BUS BAR CALCULATION
END USER = SVC A/C DGNP
CONSULTANT = NIL
SHOP ORDER NO = 7306026405
PROPOSED RATED BUS BAR CURRENT =
Ir (A) 1250
FAULT LEVEL
If (KA) 26.3
DURATION (SEC) 3
BUS BAR
W (mm) 60
T (mm) 16
R (RUN/PH) 1
BUS BAR RE-RATING TO BE DONE
AT AN AMBIENT TEMP OF =
50 DEG C
TEMP RISE CONSIDERED
WHILE RE-RATING =
55 DEG C
A. STEADY STATE THERMAL CURRENT CARRYING CAPACITY AT 40DEG C AMBIENT & 50DEG C TEMP RISE:
CURRENT CARRYING CAPACITY FOR SINGLE 60 X 16
CU BUS BAR = 1460 (REFER www.cda.org.uk)
MULT. FACTOR FOR 1 RUNS/PH= 1 (REFER www.cda.org.uk)
TOTAL CURRENT CARRYING CAPACITY / PH=
1460 X 1 = 1460
CROSS SECTION OF SINGLE BUS BAR CHAMBER IN HWX PANEL =
532 X 492 = 261744
TOTAL CU CROSS SECTION IN BUS BAR CHAMBER (INCLUDING ALL 3 PHASES)=
3 X W X T X R
= 3 X 60 X 16 X 1
= 2880
AREVA T D INDIA LIMITED
BUS BAR CALCULATION
TOTAL CU CROSS SECTION / BUS BAR CHAMBER AREA= 2880 / 261744
= 1.100311755 %
IF THIS RATIO IS LESS THAN 5%, DERATING FACTOR= 0.85
SO, ACTUAL CURRENT RATING / PH=
0.85 X 1460 = 1241 Amp
B. RE-RATING FOR DIFFERENT AMBIENT & TEMP. RISE:
RE-RATING TO BE DONE FOR:
AMBIENT TEMP= t2 = 50 DEG C
TEMP RISE= Φ2 = 55 DEG C
THEREFORE,
WORKING TEMP= T2 = 105 DEG C
SAY, REVISED BUS BAR CURRENT RATING (TO BE CALCULATED)= I2
FROM SECTION-A WE KNOW:
t1 = 40
Φ1 = 50
T1 = 90
I1 = 1241
NOW, WORKING FORMULA FOR CALCULATING THE REVISED BUS BAR CURRENT RATING :
I1 / I2 = (Φ1 / ΦΦ1 / ΦΦ1 / ΦΦ1 / Φ2)^0.61 X ((1+ρρρρ(T2-20) / (1+ρρρρ(T1-20))^0.5 (REFER www.cda.org.uk)
WHERE, ρ = TEMP. CO-EFFICIENT OF RESISTANCE FOR CU AT 20 DEG C = 0.00393
THEREFORE, REVISED BUS BAR CURRENT = I2 = 1285.90057 Amp