Modified By: Created On : Rev No: Created By : Document No: Job Number: Project Reference: Killyhevlin WTW-GAC gabriel.cucu 05/08/2014 Rev Date : Cable Analysis Report P1 CIRCUIT DETAILS Id No.: Design Current Ib (A): Cable Reference Name: To: From: Connection Load PROJECT SETTINGS Id No.: Lighting = Source Name: Type: Voltage Drop Limits (%) Other = Switching Scenario Setting: CABLES Type: Phase and Neutral Phase = CPC Neutral = Length (m): CABLE SIZING Cable Type: Ref. Method = Cables in Parallel: Grouping Details: Installation Method: Rating Factor Condition Table Rule Parameter Diversified load current in highest loaded phase Ib = In = Ir = Iz = It = It >= Iz [per parallel cable] VOLTAGE DROP Impedance: Cable Data r = Length (m) Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6 Calculations based on BS 7671:2008 (2011) Appendix 4 Design Current Ib (A/PF) N / x = Ca Cg It mV/A/m: Total m : Temperature Correction Factor (Ct) = Max. Normal (tp) = Actual = Voltage Drop (V/%) 3rd Harmonic 11A P1 MSWB GAC MCC Main cable to Switchboard 398.0 A MSWB Public BS 7671:2008 (2011) 3.00 5.00 Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 Multicore, 90°C thermosetting insulated, armoured Cu Table 4E4 120 34 - On a ladder 240 [a] No TN N/A 1 x 240 [a] 1 x 240 [a] Separate 95 E 4B1 Air Temperature (°C) = 30.0 Ca 1.00 Cg 1.00 = = 0.00 % 1.00 = Ch Ci 1.00 Run Through Insulation = No 52.2 = 398.0 A 500 A N/A 500.0 A 546.0 A In >= Ib -- BS 7671, App. 4.5, Equations 1 [per parallel cable] 0.175 0.125 21 15 120 1.00 1.00 546.0 A 90 61.9 0.9121 398.0 0.84 0.84 0.84 / / 398.0 398.0 0.0 / / / 5.57 5.57 5.57 2.42 2.42 2.42 Qty. & Size (mm²): Size (mm²): Size (mm²): (°C) : L3 L2 L1 L1 L2 L3 Fully Loaded = 5762.3 Cable Energy Loss (W): At Design Current = 5114.3 4C4 = Page 1 of 38 07/08/2014 Printed on: Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17 Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright © Amtech Group Ltd 2013 KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

Cable Analysis

Embed Size (px)

DESCRIPTION

cables

Citation preview

  • Modified By:

    Created On :

    Rev No:Created By :

    Document No:

    Job Number:Project Reference: Killyhevlin WTW-GAC

    gabriel.cucu

    05/08/2014 Rev Date :

    Cable Analysis ReportP1

    CIRCUIT DETAILS

    Id No.:

    Design Current Ib (A):

    Cable Reference Name:

    To:From:Connection

    Load

    PROJECT SETTINGS

    Id No.:

    Lighting =

    Source

    Name: Type:

    Voltage Drop Limits (%) Other =

    Switching Scenario

    Setting:

    CABLES

    Type:Phase and Neutral

    Phase =

    CPC

    Neutral =

    Length (m):

    CABLE SIZING

    Cable Type:

    Ref. Method =

    Cables in Parallel:

    Grouping Details:

    Installation Method:

    Rating Factor Condition Table RuleParameter

    Diversified load current in highest loaded phaseIb =

    In =

    Ir =

    Iz =

    It = It >= Iz [per parallel cable]

    VOLTAGE DROP

    Impedance:

    Cable Data

    r = Length (m)

    Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

    Calculations based on BS 7671:2008 (2011) Appendix 4

    Design Current Ib (A/PF)

    N

    /

    x = Ca Cg It

    mV/A/m:

    Total m :

    Temperature

    Correction Factor (Ct) =

    Max. Normal (tp) = Actual =

    Voltage Drop (V/%)

    3rd Harmonic 11A

    P1

    MSWB GAC MCC

    Main cable to Switchboard 398.0 A

    MSWB

    Public

    BS 7671:2008 (2011)3.00 5.00

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4 120

    34 - On a ladder

    240 [a]

    No

    TN

    N/A

    1 x 240 [a] 1 x 240 [a]

    Separate 95

    E

    4B1Air Temperature (C) = 30.0Ca 1.00

    Cg 1.00

    =

    = 0.00 %1.00=Ch

    Ci 1.00 Run Through Insulation = No 52.2=

    398.0 A

    500 A

    N/A

    500.0 A

    546.0 A

    In >= Ib

    --

    BS 7671, App. 4.5, Equations 1 [per parallel cable]

    0.175 0.125

    21 15

    120 1.00 1.00 546.0 A

    90 61.9

    0.9121

    398.0 0.84 0.84 0.84/ /398.0 398.0 0.0

    / / /5.57 5.57 5.572.42 2.42 2.42

    Qty. & Size (mm):

    Size (mm):

    Size (mm):

    (C) :

    L3L2L1

    L1 L2 L3

    Fully Loaded = 5762.3Cable Energy Loss (W): At Design Current = 5114.3

    4C4=

    Page 1 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • CIRCUIT DETAILS

    Id No.:Cable Reference Name:

    PROTECTIVE DEVICES

    Type:Overcurrent Rating In (A):

    Settings:

    Earth Fault

    Settings:

    Type:

    OVERCURRENT PROTECTION

    Type:Protective Device

    Rating In (A):Overload:

    Motor Rating (A): Design Current Ib (A):

    Breaking Capacity (kA): Icu = Cascaded = Ics =

    Max. Fault Current (kA): Source End = Load End =

    Line ConductorAdiabatic Check

    Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

    EARTH FAULT PROTECTION

    Protection:

    Ze Z1 Max Zs

    Circuit Protective Conductor (CPC) Details

    Section (mm )Conductor

    Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

    Z2

    External

    Zs

    Phase CPC Total

    k Value

    Phase Actual Equivalent

    Total =

    2

    Min. S (mm) =

    Earth Fault Current (kA)

    Uo/(Zs x 1000) =

    Earth Fault Disconnection Time (s)

    Actual from characteristic =

    Maximum for circuit type =

    ERRORS

    COMMENTS

    P1

    Generic BS 88-2 Fuse System E

    Generic BS 88-2 Fuse System E Rating (A): 500

    Generic BS 88-2 Fuse System E

    N/A

    N/A 398.0 A

    Phase fault discrimination check required

    N/A

    80 80No

    25.000 10.467

    Max. disconnection time (s) = (kS/I): 33.47

    Actual disconnection time (s) = 0.71

    5.932

    Generic BS 88-2 Fuse System E Rating (A): 500

    0.065100.056860.033080.014900.00924

    2.92

    5.00 4.06

    Calculated in accordance with BS 7671

    48.53

    Earth Fault Loop Impedance ()

    Adiabatic Check: Minimum Section CPC S = (It)/k

    Separate 95 95.00Actual x (k2/k1) =

    95.00

    It =48.15 x 106 As

    143

    143

    (k1)

    (k2)

    500

    500 Overload Setting Ir (A):

    Minimum Load End Fault Current Ifmin (kA) =

    Source End Earth Fault Current (kA): 25.00

    Page 2 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • Modified By:

    Created On :

    Rev No:Created By :

    Document No:

    Job Number:Project Reference: Killyhevlin WTW-GAC

    gabriel.cucu

    05/08/2014 Rev Date :

    Cable Analysis ReportP10

    CIRCUIT DETAILS

    Id No.:

    Design Current Ib (A):

    Cable Reference Name:

    To:From:Connection

    Load

    PROJECT SETTINGS

    Id No.:

    Lighting =

    Source

    Name: Type:

    Voltage Drop Limits (%) Other =

    Switching Scenario

    Setting:

    CABLES

    Type:Phase and Neutral

    Phase =

    CPC

    Length (m):

    CABLE SIZING

    Cable Type:

    Ref. Method =

    Cables in Parallel:

    Grouping Details:

    Installation Method:

    Rating Factor Condition Table RuleParameter

    Diversified load current in highest loaded phaseIb =

    In =

    Ir =

    Iz =

    It = It >= Iz [per parallel cable]

    VOLTAGE DROP

    Impedance:

    Cable Data

    r = Length (m)

    Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

    Calculations based on BS 7671:2008 (2011) Appendix 4

    Design Current Ib (A/PF)

    N

    /

    x = Ca Cg It

    mV/A/m:

    Total m :

    Temperature

    Correction Factor (Ct) =

    Max. Normal (tp) = Actual =

    Voltage Drop (V/%)

    3rd Harmonic 11A

    P10

    LCS-P1101

    Junction Box 105.4 A

    MSWB

    Public

    BS 7671:2008 (2011)3.00 5.00

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4 80

    34 - On a ladder

    35 [f]

    No

    TN

    N/A

    1 x 35 [f]

    Separate 16

    E

    4B1Air Temperature (C) = 30.0Ca 1.00

    Cg 1.00

    =

    = 0.00 %1.00=Ch

    Ci 1.00 Run Through Insulation = No 52.2=

    105.4 A

    160 A

    105.37 A

    105.4 A

    162.0 A

    In >= Ib

    Motor Overload: GN6, amendment 2, p16

    BS 7671, App. 4.5, Equations 1 [per parallel cable]

    1.15 0.135

    92 11

    80 1.00 1.00 162.0 A

    90 55.4

    0.8918

    105.4 0.81 0.81 0.81/ /105.4 105.4 0.0

    / / /4.43 4.43 4.431.93 1.93 1.93

    Qty. & Size (mm):

    Size (mm):

    Size (mm):

    (C) :

    L3L2L1

    L1 L2 L3

    Fully Loaded = 1769.3Cable Energy Loss (W): At Design Current = 1524.4

    4C4=

    Page 3 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • CIRCUIT DETAILS

    Id No.:Cable Reference Name:

    PROTECTIVE DEVICES

    Type:Overcurrent Rating In (A):

    Settings:

    Earth Fault

    Settings:

    Type:

    OVERCURRENT PROTECTION

    Type:Protective Device

    Rating In (A):Overload:

    Motor Rating (A): Design Current Ib (A):

    Breaking Capacity (kA): Icu = Cascaded = Ics =

    Max. Fault Current (kA): Source End = Load End =

    Line ConductorAdiabatic Check

    Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

    EARTH FAULT PROTECTION

    Protection:

    Ze Z1 Max Zs

    Circuit Protective Conductor (CPC) Details

    Section (mm )Conductor

    Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

    Z2

    External

    Zs

    Phase CPC Total

    k Value

    Phase Actual Equivalent

    Total =

    2

    Min. S (mm) =

    Earth Fault Current (kA)

    Uo/(Zs x 1000) =

    Earth Fault Disconnection Time (s)

