Area Served: Car Park
Ventilation Type: Mechanical Ventilation Fans
Brief description: Exhaust through high temperature rated fans.
Fresh Air make-up through Supply Fans.
Design Parameters:
Fire Size (A) = 4 x 3.60
Fire Area = 14.39 m2
Heat Rate ( Qr) = 278.00 kw/m2
Heat Production (Q) = 3999.86 kw
Perimeter ( P ) = 15.19 m
Smoke Layer Height (Y) = 2.50 m
Smoke Layer Depth (Db) = 1.50 m
Air Specific Heat ( Cp) = 1.01 kj/kg.k
Outside Air Temp. (To) = 40 Deg.c 313 k
Calculations
Min. Smoke Flow Rate (Mf) = 0.188 x P x Y1.5
= 11.2912 kg/s
Temperature Rise (Tr) = Q / (Mf x Cp)
= 350.739 Deg.c
Max. Smoke Temp. (Tc) = To + Tr
= 390.739 Deg.0c 664 K
Air Volume Flow rate (Ma) = Mf x Tc / (1.2 x To)
= 19.9532 m3/s
= 42300 cfm
Note:
As per ANSI/ASHRAE standards 62.1.2004
Recommendation provide 3.7 lit/sec/m2
Parking Area= 18000 m2
139900 cfm
Direct drive two speed smoke exhaust fans of 14.1 m3/s (64,000 cfm) rating shall be provided in each parking
zone , Fire rated for 300oC for 1 HR. Motor and Bearing shall be out of air stream.
SMOKE MANAGEMENT DESIGN CALCULATION SHEET
Shall be divided into 4 exhaust fans two speed fire protected each one is 38 000 cfm for ventilation.