7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
1/72
Oil insulatedOutdoor Instrument TransormersBuyers Guide
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
2/722 Outdoor Instrument Transormers | Buyers Guide
Table o content
Products
Technicalinormation
Page
Introduction 3
Explanations 4
Silicone Rubber (SIR) Insulators 7
Design features and Advantages
Current transormers IMB 8
Inductive voltage transormers EMF 10
Capacitor voltage transormers CPB 12
Coupling capacitors CCB 14
Technical catalogues:
Current transormers IMB 17
Inductive voltage transormers EMF 33
Capacitor voltage transormers CPB 41
Coupling capacitors CCB 53
Optional
PQSensor 60
Cable entry kits - Roxtec CF 16 64
Quality, control and testing 66
Inquiry and ordering data 68
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
3/72Buyers Guide | Outdoor Instrument Transormers 3
Day ater day, all year aroundwith ABB Instrument Transormers
ABB has been producing instrument transformers for
more than 70 years. Thousands of our products perform
vital functions in electric power networks around the
world day after day, all year round.
Their main applications include revenue metering, control,
indication and relay protection.
All instrument transformers supplied by ABB are tailor-
made to meet the needs of our customers.
An instrument transformer must be capable of
withstanding very high stresses in all climatic conditions.
We design and manufacture our products for a service life
of at least 30 years. Actually, most last even longer.
Product range Type Highest voltage for equipment (kV)
Current Transformer IMB
Hairpin/Tank typePaper, mineral oil insulation, quartz illing
IMB 36 - 800 36 - 800
Inductive Voltage Transformer EMF
Paper, mineral oil insulation, quartz illing EMF 52 - 170 52 - 170
Capacitor Voltage Transformer CPB
CVD: Mixed dielectric polypropylene-ilm and synthetic oil.
EMU: Paper, mineral oil
CPB 72 - 800 72.5 - 800
Coupling Capacitors CCB
Mixed dielectric polypropylene-ilm and synthetic oil. CCB 72 - 800 72.5 - 800
We are exible and tailor make each instrument transormer to our customers needs.
Sizes other than those mentioned above can be supplied upon request.
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
4/724 Explanations | Buyers Guide
Explanations
Technical specifcations - GeneralStandard/Customer specification
There are international and national standards, as well as cus-
tomer specifcations. ABB High Voltage Products can meet most
requirements, as long as we are aware o them. When in doubt,
please enclose a copy o your specifcations with the inquiry.
System voltage
The system voltage is the maximum voltage (phase-phase),
expressed in kV rms, o the system or which the equipment is
intended. It is also known as maximum system voltage.
Rated insulation level
The combinat ion o voltage values which characterize the
insulation o an instrument transormer with regard to its ca-
pability to withstand dielectric stresses.
The rated value given is va lid or alt itudes 1000 m above sea
level. A correction actor is introduced or higher altitudes.
Lightning impulse test
The lightning impulse test is perormed with a standardized
wave shape 1.2/50 s or simulation o lightning overvoltage.
Rated Power Frequency Withstand Voltage
This test is to show that the apparatus can withstand the
power requency over-voltages that can occur.
The Rated Power Frequency Withstand voltage indicates the
required withstand voltage. The value is expressed in kV rms.
Rated SIWL
For voltages 300 kV the power-requency voltage test is
partly replaced by the switching impulse test. The wave shape
250/2500 s simulates switching over-voltage.
The rated Switching Impulse Withstand Level (SIWL) indi-
cates the required withstand level phase-to-earth (phase-
to-ground), between phases and across open contacts. The
value is expressed in kV as a peak value.
Rated Chopped Wave Impulse Withstand voltage,
Phase-to-earth
The rated chopped wave impulse withstand level at 2 s
and 3 s respectively, indicates the required withstand level
phase-to-earth (phase-to-ground).
Rated frequencyThe rated (power) requency is the nominal requency o the
system expressed in Hz, which the instrument transormer is
designed to operate in.
Standard requencies are 50 Hz and 60 Hz.
Other requencies, such as 16 2/3 Hz and 25 Hz might be ap-
plicable or some railway applications.
Ambient temperature
Average 24 hours ambient temperature above the standard-
ized +35 C inluences the thermal design o the transormers
and must thereore be speciied.
Installation altitude
I installed >1000 m above sea level, the external dielectricstrength is reduced due to the lower density o the air. Always
speciy the installation altitude and normal rated insulation
levels. ABB will make the needed correction when an altitude
higher than 1000 meters ASL is speciied. Internal insulation is
not aected by installation altitude and dielectric routine tests
will be perormed at the rated insulation levels.
Creepage distance
The creepage distance is deined as the shortest distance
along the surace o an insulator between high voltage and
ground.
The required creepage distance is speciied by the user in:
mm (total creepage distance)
mm/kV (creepage distance in relation to the highest system
voltage).
Pollution level
Environmental conditions, with respect to pollution, are some-
times categorized in pollution levels. Five pollution levels are
described in IEC 60815-1.
There is a relation between each pollution level and a corre-
sponding minimum nominal speciic creepage distance.
Pollution level Creepage distance
Phase - Ground voltage
Creepage distance (Old)
Phase - Phase voltage
mm/kV mm/kV
a - Very light 22.0 -
b - Light 27.8 16
c - Medium 34.7 20
d - Heavy 43.3 25
e - Very Heavy 53.7 31
Wind loadThe specifed wind loads or instrument transormers intended or
outdoor normal conditions are based on a wind speed o 34 m/s.
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
5/72Buyers Guide | Explanations 5
Current transormersCurrents
The rated currents are the values o pr imary and secondary
currents on which perormance is based.
Rated primary current
The rated current (sometimes reerred to as rated current,
nominal current or rated continuous current) is the maximum
continuous current the equipment is allowed to carry.
The current is expressed in A rms.
The maximum continuous thermal current is based on average24 h ambient temperature o +35 C.
It should be selected about 10 - 40% higher than the esti-
mated operating current. Closest standardized value should
be chosen.
Extended current ratings
A actor that mult iplied by the rated current gives the maxi-
mum continuous load current and the limit or accuracy. Stan-
dard values o extended primary current are 120, 150 and
200% o rated current. Unless otherwise speciied, the rated
continuous thermal current shall be the rated primary current.
Rated secondary current
The standard values are 1, 2 and 5 A. 1 A gives an overall
lower burden requirement through lower cable burden.
Rated short-time thermal current (Ith)
The rated short-time wi thstand current is the maximum cur-
rent (expressed in kA rms) which the equipment shall be able
to carry or a speciied time duration.
Standard values or duration are 1 or 3 s. Ith
depends on the
short-circuit power o the grid and can be calculated rom theormula: I
th= P
k(MW) / U
m(kV) x 3 kA.
Rated dynamic current (Idyn
)
The dynamic short-time current is according to IEC,
Idyn
= 2.5 x Ith
and according to IEEE, Idyn
= 2.7 x Ith
Reconnection
The current t ransormer can be designed with either primary
or secondary reconnection or a combination o both to obtain
more current ratios.
Primary reconnectionThe ampere-turns always remain the same and thereby the
load capacity (burden) remains the same. The short-circuit ca-
pacity however may be reduced or the lower ratios. Primary
reconnection is available or currents in relation 2:1 or 4:2:1.
Secondary reconnection
Extra secondary terminals (taps) are taken out rom the sec-
ondary winding. The load capacity drops as the ampere-turns
decrease on the taps, but the short-circuit capacity remains
constant. Each core can be individually reconnected.
Burden and Accuracy Class (IEC)
Burden
The external impedance in the secondary circuit in ohms at
the speciied power actor. It is usually expressed as the ap-
parent power in VA -, which is taken up at rated secondary
current. It is important to determine the power consumptiono connected meters and relays including the cables. Unnec-
essarily high burdens are oten speciied or modern equip-
ment. Note that the accuracy or the measuring core, accord-
ing to IEC, can be outside the class limit i the actual burden
is below 25% o the rated burden.
Accuracy
The accuracy class or measuring cores is according to the
IEC standard given as 0.2, 0.2S, 0.5, 0.5S or 1.0 depending
on the application. For protection cores the class is normally
5P or 10P. Other classes are quoted on request, e.g. class
PR, PX, TPS, TPX or TPY.
Rct
The secondary winding resistance at 75 C
Instrument Security Factor (FS)
To protect meters and instruments rom being damaged by
high currents, an FS actor o 5 or 10 is oten speciied or
measuring cores. This means that the secondary current will
increase maximum 5 or 10 times when the rated burden is
connected. FS10 is normally suicient or modern meters.
Accuracy Limit Factor (ALF)The protection cores must be able to reproduce the ault cur-
rent without being saturated.
The overcurrent actor or protection cores is called ALF.
ALF = 10 or 20 is commonly used.
Both FS and ALF are valid at rated burden only. I lower bur-
den the FS and ALF will increase.
Burden and Accuracy Class for other standards, such as
ANSI, IEEE, etc.
More detailed inormation about standards other than IEC
can be ound in our Application Guide, Outdoor InstrumentTransormers, Catalog Publication 1HSM 9543 40-00en or in
the actual standard.
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
6/726 Explanations | Buyers Guide
Voltage transormersVoltages
The rated voltages are the values o pr imary and secondary
voltages on which the perormance is based.
