SPACE WITHIN 10' OF THIS LOCATION.
AutoCAD SHX Text
2
AutoCAD SHX Text
CONNECT NEW 1" COLD WATER SUPPLY PIPING TO EXISTING MAIN WATER SUPPLY ABOVE CEILING SERVING TENANT SPACE WITHIN 10' OF THIS LOCATION.
AutoCAD SHX Text
1
AutoCAD SHX Text
EWH-1 TO BE MOUNTED ON WALL BRACKET ATTACHED TO EXTERIOR WALL, ABOVE JANITOR SERVICE SINK.
AutoCAD SHX Text
2
AutoCAD SHX Text
30" MAX.
AutoCAD SHX Text
INSTALL 1/4" MIN. DIAMETER ASTM A-36 STEEL ANCHORS TO PROVIDE MINIMUM PULLOUT RESISTANCE OF 800 LBS IN WALL SUBSTRATE (TYPICAL OF 3).
AutoCAD SHX Text
2-1/2" x 2-1/2" x 1/4" ANGLE BRACKET. TWO REQUIRED 30" APART MAXIMUM.
AutoCAD SHX Text
3-1/2" x 3/16" STEEL BAR GRATING WITH SPACER BARS NOT MORE THAN 4" O.C.
AutoCAD SHX Text
3" MAX.
AutoCAD SHX Text
12"
AutoCAD SHX Text
45°
AutoCAD SHX Text
3/8"
AutoCAD SHX Text
3/8"
AutoCAD SHX Text
3/8"
AutoCAD SHX Text
2-1/2" x 2-1/2" x 1/4" ANGLE FRAME.
AutoCAD SHX Text
ALL STEEL TO BE ASTM A-36. ALL WELD METAL TO HAVE MINIMUM STRENGTH OF 60 KPSI (EXX). WALL BRACKET TO BE MOUNTED ABOVE CEILING.
AutoCAD SHX Text
NOTE:
AutoCAD SHX Text
WATER HEATER
AutoCAD SHX Text
0.75" DRAIN PIPE DISCHARGE TO ADJACENT JANITOR SINK INDIRECTLY VIA AIR GAP
AutoCAD SHX Text
PRESSURE AND TEMPERATURE RELIEF VALVE. 0.75" DRAIN PIPE DISCHARGE TO ADJACENT JANITOR SINK INDIRECTLY VIA AIR GAP
EXISTING PACKAGED ROOFTOP UNIT TO REMAIN. BALANCE SYSTEM TO REQUIREMENTS LISTED ABOVE. ADVISE ENGINEER IF ANY VALUES ARE NOT OBTAINABLE.
AutoCAD SHX Text
PACKAGED ROOFTOP UNIT
AutoCAD SHX Text
CARRIER
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
50TFF006
AutoCAD SHX Text
MODEL NUMBER
AutoCAD SHX Text
PERFORMANCE
AutoCAD SHX Text
60.0
AutoCAD SHX Text
TOTAL COOLING CAPACITY (BTUH)
AutoCAD SHX Text
45.0
AutoCAD SHX Text
SENSIBLE COOLING CAPACITY (MBTUH)
AutoCAD SHX Text
7.5
AutoCAD SHX Text
HEATING CAPACITY (KW)
AutoCAD SHX Text
AREA SERVED
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
MODEL NUMBER
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
CFM
AutoCAD SHX Text
RPM
AutoCAD SHX Text
BHP
AutoCAD SHX Text
ESP (IN-H20)
AutoCAD SHX Text
MOTOR HP
AutoCAD SHX Text
VOLTAGE/PHASE
AutoCAD SHX Text
INTERLOCK WITH
AutoCAD SHX Text
ACCESSORIES
AutoCAD SHX Text
ACCESSORIES:
AutoCAD SHX Text
1
AutoCAD SHX Text
VARIABLE SPEED CONTROLLER
AutoCAD SHX Text
2
AutoCAD SHX Text
INTEGRAL DISCONNECT SWITCH
AutoCAD SHX Text
3
AutoCAD SHX Text
BACKDRAFT DAMPER
AutoCAD SHX Text
4
AutoCAD SHX Text
OUTLET SCREEN
AutoCAD SHX Text
5
AutoCAD SHX Text
VIBRATION ISOLATION
AutoCAD SHX Text
ACCEPTABLE EQUAL MANUFACTURERS INCLUDE COOK AND TWIN CITY, OR WHERE APPROVED BY ENGINEER PRIOR TO SUBMISSION OF BID.
AutoCAD SHX Text
UNISEX RR #102
AutoCAD SHX Text
ACCEPTABLE EQUAL MANUFACTURERS FOR AIR DISTRIBUTION DEVICES TO INCLUDE TITUS, PRICE, OR NAILOR, OR WHERE APPROVED BY ENGINEER PRIOR TO SUBMISSION OF BID.
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
5700 AL
AutoCAD SHX Text
SD1
AutoCAD SHX Text
SD2
AutoCAD SHX Text
SD3
AutoCAD SHX Text
SD4
AutoCAD SHX Text
100
AutoCAD SHX Text
175
AutoCAD SHX Text
175
AutoCAD SHX Text
275
AutoCAD SHX Text
<15
AutoCAD SHX Text
<15
AutoCAD SHX Text
<15
AutoCAD SHX Text
<15
AutoCAD SHX Text
0.030
AutoCAD SHX Text
0.043
AutoCAD SHX Text
0.027
AutoCAD SHX Text
0.040
AutoCAD SHX Text
SD5
AutoCAD SHX Text
400
AutoCAD SHX Text
<15
AutoCAD SHX Text
0.058
AutoCAD SHX Text
SD6
AutoCAD SHX Text
550
AutoCAD SHX Text
<15
AutoCAD SHX Text
0.064
AutoCAD SHX Text
METALAIRE
AutoCAD SHX Text
SUPPLY DIFFUSER
AutoCAD SHX Text
RH
AutoCAD SHX Text
12/12
AutoCAD SHX Text
RAG1
AutoCAD SHX Text
12/12
AutoCAD SHX Text
RAG2
AutoCAD SHX Text
12/12
AutoCAD SHX Text
RAG3
AutoCAD SHX Text
22/22
AutoCAD SHX Text
RAG4
AutoCAD SHX Text
14/14
AutoCAD SHX Text
14/14
AutoCAD SHX Text
14/14
AutoCAD SHX Text
24/24
AutoCAD SHX Text
200
AutoCAD SHX Text
300
AutoCAD SHX Text
400
AutoCAD SHX Text
200
AutoCAD SHX Text
19
AutoCAD SHX Text
19
AutoCAD SHX Text
20
AutoCAD SHX Text
19
AutoCAD SHX Text
0.031
AutoCAD SHX Text
0.025
AutoCAD SHX Text
0.020
AutoCAD SHX Text
0.031
AutoCAD SHX Text
12/12, 8" ID
AutoCAD SHX Text
12/12, 10" ID
AutoCAD SHX Text
12/12, 12" ID
AutoCAD SHX Text
22/22, 8" ID
AutoCAD SHX Text
22/22
AutoCAD SHX Text
RAG5
AutoCAD SHX Text
24/24
AutoCAD SHX Text
300
AutoCAD SHX Text
19
AutoCAD SHX Text
0.025
AutoCAD SHX Text
22/22, 10" ID
AutoCAD SHX Text
22/22
AutoCAD SHX Text
RAG6
AutoCAD SHX Text
24/24
AutoCAD SHX Text
400
AutoCAD SHX Text
20
AutoCAD SHX Text
0.020
AutoCAD SHX Text
22/22, 12" ID
AutoCAD SHX Text
METALAIRE
AutoCAD SHX Text
RETURN AIR GRILLE
AutoCAD SHX Text
22/22
AutoCAD SHX Text
RAG7
AutoCAD SHX Text
24/24
AutoCAD SHX Text
800
AutoCAD SHX Text
23
AutoCAD SHX Text
0.025
AutoCAD SHX Text
22/22, 16" ID
AutoCAD SHX Text
22/22
AutoCAD SHX Text
RAG8
AutoCAD SHX Text
24/24
AutoCAD SHX Text
1000
AutoCAD SHX Text
27
AutoCAD SHX Text
0.035
AutoCAD SHX Text
22/22, 18" ID
AutoCAD SHX Text
COLOR OF ALL DEVICES TO BE SELECTED FROM MANUFACTURER'S STANDARD COLORS. ALL DEVICES TO HAVE TRIM AS MANUFACTURER FOR ADJACENT CONSTRUCTIONS. ALL AIR DISTRIBUTION DEVICES TO HAVE FULL FACE FRAMES. ALL DEVICES IN HARD CEILINGS ARE TO BE PROVIDED WITH TRIM RING FOR PLASTER AND SHEET ROCK CEILINGS TO ALLOW DEVICES TO BE LAY-IN. NO EXPOSED SCREW FASTENERS ARE PERMITTED. PAINT DEVICES TO MATCH ADJACENT FINISHES USING PAINTING CRITERIA IN ARCHITECTURAL DOCUMENTS AS WELL AS ANY REFERENCED STANDARDS.
