BURNERMATE UNIVERSAL BOILER CONTROLLER Overview
The BurnerMate Universal offerscompleteboilercontrolinaneconomic,off-the-shelf,pre-programmedcontroller.Separate processors are used for flame safeguard andcombustioncontrolforNFPA85compliance.ConfigurationisdoneinthefieldusingtheLCDkeypad,theoptionaltouchscreen,orourexclusiveBMU_EditsoftwareonyourPC.BMUfunctionsinclude:
• Advancedflamesafeguardcontrol includingfirstoutannunciation, nuisance trip protection, and lockoutsnapshot
• Combustioncontrol(jackshaft,parallelpositioning,withoptionaloxygentrim)usinguptotenservosanduptofourVariableSpeedDrives(VSDs)
• Draftcontrol• Feedwater control: single, two-element, or three-
element.• Large 10” color touch screenwith pre-programmed
graphicpages
The BurnerMateUniversal is available for immediatedelivery,requiresnoprogramming,and isrecognizedbyU.L.
AdvancedFlameSafeguardControlTheBurnerMateUniversaltakesburnersafetytoahigherlevel.Insteadofonedigital inputprovingtheboilerlimitsaremade, theBMUaccepts over forty boiler limits intoseparatedigital inputs.Thismakesfirstoutannunciationeasy,aswellasadvanceddiagnosticstoquicklypinpointwhyaboilertrippedandwhatneedstobedonetobringitonlineagain.Oneortwoflamescannerscanbeusedforaddedreliability,or increasedboilersafety.Flamesafetycontrolfeaturesinclude:
• Supportforuptothreefuels(oil,naturalgas,andasecondgasfuel).
• Fuel changeover canbe initiated locallyor remotelyeithershuttingdowntheboilerduringthefuelchange,orchangingfuel“on-the-fly”.Fuelchangecanbeinitiatedmanually,orremotelyviacontactsorModbus
• Monitorsuptoninerecyclinglimits,upto33shutdownlimitsandoneortwoflamescanners.
• Alllimitinputsare120VAC,wiredinparallel,andseparatelyannunciated
• Duringashutdown,allmajorstatusbitsarerecordedandsavedforuptothelast10lockouts.
• Adjustabletimedelaysareavailableformanylimitstoavoidtrips
• Gasvalve leak test logiccanbeconfigured (withorwithoutaventvalve)
• Automateddailylowwatercutoutblowdownwithlevelswitchtestcanbeconfiguredtoalarmorshutdowntheburnerifafaultylowwatercutoutswitchisdetected.
• Optionaloilgunpurgelogiccanbeconfigured(blow-throughintothefurnace,orsuctionedbackoutofthegunviascavengerpump)
• High fluegas temperature shutdown is included foradditionaldryboilerprotection
• Toreducecombustiblesinthefurnace,theburnercanbedriventolowfirebeforeitisshutdown
FuelAirRatioControlTheBMU supports single point positioning (jackshaft)combustion control and parallel positioning combustioncontrol.OxygentrimcanbeaddedtoeithercontrolstrategybyaddingaPreferredZPprobe.Alinktrimactuator(LTA)canbeusedtovarytheairoutputinasinglepointpositioningsystem. Fuel valves and air dampers are controlled byhighprecision(0.1°accuracy)digitalelectricservos.EachdigitalservoincludesamicroprocessorandallservosarenetworkedtotheBMUchassis.BMUfuel-airratiocontrolfunctionsinclude:
203.743.6741 • 203.798.7313www.preferred-mfg.com
Instruments & Controls
Catalog 25
Instruments &
Controls
161
• Jackshaftorparallelpositioningcombustioncontrolissupported.
• Uptotenhigh-precisionservosarenetworkedtothecontroller,and4-20mAoutputsareavailabletocontrolVSDsforFDfan,FGRfan,IDfanorFWpump
• Upto11combustioncontrolpointscanbeprogrammedforeachoutput
• Separatepointsareavailableforstandby,purge,andlight-offpositions
• OptionalO2trimcontrolissupported• Separatepointsareprovidedforeachfuel’sVSDand
VSDbypassmodeforatotalofsixcurvesperservooranalog output
• Atomizing (steam or air) pressure (or differentialpressure)controlsetpointscanbeinputasafunctionoffiringrate
• Windbox oxygen control (monitored by a separateoxygen analyzer) allows the technician to enter awindboxoxygenvs.firingratecurve.TheBMUtrimstheFGRdamper(orFGRfanVSD)tomaintainFGRflow(asmeasuredbywindboxoxygencontent)oncurveatallfiringrates
• Duringboilerpurge,allservosarestrokedandtheirfeedbacksignalsarecheckedforservointegrity
BoilerControlFunctionsMany of themost common boiler control functions areincorporatedintheBMU.Thissimplifiesthecontrolsystemandofteneliminatestheneedforadditionalrelays,timers,orothercontrolhardwaremountedintheburnermanagementsystemenclosure.Additionally,theBMUacceptshard-wiredinputsforburneroff/onandremotefiringratethatmakeiteasilyintegratedwiththePreferredChiefDispatcherlead/lagsequencer.Othercontrolfunctionsinclude:
• Burnerfiringratecontrol(localPIDcontrol,remotefiringrateinput,orremotesetpointinput)
• Draft control with optional firing rate feed forward.Controlledoutputs includeastackdamper,oran IDfanVSD
• Feedwater control (single, two-, or three-element)ControlledoutputsincludeafeedwatercontrolvalveorfeedwaterpumpVSD
• Outdoorairtemperatureresetforhotwaterboilers.• Warmstandbyanddomestichotwateroverride• Lowfireholdbasedonboilershellorfluegas
temperature• Five auxiliary relays can be configured to control
commonboilerroomauxiliaries• Supervisedorautomaticwatercolumn
blowdownandlowwaterleveltestlogic• Boiler cold start functionallows for adjustable boiler
thermalshockprotection
BURNERMATE UNIVERSAL BOILER CONTROLLER SystemOverview
BMU-SM-15 Servo Motor with optional ‘QD’electrical Quick-Connects.
HighPrecisionDigitalElectricServoMotors
The servomotors provided as part of theBurnerMateUniversalareuniquetoPreferred.TheBMUcommunicatesdigitallywith amicroprocessor controller board in eachservo.Thecontrollerboardpreciselypositions theservomotorandperformscontinuoussafetydiagnostics.Ahighprecision, sealed feedback potentiometer continuouslyreportstheservopositiontothecontrollerboardandbacktotheBMUchassis.ThecontrollerboardincludespushbuttonsforZERO,CW,andCCW“jogging”oftheservomotor.Inaddition, LEDsprovide important diagnostic informationfor each servomotor. Servos are availablewith quick-disconnectfittingstoreducewiringtime.Torqueratingsfortheservomotorsstartat3ft-lbforsmallcontrolvalvesandgoupto720ft-lbforlargeairdampersorstackdampers.
BMUFuel-Air-FGRCrossLimitedPositionPacing“PositionPacing” isaunique featureof theBurnerMateUniversal thatassures thepositionsofallFuel,Air,andFGRServosandrelatedVSDspeedsremain“oncurve.”
