SB.01 INDIVIDUAL STRUCTURAL COMPONENTS ARE DESIGNED TO SUPPORT LOADS IN THEIR FINAL ERECTEDPOSITION AS PART OF THE TOTAL COMPLETED STRUCTURE. PROVIDE TEMPORARY SHORING, GUYING ANDBRACING AS REQUIRED UNTIL ALL CONSTRUCTION AFFECTING LOAD CARRYING MEMBERS AND LATERALSTABILITY IS COMPLETED.
SB.02 CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR STABILITY OF STRUCTURE, ITS PARTS, AND JOBSITE SAFETY BY USE OF GUYING, BRACING, SHORING, BARRICADES, SAFETY RAILINGS AND DEVICES DURINGTHE ENTIRE PERIOD OF CONSTRUCTION.
SB.03 CONTRACTOR IS FULLY RESPONSIBLE FOR PROVIDING ALL TEMPORARY SHORING AND BRACING OFEXISTING ELEMENTS DURING CONSTRUCTION. ALL SHORING SHALL BE ADEQUATE TO SUPPORT ALL LOADINGSDURING MODIFICATION OF THE EXISTING BUILDING AND ERECTION OF THE NEW STRUCTURAL SUPPORTSYSTEM. TEMPORARY SHORING MUST REMAIN IN PLACE UNTIL ALL NEW STRUCTURAL MEMBERS SUPPORTINGSHORED ELEMENTS ARE IN PLACE AND ALL NEW CONNECTIONS COMPLETED.
STRUCTURAL STEEL
SS.01 ALL STRUCTURAL STEEL WORK SHALL CONFORM TO THE AISC "SPECIFICATION FOR STRUCTURALSTEEL BUILDINGS- ALLOWABLE STRESS DESIGN AND PLASTIC DESIGN" AND THE AISC "CODE OF STANDARDPRACTICE FOR STEEL BUILDINGS AND BRIDGES," LATEST EDITIONS
SS.03 ERECT AND MAINTAIN TEMPORARY BRACING TO INSURE THE ALIGNMENT AND STABILITY OF THESTRUCTURE DURING ERECTION UNTIL PERMANENT CONNECTIONS HAVE BEEN COMPLETED.
SS.07 ALL STRUCTURAL MEMBERS SHALL CONFORM TO THE FOLLOWING MINIMUM REQUIREMENTS:
WIDE FLANGE SECTIONS ASTM A 992 (Fy= 50KSI)OTHER SHAPES & PLATES ASTM A 36 (Fy= 36 KSI)STEEL TUBES SHAPED HSS SECTIONS ASTM A 500, GRADE B (Fy= 46 KSI) ROUND HSS SECTIONS ASTM A 500, GRADE B (Fy= 42 KSI)
SS.08 STEEL SHALL BE CLEAN OF RUST, LOOSE MILL SCALE, AND OTHER FOREIGN MATERIALS FORPROPER FABRICATION, FIT-UP, AND WELDING.
SS.09 ALL BOLTED CONNECTIONS SHALL BE IN ACCORDANCE WITH THE AISC "SPECIFICATION FORSTRUCTURAL JOINTS USING ASTM A 325 OR ASTM A 490 BOLTS."
SS.10 ALL BOLTS SHALL CONFORM TO THE LATEST EDITION OF ASTM A 325. BOLTS SHALL BE 7/8"DIAMETER MINIMUM. AT CONNECTIONS WITH LONG-SLOTTED HOLES IN OUTER PLYS, 5/16" PLATE WASHERSSUFFICIENT IN SIZE TO COMPLETELY COVER THE SLOT SHALL BE PROVIDED.
SS.11 ALL NUTS SHALL CONFORM TO THE LATEST EDITION OF ASTM A 563.
SS.12 ALL WASHERS SHALL CONFORM TO THE LATEST EDITION OF ASTM F 436.
SS.13 WELDING SHALL BE DONE BY AWS CERTIFIED WELDERS AND SHALL CONFORM TO THE AWS D1.1"STRUCTURE WELDING CODE," LATEST EDITION. ALL WELDING ELECTRODES SHALL BE E70XX.
SS.14 FIELD CONNECTIONS, EXCEPT WHERE SHOWN TO BE WELDED, SHALL BE BOLTED. SHOPCONNECTIONS MAY BE WELDED UNLESS NOTED OTHERWISE. MINIMUM WELDS NOT SHOWN ON THEDRAWINGS SHALL BE 1/4" FILLET WELDS.
SS.19 THERE SHALL BE NO FIELD CUTTING OF STRUCTURAL STEEL MEMBERS FOR THE WORK OF OTHERTRADES WITHOUT THE PRIOR WRITTEN APPROVAL OF THE ARCHITECT.
SS.20 PRIME PAINT ALL STEEL EXCEPT THOSE THAT ARE TO RECEIVE SPRAY-ON FIREPROOFING OR ARETO BE ENCASED IN CONCRETE.
SS.21 PROVIDE NEW EXTERIOR GALVANIZED STEEL LINTELS TO REPLACE DETERIORATED LINTELS ASREQUIRED. SEE ARCH. DRAWINGS "EXTERIOR KEYNOTES" FOR EXTERIOR LINTEL RELACEMENTREQUIREMENTS.
SS.22 ALL EXPOSED STRUCTURAL STEEL SHALL BE HOT-DIP GALVANIZED.
SS.23 UNLESS NOTED OTHERWISE, ALL SIMPLE BEAM SHEAR CONNECTIONS SHALL BE WELDED ORBEARING TYPE N BOLTED DOUBLE ANGLE FRAMED CONNECTIONS. IN NO CASE SHALL ANY CONNECTION BELESS THAN ONE-HALF THE DEPTH OF THE SUPPORTED BEAM, AND THE QUANTITY OF VERTICAL ROWS OFBOLTS SHALL NOT BE LESS THAN:
W8, C8: 2 ROWSW10, C10: 2 ROWSW12: 3 ROWSW14: 3 ROWSW16: 4 ROWS
CONCRETE AND FORMWORK
CO.01 ALL CONCRETE WORK SHALL CONFORM TO THE LATEST EDITION OF THE FOLLOWING AMERICANCONCRETE INSTITUTE PUBLICATIONS:
ACI 301 ACI 304 ACI 311ACI 315 ACI 318 ACI 347
CO.02 THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE LOCATION ANDPLACEMENT OF INSERTS, EMBEDDED PLATES, MASONRY ANCHORS, REGLETS, SLEEVES, DUCT WORK, PADS,AND ANCHOR BOLTS. THE INSERTS, EMBEDDED PLATES, ETC. SHALL NOT INTERFERE WITH CONCRETEREINFORCEMENT LOCATIONS. THE GENERAL CONTRACTOR SHALL VERIFY ALL OPENINGS THROUGH WALLSWITH SHOP DRAWINGS, SHOWING OPENINGS IN THE SLABS INCLUDING, BUT NOT LIMITED TO, SLEEVE SIZESAND LOCATIONS, DUCT SIZES AND LOCATIONS, ETC.
CO.03 SEE ARCHITECTURAL DRAWINGS FOR TYPE AND LOCATION OF ALL ARCHITECTURAL FINISHES,FLOOR FINISHES, FLOOR DEPRESSIONS, AND CURBS AND FOR ALL WATERPROOFING AND/OR DAMPPROOFINGDETAILS. SEE MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR ADDITIONAL WALL AND/OR SLABOPENINGS NOT SHOWN ON THE STRUCTURAL DRAWINGS.
CO.04 THE CONTRACTOR SHALL SUBMIT DETAILED DRAWINGS SHOWING THE LOCATIONS OF ALLCONSTRUCTION JOINTS, CURBS, AND SLAB DEPRESSIONS, IF ANY, AND DESCRIBE THE CONCRETE PLACEMENTSEQUENCE. ALL CURBS SHALL BE REINFORCED WITH AT LEAST 1-#4 CONTINUOUS AND #3 AT 16" C/C DOWELSTO THE STRUCTURE BELOW, UNLESS NOTED OTHERWISE.
CO.05 ALL CONCRETE SHALL BE NORMALWEIGHT (145 PCF DENSITY)AND SHALL DEVELOP MINIMUM 28-DAY STRENGTH AS FOLLOWS:
FOOTINGS & FOUNDATIONS f'c= 4,000 PSIFOUNDATION WALLS f'c= 4,000 PSISLABS ON GRADE f'c= 3,500 PSIFRAMED SLABS AND BEAMS f'c= 4,000 PSICOLUMNS f'c= 5,000 PSI
CO.06 ALL CONCRETE EXPOSED TO THE EXTERIOR SHALL BE AIR- ENTRAINED (MINIMUM 6%). WATERREDUCING PLASTICIZING ADMIXTURES MAY BE USED, PENDING APPROVAL OF THE ARCHITECT.
CO.07 NO CALCIUM CHLORIDE OR CHLORIDE ION PRODUCING ADMIXTURE SHALL BE USED IN ANYCONCRETE.
CO.08 FORMWORK FOR ALL CONCRETE WHICH WILL BE EXPOSED IN THE COMPLETED BUILDING SHALL BECONSTRUCTION FROM A SUITABLE PLASTIC SURFACED PLYWOOD WHICH WILL PRODUCE AN ACCEPTABLYSMOOTH SURFACE. ALSO SEE THE SPECIFICATIONS.
CO.09 VERTICAL WALL CONSTRUCTION JOINTS SHALL BE FORMED WITH VERTICAL BULKHEADS ANDKEYWAYS. WALL REINFORCEMENT SHALL BE CONTINUOUS THROUGH THE JOINT OR SHALL BE DOWELEDWITH AN EQUIVALENT AREA OF REINFORCEMENT.
CO.10 ALL CONSTRUCTION JOINTS SHALL BE WIRE-BRUSHED AND CLEANED IMMEDIATELY PRIOR TOPLACING NEW CONCRETE. ALLOW 24 HOURS MINIMUM TO ELAPSE BETWEEN PLACEMENTS.
CO.11 PROVIDE CONTINUOUS WATERSTOPS IN VERTICAL CONSTRUCTION JOINTS, IN BASEMENT ANDELEVATOR PIT WALLS, AND IN ALL OTHER WALLS ADJACENT TO BELOW GRADE SLABS.
CO.12 EXPOSED EXTERNAL CONCRETE CORNERS SHALL BE CHAMFERED PER ARCH DETAILS.
CO.13 INTERIOR SLABS ON GRADE THICKNESSES AND REINFORCEMENT SHALL BE AS SHOWN AND NOTEDON THE PLANS, THICKENED OR DEPRESSED AS REQUIRED FOR THE DETAILS. DEPRESSED SLABS SHALLMAINTAIN FULL THICKNESS UNLESS NOTED OTHERWISE. SEE NOTE RS.09 FOR THE PLACEMENT OF WELDEDWIRE FABRIC. A VAPOR RETARDED SHALL BE PROVIDED UNDER ALL INTERIOR SLABS ON GRADE PER THEPROJECT SPECIFICATIONS.
CO.14 SLABS ON GRADE SHALL BE PLACED IN ALTERNATE STRIPS WITH A MAXIMUM WIDTH OF 15'-0" OR ASSHOWN ON PLAN. CONTROL JOINTS SHALL BE CUT WITHIN A 8-12 HOURS AFTER THE CONCRETE HAS SET.CONTROL JOINTS SHALL NOT EXCEED 15'-0" INTERVALS IN EACH DIRECTION, AND SHALL BE LOCATED TOCONFORM WITH BAY SPACING WHEREVER POSSIBLE (I.E. AT COLUMN CENTERLINES, HALF-BAYS, THIRD-BAYS)
CO.15 SLOPE CONCRETE SLABS, WHERE REQUIRED, TO FLOOR DRAINS SHOWN ON THE ARCHITECTURALAND PLUMBING DRAWINGS. MAINTAIN MINIMUM SLAB THICKNESSES AS SHOWN ON THE STRUCTURALDRAWINGS.
CO.16 NO SLAB SHALL HAVE COLD JOINTS IN A HORIZONTAL PLANE. CONSTRUCTION JOINTS IN ELEVATEDCONCRETE ON METAL DECK SHALL BE MADE AT THE THIRD POINT OF THE SPAN.
CO.17 ALL EXPOSED STRUCTURAL STEEL SHALL BE HOT-DIP GALVANIZED.