AutoCAD SHX Text
3-5-7
AutoCAD SHX Text
4-7-10
AutoCAD SHX Text
1-3-9
AutoCAD SHX Text
1-3-9
AutoCAD SHX Text
1-3-11
AutoCAD SHX Text
2-4-13
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
6" ID
AutoCAD SHX Text
8" ID
AutoCAD SHX Text
8" ID
AutoCAD SHX Text
10" ID
AutoCAD SHX Text
12" ID
AutoCAD SHX Text
14" ID
AutoCAD SHX Text
6" ID
AutoCAD SHX Text
8" ID
AutoCAD SHX Text
8" ID
AutoCAD SHX Text
10" ID
AutoCAD SHX Text
12" ID
AutoCAD SHX Text
14" ID
AutoCAD SHX Text
12/12
AutoCAD SHX Text
12/12
AutoCAD SHX Text
24/24
AutoCAD SHX Text
24/24
AutoCAD SHX Text
24/24
AutoCAD SHX Text
24/24
AutoCAD SHX Text
ZONE LOAD CALC INFO
AutoCAD SHX Text
APPROXIMATE AREA (SF)
AutoCAD SHX Text
SIZING METHOD
AutoCAD SHX Text
OUTDOOR SUMMER DB/WB (%%DF)
AutoCAD SHX Text
OUTDOOR WINTER DB/WB (%%DF)
AutoCAD SHX Text
GRAINS WATER DIFFERENCE
AutoCAD SHX Text
TOTAL SENSIBLE GAIN (MBH)
AutoCAD SHX Text
TOTAL LATENT GAIN (MBH)
AutoCAD SHX Text
AHSRAE TRANSFER
AutoCAD SHX Text
29/24
AutoCAD SHX Text
69.6
AutoCAD SHX Text
45.6
AutoCAD SHX Text
9.3
AutoCAD SHX Text
1800
AutoCAD SHX Text
95/78
AutoCAD SHX Text
INDOOR DB (%%DF)
AutoCAD SHX Text
74
AutoCAD SHX Text
60
AutoCAD SHX Text
RELATIVE HUMIDITY (%%%)
AutoCAD SHX Text
54.9
AutoCAD SHX Text
TOTAL COOLING (W/OA)
AutoCAD SHX Text
18.0
AutoCAD SHX Text
TOTAL HEATING (W/OA)
AutoCAD SHX Text
FUNCTION METHOD
AutoCAD SHX Text
GREENHECK
AutoCAD SHX Text
SP-B90
AutoCAD SHX Text
DIRECT DRIVE
AutoCAD SHX Text
75
AutoCAD SHX Text
700
AutoCAD SHX Text
0.06
AutoCAD SHX Text
0.25
AutoCAD SHX Text
49.7 WATTS
AutoCAD SHX Text
120/1
AutoCAD SHX Text
LIGHT SWITCH
AutoCAD SHX Text
1,2,3,4,5
AutoCAD SHX Text
UNISEX RR #102
AutoCAD SHX Text
GREENHECK
AutoCAD SHX Text
SP-B90
AutoCAD SHX Text
DIRECT DRIVE
AutoCAD SHX Text
75
AutoCAD SHX Text
700
AutoCAD SHX Text
0.06
AutoCAD SHX Text
0.25
AutoCAD SHX Text
49.7 WATTS
AutoCAD SHX Text
120/1
AutoCAD SHX Text
LIGHT SWITCH
AutoCAD SHX Text
1,2,3,4,5
AutoCAD SHX Text
VIA BLOCK
AutoCAD SHX Text
LOAD SOFTWARE
AutoCAD SHX Text
JANITOR
AutoCAD SHX Text
GREENHECK
AutoCAD SHX Text
SP-B90
AutoCAD SHX Text
DIRECT DRIVE
AutoCAD SHX Text
75
AutoCAD SHX Text
700
AutoCAD SHX Text
0.06
AutoCAD SHX Text
0.25
AutoCAD SHX Text
49.7 WATTS
AutoCAD SHX Text
120/1
AutoCAD SHX Text
LIGHT SWITCH
AutoCAD SHX Text
1,2,3,4,5
AutoCAD SHX Text
1.
AutoCAD SHX Text
CONNECT NEW 8" EXHAUST AIR DUCTWORK TO EXISTING CAPPEDEXHAUST AIR DUCTWORK ABOVE CEILING LEVEL WITHIN 10' OF THIS LOCATION.
AutoCAD SHX Text
1
AutoCAD SHX Text
COORDINATE ANY REQUIRED ROOFING WORK WITH VILLAGES SELECTED ROOFING CONTRACTOR. ANY ROOF PENETRATIONS THAT MAY BECOME NECESSARY ARE TO BE PERFORMED BY THIS CONTRACTOR AT GENERAL CONTRACTOR'S EXPENSE.