FD Damper
FD VSD
Fuel Valve
Position Pacing
0.5 sec travel
0.5
sec
trave
l
Two Servo Example of Position Pacing
203.743.6741 • 203.798.7313www.preferred-mfg.com
Instruments & Controls
Catalog 25
Inst
rum
ents
& C
ontro
ls
162
BURNERMATE UNIVERSAL BOILER CONTROLLER SystemOverview
BMU Servo and Controller Board(with QD option)
Duringloadswings,positionpacinghelpsavoid:
• Periodsof lean combustion that can cause rumbling,vibration,orflame-outsduringfiringrateincreases
• Fuelrichconditionsthatcancausesmoking,burn-back,andexcessiveCOorunburnedhydrocarbonsduringfiringrate decreases
BMU “PositionPacing” assures that all servoactuatorsremain“oncurve”inthefollowingmanner:
• Allfuel,air,FGRServosandVSDsmovetogetherand“oncurve”--thereisnofuelorair“lead”or“lag”
• Each servo andVSDhas precise position or speedfeedbacktoensurethatalldevicesarecrosslimited.
• TheBMU“knows”howfareachservoactuatorandVSDcanmovein0.5secondsanduses“self-adaptive”positionpacingtoensurethatloadchangesnevercauseanyservoorVSDtolagbehindtheothers
• Εvery0.5seconds,theBMUexaminesallcurvesto“find”theservoorVSDworstcase0.5second‘shift’causedbyarequestedfiringratechange
• Basedonthecurves,allotherservosorVSDstargetpositionsare“scaledback”toassureALLdevicesarrive“oncurve”attheendofthenext0.5secondmove
BMU“positionpacing”isfullyautomatic,providesforsafercombustion control and drastically improved firing rateresponsetimesandrequiresnoadjustmentsbytheuser.
FlameScannersTheBurnerMateUniversalsystemincludesalineofPreferredInstrumentsflamescanners.Digital,microprocessor-basedscannersareavailableinultraviolet(UV)infrared(IR)andself-checkingUVmodels. Flamedetector and amplifierareintegratedintothescannerheadtoeliminatetheneedforseparate(panel-mounted)scanneramplifiers.Scannerhousingsaremachinedfromanodizedaluminum.Scannermountsare1/2”NPTF for theUVand IRversions,and1”NPTF for theself-checkingUVmodel.Eachscannerincludes a cooling air port for hot or dirty applications.Scanners include two LEDs--one blinks intermittentlydependingontheintensityoftheflamesignal,theotherLEDilluminateswhenthescannerclosesthe“FlameDetected”relayoutput.Electricalconnectionisbyathreadedmilitary-style quick disconnect.The scanners output a contactclosure forflameprovinganda4-20mAflamestrengthsignalfortroubleshootingdiagnostics.OneortwoscannerscanbeconnectedtoasingleBMUcontroller.Allscannersincludethesamepinoutandmilitary-stylequickdisconnectallowingforscannerstobeeasilychanged.TheBMUcanbeusedwith any othermanufacturer’s flame relay thatproducesa120VACcontactclosurewhenflameisproven.
BMU scanners available in ultraviolet, infrared, and self-checking ultraviolet. All connect by military-style quick disconnect fittings.
Up to four servos connect to each BMU-JBOX terminal. Each servo has a low voltage and high voltage quick connect cable. A single BMU-CABLE, and 120 VAC H, N, and G wires provide the
“home run” termination to the BMU chassis.
203.743.6741 • 203.798.7313www.preferred-mfg.com
Instruments & Controls
Catalog 25
Instruments &
Controls
163
BURNERMATE UNIVERSAL BOILER CONTROLLERSystemOverview
Digital CommunicationTheBurnerMateUniversal communicates via a secure,safetyrateddigitalprotocolwiththerequiredLCDkeypadandtheservonetwork.TheBMUchassiscommunicatesviaModbustotheoptionaltouchscreenOITandoptionalCommStationOIT-Bridge.BoththetouchscreenOITorOIT-BridgeactasprotocolconvertersandcanspeakModbus,ModbusoverEthernet,oranumberofotheropendigitalprotocolstoaBuildingAutomationSystem(BAS)orEnergyManagementSystem(EMS).BoththetouchscreenOITandtheOIT-Bridgearepre-loadedwithover75standardgraphicpages.Boiler overview screens canbe field-selected toresembletheboilerbeingfired.
Analog CommunicationTheBurnerMateUniversalacceptsindustrystandard4-20 mA, 0-5 VDC, 1-5 VDC, thermocouple, andthermistor inputs.Analog inputsareself-poweredby theBMU.Engineeringunits,orscaledvaluesareenteredbyparameterselectionduringtheBMUsetup.Analogoutputsare4-20mAandareavailableonlyforthedevicesshownabove.AllotheroutputsareontheBMUservonetwork.
203.743.6741 • 203.798.7313www.preferred-mfg.com
Instruments & Controls
Catalog 25
Inst
rum
ents
& C
ontro
ls
164
BURNERMATE UNIVERSAL BOILER CONTROLLERSystemOverview
External Reset
Alternate Setpoint
FD Fan Speed Mode
LWCO By-Pass PushbuttonLow Water Alarm
High Water Alarm
Domestic Hot Water Override
Local Call for Heat
12
3
456
7
8Remote Call for Heat
Burner Off-On9
10
Recycle Inputs
Operating Limit
Aux. Low Water
Low Water Flow
Fresh Air Damper OpenSpare Limit
Oil Firing Requested
High Oil Pressure
Low Oil PressureLow Atomizing Pressure
Low Atomizing Flow
Lock-out Inputs
11
1213
1415
16
17
1819
20
High/Low Oil Temperature
Oil Gun in Position
Gas Firing Requested
High Gas PressureLow Gas Pressure
Fuel 3 Firing Requested
High Fuel 3 Pressure
Low Fuel 3 Pressure
Flame Scanner 1 Proven
Flame Scanner 2 Proven
21
2223
2425
26
27
2829
30
High High Limit Shutdown
Minimum Air Flow
FD Fan Energized
VFD FD Fan EnergizedLow Water Level Cutout
High Water Level Cutout
Low Draft Pressure
ID Fan EnergizedFGR Fan Energized
Spare Limit
31
3233
3435
36
37
3839
40
Leak Test High Pressure
Leak Test Low Pressure
Draft Damper Open
Purge Air Flow
Oil Valve Proof of Closure
Gas Valve Proof of ClosureFuel 3 Proof of Closure
41
4243
44
46
47
4849
Emergency Stop
51
52
53
5455
56
62
63
65
66
Ignition TransformerPilot Gas Valves
Atomizing Shutoff Valve
Oil Shutoff Valves
Oil Gun Post PurgeMain Gas Shutoff Valves
Aux. Relay 1 N.O. Contact
Aux. Relay 2 N.O. Contact
Aux. Relay 3 N.O. Contact
Aux. Relay 3 N.C. Contact
57
5859
60
Fuel 3 Shutoff ValvesMain Gas Vent Valve
FD Fan Motor Starter (C)
FD Fan Motor Starter (NO)
61
Lockout Contact
64
Aux. Relay 3 Common Contact
68
69 Aux. Relay 4 N.O. Contact
Aux. Relay 4 N.C. Contact67
Aux. Relay 4 Common Contact
71
72 Aux. Relay 5 N.O. Contact
Aux. Relay 5 N.C. Contact70
Aux. Relay 5 Common Contact
120 VAC Outputs
Dry Contacts
Status Inputs
Disable Windbox FGR Trim 45
Digital Inputs & OutputsAlldigital inputs to theBMUare120VAC from industrystandardswitchesandcontacts.Eachofthemostcommonboiler/burnerlimitswitchesispre-assignedtoaparticulardigitalinput.Sparelimitinputsareprovided.
Auxiliary RelaysFiverelayoutputsareavailable,eachconfigurableforthefollowingfunctions:commonalarm,auxiliaryfanstarter,fuel1,2,3auxiliaries,commonauxiliaries,limitsmade,outsideairlouvers,hotwaterpump/valve,LWCOauto-blowdownvalve,flameon,fuel1,2,3open.Relayoutputsarerated120VAC5ampsandareconfiguredbyparameterselection.