GENERAL NOTES
GE.01 BEFORE SUBMITTING A PROPOSAL FOR THIS WORK, THE CONTRACTOR SHALL VISIT THEPREMISES AND ACQUAINT HIMSELF FULLY WITH THE EXISTING CONDITIONS, TEMPORARY CONSTRUCTIONREQUIRED, QUANTITIES AND TYPES OF EQUIPMENT REQUIRED, ETC. HIS BID SHALL INCLUDE ALL SUMSREQUIRED TO DO THE WORK WITHIN THE EXISTING CONDITIONS. DISRUPTION OF NORMAL ACTIVITIES INTHE WORK AREA MUST BE KEPT TO A MINIMUM
GE.02 THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONSTRUCTION, DIMENSIONS, MEMBERSIZES, AND ELEVATIONS FOR CONFORMANCE WITH THE DRAWINGS. ALL DISCREPANCIES SHALL BEBROUGHT TO THE ATTENTION OF THE ARCHITECT IMMEDIATELY.
GE.03 UNLESS NOTED OTHERWISE, DETAILS, SECTIONS, AND NOTES ON THE DRAWINGS ARE INTENDEDTO BE TYPICAL FOR SIMILAR CONDITIONS
GE.04 DIMENSIONS ON STRUCTURAL DRAWINGS ARE TO BE CHECKED AGAINST THE DRAWINGS OF OTHERDISCIPLINES, AND ALL DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECTIMMEDIATELY.
GE.05 COORDINATE WITH THE ARCHITECTURAL DRAWINGS FOR LINTELS, METAL WALL FRAMING, SHELFANGLES, SIZE AND LOCATION OF SLOPES, DEPRESSED AREAS, FINISH FILLS, CHAMFERS, GROOVES,SLEEVES, INSERTS, ETC.
GE.06 COORDINATE WITH MECHANICAL/ELECTRICAL/PLUMBING DRAWINGS FOR DUCTWORK, PIPESLEEVES, FLOOR DRAINS, INSERTS, HANGERS, TRENCHES, PITS, PADS, WALL AND SLAB OPENINGS,CONDUIT RUNS IN WALLS AND SLABS, SIZE AND LOCATION OF MACHINE OR EQUIPMENT SUPPORTS, BASES,ANCHOR BOLTS, ETC
GE.07 ELEVATIONS SHOWN REFER TO PROJECT DATUM WHICH IS ELEV 0'-0" = +17.42' CCD
GE.08 SHOP DRAWINGS PREPARED BY THE CONTRACTOR AND/OR HIS SUPPLIERS SHALL BE REVIEWEDBY THE ARCHITECT ONLY FOR CONFORMANCE WITH THE DESIGN INTENT. NO WORK SHALL BE STARTEDWITHOUT SUCH REVIEW.
GE.09 SHOP DRAWINGS PREPARED BY SUPPLIERS AND SUBCONTRACTORS SHALL BE REVIEWED BY THECONTRACTOR PRIOR TO SUBMISSION TO THE ARCHITECT
GE.10 DESIGN LOADS, ALLOWABLE STRESSES AND STRUCTURAL CAPACITIES ARE BASED ON THECHICAGO BUILDING CODE, WITH LOCAL AMENDMENTS.
DESIGN WIND LOADSMAIN WIND RESISTING SYSTEM 25 PSFCOMPONENTS & CLADDING 30 PSF
DESIGN LIVE LOADSCLASSROOM 40 PSFLABORATORIES 75 PSFAUDITORIUM - FIXED SEATS 60 PSFSTAGE FLOOR 150 PSFGYMNASIUM 100 PSF
STAIR / CORRIDOR 1ST FL 100 PSFCORRIDOR ABOVE 1ST FL 80 PSFROOF SNOW 25 PSF OR DRIFT
EXISITING DRAWINGS
EX.01 EXISTING STRUCTURE IS BASED ON THE FOLLOWING DRAWING SETS:
"ADDITION TO THE LAFAYETTE SCHOOL - WASHTENAW AVE & AUGUSTA",PREPARED BY NORMAND PATTON ARCHITECT, DATED DECEMBER 1897
"ADDITION & ALTERATIONS - LAFAYETTE PUBLIC SCHOOL,PREPARED BY JOHN C. CHRISTENSEN ARCHITECT, DATED 5-14-1921
INFORMATION RELATED TO THE ORIGINAL 1893 STRUCTURE IS BASED ON FIELD OBSERVATIONSPERFORMED BY THE AOR AND EOR.
EX.02 GC TO FIELD VERIFY CONFIGURATION OF EXISTING STRUCTURE PRIOR TO CONSTRUCTION
EXCAVATION AND BACKFILL (CONT'D)
EB.07 ALL SOIL SUPPORTED FOUNDATIONS SHALL BE FOUNDED UPON UNDISTURBED, NATURAL SUBGRADEWITH A MINIMUM ALLOWABLE BEARING CAPACITY OF 2,500 PSF, AS INDICATED IN THE GEOTECHNICAL REPORTREFERENCED IN NOTE EB.14 AND AS FIELD VERIFIED AND APPROVED BY THE OWNER'S SOIL TESTINGLABORATORY. THE FOOTING ELEVATIONS AND SOIL BEARING CAPACITIES AS SHOWN ON THE DRAWINGS AREESTIMATED FROM THE SOIL BORING DATA. FINAL, EXACT ELEVATIONS AND SOIL BEARING CAPACITIES SHALL BEFIELD DETERMINED AND VERIFIED BY THE OWNER'S SOIL TESTING LABORATORY AND REVIEWED BY THEARCHITECT/ENGINEER PRIOR TO PLACEMENT OF CONCRETE. THE CONTRACTOR SHALL IMMEDIATELY NOTIFYTHE ARCHITECT IN THE EVENT THAT THE SOIL CONDITIONS ENCOUNTERED VARY FROM THOSE ASSUMED IN THEDESIGN.
EB.08 DO NOT BACKFILL AGAINST BASEMENT WALLS UNTIL GROUND FLOOR AND LOWER LEVEL SLABS HAVEBEEN PLACED AND THE CONCRETE HAS ATTAINED FULL DESIGN STRENGTH.
EB.09 BACKFILL AGAINST SIDES OF FOUNDATION WALLS SHALL BE PLACED SIMULTANEOUSLY ON BOTHSIDES TO THE TOP OF THE WALL.
EB.10 NO MUD SLABS, FOOTINGS, OR SLABS SHALL BE PLACED ONTO OR AGAINST SUBGRADE CONTAININGFREE WATER, FROST, OR ICE.
EB.11 THE CONTRACTOR SHALL PROVIDE ALL NECESSARY MEASURES TO PREVENT ANY FROST OR ICEFROM PENETRATING ANY FOOTINGS OR SLAB SUBGRADE BEFORE AND AFTER PLACEMENT OF CONCRETE UNTILSUCH SUBGRADES ARE FULLY PROTECTED BY THE PERMANENT BUILDING STRUCTURE.
EB.12 THE CONCRETE FOR EACH ISOLATED FOOTING SHALL BE PLACED IN ONE (1) CONTINUOUSPLACEMENT.
EB.13 ALL PERIMETER WALL AND COLUMN FOOTINGS SHALL BEAR A MINIMUM OF 4'-0" BELOW FINISHEDGRADE.
EB.14 FOR ADDITIONAL SITE CONDITIONS, FOUNDATION CONSTRUCTION CONSIDERATIONS ANDRECOMMENDATIONS, REFER TO THE GEOTECHICAL REPORT, REPORT OF GEOTECHNICAL INVESTIGATION -PROPOSED IMPROVEMENTS AT JEAN DE LAFAYETTE ELEMENTARY SCHOOL, 2714 WEST AUGUSTA BLVDCHICAGO, COOK COUNTY, ILLINOIS, PREPARED BY CARDNO ATC AND DATED JANUARY 17, 2014.CARDNO ATC REPORT NO. 023.25099.1401
MAXIMUM NET SOIL BEARING PRESSURESCONTINUOUS WALL FOOTINGS 1500 PSFMAT & SPREAD FOOTINGS 1500 PSF
CONCRETE MASONRY
MS.01 ALL CONCRETE MASONRY CONSTRUCTION SHALL CONFORM TO THE LATEST EDITION OF THE"BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES," ACI 530/ASCE 5/TMS 402.
MS.02 THE OWNER'S MASONRY TESTING LABORATORY SHALL PERFORM ALL TESTING OF UNITMASONRY COMPONENTS IN ACCORDANCE WITH ACI 530/ASCE 5/TMS 402. WRITTEN REPORTS, SIGNEDAND SEALED BY THE INSPECTING PROFESSIONAL AND INCLUDING THE LICENSE EXPIRATION DATE, SHALLBE SUBMITTED TO THE ARCHITECT FOR REVIEW. SEE ALSO THE PROJECT SPECIFICATIONS.
MS.03 ALL CONCRETE MASONRY UNITS SHALL BE NORMAL WEIGHT WITH TWO CELLS AND CONFORMTO ASTM C90.
MS.04 ALL MORTAR SHALL CONFORM TO ASTM C270.
MS.05 ALL GROUT SHALL CONFORM TO ASTM C476.
MS.06 THE MINIMUM SPECIFIED NET AREA COMPRESSIVE STRENGTH OF CONCRETE MASONRY (F'M)SHALL BE 1500 PSI AND SHALL CONSIST OF THE FOLLOWING COMPONENTS:
CONCRETE MASONRY UNITS:2,150 PSI, MINIMUM NET AREA COMPRESSIVE STRENGTH
PORTLAND CEMENT MORTAR:TYPE N, 1,800 PSI, MINIMUM COMPRESSIVE STRENGTH
GROUT2,500 PSI, MINIMUM COMPRESSIVE STRENGTH
MS.07 ALL BAR REINFORCEMENT STEEL USED IN MASONRY SHALL BE HIGH STRENGTH NEW BILLETSTEEL CONFORMING TO ASTM A615, GRADE 60.
MS.08 THE MINIMUM CLEAR DISTANCE BETWEEN PARALLEL REINFORCEMENT BARS, EXCEPT INCOLUMNS, SHALL BE EQUAL TO THE GREATER OF THE NOMINAL DIAMETER OF THE BAR OR 1".
MS.09 VERTICAL REINFORCEMENT LAP SPLICES, WHERE REQUIRED, SHALL BE A MINIMUM OF 48 BARDIAMETERS.
MS.10 ALL REINFORCEMENT BARS SHALL BE COMPLETELY EMBEDDED IN GROUT AND SHALL HAVEMASONRY COVERAGE NOT LESS THAN:
#6 BARS AND LARGER 2"#5 BARS AND SMALLER 1 1/2"
MS.11 PROVIDE SOLID GROUTED MASONRY UNITS THREE COURSES DEEP BY 32" WIDE MINIMUMUNDER ALL BEAM AND LINTEL BEARING POINTS, UNLESS NOTED OTHERWISE.
MS.12 VERTICAL CELLS TO BE FILLED WITH GROUT SHALL BE ALIGNED TO PROVIDE CONTINUOUS,UNOBSTRUCTED OPENING OF THE DIMENSIONS INDICATED. CELLS WHICH WILL CONTAIN VERTICALREINFORCEMENT SHALL HAVE A MINIMUM 2” CLEAR OPENING.
MS.13 GROUT FOR FILLING REINFORCED OR NON-REINFORCED CELLS SHALL BE PLACED IN MAXIMUM4’ LIFTS AND CONSOLIDATED IN PLACE BY VIBRATION OR OTHER METHODS WHICH INSURE COMPLETEFILLING OF THE CELLS. ALL CELLS CONTAINING REINFORCEMENT BARS OR ANCHOR BOLTS SHALL BEFULLY GROUTED.
MS.14 PROVIDE ADEQUATE TEMPORARY BRACING AS REQUIRED DURING CONSTRUCTION TOWITHSTAND LATERAL LOADS AND THE PRESSURES OF FLUID GROUT.
MS.15 HOLLOW UNITS SHALL BE LAID WITH FULL MORTAR COVERAGE ON HORIZONTAL AND VERTICALFACE SHELLS. WEBS SHALL ALSO BE BEDDED WHERE THEY ARE ADJACENT TO CELLS TO BEREINFORCED OR FILLED WITH GROUT, IN THE STARTING COURSE ON FOOTINGS AND SOLID FOUNDATIONWALLS, AND IN NON-REINFORCED OR GROUTED PIERS, PILASTERS AND COLUMNS.
MS.16 SOLID MASONRY UNITS SHALL BE LAID WITH FULL HEAD AND BED JOINTS.
MS.17 PROVIDE CONTINUOUS GALVANIZED HORIZONTAL MASONRY LADDER TIE REINFORCEMENT AT16" ON CENTER, MINIMUM VERTICALLY, UNLESS NOTED OTHERWISE. DO NOT USE TRUSS TIEREINFORCEMENT.
MS.18 ALL ANCHOR BOLTS CAST INTO MASONRY UNITS SHALL CONFORM TO ASTM A 307. ALLADHESIVE, SLEEVE, OR EXPANSION ANCHORS INTO MASONRY SHALL BE MANUFACTURED BY HILTI ORAPPROVED EQUAL AND INSTALLED PER MANUFACTURER'S RECOMMENDATIONS.
