C-DAX is funded by the European Union's Seventh Framework Programme (FP7-ICT-2011-8) under grant agreement n° 318708
C-DAX:
A Cyber-Secure Data and Control
Cloud for Power Grids
Matthias Strobbe – iMinds
Paolo Romano - EPFL
Context & Cause
Transition to Active Distribution Networks• Multiple actors
• Intermittent production patterns
• New loads: e.g. EVs
• Dynamic load patterns: e.g. caused by demand response services
Need for:• Better protection, monitoring & control in distribution grids
• Support of large numbers smart grid applications with diverse requirements
• Efficient & secure communication platforms to transfer the generated data
C-DAX delivers:• Communication middleware based on Information Centric Networking
• Real-Time State Estimation of distribution grids using PMUs
C-DAX communication platform
3
Topic-based Communication
C-DAX: A Cyber-Secure Data and Control Cloud for Power Grids 4
Publisher A
Pub/sub middleware
Publisher B
Publisher C
Subscriber 1
Subscriber 2
Subscriber 3
Topic 1
Topic 2
Benefits of decoupling publishers and subscribers• Communication partners do not need to know each other• Asynchronous communication possible• Facilitating extensibility, management and configurability
Use case: real-time state estimation in
distribution networks using PMUs
Need for better observability of the grid to assure stability, power quality, voltage regulation, etc.
Can be accomplished by installing Phasor Measurement Units (PMUs) for regional/local area measurement, protection and
control
C-DAX platform needs to support the stringent latencyrequirements
C-DAX: A Cyber-Secure Data and Control Cloud , SUNSEED Workshop 8 March 2016 5
Real-time state-estimation (RTSE) of ADNs
Monitoring
Control
Protection
State estimation
Network in normal operation:• Congestion management• Optimal V/P control• Optimal dispatch of DER
Network in emergency conditions:• Islanding detection• Fault identification• Fault location
C-DAX: A Cyber-Secure Data and Control Cloud , SUNSEED Workshop 8 March 2016 6
Field Trial Purpose
• Deploy and validate C-DAX in a MV distribution grid under realistic conditions
• Identify power system applications that can run on top of LTE network
• Demonstrate that C-DAX + RTSE can help DNOs to better manage their grid
C-DAX: A Cyber-Secure Data and Control Cloud , SUNSEED Workshop 25 March 2015 7
Selected applications
• Real-time state estimation
• PQ measurements
Field-trial characteristics:
• Owner: Alliander
• Size: 18 buses (area of 12 km2)
• Nominal voltage: 10 kV (phase-to-phase)
• Installed monitoring devices: 10 PMUs (EPFL) and 1 PQ meter (NI)
• Adopted telecom: commercial LTE network (Vodafone)
Field trial setup: BML 2.10 feeder (Arnhem, NL)
C-DAX: A Cyber-Secure Data and Control Cloud for Power Grids 8
Field trial setup: Electrical substations
C-DAX: A Cyber-Secure Data and Control Cloud for Power Grids 9
OS Bemmel: Primary substation
Tuindorp:Secondary Substation(urban area)
Field trial setup: PMU locations
C-DAX: A Cyber-Secure Data and Control Cloud for Power Grids 10
Phasor Measurement Units - Basics
C-DAX: A Cyber-Secure Data and Control Cloud for Power Grids 11
Time
sync
Time
syncSignal condit ioning,
sampling and bu↵ering
Signal condit ioning,
sampling and bu↵ering
Synchrophasor Est imat ion
Algorithm
Synchrophasor Est imat ion
Algorithm
UTC
time-stamp
UTC
time-stamp
Time-baseTime-base
Data encapsulat ion and st reamingData encapsulat ion and st reaming
Est imated valuesEst imated values
Time
source
Time
sourceInput waveformsInput waveforms
Measurement dataMeasurement data
Sampled waveformsSampled waveforms
Phasor Measurement Units – The EPFL PMU
C-DAX: A Cyber-Secure Data and Control Cloud for Power Grids 12
- First PMU worldwide specifically designed for ADN operating conditions
- Rugged and compact NI-compactRIO enclosure to fit in reduced spaces
- First worldwide FPGA-based PMU (high speed and determinism)
- Equipped with a ±100 ns (max error) stationary GPS module
- Metrologically characterized at Swiss Federal Institute of Metrology (METAS)
- Steady state accuracy: 10 ppm (independently of harmonic distortion)
- Measurement reporting latency: 37 ms
- Reporting rates: 10-20-50-100-200 fps
- IEEE Std. C37.118 class-P compliant
Field trial setup: LTE network
C-DAX: A Cyber-Secure Data and Control Cloud for Power Grids 13
Substation setup
C-DAX: A Cyber-Secure Data and Control Cloud for Power Grids 14
Industrial-grade 4G router
compactRIO-based PMU
0.1 class sensors (Altea)
Field trial setup: Alliander data center
C-DAX: A Cyber-Secure Data and Control Cloud for Power Grids 15
LTE Backbone
PDC Firewall
PDC, RTSE
C-DAX
C37.118
8 c
ore
xeo
n/
red
hat
Alliander LivelabData & Control center
Synchrophasor data latencies (4G network)
C-DAX: A Cyber-Secure Data and Control Cloud for Power Grids 16
Mean Std Dev Max Min Data Loss (%)70.9 ms 8.1 ms 770.5 ms 49.2 ms 0.0053
Synchrophasor data latencies (w/ & w/o C-DAX)
C-DAX: A Cyber-Secure Data and Control Cloud for Power Grids 17
Phasor Data Concentrator (PDC)
C-DAX: A Cyber-Secure Data and Control Cloud for Power Grids 18
PDC performances
C-DAX: A Cyber-Secure Data and Control Cloud for Power Grids 19
Real-time State Estimation (RTSE)
C-DAX: A Cyber-Secure Data and Control Cloud for Power Grids 20
Definition:
“Process of estimating the network state (i.e., phase-to-ground node voltages) with an extremely high refresh rate (typically of several tens of frames per second) enabled by the use of synchrophasor measurements.”
Related applications:
Soft-real-time: Optimal V/P control, Congestion management, etc.
Hard real-time: Fault detection and location
Adopted method:
“Discrete Kalman Filter with online assessment of the model error covariance matrix”
Estimated vs. measured voltage profiles
C-DAX: A Cyber-Secure Data and Control Cloud for Power Grids 21
Estimated power Mean Square Error (MSE)
C-DAX: A Cyber-Secure Data and Control Cloud for Power Grids 22
Conclusions
The C-DAX field-trial is unique in the world in that it is the first time that a PMU-based RTSE is deployed in a DNO’s live operated MV distribution feeder, over a public LTE communication network
The C-DAX field trial has demonstrated that high refresh rate, low latency vision on distribution grid can be achieved through PMU-based RTSE via a public LTE network with a pub/sub middleware like C-DAX
The higher accuracies and refresh rates of the proposed PMU-based RTSE system has demonstrated to considerably improve the quality of service provided by a DNO by supporting a considerable amount of existing power-system applications
C-DAX: A Cyber-Secure Data and Control Cloud for Power Grids 23
Contact
www.cdax.eu
Thank you for your attention!
Questions?