203.743.6741 • 203.798.7313www.preferred-mfg.com
Instruments & Controls
Catalog 25
Instruments &
Controls
165
BURNERMATE UNIVERSAL BOILER CONTROLLERSystemOverview
Windbox Oxygen FGR ControlManymodern lowNOxandultra lowNOxburnershavechallenging limits of flammability.They require preciseamountsoffluegasrecirculation(FGR)forallfiringrates,despite changes in boiler load and ambient conditions.SincemeteringFGRflowratesisimpracticalwemeasurewindbox oxygen for closed loop control with a reliableprocess variablemeasurement.Automatic control ofwindboxoxygencontenthasprovenaneffectivemeansofconsistentFGRflow.
Atomizing Steam Pressure Control Traditionalatomizingsteampressurecontrol ishamperedby the limited turndowncapabilitiesof existingatomizingsteamdifferentialpressureregulatingvalves.Theoilflameisoftenover-atomizedat lowfire,under-atomizedathighfire,orboth.Thisproblemhasbeensolved,butbyusingveryexpensivecontrolvalveswithself-containedregulators/positioners.TheBurnerMateUniversalcontrollermonitorsatomizingsteampressure,andmodulatesaninexpensivequarterturnflowcontrolvalvetodelivervirtuallyanysteampressurerequiredatanyfiringrate.Alternately,anatomizingsteam/oildifferentialpressuretransmittercanbeusedandtheBurnerMateUniversalwillholdthesteam/oildifferentialpressure“oncurve”atallfiringrates.
Becausethissystemusesatightshut-offcharacterizedballvalveinsteadofaself-operatedpressureregulatingvalve,aseparateatomizingsteamshutoffvalve isnot required.Simply program the controller so that atomizing steampressureiszeroduringboilerstandby,andtheflowcontrolvalvewillbedrivenfullyclosed.Manyboilertechniciansliketoopentheatomizingsteamvalveduringpurgetoblowanywateroutofthelineandgetthelinehotpriortolightingofftheoilburner.TheBurnerMateUniversalprovidesseparate
FGR
S
Boiler AE
Windbox Oxygen
VFD Motor
S
BMU Controller
S
Fresh Air
Fixed PositionDamper
Gas FCV
Windbox oxygen FGR control schematic
BMUController
SOil
AtomizingSteamorAir
S Oil GunPT
OilServo
AtomizingPressureServo
AtomizingPressureXmtr
OilSSOV
OptionalShutoffValve
Atomizing steam pressure is monitored and held “on curve” at all boiler firing rates.
In this configuration, atomizing steam/oil differential pressure is monitored and held “on curve” at all boiler firing rates.
pointsforstandby,purge,andignitiontoaccommodatethispractice.
Fuel Flow Meter Display and Totalizing Tomonitor and track fuel usage (and savings) theBMUdisplaysandtotalizedfuelflowsforuptothreefuels.FuelflowsarealsoavailableonModbustocommunicatewithaplantEnergyManagementSystem(EMS)
BMUController
SOil
AtomizingSteamorAir
S Oil Gun
PT
OilServo
AtomizingPressureServo
AtomizingSteam/Oil
OilSSOV
OptionalShutoffValve
dPTXMR d/pxmtr
203.743.6741 • 203.798.7313www.preferred-mfg.com
Instruments & Controls
Catalog 25
Inst
rum
ents
& C
ontro
ls
166
BURNERMATE UNIVERSAL BOILER CONTROLLERSystemOverview
Low Fire Fuel Transfer TheBurnerMateUniversalallowstheusertochangefuelswithoutshuttingdowntheboiler,inaccordancewithNFPA85Procedures for Single Burner Simultaneous Firing of Two Fuels for Fuel Transfer Only.Thefuelchangeoverisdoneatlowfire,butthelossofproductionismuchlessthanshuttingdowntheboiler,purging,andre-lighting.Thisprocedurecanbeveryconvenientforlightingoffdifficultoil-firedburners,orNo.6oilfiredburners.
TheBurnerMateUniversalhandlesthelowfirefueltransferaccordingtothefollowingsequence:
1. Theburner fires the “old” fuel in release tomodulatemode.
2. Thefuelrequestinputschange(eitherlocallybythekeypad,orremotelybyaBAS)indicatingwhatthedesired“new’”fuelwillbe.
3. Thecurvedataforthenewfuelischeckedforerrors.4. TheBMUwaitsforthenewfuel’slimitstomake.5. Bothfuelactuatorsaresenttotheirignitionpositions.6. The controller ‘paces’ to the ignitionpositionwith all
combustionactuators/VSDs‘oncurve’.7. TheBMUwaits until both fuels reach their ignition
positions.8. Theair damper/VSDsare thenbiasedup toprovide
additonalairforthenewfuel.9. Oxygen,FGR,andfullmeteringtrimarenulledthrough
thebiasedairphases.10. TheBMUwaitsuntilthedamper/VSDsareattheirbiased
position(s)11. TheBMUthenopensthenewfuelSSOVs.Theoldfuel
flameignitesthenewfuel.12. TheBMUwaitsforMTFIsecondstoallowtheflameto
stabilize.13. TheBMUclosestheoldfuelSSOVs.14. Theairbiasisthenremoved.15. TheBMUwaitsfor10secondstoallowtheairdamper/
VSDstogetback“oncurve”.16. TheBMUthenreturnstothereleasetomodulatestate
withonlythenewfuelfiring.
Afuelselectorswitchwithacenter“Dual”positionallowsanoperatortomanuallyextendthedualfuelfiringperioduptoamaximumof90seconds(fieldadjustable).
Lowfirefueltransferisenabledbyparameterselection,andisprotectedbyan“engineer”levelpassword.
Tandem Oil/Gas Valve Servo Option For retrofitapplications, theBurnerMateUniversalallowsreplacementofthejackshaftactuatoronagasandoilfiredburnerwithasingleBMUservoandmaintainsthelinkagetotheoilandgasvalves.Theairdamperistakenoffthelinkageanddrivenbyasecondservoforparallelpositioningcontrolofbothfuels.AZPprobecanbeaddedtothesystemforparallelpositioningwithoxygentrimcontrol.Thisfeaturesreducesthenumberofservosrequiredforagas/oilburnerretrofit,andspeedsinstallation.
Separatecurvesareprovidedforstandby,purge,andignitionpositionsforoilandgas.TheBMUpositionsthegas/oilvalve(jackshaft)actuatorbasedontheBMSfuelselectionandthecorrespondingfuel’scurvedata.
203.743.6741 • 203.798.7313www.preferred-mfg.com
Instruments & Controls
Catalog 25
Instruments &
Controls
167
BURNERMATE UNIVERSAL BOILER CONTROLLEROrderingInformation
BMU Chassis SelectionThereareseveralBMUchassistochoosefromdependingonthefunctionalityrequiredinthecontrolsystemandthemountingofthe(required)LCDkeypad.The“basic”chassissupportsalltheflamesafeguard,combustioncontrol,andotherboilercontrolfunctionsoftheBMU.
The“expanded”chassissupportsalloftheabovefunctionsplusdraft,feedwatercontrol,atomizingsteam/airpressurecontrol,FGRwindboxoxygencontrol,aswellasflowmetersignal display and totalizing. Physically, the expandedchassiscontainsanextraanalogI/Oboardmountedwithinthechassishousing.
Toenableoxygenmonitoringoroxygentrim,the“Z”designationinthefifthdigitofthepartnumbermustbespecified.The“Z”optionandBMUchassisdonotneedtobepurchasedatthesametime,thisfeaturecanbefield-activatedatalaterdate.TheZPprobeandconnectingcablearepurchasedseparately.
