6

C8_ Muthukumar Swathy

Embed Size (px)

DESCRIPTION

VELOCITY OF JET

Citation preview

  • LOG SHEET Name: MUTHUKUMAR SWATHY Group: Date: GP18 Results and Discussion Tabulation and Calculations 1. Tabulate your results under the following headings in Table 1: 2. Calculate the rates of heat removal from the evaporator Q L and heat delivered to the condenser Q H at different water flow rates and then determine their coefficients of performance of air refrigerator (COPR) and heat pump (COPH) at different cooling water msflow rates. 3. Using the data obtained in Table 1 and the calculated values from step (2), plot the graphs below and discuss. (i) Heat delivered Q H (kW) to the condenser and compressor load W C (kW) against condenser water mass flow rate (kg/s). (ii) Heat delivered Q H (kW) to the condenser and COPH versus condenser water mass flow rate (kg/s). 4. Based on the data obtained for the maximum and minimum cooling water flow rates, plot the vapour compression cycle on P-H diagram (Fig. 5) and compare with those based on ideal cycles. Discuss the results obtained.

  • 1. unit 1 2 3 4 Condenser water mass flow rate, mw Kg/s x 10^-3 20 30 40 50 Compressor electrical power input, WC 590 540 520 500 Absolute pressure of condenser, PH 1451 1201 1101 1001 Absolute pressure of evaporator, PL 346 321 321 301 HFC134a temperature at compressor inlet, T1 22.3 22.5 22.4 21.8 HFC134a temperature at compressor outlet, T2

    102.6 99.0 96.4 88.1 HFC134a temperature of condensed liquid, T3

    54.6 47.7 44.1 40.4 HFC134a temperature at expansion valve outlet, T4

    10.4 8.5 7.0 5.0 Compressor cooling water inlet temperature, T5 30.3 30.9 31.3 30.5 Compressor cooling water outlet temperature, T6 30.8 31.2 31.4 30.6 Condenser water outlet temperature, T7 50.8 43.7 40.1 37.2 Refrigerant mass flow rate, m 7.5 6.9 6.5 6.3 Heat delivered to condenser, QH 1672 1567.5 1454.64 1379.4 Heat removal from 937.5 862.5 812.5 787.5

  • evaporator, QL Compressor waste heat, Qcmp 41.8 37.62 16.72 20.9 Total heat delivered, QT 1713.8 1605.1 1471.3 1399.9 Performance of air refrigerator COPR 1.588 1.597 1.562 1.575 Performance of heat pump COPH 2.833 2.90 2.79 2.75 Performance of heat pump COPH-T - 2.90 2.97 2.82 2.79 2. The values of QH , QL , COPR , COPH at different cooling water flow rates are calculated and entered in the table above. 3. (i) QH , Wc Versus condenser water mass flow rate

    Y axis : series 1 QH , Series 2 WC X axis : mw

    1672 1567.5 1454.5 1379.4

    590 540 520 500

    0 200 400 600 800 1000

    1200 1400 1600 1800

    0 10 20 30 40 50 60 heat d

    elivered

    QH ,Com

    pressor

    load

    Wc

    condenser water mass Plow rate

    Series1 Series2 Linear (Series1) Linear (Series2)

  • (ii) QH, COPH versus condenser water mass flow rate

    Y axis : series 1 QH , Series 2 COPH X axis : mw

    1672 1567.5 1454.5 1379.4

    2.833 2.9 2.79 2.75 0 200 400 600 800 1000

    1200 1400 1600 1800

    0 10 20 30 40 50 60

    heat delivered

    QH, COPH

    condenser water mass Plow rate

    Series1 Series2 Linear (Series1) Linear (Series2)

  • 4. Vapor compression cycle on P-H diagram : A difference between the real cycle and the ideal is that temperature at which evaporation takes place is lower than the temperature of the cold region so heat transfer can take place. Similarly the temperature of the heat rejection must be higher than the hot region temperature to bring about heat transfer in the condenser.