AutoCAD SHX Text
LOCATE RTU CONTROLS IN THIS LOCATION. EXTEND CIRCUITRY AS NEEDED WITHIN TENANT SPACE IF EXISTING CIRCUITRY PROVIDED IN SHELL CONSTRUCTION IS NOT OF ADEQUATE LENGTH. INTERLOCK TWO EXISTING UNITS INTO COMMON THERMOSTAT. INTERFACE NEW REMOTE TEMPERATURE SENSORS (RS) TO THIS THERMOSTAT FOR TEMPERATURE AVERAGING BETWEEN THERMOSTAT AND REMOTE SENSOR READINGS.
AutoCAD SHX Text
2
AutoCAD SHX Text
2.
AutoCAD SHX Text
ROUTE DUCTWORK AS TIGHT TO THE UNDERSIDE OF THE STRUCTURE AS POSSIBLE TO ACCOMMODATE CEILING HEIGHT AND DOWNLIGHT FIXTURE DEPTH. ROUTE SMALLER BRANCH DUCT TAPS UP THROUGH JOIST ELEMENT OPENINGS AT LOCATIONS OF DUCT CROSSES AS MAY BE NEEDED. COORDINATE DUCT ROUTING WITH LIGHT FIXTURE AND CEILING ELEVATION PRIOR TO FABRICATION AND ROUGH-IN OF ANY DUCTWORK.
AutoCAD SHX Text
CONNECT NEW 20/14 SUPPLY AIR DUCTWORK TO EXISTING SUPPLY DUCTWORK DROP WITHIN 10' OF THIS LOCATION. CONVERGE OR EXPAND DUCT AS NEEDED TO MATCH SUPPLY DROP SIZE AT CONNECTION POINT.
AutoCAD SHX Text
3
AutoCAD SHX Text
CONNECT NEW 24/14 RETURN AIR DUCTWORK TO EXISTING RETURN DUCTWORK DROP WITHIN 10' OF THIS LOCATION. CONVERGE OR EXPAND DUCT AS NEEDED TO MATCH RETURN DROP SIZE AT CONNECTION POINT. ELBOW CONNECTION TO BE MADE BELOW DROP. NO PLENUM TYPE FITTINGS PERMITTED UNLESS OTHERWISE SHOWN OR NOTED.
AutoCAD SHX Text
4
AutoCAD SHX Text
SYSTEM TO OPERATE ON OWNER'S TIME OF DAY SCHEDULING OR
AutoCAD SHX Text
MANUAL OVERRIDE.
AutoCAD SHX Text
DURING OCCUPIED PERIODS, SYSTEMS TO RUN AT OCCUPIED
AutoCAD SHX Text
SETPOINT TEMPERATURE WITH BLOWER RUNNING CONTINUOUSLY
AutoCAD SHX Text
AND HEATING/COOLING CYCLES OPERATING ON SPACE
AutoCAD SHX Text
TEMPERATURE DEMAND. DURING UNOCCUPIED PERIODS, SYSTEMS
AutoCAD SHX Text
TO RUN AT UNOCCUPIED SETPOINT TEMPERATURE WITH BLOWER
AutoCAD SHX Text
AND HEATING/COOLING STAGES OPERATING ON SPACE
AutoCAD SHX Text
TEMPERATURE DEMAND.
AutoCAD SHX Text
OUTDOOR AIR DAMPER TO OPEN TO MAXIMUM SETPOINT POSITION
AutoCAD SHX Text
WHEN SYSTEM IS IN OCCUPIED PERIODS.
AutoCAD SHX Text
OUTDOOR AIR DAMPER TO CLOSE WHEN THE SYSTEM BLOWER IS
AutoCAD SHX Text
OFF AND IN UNOCCUPIED PERIODS.
AutoCAD SHX Text
INTERFACE NEW REMOTE TEMPERATURE SENSORS TO EXISTING
AutoCAD SHX Text
THERMOSTAT. AVERAGE REMOTE TEMPERATURE SENSOR READINGS.
AutoCAD SHX Text
REMOVE ALL DEVICES, AIR DISTRIBUTION, DUCTWORK, ETC WITHIN AREA OF WORK AS NECESSARY TO PREPARE FOR ACCOMMODATION OF RENOVATED/NEW SYSTEMS AS SHOWN ON THESE PLANS.
AutoCAD SHX Text
NOTE: EXISTING SYSTEMS CONNECTION POINTS ARE BASED UPON BEST AVAILABLE INFORMATION DURING DESIGN, LIMITED ONLY TO ITEMS THAT ARE CLEARLY VISIBLE PRE-DEMOLITION. CONTRACTOR TO COORDINATE EXACT EXISTING SYSTEMS LOCATIONS AFTER COMMENCEMENT OF DEMOLITION AND PRIOR TO ANY ROUGH-IN WORK. ADVISE ENGINEER IF UTILITY CONNECTION POINTS DIFFER.
AutoCAD SHX Text
NO WORK THIS AREA UNLESS OTHERWISE NOTED
ELECTRICAL ABBREVIATIONS
SYMBOL DESCRIPTION
ELECTRICAL SYMBOL LEGEND
DESCRIPTIONSYMBOL
ELECTRICAL INDEX
SHEET TITLESHEET NUMBER
MOUNTINGDESCRIPTIONSYMBOL
ELECTRICAL DEVICE SCHEDULE
MOUNTINGDESCRIPTIONSYMBOL
COMMUNICATIONS DEVICE SCHEDULE
FIRE ALARM SCHEDULE
DESCRIPTIONSYMBOL MANUFACTURER MODEL NUMBER NOTES
CONTROL PANEL AND ACCESSORIES
INITIATING DEVICES
NOTIFICATION/RESPONSE DEVICES
FIRE ALARM RISER NOT TO SCALE
FIRE ALARM CONDUCTOR SIZES
WIRE TYPEDESCRIPTION WIRE COLOR
MFGTAG DESCRIPTION LAMP(S)MODEL NUMBER NOTEVOLT EQUAL MFG.