ThesixthdigitinthepartnumberspecifiesthemountingoftherequiredLCDkeypad.Inmostinstances,thekeypadwillbeshippedloosetobeflush-mountedonthedoorofanenclosure.Alternatively,itcanbemountedinthechassiscovereitherhorizontallyorverticallyforlandscapeorportraitchassisorientation,respectively.Thekeypadisrequiredwhetherornottheoptional10”OITcolortouchscreenisprovided.
BMU Chassis SpecificationsElectrical
InputVoltage: 120VAC(+/-15%)Frequency: 60Hz,singlephaseConsumption: 42VA
EnvironmentalOperatingTemperature: 32to140deg.FStorageTemperature: -20to150deg.FHumidity: 15to95%
noncondensingOrderingInformation
Chassis Description Catalog Number
“Basic”controllerchassissupportsuptoseven(7)independentservoactuators--3forfuel,1forair,1forFGRand2Auxiliaries.Alsotwo(2)4to20madcoutputsforFDfanVSD/orAuxiliary2curve(ifnotaservo)
“Expanded”controllerchassisisrequiredfordraftorfeedwatercontrol.Supportsuptoten(10)independentservoactuators--3fuel,1air,1FGR,1feedwaterflowcontrolvalve,1draftdamperandatomizingsteamflowcontrolvalve.Alsouptosix(6)4to20madcoutputsfor:firingrate,FD,IDfanVSDs,Auxiliary2valveordamper,adraftdamperandafeedwatercontrolvalveorfeedwaterpumpVSD.
ControllerdoesnotsupportZPoxygenprobe
ControllersupportsZPoxygenprobe(fieldupgradable)
LCDkeypadisshippedloose(standard)
LCDkeypadisflush-mountedontheBMUcontrollerchassiscoverforlandscapechassismounting
LCDkeypadisflush-mountedontheBMUcontrollerchassiscoverforportraitchassismounting
BMU-______0
0
1
N
H
V
0
Z
203.743.6741 • 203.798.7313www.preferred-mfg.com
Instruments & Controls
Catalog 25
Inst
rum
ents
& C
ontro
ls
168
Description Catalog NumberControlPanel,24”Hx30”Wx10”D BMU-PANEL243010ControlPanel,30”Hx24”Wx10”D BMU-PANEL302410OITControlPanel,24”Hx30”Wx10”D BMU-PANEL243010-OITOITControlPanel,30”Hx24”Wx10”D BMU-PANEL302410-OITCustomDesignedEnclosure Consult Factory
BMU Standard Enclosure OptionsFourstandardenclosureoptionsareofferedfortheBMU.ThestandardenclosuresareNEMA12,hingedontheleft,includetwolockingmechanisms,andfeaturethefollowingcomponents,mountedandwired:
• LCDkeypad,burneroff-onselectorswitch,fuelselectorswitch,pilotlights,andanemergencystoppushbuttonmountedontheenclosuredoor.
• Abeaconandalarmhornaremountedandwiredtotheenclosureshell.
• BMUchassis,circuitbreaker,fuses,and24VDCpowersupply(ifOIToptionsarespecified)andanumberof120VACterminals.
• The panel-mounted devices are factory-wired asshown.All other devices are field-wired directly totheBMU terminals.Standard drawings showing thepanelarrangementand the internalwiringschematicarepresentedintheBurnerMateUniversalInstructionManual.
AdditionalDINrailisprovidedtomountotherdevicesasrequired,inthefield.Customdesignedcabinetareavailable.Consultfactoryforoptions,leadtimes,andpricing.
BMU-PANEL-2430-OIT
Interior view of BMU-PANEL-2430-OIT standard enclosure
BURNERMATE UNIVERSAL BOILER CONTROLLEROrderingInformation
203.743.6741 • 203.798.7313www.preferred-mfg.com
Instruments & Controls
Catalog 25
Instruments &
Controls
169
BMU Digital Servo ActuatorsBMUservosare available in output torques from3 ft-lbto720ft-lbs.Eachincludesanactuatorpositionerboard,and integral feedback potentiometer. The feedbackpotentiometer is used to prove servo position therebyeliminatingtheneedforauxiliaryproofofpositionswitches.Servoscanbeusedforthefollowingcontrolfunctions:• Natural gas, fuel oil and/ or “other gas” flow control
valve(s)• FDfandamper• Auxiliaryfinalcontrolelement(secondFDfandamper,
atomizingsteam/airvalveor…)• FGR damper• PreferredInstrumentsLTAoxygentrimactuator• Jackshaftactuator• Boileroutlet(stack)damper• Feedwatercontrolvalve• Auxiliaryservoforairsleeve,secondgasFCV,etc.
Forthelarger“UM”Actuatorsafloorstandisincludedasastandard.Damper/actuatorinterconnectinglinkagerod,linkagerodendsanddrivearmsmustalsobepurchased.
BURNERMATE UNIVERSAL BOILER CONTROLLEROrderingInformation
BMU Chassis SpecificationsElectrical
Motor: 120VAC(+/-15%),60Hz,singlephase
BMU-SM <0.2ABMU-UM <2ABMU-UM-720 3.4APositioner 24VDC,23mA
Servo PerformanceSpeed: 25sec/90°Rotation: 15°to180°(SM)
0°to90°(UM)DutyCycle: 100%Accuracy: +/-0.1°(SM)
+/-0.4°(UM)
EnvironmentalNEMARating:BMU-SM NEMA12BMU-UM NEMA4OperatingTemperature 32°to140°F
MechanicalBMU-SM-3 4”Wx5.8”Hx5.5”D
8mm“D”shaftBMU-SM-15 5”Wx5.8”Hx5.5”D
12mm“D”shaftBMU-SM-37 5”Wx6.7”Hx5.5”D
12mm“D”shaft
ConsultfactoryforBMU-UMdimensions
“SM” Model DescriptionCatalog Number
ServoActuator,3ft-lb.Torque(ShaftExtensionrequired)
BMU-SM-03
Asabovew/15ft-lb.Torque(ShaftExtensionrequired)
BMU-SM-15
Asabovew/37ft-lb.Torque(ShaftExtensionrequired)
BMU-SM-37
ElectricalQuickDisconnectOption BMU-SM-xx-QD
“UM”ModelDescriptionCatalogNumber
RotaryActuator, 72 ft-lb. torque. In-cludesfloorstand,positionerboardandinterconnectingcable.
BMU-UM-072-FS
Asabovew/140ft-lb.torque BMU-UM-140-FSAsabovew/280ft-lb.torque BMU-UM-280-FSAsabovew/420ft-lb.torque BMU-UM-430-FSAsabovew/720ft-lb.torque BMU-UM-720-FSElectricalQuickDisconnectOption BMU-SM-xx-QD
ModelDescriptionCatalogNumber**
BMUCommQuickDisconnectCable COMM-CABLE-ASSEMBLY-xx**
BMUPowerQuickDisconnectCable PWR-CABLE-ASSEMBLY-xx**
BMUQuickConnectTerminationBox BMU-JBOX
BMU“HomeRun”Cable BMU-CABLE-xx**
Servomountingneedstobeassolidaspossibletominimizehysteresisandensureconsistentburnersettings.