Voltage factor (FV)
It is important that the voltage transormer, or thermal and
protection reasons, can withstand and reproduce the continu-
ous ault overvoltages that can occur in the net. The over-
voltage actor is abbreviated as FV.
The IEC standard speciies a voltage actor o 1.2 cont inu-ously and simultaneously 1.5/30 sec. or systems with eec-
tive grounding with automatic ault tripping, and 1.9/8 hrs or
systems with insulated neutral point without automatic ground
ault systems.
Accuracy, according to IEC, or measuring windings is uli lled
between 0.8 and 1.2 x rated voltage and or protection wind-
ings up to the voltage actor (1.5 or 1.9 x rated voltage).
Reconnection
The voltage transormer can be designed with secondary
reconnection.Secondary reconnection means that extra secondary termi-
nals (taps) are taken out rom the secondary winding(s).
Burden and accuracy class
Burden
The externa l impedance in the secondary circuit in ohms at
the speciied power actor. It is usually expressed as the ap-
parent power in VA -, which is taken up at the rated sec-
ondary voltage.
(See Current Transormers above).
The accuracy class or measuring wind ings, according to IEC,is given as 0.2, 0.5 or 1.0 depending on the application. A
rated burden o around 1.3-1.5 times the connected burden
will give maximum accuracy at the connected burden.
For protection purposes the class is normally 3P or 6P
Simultaneous burden (IEC)
Metering windings and protection windings not connected in
open delta are considered as simultaneously loaded. A pro-
tection winding connected in open delta is not considered as
a simultaneous load.
Thermal limit burden
Thermal limi t burden is the total power the transormer can
supply without excessively high temperature rise. The trans-
ormer is engineered so that it can be loaded with the imped-
ance corresponding to the load at rated voltage, multiplied by
the square o the voltage actor. This means that at a voltage
actor o 1.9/8h, or example, the limit burden = total rated
burden x 1.92.
The transormer cannot be subjected to a higher limit burden
without being loaded higher than the rated burden. Conse-
quently, because o loading considerations, it is unnecessary
to speciy a higher thermal limit burden.
Voltage drop
The voltage drop in an external secondary circuit (cables and
uses) can have a signiicantly larger inluence on the system
ratio error than incorrect burden.
Ferroresonance
Ferroresonance is a potential source o transient overvoltage.
Three-phase, single-phase switching, blown uses, and bro-
ken conductors can result in overvoltage when erroresonance
occurs between the magnetizing impedance o a transormer
and the system capacitance o the isolated phase or phases.For example, the capacitance could be as simple as a length
o cable connected to the ungrounded winding o a trans-
ormer. Another example o erroresonance occurring is when
an inductive voltage transormer is connected in parallel with
a large grading capacitor across the gap o a circuit breaker.
Ferroresonance is usually known as a series resonance.
Additional for Capacitor Voltage Transformers (CVT) and
Capacitor Voltage Divider (CVD)
Capacitance phase - ground
Requirements or capacitance values can be applicable whenusing the CVT or communication over lines (or relay unc-
tions or remote control).
PLC = Power Line Carrier.
Higher capacitance => Smaller impedance or signal.
The ABB line matching unit can be adjusted to any capaci-
tance within requency range 50-500 kHz.
The lower applied requency decide the minimum capacitance
o coupling capacitor.
More information regarding instrument transformers
More detailed inormation about instrument transormers canbe ound in our Application Guide, Outdoor Instrument Trans-
ormers. Catalog Publication 1HSM 9543 40-00en
Explanations
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
7/72Buyers Guide | Outdoor Instrument Transormers 7
Silicone Rubber Insulators
Wide range of instrument transformers with silicone rubber
(SIR) insulators
ABB can supply most o our instrument t rans ormers with
patented helical extrusion-moulded silicone rubber insulation.
CT IMB 36 - 800 kV
VT EMF 52 - 170 kV
CVT CPB 72 - 800 kV
CC CCB 72 - 800 kV
Why Silicone Rubber Insulators?Ceramic (porcelain) insulators have perormed well or several de-
cades, but one o the disadvantages with porcelain is its ragility.
Listed below are some o the advantages o silicone rubber
insulators compared to porcelain:
Non-brittle
Minimum risk or handling and transport damages
Minimum risk or vandalism
Light-weight
Explosion saety
Excellent pollution perormance Minimum maintenance in polluted areas
Hydrophobic
There are several polymeric insulator materials available,
of which silicone has proven to be superior.
Comparison of polymeric insulators
Epoxy EP-rubber Silicone
Brittle Low Excellent Excellent
Insulation Fair Good Excellent
Weight Good Excellent Excellent
Mechanical strength Excellent Good Excellent
Saety Good Good Excellent
Earthquake Good Excellent Excellent
Handling Good Excellent Excellent
Maintenance Fair Fair Excellent
Ageing Fair Good Exce llent
UV-resistance Good Good Excellent
Experience of material
ABB has used silicone rubber (SIR) insu lators s ince 1985,
starting with surge arresters, and has gained considerable
experience thereo.
ABB manufacturing technique
The patented helical extrusion moulded silicone rubber insula-
tors without joints (chemical bonds between spirals) mini-
mizes electrical ield concentrations and reduces build-up o
contamination. The cross-laminated iberglass tube inside the
insulator provides high mechanical strength.
Completed tests
The silicone material used or ABB Inst rument Transormers is
approved according to IEC and ANSI/IEEE standards.
Tests perormed: Acce lerated ageing test (1000 h)
Lightning impulse test, wet power requency test and wet
switching impulse test
Short circuit test
Temperature rise test
Color
The (SIR) insulators or the instrument transormers are sup-
plied in a light gray color.
Deliveries
ABB in Ludvika has supplied instrument transormers with(SIR) insulators or the most severe conditions, rom marine
climate to desert and/or polluted industrial areas.
A reerence l ist can be provided on request.
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
8/728 Outdoor Instrument Transormers | Buyers Guide
IMBDesign eatures and advantages
ABBs oil minimum current transformers type IMB is based
on a hairpin design (shape of the primary conductor) also
known as tank type. The basic design has been used by
ABB for more than 70 years, with more than 170 000 units
delivered.
The design corresponds with the demands o both the IEC
and IEEE standards. Special design solutions to meet other
standards and/or speciications are also available.
The unique illing with quartz grains saturated in o il gives a
resistant insulation in a compact design where the quantity ooil is kept to a minimum
The IMB transormer has a very lexible design that, or ex-
ample, allows large and/or many cores.
Primary winding
The primary winding consists o one or more parallel conduc-
tor o aluminum or copper designed as a U-shaped bushing
with voltage grading capacitor layers.
The insu lation technique is automated to give a simple and
controlled wrapping, which improves quality and minimizes
variations.
The conductor is insulated with a special paper with high
mechanical and dielectric strength, low dielectric losses and
good resistance to ageing.
This design is a lso very suitable or pr imary windings with
many primary turns. This is used when the primary current is
low, or instance unbalance protection in capacitor banks.
(Ex. ratio 5/5 A)
Cores and secondary windings
The IMB type current transormers are lexib le and can nor-mally accommodate any core coniguration required.
Cores or metering purposes are usually made o nickel alloy,
which eatures low losses (= high accuracy) and low satura-
tion levels.
The protection cores are made o high-grade oriented stee l
strip. Protection cores with air gaps can be supplied or spe-
cial applications.
The secondary winding consists o double enamelled cop-
per wire, evenly distributed around the whole periphery o thecore. The leakage reactance in the winding and also between
extra tapping is thereore negligible.
Impregnation
Heating in a vacuum dries the windings. Ater assembly all
ree space in the transormer (approx. 60%) is illed with clean
and dry quartz grain. The assembled transormer is vacuum-
treated and impregnated with degassed mineral oil. The trans-
ormer is always delivered oil-illed and hermetically sealed.
Tank and Insulator
The lower section o the transormer consists o an aluminum
tank in which the secondary windings and cores are mounted.
The insu lator, mounted above the transormer tank, consists
as standard o high-grade brown-glazed porcelain. Designsusing light gray porcelain or silicon rubber can be quoted on
request.
The seal ing system consists o O-ring gaskets.
Expansion system
The IMB has an expansion vessel placed on top o the insula-
tor. A hermetically sealed expansion system, with a nitrogen
cushion compressed by thermal expansion o the oil, is used
in the IMB as the standard design. An expansion system with
stainless steel expansion bellows can be quoted on request.
On request Capacitive voltage tap
The capacitive layers in the h igh voltage insu lation can be
utilized as a capacitive voltage divider. A tap is brought out
rom the second to last capacitor layer through a bushing on
the transormer tank (in the terminal box or in a separate box,
depending on the IMB tank design). An advantage o the ca-
pacitive terminal is that it can be used or checking the condi-
tion o the insulation through dielectric loss angle (tan delta)
measurement without disconnecting the primary terminals.
The tap can also be used or voltage indication, synchronizing
or similar purpose, but the output is limited by the low capaci-
tance o the layers.
The load connected must be less than 10 kohms and the tap
must be grounded when not in use.
One model o IMB 72 - 123 is provided with a DDF (Dielectric Dis-
sipation Factor) terminal in the secondary terminal box. The
terminal must be connected to ground during normal service, but
can be disconnected rom ground and used or checking the
dielectric dissipation actor o the internal high voltage insulation
between primary terminals and ground
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
9/72Buyers Guide | Outdoor Instrument Transormers 9
Climate
The transormers are designed or, and are insta lled in, widely
shiting conditions, rom polar to desert climates all over the
world.