DUPLEX RECEPTACLE 125 VOLT, 20 AMP, NEMA 5-20R LEVITON #16352
AutoCAD SHX Text
18" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
CEILING SECURE TO STRUCTURE ABOVE
AutoCAD SHX Text
DUPLEX RECEPTACLE 125 VOLT, 20 AMP, NEMA 5-20R LEVITON #16352
AutoCAD SHX Text
CEILING MOUNTED VACANCY SENSOR (PIR/ACTIVE ULTRASONIC) LEVITON #O3C20-MDW; 2000 SF COVERAGE, WHITE HOUSING FURNISH COMPLETE WITH 20A POWER PACKS AND 15A ADD-A-RELAY AS NEEDED OR SHOWN
AutoCAD SHX Text
48" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
CEILING SECURE TO STRUCTURE ABOVE
AutoCAD SHX Text
VACANCY SENSING SWITCH (PIR/ACTIVE ULTRASONIC) LEVITON #OSSMT-GT SET TO 30 MINUTES SEQUENCE OF OPERATION: MANUAL ON, MANUAL/SENSOR OFF
AutoCAD SHX Text
VS
AutoCAD SHX Text
S
AutoCAD SHX Text
CLG
AutoCAD SHX Text
DUPLEX RECEPTACLE 125 VOLT, 20 AMP, NEMA 5-20R LEVITON #16352, SPLIT WIRED FOR SWITCHED CONTROL
AutoCAD SHX Text
18" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
DUPLEX GROUND FAULT RECEPTACLE 125 VOLT, 20 AMP, NEMA 5-20R LEVITON #6899
AutoCAD SHX Text
18" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
G
AutoCAD SHX Text
DUPLEX GROUND FAULT RECEPTACLE 125 VOLT, 20 AMP, NEMA 5-20R LEVITON #6899 W/LEVITON #T5979 IN-USE COVER
AutoCAD SHX Text
26" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
WPG
AutoCAD SHX Text
48" AFF OR 2" ABOVE COUNTER/BACKSPLASH
AutoCAD SHX Text
(2) DUPLEX RECEPTACLES 125 VOLT, 20 AMP, NEMA 5-20R (2) LEVITON #16352
AutoCAD SHX Text
18" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
DUPLEX RECEPTACLE 125 VOLT, 20 AMP, NEMA 5-20R LEVITON #16352
AutoCAD SHX Text
(2) DUPLEX RECEPTACLES 125 VOLT, 20 AMP, NEMA 5-20R (2) LEVITON #16352
AutoCAD SHX Text
48" AFF OR 2" ABOVE COUNTER/BACKSPLASH
AutoCAD SHX Text
FLOOR BOX STEEL CITY 667SC SERIES WITH FEED THROUGH CABLE IN-USE COVER PROVIDE RECEPTACLE COUNT AS SHOWN ON FLOOR PLAN. PROVIDE CONDUIT COUNT AS SHOWN IN DEVICE SCHEDULES
AutoCAD SHX Text
FL
AutoCAD SHX Text
FL
AutoCAD SHX Text
FL
AutoCAD SHX Text
FL
AutoCAD SHX Text
FL
AutoCAD SHX Text
FLUSH SECURE TO STRUCTURE
AutoCAD SHX Text
TWO GANG WALL BOX WITH (3) 0.75" SYSTEMS CONDUITS TO CEILING (1) POWER RECEPTACLE, (1) 4-PORT MULTI-INSERT COVER, LEVITON #41644 (1) CAT6 JACK, LEVITON #61110 (1) F-CONNECTOR, LEVITON #40831 (2) BLANKS, LEVITON #41084 ALL DEVICES UNDER COMMON FACEPLATE
AutoCAD SHX Text
84" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
48" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
TOGGLE SWITCH SINGLE POLE/SINGLE THROW, 20 AMP LEVITON #5621-2
VACANCY SENSING MULTI-WAY SWITCH (PIR/ACTIVE ULTRASONIC) LEVITON #OSSMT SERIES, SET TO 30 MINUTES SEQUENCE OF OPERATION: MANUAL ON, MANUAL/SENSOR OFF
AutoCAD SHX Text
S
AutoCAD SHX Text
3
AutoCAD SHX Text
48" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
VACANCY SENSING DUAL RELAY SWITCH (PIR/ACTIVE ULTRASONIC) LEVITON #OSSMT SERIES, 10 MIN. DELAY OFF ON FAN CIRCUIT SEQUENCE OF OPERATION: MANUAL ON, MANUAL/SENSOR OFF
AutoCAD SHX Text
S
AutoCAD SHX Text
F
AutoCAD SHX Text
48" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
DIMMER PRESET WITH LED LOCATOR, 1000 WATT MINIMUM LEVITON #ILLUMATECH
AutoCAD SHX Text
D
AutoCAD SHX Text
VS
AutoCAD SHX Text
VS
AutoCAD SHX Text
48" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
MOTOR RATED SWITCH SQUARE D CLASS 2510 WITH ENCLOSURE
AutoCAD SHX Text
S
AutoCAD SHX Text
M
AutoCAD SHX Text
MEASUREMENTS ARE TO THE CENTERLINE OF THE DEVICE. DEVICES ARE TO BE MOUNTED IN VERTICAL POSITION UNLESS OTHERWISE NOTED. RECEPTACLES MOUNTED VERTICALLY TO BE MOUNTED WITH GROUND CONTACT IN THE UP POSITION. GFCI RECEPTACLE CIRCUITS MAY BE PROTECTED BY SINGLE GFCI RECEPTACLE AT BEGINNING OF CIRCUIT. RECEPTACLES SERVING ELECTRIC WATER COOLERS TO BE FURNISHED WITH GFCI PROTECTION. DEVICE AND DEVICE PLATE COLORS ARE TO BE WHITE AS SELECTED BY TENANT.
AutoCAD SHX Text
DUPLEX DATA OUTLET BLANK TELCO JUNCTION BOX. STUB (1) 3/4"C. W/90° BENDS AND BUSHINGS INTO ACCESSIBLE CEILING.PROVIDE PULL STRING.
AutoCAD SHX Text
QUAD DATA OUTLET BLANK TELCO JUNCTION BOX. STUB (1) 3/4"C. W/90° BENDS AND BUSHINGS INTO ACCESSIBLE CEILING. PROVIDEPULL STRING AND 4-11/16" BACK BOX.
AutoCAD SHX Text
18" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
18" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
18" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
SIMPLEX DATA OUTLET BLANK TELCO JUNCTION BOX. STUB (1) 3/4"C. W/90° BENDS AND BUSHINGS INTO ACCESSIBLE CEILING.PROVIDE PULL STRING.
AutoCAD SHX Text
CATV OUTLET. PROVIDE 3/4" C. TO TTB. PROVIDE PULL STRING.
AutoCAD SHX Text
REFER TO DRAWINGS
AutoCAD SHX Text
'TTB'
AutoCAD SHX Text
TELEPHONE TERMINAL BOARD 4'x8x0.75" EXTERIOR PLYWOOD WITH 2 COATS OF GRAY FIRE RETARDANT PAINT. PROVIDE #6 CU GROUND TO MAIN ELECTRICAL SERVICE GROUND W/6' SLACK AT BOARD.
AutoCAD SHX Text
18" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
MEASUREMENTS ARE TO CENTER LINE OF DEVICE. CABLE ASSOCIATED WITH CATV SHALL BE #F6SSVV 75 OHM DROP CABLECATV (ETL) AS MANUFACTURED BY COMMSCOPE OR EQUAL. PROVIDE SURGE SUPPRESSION ON ALL LOW VOLTAGE CONDUCTORS ENTERING OR EXITING THE BUILDING, INCLUDING BUT NOT LIMITED TO, VOICE/DATA/CATV/CCTV. DEVICE AND DEVICE PLATE COLORS ARE TO BE WHITE AS SELECTED BY TENANT.
AutoCAD SHX Text
48" AFF UNLESS OTHERWISE NOTED
AutoCAD SHX Text
DIMMER 0-10V LOW VOLTAGE MATCHED TO CONTROL LIGHT FIXTURES ASSOCIATED WITH RESPECTIVE CONTROL DEVICE
AutoCAD SHX Text
D
AutoCAD SHX Text
L
AutoCAD SHX Text
-
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text
FIRE ALARM CONTROL PANEL
AutoCAD SHX Text
FACP
AutoCAD SHX Text
.
AutoCAD SHX Text
-
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text
FIRE ALARM ANNUNCIATOR PANEL
AutoCAD SHX Text
FAAP
AutoCAD SHX Text
.