**Specifycablelengthinfeet(3,6,or12ft)
203.743.6741 • 203.798.7313www.preferred-mfg.com
Instruments & Controls
Catalog 25
Inst
rum
ents
& C
ontro
ls
170
BURNERMATE UNIVERSAL BOILER CONTROLLEROrderingInformation
StandardValveMountingBracket/CouplingPartNumbersValveManufacturer&
ModelValveSize ServoModel BracketModel CouplingModel
HoneywellV51EGasButter f ly Valves/5PSIGrating
1-1/2” BMU-SM-15 Factory Factory2” BMU-SM-15 “ “
2-1/2” BMU-SM-15 26189 B-201543” BMU-SM-15 C-30009 B-201544” BMU-SM-15 C-30009 B-20154
Hauck BVA Gas &AirButterflyValves/5PSIGrating
1-1/2” BMU-SM-15 Factory Factory2” BMU-SM-15 “ “
2-1/2” BMU-SM-15 “ “3” BMU-SM-15 “ “
EclipseBV-AFullPortGas ButterflyValves(360 deg. rotation)/5PSIGrating
3/4” BMU-SM-15 Factory Factory1” BMU-SM-15 “ “
1-1/4” BMU-SM-15 Factory Factory1-1/2” BMU-SM-15 “ “2” BMU-SM-15 “ “
2-1/2” BMU-SM-15 “ “3” BMU-SM-15 “ “
M i l w a u k e e B BSeriesGas ButterflyVa lves /150 PSIGrating
3/4” BMU-SM-37 26178 (1) 26173-1B(1) 26179
(2) 5636-008A-101” BMU-SM-37 26178 (1) 26173-1B
(1) 26179(2) 5636-008A-10
1-1/4” BMU-SM-37 26178 (1) 26173-1B(1) 26179
(2) 5636-008A-101-1/2” BMU-SM-37 26178 (1) 26173-1B
(1) 26179(2) 5636-008A-10
2” BMU-SM-37 26178 (1) 26173-1B(1) 26179
(2) 5636-008A-10
203.743.6741 • 203.798.7313www.preferred-mfg.com
Instruments & Controls
Catalog 25
Instruments &
Controls
171
BURNERMATE UNIVERSAL BOILER CONTROLLEROrderingInformation
StandardValveMountingBracket/CouplingPartNumbers(continued)
Milwaukee “HP1L”&“HP1W” Series GasButterfly Valves/150PSIGrating
2-1/2” BMU-SM-37 Factory Factory
3” BMU-SM-37 20150 20149-1
4” BMU-SM-37 20150 20149-1
HauckMOV&MCOVOilValves/300PSIGrating
3/8” BMU-SM-15 Factory Factory
1/2” BMU-SM-15 26177 26180-1
Wo r c e s t e r C P TCharacterized SeatBallValves/300PSIGrating (gas,water, orsteam)
1/2” BMU-SM-15 Factory Factory
3/4” BMU-SM-15 Factory Factory
1” BMU-SM-37 26187 26186
1-1/2” BMU-SM-37 20136 20140
FlowTekSeries 8000Characterized SeatBallValves.300PSIGrating (gas,water, orsteam)
1/2” BMU-SM-15 20135 (2) 26173(1) 20152
(2) 5636-008-103/4” BMU-SM-15 20135 20152
1” BMU-SM-15 20136 20138
1-1/4” BMU-SM-37 20136 20138
1-1/2” BMU-SM-37 20143 (2) 26173(1) 20152
(2) 5636-008-102” BMU-SM-72 20143 20146
F l o w Te k S e r i e s“ F 1 5 ” & “ RF 1 5 ”Characterized SeatBallValves.150PSIGrating (gas,water, orsteam)
2” BMU-SM-72 20143 20146
2-1/2” BMU-SM-72 20144 B-20009
3” BMU-SM-140 20144 20163
4” BMU-SM-140 20167 B-20016
BMU-UM-72-FS Servo with Integral Floor Stand
203.743.6741 • 203.798.7313www.preferred-mfg.com
Instruments & Controls
Catalog 25
Inst
rum
ents
& C
ontro
ls
172
BURNERMATE UNIVERSAL BOILER CONTROLLEROrderingInformation
ZP Zirconium Oxide In-situ Oxygen Probe
ModelDescriptionCatalog Number
In-SituDetector&ProbeAssembly20” ZP-20
In-SituDetector&ProbeAssembly30” ZP-30
In-SituDetector&ProbeAssembly45” ZP-45
In-SituDetector&ProbeAssembly65” ZP-65
In-SituDetector&ProbeAssembly90” ZP-90
ZP Probe Connecting Cable – SevenWire.Specifylengthrequired(Maximumis500feet)
190130
ZPProbeMountingKit,Includes:(1) 3”125#Castironthreadedflange(1) 3”Pipe,half-coupling,threaded(1) 3”x8”longpipenipple,threaded(8) Hexnut,5/8-11(8) Washer,5/8(2) 1/8”Ballvalve(brass)(1) 3”Gasket(50) Footcoppertubing,¼”OD(8) Hexheadscrew,5/8-11x2½(2) Straightfitting(brass)
190680
ZP Oxygen Analyzer ProbeTheBMUusesthesameZPprobeastheBurnerMateTS,PCC-III,andUtilitySaver.TheZPcontroller/amplifierisbuiltintotheBMUchassis.
ZPprobesshouldbefieldcalibratedwithtestgasesevery6-12months. However, a new probe includes factorycalibrationparametersthatcanbeenteredintotheBMULCDkeypad.Thiseliminatestheneedtohavecalibrationgasduringtheinitialstart-up.
TheBMUallowsforstackoxygenindication,andoxygentrimdependingontheparameterselectionsmadeduringcommissioning.Whenastacktemperaturethermocoupleisinstalled,theBMUcalculatescombustionefficiencyforNo.2oil,No.6oil,ornaturalgas.
203.743.6741 • 203.798.7313www.preferred-mfg.com
Instruments & Controls
Catalog 25
Instruments &
Controls
173
BURNERMATE UNIVERSAL BOILER CONTROLLEROrderingInformation
BurnerMate Universal OIT Touch ScreenAll of the control functionsof theBurnerMateUniversalcan be accessed through the LCD key pad.TheBMU-OIT-10colortouchscreendisplayisavailableforenhancedgraphicsandcommunications.Supportedcommunicationprotocolsinclude:
• 10/100 Base Ethernet, Modbus TCP/IP, ModbusRTU,SCADA/BASconnection,BacNet IP, andBMUconnection
• OneRS-485port
Over 75 pre-programmedgraphics pages are included.Boiler overview screens are field-selectable to fit theapplication. Typical Boiler Overview Screen
Touch Screen Specifications
Electrical InputVoltage: 24VDC,1.4A
Monitor PerformanceSize: 10.4”Colors: 256VGAResolution: 640x480pixels
EnvironmentalNEMARating: NEMA4X(flush-mount)
Fuel Combustion Curve Setup Screen
Trending screens help fine-tune control loopsController I/O screens help troubleshoot problems
Description Catalog Number
10.4”OperatorInterfaceTerminalColorTouchScreenDisplaywithBMUoperationandcommissioningdisplays. BMU-OIT10
OITTerminalWiringAdapter 190777
120VAC/24VDC/2.5ADINrailpowersupply 92443
203.743.6741 • 203.798.7313www.preferred-mfg.com
Instruments & Controls
Catalog 25
Inst
rum
ents
& C
ontro
ls
174
BURNERMATE UNIVERSAL BOILER CONTROLLEROrderingInformation
BMU Flame ScannersTheBMUcanacceptoneortwoflamescanners.Theyareavailableinultraviolet,infrared,andultravioletself-checkingversions.