MS.19 UNLESS NOTED OTHERWISE, REINFORCE ALL 6 INCH AND 8 INCH CMU WITH #5 @ 32" OC IN SOLIDGROUTED CELLS.
MS.20 AT WALLS TO BE SOLID GROUTED, THE OWNER’S TESTING AGENT SHALL INSPECT WALLREINFORCEMENT PLACEMENT PRIOR TO GROUTING.
STEEL DECK
SD.01 ALL DESIGN, DETAILING, FABRICATION AND ERECTION OF DECK UNITS SHALL. CONFORM TOTHE LATEST EDITIONS OF THE STEEL DECK INSTITUTE (SDI) SPECIFICATIONS FOR STEEL FLOOR DECKAND FOR STEEL ROOF DECK. DECK SECTION PROPERTIES SHALL. BE COMPUTED IN ACCORDANCEWITH AISI "SPECIFICATION FOR THE DESIGN OF COLD FORMED STEEL STRUCTURAL MEMBERS” ANDHAVE MINIMUM DECK PROPERTIES AS FOLLOWS:
Ip In Sp Sn1 1/2" TYPE B ROOF DECK, 20GA. 0.210 0.210 0.232 0.2452" TYPE VLI COMPOSITE DECK, 20GA. 0.430 0.430 0.369 0.386
SD.02 ROOF DECK SHALL BE FABRICATED FROM STEEL CONFORMING TO ASTM A1008 WITH AMINIMUM YIELD STRENGTH OF 33,000 PSI. COMPOSITE AND NON-COMPOSITE FLOOR DECK SHALL BEFABRICATED FROM STEEL CONFORMING TO ASTM A653, STRUCTURAL QUALITY GRADE 33.
SD.03 ROOF DECK SHALL BE SHOP PAINTED WITH PHOSPHATE PAINT. FLOOR DECK SHALL BEGALVANIZED. GALVANIZING SHALL CONFORM TO ASTM A924, CLASS G60.
SD.04 THE DEPTH AND GAGE OF ALL DECK TYPES SHALL BE AS INDICATED ON THE DRAWINGS. ALLROOF DECK SHALL BE WIDE RIB.
SD.05 PROVIDE CONTINUOUS SHEET METAL CLOSURES AT ALL SLAB OPENINGS AND SLAB EDGESAND CONTINUOUS DECK CLOSURES AT ALL DECK ENDS. PROVIDE STEEL ANGLE OR BENT PLATECLOSURES AS INDICATED ON THE DRAWINGS.
SD.06 ROOF DECK SHALL BE WELDED AT EACH SUPPORT. PROVIDE SCREWED OR WELDED SIDELAPS. SIDE LAP WELDS SHALL BE EITHER A 5/8” PUDDLE WELD OR A 1/16" X 1 1/2" ARC SEAM WELD.SCREWS SHALL BE TEK SCREWS.
SD.07 PRIOR TO THE START OF ERECTION, A WELDING PROCEDURE SHALL BE ESTABLISHED FORTHE PLUG WELDING OF THE STEEL DECKING TO THE STRUCTURAL STEEL FOR THE PARTICULAR GAGEOF DECK USED. ALL WELDERS SHALL BE AWS CERTIFIED USING THIS PROCEDURE.
SD.08 ALL ROOF DECK SHALL BE FORMED WITH TELESCOPED ENDS TO LAP ENDS OF SHEETS AMINIMUM OF 2".
SD.09 PROVIDE CONTINUOUS RIDGE AND VALLEY PLATES, COLUMN CLOSURES, CANT STRIPS, SUMPPLATES AT PIPING PENETRATIONS AND RECESSED SUMP PANS AT ALL ROOF DRAINS AND ROOF VENTS,AS REQUIRED. PROVIDE SUPPLEMENTAL FRAMING AT OPENINGS AS SHOWN FOR THE SUPPORT OF THEMETAL DECK. ALL OPENINGS SHALL BE COORDINATED WITH THE ARCHITECTURAL, MECHANICAL,PLUMBING, AND ELECTRICAL DRAWINGS.
SD.10 STEEL DECKING SHOULD BE STORED OFF THE GROUND WITH ONE END ELEVATED TOPROVIDE DRAINAGE AND SHOULD BE PROTECTED FROM THE ELEMENTS WITH A WATERPROOFCOVERING VENTILATED TO AVOID CONDENSATION.
REINFORCEMENT STEEL
RS.01 ALL CONCRETE REINFORCEMENT SHALL BE DETAILED, FABRICATED, LABELED, SUPPORTED ANDSPACED IN FORMS, AND SECURED IN PLACE IN ACCORDANCE WITH PROCEDURES AND REQUIREMENTSOUTLINES IN THE LATEST EDITIONS OF THE "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE"(ACI 318) AND THE "DETAILS AND DETAILING OF CONCRETE REINFORCEMENT" (ACI 315). AT EPOXY COATEDBARS, USE DIELECTRIC MATERIAL FOR BAR SUPPORTS AND NYLON COATED TIE WIRE.
RS.02 CHECKED SHOP DRAWINGS SHOWING REINFORCEMENT DETAILS, INCLUDING STEEL SIZES,SPACING, AND PLACEMENT SHALL BE SUBMITTED TO THE ARCHITECT FOR REVIEW PRIOR TO FABRICATION.
RS.03 ALL REINFORCEMENT STEEL SHALL BE HIGH STRENGTH NEW BILLET STEEL CONFORMING TO THELATEST EDITION OF ASTM A 615. GRADE 60.
RS.04 ALL WELDED WIRE FABRIC SHALL CONFORM TO LATEST EDITION OF ASTM A 185
RS.05 THE FOLLOW CLEAR COVER SHALL BE PROVIDED FOR REINFORCEMENT IN CAST-IN-PLACECONCRETE, UNLESS NOTED OTHERWISE:
CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH 3"
EXPOSED TO EARTH OR WEATHER:#6 THROUGH #18 BARS 2"#5 BARS, 5/8" DIA. WIRE AND SMALLER 1 1/2"
NOT EXPOSED TO WEATHER IN CONTACT WITH GROUND:SLABS & WALLS 3/4"
PIERS, COLUMNS, AND BEAMS:PRIMARY REINFORCEMENT, TIES, AND STIRRUPS 1 1/2"
RS.06 PROVIDE ADEQUATE BOLSTERS, HIGH CHAIRS, SUPPORT BARS, ETC. TO MAINTAIN SPECIFIEDCLEARANCES FOR THE ENTIRE LENGTH OF ALL REINFORCEMENT BARS. PROVIDE CONTINUOUS #4 SPACERBARS IN WALLS AND SLABS TO SUPPORT DOWELS, AS REQUIRED. WELDED WIRE FABRIC SHALL BESUPPORTED IN PROPER POSITION ON CHAIRS AND CARRIER BARS.
RS.07 ALL EMBEDMENT LENGTHS SHALL CONFORM TO THE LATEST EDITION OF ACI 318.
RS.08 ALL REINFORCEMENT SPLICES SHALL BE LAP SPLICED AND WIRED TOGETHER IN CONTACT. SPLICELENGTHS SHALL CONFORM TO THE LATEST ACI CRITERIA FOR SIZE AND TYPE OF REINFORCEMENT STEELAND CONCRETE COMPRESSIVE STRENGTHS SPECIFIED. UNLESS NOTED OTHERWISE, MINIMUM LAP SHALL BE40 BAR DIAMETERS.
RS.09 ALL WELDED WIRE FABRIC SHALL BE LAPPED TWO (2) FULL MESH PANELS AT SIDE AND END LAPSAND TIED SECURELY. PROVIDE ADDITIONAL REINFORCEMENT WHERE SHOWN ON THE DRAWINGS. PLACEMESH 1" FROM THE TOP OF SLABS. NO ELECTRICAL CONDUIT SHALL BE PLACED ABOVE WELDED WIREFABRIC SLABS.
RS.10 NO REINFORCEMENT STEEL SHALL BE WELDED IN ANYWAY UNLESS PRIOR WRITTEN APPROVAL ISGIVEN BY THE ARCHITECT.
RS.11 CORNER BARS SHALL BE PROVIDED AT WALL CORNERS EQUAL TO THE HORIZONTAL WALLREINFORCEMENT.
RS.12 ALL CONCRETE FORMED SLAB OR WALL OPENINGS SHALL BE REINFORCED WITH 2-#5 BARSPLACED ONE IN EACH FACE AT 45 DEGREES TO OPENING CORNERS.
RS.13 UNLESS NOTED OTHERWISE, ALL CONCRETE WORK SHALL CONTAIN AT LEAST MINIMUMREINFORCEMENT AS REQUIRED BY ACI 318.
EXCAVATION AND BACKFILL
EB.01 BEFORE ANY OTHER BUILDINGS OPERATIONS ARE STARTED, REMOVE ALL BITUMINOUS PAVEMENT,LOOSE GRAVEL, ABANDONED FOUNDATIONS, BLACK LOAM, ORGANIC MATERIAL, AND FILL ENCOUNTEREDWITHIN THE AREA TO BE OCCUPIED BY NEW CONSTRUCTION. NONE OF THIS MATERIAL OR OTHEREXCAVATED ON-SITE SOILS, WHICH ARE FOUND TO BE UNSUITABLE, SHALL BE USED FOR FILL WITHIN ORADJACENT TO THE BUILDING. STORE GRAVEL ON SITE FOR POTENTIAL REUSE.
EB.02 GENERAL MACHINE EXCAVATION FOR FOOTINGS SHALL STOP NOT LESS THAN 6" ABOVE SCHEDULEDELEVATIONS OF BOTTOMS OF FOOTINGS. FINAL EXCAVATION TO UNDISTURBED SOIL AT REQUIREDFOOTING ELEVATION SHALL BE DONE BY HAND NOT MORE THAN 48 HOURS BEFORE THE FOOTING IS PLACED.
EB.03 ALL NECESSARY CHANGES IN ELEVATION OF WALL FOOTINGS SHALL BE MADE IN STEPS OF NOTMORE THAN 2'-0" HIGH AND A MINIMUM OF 4'-0" APART, EXCEPT AS OTHERWISE DETAILED.
EB.04 AFTER EXCAVATING FOR ALL EARTH-SUPPORTED SLABS AND PRIOR TO PLACING FILL, THE EXPOSEDNATURAL SOIL SHALL BE COMPACTED TO 95% OF ASTM D-1557 (MODIFIED PROCTOR) MAXIMUM DENSITY ATOPTIMUM MOISTURE CONTENT.
EB.05 SEE GEOTECHNIC REPORT FOR FOUNDATION BACKFILL AND FILL REQUIRED TO ESTABLISH FINALSUB-GRADES. ALL EARTH-SUPPORTED SLABS SHALL HAVE AT LEAST 6" OF CA6 DIRECTLY BELOW THE SLABCOMPACTED TO 95% OF ASTM D-1557 (MODIFIED PROCTOR) MAXIMUM DENSITY AT OPTIMUM MOISTURECONTENT.
EB.06 BACKFILL PLACED DIRECTLY ADJACENT TO BASEMENT AND RETAINING WALLS SHALL BE CA6COMPACTED TO 95% OF ASTM D-1557 (MODIFIED PROCTOR) MAXIMUM DENSITY AT OPTIMUM MOISTURECONTENT. AT TOP OF BACKFILL, PROVIDE 1'-6" OF CA6 COMPACTED TO 95% OF ASTM D-1557 (MODIFIEDPROCTOR) MAXIMUM DENSITY AT OPTIMUM MOISTURE CONTENT.
FIRE PROOFING
FP.01 SEE ARCHITECURE DRAWINGS AND PROJECT SPECIFICATIONS FOR PROJECT FIRE SEPARATIONREQUIREMENTS AND PROJECT FIREPROOFING REQUIREMENTS.
FP.02 EXISTING STRUCTURE INLCUDES CLAY TILE ELEMENTS WHICH PROVIDE REQUIRED FIREPROOFINGOF STRUCTURAL ELEMENTS. MAINTAIN EXISTING FIRE PROTECTION AND FIRE RATING AT EXISTING STEELSTRUCTURE .
FP.03 AT NEW ATTACHMENTS AND MODIFICATIONS TO EXISTING STRUCTURAL STEEL ELEMENTS, WHEREFIRE PROTECTION IS DISTURBED, PROVIDE SPRAY ON FIREPROOFING AS REQUIRED TO MAINTAIN SPECIFIEDFIRE RATING.