Service life
The IMB transormer is hermetically sealed and the low and
even voltage stress in the primary insulation gives a reliable
product with expected service lie o more than 30 years. The
IMB and its predecessors have since the 1930s been supplied
in more than 170 000 units.
Expansion system
The expansion system, with a ni trogen gas cushion, increases
operating reliability and minimizes the need o maintenance
and inspections. This type o expansion system can be used
in the IMB since the quartz illing reduces the oil volume and a
relatively large gas volume minimizes pressure variations.
For higher rated currents an expansion vessel with external
cooling ins is used to increase the cooling area and heat dis-
sipation to the surrounding air.
An expansion system with gas- illed stainless stee l expansionunits surrounded by the oil and compressed by oil expansion
can be quoted on request.
Quartz filling
Minimizes the quantity o oil and provides a mechanical sup-
port or the cores and primary winding during transport and in
the event o a short-circuit.
Flexibility
The IMB covers a wide range o primary currents up to 4 000 A.
It can easily be adapted or large and/or many cores by in-
creasing the volume o the tank.
Resistance to corrosion
The selected aluminum alloys give a high degree o resistance
to corrosion, without the need o extra protection. Anodized
parts or IMB 36-170 kV can be oered on request, or use in
extreme environments.
IMB >170 kV can be delivered with a protective painting.
Seismic strength
The IMB has a mechanical ly robust construction, designed to
withstand high demands o seismic acceleration without the
need o dampers.
Current Transformer IMB
1
3
4
8
9
10
11
5
7
6
2
1 Gas cushion
2 Oil i ll ing uni t (hidden)
3 Quartz illing
4 Paper-insulated primary
conductor
5 Cores/secondary windings
6 Secondary te rminal box
7 Capac it ive vol tage tap
(on request)
8 Expans ion vessel
9 Oil sight glass
10 Primary termina l
11 Ground terminal
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
10/7210 Outdoor Instrument Transormers | Buyers Guide
ABBs inductive voltage transformers are intended for
connection between phase and ground in networks with
insulated or direct-grounded neutral points.
The design corresponds with the requirements in the IEC and
IEEE standards. Special design solutions to meet other stan-
dards and customer requirements are also possible.
The transormers are designed with a low lux density in the
core and can oten be dimensioned or 190% o the rated
voltage or more than 8 hours.
Primary windingsThe primary winding is designed as a mult i-layer coil o double
enamelled wire with layer insulation o special paper.
Both ends o the windings are connected to metal shields.
Secondary and tertiary windings
In its standard design the transormer has a secondary
measurement winding and a tertiary winding or ground ault
protection, but other conigurations are available as required.
(2 secondary windings in a design according to IEEE standard)
The windings are designed with double enamelled wire and
are insulated rom the core and the primary winding with
pressboard (presspahn) and paper.The windings can be equipped with additional terminals or
other ratios (taps).
Core
The transormer has a core o careully selected materia l, to
give a lat magnetization curve. The core is over-dimensioned
with a very low lux at operating voltage.
Impregnation
Heating in a vacuum dries the windings. Ater assembly, all
ree space in the transormer (approximately 60%) is illed with
clean and dry quartz grains. The assembled transormer isvacuum-treated and impregnated with degassed mineral oil.
The transormer is a lways delivered oil- illed and hermet ical ly
sealed.
Tank and insulator
EMF 52-170: The lower section o the transormer consists o
an aluminum tank in which the winding and core are placed.
The tank consists o selected aluminum alloys that give a high
degree o resistance to corrosion, without the need o extra
protection. Anodized aluminum can be oered on request.
The seal ing system consists o O-ring gaskets.
The insu lator, in i ts standard design, consists o high qual ity,
brown glazed porcelain. The voltage transormers can also be
supplied with silicone rubber insulators.
Expansion system
The EMF has an expansion vessel placed on the top sect ion
o the porcelain. The EMF has a closed expansion system,
without moving parts and with a nitrogen cushion, that is
compressed by the expansion o the oil. A prerequisite or this
is that the quartz sand illing reduces the oil volume, and the
use o a relatively large gas volume, which gives small pres-
sure variations in the system.
Ferro-resonance
The design o the EMF notably counteracts the occurrence o
erro-resonance phenomena:
The low lux in the core at the operating voltage gives a
large saety margin against saturation i erro-resonance
oscillations should occur.
The lat magnetization curve gives a smooth increase o
core losses, which results in an eective attenuation o the
erro-resonance.
I the EMF transormer will be installed in a network with
a high risk or erro-resonance, it can, as a urther saety
precaution, be equipped with an extra damping burden, on a
delta connected tertiary winding. See the igure below.
EMFDesign eatures and advantages
Damping of ferro-resonance
a n a n a n
A N A N A N
da dn da dn da dn
60 ohm, 200 W
R
S
T
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
11/72Buyers Guide | Outdoor Instrument Transormers 11
Climate
These transormers are designed or, and are installed in a
wide range o shiting conditions, rom polar to desert cli-
mates all over the world.
Service Life
The low and even voltage stresses in the primary winding give
a reliable product with a long service lie. EMF and its prede-
cessors have been supplied in more than 60 000 units since
the 1940s.
Expansion systemThe expansion system based on the nitrogen cushion gives
superior operating reliability and minimizes the need o main-
tenance and inspection o the transormer.
Quartz filling
Minimizes the quantity o oil and provides a mechanical sup-
port to the cores and primary winding.
Resistance to corrosion
EMF 52-170: The selected aluminum alloys give a high degree
o resistance to corrosion without the need o extra protection.
Anodized aluminum can be o ered on request.
Seismic strength
EMF is designed to withstand the high demands o seismic
acceleration.
Voltage transformer EMF 145
1 Primary terminal
2 O il level s ight glass
3 Oil
4 Quartz illing
5 Insulator
6 Liting lug
7 Secondary terminal box
8 Neut ral end terminal
9 Expansion system
10 Paper insulat ion
11 Tank
12 Primary w inding
13 Secondary windings
14 Core
15 Secondary te rminals
16 Ground connect ion
1
2
4
5
7
8
9
12
13
14
15
16
11
10
3
6
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
12/7212 Outdoor Instrument Transormers | Buyers Guide
CPBDesign eatures and advantages
ABBs Capacitor Voltage Transformers (CVTs) are intended
for connection between phase and ground in networks
with isolated or grounded neutral.
ABB oers a world-class CVT with superior erro-resonance
suppression and transient response.
The design corresponds to the requirements o IEC and al l
national standards based upon them. Special designs to meet
other standards and customer unique speciications are also
available.
The high qual ity, state o the art, automated manuacture o
the capacitor elements provides consistent quality to ensure
long term reliability and perormance. Due to the optimized
proportions o the mixed dielectric, the capacitor elements
are subject to low electrical stress with high stability under
extreme temperature variations.
CPB portfolio features
The port olio consists o three versions o Capacitor Voltage
Dividers (CVDs), light, medium and heavy, combined with two
sizes o Electromagnetic Units (EMU). The two sizes o EMU
comprise a medium size optimized in respect to market re-quirements or number o windings and perormance. A lighter
EMU is available where customers have lower burden require-
ments. The light capacitance CVD is manuactured up to 245
kV and can only be incorporated with the lightweight EMU.
This special cost eective combination is in this document
designated CPB(L).
Capacitor Voltage Divider
The capacitor voltage divider (CVD) consists o one or more
capacitor units, assembled on top o each other, with each
unit containing the required number o series-connected, oil-
insulated capacitor elements. The units are completely illedwith synthetic oil, hermetically sealed with stainless steel bel-
lows and incorporate o-ring seals throughout the design.
The design o the capacitive elements is consistent with
requirements o revenue metering, with the active component
o aluminum oils insulated with polypropylene ilm and paper
and impregnated with PCB ree synthetic oil. The synthetic oil
has superior and consistent insulating properties when com-
pared to mineral oil.
The automated processing o the capacitor un its urther
contributes to the long term high reliability and perormance
o the CPB.
Electromagnetic Unit (EMU)The voltage divider and the electromagnetic unit are connect-
ed by internal bushings, which is necessary or applications
with high accuracy.
The EMU has double-enamelled copper windings and an i ron
core assembled with high quality magnetic core steel and is
oil impregnated and mounted in a hermetically sealed alumi-
num tank with mineral oil illing.
The primary winding is divided into a main part , and a set o
externally adjustable connected trimming windings. The nomi-
nal intermediate voltage is approximately 22/3 kV.
The EMU incorporates an inductive reactor, connected in
series between the voltage divider and the high voltage end
o the primary winding to compensate or the shit in phase
angle caused by the capacitive reactance o the CVD. This
inductive reactance is tuned individually on each transormer
to achieve the required accuracy.
For special applications, such as HVDC stations, measure-
ment o harmonics, etc an alternative EMU is available without
a separate compensating reactor. For this special type o EMU
the unction o the compensating reactor and primary wind-ing o the intermediate transormer are combined into one
device. This arrangement gives additional advantages such as
a wider requency operating range and urther improvement in
the transient response. This special type o EMU is limited to
lower burden requirements.
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
13/72Buyers Guide | Outdoor Instrument Transormers 13
Climate
These transormers are designed or, and are installed in
widely varying conditions, rom arctic to desert climates, on
every continent.