Unitized DesignTheBMUscanners,likemostmodernflamescanners,areunified.Thismeanstheflamedetectorandamplifiercircuitryarecombinedandhousedinthescanner.Thiseliminatestheneedforaseparateenclosure-mountedamplifier.Whethertheflamedetectorcontainsanultraviolet,infrared,orself-checkingultravioletdetector,theoutputstotheBMUarethesame--acontactclosurethatprovesflameisdetected,anda4-20mAsignalproportionaltotheflamesignal.IntheBMU,the4-20mAsignalisusedforflameindicationonly.
Advanced DiagnosticsOn-boarddiagnostics in theflamescanners, andbuilt into theBMU,make trouble-shootingof a flamescanningproblemeasy.AllBMUscannerscontaintwoLEDsonthefrontofthescanner.The“flamestatus”(left)LEDblinksatarateproportionaltotheflamesignalstrength.The“flamerelay”LEDilluminatescontinuouslywhentheflamesignalissufficienttoclosetheflameprovenrelay.
Inaddition to the twoLEDs, thescannersoutputa4-20mAsignaltotheBMU,proportionaltotheflamesignal.TheflamesignalstrengthcanbeviewedfromseveralscreensontheBMU.
BMU Scanners Feature:• Digitalflamesignalprocessingformorereliableflame
detection.• Highqualityfusedsilicaquartzlens.• MachinedalloyhousingwithNEMA4seals.• Militaryspecificationcomponentsusedinessentialintegratedcircuitsandconnectors.• Military-stylequickdisconnectfittingsallowfor
scannerreplacementwithoutrewiring.• Redundantflamerelaycontactsarefullysupervised.
UV Self-Check Scanners Feature:• Detectorandsignalprocessorsautomaticallycheckedevery10seconds.• Newopticalinterruptertechnologywith100millioncyclelifespan.(That’sover30years!)
• Rugged1”NPTFscannermounting.
Ultra-Violet Flame ScannersTheBMU-UVandBMU-UVSCflamescannersuseaUVdetectortubeasasensingelement.IncomingUVradiationfroma flame is focusedandamplifiedoptically.TheUVradiationenergizes thedetector tube,whichworkson theGeiger-Mueller principle.TheBMU-UVSCself-checkingdetectorandpulseprocessorarecontinuouslysupervised
BMU-UVSC and IR Flame Scanners
bymeansoftheuniqueopticalinterruptermechanismthatbreakstheUVlightpathbetweenlensanddetectortube.Thescanner’spulseprocessorisfail-safebynature,sinceanyfailuremoderesultsinatotallossofsignal.
Infrared Frequency-Based ScannersTheBMU-IRflamescannerusesa lead sulfide sensingelement.Thepresenceofaflame isdetectedbysensingthe variations of flame luminosity.This technique aidsdiscriminationof flame radiatedenergyandbackgroundradiation fromheated furnaceparts.Consult factory foravailabilityofIRscanners.
Recommended Scanner
Application UVSC IRGasOnlyFired XNo.2Oil,AirAtomized XNo.2Oil,SteamAtomized XNo.2Oil,PressureAtomized XNo.6Oil,SteamAtomized XNo.6Oil,RotaryCup XDigesterorLandfillGas XRefineryGas X
203.743.6741 • 203.798.7313www.preferred-mfg.com
Instruments & Controls
Catalog 25
Instruments &
Controls
175
BURNERMATE UNIVERSAL BOILER CONTROLLEROrderingInformation
ScannerApplicationConsult the burnermanufacturer to determine themosteffectiveflamescanner type for yourburnerapplication.However, typicallyultraviolet(UV)scannersareusedforgasflamesandinfrared(IR)scannersareusedforheavyoil,orsteam-atomizedlightoilflames.Preferred’sUVflamescannersaretraditionalUVtubescanners.TheIRscannerusesaleadsulfidedetector.
BecauseUVtubescannerscanfailshowingflame(runawayscannercondition)aself-checkingUVscannershouldbeusedforapplicationswheretheburnerdoesnottypicallycycleoffatleastonceineacheighthourperiod.IRscannersdonottypicallyfailshowingflame.
BMU-UVSC-10CUltraviolet
Self-CheckScanner
BMU-UV-10CUltraviolet
NonSelf-CheckScanner
BMU-IR-10CInfrared
NonSelf-CheckScannerMechanical:OverallLengthDiameterHousingConstructionFinishSightTubeConnectionPurgeAirConnection
7”(177.8mm)3.25”(82.5mm)Machined5052Alum.ClearAnodized1”NPT(female)3/8”NPT(female)
3”(76.2mm)2.25”(57.15mm)Machined5052Alum.ClearAnodized1/2”NPT(female)3/8”NPT(female)
3”(76.2mm)2.25”(57.15mm)Machined5052Alum.ClearAnodized1/2”NPT(female)3/8”NPT(female)
Electrical:SupplyVoltageRequiredPowerContact OutputCurrent OutputCurrent Output specs(2wirecurrentloop)
120VOLT50/60HZ2VA120VAC,1amp4to20madcSpanerror–0.5%Non-linearity–0.03%Loop supply voltage 7.5to36Volts
120VOLT50/60HZ2VA120VAC,1amp4to20madc
120VOLT50/60HZ2VA120VAC,1amp4to20madc
Environmental:ClassTemperature
NEMA40to140deg.F.
NEMA40to140deg.F.
NEMA40to185deg.F.
Optical:Lens
FusedSilica FusedSilica FusedSilica
SpectralSensitivityWavelength(nanometers)
180–230(UV) 180–230(UV) 400–1050(IR)
BMU-IRinfraredscannerswillbeavailablesoon.Consultfactoryforavailability.
DescriptionCatalogNumber
Ultraviolet Self-CheckScanner; 10 ftcable & connector BMU-UVSC-10C
UltravioletNonSelf-CheckScanner;10ft cable & connector BMU-UV-10C
InfraredNonSelf-CheckScanner;10ftcable&connector.Consult factory foravailability.
BMU-IR-10C
ScannerCable(lengthsotherthan10’) 5000-02-xx
203.743.6741 • 203.798.7313www.preferred-mfg.com
Instruments & Controls
Catalog 25
Inst
rum
ents
& C
ontro
ls
176
BURNERMATE UNIVERSAL BOILER CONTROLLEROrderingInformation
BMU_EditIn the tradition of PCC-III_Edit and PWC_Edit, theBurnerMateUniversalisavailablewithBMU_Editsoftwarethat runs on yourWindows-basedPC and allows youto set the parameters of the BMU from your laptop.CommunicationbetweentheBMUandyourPCisdoneviaastandardUSBA/B(printer)cable.
Easy pull-downmenusand text boxes allowparameterselectionsinyourofficetobewrittenintotheBMUchassiseither before installationor during commissioning.Oncecommissioningiscomplete,BMU_Editallowsyoutoreadfrom the BMU chassis and save the latest parametersettingsandcurvedatainthePC.ThissettinginformationcanbeusedtosetupadditionalBMUsorusedasanarchiveiftheBMUconfigurationbecomescorrupted.
BMU_Edit includestoolsthatallowtheperformanceofaparameterchecktomakesureparametershaven’tbeensettoincompatiblevalues.ThesoftwarewillalsoconvertsettingdatafromoneBMUversiontoanother.Inaddition,BMU_Edit can compare two BMU configurations andmakea detailed list of the differencesbetween the twoconfigurations.Thisfeatureisimportantwhenmorethanonetechnicianmayworkonthesameboiler.
The compare function tracks any changes made to a BMU configuration for easy trouble-shooting.
The curve viewer function allows a technician to quickly view all the combustion related curves input in a BMU. This can be useful when diagnosing a problem. It can also be used to archive curve information quickly and easily. Parameter settings and fuel-air curves can be written back to the BMU, but the points must be verified before leaving commissioning mode.