Structural Drawing List
S0.0 GENERAL NOTESS0.1 KEY PLANSS0.2 KEY PLANSS0.3 KEY PLANSS0.4 LINTEL KEY PLANS0.5 LINTEL KEY PLANS0.6 LINTEL KEY PLANS0.7 LINTEL KEY PLANS1.0 ELEVATOR PLANS, SECTIONS & DETAILSS1.1 PLANS, SECTIONS & DETAILSS2.0 AUDITORIUM PLANS, SECTIONS & DETAILSS2.1 AUDITORIUMS2.2 CHILLER ENCLOSURES3.0 LULA PLANS. SECTIONS & DETAILSS4.0 PLANS, SECTIONS & DETAILSS4.1 ROOF PART PLANS & SECTIONSS4.2 ROOF PLANS, SECTIONS & DETAILSS5.0 PLANS, SECTIONS & DETAILSS6.0 PLANS, SECTIONS & DETAILSS6.1 SECTIIONS AND DETAILS
S-ALT1 ALTERNATE STRUCTURAL DETAILS
CHICAGOPUBLICSCHOOLS
CPS
2013 KOO AND ASSOCIATES LTDC
DRAWING NO.
FILE:
JOB:
SCALE:
DRAWN BY:
REVISIONS
WARNING: ASBESTOS-CONTAINING BUILDING MATERIALS ARE ORMAY BE PRESENT IN THIS BUILDING. AN ASBESTOS MANAGEMENTPLAN IS AVAILABLE IN THE SCHOOL FOR REVIEW UPON REQUEST. NOPERSON MAY DISTURB ASBESTOS-CONTAINING MATERIALS UNLESSTHAT PERSON IS A LICENSED ASBESTOS WORKER OR CONDUCTSSUCH WORK IN ACCORDANCE WITH SPECIFICATIONS(S) CONTAINEDIN THE PROJECT DOCUMENTS AND IN COMPLIANCE WITH ILLINOISDEPARTMENT OF HEALTH RULES AND REGULATIONS.
CAPITAL IMPROVEMENT PROGRAMDEPARTMENT OF FACILITIES
Goodfriend Magruder Structure LLC53 W Jackson Blvd, Suite 352Chicago IL 60604312 265 2645www.gmstructure.com
Structural Design and Engineering
KOO AND ASSOCIATES LTD53 W JACKSON BLVD STE 215CHICAGO IL 60604312- 235-0920 PH
KJWW231 S. LaSalle St., Suite 600Chicago IL 60604312 294 0501www.kjww.com
PROJECT NO. 2014-24121-CSP
LAFAYETTE SCHOOL
2714 W. AUGUSTA BLVD.CHICAGO, ILLINOIS 60622
NORTH
Terra Engineering Ltd.225 W Ohio St.Chicago, IL 60654312 467-0123www.terraengineering.com
2/26
/201
4 1:
58:1
5 P
M
S0.0
GENERAL NOTES
Author
NO DATE DESCRIPTION1 02/06/14 BID AND PERMIT2 02/19/14 ISSUED FOR PERMIT3 02/26/14 ADDENDUM #4
3
CLASSROOM102
CLASSROOM104
CLASSROOM101
CLASSROOM103
OFFICES105
MAINOFFICE107
ADJACENTOFFICE109
CLASSROOM106
CLASSROOM110
TEACHER'SLOUNGE108
CLASSROOM111
CLASSROOM113
CLASSROOM115
CLASSROOM112
CLASSROOM117
CLASSROOM119
CLASSROOM121
CLASSROOM123
CLASSROOM125
CLASSROOM120
STORAGE120C
STORAGE120B
TOILETROOM120A
STAIRWELL7A
STAIRWELL2
STAIRWELL2A
STAIRWELL3
STAIRWELL5
STAIRWELL5A
STAIRWELL6
CORRIDORC-1
CORRIDORC-1
CORRIDORC-1
CORRIDORC-1
CORRIDORC-1
CORRIDORC-1
ASHROOM004L
LADDER UPMECH RM
01
09
10
18
19
27
BCDEFGHIJKLM AN
UP
UP
UP
UPUP
D
W
UP
EXST. V.I.F.
1:7 SLOPEEXST. V.I.F.1:8 SLOPE
EXST. V.I.F.
UP
UP
UPUP
UP
UP
UP
UP
DAYCARE025
DAYCARE019
LUNCHROOM002
LUNCHROOM001
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
8'-6" VIF
10'-11" VIF
DN
UP
DNUP
DN
DNUP
UP
DN
UP
DN
CLASSROOM102
CLASSROOM104
CLASSROOM101
CLASSROOM103
OFFICES105
MAINOFFICE107
ADJACENTOFFICE109
CLASSROOM106
CLASSROOM110
TEACHER'SLOUNGE108
CLASSROOM111
CLASSROOM113
CLASSROOM115
CLASSROOM112
CLASSROOM117
CLASSROOM119
CLASSROOM121
CLASSROOM123
CLASSROOM125
CLASSROOM120
STORAGE120C
STORAGE120B
TOILETROOM120A
STAIRWELL7A
STAIRWELL2
STAIRWELL2A
STAIRWELL3
STAIRWELL5
STAIRWELL5A
STAIRWELL6
CORRIDORC-1
CORRIDORC-1
CORRIDORC-1
CORRIDORC-1
CORRIDORC-1
CORRIDORC-1
UPPERCOAL ROOM
004L
LADDER TOMECH RM
UP
SLOPE 5%UP
SLOPE 5%
36"
48"
36"
48"
1'-0"
1'-6"MIN
1'-6"MIN
1'-6"
MIN
1'-6"
MIN
1'-6"
MIN
ADA
2' x 2'
TABLE9' x 4'
10 CHAIRS
ADMINISTRATIVEMANAGER
ADMINISTRATIVEASSISTANT
ADMINISTRATIVEASSISTANT
ADMISSIONSASSISTANT
ADMISSIONSASSISTANT
ADMISSIONSMANAGER
INSTRUCTIONALCOACH
INSTRUCTIONALCOACH
FRESHMANACADEMYLEADER
GUIDANCECOUNSELOR
POST SECONDARYCOUNSELOR
CASEMANAGER
DEAN OFSTUDENTS
102A
101A
105A
106A
108A
107A 109A
110A
112A
112B
111A
113A 115A
117A
119A
120B
121
120A
123A
CL-1B
126A
125A
127A
104CL-1A
103A
102B
101B
103B
106B
106C
106D
108B
105B
105C
105D
105E
107B
107C
110B
109B
109C
111B
111C
111D
112C
112D
112E
113B
113C
113D
115C
115B
115D
117B
117C
117D
119B
123B
125B
GT-1
120C 120D 120E
C-1A
C-1B
C-1C C-1D
107D
E.WD
RT
E.WD
RT
E.WD
RT
E.WD
RT RT
TILEE.AC
RT
RT
RT
RT
RT
WD
RT
RT
RT
RT
RT
RT
RT
RT
RT
RT
RT
RT
RT
RT
RT
RT
RT
RT
RT
RT
RT
RT
RT
RT
RT
RT
RT
RT
RT
E.AC
RT
TILE RT
RT
E.WD
RT
E.WD
RT
E.WD
E.AC
RT
E.AC
RT
E.VCT
RT
RT
RT
CONFERENCEROOM109A
RECEPTIONAREA107A
CLASSROOM125
LARGEENSEMBLE
121
STORAGE120B
VISUAL ARTSOFFICE120A
GALLERY120
CLASSROOM117
STORAGE120C
PRINCIPAL'SOFFICE109B
ASSISTANTPRINCIPAL
109C
CLASSROOM103
CLASSROOM101
BOY'STOILET RM.
CLASSROOM106
TEACHER'SLOUNGE108
CLASSROOM110
CLASSROOM111
CLASSROOM112
CLASSROOM113
CLASSROOM115
CLASSROOM119
GIRL'STOILET RM.
CLASSROOM102
CLASSROOM104
OFFICES107B
OFFICES105
TOILETROOM108B
ADA
ADA
ADA
ADA
ADAADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADAADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
ADA
48"
48"
48"
48"
HS
SE
LEC
T.
S
01
09
10
18
19
27
BCDEFGHIJKLM AN
UP
UP
UP
UPUP
D
W
UP
EXST. V.I.F.
1:7 SLOPEEXST. V.I.F.1:8 SLOPE
EXST. V.I.F.
UP
UP
UPUP
UP
UP
UP
UP
DAYCARE025
DAYCARE019
LUNCHROOM002
LUNCHROOM001
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
12
12
A A
P P
C
6
S1.0E
2S2.1
1
1
S6.0F
S6.0D2BOILER ROOM ROOF
12
12
A A
P P
C
6
S1.0D
S2.0A
S2.2A
1
1
S6.0B
S6.0C
S6.0E
S4.04
S6.0G
S6.04
S6.0J
S1.1B
S6.0H
S-ALT1A
CHICAGOPUBLICSCHOOLS
CPS
2013 KOO AND ASSOCIATES LTDC
DRAWING NO.
FILE:
JOB:
SCALE:
DRAWN BY:
REVISIONS
WARNING: ASBESTOS-CONTAINING BUILDING MATERIALS ARE ORMAY BE PRESENT IN THIS BUILDING. AN ASBESTOS MANAGEMENTPLAN IS AVAILABLE IN THE SCHOOL FOR REVIEW UPON REQUEST. NOPERSON MAY DISTURB ASBESTOS-CONTAINING MATERIALS UNLESSTHAT PERSON IS A LICENSED ASBESTOS WORKER OR CONDUCTSSUCH WORK IN ACCORDANCE WITH SPECIFICATIONS(S) CONTAINEDIN THE PROJECT DOCUMENTS AND IN COMPLIANCE WITH ILLINOISDEPARTMENT OF HEALTH RULES AND REGULATIONS.
CAPITAL IMPROVEMENT PROGRAMDEPARTMENT OF FACILITIES
Goodfriend Magruder Structure LLC53 W Jackson Blvd, Suite 352Chicago IL 60604312 265 2645www.gmstructure.com
Structural Design and Engineering
KOO AND ASSOCIATES LTD53 W JACKSON BLVD STE 215CHICAGO IL 60604312- 235-0920 PH
KJWW231 S. LaSalle St., Suite 600Chicago IL 60604312 294 0501www.kjww.com
PROJECT NO. 2014-24121-CSP
LAFAYETTE SCHOOL
2714 W. AUGUSTA BLVD.CHICAGO, ILLINOIS 60622
NORTH
Terra Engineering Ltd.225 W Ohio St.Chicago, IL 60654312 467-0123www.terraengineering.com
2/26
/201
4 1:
58:3
8 P
M
S0.1
KEY PLANS
Author
SCALE: 1/32" = 1'-0" B KEY PLAN FIRST FLOORSCALE: 1/32" = 1'-0" A KEY PLAN GROUND FLOOR
NO DATE DESCRIPTION1 02/06/14 BID AND PERMIT2 02/19/14 ISSUED FOR PERMIT3 02/25/14 ADDENDUM #34 02/26/14 ADDENDUM #4
3
4
1S1.0
+/-
3' -
8"
NOT VERIFIED3' - 8"
1' -
0"
NEW CONCRETEFOUNDATION
8S1.0
L
8
5" INFILL SLAB
CAVITY WALL wBRICK VENEERABOVESEE ARCH
ELEV PITSEE ARCH
3S1.1
8' - 4"6'
- 3"
+/-
2'-8
"
+/-
1'-5
"
1S1.0
8S1.0 NEW 8" CMU
ALL-AROUND TYP
CAVITY WALL wBRICK VENEERSEE ARCH
3S1.0
3S1.0
L
8
5" INFILL SLAB
8' - 4"
6' -
3"
L3.5x3.5x5/16
+/-
2'-8
"
+/-
1'-5
"
1S1.0
8S1.0
L
8
5" INFILL SLAB
8' - 4"
6' -
3"
L3.5x3.5x5/16
+/-
2'-8
"
+/-
1'-5
"
1S1.0
8S1.0
L
8
5" INFILL SLAB
8' - 4"
6' -
3"
6S1.0
L3.5x3.5x5/16
TYP
L1-
L3
1S1.0
8S1.0
5" INFILL SLAB
HOIST BEAM BELOW
8"+4" BRICK
L
8
W8X35
11S5.0
L4X4X3/8
L4X4X3/8L4X4
X3/8
L4X4
X3/8
8' - 4"
6' -
3"
S1.02
6' - 3"
HOIST BEAM
NEW ROOF DECK3" CONCRETE ON 2" DECKINFILL SLAB PER 3/S5.0
NEW 5" INFILL SLAB
NEW 5" INFILL SLAB
NEW 5" INFILL SLAB
NEW 5" INFILL SLAB
NEW 8" CMU WALLw/ #5@24" VERT INSOLID GROUTEDCELLS, TYP. SEE ARCHFOR ADD'L WALLINFORMATION
W8x21 LINTEL+ 3/8" PL
W8x21 LINTEL+ 3/8" PL
W8x21 LINTEL+ 3/8" PL
W8x21 LINTEL+ 3/8" PL
8" DEEP BONDBM LINTEL w/(2)#5 CONTTYP
BOND BMLINTEL
BOND BMLINTEL
BOND BMLINTEL
L
4" BRICK ON 8" CMUSEE ARCH
S1.04
FIELD VERIFY EXTENT OF EXTGFOUNDATIONS AT ELEVATORPRIOR TO CONSTRUCTION.NOTIFY ARCHITECT OF ANYDISCREPENCIES
TYP
T/CONC ROOF LEVEL
SEE ARCH
T/WALL
SEE ARCH
THIRD FLOOR
SEE ARCH
SECOND FLOOR
SEE ARCH
FIRST FLOOR
SEE ARCH
GROUND FLOOR
EL 0'-0"
T/PIT SLAB
EL -5'-6"
+/-3' - 8"
+/-2' - 8"
+/-1' - 8"
+/-6"
+/-6"
+/-
1' -
2"
1' -
0"
EXTG MASONRY BEARING WALL
EXTG FOUNDATION WALL
EXTG FOUNDATION
PIT6' - 3"
1' - 2"
3"
DRILL IN DOWELS#5@12". USE HILTIHIT-RE500 ADHESIVETYP.