    Actual from characteristic =

    Maximum for circuit type =

    ERRORS

    COMMENTS

    P10

    Generic BS 88-2 Fuse System E

    Generic BS 88-2 Fuse System E Rating (A): 160

    Generic BS 88-2 Fuse System E

    105.37 A

    N/A 105.4 A

    Phase fault discrimination check required

    N/A

    80 80No

    10.467 3.766

    CPD Energy Let-through (As): 160.00

    Adiabatic Limit kS (As): 25.05

    3.085

    Phase Conductor Section S (mm) = 35

    Generic BS 88-2 Fuse System E Rating (A): 160

    0.280480.219130.115090.053480.05686

    1.92

    5.00 1.05

    Calculated in accordance with BS 7671

    10.21

    Earth Fault Loop Impedance ()

    Adiabatic Check: Minimum Section CPC S = (It)/k

    Separate 16 16.00Actual x (k2/k1) =

    16.00

    x 10 3

    6x 10

    It =2.13 x 106 As

    143

    143

    (k1)

    (k2)

    160

    160 Motor Overload Setting Ir (A):

    Minimum Load End Fault Current Ifmin (kA) =

    Source End Earth Fault Current (kA): 4.06

    Page 4 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • Modified By:

    Created On :

    Rev No:Created By :

    Document No:

    Job Number:Project Reference: Killyhevlin WTW-GAC

    gabriel.cucu

    05/08/2014 Rev Date :

    Cable Analysis ReportP10-A

    CIRCUIT DETAILS

    Id No.:

    Design Current Ib (A):

    Cable Reference Name:

    To:From:Connection

    Load

    PROJECT SETTINGS

    Id No.:

    Lighting =

    Source

    Name: Type:

    Voltage Drop Limits (%) Other =

    Switching Scenario

    Setting:

    CABLES

    Type:Phase and Neutral

    Phase =

    CPC

    Length (m):

    CABLE SIZING

    Cable Type:

    Ref. Method =

    Cables in Parallel:

    Grouping Details:

    Installation Method:

    Rating Factor Condition Table RuleParameter

    Diversified load current in highest loaded phaseIb =

    In =

    Ir =

    Iz =

    It = It >= Iz [per parallel cable]

    VOLTAGE DROP

    Impedance:

    Cable Data

    r = Length (m)

    Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

    Calculations based on BS 7671:2008 (2011) Appendix 4

    Design Current Ib (A/PF)

    N

    /

    x = Ca Cg It

    mV/A/m:

    Total m :

    Temperature

    Correction Factor (Ct) =

    Max. Normal (tp) = Actual =

    Voltage Drop (V/%)

    3rd Harmonic 11A

    P10-A

    LCS-P1101 P1101

    Motor, Soft Start, three phase 105.4 A

    MSWB

    Public

    BS 7671:2008 (2011)3.00 5.00

    Multi Core 85C rubber insulated Cu

    Multi Core 85C rubber insulated Cu 10

    33 - Spaced from a wall

    25 [a]

    No

    TN

    N/A

    1 x 25 [a]

    Integral 25

    E

    4B1Air Temperature (C) = 30.0Ca 1.00

    Cg 1.00

    =

    = 0.00 %1.00=Ch

    Ci 1.00 Run Through Insulation = No 52.2=

    105.4 A

    160 A

    105.37 A

    105.4 A

    123.0 A

    In >= Ib

    Motor Overload: GN6, amendment 2, p16

    BS 7671, App. 4.5, Equations 1 [per parallel cable]

    1.6 0.15

    16 2

    10 1.00 1.00 123.0 A

    85 70.4

    0.9535

    105.4 0.81 0.81 0.81/ /105.4 105.4 0.0

    / / /0.81 0.81 0.810.35 0.35 0.35

    Qty. & Size (mm):

    Size (mm):

    Size (mm):

    (C) :

    L3L2L1

    L1 L2 L3

    Fully Loaded = 307.7Cable Energy Loss (W): At Design Current = 289.7

    4C4=

    Page 5 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • CIRCUIT DETAILS

    Id No.:Cable Reference Name:

    PROTECTIVE DEVICES

    Type:Overcurrent Rating In (A):

    Settings:

    Earth Fault

    Settings:

    Type:

    OVERCURRENT PROTECTION

    Type:Protective Device

    Rating In (A):Overload:

    Motor Rating (A): Design Current Ib (A):

    Breaking Capacity (kA): Icu = Cascaded = Ics =

    Max. Fault Current (kA): Source End = Load End =

    Line ConductorAdiabatic Check

    Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

    EARTH FAULT PROTECTION

    Protection:

    Ze Z1 Max Zs

    Circuit Protective Conductor (CPC) Details

    Section (mm )Conductor

    Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

    Z2

    External

    Zs

    Phase CPC Total

    k Value

    Phase Actual Equivalent

    Total =

    2

    Min. S (mm) =

    Earth Fault Current (kA)

    Uo/(Zs x 1000) =

    Earth Fault Disconnection Time (s)

    Actual from characteristic =

    Maximum for circuit type =

    ERRORS

    COMMENTS

    P10-A

    Generic BS 88-2 Fuse System E

    Generic BS 88-2 Fuse System E Rating (A): 160

    Generic BS 88-2 Fuse System E

    105.37 A

    160 A 105.4 A

    Phase fault discrimination check required

    N/A

    80 80No

    3.766 3.371

    CPD Energy Let-through (As): 160.00

    Adiabatic Limit kS (As): 11.22

    2.750

    Phase Conductor Section S (mm) = 25

    Generic BS 88-2 Fuse System E Rating (A): 160

    0.280480.237640.009280.009280.21913

    2.62

    5.00 0.97

    Calculated in accordance with BS 7671

    11.73

    Earth Fault Loop Impedance ()

    Adiabatic Check: Minimum Section CPC S = (It)/k

    Integral 25 25.00Actual x (k2/k1) =

    25.00

    x 10 3

    6x 10

    It =2.47 x 106 As

    134

    134

    (k1)

    (k2)

    160

    160 Motor Overload Setting Ir (A):

    Minimum Load End Fault Current Ifmin (kA) =

    Source End Earth Fault Current (kA): 1.05

    Page 6 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • Modified By:

    Created On :

    Rev No:Created By :

    Document No:

    Job Number:Project Reference: Killyhevlin WTW-GAC

    gabriel.cucu

    05/08/2014 Rev Date :

    Cable Analysis ReportP11

    CIRCUIT DETAILS

    Id No.:

    Design Current Ib (A):

    Cable Reference Name:

    To:From:Connection

    Load

    PROJECT SETTINGS

    Id No.:

    Lighting =

    Source

    Name: Type:

    Voltage Drop Limits (%) Other =

    Switching Scenario

    Setting:

    CABLES

    Type:Phase and Neutral

    Phase =

    CPC

    Length (m):

    CABLE SIZING

    Cable Type:

    Ref. Method =

    Cables in Parallel:

    Grouping Details:

    Installation Method:

    Rating Factor Condition Table RuleParameter

    Diversified load current in highest loaded phaseIb =

    In =

    Ir =

    Iz =

    It = It >= Iz [per parallel cable]

    VOLTAGE DROP

    Impedance:

    Cable Data

    r = Length (m)

    Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

    Calculations based on BS 7671:2008 (2011) Appendix 4

    Design Current Ib (A/PF)

    N

    /

    x = Ca Cg It

    mV/A/m:

    Total m :

    Temperature

    Correction Factor (Ct) =

    Max. Normal (tp) = Actual =

    Voltage Drop (V/%)

    3rd Harmonic 11A

    P11

    LCS-P1102

    Junction Box 105.4 A

    MSWB

    Public

    BS 7671:2008 (2011)3.00 5.00

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4 80

    34 - On a ladder

    35 [f]

    No

    TN

    N/A

    1 x 35 [f]

    Separate 16

    E

    4B1Air Temperature (C) = 30.0Ca 1.00

    Cg 1.00

    =

    = 0.00 %1.00=Ch

    Ci 1.00 Run Through Insulation = No 52.2=

    105.4 A

    160 A

    105.37 A

    105.4 A

    162.0 A

    In >= Ib

    Motor Overload: GN6, amendment 2, p16

    BS 7671, App. 4.5, Equations 1 [per parallel cable]

    1.15 0.135

    92 11

    80 1.00 1.00 162.0 A

    90 55.4

    0.8918

    105.4 0.81 0.81 0.81/ /105.4 105.4 0.0

    / / /4.43 4.43 4.431.93 1.93 1.93

    Qty. & Size (mm):

    Size (mm):

    Size (mm):

    (C) :

    L3L2L1

    L1 L2 L3

    Fully Loaded = 1769.3Cable Energy Loss (W): At Design Current = 1524.4

    4C4=

    Page 7 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • CIRCUIT DETAILS

    Id No.:Cable Reference Name:

    PROTECTIVE DEVICES

    Type:Overcurrent Rating In (A):

    Settings:

    Earth Fault

    Settings:

    Type:

    OVERCURRENT PROTECTION

    Type:Protective Device

    Rating In (A):Overload:

    Motor Rating (A): Design Current Ib (A):

    Breaking Capacity (kA): Icu = Cascaded = Ics =

    Max. Fault Current (kA): Source End = Load End =

    Line ConductorAdiabatic Check

    Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

    EARTH FAULT PROTECTION

    Protection:

    Ze Z1 Max Zs

    Circuit Protective Conductor (CPC) Details

    Section (mm )Conductor

    Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

    Z2

    External

    Zs

    Phase CPC Total

    k Value

    Phase Actual Equivalent

    Total =

    2

    Min. S (mm) =

    Earth Fault Current (kA)

    Uo/(Zs x 1000) =

    Earth Fault Disconnection Time (s)

    Actual from characteristic =

    Maximum for circuit type =

    ERRORS

    COMMENTS

    P11

    Generic BS 88-2 Fuse System E

    Generic BS 88-2 Fuse System E Rating (A): 160

    Generic BS 88-2 Fuse System E

    105.37 A

    N/A 105.4 A

    Phase fault discrimination check required

    N/A

    80 80No

    10.467 3.766

    CPD Energy Let-through (As): 160.00

    Adiabatic Limit kS (As): 25.05

    3.085

    Phase Conductor Section S (mm) = 35

    Generic BS 88-2 Fuse System E Rating (A): 160

    0.280480.219130.115090.053480.05686

    1.92

    5.00 1.05

    Calculated in accordance with BS 7671

    10.21

    Earth Fault Loop Impedance ()

    Adiabatic Check: Minimum Section CPC S = (It)/k

    Separate 16 16.00Actual x (k2/k1) =

    16.00

    x 10 3

    6x 10

    It =2.13 x 106 As

    143

    143

    (k1)

    (k2)

    160

    160 Motor Overload Setting Ir (A):

    Minimum Load End Fault Current Ifmin (kA) =

    Source End Earth Fault Current (kA): 4.06

    Page 8 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • Modified By:

    Created On :

    Rev No:Created By :

    Document No:

    Job Number:Project Reference: Killyhevlin WTW-GAC

    gabriel.cucu

    05/08/2014 Rev Date :

    Cable Analysis ReportP11-A

    CIRCUIT DETAILS

    Id No.:

    Design Current Ib (A):

    Cable Reference Name:

    To:From:Connection

    Load

    PROJECT SETTINGS

    Id No.:

    Lighting =

    Source

    Name: Type:

    Voltage Drop Limits (%) Other =

    Switching Scenario

    Setting:

    CABLES

    Type:Phase and Neutral

    Phase =

    CPC

    Length (m):

    CABLE SIZING

    Cable Type:

    Ref. Method =

    Cables in Parallel:

    Grouping Details:

    Installation Method:

    Rating Factor Condition Table RuleParameter

    Diversified load current in highest loaded phaseIb =

    In =

    Ir =

    Iz =

    It = It >= Iz [per parallel cable]

    VOLTAGE DROP

    Impedance:

    Cable Data

    r = Length (m)

    Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

    Calculations based on BS 7671:2008 (2011) Appendix 4

    Design Current Ib (A/PF)

    N

    /

    x = Ca Cg It

    mV/A/m:

    Total m :

    Temperature

    Correction Factor (Ct) =

    Max. Normal (tp) = Actual =

    Voltage Drop (V/%)

    3rd Harmonic 11A

    P11-A

    LCS-P1102 P1102

    Motor, Soft Start, three phase 105.4 A

    MSWB

    Public

    BS 7671:2008 (2011)3.00 5.00

    Multi Core 85C rubber insulated Cu

    Multi Core 85C rubber insulated Cu 10

    33 - Spaced from a wall

    25 [a]

    No

    TN

    N/A

    1 x 25 [a]

    Integral 25

    E

    4B1Air Temperature (C) = 30.0Ca 1.00

    Cg 1.00

    =

    = 0.00 %1.00=Ch

    Ci 1.00 Run Through Insulation = No 52.2=

    105.4 A

    160 A

    105.37 A

    105.4 A

    123.0 A

    In >= Ib

    Motor Overload: GN6, amendment 2, p16

    BS 7671, App. 4.5, Equations 1 [per parallel cable]

    1.6 0.15

    16 2

    10 1.00 1.00 123.0 A

    85 70.4

    0.9535

    105.4 0.81 0.81 0.81/ /105.4 105.4 0.0

    / / /0.81 0.81 0.810.35 0.35 0.35

    Qty. & Size (mm):

    Size (mm):

    Size (mm):

    (C) :

    L3L2L1

    L1 L2 L3

    Fully Loaded = 307.7Cable Energy Loss (W): At Design Current = 289.7

    4C4=

    Page 9 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • CIRCUIT DETAILS

    Id No.:Cable Reference Name:

    PROTECTIVE DEVICES

    Type:Overcurrent Rating In (A):

    Settings:

    Earth Fault

    Settings:

    Type:

    OVERCURRENT PROTECTION

    Type:Protective Device

    Rating In (A):Overload:

    Motor Rating (A): Design Current Ib (A):

    Breaking Capacity (kA): Icu = Cascaded = Ics =

    Max. Fault Current (kA): Source End = Load End =

    Line ConductorAdiabatic Check

    Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

    EARTH FAULT PROTECTION

    Protection:

    Ze Z1 Max Zs

    Circuit Protective Conductor (CPC) Details

    Section (mm )Conductor

    Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

    Z2

    External

    Zs

    Phase CPC Total

    k Value

    Phase Actual Equivalent

    Total =

    2

    Min. S (mm) =

    Earth Fault Current (kA)

    Uo/(Zs x 1000) =

    Earth Fault Disconnection Time (s)

    Actual from characteristic =

    Maximum for circuit type =

    ERRORS

    COMMENTS

    P11-A

    Generic BS 88-2 Fuse System E

    Generic BS 88-2 Fuse System E Rating (A): 160

    Generic BS 88-2 Fuse System E

    105.37 A

    160 A 105.4 A

    Phase fault discrimination check required

    N/A

    80 80No

    3.766 3.371

    CPD Energy Let-through (As): 160.00

    Adiabatic Limit kS (As): 11.22

    2.750

    Phase Conductor Section S (mm) = 25

    Generic BS 88-2 Fuse System E Rating (A): 160

    0.280480.237640.009280.009280.21913

    2.62

    5.00 0.97

    Calculated in accordance with BS 7671

    11.73

    Earth Fault Loop Impedance ()

    Adiabatic Check: Minimum Section CPC S = (It)/k

    Integral 25 25.00Actual x (k2/k1) =

    25.00

    x 10 3

    6x 10

    It =2.47 x 106 As

    134

    134

    (k1)

    (k2)

    160

    160 Motor Overload Setting Ir (A):

    Minimum Load End Fault Current Ifmin (kA) =

    Source End Earth Fault Current (kA): 1.05

    Page 10 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • Modified By:

    Created On :

    Rev No:Created By :

    Document No:

    Job Number:Project Reference: Killyhevlin WTW-GAC

    gabriel.cucu

    05/08/2014 Rev Date :

    Cable Analysis ReportP12

    CIRCUIT DETAILS

    Id No.:

    Design Current Ib (A):

    Cable Reference Name:

    To:From:Connection

    Load

    PROJECT SETTINGS

    Id No.:

    Lighting =

    Source

    Name: Type:

    Voltage Drop Limits (%) Other =

    Switching Scenario

    Setting:

    CABLES

    Type:Phase and Neutral

    Phase =

    CPC

    Length (m):

    CABLE SIZING

    Cable Type:

    Ref. Method =

    Cables in Parallel:

    Grouping Details:

    Installation Method:

    Rating Factor Condition Table RuleParameter

    Diversified load current in highest loaded phaseIb =

    In =

    Ir =

    Iz =

    It = It >= Iz [per parallel cable]

    VOLTAGE DROP

    Impedance:

    Cable Data

    r = Length (m)

    Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

    Calculations based on BS 7671:2008 (2011) Appendix 4

    Design Current Ib (A/PF)

    N

    /

    x = Ca Cg It

    mV/A/m:

    Total m :

    Temperature

    Correction Factor (Ct) =

    Max. Normal (tp) = Actual =

    Voltage Drop (V/%)

    3rd Harmonic 11A

    P12

    LCS-P1103

    Junction Box 105.4 A

    MSWB

    Public

    BS 7671:2008 (2011)3.00 5.00

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4 80

    34 - On a ladder

    25 [a]

    No

    TN

    N/A

    1 x 25 [a]

    Separate 16

    E

    4B1Air Temperature (C) = 30.0Ca 1.00

    Cg 1.00

    =

    = 0.00 %1.00=Ch

    Ci 1.00 Run Through Insulation = No 52.2=

    105.4 A

    160 A

    105.37 A

    105.4 A

    131.0 A

    In >= Ib

    Motor Overload: GN6, amendment 2, p16

    BS 7671, App. 4.5, Equations 1 [per parallel cable]

    1.6 0.14

    128 11

    80 1.00 1.00 131.0 A

    90 68.8

    0.9338

    105.4 0.81 0.81 0.81/ /105.4 105.4 0.0

    / / /6.29 6.29 6.292.73 2.73 2.73

    Qty. & Size (mm):

    Size (mm):

    Size (mm):

    (C) :

    L3L2L1

    L1 L2 L3

    Fully Loaded = 2461.7Cable Energy Loss (W): At Design Current = 2253.2

    4C4=

    Page 11 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • CIRCUIT DETAILS

    Id No.:Cable Reference Name:

    PROTECTIVE DEVICES

    Type:Overcurrent Rating In (A):

    Settings:

    Earth Fault

    Settings:

    Type:

    OVERCURRENT PROTECTION

    Type:Protective Device

    Rating In (A):Overload:

    Motor Rating (A): Design Current Ib (A):

    Breaking Capacity (kA): Icu = Cascaded = Ics =

    Max. Fault Current (kA): Source End = Load End =

    Line ConductorAdiabatic Check

    Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

    EARTH FAULT PROTECTION

    Protection:

    Ze Z1 Max Zs

    Circuit Protective Conductor (CPC) Details

    Section (mm )Conductor

    Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

    Z2

    External

    Zs

    Phase CPC Total

    k Value

    Phase Actual Equivalent

    Total =

    2

    Min. S (mm) =

    Earth Fault Current (kA)

    Uo/(Zs x 1000) =

    Earth Fault Disconnection Time (s)

    Actual from characteristic =

    Maximum for circuit type =

    ERRORS

    COMMENTS

    P12

    Generic BS 88-2 Fuse System E

    Generic BS 88-2 Fuse System E Rating (A): 160

    Generic BS 88-2 Fuse System E

    105.37 A

    N/A 105.4 A

    Phase fault discrimination check required

    N/A

    80 80No

    10.467 3.007

    CPD Energy Let-through (As): 160.00

    Adiabatic Limit kS (As): 12.78

    2.431

    Phase Conductor Section S (mm) = 25

    Generic BS 88-2 Fuse System E Rating (A): 160

    0.280480.239680.115090.074180.05686

    2.70

    5.00 0.96

    Calculated in accordance with BS 7671

    11.08

    Earth Fault Loop Impedance ()

    Adiabatic Check: Minimum Section CPC S = (It)/k

    Separate 16 16.00Actual x (k2/k1) =

    16.00

    x 10 3

    6x 10

    It =2.51 x 106 As

    143

    143

    (k1)

    (k2)

    160

    160 Motor Overload Setting Ir (A):

    Minimum Load End Fault Current Ifmin (kA) =

    Source End Earth Fault Current (kA): 4.06

    Page 12 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • Modified By:

    Created On :

    Rev No:Created By :

    Document No:

    Job Number:Project Reference: Killyhevlin WTW-GAC

    gabriel.cucu

    05/08/2014 Rev Date :

    Cable Analysis ReportP12-A

    CIRCUIT DETAILS

    Id No.:

    Design Current Ib (A):

    Cable Reference Name:

    To:From:Connection

    Load

    PROJECT SETTINGS

    Id No.:

    Lighting =

    Source

    Name: Type:

    Voltage Drop Limits (%) Other =

    Switching Scenario

    Setting:

    CABLES

    Type:Phase and Neutral

    Phase =

    CPC

    Length (m):

    CABLE SIZING

    Cable Type:

    Ref. Method =

    Cables in Parallel:

    Grouping Details:

    Installation Method:

    Rating Factor Condition Table RuleParameter

    Diversified load current in highest loaded phaseIb =

    In =

    Ir =

    Iz =

    It = It >= Iz [per parallel cable]

    VOLTAGE DROP

    Impedance:

    Cable Data

    r = Length (m)

    Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

    Calculations based on BS 7671:2008 (2011) Appendix 4

    Design Current Ib (A/PF)

    N

    /

    x = Ca Cg It

    mV/A/m:

    Total m :