ModelDescription
Catalog Number
BMU_EditSoftware BMU_Edit
203.743.6741 • 203.798.7313www.preferred-mfg.com
Instruments & Controls
Catalog 25
Instruments &
Controls
177
BURNERMATE UNIVERSAL BOILER CONTROLLEROrderingInformation
Digital Communication OptionsManyplantownersandengineersdesiretomonitorthestatusoftheboilerroomremotely.TheBMUhasModbusaddressesassignedforthestatusofmanydigitalandanaloginputsandoutputs.ThisdataisaccessiblebyModbususingtheRS485connectionontheBMUchassis.TheRS485connectioncan
beconvertedtoEthernetusingeithertheOITtouchscreenoranOIT-Bridge.Generally,anydatapointdisplayedonthetouchscreenhasaModbusaddressandcanbemonitoredremotelyviaModbus.APWC,PCC-III,orDCS-IIIloopcontrollercanbeusedtomakeanyotherpointsavailableviaModbus.
This is the most common digital communication scenario used with the BMU. The OIT touch screen is supplied for its graphics capability, and is also used to convert the RS485 bus to Ethernet. There are many terms for the control system the BMU typically interfaces with, including: Distributed Control System (DCS), Building Automation System, (BAS) Energy Management System (EMS) or Preferred Supervisory Control and Data Acquisition System (SCADA). Most of these systems can communicate via Modbus over Ethernet or have converters that can communicate via Modbus.
As an economical alternative to the OIT touch screen, Preferred offers the OIT-Bridge that provides a pre-configured communication interface between the Modbus RS485 BMU chassis and Modbus over Ethernet. The OIT-Bridge is pre-configured to the Modbus addresses of the BMU. It offers the same communication capabilities as the OIT touch screen at a much lower price.
A l l o f the BMU chass is opt ions communicate using Modbus protocol on an RS485 bus without any additional equipment required.
RS485 ETHERNETor BacNet IP
BMUCHASSIS
OITTOUCH SCREEN
PLANTDCS, BAS,
EMS, SCADA, ETC.
RS485 ETHERNETor BacNet IP
BMUCHASSIS
OITBRIDGE
PLANTDCS, BAS,
EMS, SCADA, ETC.
RS485Modbus
BMUCHASSIS
PLANTDCS, BAS,
EMS, SCADA, ETC.
203.743.6741 • 203.798.7313www.preferred-mfg.com
Instruments & Controls
Catalog 25
Inst
rum
ents
& C
ontro
ls
178
BURNERMATE UNIVERSAL BOILER CONTROLLEROrderingInformation
This is the ultimate in-plant monitoring capability in an entirely pre-engineered package. Up to three boilers can be controlled and monitored using off-the-shelf BMU boiler masters, a Chief Dispatcher plant master, and the CommStation communication interface that provides a single Ethernet connection to the plant. Because the components of this system are completely pre-engineered, this is a very economic package that will typically be competing with a custom engineered PLC-based system.
Description
CatalogNumber
Optionalwebbrowserremotecommunicationmodulewithpre-configuredBMUoperationandcommissiondisplaysvisiblefromastandardwebbrowser.OneEthernet,oneRS-485,andtwoRS-232communicationportsarebuilt-in.
BMU-OIT-BRIDGE
Historicalmemory2GBcompactflashcardforextendedhistoricalmemorycollectionandexporttoMSExcel 90283
Communicationexpansioncard.ProvidesoneadditionalRS-232andRS-485port. 90284CommStationthreeboilerBMU/ChiefDispatcherEthernetinterface 190781–RS-485120VAC/24VDC/2.5ADINrail-mountedpowersupply 92243
MULTIPLE BMUs IN ONE PLANT SINGLE ETHERNET CONNECTION TO
PLANT
RS485
RS485
RS485 ONE CHIEF DISPATCHER
PREFERREDCOMMSTATION190781-RS-485
ETHERNET
RS485
203.743.6741 • 203.798.7313www.preferred-mfg.com
Instruments & Controls
Catalog 25
Instruments &
Controls
179
BURNERMATE UNIVERSAL BOILER CONTROLLERSuggestedSpecifications
1. Quality AssuranceTheboilercontrolsystemshallbemanufacturedandsupportedintheUnitedStatesbyPreferredInstruments.Theburnerfuel-air-FGR ratio control systemand the burner flame safeguardsystemshallbemanufacturedand labelled inaccordancewithU.L.372,U.L.1998,andCSAC22.2#199.SimplysupplyingULrecognizedindividualcomponentsisnotsufficient.Theassembledcontrolcabinetasawholemustbeinspectedforproperwiringmethods, fusing, etc., andmust be labeled as conforming toUL508AandCSAC22.1#14.InspectionandlabelingshallbesupervisedanOSHAapprovedNationallyRecognizedTestLab(NRTL).ThesystemshallcomplywithNFPA85“RequirementforIndependence,” the flamesafeguard systemshall beprovidedwith independent hardware shall bephysically separated fromthecombustioncontrollogic.2. Parallel Positioning Combustion ControlAparallelpositioningcombustioncontrolsystemwithoxygentrimand(optional)VSDcontrolshallbeprovidedforeachboiler.Eachsystemshallbedesignedtoprovidecontinuousboileroperationwithinboilerdesignlimitswithahighlevelofsafetyandenergyefficiency. As required the system shall provide continuousmonitoringandcontrolofsteampressure(orwatertemperature),waterlevel,combustionairandfuelratio&fluegasrecirculation.Thesystemshallbefullyintegratedtotheburnermanagementsystemtoprovidefullyautomatic,safeandreliablestartupandshutdown.Positionpacingshallbeused toensureup toeightservoswillbecontinuallymonitoredandheld“oncurve”duringboilerloadchanges.3. Oxygen Trim SystemProvideaboilerbreechingmountedin-situ,zirconiumoxideoxygenanalyzer for eachboiler.Extractive typeoxygenanalyzersarenotacceptableforcombustioncontrol.Theprobeshallbeofasuitablelengthtosensetheoxygenlevelinthemiddlethirdofthebreeching.Allwettedpartsshallbestainlesssteel.Theoxygenanalyzershall:• Includecontinuousself-diagnosticswithdiagnosticcodesfor
atleast10commonfaults.• Automaticallysendthe trimcontrol to the ‘null’positionand
triggerthealarmdrycontactsintheeventofanoxygenanalyzerfault.
• Thedetectorshallbefieldreplaceablewithoutremovingtheprobefromthestackandshallnotrequirespecialtools.
• Theanalyzershallautomaticallyperformperiodicdetectorcellimpedanceteststobeusedbytheoperatorasanindicationofcalibrationshift.
• Analyzercalibrationshallbepushbuttonsemi-automatic(notrim pots) with English language prompts and diagnosticmessages.Analyzeroutputshallbefieldselectableas0-10%or0-21%withoutfieldre-calibration.