#5@9 EA WAYTBOTTOM
(2) #5 T & B
#5 @16"HORZ & VERT
DOWELS TO MATCHCMU VERT.
L
T/PIT
CONTINUOUS2x4 KEYWAY, TYP
18"x18" SUMPPIT 18" DEEP
#4 @12 EACHWAY BOTTOM
CONTINUOUS2x4 KEYWAY, TYP
SUMP PIT
#5 @16"HORZ & VERT
FIELD VERIFY EXTENT OF EXTGFOUNDATIONS AT ELEVATORPRIOR TO CONSTRUCTION.NOTIFY ARCHITECT OF ANYDISCREPENCIES
2S1.1
S1.13
UNDERPINNING 8" 2'-0"
#5@12" O.C.EA WAY TOP
8"
GROUND FLOOR
EL 0'-0"
T/PIT SLAB
EL -5'-6"
EXTG S.O.G.VIF
8" 1'-6"
6"
#5 CONT
DRILL IN DOWELS#5@12". USE HILTI HIT-RE500 ADHESIVETYP.
SEE GENERAL NOTES & GEOTECHREPORT FOR BACKFILL &COMPACTION REQIREMENTS
2'-0
"2'
-0"
2'-0
"2'
-0"
2"DRILL IN DOWELS#4@12" w/STD HKUSE HILTI HIT-RE500ADHESIVE
8"
W8x21
W8x21
W8x21
W8x21
8
T/CONC ROOF LEVEL
SEE ARCH
T/WALL
SEE ARCH
S1.05
THIRD FLOOR
SEE ARCH
SECOND FLOOR
SEE ARCH
FIRST FLOOR
SEE ARCH
GROUND FLOOR
EL 0'-0"
T/PIT SLAB
EL -5'-6"
SEE ARCH3'-11" TYP
OPNG IN NEWCMU WALL, TYP
OPNG IN EXTGMASONRYWALL, TYP
SEE ARCHFOR INFILL ATEXTGWINDOWS
SEE ARCH8'-8" TYP
JOINT AT NEW CMU / EXTGMASONRY: PROVDE 1/2"BACKER ROD ANDELASTOMERIC SEALANT, TYP.
CONNECT ANGLE TO EXTGMASONRY @24" O.C. w/ 5/8" x8" LONG HILTI HAS-E RODSw/ NUT & WASHER. USE HIT-20 ADHESIVE
EXTG MASONRYWALL
NEW GALVANIZEDLATERAL SUPPORTANGLE L4x4x3/8 INGROUTED CMUCELLS
NEW CMU WALL
L
BOND BEAM LINTEL
BOND BEAM w/ (2)#5EXTEND REINF 24"BEYOND OPENING
WALL VERTREINF. INGROUTED CELLS
8" NOM. CMU.
T/CONC
SEE ARCH
L4X4X3/8
5/8' DIA EXPANANCHORS AT 24" O.C.w/3-3/8" EMBED
5" INFILL SLABPER3/S5.0
TYP ALL-AROUND ELEVATOR
8" CMU + 4" BRICKVENEER. SEE ARCH
L
EXTGMASONRYWALL
NEW CMU WALL
1' - 5" +/-
MIN3"
3"2"
NEW INFILL SLABEXTG FLOORSLAB
DECK SUPPORT ANGLEBEYOND w/(2) 5/8" DIAEXPAN ANCHORS @18"O.C. EMBED 3-3/8"
#4@12@ DOOR OPNG8"
1' -
0"
DECK BEARINGON EXTG WALL
8"DRILL#4@12INSTALL w/HILTI HIT HY-70ADHESIVE
4
PLAN VIEW
L4x4
HAS ROD
SLOT END OFCMU WALLGROUT SOLID
CHICAGOPUBLICSCHOOLS
CPS
2013 KOO AND ASSOCIATES LTDC
DRAWING NO.
FILE:
JOB:
SCALE:
DRAWN BY:
REVISIONS
WARNING: ASBESTOS-CONTAINING BUILDING MATERIALS ARE ORMAY BE PRESENT IN THIS BUILDING. AN ASBESTOS MANAGEMENTPLAN IS AVAILABLE IN THE SCHOOL FOR REVIEW UPON REQUEST. NOPERSON MAY DISTURB ASBESTOS-CONTAINING MATERIALS UNLESSTHAT PERSON IS A LICENSED ASBESTOS WORKER OR CONDUCTSSUCH WORK IN ACCORDANCE WITH SPECIFICATIONS(S) CONTAINEDIN THE PROJECT DOCUMENTS AND IN COMPLIANCE WITH ILLINOISDEPARTMENT OF HEALTH RULES AND REGULATIONS.
CAPITAL IMPROVEMENT PROGRAMDEPARTMENT OF FACILITIES
Goodfriend Magruder Structure LLC53 W Jackson Blvd, Suite 352Chicago IL 60604312 265 2645www.gmstructure.com
Structural Design and Engineering
KOO AND ASSOCIATES LTD53 W JACKSON BLVD STE 215CHICAGO IL 60604312- 235-0920 PH
KJWW231 S. LaSalle St., Suite 600Chicago IL 60604312 294 0501www.kjww.com
PROJECT NO. 2014-24121-CSP
LAFAYETTE SCHOOL
2714 W. AUGUSTA BLVD.CHICAGO, ILLINOIS 60622
NORTH
Terra Engineering Ltd.225 W Ohio St.Chicago, IL 60654312 467-0123www.terraengineering.com
2/26
/201
4 1:
58:4
8 P
M
S1.0
ELEVATOR PLANS,SECTIONS & DETAILS
Author
SCALE: 1/4" = 1'-0" E ELEV PART PLAN - GROUNDSCALE: 1/4" = 1'-0" D ELEV PART PLAN - 1ST
SCALE: 1/4" = 1'-0" C ELEV PART PLAN - 2NDSCALE: 1/4" = 1'-0" B ELEV PART PLAN - 3RD
SCALE: 1/4" = 1'-0" A ELEV PART PLAN - ROOF
SCALE: 3/16" = 1'-0" 1 ELEVATOR SECTION
SCALE: 1/2" = 1'-0" 2 SECTION AT ELEV PIT
SCALE: 3/16" = 1'-0" 8 ELEVATOR SECTION
SCALE: 1/2" = 1'-0" 3 CONN TO EXTG WALL
SCALE: 3/4" = 1'-0" 4 BOND BEAM SECTION
SCALE: 1" = 1'-0" 5 TYP DECK SUPPORT
SCALE: 3/4" = 1'-0" 6 TYP THRESHOLD SECTION L1-L3
3 3 3 3
NO DATE DESCRIPTION1 02/06/14 BID AND PERMIT2 02/19/14 ISSUED FOR PERMIT3 02/25/14 ADDENDUM #34 02/26/14 ADDENDUM #4
3
4
IN E
X TG
WAL
L
4' -
0" N
EW O
PNG
PIT SLAB1
S3.0
EXTG CEILINGFRAMINGFIELD VERIFYELEVATION
C8X11.5
C10X15.3
C8X
11.5
W8X
35
CONN TO EXTGMASONRY WALL10/S5.0
CONN TO EXTGMASONRY WALL 10/S5.0
NEW 4"CONCRETE ONEXTG WALL
2S3.0
A
B
9 10
EXTG SECONDFLOORSTRUCTURE
19' - 7"
11' -
9 1
/2"
6'-8 1/2"
5'-9
"1'
-0 5
/8"
C10X15.3
L4X4
X3/8
4
10S4.2
1S3.0
W8x
35 L
INTE
L A
BO
VE
EX
LIN
TEL
ABO
VE
NEW OPNG INGYM LEVEL
FLOOR
EXTG STAIR
W8X
35
EX I10X25
EX C10X15
EX I15X42
2S3.0
NEW OPNGA
B
9 10
EXTG GYM FLOORSTRUCTURE
19' - 7"
11' -
9 1
/2"
NEW 5"INFILL SLAB
L4X
4X3/
8
L3x3x3/8
EXTG TIE RODS WALL BELOW
BM POCKET ATEXTG WALL 10/S5.0
+C8x11.5
6'-8 1/2"
5'-9
"
BM POCKET ATEXTG WALL10/S5.0 FOR C8
BM POCKET AT EXTGWALL 10/S5.0 FOR C8
10S4.2
1'-0
"
1'-6"
L4X4
X3/8
AT L4x4PROVIDE 1/2" DIA HLCSLEEVE ANCHORS @8" O.C. w/ 1-1/2"EMBEDMENT INTOSOLID MASONRY
1S3.0
EXTG STAIR
EX
LIN
TEL
ABO
VE
NEW FLOOR OPNG
EXTG 13" TILE ARCHES ATGYM FLOOR LEVEL DECK
EX
C9X
13.4
EX I10X25
EX I15X42
EX C10X15
EX I5X9.75
EX I10X25
EXTENT OF DEMO8' - 3 1/4"
EXTE
NT
OF
DEM
O7'
- 5
1/4"
+/-
EXTGFLOOROPNG
2S3.0
A
B
9 10
EXTG GYM FLOORSTRUCTURE
19' - 7"
11' -
9 1
/2"
DEM
O3'
-10"
+/-
DEMO1'-6" DENO EXTG 13" DECK
FOR NEW OPNG.