    Temperature

    Correction Factor (Ct) =

    Max. Normal (tp) = Actual =

    Voltage Drop (V/%)

    3rd Harmonic 11A

    P12-A

    LCS-P1103 P1103

    Motor, Soft Start, three phase 105.4 A

    MSWB

    Public

    BS 7671:2008 (2011)3.00 5.00

    Multi Core 85C rubber insulated Cu

    Multi Core 85C rubber insulated Cu 10

    33 - Spaced from a wall

    35 [f]

    No

    TN

    N/A

    1 x 35 [f]

    Integral 35

    E

    4B1Air Temperature (C) = 30.0Ca 1.00

    Cg 1.00

    =

    = 0.00 %1.00=Ch

    Ci 1.00 Run Through Insulation = No 52.2=

    105.4 A

    160 A

    105.37 A

    105.4 A

    151.0 A

    In >= Ib

    Motor Overload: GN6, amendment 2, p16

    BS 7671, App. 4.5, Equations 1 [per parallel cable]

    1.15 0.15

    12 2

    10 1.00 1.00 151.0 A

    85 56.8

    0.9104

    105.4 0.81 0.81 0.81/ /105.4 105.4 0.0

    / / /0.57 0.57 0.570.25 0.25 0.25

    Qty. & Size (mm):

    Size (mm):

    Size (mm):

    (C) :

    L3L2L1

    L1 L2 L3

    Fully Loaded = 221.2Cable Energy Loss (W): At Design Current = 196.2

    4C4=

    Page 13 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • CIRCUIT DETAILS

    Id No.:Cable Reference Name:

    PROTECTIVE DEVICES

    Type:Overcurrent Rating In (A):

    Settings:

    Earth Fault

    Settings:

    Type:

    OVERCURRENT PROTECTION

    Type:Protective Device

    Rating In (A):Overload:

    Motor Rating (A): Design Current Ib (A):

    Breaking Capacity (kA): Icu = Cascaded = Ics =

    Max. Fault Current (kA): Source End = Load End =

    Line ConductorAdiabatic Check

    Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

    EARTH FAULT PROTECTION

    Protection:

    Ze Z1 Max Zs

    Circuit Protective Conductor (CPC) Details

    Section (mm )Conductor

    Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

    Z2

    External

    Zs

    Phase CPC Total

    k Value

    Phase Actual Equivalent

    Total =

    2

    Min. S (mm) =

    Earth Fault Current (kA)

    Uo/(Zs x 1000) =

    Earth Fault Disconnection Time (s)

    Actual from characteristic =

    Maximum for circuit type =

    ERRORS

    COMMENTS

    P12-A

    Generic BS 88-2 Fuse System E

    Generic BS 88-2 Fuse System E Rating (A): 160

    Generic BS 88-2 Fuse System E

    105.37 A

    160 A 105.4 A

    Phase fault discrimination check required

    N/A

    80 80No

    3.007 2.813

    Max. disconnection time (s) = (kS/I): 4.26

    Actual disconnection time (s) = 0.12

    2.271

    Generic BS 88-2 Fuse System E Rating (A): 160

    0.280480.253070.006700.006700.23968

    3.32

    5.00 0.91

    Calculated in accordance with BS 7671

    12.42

    Earth Fault Loop Impedance ()

    Adiabatic Check: Minimum Section CPC S = (It)/k

    Integral 35 35.00Actual x (k2/k1) =

    35.00

    It =2.77 x 106 As

    134

    134

    (k1)

    (k2)

    160

    160 Motor Overload Setting Ir (A):

    Minimum Load End Fault Current Ifmin (kA) =

    Source End Earth Fault Current (kA): 0.96

    Page 14 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • Modified By:

    Created On :

    Rev No:Created By :

    Document No:

    Job Number:Project Reference: Killyhevlin WTW-GAC

    gabriel.cucu

    05/08/2014 Rev Date :

    Cable Analysis ReportP13

    CIRCUIT DETAILS

    Id No.:

    Design Current Ib (A):

    Cable Reference Name:

    To:From:Connection

    Load

    PROJECT SETTINGS

    Id No.:

    Lighting =

    Source

    Name: Type:

    Voltage Drop Limits (%) Other =

    Switching Scenario

    Setting:

    CABLES

    Type:Phase and Neutral

    Phase =

    CPC

    Neutral =

    Length (m):

    CABLE SIZING

    Cable Type:

    Ref. Method =

    Cables in Parallel:

    Grouping Details:

    Installation Method:

    Rating Factor Condition Table RuleParameter

    Diversified load current in highest loaded phaseIb =

    In =

    Ir =

    Iz =

    It = It >= Iz [per parallel cable]

    VOLTAGE DROP

    Impedance:

    Cable Data

    r = Length (m)

    Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

    Calculations based on BS 7671:2008 (2011) Appendix 4

    Design Current Ib (A/PF)

    N

    /

    x = Ca Cg It

    mV/A/m:

    Total m :

    Temperature

    Correction Factor (Ct) =

    Max. Normal (tp) = Actual =

    Voltage Drop (V/%)

    3rd Harmonic 11A

    P13

    LCS-P1201

    Junction Box 73.1 A

    MSWB

    Public

    BS 7671:2008 (2011)3.00 5.00

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4 50

    34 - On a ladder

    10 [a]

    No

    2 Derating for 2 circuits/cables

    TN

    N/A

    1 x 10 [a] 1 x 10 [a]

    Armour 43

    E

    4B1Air Temperature (C) = 30.0Ca 1.00

    Cg 0.87

    =

    = 0.00 %1.00=Ch

    Ci 1.00 Run Through Insulation = No 52.2=

    73.1 A

    100 A

    105.37 A

    63.1 A

    78.0 A

    In >= Ib

    Motor Overload: GN6, amendment 2, p16

    BS 7671, App. 4.5, Equations 3/4 [per parallel cable]

    4 0

    200 0

    50 1.00 0.87 78.0 A

    90 99.7

    1.0000

    73.1 0.78 0.78 0.78/ /73.1 73.1 0.0

    / / /

    Total Number of Grouped Circuits =

    Subject to simultaneous overload = No No. of ladders = 1

    No. of circuits per ladder = 2

    6.59 6.59 6.592.86 2.86 2.86

    Qty. & Size (mm):

    Size (mm):

    Size (mm):

    (C) :

    L3L2L1

    L1 L2 L3

    Fully Loaded = 1853.6Cable Energy Loss (W): At Design Current = 1925.6

    Arrangement: Horizontal Touching

    4C4=

    Page 15 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • CIRCUIT DETAILS

    Id No.:Cable Reference Name:

    PROTECTIVE DEVICES

    Type:Overcurrent Rating In (A):

    Settings:

    Earth Fault

    Settings:

    Type:

    OVERCURRENT PROTECTION

    Type:Protective Device

    Rating In (A):Overload:

    Motor Rating (A): Design Current Ib (A):

    Breaking Capacity (kA): Icu = Cascaded = Ics =

    Max. Fault Current (kA): Source End = Load End =

    Line ConductorAdiabatic Check

    Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

    EARTH FAULT PROTECTION

    Protection:

    Ze Z1 Max Zs

    Circuit Protective Conductor (CPC) Details

    Section (mm )Conductor

    Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

    Z2

    External

    Zs

    Phase CPC Total

    k Value

    Phase Actual Equivalent

    Total =

    2

    Min. S (mm) =

    Earth Fault Current (kA)

    Uo/(Zs x 1000) =

    Earth Fault Disconnection Time (s)

    Actual from characteristic =

    Maximum for circuit type =

    ERRORS

    COMMENTS

    P13

    Generic BS 88-2 Fuse System E

    Generic BS 88-2 Fuse System E Rating (A): 100

    Generic BS 88-2 Fuse System E

    105.37 A

    N/A 73.1 A

    Phase fault discrimination check required

    N/A

    80 80No

    10.467 3.670

    CPD Energy Let-through (As): 60.00

    Adiabatic Limit kS (As): 2.04

    1.559

    Phase Conductor Section S (mm) = 10

    Generic BS 88-2 Fuse System E Rating (A): 100

    0.442310.341840.234950.057740.05686

    1.77

    5.00 0.68

    Calculated in accordance with BS 7671

    6.29

    Armour

    Earth Fault Loop Impedance ()

    Adiabatic Check: Minimum Section CPC S = (It)/k

    43 13.83Actual x (k2/k1) =

    13.83

    x 10 3

    6x 10

    It =809.26 x 103 As

    143

    46

    (k1)

    (k2)

    100

    100 Motor Overload Setting Ir (A):

    Minimum Load End Fault Current Ifmin (kA) =

    Source End Earth Fault Current (kA): 4.06

    Page 16 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • Modified By:

    Created On :

    Rev No:Created By :

    Document No:

    Job Number:Project Reference: Killyhevlin WTW-GAC

    gabriel.cucu

    05/08/2014 Rev Date :

    Cable Analysis ReportP13-A

    CIRCUIT DETAILS

    Id No.:

    Design Current Ib (A):

    Cable Reference Name:

    To:From:Connection

    Load

    PROJECT SETTINGS

    Id No.:

    Lighting =

    Source

    Name: Type:

    Voltage Drop Limits (%) Other =

    Switching Scenario

    Setting:

    CABLES

    Type:Phase and Neutral

    Phase =

    CPC

    Neutral =

    Length (m):

    CABLE SIZING

    Cable Type:

    Ref. Method =

    Cables in Parallel:

    Grouping Details:

    Installation Method:

    Rating Factor Condition Table RuleParameter

    Diversified load current in highest loaded phaseIb =

    In =

    Ir =

    Iz =

    It = It >= Iz [per parallel cable]

    VOLTAGE DROP

    Impedance:

    Cable Data

    r = Length (m)

    Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

    Calculations based on BS 7671:2008 (2011) Appendix 4

    Design Current Ib (A/PF)

    N

    /

    x = Ca Cg It

    mV/A/m:

    Total m :

    Temperature

    Correction Factor (Ct) =

    Max. Normal (tp) = Actual =

    Voltage Drop (V/%)

    3rd Harmonic 11A

    P13-A

    LCS-P1201 P1201

    Motor, Star delta started, three phase and neutralat GAC MCC 73.1 A

    MSWB

    Public

    BS 7671:2008 (2011)3.00 5.00

    Multi Core 85C rubber insulated Cu

    Multi Core 85C rubber insulated Cu 5

    33 - Spaced from a wall

    35 [f]

    No

    TN

    N/A

    1 x 35 [f] 1 x 35 [a]

    Separate 10

    E

    4B1Air Temperature (C) = 30.0Ca 1.00

    Cg 1.00

    =

    = 0.00 %1.00=Ch

    Ci 1.00 Run Through Insulation = No 52.2=

    73.1 A

    100 A

    105.37 A

    60.8 A

    151.0 A

    In >= Ib

    Motor Overload: GN6, amendment 2, p16

    BS 7671, App. 4.5, Equations 1 [per parallel cable]

