8/19/2019 Cable Sizing With Clarifications1111111
1/1
Proj.No. :
1361
BUILDING (40) rev 0
CABLE NO.: F-SMSB.40.G.1
destination route/type load
From : AIR 0.380 kVTo : XLPE 238 kW
Length : 150 m 0.8 p.f.
Design Current , Ib = Max. Dem. KW = 452 A
3 x kV x p.f. TO IEC STANDARD.
Nearest Nominal AT , I 500 A . 630 AF frame .
BREAK ER SIZING
Correction Factor,C.F.= Ca x Cg x Cf x Ci (Ca= 1 for ambient temperature) Sewedy p. 15
= 1 x Cg x 1 x 1 (Cg= 0.91 for grouped cables) Sewedy p.17, 18
= 0.91 (Cf=1, for cables protected by C.B.)
(Ci=1, for uninsulated installation)
target Ampacity, It = Ib = 452 = 497 A
C.F. 0.91
Select Cable Size: ccc >= It
ccc = 404 A for S = 185 mm -- Sewedy p. 63 AIR
use 497 2 // cables x 185 mm multicore
404 808 A ( catalog ccc )
Sending End S.E.Imped.(in milli Ohms) = 3.48
Derated Ampacity , Iz= CCC x C.F + Cable Cab.Imped.(in milli Ohms) = 10.44= 735 A ------>> Receiving End R.E.Imped.(in milli Ohms) = 13.92
R.E.Symm.Fault (in kA) = 15.77
CHECK PROTECTION CRITERIA : (=kV*1000/sqrt(3)*R.E.Imped.milli Ohms)
1- That Iz >= In , or ,
735 >= 500 SUCCEED .
CHECK VOLTAGE DROP CRITERIA :
1- Individual V.D. :V.D.1 = mV/A/m / # cables x Ib x L
= 0.241 x 452.4 x 150 mV -> Sewedy p. 23 XLPE
2
= 8.177 V
= 2.152 %
2- Accumulated V.D. :
Acc V.D.= V.D.1 + V.D. on upstream cable
= 2.152 + 0.024 % ---->
= 2.176 % (Should be