EXTG MASONRY WALLBELOW
EXTG TIE RODS
+/-1'-5"
+/-1'-9"
1'-5
" +/-
7'-8
" +/-
+/-
1'-5
"
NEWSTEELLINTEL
EXTG 13' CLAY TILEARCH AT GYM LEVEL
CONNECT EXTG I-SECTION TONEW WF. REMOVE FIREPROFFINGTO ENSURE BEARING OF EXTGSTEEL ON NEW STEEL
EXTG CEILING FRAMINGFIELD VERIFY ELEVATIONAND CLEARANCE
NEW CONCRETEON STEEL DECK3A/S5.0
EXTG 11" CLAY TILE DECK
NEW STEELDECK SUPPORT
1' -
2"5" EXTG MASONRY
WALL
EXTG CEILING HANGER
EX I10X25
W8X35C8X11.5
NEW 8" CMU w/ #4@32" VERT
10
GYM FLOOR LEVEL
2ND FLOOR LEVEL
1/2" DIA HLC SLEEVE ANCHORS@8" O.C., STAGGERED, w/ 1-1/2"EMBEDDMENT INTO SOLIDMASONRY (MIN 10 ANCHORS)
DRILL IN DOWELS#4@12"w/ 8" HOOKS.USE HILTI HIT-RE500ADHESIVE1/2" DIA HLC SLEEVE
ANCHORS @16 O.C. w/ 1-1/2"EMBEDDMENT INTO SOLIDGROUTED CMU
L4X4X3/8
CO
OR
D w
/ LU
LA7'
-4" C
LR
CO
OR
D w
/ LU
LA7'
-4" C
LR
NEW BOND BEAMLINTEL w/(2)#5
3"
W8X35
NEW BOND BEAMLINTEL w/(2)#5
CEILING LEVEL3"
CLA
Y TI
LE1'
-0"
6'-8 1/2"
EXTG WALL1'-5" +/-
W10X19
L4X4X3/8L6X6X3/8
CONT BOND BEAM w/(2)#5 ALL-AROUND
1/4 3"@12"TYP
@4@12" @ DOORWAY
8'-10" +/-
FILL VOID w/ GROUT
S3.04
6"
4EXTG CEILING FRAMINGFIELD VERIFY ELEVATIONAND CLEARANCE
NEW CONCRETEON STEEL DECK
EXTG MASONRY WALL
C10X15.3 C8X11.5
C8X11.5
EX I15X42
A
GYM FLOOR LEVEL
2ND FLOOR LEVEL
CL OF EXTG I157'-8" +/-
+/-1'-5"
1/2" DIA HLC SLEEVE ANCHORS @12" O.C. w/ 1-1/2" EMBEDDMENTINTO SOLID MASONRY
C10X15.3
1/4 3"@12"TYP
1/4 3"@12"
5'-9"
CEILING LEVEL
L4X4X3/8EX I10X25 L4X4X3/8
1/4 3"@12"TYP
C8X11.5
7'-5 1/4"
1S3.0
2S3.0
EXTG SUSPENDEDCEILING FRAMING. FIELDVERIFY ELEVATION
EXTG CEILINGHANGER RODS
EXTENT OF DEMO
EXTE
NT
OF
DEM
O
A
B
9 10
EXTGSECONDFLOORSTRUCTURE
19' - 7"
11' -
9 1
/2"
+/-
1'-5
"
+/-
1'-5
"
1'-5" +/-
+/-
1'-5
"
+/-1'-9"
10S4.2
1S3.0
2S3.0
A
B
9 10
5'-2
" +/-
5'-1
1" +
/-
EX I10X25
EX I10X25
EX C10X15
W10
X19
L4X4
X3/8
L4X4X3/8
TYP. 2 SIDES
EXTG MASONRY WALLBELOW EXTG MASONRY WALL
ABOVE
EXTG 12" TILE ARCHES
19' - 7"
11' -
9 1
/2"
PRESERVEINTACT EXTG TIERODS
3S3.0
EX
I10X
25
8'-10" +/-
6'-8 1/2"5'
-9"
C8X11.5
+/-4"
+/-1'-1"
CONN TO WALLPER 10/S5.0
5" DECK3" COMP. STEEL DECK:VULCRAFT VLI 2.0, MIN 20 GA,OR APPROVED EQUIVALENT
4S3.0
CMU BRACEANGLE, TYPL6x4x5/16 LLH(8X)
TYP1'-0"
TYP.1'-4"
L4X4X3/8
5S3.0
6S3.0
7S3.0
BM POCKET ATEXTG WALL10/S5.0 FOR C8
8S3.0
3/163/16
3 SIDES TYP
3/8' THK FITTED STIFFPLATE @I10
5/16L6X6X3/8
W10X19EX I10X25
PROVIDE STEEL SHIMS ATEX I10 TO ENSUREBEARING ON L6x6 ANDTACK WELD IN PLACE
1/4 12"
REMOVE FIREPROFFING TOENSURE BEARING OF EXTGSTEEL ON NEW STEEL
3"
A
B
9 10
5'-2
" +/-
5'-1
1" +
/-
EX I10X25
EX I10X25
EX C10X15
EXTG MASONRY WALLBELOW
EXTG MASONRY WALLABOVE
EXTG 12" TILE ARCHES
19' - 7"
11' -
9 1
/2"
DO NOT CUT TIERODS OUTSIDEOF DEMOREGION, TYP.
EX
I10X
25
DEMO8'-10" +/-
DEM
O11
'-1" +
/-
SAW-CUT AND REMOVE EXTGSLAB - DO NOT REMOVE TIERODS UNTIL NEW FRAMING IS INPLACE
+/-4"
+/-1'-1"
REINFORCMENT:WWF 6x6-W1.4xW1.4
3" COMPOSITE STEEL DECK:VULCRAFT VLI 3.0, MIN 20 GA,OR APPROVED EQUIVALENT
NWT CONCRETE,TYP.
EXTG MASONRY WALL
WELD DECK TO SUPPORTSw/ 5/8" DIA. PUDDLE WELDS@ 12" O.C.
DECK SUPPORTANGLE L4x4
1/2" DIA HLC SLEEVEANCHORS @8" O.C. w/1-1/2" EMBEDMENTINTO SOLID MASONRY,TYP
5"
CONT BOND BEAM w/(2)#5 ALL-AROUND
L6x4x5/16 LLHx12" LONG -SEE PLAN
(3) 3/8" DIA EXPANANCHORS AT 8'" O.C.w/2-1/2" EMBED, TYPHILTI KWIK-BOLT3
3 3/8"
COORD LOCATION w/DECK RIBS
PROVIDE VERTSLOT IN ANGLEVERT LEG
EX C10X15
W10X19
L4x4x3/8 x 8" LONGFOR EXTG C10 CONN
1/4
REMOVE FIREPROFFINGTO ENSURE BEARINGOF EXTG STEEL ONNEW STEEL
COPE BEAM
1/43 SIDES
EX I10X25
C8X11.5
WF
(2)3/8" FITTEDCONN PLs
4"
1/4TYP
1/4 3"@12"1/4 3"@12"
EX I10X25 EX I10X25
5/8" x 4" CONN.PLATE
6"
3/16
3/16
(2)L4x4x1/4
3/16
3/16
CHICAGOPUBLICSCHOOLS
CPS
2013 KOO AND ASSOCIATES LTDC
DRAWING NO.
FILE:
JOB:
SCALE:
DRAWN BY:
REVISIONS
WARNING: ASBESTOS-CONTAINING BUILDING MATERIALS ARE ORMAY BE PRESENT IN THIS BUILDING. AN ASBESTOS MANAGEMENTPLAN IS AVAILABLE IN THE SCHOOL FOR REVIEW UPON REQUEST. NOPERSON MAY DISTURB ASBESTOS-CONTAINING MATERIALS UNLESSTHAT PERSON IS A LICENSED ASBESTOS WORKER OR CONDUCTSSUCH WORK IN ACCORDANCE WITH SPECIFICATIONS(S) CONTAINEDIN THE PROJECT DOCUMENTS AND IN COMPLIANCE WITH ILLINOISDEPARTMENT OF HEALTH RULES AND REGULATIONS.
CAPITAL IMPROVEMENT PROGRAMDEPARTMENT OF FACILITIES
Goodfriend Magruder Structure LLC53 W Jackson Blvd, Suite 352Chicago IL 60604312 265 2645www.gmstructure.com
Structural Design and Engineering
KOO AND ASSOCIATES LTD53 W JACKSON BLVD STE 215CHICAGO IL 60604312- 235-0920 PH
KJWW231 S. LaSalle St., Suite 600Chicago IL 60604312 294 0501www.kjww.com
PROJECT NO. 2014-24121-CSP
LAFAYETTE SCHOOL
2714 W. AUGUSTA BLVD.CHICAGO, ILLINOIS 60622
NORTH
Terra Engineering Ltd.225 W Ohio St.Chicago, IL 60654312 467-0123www.terraengineering.com
2/26
/201
4 1:
58:5
1 P
M
S3.0
LULA PLANS.SECTIONS &
DETAILS
Author
SCALE: 1/4" = 1'-0" A2 SECOND FLOOR LEVEL AT LULASCALE: 1/4" = 1'-0" B2 GYM FLOOR LEVEL AT LULA
SCALE: 1/4" = 1'-0" B1 DEMO PLAN - GYM FLOOR AT LULA
SCALE: 3/8" = 1'-0" 1 SECTION AT LULA - EWSCALE: 3/8" = 1'-0" 2 SECTION AT LULA - NS
SCALE: 1/4" = 1'-0" A1 DEMO PLAN -SECOND FLOOR AT LULA
SCALE: 1/4" = 1'-0" C2 LULA CAP - THIRD FLOOR LEVEL
SCALE: 1" = 1'-0" 3 CONN DETAIL @ EXTG BM
SCALE: 1/4" = 1'-0" C1 DEMO PLAN - LULA CAP
NO DATE DESCRIPTION1 02/06/14 BID AND PERMIT2 02/19/14 ISSUED FOR PERMIT3 02/25/14 ADDENDUM #34 02/26/14 ADDENDUM #4
SCALE: 1" = 1'-0" 4 INFILL SECTION
SCALE: 1" = 1'-0" 5 CMU BRACE
SCALE: 1" = 1'-0" 6 EX CHANNEL CONN
3
SCALE: 1" = 1'-0" 7 CONN DETAIL
SCALE: 1" = 1'-0" 8 CONN DETAIL
C8
4
4
4
4
1S4.1
NEWSUPPLYOPNG
NEWRETURNOPNG
EXTG 12" THICK CLAYTILE ROOF DECK
EXTG TIE RODS
NEW 5" INFILL SLABPER 5/S3.0FLUSH TOP w EXTGROOF DECK
C10
X15
.3
C10
X15
.3
L4X4X3/8
L4X4
X3/8
EX I10X25
EX I10X25
EX
C6
X8
SEE MEP & ARCH DWGSNEW RTU#1
SEE
MEP
& A
RC
H D
WG
S
NEW
RTU
#1
EX I10X25
9 10
RTU#14140LBS
V.I.F.19' - 7" +/-
EXTG SKYLIGHT OPENING15' - 0" +/-
EXTG MASONRYWALL
EX7I 15
EX7I 15
EX7I 15
C10X15.3
EX
I12
X31
.5E
X I1
2 X
31.5
9'-0
" +/-
11S4.2
C10
X15
.3
C10
X15
.3
C10
X15
.3
L4X4X3/8
ALIGN RTU w/WALL BELOW
3 4
5' -
3" +
/- V.
I.F.
5' -
3" +
/- V.
I.F.
5' -
3" +
/- V.
I.F.
EX I8 18
EX I8 18
EX I8 18
2S4.1
EXTG TIE RODS
RTU#2 2494 LBS
EXTG 10" CLAY TILE
C10
X15
.3
C10
X15
.3
5S4.1
NEW 5" INFILLSLAB PER 3/S5.0
C10
X15
.3
C10
X15
.3
L4X4X3/8
C10
X15
.3
C10
X15
.3
L4X4X3/8C10
X15
.3
C10
X15
.3
w/ MEP3'-2" CORRD
L4X4X3/8
L4X4X3/8
L4X4X3/8
7S4.1
8S4.1
RTU-2
RTU
-2
L
M
9
RTU#41017 LBS
EXTG MASONRY WALLBELOW (AT ATTIC LEVEL)
W10
X22
NEW DUCTOPNGS
3S4.1
5S4.2
EXTG ROOF FRAMING: 2X10@16" O.C.NOTE EXTG ROOF JOIST LOCATIONSARE APPROXIMATE. VERIFY IN FIELD
W10
X22
W10X22
W10X22
5" INFILL SLAB
C10
X15
.3
REQUIREMENTS8'-4" +/- COORD w/ RTU
10S5.0
CO
OR
D w
/ RTU
REQ
UIR
E MEN
TS
13' -
4" +
/-
C10X15.3
C10X15.3 HSS4X4X
5/16
HSS4X4X
5/16
CONN C10 TO W10PER 7/S4.2 EA END
C8X11.5
C8X
11.5
CO
OR
D w
/ MEP
5'-0
" +/-
RTU
K1K1K1
K1
KICKER PER6/S4.1 (4X)
L
M
6
RTU#33085LBS
4S4.1
HSS4X4X
5/16
EXTG MASONRY WALLBELOW
EXTG WOODROOF TRUSS
EXTG WOOD DECK ON EXTG ROOFFRAMING : 2X10@16" O.C. +/-NOTE EXTG ROOF JOIST LOCATIONSARE APPROXIMATE. VERIFY IN FIELD
NEW DUCT OPNGS
EX ROOF 1893
EXTG MASONRY WALLBELOW
EXTG WOODROOF TRUSS
HSS4X4X
5/16HSS4X4X5/16
HSS4X4X5/16
W12
X26
W12
X26
C10X15.3
C10X15.3
C10X15.3
C10X15.3
W10X22
5" INFILL SLAB
6S4.1 W10X22
9S4.1
(2) 2
x12
(2) 2
x12
RTU-3
RTU
-3
K1 K1
K1 K1
K1 K1
K1K1
EXTG ROOF DECK
RTU#1SEE ARCH &MEP DWGS
RTU CURBSEE M/E/P DWGS
11S4.2
C10 EXI10EXI10
1/4
(2)L4x4x5/16, TYP
L4X4X3/8
RTU#22494 LBS
L4X4X3/8
EXTG ROOF
RTU CURBSEE M/E/P DWGS
L4X4X3/8L4X4X3/8 L4X4X3/8
3/16TYP
EXTG 2X WOODROOF JOISTS
RTU#41017 LBS
BOLT NEW 2X12 TOSTEEL BM w/5/8" DIAA325 BOLTS @ 24" OC
W10X22
C10X15.3 W10X22W10X22
5" INFILL SLAB EXTG ROOF
2X WOODBLOCKING
2x12
RTU CURBSEE M/E/P DWGS
2x12
NAIL DECK TOJOIST w/10d NAILS@4" O.C, MIN 1-5/8"PENETRATION, TYP
6
RTU#33085#
EXTG ROOF
EXTG 2X WOODROOF JOISTS
BOLT NEW 2X12 TOSTEEL BM w/5/8" DIAA325 BOLTS @ 24" OC
2X WOODBLOCKING
RTU CURBSEE M/E/P DWGS
W12X26W12X26 (2) 2x12(2) 2x12
2S4.1
RTU#22494 LBS
C10X15.3C10X15.3 C10X15.3 C10X15.3
REQUIREMENTSCOORD w/RTU
S4.18
TYP
3 4
2S4.1
5S4.1
5' -
3" +
/- V.