Ferro-resonance
The low induction, combined with an eic ient damping circuit,
gives a sae and stable damping o erro-resonance at all
requencies and voltages up to the rated voltage actor; see
page 40.
Life timeThe low voltage stress within the capacitor elements ensures
a sae product with an expected service lie o more than 30
years. The long term reliability and perormance is urther
ensured by the state o the art, automated manuacture and
processing o the capacitor elements and units.
Transient properties
The high intermediate voltage and high capacitance result in
good transient properties.
Adjustment
The adjustment windings or ratio adjustment are accessiblein the terminal box, under a sealed cover.
Power Line Carrier (PLC)
The CPB is designed with the compensating reactor connect-
ed on the high voltage side o the primary winding, providing
the option o using higher requencies (> 400 kHz) or power
line carrier transmission.
Stray capacitance
The design with the compensating reactor on the high voltage
side o the main winding ensures less than 200 pF stray ca-
pacitance, which is the most stringent requirement in the IECstandard or carrier properties.
Stability
The CPB has a high Quali ty Factor as a resul t o the compara-
tively high capacitance combined with the high intermediate
voltage. The Quality Factor = Cequivalent
x U2intermediate
is a mea-
sure o the accuracy stability and the transient response. The
higher this actor, the better the accuracy, and the better the
transient response.
Capacitor Voltage Divider
1 Expansion system
2 Capac ito r elements
3 Intermediate vol tage bushing
8 Primary terminal, lat 4-hole Al-pad
10 Low voltage terminal (or carrier requency use)
Electromagnetic unit
4 Oil level glass
5 Compensat ing reactor
6 Ferro-resonance damping circuit
7 Primary and secondary windings
9 Gas cushion
11 Secondary termina l box
12 Core
2
10
712
3
5
9
4
6
1
8
11
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
14/7214 Outdoor Instrument Transormers | Buyers Guide
CCBDesign eatures and advantages
ABBs coupling capacitors are intended for connection
between phase and ground in networks with isolated or
grounded neutral.
Application
ABB oers a world-class coupling capacitor wi th superior
properties or PLC application as well as iltering and other
general capacitor applications. ABBs coupling capacitors
(designated CCB) are intended or connection between phase
and ground in high voltage networks with isolated or ground-
ed neutral.
The design corresponds to the requirements o IEC 60358-1
and all national standards based on this standard. Special
designs to meet other standards and customer speciications
are also available. Due to the design o the capacitor units,
described below, the coupling capacitor elements are com-
bining both low voltage stress and high stability to tempera-
ture variations.
CCB portfolio features
The port olio consists o three versions o coupl ing capacitors
(CCs), light, medium and heavy, o which the light capaci-
tance CC is manuactured up to 245 kV.
Capacitor design
The coupling capacitor consists o one up to our capacitor
units, assembled on top o each other. Each unit contains
a large number o series-connected, oil-insulated capacitor
elements. The units are completely illed with synthetic oil,
hermetically sealed with stainless steel bellows and incorpo-
rated o-ring seals are used throughout the design.
The capacitor insulators and elements are designed with
respect to the same demands as or the capacitor part o
revenue metering CVT and thus also share the same conser-
vative design philosophy. This conservative philosophy resultsin a design with low voltage stress that makes the coupling
capacitors capable o handling a voltage actor up to 1.9/8
hrs although this is not required by the IEC coupling capacitor
standard.
Thei r active component consists o aluminum oi l, insulated
with paper/polypropylene ilm, impregnated by a PCB-ree
synthetic oil which has better insulating properties than min-
eral oil and is a perect matching or the mixed dielectric. Due
to its proportions between paper and polypropylene ilm this
dielectric has proven itsel much more insensitive to tempera-
ture changes in contradiction to e.g. ull ilm capacitors.
The automated processing o the capacitor units urther contrib-
utes to the long term high reliability and perormance o the CCB.
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
15/72Buyers Guide | Outdoor Instrument Transormers 15
Climate
These coupling capacitors are designed or being installed in
widely varying conditions, rom arctic to desert climates, on
every continent.
Life time
The low voltage stress within the capacitor elements ensures
a sae product with an expected service lie o more than 30
years.
Power Line Carrier (PLC)
The CCB are designed or use with in the entire power linecarrier transmission requency range rom 30 kHz to 500 kHz.
However, the light capacitance CCB 72 - 245 is not designed
or line trap on the top.
1
2
3
44
56
Coupling Capacitor CCB
1 Primary terminal, lat 4-hole Al-pad
2 Expansion system
3 Capacitor elements
4 Rating plate (For low capacitance CCB 72-245 its placed on the
expansion cover)
5 L- (low vol tage) terminal / Ground clamp
6 Support Insulators (mainly or PLC use)
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
16/7216 Outdoor Instrument Transormers | Buyers Guide
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
17/72Buyers Guide | Outdoor Instrument Transormers 17
For revenue metering and protection in high voltage
networks, the oil-paper insulated current transformer IMB
is the most sold transformer in the world.
Designed for widely shifting conditions, from polar to
desert climate
Flexible tank type design allows large and/or many
cores
The unique quartz filling minimizes the quantity of oil and
provides a mechanical support to the cores and primary
winding.Due to the low center of gravity the IMB is very suitable
for areas with high seismic activity.
From international studies we can see that the IMB design
is a reliable product (failure rate more than 4 times lower
than average) with no need for regular maintenance.
IMB 36-800 kVTank type current transormer
Brief performance data
Installation Outdoor
Design Tank (Hai rpin) type
Insulation Oil-paper-quartz
Highest voltage for equipment 36 - 800 kV
Max primary current Up to 4 000 A
Short-circuit current Up to 63 kA/1 sec
Insulators Porcelain
On request silicon rubber (SIR)
Creepage distance 25 mm/kV
(Longer on request)
Service conditions
Ambient temperatu re
Design altitude
-40 C to +40 C
(Others on request)
Maximum 1000 m
(Others on request)
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
18/7218 Outdoor Instrument Transormers | Buyers Guide
Material
All external metal suraces are made o an a luminum alloy,
resistant to most known environment actors. Bolts, nuts,
etc. are made o acid-proo steel. The aluminum suraces do
not normally need painting. We can, however, oer anodized
aluminum or a protective paint.
Creepage distance
As standard, IMB is oered with creepage distance 25 mm/kV.
Longer creepage distance can be provided on request.
Mechanical stabilityThe mechanical stabi lity gives su icient saety margins or
normal wind loads and terminal orces. Static orce on primary
terminal may be up to 6 000 N in any direction. The IMB will
also withstand most cases o seismic stress.
Rating plates
Rating plates o stainless steel with engraved text and the wir-
ing diagram are mounted on the cover o the terminal box.
Transport - storage
The IMB 36 - 145 is normally transported (3-pack) and stored
vertically. I horizontal transport is required this must be statedon the order.
The IMB 170 - 800 is packed or horizontal transport (1-pack).
The transormer(s) must be stored on a lat and stable surace
with a suitable load capacity, and i possible, in its original
packaging.
For extended storage, the contact suraces should be pro-
tected rom corrosion. Beore placing in service, ensure that
all contact suraces are thoroughly cleaned.
I the transormer(s) is stored horizontally, under unavorableclimatic conditions, corrosion can occur on secondary termi-
nals and accessories in the terminal box due to drainage not
unctioning properly in the horizontal position. When stored
horizontally, the terminal box must be checked or conden-
sation and penetrating moisture. Beore long-term storage,
appropriate measures must be taken, such as connecting
heating elements, i available, or providing the terminal box
with silica gel or an equivalent drying agent. This applies or
storage o up to two years. For longer storage, up to ive
years, the transormer must be stored indoors or under roo.
The maximum time when stored in i ts orig inal crate wi thoutany protection is six months. I the transormer is stored pro-
tected, make sure the building is very well ventilated.
Make sure that the transormer(s) is put in vertical position at
least 48 h prior to energizing (96 h or 800 kV).
Arrival inspection - assembly
Please check the packaging and contents with regard to
transport damage on arrival. In the event o damage to the
goods, contact ABB or advice beore urther handling o the
goods. Any damage should be documented (photographed).
The transormer must be assembled on a lat surace. An un-
even surace can cause misalignment o the transormer, with
the risk o oil leakage.
Assembly instructions are provided with each delivery.
MaintenanceThe maintenance requirements are small , as IMB is hermeti-
cally sealed and designed or a service lie o more than 30
years. Normally it is suicient to check the oil level and that no
oil leakage has occurred. Tightening o the primary connec-
tions should be checked occasionally to avoid overheating.
A more detailed check is recommended ater 20-25 years o
service. A manual or conditional monitoring can be sup-
plied on request. This gives urther guarantees or continued
problem-ree operation.
The methods and the scope o the checks depend great ly onthe local conditions. Measurements o the dielectric losses o
the insulation (tan delta-measurement) and/or oil sampling or
dissolved gas analysis are recommended check methods.
Maintenance instructions are supplied with each delivery.
Oil sampling
This is normally done through the oil- ill ing terminal. I re-
quired, we (ABB, HV Components) can oer other solutions
and equipment or oil sampling.
Impregnation agentThe oil is according to IEC 60296 grade 2 and is ree o PCB
and other heavily toxic substances and has a low impact on
the environment.
