Cable Selection13

Embed Size (px)

Citation preview

  • 8/11/2019 Cable Selection13

    1/8

  • 8/11/2019 Cable Selection13

    2/8

    Calculate the design current (Ib).

    Select the type and nominal rating of protective

    device (In). Determine and apply the correction factors to In.

    Select Cable from the table IEE Regulation Iz.

    Calculate the Voltage Drop and check forcompliance.

    Check the circuit complies with shock protection.

    Check the circuit complies with thermal constraints.

  • 8/11/2019 Cable Selection13

    3/8

    The amount of current which flows to the load.

    That current is knows as Designing current Ib.

    The factors which are used to determine thedesigning current are Power factor, Rated Voltage &

    Power of the connected load.

    KW=KVA*P.F.

    Ib=(KVA*1000)/(1.732*V)

  • 8/11/2019 Cable Selection13

    4/8

    The Protective device is used to protect

    the load from overload current and fault

    current.

    So the Cable size with respect to

    protective device rating depends upon

    Amplitude and duration in time.

  • 8/11/2019 Cable Selection13

    5/8

    Ca: Correction factor for ambienttemperature.

    Cg: Correction factor for grouping.Ci: Correction factor for thermal

    insulation.

    So based on these factors the size of thecable is chosen from the table based onIEE Regulation.

  • 8/11/2019 Cable Selection13

    6/8

    A cable's conductor can be seen as an impedance and

    therefore whenever current flows through a cable, there

    will be a voltage drop across it, which can be derived by

    OhmsLaw (i.e. V = IZ).

    The impedance of the cable is a function of the cable size

    (cross-sectional area) and the length of the cable.

    Most cable manufacturers will quote acables

    resistanceand reactance in /km.

  • 8/11/2019 Cable Selection13

    7/8

    Shocks occur when electric currents flow through the body

    between points at different voltage.

    Earth fault occurs when some phase conductor touches

    neutral (for earthed system) or ground potential.

    The shock voltage is calculated by multiplying the

    resistance of the earth conductor over the length of the

    cable by the current that will trip the protective device in

    five seconds . The disconnection time is checked by finding the current

    that will trip the device in the required time (0.4 or 5

    seconds), and determining whether the current flow in an

    earth fault will reach this level.

  • 8/11/2019 Cable Selection13

    8/8

    When the large amount of fault current occurs , the

    temperature of the cable increases which would then

    melt and fire would start. so to reduce the heat the

    proper size of the cable should be selected.

    The size is found using the factors such as K(The

    factors depending on the conductor and insulating

    materials), t(The operating time of the disconnectingdevice in seconds), I(The value of fault current).

    S=Sqrt(It)/K