I.F.
5' -
3" +
/- V.
I.F.
5' -
3" +
/- V.
I.F.
EX I8 18
EX I8 18
EX I8 18
EXTG TIE RODS
EXTG 10" CLAY TILE
16' - 10 1/2"
TIE ROD CONNPER 9/S5.0
TIE ROD CONNPER 9/S5.0
SAW-CUT ANDREMOVE EXTG SLAB -DO NOT REMOVE TIERODS UNTIL NEWFRAMING IS IN PLACE
MAINTAIN INTACTEXTG I-BEAMS
MAINTAIN INTACTEXTG I-BEAMS
w/ MEP3'-2" COORD
DO NOT CUT TIERODS OUTSIDEOF DEMOREGION, TYP.
9 10
EXTG 12" THICK CLAYTILE ROOF DECK
EXTG TIE RODS
EX I10X25
EX I10X25
EX
C6
X8
EX I10X25
V.I.F.19' - 7" +/-
EXTG SKYLIGHT OPENING15' - 0" +/-
EX7I 15
EX7I 15
EX7I 154' -
1" +
/-9'
- 0"
+/-
6' -
0 1/
2" +
/-
EX
I12
X31
.5E
X I1
2 X
31.5
EXTG MASONRYWALL
EXTG SKYLIGHTINFILL TO BEREMOVED
8'-0
" +/-
EX I10X25
11S4.2
9'-0
" +/-
DEM
O
17'-5" +/- DEMO
6
KICKER "K1"L4x4x5/16 BRACE, TYP ATEA POST, 2 SIDES @ EAPOST
3/8" CONN PL 6"x6", TYP
CONN . PER 5/S4.2
EXTG WALL BELOW
RTU#3
3/16
3/16TYP
3/16TYP
CONN W10 TOW12 PER 7/S4.2
W10X22
W12X26
HSS4X4X
5/16
CONN W12 POSTPER 8/S4.2
C10X15.3C10X15.3
EX I8 18
5/8" CONN. PLATE10" WIDE, TYP
(2)L4x4x5/16
1'-0
"
(2)L4x4x5/16
3/16
3/16TYP
3/16
3/16TYP3/16
3/163 SIDES, TYP
EX I8 18
1/4
CONN. ANGLE(2) L4x4x5/16 x 12"LONG
SHIM C10 TIGHTTO UNDERSIDEOF EXTG DECK
EXTG ROOFDECK
L4X4X3/8
C10X15.3
2"
NEW INFILLSLAB
3/8"x4"x4" CONN PLATE w/ 5/8"DIA EXPANSION ANCHOR, TYP@ C10 MIDSPAN
C10X15.3
GROUT SOLIDAT ANCHOR, TYP
4 1/
8"
8A 8B
LM
RTU#33085#
RTU CURBSEE M/E/PDWGS
W10X22 C10X15.3 C10X15.3 C10X15.3C10X15.3
W10X22EXTG TIMBERROOF TRUSS
EXTG ROOF DECK
CANT DECKPROVIDE DECKCLOSURE
CHICAGOPUBLICSCHOOLS
CPS
2013 KOO AND ASSOCIATES LTDC
DRAWING NO.
FILE:
JOB:
SCALE:
DRAWN BY:
REVISIONS
WARNING: ASBESTOS-CONTAINING BUILDING MATERIALS ARE ORMAY BE PRESENT IN THIS BUILDING. AN ASBESTOS MANAGEMENTPLAN IS AVAILABLE IN THE SCHOOL FOR REVIEW UPON REQUEST. NOPERSON MAY DISTURB ASBESTOS-CONTAINING MATERIALS UNLESSTHAT PERSON IS A LICENSED ASBESTOS WORKER OR CONDUCTSSUCH WORK IN ACCORDANCE WITH SPECIFICATIONS(S) CONTAINEDIN THE PROJECT DOCUMENTS AND IN COMPLIANCE WITH ILLINOISDEPARTMENT OF HEALTH RULES AND REGULATIONS.
CAPITAL IMPROVEMENT PROGRAMDEPARTMENT OF FACILITIES
Goodfriend Magruder Structure LLC53 W Jackson Blvd, Suite 352Chicago IL 60604312 265 2645www.gmstructure.com
Structural Design and Engineering
KOO AND ASSOCIATES LTD53 W JACKSON BLVD STE 215CHICAGO IL 60604312- 235-0920 PH
KJWW231 S. LaSalle St., Suite 600Chicago IL 60604312 294 0501www.kjww.com
PROJECT NO. 2014-24121-CSP
LAFAYETTE SCHOOL
2714 W. AUGUSTA BLVD.CHICAGO, ILLINOIS 60622
NORTH
Terra Engineering Ltd.225 W Ohio St.Chicago, IL 60654312 467-0123www.terraengineering.com
2/26
/201
4 1:
58:5
5 P
M
S4.1
ROOF PART PLANS &SECTIONS
Author
SCALE: 1/4" = 1'-0" A-2 ROOF PART PLAN AT RTU#1
SCALE: 1/4" = 1'-0" B-2 ROOF PART PLAN AT RTU#2
SCALE: 1/4" = 1'-0" D ROOF PART PLAN AT RTU#4
SCALE: 1/4" = 1'-0" C ROOF PART PLAN AT RTU#3
SCALE: 3/8" = 1'-0" 1 SECTION AT RTU#1 - NS
SCALE: 3/8" = 1'-0" 2 SECTION AT RTU#2 - NS
SCALE: 3/8" = 1'-0" 3 SECTION AT RTU#4 - EW
SCALE: 3/8" = 1'-0" 4 SECTION AT RTU#3 - EW
SCALE: 3/8" = 1'-0" 5 SECTION AT RTU#2 - EWSCALE: 1/4" = 1'-0" B-1 ROOF DEMO PLAN AT RTU#2
SCALE: 1/4" = 1'-0" A-1 ROOF DEMO PART PLAN AT RTU#1
SCALE: 1/2" = 1'-0" 6 SECTION AT RTU#3
SCALE: 1" = 1'-0" 7 CONNX DETAIL @ NEW/EXTGSCALE: 1" = 1'-0" 8 CONNX DETAIL @ INFILL
SCALE: 3/8" = 1'-0" 9 SECTION AR RTU#3 -NS
33
3
3
33
3
NO DATE DESCRIPTION1 02/06/14 BID AND PERMIT2 02/19/14 ISSUED FOR PERMIT3 02/25/14 ADDENDUM #34 02/26/14 ADDENDUM #4
4
4
4
4
4
G
9 10
NEW 5"INFILL SLABPER 3/S5.0
PRESERVEINTACTEXTG TIERODS
EX
C6
X8
EX
C6
X8
EX I12 X31.5
EX I12 X31.5
EX 10" CLAY TILE
L5X
3X5/
16
L5X
3X5/
16
3S4.2
5'-7
1/2
" +/-
5'-7
1/2
" +/-
V.I.F.8'-4 1/2" +/-
4S4.2
B
11
1S4.2
2S4.2
3' - 0"
CLE
AR4'
- 0"
ENLARGED ROOF OPNG
L5X
3X5/
16
REMOVE EXTG DECKTO CL OF EXTG BEAMPROVIDE NEW 5" INFILLDECK PER 3/S5.0
EX
I9X
21
EX
I9X
21
C10X15.3
EX 12" CLAY TILE
L4X4X3/8
L4X4
X3/8
B
11
EX C6 X8
EX
C6
X8
EX
I9X
21
EX
I9X
21
V.I.F.3' - 0" +/-
V.I.
F.3'
- 0"
+/-EXTG
HATCHOPNG
EXTG TIE RODSTO REMAIN
EXTG 12"CLAY TILE
V.I.F.5' - 3" +/-
V.I.F.5' - 3" +/-
V.I.F.5' - 3" +/-
DEMO EXTGHATCH FRAMING
EX
I9X
21
EXTGMASONRYWALL
PARTIAL DEMOOF EXTG ROOFDECK
DEM
O
4'-0
"
DEMO
2S4.2
T/EXTG ROOFV.I.F.
L5X3X5/16
5" INFILL SLAB
1/41/4
TYP
L4X4X3/8
EX I9X21EX I9X21
1/41/4
5/8" CONN PLATE 4" WIDE1/41/4
C10X15.3
1/4
1S4.2
5" INFILL SLAB T/EXTG ROOFV.I.F.
POCKET INTO WALL
L5X3X5/16
1/4TYP
C10X15.3
L4X4X3/8GROUT SOLID
8"
CEILING 1921 EASTEL: 54'-11"
3/4" x6" x 12" BASEPLATE ON 3/4" NON-SHRNK GROUT
(2) 5/8" DIA EXP.ANCHORS @ 9" O.CHILTI KWIKBOLT-3 w/ 6"EMBEDMENT
6"
3/4"
3/16TYP
EXTG MASONRY WALL
1' - 5" +/-
CL.
1/43 SIDES, TYP
STD. ABOUBLE ANLGE AISCSHEAR CONNECTION.
WF BEAM OR CHANNEL,SEE PLAN
WF OR CHANNEL BEAMSEE PLAN
3"3"
3"
CL.
T/COL: 3/8" CAPPLATE, TYP.
1/41/4
TYP
TYP
STEEL BEAM
3/8" THRU PLATE
HSS COLUMNSEE PLANS
3"3"
3"
2"
AT MASONRY WALLS1/2" DIA HLC SLEEVE ANCHORS@8" O.C., STAGGERED, w/ 1-1/2"EMBEDDMENT INTO SOLIDMASONRY (MIN 4 ANCHORS)TYP U.O.N.
L5X3X5/16 L5X3X5/16
5" INFILL SLAB
EXTG SKYLIGHT CURB TOBE REMOVED - SEE ARCH
EXTG 10" CLAY TILEROOF DECK1/4
TYP
1/4TYP
EX I12 X31.5
L4X4X3/8
3/16TYP
CONN PL3/8"x6"x4"EACH END
6" EX C10X15
EX I10X25
L4x4
ANGLE BEYOND3/16
3/16TYP
3/16TYP
1/2"
1S4.1
9
RTU#1SEE ARCH &MEP DWGS
RTU CURBSEE M/E/PDWGS
EX I12 X31.5 C10X15.3 C10X15.3 C10X15.3 C10X15.3 C10X15.3
EX C6 X8
EXTG CURB ANDBEAM TO BEREMOVED
EXTG CURB TOBE REMOVED
T/EXTG ROOFV.I.F.
1/4
L4X4X3/8
CHICAGOPUBLICSCHOOLS
CPS
2013 KOO AND ASSOCIATES LTDC
DRAWING NO.
FILE:
JOB:
SCALE:
DRAWN BY:
REVISIONS
WARNING: ASBESTOS-CONTAINING BUILDING MATERIALS ARE ORMAY BE PRESENT IN THIS BUILDING. AN ASBESTOS MANAGEMENTPLAN IS AVAILABLE IN THE SCHOOL FOR REVIEW UPON REQUEST. NOPERSON MAY DISTURB ASBESTOS-CONTAINING MATERIALS UNLESSTHAT PERSON IS A LICENSED ASBESTOS WORKER OR CONDUCTSSUCH WORK IN ACCORDANCE WITH SPECIFICATIONS(S) CONTAINEDIN THE PROJECT DOCUMENTS AND IN COMPLIANCE WITH ILLINOISDEPARTMENT OF HEALTH RULES AND REGULATIONS.