Disposal
Ater separating the oil and quartz the oil can be burned in an
appropriate installation. Oil residue in the quartz can be burnt,
whereater the quartz can be deposited.
The disposal should be carried out in accordance with local
regulatory requirements.
The porcelain can, ater it has been crushed, be used aslandill.
The metals used in the t ransormer can be recycled. To recy-
cle the aluminum and copper in the windings, the oil-soaked
paper insulation should be burnt.
IMB 36-800 kVTank type current transormer
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
19/72Buyers Guide | Outdoor Instrument Transormers 19
Primary terminals
IMB 36 800 is as standard equipped with aluminum bar
terminals, suitable or IEC and NEMA speciications. Other
customer speciic solutions can be quoted on request.
Maximum static and dynamic orce on the terminal is up to
6 000 and 8 400 N respectively, depending on type o IMB.
Maximum torsional moment is 1 000 Nm.
Secondary terminal box and secondary terminals
The transormer is equipped with a secondary terminal box,
protection class IP 55, according to IEC 60529. This box is
equipped with a detachable, undrilled gland plate, which on
installation can be drilled or cable bushings.
The terminal box is provided with a drain.
The standard terminal box can accommodate up to 30 (16)
terminals o the type Phoenix UK10N or cross section
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
20/7220 Outdoor Instrument Transormers | Buyers Guide
IMB 36-800 kVTank type current transormer
Maximum continuous primary current and short-time current
Type Normal current Cooling flanges Cooler Maximum short-time
current 1 sec
Maximum short-time
current 3 sec
Maximum dynamic
current
A A A kA kA kA peak value
IMB 36-72 1) 1200 - - 40 31.5 108
IMB 36-72 1) 2000 - - 40 31.5 108
IMB 84-123 1) 720 - - 31.5 12.5 78.8
IMB 84-123 1) 1440 - - 40 31.5 108
IMB 36-170 2) 2400 - 3150 63 40 170
1200 - 1500 40 40 108
400 - - 31.5 18 85
150 - - 16 9 43IMB 245 2) 1600 - 2000 40 40 108
IMB 245 3) 2000 2400 3150 63 63 170
1000 1200 1500 40 40 108
300 - - 31.5 18 85
150 - - 16 9 45
IMB 300-420 3) 2500 - 3150 63 63 170
1200 - 1500 40 40 108
IMB 420-550 4, 5) 2500 - 4000 63 40 170
1200 - 2000 40 40 108
IMB 800 5) - - 4000 63 40 1701) Light tank, 2) Standard tank, 3) Heavy tank, 4) Octagon tank, 5) HV tank
Other types o primary conductors can be supplied on requestMaximum continuous primary current = load actor x primary rated current related to a daily mean temperature that does not exceed 35 C
Primary winding can be designed with reconnection alternative between two or three primary rated currents with a ratio o 2:1 or 4:2:1
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
21/72Buyers Guide | Outdoor Instrument Transormers 21
Nominal flashover and creepage distance (Porcelain)
Normal creepage distance 25 mm/kV
(Min. values)
Long creepage distance 31 mm/kV
(Min. values)
Type Flashover
distance
Total creepage
distance
Protected creepage
distance
Flashover
distance
Total creepage
distance
Protected creepage
distance
mm mm mm mm mm mm
IMB 361) - - - 660 1813 800
IMB 361) - - - 635 1813 762
IMB 721) 660 1813 800 1005 3075 1300
IMB 721) 635 1813 762 980 3160 1307
IMB 841) - - - 1005 3075 1300
IMB 841)
- - - 980 3160 1307IMB 1231, 6) 1005 3075 1300 1215 3625 1600
IMB 1231) 980 3160 1307 1190 3880 1634
IMB 362) - - - 630 2248 1020
IMB 722) - - - 630 2248 1020
IMB 842) 630 2248 1020 - - -
IMB 1232) 1120 3625 1400 1120 4495 1860
IMB 1452) 1120 3625 1400 1120 4495 1860
IMB 1702) - - - 1330 5270 2200
IMB 1702, 7) - - - 1600 6525 2740
IMB 2452, 3) 1915 6740 2850 2265 8490 3685
IMB 3003) 2265 8250 3495 2715 10430 4645
IMB 3623) 2715 10430 4645 3115 12480 5630IMB 4203) 3115 12480 5630 3635 14325 6465
IMB 4204, 5) 3215 11550 4800 3820 15280 6870
IMB 5504, 5) 3820 15280 6870 4715 18944 8340
IMB 8005) 5520 20000 8405 - - -
1) Light tank, 2) Standard tank, 3) Heavy tank, 4) Octagon tank, 5) HV tank6) 25 mm/kV or 29 mm/kV or 123 kV system voltage.7) 38 mm/kV or 170 kV system voltage and 45 mm/kV or 145 kV system voltage is available.
Note: Long creepage distance eects dimensions A, B, D (see dimensions)
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
22/7222 Outdoor Instrument Transormers | Buyers Guide
IMB 36-800 kVTank type current transormer
Test Voltages IEC 61869-2
Type Highest voltage for
equipment (Um)
AC voltage tes t,
1 minute, wet/dry
Lightning impulse
1.2/50 s
Switching impulse
250/2500 s
RIV test
voltage
Max RIV
level
kV kV kV kV kV Max. V
IMB 36 36 70/70 170 - - -
IMB 72 72.5 140/140 325 - - -
IMB 123 123 230/230 550 - 78 2500
IMB 145 145 275/275 650 - 92 2500
IMB 170 170 325/325 750 - 108 2500
IMB 245 245 460/460 1050 - 156 2500
IMB 300 300 -/460 1050 850 191 2500
IMB 362 362 -/510 1175 950 230 2500IMB 420 420 -/630 1425 1050 267 2500
IMB 550 550 -/680 1550 1175 334 2500
IMB 800 800 -/975 2100 1550 486 2500
Test voltages above applies at 1000 meters above sea level
Test Voltages IEEE C 57.13, RIV test values according to IEEE C 57.13.5
Type Highest system
voltage
Power frequency
applied voltage test
AC-test Wet,
10 sec
Lightning impulse
(BIL) 1.2/50 s
Chopped
impulse
RIV test
voltage
Max RIV
level1)
kV kV kV kV Max. kV kV V
IMB 36 36.5 70 70 200 230 - -
IMB 72 72.5 140 140 350 400 - -
IMB 123 123 230 230 550 630 71 200IMB 145 145 275 275 650 750 84 200
IMB 170 170 325 315 750 865 98 200
IMB 245 245 460 445 1050 1210 142 250
IMB 362 362 575 - 1300 1500 209 250
IMB 550 550 800 - 1800 2070 303 350
IMB 800 800 920 - 2050 2360 462 5001) Test procedure according to IEC. Test voltages above applies at 1000 meters above sea level
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
23/72Buyers Guide | Outdoor Instrument Transormers 23
Burdens
Our current transormer IMB has a very lexible design allow-
ing large burdens. However, it is important to determine the
real power consumption o connected meters and relays in-
cluding the cables. Unnecessary high burdens are oten speci-
ied or modern equipment. Note that the accuracy or the
measuring core, according to IEC, can be outside the class
limit i the actual burden is below 25% o the rated burden.
Over-voltage protection across primary winding
The voltage drop across the primary winding o a current
transormer is normally very low. At rated primary current itis only a couple o volts and at short-circuit current a ew
hundred volts.
I a high requency current or voltage wave passes through
the primary winding can, due to the winding inductance,
high voltage drops occur. This is not dangerous or a current
transormer with a single-turn primary winding, but or multi-
turn primaries may it lead to dielectric puncture between the
primary turns.
It is thereore ABBs practice to protect the primary winding in
multi-turn designs with a surge arrester connected in parallel
with the primary.
Standard design o IMB current transormer is without surgearrester. Surge arrester o type POLIM C 1.8N will however
be included when needed.
Standard accuracy Classes.
Current transormers o the type IMB are designed to comply with the ollowing accuracy classes.
Other classes can be quoted on request.