    1.15 0.15

    6 1

    5 1.00 1.00 151.0 A

    85 42.9

    0.8664

    73.1 0.78 0.78 0.78/ /73.1 73.1 0.0

    / / /0.18 0.18 0.180.08 0.08 0.08

    Qty. & Size (mm):

    Size (mm):

    Size (mm):

    (C) :

    L3L2L1

    L1 L2 L3

    Fully Loaded = 53.3Cable Energy Loss (W): At Design Current = 44.3

    4C4=

    Page 17 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • CIRCUIT DETAILS

    Id No.:Cable Reference Name:

    PROTECTIVE DEVICES

    Type:Overcurrent Rating In (A):

    Settings:

    Earth Fault

    Settings:

    Type:

    OVERCURRENT PROTECTION

    Type:Protective Device

    Rating In (A):Overload:

    Motor Rating (A): Design Current Ib (A):

    Breaking Capacity (kA): Icu = Cascaded = Ics =

    Max. Fault Current (kA): Source End = Load End =

    Line ConductorAdiabatic Check

    Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

    EARTH FAULT PROTECTION

    Protection:

    Ze Z1 Max Zs

    Circuit Protective Conductor (CPC) Details

    Section (mm )Conductor

    Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

    Z2

    External

    Zs

    Phase CPC Total

    k Value

    Phase Actual Equivalent

    Total =

    2

    Min. S (mm) =

    Earth Fault Current (kA)

    Uo/(Zs x 1000) =

    Earth Fault Disconnection Time (s)

    Actual from characteristic =

    Maximum for circuit type =

    ERRORS

    COMMENTS

    P13-A

    Generic BS 88-2 Fuse System E

    Generic BS 88-2 Fuse System E Rating (A): 100

    Generic BS 88-2 Fuse System E

    105.37 A

    100 A 73.1 A

    Phase fault discrimination check required

    N/A

    80 80No

    3.670 3.594

    CPD Energy Let-through (As): 60.00

    Adiabatic Limit kS (As): 22.00

    1.525

    Phase Conductor Section S (mm) = 35

    Generic BS 88-2 Fuse System E Rating (A): 100

    0.442310.354470.011000.001670.34184

    2.02

    5.00 0.65

    Calculated in accordance with BS 7671

    6.92

    Earth Fault Loop Impedance ()

    Adiabatic Check: Minimum Section CPC S = (It)/k

    Separate 10 8.58Actual x (k2/k1) =

    8.58

    x 10 3

    6x 10

    It =859.32 x 103 As

    134

    115

    (k1)

    (k2)

    100

    100 Motor Overload Setting Ir (A):

    Minimum Load End Fault Current Ifmin (kA) =

    Source End Earth Fault Current (kA): 0.68

    Page 18 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • Modified By:

    Created On :

    Rev No:Created By :

    Document No:

    Job Number:Project Reference: Killyhevlin WTW-GAC

    gabriel.cucu

    05/08/2014 Rev Date :

    Cable Analysis ReportP14

    CIRCUIT DETAILS

    Id No.:

    Design Current Ib (A):

    Cable Reference Name:

    To:From:Connection

    Load

    PROJECT SETTINGS

    Id No.:

    Lighting =

    Source

    Name: Type:

    Voltage Drop Limits (%) Other =

    Switching Scenario

    Setting:

    CABLES

    Type:Phase and Neutral

    Phase =

    CPC

    Neutral =

    Length (m):

    CABLE SIZING

    Cable Type:

    Ref. Method =

    Cables in Parallel:

    Grouping Details:

    Installation Method:

    Rating Factor Condition Table RuleParameter

    Diversified load current in highest loaded phaseIb =

    In =

    Ir =

    Iz =

    It = It >= Iz [per parallel cable]

    VOLTAGE DROP

    Impedance:

    Cable Data

    r = Length (m)

    Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

    Calculations based on BS 7671:2008 (2011) Appendix 4

    Design Current Ib (A/PF)

    N

    /

    x = Ca Cg It

    mV/A/m:

    Total m :

    Temperature

    Correction Factor (Ct) =

    Max. Normal (tp) = Actual =

    Voltage Drop (V/%)

    3rd Harmonic 11A

    P14

    LCS-P1202

    Junction Box 73.1 A

    MSWB

    Public

    BS 7671:2008 (2011)3.00 5.00

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4 50

    34 - On a ladder

    35 [f]

    No

    2 Derating for 2 circuits/cables

    TN

    N/A

    1 x 35 [f] 1 x 35 [f]

    Armour 80

    E

    4B1Air Temperature (C) = 30.0Ca 1.00

    Cg 0.87

    =

    = 0.00 %1.00=Ch

    Ci 1.00 Run Through Insulation = No 52.2=

    73.1 A

    100 A

    105.37 A

    63.1 A

    162.0 A

    In >= Ib

    Motor Overload: GN6, amendment 2, p16

    BS 7671, App. 4.5, Equations 3/4 [per parallel cable]

    1.15 0.135

    58 7

    50 1.00 0.87 162.0 A

    90 46.2

    0.8963

    73.1 0.78 0.78 0.78/ /73.1 73.1 0.0

    / / /

    Total Number of Grouped Circuits =

    Subject to simultaneous overload = No No. of ladders = 1

    No. of circuits per ladder = 2

    1.88 1.88 1.880.82 0.82 0.82

    Qty. & Size (mm):

    Size (mm):

    Size (mm):

    (C) :

    L3L2L1

    L1 L2 L3

    Fully Loaded = 532.9Cable Energy Loss (W): At Design Current = 439.5

    Arrangement: Horizontal Touching

    4C4=

    Page 19 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • CIRCUIT DETAILS

    Id No.:Cable Reference Name:

    PROTECTIVE DEVICES

    Type:Overcurrent Rating In (A):

    Settings:

    Earth Fault

    Settings:

    Type:

    OVERCURRENT PROTECTION

    Type:Protective Device

    Rating In (A):Overload:

    Motor Rating (A): Design Current Ib (A):

    Breaking Capacity (kA): Icu = Cascaded = Ics =

    Max. Fault Current (kA): Source End = Load End =

    Line ConductorAdiabatic Check

    Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

    EARTH FAULT PROTECTION

    Protection:

    Ze Z1 Max Zs

    Circuit Protective Conductor (CPC) Details

    Section (mm )Conductor

    Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

    Z2

    External

    Zs

    Phase CPC Total

    k Value

    Phase Actual Equivalent

    Total =

    2

    Min. S (mm) =

    Earth Fault Current (kA)

    Uo/(Zs x 1000) =

    Earth Fault Disconnection Time (s)

    Actual from characteristic =

    Maximum for circuit type =

    ERRORS

    COMMENTS

    P14

    Generic BS 88-2 Fuse System E

    Generic BS 88-2 Fuse System E Rating (A): 100

    Generic BS 88-2 Fuse System E

    105.37 A

    N/A 73.1 A

    Phase fault discrimination check required

    N/A

    80 80No

    10.467 6.865

    CPD Energy Let-through (As): 60.00

    Adiabatic Limit kS (As): 25.05

    3.313

    Phase Conductor Section S (mm) = 35

    Generic BS 88-2 Fuse System E Rating (A): 100

    0.442310.194150.127000.016710.05686

    0.19

    5.00 1.19

    Calculated in accordance with BS 7671

    3.66

    Armour

    Earth Fault Loop Impedance ()

    Adiabatic Check: Minimum Section CPC S = (It)/k

    80 25.73Actual x (k2/k1) =

    25.73

    x 10 3

    6x 10

    It =274.66 x 103 As

    143

    46

    (k1)

    (k2)

    100

    100 Motor Overload Setting Ir (A):

    Minimum Load End Fault Current Ifmin (kA) =

    Source End Earth Fault Current (kA): 4.06

    Page 20 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • Modified By:

    Created On :

    Rev No:Created By :

    Document No:

    Job Number:Project Reference: Killyhevlin WTW-GAC

    gabriel.cucu

    05/08/2014 Rev Date :

    Cable Analysis ReportP14-A

    CIRCUIT DETAILS

    Id No.:

    Design Current Ib (A):

    Cable Reference Name:

    To:From:Connection

    Load

    PROJECT SETTINGS

    Id No.:

    Lighting =

    Source

    Name: Type:

    Voltage Drop Limits (%) Other =

    Switching Scenario

    Setting:

    CABLES

    Type:Phase and Neutral

    Phase =

    CPC

    Neutral =

    Length (m):

    CABLE SIZING

    Cable Type:

    Ref. Method =

    Cables in Parallel:

    Grouping Details:

    Installation Method:

    Rating Factor Condition Table RuleParameter

    Diversified load current in highest loaded phaseIb =

    In =

    Ir =

    Iz =

    It = It >= Iz [per parallel cable]

    VOLTAGE DROP

    Impedance:

    Cable Data

    r = Length (m)

    Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

    Calculations based on BS 7671:2008 (2011) Appendix 4

    Design Current Ib (A/PF)

    N

    /

    x = Ca Cg It

    mV/A/m:

    Total m :

    Temperature

    Correction Factor (Ct) =

    Max. Normal (tp) = Actual =

    Voltage Drop (V/%)

    3rd Harmonic 11A

    P14-A

    LCS-P1202 P1202

    Motor, Star delta started, three phase and neutralat GAC MCC 73.1 A

    MSWB

    Public

    BS 7671:2008 (2011)3.00 5.00

    Multicore, 90C thermosetting, armoured *RUN TO 70C Cu

    Multicore, 90C thermosetting, armoured *RUN TO 70C Cu 5

    34 - On a ladder

    16 [a]

    No

    2 Derating for 2 circuits/cables

    TN

    N/A

    1 x 16 [a] 1 x 16 [a]

    Armour 49 + Integral 16

    E

    4B1Air Temperature (C) = 30.0Ca 1.00

    Cg 0.87

    =

    = 0.00 %1.00=Ch

    Ci 1.00 Run Through Insulation = No 52.2=

    73.1 A

    100 A

    105.37 A

    63.1 A

    83.0 A

    In >= Ib

    Motor Overload: GN6, amendment 2, p16

    BS 7671, App. 4.5, Equations 3/4 [per parallel cable]

    2.4 0

    12 0

    5 1.00 0.87 83.0 A

    70 71

    1.0000

    73.1 0.78 0.78 0.78/ /73.1 73.1 0.0

    / / /

    Total Number of Grouped Circuits =

    Subject to simultaneous overload = No No. of ladders = 1

    No. of circuits per ladder = 2

    0.40 0.40 0.400.17 0.17 0.17

    Qty. & Size (mm):

    Size (mm):

    Size (mm):

    (C) :

    L3L2L1

    L1 L2 L3

    Fully Loaded = 111.2Cable Energy Loss (W): At Design Current = 111.7

    Arrangement: Horizontal Touching

    4C4=

    Page 21 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • CIRCUIT DETAILS

    Id No.:Cable Reference Name:

    PROTECTIVE DEVICES

    Type:Overcurrent Rating In (A):

    Settings:

    Earth Fault

    Settings:

    Type:

    OVERCURRENT PROTECTION

    Type:Protective Device

    Rating In (A):Overload:

    Motor Rating (A): Design Current Ib (A):

    Breaking Capacity (kA): Icu = Cascaded = Ics =

    Max. Fault Current (kA): Source End = Load End =

    Line ConductorAdiabatic Check

    Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

    EARTH FAULT PROTECTION

    Protection:

    Ze Z1 Max Zs

    Circuit Protective Conductor (CPC) Details

    Section (mm )Conductor

    Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

    Z2

    External

    Zs

    Phase CPC Total

    k Value

    Phase Actual Equivalent

    Total =

    2

    Min. S (mm) =

    Earth Fault Current (kA)

    Uo/(Zs x 1000) =

    Earth Fault Disconnection Time (s)

    Actual from characteristic =

    Maximum for circuit type =

    ERRORS

    COMMENTS

    P14-A

    Generic BS 88-2 Fuse System E

    Generic BS 88-2 Fuse System E Rating (A): 100

    Generic BS 88-2 Fuse System E

    105.37 A

    100 A 73.1 A

    Phase fault discrimination check required

    N/A

    80 80No

    6.865 6.388

    CPD Energy Let-through (As): 60.00

    Adiabatic Limit kS (As): 3.39

    3.034

    Phase Conductor Section S (mm) = 16

    Generic BS 88-2 Fuse System E Rating (A): 100

    0.442310.200450.002930.003460.19415

    0.22

    5.00 1.15

    Calculated in accordance with BS 7671

    4.71

    Armour

    Earth Fault Loop Impedance ()

    Adiabatic Check: Minimum Section CPC S = (It)/k

    Integral

    49

    16

    49.00

    16.00

    Actual x (k2/k1) =

    Actual x (k2/k1) =

    65.00

    x 10 3

    6x 10

    It =293.49 x 103 As

    115

    115

    115

    (k1)

    (k2)

    (k2)

    100

    100 Motor Overload Setting Ir (A):

    Minimum Load End Fault Current Ifmin (kA) =

    Source End Earth Fault Current (kA): 1.19

    Page 22 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • Modified By:

    Created On :

    Rev No:Created By :

    Document No:

    Job Number:Project Reference: Killyhevlin WTW-GAC

    gabriel.cucu

    05/08/2014 Rev Date :

    Cable Analysis ReportP2

    CIRCUIT DETAILS

    Id No.:

    Design Current Ib (A):

    Cable Reference Name:

    To:From:Connection

    Load

    PROJECT SETTINGS

    Id No.:

    Lighting =

    Source

    Name: Type:

    Voltage Drop Limits (%) Other =

    Switching Scenario

    Setting:

    CABLES

    Type:Phase and Neutral

    Phase =

    CPC

    Neutral =

    Length (m):

    CABLE SIZING

    Cable Type:

    Ref. Method =

    Cables in Parallel:

    Grouping Details:

    Installation Method:

    Rating Factor Condition Table RuleParameter

    Diversified load current in highest loaded phaseIb =

    In =

    Ir =

    Iz =

    It = It >= Iz [per parallel cable]

    VOLTAGE DROP

    Impedance:

    Cable Data

    r = Length (m)

    Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

    Calculations based on BS 7671:2008 (2011) Appendix 4

    Design Current Ib (A/PF)

    N

    /

    x = Ca Cg It

    mV/A/m:

    Total m :

    Temperature

    Correction Factor (Ct) =

    Max. Normal (tp) = Actual =

    Voltage Drop (V/%)

    3rd Harmonic 11A

    P2

    GAC MCC Site Lighting

    Distribution Board 0.0 A

    MSWB

    Public

    BS 7671:2008 (2011)3.00 5.00

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4 10

    34 - On a ladder

    10 [f]

    No

    TN

    N/A

    1 x 10 [f] 1 x 10 [f]

    Armour 43

    E

    4B1Air Temperature (C) = 30.0Ca 1.00

    Cg 1.00

    =

    = 0.00 %1.00=Ch

    Ci 1.00 Run Through Insulation = No 52.2=

    0.0 A

    50 A

    N/A

    50.0 A

    78.0 A

    In >= Ib

    --

    BS 7671, App. 4.5, Equations 1 [per parallel cable]

    4 0

    40 0

    10 1.00 1.00 78.0 A

    90 30

    1.0000

    0.0 0.00 0.00 0.00/ /0.0 0.0 0.0

    / / /0.00 0.00 0.000.00 0.00 0.00

    Qty. & Size (mm):

    Size (mm):

    Size (mm):

    (C) :

    L3L2L1

    L1 L2 L3

    Fully Loaded = 0Cable Energy Loss (W): At Design Current = 0

    4C4=

    Page 23 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • CIRCUIT DETAILS

    Id No.:Cable Reference Name:

    PROTECTIVE DEVICES

    Type:Overcurrent Rating In (A):

    Settings:

    Earth Fault

    Settings:

    Type:

    OVERCURRENT PROTECTION

    Type:Protective Device

    Rating In (A):Overload:

    Motor Rating (A): Design Current Ib (A):

    Breaking Capacity (kA): Icu = Cascaded = Ics =

    Max. Fault Current (kA): Source End = Load End =

    Line ConductorAdiabatic Check

    Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

    EARTH FAULT PROTECTION

    Protection:

    Ze Z1 Max Zs

    Circuit Protective Conductor (CPC) Details

    Section (mm )Conductor

    Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

    Z2

    External

    Zs

    Phase CPC Total

    k Value

    Phase Actual Equivalent

    Total =

    2

    Min. S (mm) =

    Earth Fault Current (kA)

    Uo/(Zs x 1000) =

    Earth Fault Disconnection Time (s)

    Actual from characteristic =

    Maximum for circuit type =

    ERRORS

    COMMENTS

    P2

    Generic BS 88-2 Fuse System E

    Generic BS 88-2 Fuse System E Rating (A): 50

    Generic BS 88-2 Fuse System E

    N/A

    N/A 0.0 A

    Phase fault discrimination check required

    N/A

    80 80No

    10.467 6.200

    CPD Energy Let-through (As): 13.50

    Adiabatic Limit kS (As): 2.04

    2.868

    Phase Conductor Section S (mm) = 10

    Generic BS 88-2 Fuse System E Rating (A): 50

    1.045440.121820.046990.023090.05686

    0.05

    5.00 1.90

    Calculated in accordance with BS 7671

    0.81

    Armour

    Earth Fault Loop Impedance ()

    Adiabatic Check: Minimum Section CPC S = (It)/k

    43 13.83Actual x (k2/k1) =

    13.83

    x 10 3

    6x 10

    It =13.50 x 10 3 As

    143

    46

    (k1)

    (k2)

    50

    50 Overload Setting Ir (A):

    Minimum Load End Fault Current Ifmin (kA) =

    Source End Earth Fault Current (kA): 4.06

    Page 24 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • Modified By:

    Created On :

    Rev No:Created By :

    Document No:

    Job Number:Project Reference: Killyhevlin WTW-GAC

    gabriel.cucu

    05/08/2014 Rev Date :

    Cable Analysis ReportP3

    CIRCUIT DETAILS

    Id No.:

    Design Current Ib (A):

    Cable Reference Name:

    To:From:Connection

    Load

    PROJECT SETTINGS

    Id No.:

    Lighting =

    Source

    Name: Type:

    Voltage Drop Limits (%) Other =

    Switching Scenario

    Setting:

    CABLES

    Type:Phase and Neutral

    Phase =

    CPC

    Neutral =

    Length (m):

    CABLE SIZING

    Cable Type:

    Ref. Method =

    Cables in Parallel:

    Grouping Details:

    Installation Method:

    Rating Factor Condition Table RuleParameter

    Diversified load current in highest loaded phaseIb =

    In =

    Ir =

    Iz =

    It = It >= Iz [per parallel cable]

    VOLTAGE DROP

    Impedance:

    Cable Data

    r = Length (m)

    Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

    Calculations based on BS 7671:2008 (2011) Appendix 4

    Design Current Ib (A/PF)

    N

    /

    x = Ca Cg It

    mV/A/m:

    Total m :

    Temperature

    Correction Factor (Ct) =

    Max. Normal (tp) = Actual =

    Voltage Drop (V/%)

    3rd Harmonic 11A

    P3

    GAC MCC Potable Water Booster

    Distribution Board 0.0 A

    MSWB

    Public

    BS 7671:2008 (2011)3.00 5.00

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4 10

    34 - On a ladder

    6 [f]

    No

    TN

    N/A

    1 x 6 [f] 1 x 6 [f]

    Armour 36

    E

    4B1Air Temperature (C) = 30.0Ca 1.00

    Cg 1.00

    =

    = 0.00 %1.00=Ch

    Ci 1.00 Run Through Insulation = No 52.2=

    0.0 A

    32 A

    N/A

    32.0 A

    56.0 A

    In >= Ib

    --

    BS 7671, App. 4.5, Equations 1 [per parallel cable]

    6.8 0

    68 0

    10 1.00 1.00 56.0 A

    90 30

    1.0000

    0.0 0.00 0.00 0.00/ /0.0 0.0 0.0

    / / /0.00 0.00 0.000.00 0.00 0.00

    Qty. & Size (mm):

    Size (mm):

    Size (mm):

    (C) :

    L3L2L1

    L1 L2 L3

    Fully Loaded = 0Cable Energy Loss (W): At Design Current = 0

    4C4=

    Page 25 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • CIRCUIT DETAILS

    Id No.:Cable Reference Name:

    PROTECTIVE DEVICES

    Type:Overcurrent Rating In (A):

    Settings:

    Earth Fault

    Settings:

    Type:

    OVERCURRENT PROTECTION

    Type:Protective Device

    Rating In (A):Overload:

    Motor Rating (A): Design Current Ib (A):

    Breaking Capacity (kA): Icu = Cascaded = Ics =

    Max. Fault Current (kA): Source End = Load End =

    Line ConductorAdiabatic Check

    Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

    EARTH FAULT PROTECTION

    Protection:

    Ze Z1 Max Zs

    Circuit Protective Conductor (CPC) Details

    Section (mm )Conductor

    Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

    Z2

    External

    Zs

    Phase CPC Total

    k Value

    Phase Actual Equivalent

    Total =

    2

    Min. S (mm) =

    Earth Fault Current (kA)

    Uo/(Zs x 1000) =

    Earth Fault Disconnection Time (s)