AutoCAD SHX Text
DOUBLE ACTION UL LISTED FIRE ALARM PULL STATION
AutoCAD SHX Text
.
AutoCAD SHX Text
DUCT SMOKE DETECTOR HOUSING WITH PHOTOELECTRIC DETECTOR AND SAMPLING TUBES (300-4000 FPM VELOCITY). PROVIDE RELAY FOR AHU BLOWER SHUTDOWN
AutoCAD SHX Text
.
AutoCAD SHX Text
STROBE W/LOW PROFILE WHITE HOUSING W/CONCEALED MOUNTING SCREWS W/MINIMUM 75 cd RATING (80-96" AFF)
AutoCAD SHX Text
.
AutoCAD SHX Text
F
AutoCAD SHX Text
75 cd
AutoCAD SHX Text
COMBINATION HORN/STROBE WITH WHITE HOUSING, FIELD SELECTABLE CANDELA SETTING 75 cd RATING CEILING MOUNTED
AutoCAD SHX Text
.
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
75 cd
AutoCAD SHX Text
CLG
AutoCAD SHX Text
NOTE: SEE FLOOR PLANS FOR SPECIFIC DEVICE QUANTITIES AND LOCATIONS.
AutoCAD SHX Text
FACP
AutoCAD SHX Text
FAAP
AutoCAD SHX Text
FASU
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
...
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
...
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
...
AutoCAD SHX Text
...
AutoCAD SHX Text
...
AutoCAD SHX Text
...
AutoCAD SHX Text
AUTO DIALER TO TELEPHONE LINE
AutoCAD SHX Text
TO 120V POWER CIRCUIT
AutoCAD SHX Text
CONTRACTOR TO PROVIDE ANY AND ALL SHOP DRAWINGS, WORKING DRAWINGS, AND DETAILS AS REQUIRED BY LOCAL, STATE, AND NATIONAL AUTHORITIES HAVING JURISDICTION FOR PERFORMANCE OF THE WORK OF THIS FIRE ALARM SYSTEM AS REQUIRED FOR ANY AND ALL SPECIAL PERMITTING. CONTRACTOR TO SUBMIT THESE DRAWINGS AND ALL SYSTEM COMPONENT CUTSHEETS AND DATA FOR ENGINEER'S REVIEW AND COMMENT.
AutoCAD SHX Text
FIRE ALARM SYSTEM PLANS INCLUDED HEREIN ARE DIAGRAMMATIC. CONTRACTOR TO PROVIDE COMPLETE AND OPERATING FIRE ALARM SYSTEM IN MANNER CONSISTENT WITH THESE DOCUMENTS AND NFPA 72 NATIONAL FIRE ALARM CODE.
AutoCAD SHX Text
1.
AutoCAD SHX Text
2.
AutoCAD SHX Text
18/2
AutoCAD SHX Text
ADDRESSIBLE CIRCUIT
AutoCAD SHX Text
RED JACKET BLACK AND RED
AutoCAD SHX Text
14/2
AutoCAD SHX Text
24V DC POWER
AutoCAD SHX Text
WHITE AND BLACK
AutoCAD SHX Text
14/2
AutoCAD SHX Text
STROBE SIGNAL
AutoCAD SHX Text
RED AND BLUE
AutoCAD SHX Text
14/2
AutoCAD SHX Text
MISC. UNDERGROUND
AutoCAD SHX Text
WHITE AND BLACK
AutoCAD SHX Text
FURNISH IN ACCORDANCE WITH THIS SCHEDULE UNLESS OTHERWISE NOTED. ALL WIRES ARE TO BE COPPER, FPL, OR FPLR FOR RISERS UNLESS OTHERWISE NOTED. ALL INITIATING AND SIGNAL CIRCUITS TO BE INSTALLED IN 0.5" METAL CONDUIT.
AutoCAD SHX Text
WORK OF THIS SYSTEM TO BE PERFORMED BY OWNER'S DESIGNATED FIRE ALARM SERVICE CONTRACTOR.
AutoCAD SHX Text
3.
AutoCAD SHX Text
MATCH EXISTING SYSTEM TO GREATEST EXTENT POSSIBLE
AutoCAD SHX Text
MATCH EXISTING SYSTEM TO GREATEST EXTENT POSSIBLE
AutoCAD SHX Text
MATCH EXISTING SYSTEM TO GREATEST EXTENT POSSIBLE
AutoCAD SHX Text
MATCH EXISTING SYSTEM TO GREATEST EXTENT POSSIBLE
AutoCAD SHX Text
...
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
...
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
...
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
...
AutoCAD SHX Text
INTERCEPT EXISTING LOCAL INITIATION AND NOTIFICATION CIRCUITS AND EXTEND TO NEW APPLIANCES. VERIFY AVAILABLE CIRCUIT AND BATTERY CAPACITY PRIOR TO INTERCONNECTION. PROVIDE NEW INITIATION AND NOTIFICATION CIRCUITRY IF EXISTING CIRCUIT IS NOT ADEQUATE.
AutoCAD SHX Text
(NEW)
AutoCAD SHX Text
(NEW)
AutoCAD SHX Text
(NEW)
AutoCAD SHX Text
(NEW)
AutoCAD SHX Text
CLG
AutoCAD SHX Text
CLG
AutoCAD SHX Text
VERIFY ALL REQUIREMENTS WITH LOCAL FIRE MARSHAL PRIOR TO BID. ISSUANCE OF BID INDICATES THIS COORDINATION.
AutoCAD SHX Text
4.
AutoCAD SHX Text
CEILING MOUNTED DEVICES IN ACOUSTIC TILE CEILINGS TO BE MOUNTED IN CENTER OF TILE.
AutoCAD SHX Text
5.