IEC 61869-2 IEEE C57.13 / IEEE C57.13.6
Class Application Class Application
0.2 Precision revenue metering 0.15 Precision revenue metering
0.2S Precision revenue metering 0.15S Precision revenue metering0.5 Standard revenue metering 0.3 Standard revenue metering
0.5S Precision revenue metering 0.6 Metering
1.0 Industrial grade meters 1.2 Metering
3.0 Instruments C100 Protection
5.0 Instruments C200 Protection
5P Protection C400 Protection
5PR Protection C800 Protection
10P Protection X Protection
10PR Protection
PX Protection
PXR Protection
TPS Protection
TPX Protection
TPY Protection
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
24/7224 Outdoor Instrument Transormers | Buyers Guide
IMB 36-800 kVDesign and shipping data
Dimensions
A B C D E F G H J K
Type Total
height
Height to
primary
terminal
Ground
level
height
Flashover
distance
Length across
primary terminal
bushing
Dimension of
bottom tank
Height to
terminal box
Spacing for
mounting holes
mm mm mm mm mm mm mm mm mm mm
IMB 36 1) 1718 1424 611 660 359 197.5 279 395 138 335
IMB 36 1) 1718 1424 636 635 359 197.5 279 395 138 335
IMB 72 1) 1718 1424 611 660 359 197.5 279 395 138 335
IMB 72 1) 1718 1424 636 635 359 197.5 279 395 138 335
IMB 84 1) 2063 1769 611 1005 359 197.5 279 395 138 335
IMB 841)
2063 1769 636 980 359 197.5 279 395 138 335IMB 123 1) 2063 1769 611 1005 359 197.5 279 395 138 335
IMB 123 1) 2063 1769 636 980 359 197.5 279 395 138 335
IMB 36 2) 2000 1635 840 630 470 235 335 595 110 410
IMB 72 2) 2000 1635 840 630 470 235 335 595 110 410
IMB 84 2) 2000 1635 840 630 470 235 335 595 110 410
IMB 123 2) 2490 2125 840 1120 470 235 335 595 110 410
IMB 145 2) 2490 2125 840 1120 470 235 335 595 110 410
IMB 170 2) 2700 2335 840 1330 470 235 335 595 110 410
IMB 245 2) 3320 2950 865 1915 440 235 335 595 110 410
IMB 245 3) 3640 3050 965 1915 440 270 370 750 475 450
IMB 300 3) 4150 3405 965 2265 490 270 370 750 475 450
IMB 362 3) 4600 3855 965 2715 490 270 370 750 475 450IMB 420 3) 5000 4255 965 3115 490 270 370 750 475 450
IMB 420 4) 5505 4760 1365 3215 490 320 380 1040 783 500
IMB 420 5) 5580 4790 1390 3215 526 360 410 1105 805 600
IMB 550 4) 6100 5360 1365 3820 490 320 380 1040 783 500
IMB 550 5) 6180 5390 1390 3820 526 360 410 1105 805 600
IMB 800 5) 8840 7090 1390 5520 526 360 410 1105 805 600
1) Light tank, 2) Standard tank, 3) Heavy tank, 4) Octagon tank, 5) HV tank
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
25/72Buyers Guide | Outdoor Instrument Transormers 25
IMB 36 - 123 IMB 36 - 170
A
B
J2
0
G F
K
K
C
D
E
J
C
D
E
A
B
KH
K
K
G
F
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
26/7226 Outdoor Instrument Transormers | Buyers Guide
IMB 36-800 kVDesign and shipping data
IMB 245 2)IMB 245 1)
E
D
C
J
K
A
B
H
K
K
G
F
H
K
F
G
C
D
K
E
25
A
B
K
J
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
27/72Buyers Guide | Outdoor Instrument Transormers 27
K
J
E
C
D
BA
K
F G
H
K
30
IMB 300 - 420 2) IMB 420 - 550 3)
C
D A
B
E
K K25
J
H
K
F
G
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
28/7228 Outdoor Instrument Transormers | Buyers Guide
IMB 36-800 kVDesign and shipping data
30
E
D
B
A
C
J
K K
KH
F G
IMB 420 - 550 4)
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
29/72Buyers Guide | Outdoor Instrument Transormers 29
30
K
K
F G
H
E
C
B
D
A
K
J
IMB 800 4)
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
30/7230 Outdoor Instrument Transormers | Buyers Guide
IMB 36-800 kVDesign and shipping data
Changes, special design of dimensions
A, B , C A A A A
Tank-type Increased tank height Cooling flange Cooler Three primary ratios Horizontal transport
mm mm mm mm mm
Light tank - - - - 10
Standard tank 210 - 255 193 -
Heavy tank 210 or 420 210 35 / 240 *) - -
Octagon tank 150 - 440 - -
HV tank 200 or 400 - 400 **) - -
*) 35 mm or IMB 245, 240 mm or IMB 300 - 420**) 400 mm or IMB 420 - 550, IMB 800 is always equipped with cooler
Shipping data for standard IMB
Type Net weight incl. oil Oil Shipping weight Shipping dimensions Shipping volume
1-pack/3-pack 1-pack/3-pack 1-pack/3-pack
kg kg kg LxWxH m m3
IMB 36 1) 200 25 340 / 730 1.97x0.65x1.08 / 1.73x0.79x1.93 1.4 / 2.6
IMB 36 1) 240 26 380 / 850 1.97x0.65x1.08 / 1.73x0.79x1.93 1.4 / 2.6
IMB 72 1) 200 25 340 / 730 1.97x0.65x1.08 / 1.73x0.79x1.93 1.4 / 2.6
IMB 72 1) 240 26 380 / 850 1.97x0.65x1.08 / 1.73x0.79x1.93 1.4 / 2.6
IMB 84 1) 240 27 395 / 870 2.31x0.65x1.08 / 1.73x0.79x2.42 1.6 / 3.3
IMB 84 1) 290 28 445 / 1020 2.31x0.65x1.08 / 1.73x0.79x2.42 1.6 / 3.3
IMB 123 1) 240 27 395 / 870 2.31x0.65x1.08 / 1.73x0.79x2.42 1.6 / 3.3IMB 123 1) 290 28 445 / 1020 2.31x0.65x1.08 / 1.73x0.79x2.42 1.3 / 3.3
IMB 36 2) 420 45 530 / 1350 2.26x0.6x0.94 / 1.67x0.8x2.21 1.3 / 3
IMB 72 2) 420 45 530 / 1350 2.26x0.6x0.94 / 1.67x0.8x2.21 1.3 / 3
IMB 84 2) 420 45 530 / 1350 2.26x0.6x0.94 / 1.67x0.8x2.21 1.3 / 3
IMB 123 2) 490 50 620 / 1580 2.75x0.6x0.94 / 1.67x0.8x2.7 1.5 / 3.6
IMB 145 2) 490 50 620 / 1580 2.75x0.6x0.94 / 1.67x0.8x2.7 1.5 / 3.6
IMB 170 2) 550 55 700 / - 2.96x0.6x0.94 / - 1.7 / -
IMB 245 2) 750 80 970 / - 3.48x0.6x0.94 / - 2.0 / -
IMB 245 3) 1100 110 1460 / - 3.91x1.06x1.26 / - 5.2 / -
IMB 300 3) 1400 170 1815 / - 4.5x1.06x1.26 / - 5.2 / -
IMB 362 3) 1500 180 1915 / - 4.7x1.06x1.26 / - 6.3 / -
IMB 420 3) 1600 190 2050 / - 5.1x1.05x1.31 / - 7.0 / -
IMB 420 4) 2500 300 3120 / - 5.82x1.23x1.22 / - 8.8 / -
IMB 420 4) 2600 290 3220 / - 5.74x1.06x1.47 / - 9.0 / -
IMB 550 4) 2800 330 3480 / - 6.42x1.23x1.22 / - 9.7 / -
IMB 550 5) 3500 510 4180 / - 6.34x1.06x1.47 / - 9.9 / -
IMB 800 5) 4200 670 6400 / - 8.71x1.06x1.47 / - 13.5 / -1) Light tank2) Standard tank3) Heavy tank4) Octagon tank5) HV tank
IMB 36 - 145 is normally packed or vertical transport in a 3-pack.
Vert ical transport in a 1-pack can be quoted on request.
IMB 170 - 800 is always packed or horizontal transport in 1-pack.
Additional weights
Weight indicated in table above is or standard IMB.
Additional weights may occur depending on requirements and coniguration.
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
31/72Buyers Guide | Outdoor Instrument Transormers 31
IMB 36-800 kVReconnection
General
The current t ransormer can be reconnected to adapt or vary-
ing currents. The IMB type can be delivered in a coniguration
that permits reconnection either on primary or secondary side,
or a combination o the two.
Connection above is for the lower current Connection above is for the higher current
The unused taps on the reconnectable secondary winding
must be let open.
I windings/cores are not used in a current transormer they
must be short-circuited between the highest ratio taps (e.g.
S1 - S5) and shall be grounded.
Secondary reconnection
Two primary ratios for two turns Two primary ratios, connected for one turn
C2C1C2
C1
P1 P2
S1 S5S4S3S2
Caution!
Never leave an unused secondary winding open.
Very high-induced voltages are generated across the
terminals and both the user and the transormer are
subjected to danger.
Primary reconnection
The advantage o pr imary reconnection is that the ampere-
turns remains the same and thereby the output (VA). The dis-
advantage is that the short-circuit capability may be reduced
or the lower ratio(s).
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
32/7232 Outdoor Instrument Transormers | Buyers Guide
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
33/72Buyers Guide | Outdoor Instrument Transormers 33
EMF 52-170 kVInductive voltage transormer
For revenue metering and protection in high voltage
networks, the oil-paper insulated voltage transformer
EMF is the most sold inductive voltage transformer in the
world.
Designed for widely shifting conditions, from polar to
desert climate.
Low flux in the core at operating voltage gives a wide
safety margin against saturation and ferro-resonance.
The unique quartz filling minimizes the quantity of oil and
allows a simple and reliable expansion system.
Brief performance data
Installation Outdoor
Design Inductive type
Insulation Oil-paper-quartz
Highest voltage for equipment 52 - 170 kV
Voltage fac tor (Vf) Up to 1.9/8 hrs
Insulators Porcelain
On request silicon rubber (SIR)
Creepage distance 25 mm/kV
(Longer on request)
Service conditions
Ambient temperatu re
Design altitude
-40 C to +40 C
(Others on request)
Maximum 1000 m
(Others on request)
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
34/7234 Outdoor Instrument Transormers | Buyers Guide
EMF 52-170 kVInductive voltage transormer
Material
EMF 52-170: All external metal suraces are made o an
aluminum alloy, resistant to most known environment actors.