    Actual from characteristic =

    Maximum for circuit type =

    ERRORS

    COMMENTS

    P3

    Generic BS 88-2 Fuse System E

    Generic BS 88-2 Fuse System E Rating (A): 32

    Generic BS 88-2 Fuse System E

    N/A

    N/A 0.0 A

    Phase fault discrimination check required

    N/A

    80 80No

    10.467 4.709

    CPD Energy Let-through (As): 3,400.00

    Adiabatic Limit kS (As): 736.16

    2.065

    Phase Conductor Section S (mm) = 6

    Generic BS 88-2 Fuse System E Rating (A): 32

    1.840270.144950.054610.039260.05686

    0.05

    5.00 1.59

    Calculated in accordance with BS 7671

    0.41

    Armour

    Earth Fault Loop Impedance ()

    Adiabatic Check: Minimum Section CPC S = (It)/k

    36 11.58Actual x (k2/k1) =

    11.58

    3x 10

    It =3,400.00 As

    143

    46

    (k1)

    (k2)

    32

    32 Overload Setting Ir (A):

    Minimum Load End Fault Current Ifmin (kA) =

    Source End Earth Fault Current (kA): 4.06

    Page 26 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • Modified By:

    Created On :

    Rev No:Created By :

    Document No:

    Job Number:Project Reference: Killyhevlin WTW-GAC

    gabriel.cucu

    05/08/2014 Rev Date :

    Cable Analysis ReportP4

    CIRCUIT DETAILS

    Id No.:

    Design Current Ib (A):

    Cable Reference Name:

    To:From:Connection

    Load

    PROJECT SETTINGS

    Id No.:

    Lighting =

    Source

    Name: Type:

    Voltage Drop Limits (%) Other =

    Switching Scenario

    Setting:

    CABLES

    Type:Phase and Neutral

    Phase =

    CPC

    Neutral =

    Length (m):

    CABLE SIZING

    Cable Type:

    Ref. Method =

    Cables in Parallel:

    Grouping Details:

    Installation Method:

    Rating Factor Condition Table RuleParameter

    Diversified load current in highest loaded phaseIb =

    In =

    Ir =

    Iz =

    It = It >= Iz [per parallel cable]

    VOLTAGE DROP

    Impedance:

    Cable Data

    r = Length (m)

    Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

    Calculations based on BS 7671:2008 (2011) Appendix 4

    Design Current Ib (A/PF)

    N

    /

    x = Ca Cg It

    mV/A/m:

    Total m :

    Temperature

    Correction Factor (Ct) =

    Max. Normal (tp) = Actual =

    Voltage Drop (V/%)

    3rd Harmonic 11A

    P4

    GAC MCC Building Services

    Distribution Board 0.0 A

    MSWB

    Public

    BS 7671:2008 (2011)3.00 5.00

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4 20

    34 - On a ladder

    6 [f]

    No

    TN

    N/A

    1 x 6 [f] 1 x 6 [f]

    Armour 36

    E

    4B1Air Temperature (C) = 30.0Ca 1.00

    Cg 1.00

    =

    = 0.00 %1.00=Ch

    Ci 1.00 Run Through Insulation = No 52.2=

    0.0 A

    40 A

    N/A

    40.0 A

    56.0 A

    In >= Ib

    --

    BS 7671, App. 4.5, Equations 1 [per parallel cable]

    6.8 0

    136 0

    20 1.00 1.00 56.0 A

    90 30

    1.0000

    0.0 0.00 0.00 0.00/ /0.0 0.0 0.0

    / / /0.00 0.00 0.000.00 0.00 0.00

    Qty. & Size (mm):

    Size (mm):

    Size (mm):

    (C) :

    L3L2L1

    L1 L2 L3

    Fully Loaded = 0Cable Energy Loss (W): At Design Current = 0

    4C4=

    Page 27 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • CIRCUIT DETAILS

    Id No.:Cable Reference Name:

    PROTECTIVE DEVICES

    Type:Overcurrent Rating In (A):

    Settings:

    Earth Fault

    Settings:

    Type:

    OVERCURRENT PROTECTION

    Type:Protective Device

    Rating In (A):Overload:

    Motor Rating (A): Design Current Ib (A):

    Breaking Capacity (kA): Icu = Cascaded = Ics =

    Max. Fault Current (kA): Source End = Load End =

    Line ConductorAdiabatic Check

    Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

    EARTH FAULT PROTECTION

    Protection:

    Ze Z1 Max Zs

    Circuit Protective Conductor (CPC) Details

    Section (mm )Conductor

    Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

    Z2

    External

    Zs

    Phase CPC Total

    k Value

    Phase Actual Equivalent

    Total =

    2

    Min. S (mm) =

    Earth Fault Current (kA)

    Uo/(Zs x 1000) =

    Earth Fault Disconnection Time (s)

    Actual from characteristic =

    Maximum for circuit type =

    ERRORS

    COMMENTS

    P4

    Generic BS 88-2 Fuse System E

    Generic BS 88-2 Fuse System E Rating (A): 40

    Generic BS 88-2 Fuse System E

    N/A

    N/A 0.0 A

    Phase fault discrimination check required

    N/A

    80 80No

    10.467 2.932

    CPD Energy Let-through (As): 8,500.00

    Adiabatic Limit kS (As): 736.16

    1.220

    Phase Conductor Section S (mm) = 6

    Generic BS 88-2 Fuse System E Rating (A): 40

    1.353000.237510.109220.078520.05686

    0.06

    5.00 0.97

    Calculated in accordance with BS 7671

    0.64

    Armour

    Earth Fault Loop Impedance ()

    Adiabatic Check: Minimum Section CPC S = (It)/k

    36 11.58Actual x (k2/k1) =

    11.58

    3x 10

    It =8,500.00 As

    143

    46

    (k1)

    (k2)

    40

    40 Overload Setting Ir (A):

    Minimum Load End Fault Current Ifmin (kA) =

    Source End Earth Fault Current (kA): 4.06

    Page 28 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • Modified By:

    Created On :

    Rev No:Created By :

    Document No:

    Job Number:Project Reference: Killyhevlin WTW-GAC

    gabriel.cucu

    05/08/2014 Rev Date :

    Cable Analysis ReportP5

    CIRCUIT DETAILS

    Id No.:

    Design Current Ib (A):

    Cable Reference Name:

    To:From:Connection

    Load

    PROJECT SETTINGS

    Id No.:

    Lighting =

    Source

    Name: Type:

    Voltage Drop Limits (%) Other =

    Switching Scenario

    Setting:

    CABLES

    Type:Phase and Neutral

    Phase =

    CPC

    Neutral =

    Length (m):

    CABLE SIZING

    Cable Type:

    Ref. Method =

    Cables in Parallel:

    Grouping Details:

    Installation Method:

    Rating Factor Condition Table RuleParameter

    Diversified load current in highest loaded phaseIb =

    In =

    Ir =

    Iz =

    It = It >= Iz [per parallel cable]

    VOLTAGE DROP

    Impedance:

    Cable Data

    r = Length (m)

    Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

    Calculations based on BS 7671:2008 (2011) Appendix 4

    Design Current Ib (A/PF)

    N

    /

    x = Ca Cg It

    mV/A/m:

    Total m :

    Temperature

    Correction Factor (Ct) =

    Max. Normal (tp) = Actual =

    Voltage Drop (V/%)

    3rd Harmonic 11A

    P5

    GAC MCC LCP1

    Distribution Board 21.0 A

    MSWB

    Public

    BS 7671:2008 (2011)3.00 5.00

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4 60

    34 - On a ladder

    6 [f]

    No

    TN

    N/A

    1 x 6 [f] 1 x 6 [f]

    Armour 40

    E

    4B1Air Temperature (C) = 30.0Ca 1.00

    Cg 1.00

    =

    = 0.00 %1.00=Ch

    Ci 1.00 Run Through Insulation = No 52.2=

    21.0 A

    32 A

    N/A

    32.0 A

    56.0 A

    In >= Ib

    --

    BS 7671, App. 4.5, Equations 1 [per parallel cable]

    6.8 0

    408 0

    60 1.00 1.00 56.0 A

    90 38.4

    0.8389

    21.0 1.00 1.00 1.00/ /21.0 21.0 0.0

    / / /4.15 4.15 4.151.80 1.80 1.80

    Qty. & Size (mm):

    Size (mm):

    Size (mm):

    (C) :

    L3L2L1

    L1 L2 L3

    Fully Loaded = 311.6Cable Energy Loss (W): At Design Current = 247.4

    4C4=

    Page 29 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • CIRCUIT DETAILS

    Id No.:Cable Reference Name:

    PROTECTIVE DEVICES

    Type:Overcurrent Rating In (A):

    Settings:

    Earth Fault

    Settings:

    Type:

    OVERCURRENT PROTECTION

    Type:Protective Device

    Rating In (A):Overload:

    Motor Rating (A): Design Current Ib (A):

    Breaking Capacity (kA): Icu = Cascaded = Ics =

    Max. Fault Current (kA): Source End = Load End =

    Line ConductorAdiabatic Check

    Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

    EARTH FAULT PROTECTION

    Protection:

    Ze Z1 Max Zs

    Circuit Protective Conductor (CPC) Details

    Section (mm )Conductor

    Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

    Z2

    External

    Zs

    Phase CPC Total

    k Value

    Phase Actual Equivalent

    Total =

    2

    Min. S (mm) =

    Earth Fault Current (kA)

    Uo/(Zs x 1000) =

    Earth Fault Disconnection Time (s)

    Actual from characteristic =

    Maximum for circuit type =

    ERRORS

    COMMENTS

    P5

    Generic BS 88-2 Fuse System E

    Generic BS 88-2 Fuse System E Rating (A): 32

    Generic BS 88-2 Fuse System E

    N/A

    N/A 21.0 A

    Phase fault discrimination check required

    N/A

    80 80No

    10.467 1.152

    CPD Energy Let-through (As): 3,400.00

    Adiabatic Limit kS (As): 736.16

    0.460

    Phase Conductor Section S (mm) = 6

    Generic BS 88-2 Fuse System E Rating (A): 32

    1.840270.611760.327660.235560.05686

    0.05

    5.00 0.38

    Calculated in accordance with BS 7671

    0.41

    Armour

    Earth Fault Loop Impedance ()

    Adiabatic Check: Minimum Section CPC S = (It)/k

    40 40.00Actual x (k2/k1) =

    40.00

    3x 10

    It =3,400.00 As

    143

    143

    (k1)

    (k2)

    32

    32 Overload Setting Ir (A):

    Minimum Load End Fault Current Ifmin (kA) =

    Source End Earth Fault Current (kA): 4.06

    Page 30 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • Modified By:

    Created On :

    Rev No:Created By :

    Document No:

    Job Number:Project Reference: Killyhevlin WTW-GAC

    gabriel.cucu

    05/08/2014 Rev Date :

    Cable Analysis ReportP6

    CIRCUIT DETAILS

    Id No.:

    Design Current Ib (A):

    Cable Reference Name:

    To:From:Connection

    Load

    PROJECT SETTINGS

    Id No.:

    Lighting =

    Source

    Name: Type:

    Voltage Drop Limits (%) Other =

    Switching Scenario

    Setting:

    CABLES

    Type:Phase and Neutral

    Phase =

    CPC

    Neutral =

    Length (m):

    CABLE SIZING

    Cable Type:

    Ref. Method =

    Cables in Parallel:

    Grouping Details:

    Installation Method:

    Rating Factor Condition Table RuleParameter

    Diversified load current in highest loaded phaseIb =

    In =

    Ir =

    Iz =

    It = It >= Iz [per parallel cable]

    VOLTAGE DROP

    Impedance:

    Cable Data

    r = Length (m)

    Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

    Calculations based on BS 7671:2008 (2011) Appendix 4

    Design Current Ib (A/PF)

    N

    /

    x = Ca Cg It

    mV/A/m:

    Total m :

    Temperature

    Correction Factor (Ct) =

    Max. Normal (tp) = Actual =

    Voltage Drop (V/%)

    3rd Harmonic 11A

    P6

    GAC MCC LCP2

    Distribution Board 29.1 A

    MSWB

    Public

    BS 7671:2008 (2011)3.00 5.00

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4 60

    34 - On a ladder

    6 [f]

    No

    TN

    N/A

    1 x 6 [f] 1 x 6 [f]

    Armour 40

    E

    4B1Air Temperature (C) = 30.0Ca 1.00

    Cg 1.00

    =

    = 0.00 %1.00=Ch

    Ci 1.00 Run Through Insulation = No 52.2=

    29.1 A

    32 A

    N/A

    32.0 A

    56.0 A

    In >= Ib

    --

    BS 7671, App. 4.5, Equations 1 [per parallel cable]

    6.8 0

    408 0

    60 1.00 1.00 56.0 A

    90 46.1

    0.8630

    29.1 1.00 1.00 1.00/ /29.1 29.1 0.0

    / / /5.91 5.91 5.912.57 2.57 2.57

    Qty. & Size (mm):

    Size (mm):

    Size (mm):

    (C) :

    L3L2L1

    L1 L2 L3

    Fully Loaded = 596.4Cable Energy Loss (W): At Design Current = 491.8

    4C4=

    Page 31 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • CIRCUIT DETAILS

    Id No.:Cable Reference Name:

    PROTECTIVE DEVICES

    Type:Overcurrent Rating In (A):

    Settings:

    Earth Fault

    Settings:

    Type:

    OVERCURRENT PROTECTION

    Type:Protective Device

    Rating In (A):Overload:

    Motor Rating (A): Design Current Ib (A):

    Breaking Capacity (kA): Icu = Cascaded = Ics =

    Max. Fault Current (kA): Source End = Load End =

    Line ConductorAdiabatic Check

    Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

    EARTH FAULT PROTECTION

    Protection:

    Ze Z1 Max Zs

    Circuit Protective Conductor (CPC) Details

    Section (mm )Conductor

    Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

    Z2

    External

    Zs

    Phase CPC Total

    k Value

    Phase Actual Equivalent

    Total =

    2

    Min. S (mm) =

    Earth Fault Current (kA)

    Uo/(Zs x 1000) =

    Earth Fault Disconnection Time (s)

    Actual from characteristic =

    Maximum for circuit type =

    ERRORS

    COMMENTS

    P6

    Generic BS 88-2 Fuse System E

    Generic BS 88-2 Fuse System E Rating (A): 32

    Generic BS 88-2 Fuse System E

    N/A

    N/A 29.1 A

    Phase fault discrimination check required

    N/A

    80 80No

    10.467 1.152

    CPD Energy Let-through (As): 3,400.00

    Adiabatic Limit kS (As): 736.16

    0.460

    Phase Conductor Section S (mm) = 6

    Generic BS 88-2 Fuse System E Rating (A): 32

    1.840270.611760.327660.235560.05686

    0.05

    5.00 0.38

    Calculated in accordance with BS 7671

    0.41

    Armour

    Earth Fault Loop Impedance ()

    Adiabatic Check: Minimum Section CPC S = (It)/k

    40 40.00Actual x (k2/k1) =

    40.00

    3x 10

    It =3,400.00 As

    143

    143

    (k1)

    (k2)

    32

    32 Overload Setting Ir (A):

    Minimum Load End Fault Current Ifmin (kA) =

    Source End Earth Fault Current (kA): 4.06

    Page 32 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • Modified By:

    Created On :

    Rev No:Created By :

    Document No:

    Job Number:Project Reference: Killyhevlin WTW-GAC

    gabriel.cucu

    05/08/2014 Rev Date :

    Cable Analysis ReportP7

    CIRCUIT DETAILS

    Id No.:

    Design Current Ib (A):

    Cable Reference Name:

    To:From:Connection

    Load

    PROJECT SETTINGS

    Id No.:

    Lighting =

    Source

    Name: Type:

    Voltage Drop Limits (%) Other =

    Switching Scenario

    Setting:

    CABLES

    Type:Phase and Neutral

    Phase =

    CPC

    Neutral =

    Length (m):

    CABLE SIZING

    Cable Type:

    Ref. Method =

    Cables in Parallel:

    Grouping Details:

    Installation Method:

    Rating Factor Condition Table RuleParameter

    Diversified load current in highest loaded phaseIb =

    In =

    Ir =

    Iz =

    It = It >= Iz [per parallel cable]

    VOLTAGE DROP

    Impedance:

    Cable Data

    r = Length (m)

    Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

    Calculations based on BS 7671:2008 (2011) Appendix 4

    Design Current Ib (A/PF)

    N

    /

    x = Ca Cg It

    mV/A/m:

    Total m :

    Temperature

    Correction Factor (Ct) =

    Max. Normal (tp) = Actual =

    Voltage Drop (V/%)

    3rd Harmonic 11A

    P7

    GAC MCC Plant Room Hoist

    Distribution Board 0.0 A

    MSWB

    Public

    BS 7671:2008 (2011)3.00 5.00

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4

    Multicore, 90C thermosetting insulated, armoured Cu Table 4E4 20

    34 - On a ladder

    6 [f]

    No

    TN

    N/A

    1 x 6 [f] 1 x 6 [f]

    Armour 36

    E

    4B1Air Temperature (C) = 30.0Ca 1.00

    Cg 1.00

    =

    = 0.00 %1.00=Ch

    Ci 1.00 Run Through Insulation = No 52.2=

    0.0 A

    10 A

    N/A

    10.0 A

    56.0 A

    In >= Ib

    --

    BS 7671, App. 4.5, Equations 1 [per parallel cable]

    6.8 0

    136 0

    20 1.00 1.00 56.0 A

    90 30

    1.0000

    0.0 0.00 0.00 0.00/ /0.0 0.0 0.0

    / / /0.00 0.00 0.000.00 0.00 0.00

    Qty. & Size (mm):

    Size (mm):

    Size (mm):

    (C) :

    L3L2L1

    L1 L2 L3

    Fully Loaded = 0Cable Energy Loss (W): At Design Current = 0

    4C4=

    Page 33 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • CIRCUIT DETAILS

    Id No.:Cable Reference Name:

    PROTECTIVE DEVICES

    Type:Overcurrent Rating In (A):

    Settings:

    Earth Fault

    Settings:

    Type:

    OVERCURRENT PROTECTION

    Type:Protective Device

    Rating In (A):Overload:

    Motor Rating (A): Design Current Ib (A):

    Breaking Capacity (kA): Icu = Cascaded = Ics =

    Max. Fault Current (kA): Source End = Load End =

    Line ConductorAdiabatic Check

    Calculations based on BS 7671:2008 433.1, 434.5.1, 536.1 Para. 3

    EARTH FAULT PROTECTION

    Protection:

    Ze Z1 Max Zs

    Circuit Protective Conductor (CPC) Details

    Section (mm )Conductor

    Calculations based on BS 7671:2008 411.3.2, 411.3.3, 411.4, 411.5, 543.1

    Z2

    External

    Zs

    Phase CPC Total

    k Value

    Phase Actual Equivalent

    Total =

    2

    Min. S (mm) =

    Earth Fault Current (kA)

    Uo/(Zs x 1000) =

    Earth Fault Disconnection Time (s)

    Actual from characteristic =

    Maximum for circuit type =

    ERRORS

    COMMENTS

    P7

    Generic BS 88-2 Fuse System E

    Generic BS 88-2 Fuse System E Rating (A): 10

    Generic BS 88-2 Fuse System E

    N/A

    N/A 0.0 A

    Phase fault discrimination check required

    N/A

    80 80No

    10.467 2.932

    CPD Energy Let-through (As): 280.00

    Adiabatic Limit kS (As): 736.16

    1.220

    Phase Conductor Section S (mm) = 6

    Generic BS 88-2 Fuse System E Rating (A): 10

    7.187480.237510.109220.078520.05686

    0.04

    5.00 0.97

    Calculated in accordance with BS 7671

    0.12

    Armour

    Earth Fault Loop Impedance ()

    Adiabatic Check: Minimum Section CPC S = (It)/k

    36 11.58Actual x (k2/k1) =

    11.58

    3x 10

    It =280.00 As

    143

    46

    (k1)

    (k2)

    10

    10 Overload Setting Ir (A):

    Minimum Load End Fault Current Ifmin (kA) =

    Source End Earth Fault Current (kA): 4.06

    Page 34 of 38

    07/08/2014Printed on:Project: C:\Users\gabriel.cucu\Desktop\killyhevlinwtw\Killyhevlin Power Cables.p17Created using: v2013.0.0 BS 7671:2008 (2011) - Lagan Water Ltd Copyright Amtech Group Ltd 2013

    KEY: [a] = Auto setting; [f] = Fixed setting; [m] = Maximum setting; [d] = double neutral * denotes Error condition

  • Modified By:

    Created On :

    Rev No:Created By :

    Document No:

    Job Number:Project Reference: Killyhevlin WTW-GAC

    gabriel.cucu

    05/08/2014 Rev Date :

    Cable Analysis ReportP8

    CIRCUIT DETAILS

    Id No.:

    Design Current Ib (A):

    Cable Reference Name:

    To:From:Connection

    Load

    PROJECT SETTINGS

    Id No.:

    Lighting =

    Source

    Name: Type:

    Voltage Drop Limits (%) Other =

    Switching Scenario

    Setting:

    CABLES

    Type:Phase and Neutral

    Phase =

    CPC

    Neutral =

    Length (m):

    CABLE SIZING

    Cable Type:

    Ref. Method =

    Cables in Parallel:

    Grouping Details:

    Installation Method:

    Rating Factor Condition Table RuleParameter

    Diversified load current in highest loaded phaseIb =

    In =

    Ir =

    Iz =

    It = It >= Iz [per parallel cable]

    VOLTAGE DROP

    Impedance:

    Cable Data

    r = Length (m)

    Calculations based on BS 7671:2008 (2011) Appendix 4, Section 6

    Calculations based on BS 7671:2008 (2011) Appendix 4

    Design Current Ib (A/PF)

    N

    /

    x = Ca Cg It

    mV/A/m:

    Total m