AutoCAD SHX Text
CEILING MOUNTED OCCUPANCY SENSOR (PIR/ACTIVE ULTRASONIC) LEVITON #OSC20-MOW; 2000 SF COVERAGE, WHITE HOUSING FURNISH COMPLETE WITH 20A POWER PACKS AND 15A ADD-A-RELAY AS NEEDED OR SHOWN
AutoCAD SHX Text
CEILING SECURE TO STRUCTURE ABOVE
AutoCAD SHX Text
OS
AutoCAD SHX Text
ELECTRICAL - NOTES
AutoCAD SHX Text
E.002
AutoCAD SHX Text
FURNISHED
AutoCAD SHX Text
120
AutoCAD SHX Text
-
AutoCAD SHX Text
EXIT LIGHT SINGLE FACE LED UNIVERSAL MOUNT/ARROWS THERMOPLASTIC, WHITE, RED LETTERS SELF DIAGNOSTICS
SELECTED BY ARCHITECT OR OWNER PURCHASED AND INSTALLED BY CONTRACTOR $350 ALLOWANCE FOR PURCHASE PER FIXTURE
AutoCAD SHX Text
WALL MOUNTED OVER THE MIRROR LIGHT LED RETROFIT LAMP (CONFIRM EXACT LAMP REQUIREMENTS WITH FIXTURE SELECTED)
AutoCAD SHX Text
A1: 2LP3GS232-26AL-UNV-E5
AutoCAD SHX Text
120/277
AutoCAD SHX Text
1
AutoCAD SHX Text
2x4 LED TROFFER WITH ROOM SIDE HEAT SINK, 5400 LUMEN, 3500K A1: EMERGENCY BATTERY
AutoCAD SHX Text
DAYBRITE
AutoCAD SHX Text
WILLIAMS
AutoCAD SHX Text
COOPER
AutoCAD SHX Text
COLUMBIA
AutoCAD SHX Text
A: 2EVG54L835-4-D-UNV
AutoCAD SHX Text
55W
AutoCAD SHX Text
LED
AutoCAD SHX Text
CEILING MOUNTED
AutoCAD SHX Text
A1: 2EVG54L835-4-D-UNV-
AutoCAD SHX Text
NOTES:
AutoCAD SHX Text
IN LIEU OF THE SPECIFIED TYPE 'A' AND 'A1' FIXTURE IN THE LIGHTING FIXTURE SCHEDULE, PROVIDE ALTERNATE PRICING FOR SUBSTITUTION OF FIXTURE 'A-ALT' AND 'A1-ALT', RESPECTIVELY. AS PART OF ALTERNATE PRICING, INCLUDE REPLACEMENT OF STANDARD SWITCHES SHOWN ON SHEET EL.101 WITH LOW VOLTAGE SWITCH MATCHED TO FIXTURE 'A-ALT' IF NEEDED FOR COMPATIBILITY.
AutoCAD SHX Text
1.
AutoCAD SHX Text
EMLED
AutoCAD SHX Text
WALL MOUNTED
AutoCAD SHX Text
CEILING MOUNTED
AutoCAD SHX Text
CREE
AutoCAD SHX Text
120
AutoCAD SHX Text
-
AutoCAD SHX Text
6x48 LED SURFACE MOUNT LINEAR PRISMATIC ACRYLIC LENS, 4000 LUMENS 3500K
FURNISH CONDUCTORS IN ACCORDANCE WITH THIS SCHEDULE UNLESS OTHERWISE NOTED. ALL WIRES ARE TO BE COPPER, THHN, UNLESS OTHERWISE NOTED. SEE ELECTRICAL NOTES FOR ADDITIONAL CONDUIT AND WIRE INSULATION REQUIREMENTS.
AutoCAD SHX Text
0-20 AMPS
AutoCAD SHX Text
#10
AutoCAD SHX Text
#10
AutoCAD SHX Text
#8
AutoCAD SHX Text
#10
AutoCAD SHX Text
#8
AutoCAD SHX Text
#10
AutoCAD SHX Text
51-60 AMPS
AutoCAD SHX Text
#6
AutoCAD SHX Text
#10
AutoCAD SHX Text
61-70 AMPS
AutoCAD SHX Text
#4
AutoCAD SHX Text
#8
AutoCAD SHX Text
71-80 AMPS
AutoCAD SHX Text
#4
AutoCAD SHX Text
#8
AutoCAD SHX Text
81-90 AMPS
AutoCAD SHX Text
#3
AutoCAD SHX Text
#8
AutoCAD SHX Text
91-100 AMPS
AutoCAD SHX Text
#3
AutoCAD SHX Text
#8
AutoCAD SHX Text
0.75"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
0.75"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
0.50"
AutoCAD SHX Text
1"
AutoCAD SHX Text
0.75"
AutoCAD SHX Text
-
AutoCAD SHX Text
1.25"
AutoCAD SHX Text
1"
AutoCAD SHX Text
-
AutoCAD SHX Text
1.25"
AutoCAD SHX Text
1"
AutoCAD SHX Text
-
AutoCAD SHX Text
1.25"
AutoCAD SHX Text
1"
AutoCAD SHX Text
-
AutoCAD SHX Text
1.25"
AutoCAD SHX Text
1.25"
AutoCAD SHX Text
-
AutoCAD SHX Text
1"
AutoCAD SHX Text
0.75"
AutoCAD SHX Text
-
AutoCAD SHX Text
1.25"
AutoCAD SHX Text
1.25"
AutoCAD SHX Text
-
AutoCAD SHX Text
2
AutoCAD SHX Text
EXISTING 200 AMP FUSES IN EXISTING NEMA 3R ENCLOSURE TO REMAIN.
AutoCAD SHX Text
UTILITY TRANSFORMER
AutoCAD SHX Text
S/N
AutoCAD SHX Text
METER
AutoCAD SHX Text
1 SET OF (4) 3/0 CU THHN/THWN
AutoCAD SHX Text
MAIN ELECTRIC COURTYARD
AutoCAD SHX Text
METER
AutoCAD SHX Text
METER
AutoCAD SHX Text
(EXISTING)
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
'F'
AutoCAD SHX Text
MAIN
AutoCAD SHX Text
208/120V
AutoCAD SHX Text
3%%C, 4W
AutoCAD SHX Text
METER
AutoCAD SHX Text
CARTER HEALTH CARE
AutoCAD SHX Text
+ #6 CU GND IN 3.0"C.
AutoCAD SHX Text
G
AutoCAD SHX Text
F
AutoCAD SHX Text
E
AutoCAD SHX Text
D
AutoCAD SHX Text
TVSS
AutoCAD SHX Text
1
AutoCAD SHX Text
METER
AutoCAD SHX Text
METER
AutoCAD SHX Text
METER
AutoCAD SHX Text
G
AutoCAD SHX Text
J VIA K
AutoCAD SHX Text
K.J.
AutoCAD SHX Text
METER
AutoCAD SHX Text
H-1
AutoCAD SHX Text
200A
AutoCAD SHX Text
208/3
AutoCAD SHX Text
LIGHTS-INTERIOR
AutoCAD SHX Text
LIGHTS-INTERIOR
AutoCAD SHX Text
RECEPTS
AutoCAD SHX Text
RECEPTS
AutoCAD SHX Text
RECEPTS
AutoCAD SHX Text
RECEPTS
AutoCAD SHX Text
RECEPTS
AutoCAD SHX Text
RECEPTS
AutoCAD SHX Text
RECEPTS
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
EWH-1
AutoCAD SHX Text
"
AutoCAD SHX Text
RECEPTS-RTU
AutoCAD SHX Text
RTU-4
AutoCAD SHX Text
TIMECLOCK
AutoCAD SHX Text
34
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
20
AutoCAD SHX Text
20
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
20
AutoCAD SHX Text
1
AutoCAD SHX Text
-
AutoCAD SHX Text
EXISTING 200 AMP PANELBOARD 'F' TO REMAIN.
AutoCAD SHX Text
2
AutoCAD SHX Text
DISCONNECT
AutoCAD SHX Text
PNL 'H-1'
AutoCAD SHX Text
METER
AutoCAD SHX Text
C
AutoCAD SHX Text
METER
AutoCAD SHX Text
B
AutoCAD SHX Text
METER
AutoCAD SHX Text
A
AutoCAD SHX Text
*
AutoCAD SHX Text
NEW LOAD TO BE CONNECTED TO EXISTING CIRCUIT BREAKER MADE
AutoCAD SHX Text
AVAILABLE BY DEMOLITION WORK OF THIS PROJECT.