Bolts, nuts, etc. are made o acid-proo steel. The aluminum
suraces do not normally need painting. We can, however, o-
er a protective paint or anodized aluminum.
Creepage distance
EMF is available as standard with normal or long creepage
distances according to the table on page 36. Longer creep-
age distances can be quoted on request.
Mechanical stability
The mechanical stabi lity gives a suic ient saety margin or
normal wind loads and stress rom conductors. EMF can also
withstand high seismic orces.
Rating plates
Rating plates o stainless steel, with engraved text and wiring
diagrams are mounted on the transormer enclosure.
Transport - storage
The EMF 52-84 is always transported (3-pack) and stored
vertically.
The EMF 123-170 is normal ly t ransported (3-pack) and stored
vertically. I horizontal transport is required this must be stated
on the order.
The transormer(s) must be stored on a lat and stable surace
with a suitable load capacity, and i possible, in its original
packaging.
For extended storage, the contact suraces should be pro-
tected rom corrosion. Beore placing in service, ensure that
all contact suraces are thoroughly cleaned.
I the transormer(s) is stored horizontally (only EMF 123-170),
under unavorable climatic conditions, corrosion can occur on
secondary terminals and accessories in the terminal box due
to drainage not unctioning properly in the horizontal position.
When stored horizontally, the terminal box must be checked
or condensation and penetrating moisture. Beore long-term
storage, appropriate measures must be taken, such as con-
necting heating elements, i available, or providing the terminal
box with silica gel or an equivalent drying agent. This applies
or storage o up to two years. For longer storage, up to ive
years, the transormer must be stored indoors or under roo.
The maximum time when stored in i ts orig inal crate wi thout
any protection is six months. I the transormer is stored pro-
tected, make sure the building is very well ventilated.
Make sure that the transormer(s) is put in vertical position at
least 48 h prior to energizing.
Arrival inspection - assembly
Please check the packaging and contents with regard to
transport damage on arrival. In the event o damage to the
goods, contact ABB or advice, beore urther handling o the
goods. Any damage should be documented (photographed).
The transormer must be assembled on a lat surace. An un-
even surace can cause misalignment o the transormer, with
the risk o oil leakage.Assembly instructions are provided with each delivery.
Maintenance
Maintenance requirements are insigniicant as EMF is de-
signed or a service lie o more than 30 years.
Normally it is only necessary to check that the oil level is cor-
rect, and that no oil leakage has occurred. The transormers are
hermetically sealed and thereore require no other inspection.
A comprehensive inspection is recommended ater 30 years.
This provides increased saety and cont inued problem-reeoperation. The inspection methods and scope very signiicant-
ly depending on the local conditions. As the primary winding
is not capacitive graded, the measurement o tan-delta gives
no signiicant result. Thereore oil sampling or dissolved gas
analysis is recommended or checking the insulation.
Maintenance instructions are supplied with each delivery.
ABB, High Voltage Products is at your disposal or discus-
sions and advice.
Impregnation agent
The oil is according to IEC 60296 grade 2 and is ree o PCBand other heavily toxic substances and has a low impact on
the environment.
Disposal
Ater separating the oil and quartz the oil can be burned in an
appropriate installation. Oil residue in the quartz can be burnt,
whereater the quartz can be deposited.
The disposal should be carried out in accordance with local
regulatory requirements.
The porcelain can, ater it has been crushed, be used as
landill.The metals used in the t ransormer can be recycled. To recy-
cle the copper in the windings, the oil-soaked paper insulation
should be burnt.
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
35/72Buyers Guide | Outdoor Instrument Transormers 35
Primary terminals
EMF 52-170 is as standard equipped with an aluminum bar
terminal, suitable or IEC and NEMA speciications.
The primary terminal is a voltage terminal and should thereore,
according to standards, withstand static orce o 1 000 N or Um
(system voltage) 123 170 kV and 500 N or lower voltages.
Withstand dynamic orce is 1 400 and 700 N respectively.
Secondary terminal box and
Secondary terminals
The terminal box or the secondary winding terminal is mounted
on the transormer enclosure. As standard the terminal box is
manuactured o corrosion resistant, cast aluminum.
This box is equipped with a detachable, undr illed gland plate,
which on installation can be drilled or cable bushings. It can, on
request, be quoted with cable glands according to the custom-
ers speciication.
The terminal box is provided with a drain.
EMF 52-170: Secondary terminals accept wires with cross-
sections up to 10 mm2.
Protection class or the terminal box is IP 55.
Ground (Earth) connections
The transormer is normally equipped with a ground terminal
with a clamp o nickel-plated brass.
For conductors =5-16 mm (area 20-200 mm2), see the igure.
A stain less stee l bar, 80 x 145 x 8 mm, can be quoted on
request. The bar can be supplied drilled according to IEC or
NEMA standards.
Grounding o the secondary circuits is made inside the terminal
box.
EMF 52-170
EMF 52-84 EMF 123-170
EMF 52-84
EMF 123-170
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
36/7236 Outdoor Instrument Transormers | Buyers Guide
EMF 52-170 kVDesign data
Nominal flash-over and creepage distance
Normal porcela in (min. nom. va lues) Porce lain with long c reepage distance (min . nom. values)
Type Flash-over
distance
Creepage
distance
Protected creepage
distance
Flash-over
distance
Creepage
distance
Protected creepage
distance
mm mm mm mm mm mm
EMF 52 630 2248 1020
Others on request.
Normally insulator or the nearest higher voltage.
EMF 72 630 2248 1020
EMF 84 630 2248 1020
EMF 123 1200 3625 1400
EMF 145 1200 3625 1400
EMF 170 1330 5270 2200
Test voltages IEC 61869-3, (SS-EN 60044-2)
Type Highest voltage for
equipment
(Um)
1 min
wet/dry
LIWL
1.2/50 s
RIV test
voltage
RIV level
kV kV kV kV Max. V
EMF 52 52 95 250 30 125
EMF 72 72.5 140 325 46 125
EMF 84 84 150 380 54 125
EMF 123 123 230 550 78 2500
EMF 145 145 275 650 92 2500
EMF 170 170 325 750 108 2500Test voltages above are valid or altit udes 1000 meters above sea level.
Test voltages IEEE C 57.13 (CAN/CSA 60044-2)
Type Highest voltage for equipment
(Um)
AC test
dry, 1 min
AC test
wet, 10 sec
BIL
1.2/50 s
kV kV kV kV Max.
EMF 52 52 95 95 250
EMF 72 72.5 140 175 350
EMF 123 121 (123) 230 230 550
EMF 145 145 275 275 650
EMF 170 169 (170) 325 315 (325) 750
Values wi thin bracke ts reer to CAN/CSA 60044-2. Test voltages above are valid or altitudes 1000 meters above sea level.
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
37/72Buyers Guide | Outdoor Instrument Transormers 37
Secondary voltages and burdens according to IEC
Standards
International IEC 61869-3
Swedish Standard SS-EN 60044-2
All nationa l standards based on IEC
Rated data at 50 or 60 Hz, Voltage factor 1.5 or 1.9
The transormer normally has one or two windings or cont inu-
ous load and one residual voltage winding.
Other conigurations can be quoted according to require-
ments.
Standard accuracy classes and burdens
According to IEC
50 VA class 0.2 100 VA class 3P
100 VA class 0.5 100 VA class 3P
150 VA class 1.0 100 VA class 3P
For lower or higher burdens please contact us.
The standards state as standard values for rated voltage factor 1.5/30 sec.
for effectively earthed systems, 1.9/30 sec. for systems without effective
earthing with automatic earth fault tripping and 1.9/8 hrs for systems with
insulated neutral point without automatic earth fault tripping.Since the residual voltage winding is not loaded except dur-
ing a ault, the eect o its load on the accuracy o the other
windings is disregarded in accordance with IEC.
Please note that modern meters and protection
require much lower burdens than those above, and
to achieve best accuracy you should avoid speciying
burdens higher than necessary; see page 6.
Secondary voltages and burdens according to IEEE and
CAN
Standards
Amer ican IEEE C57.13-2008
Canadian CAN/CSA 60044-2
Rated data at 60 Hz, Voltage factor 1.4
The transormer normally has one or two secondary windings
or continuous load (Y-connected).
Example o turns ratios:
350-600:1 means one secondary winding with the ratio 350:1
and one tertiary winding ratio 600:1350/600:1:1 means one secondary winding and one tertiary
winding both with taps or ratios 350:1 and 600:1
Protective classes according to CAN/CSA (1P, 2P, 3P) can be
quoted on request.
Voltage actor 1.9 according to CAN/CSA can be quoted on
request.
Standard accuracy classes and burdens
According to IEEE and CAN/CSA
0.3 WXY 0.6 WXYZ 1.2/3P WXYZ
For lower or higher burdens please contact us.
