Document DatedName 15/11/12
1.00 General Data
Unit weight of Concrete = 25
Unit weight of Reinforcement = 78.5
Bearing Capacity of Soil @ 1m below ground = 150
= 45 m/s
= (Equation 8, BS 6399-2:1997)
= 1 (Cl 2.2.2.2, BS 6399-2:1997)
= 1 (Cl 2.2.2.3, BS 6399-2:1997)
= 1 (Cl 2.2.2.4, BS 6399-2:1997)
= 1 (Cl 2.2.2.5, BS 6399-2:1997)
1.1 For Pylon - 1
1.1.1 Calculation of Loads
= 45 m/s
=
= 1.58 (Table 4, BS 6399-2:1997)
= 71.1 m/s
= (Equation 1, BS 6399-2:1997)
= 3.10
Height of Signboard, H = 10 mWidth of Signboard, W = 3.2 m
Effective area against wind = 32 m2Wind load on the frame = 99.16 kN
5.50 m
3.5
0 m
0.30 m
1.5
0 m
DESIGN OF FOUNDATION FOR SIGNBOARDSPylon 01 & 02
kN/m3
kN/m3
kN/m2
Vb (Basic wind speed)
Vs (site wind speed) Vb x Sa x Sd x Ss x Sp
Sa (Altitude factor)
Sd (Direction Factor)
Ss (Seasonal Factor)
Sp (Probability Factor)
Vs
Ve Vs x Sb
Sb
Ve
qe 0.613 x Ve2
qe kN/m2
SIG
NB
OA
RD
SIGNBOARD
2 of 6
Document DatedName 15/11/12
DESIGN OF FOUNDATION FOR SIGNBOARDSPylon 01 & 02
Length of Foundation, L = 3.5 mWidth of Foundation, B = 5.5 mDepth of Foundation, D = 1.5 m
= 19.25 m2Volume of Concrete in Foundation = 28.875 m3
= 17.65 m3
= 721.875 kN
= 20 kN
Total Downward load, P = 741.875 kN
= 644.56 kN-m
1.1.2 Check for Bearing PressureMax. Pressure at bottom of Foundation = 75.07 kN/m2Min. Pressure at bottom of Foundation = 2.01 kN/m2
1.2 For Pylon - 21.2.1 Calculation of Loads
= 45 m/s
=
= 1.73 (Table 4, BS 6399-2:1997)
= 77.85 m/s
= (Equation 1, BS 6399-2:1997)
= 3.72 kN/m2
Height of Signboard, H = 4 mWidth of Signboard, W = 4.6 m
Effective area against wind = 18.4 m2Wind load on the frame = 68.36 kN
3.50 m
3.9
0 m
FGL 0.30 m
Area of Foundation, Af
Sectional Modulus of Foundation, Zf
Weight of Foundation block, Wf
Weight of Structure, Ws
Moment at the base of Foundation, Mf
Pressure less than 150kN/m2 Hence Safe
Vs
Ve Vs x Sb
Sb
Ve
qe 0.613 x Ve2
qe
SIG
NB
OA
RD
SIGNBOARD
3 of 6
Document DatedName 15/11/12
DESIGN OF FOUNDATION FOR SIGNBOARDSPylon 01 & 02
3.9
0 m
1.0
0 m
Length of Foundation, L = 3.9 mWidth of Foundation, B = 3.5 mDepth of Foundation, D = 1 m
= 13.65 m2Volume of Concrete in Foundation = 13.65 m3
= 7.96 m3
= 341.25 kN
= 20 kN
Total Downward load, P = 361.25 kN
= 205.08 kN-m
1.2.2 Check for Bearing PressureMax. Pressure at bottom of Foundation = 52.22 kN/m2Min. Pressure at bottom of Foundation = 0.71 kN/m2
1.3 Reinforcement Calculation
Reinforcement Provided is 16 dia @ 200 c/c
Area of Foundation, Af
Sectional Modulus of Foundation, Zf
Weight of Foundation block, Wf
Weight of Structure, Ws
Moment at the base of Foundation, Mf
Pressure less than 150kN/m2 Hence Safe
As the foundations provided are of block type, hence structural calculation is not required & reinforcement is provided as per engineering judgement
SIG
NB
OA
RD
4 of 6
Document DatedName 15/11/12
DESIGN OF FOUNDATION FOR SIGNBOARDSPylon 01 & 02
1.00 General Data
Unit weight of Concrete = 25
Unit weight of Reinforcement = 78.5
Bearing Capacity of Soil @ 1m below ground = 150
= 45 m/s
= (Equation 8, BS 6399-2:1997)
= 1 (Cl 2.2.2.2, BS 6399-2:1997)
= 1 (Cl 2.2.2.3, BS 6399-2:1997)
= 1 (Cl 2.2.2.4, BS 6399-2:1997)
= 1 (Cl 2.2.2.5, BS 6399-2:1997)
1.1 For Pylon - 1
1.1.1 Calculation of Loads
= 45 m/s
=
= 1.73 (Table 4, BS 6399-2:1997)
= 77.85 m/s
= (Equation 1, BS 6399-2:1997)
= 3.72 kN/m2
Height of Signboard, H = 10 mWidth of Signboard, W = 3.2 m
Effective area against wind = 32 m2Wind load on the frame = 118.89 kN
0.50 m 5.00 m
3.5
0 m
1.5
0 m
kN/m3
kN/m3
kN/m2
Vb (Basic wind speed)
Vs (site wind speed) Vb x Sa x Sd x Ss x Sp
Sa (Altitude factor)
Sd (Direction Factor)
Ss (Seasonal Factor)
Sp (Probability Factor)
Vs
Ve Vs x Sb
Sb
Ve
qe 0.613 x Ve2
qe
SIG
NB
OA
RD SIG
NB
OA
RD Case (I)
WindCase (II) Wind
A B
Length of Foundation, L = 5.5 mWidth of Foundation, B = 3.5 mDepth of Foundation, D = 1.5 m
= 19.25 m2Volume of Concrete in Foundation = 28.875 m3
= 11.23 m3
= 721.875 kN
= 20 kN
Total Downward load, P = 741.875 kN
Moment at the base of Fdn due to wind, Mw = 772.75 kN-m
Case (I)
Moment about A = 1222.403 kN-mMoment about B = -2857.91 kN-m
Case (II)
Moment about A = 2767.910 kN-mMoment about B = -1312.40 kN-m
1.1.2 Check for Bearing Pressure
Max. Pressure at bottom of Foundation = 285.03 kN/m2Min. Pressure at bottom of Foundation = -215.97 kN/m2
Area of Foundation, Af
Sectional Modulus of Foundation, Zf
Weight of Foundation block, Wf
Weight of Structure, Ws
A B