AutoCAD SHX Text
**
AutoCAD SHX Text
NEW PANEL-MATCHING CIRCUIT BREAKER INSTALLED IN AVAILABLE
AutoCAD SHX Text
CIRCUIT BREAKER SPACE FOR NEW LOAD.
AutoCAD SHX Text
~
AutoCAD SHX Text
EXISTING LOAD ON PANEL/SERVICE TO REMAIN UNCHANGED.
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
*
AutoCAD SHX Text
**
AutoCAD SHX Text
1.
AutoCAD SHX Text
ALL ELECTRICAL DEVICE AND DEVICE PLATE COVERS TO BE AS SELECTED BY TENANT AND APPROVED BY LANDLORD.
AutoCAD SHX Text
2.
AutoCAD SHX Text
UNIT MOUNTED POWER RECEPTACLES ADJACENT TO RTU-4 TO REMAIN.
AutoCAD SHX Text
3.
AutoCAD SHX Text
PROVIDE PUDDY PACK FOR ANY NEW DEVICES BEING MOUNTED IN FIRE RATED WALL ASSEMBLY.
AutoCAD SHX Text
4.
AutoCAD SHX Text
COORDINATE ANY REQUIRED ROOFING WORK WITH VILLAGES SELECTED ROOFING CONTRACTOR. ANY ROOF PENETRATIONS THAT MAY BECOME NECESSARY ARE TO BE PERFORMED BY THIS CONTRACTOR AT TENANT'S EXPENSE.
AutoCAD SHX Text
EXISTING PANELBOARD 'F' TO REMAIN.
AutoCAD SHX Text
1
AutoCAD SHX Text
ELECTRIC WATER HEATER EWH-1: MOTOR RATED SWITCH PROVIDE 3-#10 CU + GND IN 0.75" CONDUIT FROM DISCONNECT TO NEW PANEL-MATCHING CIRCUIT BREAKER. PROVIDE ENGRAVED TAG ON CEILING INDICATING:
AutoCAD SHX Text
3
AutoCAD SHX Text
"WATER HEATER DISCONNECTING MEANS ABOVE"
AutoCAD SHX Text
ALL EXISTING DEVICES IN WALLS BEING REMOVED AS PART OF THIS PROJECT ARE TO BE REMOVED INCLUDING ALL ASSOCIATED ABOVE SLAB BRANCH CIRCUIT CONDUITS AND CONDUCTORS (BACK TO FIRST UPSTREAM JUNCTION BOX). IF REMOVAL OF DEVICE BREAKS THE CIRCUIT TO DOWNSTREAM DEVICES INTERCEPT AND EXTEND AS REQUIRED TO EXTEND CIRCUIT. PROVIDE ANY ASSOCIATED SYSTEM APPURTENANCES AS NEEDED. IF ALL DEVICES AND FIXTURES ON A PARTICULAR CIRCUIT ARE REMOVED, REMOVE ALL CONDUIT AND CONDUCTORS BACK TO BRANCH CIRCUIT BREAKER IN PANELBOARD (TURNING CIRCUIT BREAKER TO 'OFF' POSITION). IF EXISTING UNDER SLAB CONDUITS OBSTRUCT ROUTING OF NEW UTILITY SERVICE OF ANY KIND, EXISTING CONDUIT TO BE REMOVED. DO NOT REMOVE ANY SYSTEM COMPONENT THAT WOULD AFFECT ANY SERVICE FOR ADJACENT SPACES.
AutoCAD SHX Text
NOTE: EXISTING SYSTEMS CONNECTION POINTS ARE BASED UPON BEST AVAILABLE INFORMATION DURING DESIGN, LIMITED ONLY TO ITEMS THAT ARE CLEARLY VISIBLE PRE-DEMOLITION. CONTRACTOR TO COORDINATE EXACT EXISTING SYSTEMS LOCATIONS AFTER COMMENCEMENT OF DEMOLITION AND PRIOR TO ANY ROUGH-IN WORK. ADVISE ENGINEER IF UTILITY CONNECTION POINTS DIFFER.
AutoCAD SHX Text
REMOVE ALL FIXTURES, DEVICES, AND RACEWAYS WITHIN AREA OF WORK AS NECESSARY TO PREPARE FOR ACCOMMODATION OF RENOVATED/NEW SYSTEMS AS SHOWN ON THESE PLANS.
AutoCAD SHX Text
INTERCEPT AND EXTEND EXISTING COMMUNICATIONS CONDUITS WITHIN THIS TENANT SPACE TO NEW TELEPHONE TERMINAL BOARD (TTB) LOCATION SHOWN ON THIS PLAN.
AutoCAD SHX Text
2
AutoCAD SHX Text
EXISTING FIRE ALARM NOTIFICATION AND/OR INITIATION APPLIANCE TO REMAIN. REMOVE AND RE-INSTALL IN SAME LOCATION IF NEEDED TO ACCOMMODATE NEW WALL FINISHES.
MIN 2.75" THICK PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING ON ONE SIDE OF WALL AS A PERMANENT FORM
AutoCAD SHX Text
3.75" LIGHTWEIGHT CONCRETE
AutoCAD SHX Text
PIPE MATERIAL AS SCHEDULED
AutoCAD SHX Text
OPTIONAL METALLIC SLEEVE 10" DIA. MAX.; SCH. 5 MIN.; CAST OR GROUTED IN PLACE
AutoCAD SHX Text
3/8" DIAMETER MIN BEAD ALL AROUND
AutoCAD SHX Text
SEALANT OR PUTTY; MIN 1" APPLIED WITHIN ANNULAR SPACE. FLUSH WITH WALL SURFACE. APPLY 3/8" DIA MIN BEAD OF FILL MATERIAL AT PEENTRANT/CONCRETE OR PEENTRANT/SLEEVE INTERFACE
AutoCAD SHX Text
SECTION VIEW
AutoCAD SHX Text
UL SEALANT OR PUTTY
AutoCAD SHX Text
MINERAL WOOL PACKING MATERIAL
AutoCAD SHX Text
PIPE MATERIAL AS SCHEDULED
AutoCAD SHX Text
OPTIONAL STEEL SLEEVE
AutoCAD SHX Text
THROUGH PENETRATION - CONCRETE WALL OR SLAB UL SYSTEM NO: W-J-1106
AutoCAD SHX Text
PIPE MATERIAL AS SCHEDULED
AutoCAD SHX Text
1/4" MINIMUM CAULK TYPICAL ALL AROUND AND BOTH SIDES. ADDITIONAL FILL MATERIAL TO BE INSTALLED SUCH THAT A MIN 1/4" CROWN IS FORMED AROUND THE PENETRATING ITEM AND LAPPING 1/2" BEYOND THE PERIPHERY OF THE OPENING.
AutoCAD SHX Text
FIRE RATED WALL CONSTRUCTION BY OTHERS
AutoCAD SHX Text
SECTION VIEW
AutoCAD SHX Text
PIPE MATERIAL AS SCHEDULED
AutoCAD SHX Text
ANNULAR SPACE TO BE 1/8" MIN, 1/4" MAX.