Rated burdens:
W = 12.5 VA power actor 0.1
X = 25 VA power actor 0.7
Y = 75 VA power actor 0.85
YY = 150 VA power actor 0.85Z = 200 VA power actor 0.85
ZZ = 400 VA power actor 0.85
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
38/7238 Outdoor Instrument Transormers | Buyers Guide
EMF 52-170 kVDesign data
Voltage transformers EMF
A B C D E F
Type Total
height
Flash-over
distance
Height to
terminal box
Fixing hole
dimensions
Ground level
height
Expansion
vessel diameter
mm mm mm mm mm mm
EMF 52 1464 630 114 335 x 335 540 324
EMF 72 1464 630 114 335 x 335 540 324
EMF 84 1464 630 114 335 x 335 540 324
EMF 123 2360 1200 65 410 x 410 760 416
EMF 145 2360 1200 65 410 x 410 760 416
EMF 170 2490 1330 65 410 x 410 760 416
EMF 52-84
Note: Primary terminal will be mounted at site
EMF 123-170
Note: Primary terminal will be mounted at site
A
B
E
C
D
F
135
D
20
C
B
E
D20
A
D
F
135
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
39/72Buyers Guide | Outdoor Instrument Transormers 39
EMF 52-170 kVShipping data
Voltage transformers EMF (Vertical 3-pack)
Type Net weight incl. oil Oil Shipping weight Shipping dimensions Shipping volume
Porcelain insulator 3-pack 3-pack, L x W x H 3-pack
kg kg kg m m3
EMF 52 300 40 1040 1.6 x 0.9 x 1.7 2.5
EMF 72 300 40 1040 1.6 x 0.9 x 1.7 2.5
EMF 84 300 40 1040 1.6 x 0.9 x 1.7 2.5
EMF 123 570 80 1975 2.0 x 1.0 x 2.6 5.2
EMF 145 570 80 1975 2.0 x 1.0 x 2.6 5.2
EMF 170 610 83 2130 2.0 x 1.0 x 2.7 5.4
EMF 52 - 84 must not be tilted more than 60 during transport and storage.
EMF 123 - 170 is normally packed or vertical transport (3-pack). However, it can be transported in a horizontal position and is
available on request or horizontal transport (1-pack).
Voltage transformers EMF (Horizontal 1-pack)
Type Net weight incl. oil Oil Shipping weight Shipping dimensions Shipping volume
Porcelain insulator 1-pack 1-pack, L x W x H 1-pack
kg kg kg m m3
EMF 123 570 80 720 2.7 x 0.8 x1.1 2.0
EMF 145 570 80 720 2.8 x 0.8 x 1.1 2.1EMF 170 610 83 765 2.8 x 0.8 x 1.1 2.1
EMF 170 1) 670 86 810 3.1 x 0.8 x 1.1 2.21) Insulator with long creepage distance.
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
40/7240 Outdoor Instrument Transormers | Buyers Guide
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
41/72Buyers Guide | Outdoor Instrument Transormers 41
CPB 72-800 kVCapacitor voltage transormer
The CPB is designed for revenue metering and protection
in high voltage networks.
The high quality, state of the art, automated manufacture
of the capacitor elements provides consistent quality
to ensure long term reliability and performance. Due to
the optimized proportions of the mixed dielectric the
capacitor elements are subject to low electrical stress
with high stability under extreme temperature variations.
The CPB is designed for a wide range of shifting
conditions including polar and desert climates.
Brief performance data
Installation Outdoor
Design Capacitor type, complies with IEC
Insulation
CVD
EMU
Aluminum-oi l / paper /
polypropylene-ilm, synthetic oil
Paper - mineral oil
Highest voltage for equipment 72 - 800 kV
Voltage fac tor (Vf) Up to 1.9/8 hrs
Insulators Porcelain / Silicon rubber (SIR)
Creepage distance 25 mm/kV (Longer on request)
Service conditions
Ambient temperatu re
Design altitude
-40 C to +40 C (Other on request)
Maximum 1 000 m(Other altitude on request)
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
42/7242 Outdoor Instrument Transormers | Buyers Guide
Material
All external metal suraces are made o an a luminum alloy,
resistant to most known environment actors. Bolts, nuts, etc.
are made o acid-proo stainless steel. The aluminum suraces
do not normally need painting. We can however oer anodiza-
tion or protective paint, (normally light gray).
Creepage distance
As standard the CPB is oered with creepage distance
25 mm/kV. Longer creepage distances can be oered on
request.
Silicone Rubber Insulators
The complete CPB range is available with silicone rubber
insulators. Our SIR insulators are produced with a patented
helical extrusion molding technique, which gives completely
joint-ree insulators wi th outstanding perormance. All CVTs
with this type o insulators have the same high creepage dis-
tance, 25 mm/kV phase-phase, as porcelain.
Mechanical stability
The mechanical stabi lity gives su icient saety margin or
normal wind loads and conductor orces. For all combinations
except CPB(L), it is possible to mount line traps on top o thecapacitor divider. The CPB will also withstand most cases o
seismic stress.
Ferroresonance damping circuit
All CVTs need to incorporate some kind o erro-resonance
damping, since the capacitance in the voltage divider, in
series with the inductance o the transormer and the series
reactor, constitutes a tuned resonance circuit.
This circuit can be brought into resonance, that may saturate
the iron core o the transormer by various disturbances in
the network. This phenomenon can also overheat the electro-magnetic unit, or lead to insulation breakdown.
The CPB use a damping ci rcuit, connected in parallel with
one o the secondary windings (see diagram on page 51). The
damping circuit consists o a reactor with an iron core, and
an oil-cooled resistor in series. Under normal use, the iron
core o the damping reactor is not saturated, yielding a high
impedance, so that practically no current is lowing through
this circuit.
The damping circuit has two bridged terminals; d1- d2, be-
hind a sealed covering hood in the terminal box. In particular
cases, and ater agreement, this bridge can be opened, to
check that the circuit is intact, by resistance measurement.
Ratio adjustment
The transormer o the electromagnetic unit has ive adjust-
ment windings on the earth side o the primary winding. The
numbers o turns o these windings have been chosen so that
the ratio can be adjusted 6.05% in steps o 0.05%. These
windings are externally accessible, behind a sealed cover-
ing hood in the secondary terminal box. The CVT is deliveredadjusted or a speciied burden and class, and normally no
urther adjustment is necessary.
I needed, the adjustment windings enable exchange o the
voltage divider on site, and readjustment o the transormer
or the new combination o voltage divider/electromagnetic
unit.
Rating plates
Corrosion resistant rating plates with text and wiring diagrams
are used. General data can be ound on the door o the termi-
nal box, connection diagrams and secondary winding data onthe inside.
Each capacitor unit is marked with measured capacitance at
the top.
Potential Grounding Switch
A potential grounding switch can be included in the EMU.
Power Line Carrier (PLC)
As an option al l CVTs can be equipped with Carr ier Acces-
sories. Modern PLC equipment are adapted or a wide range
o coupling capacitors. No speciic capacitance is required.Only minimum capacitance must be speciied due to choice o
requency.
CPB 72-800 kVCapacitor voltage transormer
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
43/72Buyers Guide | Outdoor Instrument Transormers 43
Standard terminal box
The transformer can also be equipped with larger
terminal box with space for power line carrier equipment.
Primary terminal
The CPB is normally delivered with a lat 4-hole a luminum pad,
suitable or bolts with C-C rom 40 to 50 mm and or connecting
normal aluminum cable clamps.
Other primary terminals can be oered on request, such as a
round aluminum studs, =30 mm.
Test orces at the primary terminal as per IEC 61869-5
Highest voltage for
equipment Um (kV)
Static withstand test load FR
(N)
CPB(L) CPB
72.5 to 100 500 2500123 to 170 1000 3000
245 1250 2500
300 to 362 - 1250
420 - 1500
Secondary terminal box and secondary terminals
The transormer is equipped with a secondary terminal box,
protection class IP 55. This box is equipped with a detachable,
undrilled gland plate, which on installation can be drilled or cable
bushings. It is also provided with a drain. The terminal box can
also be equipped with uses or micro circuit breakers.
The secondary terminals normally consist o Phoenix UK10N
standard terminal blocks or wire cross-section 10 mm.
In the terminal box are also terminals (d1-d2) or damping circuit,
terminals or the adjustment windings (B1 to B11) and the capac-
itor low voltage terminal L (or power line carrier equipment).
Terminals d1 - d2 and B1 - B11 are intended or actory sett ings
and thus located behind a sealed covering hood to prevent inad-
vertent reconnection.
The L terminal must always be grounded i no
carrier equipment is connected.
Ground terminals
The transormer is normally equipped with a ground clamp wi th a
cap o nickel-plated brass or IEC conductors 8 16 mm
(area 50 200 mm2) and or ANSI conductors # 2 SOL to 500
MCM, which can be moved to either mounting oot.
A stainless steel bar, 80 x 145 x 8 mm, can be quoted on request.
The bar can be supplied drilled according to IEC or NEMA standards.
Grounding terminals or the secondary circuits are placed inside
the terminal box.
14
40
50
135
40
20
75100
7/28/2019 Buyers Guide Oil Insulated Outdoor Instrument Transformers Ed 7 En
44/7244 Outdoor Instrument Transormers | Buyers Guide
Unpacking
Please check the crates and their contents or damage during
transportation upon receipt. Should there be any damage,
please contact ABB or advice beore the goods are handled
urther. Any damage should be documented (photographed).
Storage
The ollowing have to be considered during storage:
The transormer(s) must be stored on a lat and stable surace
with a suitable load capacity, and i possible, in its original
packaging.
For extended storage, the contact suraces should be pro-
tected rom corrosion. Beore placing in service, ensure that
all contact suraces are thoroughly cleaned.
I the transormer(s) is stored horizontally, under unavorable
climatic conditions, corrosion can occur on