4. Flame Safeguard System (FSG)Integral to the control system furnished shall be a BurnerManagementSystem (BMS) /FlameSafeguardSystem (FSG)controller.Thesystemshallbedesignedtoensurethesafestart-up, on-line operation, and shutdown of fuel firing equipment.Burnermanagement system components shall be located inthe combustion control cabinet and shall be fully integratedforautomaticsequencingof lightoffandshutdown.ForsafetytheBMSmicroprocessorandBMSVDshallbeonaphysicallyseparatecircuitboard.Microprocessor-basedFSGshallprovide:safetyinterlocks,flamemonitoringprotection, and timed sequences.Sequences shallincludeforceddraftfanstartandstop,furnacepurge,burnerlightoffandshutdownandpost-purge.TheFSGshallbecapableoffiringuptothreefuels(twogasfuels,oneoilfuel),onefuelatatime.Fuelchangeovershallfromoiltogas,orgastooilfiringshallbeaccomplished“onthefly”atlowfirewithoutboilershutdownperNFPA.A panel front-mounted English language, four line, twentycharacter LCDmessage display shall be provided to displayflamesignal strength, startup and shutdown sequence status,alarm,systemdiagnostic,first-outmessagesandburnerhistoricalinformation.Historicalinformationshallincludethestatusofalllimitsandservosforthelasttenlockouts.To ensure boiler lowwater cutouts areworking correctly, thecontrollershallbecapableofperformingadailyautomaticwatercolumnblow-downtest.Theusershallselectthetimeofdayanddurationofthewatercolumnblow-downtest.Thecontrollershallensure the lowwater cutoff switches are functioning correctly,andalarmtheoperatororlockouttheboilerifitdetectsaswitchmalfunction.To prevent nuisance trips, the flame safeguard system shallaccommodate two flame scannerswith one required to proveflame.Thecontrollershallprovide120VACor24VDCscannerpower,andaccept twoanalog inputs indicatingflamestrength.Flamesafeguardsystemshallincludeoilgunpostpurgeforoilfiring.Assuredlowfirecutoffshallbeprovided.Foradditionalnuisancetripprotection,fieldadjustabletimedelaysshallbeprovidedforF.D.fanstart,freshairdamper,minimumairflow,lowdraftcutout,andfuelpressurelimits.Fivefieldselectableauxiliaryrelaysshallbeincludedforcommonalarm,auxiliaryfanstart,blow-down,flameon,fuelvalveopen,hotwaterpumporvalve.Toprotectagainstdryfiring,anoptionshallbeavailableforhighfluegastemperaturelockout.Toensureairswitchesarefunctioning,aminimumairflowpressureswitchandpurgeairflowpressureswitchsafestartcheckshallbeincluded.5. Feedwater ControlProvideaboilerwaterlevelcontrollercapableofsingle-,two-,orthree-elementfeedwatercontrolwiththeabilitytoautomaticallyswitchbetweencontrolstrategiesdependentonsystemdemands.6. Draft ControlThecontrollershallprovidetwo-elementdraftcontrolutilizingaPreferredInstrumentsJC-22XMTRdrafttransmitter.Burnerfiringrateshallbeusedasafeedforwardforimprovedresponsetoloadchanges.Thecontrolshallprovidebothautomaticandmanualdampercontrol.Alladjustmentsshallbemadefromthefrontpaneldisplayinengineeringunits.
203.743.6741 • 203.798.7313www.preferred-mfg.com
Instruments & Controls
Catalog 25
Inst
rum
ents
& C
ontro
ls
180
BURNERMATE UNIVERSAL BOILER CONTROLLERSuggestedSpecifications
7. Flue Gas Recirculation Valve ControlThecontrollershallhaveacharacterizablesetpointcurveoutputsignal for the fan to vary or damper its speed.All the logicrequired to automatically signal pre-purge, postpurge, light-off,andburnermodulatecyclesshallbeprovidedwithinthecontroller.Alternatively,thecontrolwillregulateFGRaccordingtoapresetwindboxoxygensetpointcurve.8. Windbox Oxygen FGR ControlThecontrollershallacceptananalog input forburnerwindboxoxygentobeusedasameasureoffluegasrecirculationrate.During commissioning, awindboxoxygen vs. firing rate curveshallbeestablished.Thecontrollershallmodulatethefluegasrecirculationvalve (or fluegasblowermotorVSD) tomaintainwindboxoxygenonthepre-establishedcurvedespitechangesinambientconditions.9. Atomizing Media Pressure ControlThecontrollershallacceptaninputforatomizingsteampressureoratomizingsteam/oildifferentialpressure.Duringcommissioning,anatomizingsteampressure(oratomizingsteam/oildifferentialpressure)curveshallbeestablished.Thecontrollerwillmodulateanatomizingsteamflowcontrolvalvetokeeptheatomizingsteampressureoncurveatallfiringrates.10. Additional Control Requirements:• Minimumnumberoff(x)Curvestobeprovidedperservo:6• Minimumnumberofpointsperf(x)Curvetobeprovided:11• ColdFGR lowfirecutbackshallbeprovidedwhenFGR is
utilizedforNOxreduction.• SeparatecurvesshallbeprovidedforFDfanfullspeedbypass
ofVSDincaseofVSDfailure.• Controllershall include thecapabilityof receivingaremote
firingrateinputandremotesetpointinput.• Controller shall include dual outdoor reset setpoint curves
(normalandsetback)• Controllershallincludewarmstandbystart/stopcycle.• Controllershallincludelowfirehold,andcoldstartwarmup
ramping.• Allexternalorauxiliarypowersuppliesnecessaryforelectronic
transmitters(orfinalcontrolelement)shallbeincluded.• BoilercontrolsoftwareshallbeU.L.372/U.L.1998recognized
and inaccessible toprevent tampering.Unitcommissioningshallbebyparameterselection,notrequiringladderlogicorblockwareprogramming.
• Thecontrollershallacceptstandard4-20mA,1-5VDC,orthermistorinputsforanaloginputs.Nospecialsensorsshallberequired.
• Controllershallreceiveanddisplayinputsforfuelflow,airflow,andsteamflow.Controllershallbecapableoffutureupgradestofullymeteredcombustioncontrol.
11. OIT Color Touch ScreenProvideasanoptionaten(10)inchOperatorInterfaceTerminal(OIT) designed to provide local operation, graphic display ofinformation, alarmmessage display, historical and real timetrending,remotecontroltuning,x/yplotsoffuel-aircurvedatafor intuitivecommissioning,Ethernetconnectivityandstandardinternetbrowserremotecommunication.TheOITshallcontainaminimum of 75 graphic pages and be networked to theboilercontrolandburnermanagementsystems.TheOITshallprovidegraphicpagesallowing step-by-step commissioningofthecontrollerparametersusingEnglish languagepromptsandselections.The systemshall bean industrial hardenedoperator interfaceterminal.The terminal shall be enabledby thewebandallowremotemonitoringviaastandardinternetbrowserandsupportModbusTCP/IPMaster,TCP/IPSlave,RS-485ModbusMaster,andEthernetcommunications.12. High Torque Servo Features:• Easypushbuttonset-up,notrequiringtheadjustmentofinternal
orexternalpotentiometers.• Servozero,span,anddirectionoftravelshallbeaccomplished
bypush-buttonconfiguration.• Totallyenclosed,dusttight,andsplash-proofcovers.• Provideaseparatedirectactingdigitalservoactuatorsforthe
fuelgasandfueloil.• Electrically isolated shaft position feedback potentiometer,
integralbrake,90°rotationin25seconds.• Theactuatorshallbecapableofbeingstopped,started,or
instantlyreversedwithoutlossofpoweroroverloading.• Servoactuatorpositioningaccuracy:0.1degrees.Servofull
strokesafestartcheckshallbeprovided.• For high torque applications such aswatertube boiler air
dampers,servotorqueshallberatedminimum70ft-lbswith0.4degreeaccuracy.
• No servo feedback adjustments shall be required withpushbuttonzerosetup.Adjustabletravellimitswitchesshallbeintegral,withre-adjustmentnotrequiringnewfuelairratiocurvere-entry.
• Servos shall be cycledduringeach light-off cycle, and thefeedbackfromeachservomonitoredtoensuresafeactuatoroperation.
• Servos shall bePreferred Instruments,modelBMU-SMorBMU-UM(hightorque).