AutoCAD SHX Text
THROUGH PENETRATION - FRAME WALL UL SYSTEM NO: W-L-1033
AutoCAD SHX Text
MIN 1" THICK 4 PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING. PACKING MATERIAL TO BE RECESSED FROM BOTH SURFACES OF WALL. TYPICAL ALL AROUND BOTH SIDES.
AutoCAD SHX Text
TO LOAD
AutoCAD SHX Text
PPR
AutoCAD SHX Text
D
AutoCAD SHX Text
CR
AutoCAD SHX Text
CR
AutoCAD SHX Text
D
AutoCAD SHX Text
D
AutoCAD SHX Text
CR
AutoCAD SHX Text
S
AutoCAD SHX Text
TO LOAD
AutoCAD SHX Text
CR
AutoCAD SHX Text
S
AutoCAD SHX Text
TO LOAD
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
TO LOAD
AutoCAD SHX Text
TO CIRCUIT
AutoCAD SHX Text
TO LOAD
AutoCAD SHX Text
PPR
AutoCAD SHX Text
S
AutoCAD SHX Text
CR
AutoCAD SHX Text
VS
AutoCAD SHX Text
VS
AutoCAD SHX Text
VS
AutoCAD SHX Text
CEILING MOUNTED PIR/ULTRASONIC VACANCY SENSOR
AutoCAD SHX Text
D
AutoCAD SHX Text
ON/OFF SWITCH
AutoCAD SHX Text
DIMMER
AutoCAD SHX Text
LOW VOLTAGE POWER PACK WITH RELAY
AutoCAD SHX Text
CONTROL RELAY; ADD-A-RELAY
AutoCAD SHX Text
ALL SPACE LIGHTING ZONES TO BE CONTROLLED BY AN OCCUPANCY OR VACANCY CONTROL SYSTEM. COMMON SIGNAL FOR MULTIPLE OCCUPANCY AND/OR VACANCY SENSORS TO SYSTEM RELAYS TO ENABLE ALL SWITCHING AND DIMMING FUNCTIONS IN ALL SPACE ZONES FOR USE, OPERATION, AND ADJUSTMENT BY USER. OCCUPANCY AND/OR VACANCY SENSING CIRCUIT TO HAVE 10 TO 60 MINUTE ADJUSTABLE INTERVAL. ALL RELAYS FOR POWER AND ZONING REQUIREMENTS TO BE FURNISHED BY OCCUPANCY AND/OR VACANCY SENSOR. SYSTEM TO BE AS MANUFACTURED BY WATTSTOPPER, LEVITON, OR LUTRON. DEFAULT SEQUENCE OF OPERATION TO BE ON BY MANUAL SWITCH, OFF BY MANUAL SWITCH OR OCCUPANCY/VACANCY SENSOR SIGNAL UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
CEILING MOUNTED PIR/ULTRASONIC OCCUPANCY SENSOR
AutoCAD SHX Text
1.
AutoCAD SHX Text
ALL ELECTRICAL DEVICE AND DEVICE PLATE COVER COLORS TO BE AS SELECTED BY TENANT AND APPROVED BY LANDLORD.
AutoCAD SHX Text
2.
AutoCAD SHX Text
UNIT MOUNTED SERVICE LIGHTS ADJACENT TO RTU-4 TO REMAIN.
AutoCAD SHX Text
3.
AutoCAD SHX Text
PROVIDE PUDDY PACK FOR ANY NEW DEVICES BEING MOUNTED IN FIRE RATED WALL ASSEMBLY.
AutoCAD SHX Text
4.
AutoCAD SHX Text
ALL EMERGENCY AND EXIT LIGHT FIXTURES TO BE CONNECTED TO LOCAL LIGHT CIRCUIT AHEAD OF ANY SWITCH OR RELAY UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
LANDLORD PROVIDED TENANT SIGNAGE TO BE CONNECTED TO AVAILABLE SPARE CIRCUIT BREAKER IN EXISTING PANEL 'F' VIA LANDLORD PROVIDED JUNCTION BOX ABOVE ACCESSIBLE CEILING. EXTEND JUNCTION BOX FROM EXTERIOR WALL TO EDGE OF GYPSUM SOFFIT TO MAINTAIN CODE REQUIRED ACCESSIBILITY. CIRCUIT THROUGH HOUSE EXTERIOR LIGHTING CONTROLS VIA LANDLORD PROVIDED JUNCTION BOX AND CONDUIT.
AutoCAD SHX Text
1
AutoCAD SHX Text
EXISTING EXTERIOR LIGHTING CIRCUITED TO HOUSE PANEL TO REMAIN.
AutoCAD SHX Text
2
AutoCAD SHX Text
ALL EXISTING DEVICES IN WALLS BEING REMOVED AS PART OF THIS PROJECT ARE TO BE REMOVED INCLUDING ALL ASSOCIATED ABOVE SLAB BRANCH CIRCUIT CONDUITS AND CONDUCTORS (BACK TO FIRST UPSTREAM JUNCTION BOX). IF REMOVAL OF DEVICE BREAKS THE CIRCUIT TO DOWNSTREAM DEVICES INTERCEPT AND EXTEND AS REQUIRED TO EXTEND CIRCUIT. PROVIDE ANY ASSOCIATED SYSTEM APPURTENANCES AS NEEDED. IF ALL DEVICES AND FIXTURES ON A PARTICULAR CIRCUIT ARE REMOVED, REMOVE ALL CONDUIT AND CONDUCTORS BACK TO BRANCH CIRCUIT BREAKER IN PANELBOARD (TURNING CIRCUIT BREAKER TO 'OFF' POSITION). IF EXISTING UNDER SLAB CONDUITS OBSTRUCT ROUTING OF NEW UTILITY SERVICE OF ANY KIND, EXISTING CONDUIT TO BE REMOVED. DO NOT REMOVE ANY SYSTEM COMPONENT THAT WOULD AFFECT ANY SERVICE FOR ADJACENT SPACES.
AutoCAD SHX Text
NOTE: EXISTING SYSTEMS CONNECTION POINTS ARE BASED UPON BEST AVAILABLE INFORMATION DURING DESIGN, LIMITED ONLY TO ITEMS THAT ARE CLEARLY VISIBLE PRE-DEMOLITION. CONTRACTOR TO COORDINATE EXACT EXISTING SYSTEMS LOCATIONS AFTER COMMENCEMENT OF DEMOLITION AND PRIOR TO ANY ROUGH-IN WORK. ADVISE ENGINEER IF UTILITY CONNECTION POINTS DIFFER.
AutoCAD SHX Text
REMOVE ALL FIXTURES, DEVICES, AND RACEWAYS WITHIN AREA OF WORK AS NECESSARY TO PREPARE FOR ACCOMMODATION OF RENOVATED/NEW SYSTEMS AS SHOWN ON THESE PLANS.
AutoCAD SHX Text
EXISTING EXIT SIGN TO REMAIN. RE-CIRCUIT TO LOCAL 120V LIGHTING CIRCUIT AHEAD OF ANY SWITCH.