CAPITAL IMPROVEMENT PROGRAMDEPARTMENT OF FACILITIES
Goodfriend Magruder Structure LLC53 W Jackson Blvd, Suite 352Chicago IL 60604312 265 2645www.gmstructure.com
Structural Design and Engineering
KOO AND ASSOCIATES LTD53 W JACKSON BLVD STE 215CHICAGO IL 60604312- 235-0920 PH
KJWW231 S. LaSalle St., Suite 600Chicago IL 60604312 294 0501www.kjww.com
PROJECT NO. 2014-24121-CSP
LAFAYETTE SCHOOL
2714 W. AUGUSTA BLVD.CHICAGO, ILLINOIS 60622
NORTH
Terra Engineering Ltd.225 W Ohio St.Chicago, IL 60654312 467-0123www.terraengineering.com
2/26
/201
4 1:
58:5
8 P
M
S4.2
ROOF PLANS,SECTIONS & DETAILS
Author
SCALE: 1/4" = 1'-0" A ROOF LEVEL- SKYLIGHT INFILLSCALE: 1/4" = 1'-0" B ROOF PART PLAN AT HATCH - NEW
SCALE: 1/4" = 1'-0" C ROOF DEMO PLAN AT HATCH
SCALE: 1/2" = 1'-0" 1 SECTION
SCALE: 1/2" = 1'-0" 2 SECTION
SCALE: 1" = 1'-0" 5 SECT @ RTUSCALE: 3/4" = 1'-0" 7 STEEL BEAM TO BEAM
SCALE: 3/4" = 1'-0" 8 CONNECTION DETAILSCALE: 1" = 1'-0" 9 SECTION
SCALE: 1/2" = 1'-0" 3 INFILL SECTION
SCALE: 3/4" = 1'-0" 4 CONNECTION DETAIL
3
3
3
3
3
3
3
3
NO DATE DESCRIPTION1 02/06/14 BID AND PERMIT2 02/19/14 ISSUED FOR PERMIT3 02/25/14 ADDENDUM #34 02/26/14 ADDENDUM #4
4
SCALE: 1" = 1'-0" 10 CONNX DETAIL
4
4
4
SCALE: 3/8" = 1'-0" 11 SECTION AT RTU#1 - EW
4
4
5" INFILL SLAB
C8X
11.5
W8X
15
W8X
15
C8X
11.5
EX C6 X8
EX 6I X12.5
EX
6I X
12.5EX 6I X12.5
EX
6I X
12.5
EX
C6
X8
EX C6 X8
EX I12 X31.5
EX I12 X31.5
EX
C6
X8
2' - 0"2' - 0"
NEW INFILL SLAB14' - 9 3/4" +/-
NEW
INFI
LL S
LAB
7' -
6 3/
4" +
/-
9 10
6S6.0
5S6.0
3A/S5.0
F
8 NEW SLAB OPENINGSEE ARCH & MEP DWGS
EXTG 8" CLAY TILE
EXTG MASONRY WALL
EX C6 X8
W8X18
L4X4
X3/8
EX 6I X12.5
EX
20I6
5
L4X4
X3/8
5" INFILL SLABPER 3/S5.0
7S6.0
L5X5X3/8
5'-3
" +/-
POCKETCONN PER10/S5.0
9S6.0
CONN L5 TO EXI20PER 9/S6.0 SIM
7
EXTG MASONRYPIERS TO BEREMEDIATED, TYP
+/-
PIER1' - 0"
+/-
PIE
R1'
- 0"
EXTG 6" HIGHSUPPORT BM, TYP
FOUNDATIONS SHOWNARE APPROXIMATEV.I.F.
1S6.0
EXTG COILS:SEE ARCH & MEP DWGSFOR INFORMATION
J
EXTG 6" STEEL BEAM TO REMAINSHORE AS REQUIRED.SHORING TO REMAIN UNTIL NEW PIERSHAVE ATTAINED 28-DAY COMPRESSIVESTRENGTH, f'c = 4000 PSI
NEW12"x12" C.I.P. CONCRETEPIER TO REPLACE EXTGMASONRY PIER
(3) #4 TIES
3"3"
2"
3/4"x10"X10" BEARINGPLATE ON HIGH-STRENGTH,NON-SHRINK GROUT
3/4"3/
4"1 1/2"
(4) 5/8" DIA EXPANSIONANCHORS
(4) #6 VERT
DRILL & EPOXY GROUTINTO EXTG FTG.
8"
VA
RIE
S -
V.I.F
.
T/SLABEL V.I.F.
T/FTGEL V.I.F.
3/163/16
TYP
7EXTG MASONRYPIERS TO BEREMEDIATED, TYP
+/-
PIER1' - 0"
EXTG 6" HIGHSUPPORT BM, TYP
FOUNDATIONS SHOWNARE APPROXIMATEV.I.F.
1S6.0
EXTG COILS:SEE ARCH & MEP DWGSFOR INFORMATION
G
9 EXTG MASONRYPIERS TO BEREMEDIATED, TYP
+/-
PIE
R1'
- 0"
EXTG 6" HIGHSUPPORT BM, TYP
FOUNDATIONS SHOWNARE APPROXIMATEV.I.F.
EXTG COILS:SEE ARCH & MEP DWGSFOR INFORMATION
1S6.0
NEW 5" INFILLSLAB PER 3A/S5.0IN EXTG ROOFOPNG
NEW 5" INFILL SLABPER 3A/S5.0 IN EXTGROOF OPNG
NEW 5" INFILLSLAB 3A/S5.0 INEXTG ROOF OPNG
L3X3
X3/8
L4X3
X3/8
L3X3
X3/8
L3X3
X3/8
L3X3
X3/8
L4X3
X3/8
G
H
5 6 7
6' -
9"
EX I8 18
EX I8 18
EX I8 18
EX
C4X
5.4
EX
C4X
5.4
EX
C4X
5.4
EX
C4X
5.4
EXTG 11" CLAY TILE
EX
7I 1
5
EX
7I 1
5
EX C5X6.5 EX C5X6.5
EX C5X6.5EX C5X6.5
EXTG 11" CLAY TILE
EXTG 9" CLAY TILE
EXTG 11" CLAY TILE
J
6'-0' +/- 5'-6" +/-
VIF
6'-0
' +/-
6'-0" +/-
5'-7
3/4
" VIF
5'-7
3/4
" VIF
+/-
3'-8
"
8S6.0
8S6.0
SIM.
EX I8 18
EX I8 188
S6.0SIM.
L3X3X3/8
L3X3
X3/8
L4X3
X3/8
L3X3X3/8
L3X3X3/8
EX
7I 1
5
L3X3X3/8
EX 12" CLAY TILE
L3X3X3/8
EX 12" CLAY TILE
L3X3X3/8
DEMO EXTGSUSPENDEDPARTITION
LINE OF DEMO
EXTG MASONRYWALL TO REMAIN
EXTG MASONRYWALL TO REMAIN
LINE OF DEMO
VIF VIF
PRESERVEINTACT EXTGFLOORFRAMING ANDENCASEMENT
SEE ARCH FOR WARDROBE LOCATIONS TO BE REMOVEDEXTG FRAMING PER 1921 CHRISTENSEN DRAWINGS, NOTE EX.01, DRAWING S0.0
H
9EXTG MASONRYPIERS TO BEREMEDIATED, TYP
EXTG 6" HIGH STEELSUPPORT BM, TYP
FOUNDATIONS SHOWNARE APPROXIMATEV.I.F.
EXTG COILS:SEE ARCH & MEP DWGSFOR INFORMATION
+/-1'-0"
1S6.0
F
9 10
FIELD VERIFYCONFIGURATION OF EXTGFOUNDATION WALLS
STEEL GRATE2"x3/16" TYPE 19-DT-4BY OHIO GRATINGS ORAPPROVED EQUIVALENT.
8'-10 3/8" +/-
3'-4 5/8" +/-
PROVIDE MECH. GRATEFASTENERS TO SUPPORTS PERMANUFAC. RECOMMENDATIONS
L4X4X3/8
L4X4X3/8
FASTEN SUPPORT ANGLE TO EXTGWALL w/1/2" DIA HLC SLEEVEANCHORS @ 12" O.C. w/ 1-1/2"EMBEDMENT INTO SOLID MASONRY
M
9
NEW RAMP SLAB
SAW-CUT ANDREMOVE EXTG S.O.G.
SEE ARCH3'-10 3/8"
SIM.7S4.0
F
8
DEMO EXTG SLAB
EXTG 8" CLAY TILE
EXTG MASONRY WALL
EX C6 X8
DEM
O5'
-1 1
/2" +
/-
DEMO6'-8 3/8" +/-
EX 6I X12.5
CONN EXTG TIEDROD PER 9/S5.0DO NOT CUT TIE
RODS OUTSIDEOF DEMOREGION, TYP.
9S6.0
L
5
NEW PAD FORBOOSTER PUMPSEE ARCH & MEP DWGS
4'-6"
3'-1
0"
3S6.0
DRILL & EPOXY IN #4@12"ALL-AROUND. USE HILTI HIYHY500 ADHESIVE
T/PADEL=-SEE PLAN
T/SLABEL=SEE PLAN
#5@12" EACHWAY BOTTOM
1' -
0"
1' -
0"
W.W.F. 6x6W1.4-W1.4
1' - 0"8" 3" C
LR
SAW-CUT EXTGSLAB-ON-GRADE
1/4(2)L4x4X3/8
COPE BEAM
6"
1/4TYP
W8X15C8X11.5
NEW INFILL SLAB PER 3/S5.0ALIGN w/ T/EXTG ROOF DECK
L5X5X3/8 W8X18 EX C6 X8
CLEAR DIMSEE ARCH FOR
EX 6I X12.5
L4x4
3/8" CONN PLTYP
3/16TYP
ALIGN NEW INFILL SLAB w/EXTG. SEE ARCH FORFINISH REQUIREMENTS
EX I8 18
3/16
3/16
L3x3
REMOVE EXTGSKYLIGHT CURB
EX20I65
WF
(2) L4x4x5/16x6" LONG
1/4TYP
ALIGN NEW INFILL SLAB w/EXTG. SEE ARCH FORFINISH REQUIREMENTS
CHICAGOPUBLICSCHOOLS
CPS
2013 KOO AND ASSOCIATES LTDC
DRAWING NO.
FILE:
JOB:
SCALE:
DRAWN BY:
REVISIONS
WARNING: ASBESTOS-CONTAINING BUILDING MATERIALS ARE ORMAY BE PRESENT IN THIS BUILDING. AN ASBESTOS MANAGEMENTPLAN IS AVAILABLE IN THE SCHOOL FOR REVIEW UPON REQUEST. NOPERSON MAY DISTURB ASBESTOS-CONTAINING MATERIALS UNLESSTHAT PERSON IS A LICENSED ASBESTOS WORKER OR CONDUCTSSUCH WORK IN ACCORDANCE WITH SPECIFICATIONS(S) CONTAINEDIN THE PROJECT DOCUMENTS AND IN COMPLIANCE WITH ILLINOISDEPARTMENT OF HEALTH RULES AND REGULATIONS.
CAPITAL IMPROVEMENT PROGRAMDEPARTMENT OF FACILITIES
Goodfriend Magruder Structure LLC53 W Jackson Blvd, Suite 352Chicago IL 60604312 265 2645www.gmstructure.com
Structural Design and Engineering
KOO AND ASSOCIATES LTD53 W JACKSON BLVD STE 215CHICAGO IL 60604312- 235-0920 PH
KJWW231 S. LaSalle St., Suite 600Chicago IL 60604312 294 0501www.kjww.com
PROJECT NO. 2014-24121-CSP
LAFAYETTE SCHOOL
2714 W. AUGUSTA BLVD.CHICAGO, ILLINOIS 60622
NORTH
Terra Engineering Ltd.225 W Ohio St.Chicago, IL 60654312 467-0123www.terraengineering.com
2/26
/201
4 1:
59:0
2 P
M
S6.0
PLANS, SECTIONS &DETAILS
Author
SCALE: 1/4" = 1'-0" A THIRD FLOOR LEVEL - SKYLIGHT INFILL
SCALE: 1/4" = 1'-0" D2 FIRST FLOOR LEVEL - RETURN AIR
SCALE: 1/4" = 1'-0" B GROUND FLOOR PLAN AT COILSSCALE: 1" = 1'-0" 1 SECTION AT PREHEAT COIL
SCALE: 1/4" = 1'-0" C GROUND FLOOR PLAN AT COILS2
SCALE: 1/4" = 1'-0" E GROUND FLOOR PLAN AT COILS3
SCALE: 1/8" = 1'-0" F BOILER ROOM ROOF
SCALE: 3" = 1'-0" 2 DEMO - EXTG WARDROBE
SCALE: 1/4" = 1'-0" G GROUND FLOOR PLAN AT COILS4
SCALE: 1/4" = 1'-0" H GROUND FLOOR PLANSCALE: 1/4" = 1'-0" 4 GRND FLR PART PLAN - RAMP
SCALE: 1/4" = 1'-0" D1 FIRST FLOOR DEMO PLAN - RETURN AIR
SCALE: 1/4" = 1'-0" J GROUND FLOOR AT BOOSTER PUMPSCALE: 1" = 1'-0" 3 FNDN SECTION
SCALE: 1" = 1'-0" 5 CONNX @ SKYLIGHT
SCALE: 1/2" = 1'-0" 6 CONNX @ SKYLIGHT
SCALE: 1/2" = 1'-0" 7 SECTION@RETURNAIR
SCALE: 1" = 1'-0" 8 SECTION@BOILER ROOF
3
3
3
3
3
3
3
NO DATE DESCRIPTION1 02/06/14 BID AND PERMIT2 02/19/14 ISSUED FOR PERMIT3 02/25/14 ADDENDUM #34 02/26/14 ADDENDUM #4
SCALE: 1" = 1'-0" 9 CONNX DETAIL
4
4
44
4
4