Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant Consulting Services, Inc. 973-983-0813 [email protected] www.outsideplantconsulting.com 2009 AASHTO Right of Way & Utili Subcommittee Conference Oklahoma City April 20, 2009

Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Embed Size (px)

Citation preview

Page 1: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Buried Duct Network for Upgrading Utility Cables –

Recent Field Trials

PSC

Outside Plant Consulting Services, Inc.

Dr. Lawrence M. SlavinOutside Plant Consulting Services, [email protected]

2009 AASHTO Right of Way & UtilitiesSubcommittee ConferenceOklahoma CityApril 20, 2009

Page 2: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Sponsor

Funding:US Department of Transportation

Technical Oversight:FHWA Turner-Fairbank Highway Research Center

Page 3: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Objectives & Goals

Short-Term:Develop improved method of buried

construction for utility cables (telecommunications, CATV, power)

Long-Term:• Avoid damage to roads and

transportation systems• Minimize proliferation of utility

poles

Page 4: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Background

Page 5: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Cable Construction Methods

Overhead Utility Poles

Below ground• Underground conduit• Direct-Buried

PS

C

Page 6: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

cables placed directly in trench PS

C

Page 7: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Direct-Buried Philosophy

• Cables directly placed in trench

• Robust cable designs•electrically insulated (power, ...)•waterproof•mechanical protection (armor, …)

• Sized for “ultimate” future needs

PS

C

Page 8: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Direct-Buried Philosophy

• Typically, no convenient means of cable addition, replacement or

upgrade*

* Sometimes a duct is provided in trench by a utility, but is not a uniform practice across all utilities and regions, or necessarily done in the most cost-effective manner

Page 9: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Direct-Buried Philosophy• Does it usually work (successful) ?

• Often (in use for several decades)

• Does it always work ?

• No•new technology•exhausted capacity•cable degradation or damage•new service providers

PS

C

Page 10: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Direct-Buried Philosophy

• Cable additions require aggressive construction (open-cut trenching, directional drilling, …)

THUS

• Possible damage to roads, property, utilities, ...

• Safety hazards PS

C

Page 11: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Buried Duct Network (BDN)

Page 12: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Benefits

* e.g., US DOT - Office of Pipeline Safety

For buried facilities (requiring future upgrades, maintenance, …), avoids

• Road damage (road cuts, ...)• Corresponding traffic delays• Damage to buried lines (gas*, electric,…)• Damage to Intelligent Transportation

System (cables, …)

PS

C

Page 13: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Benefits

* A Policy for Accommodating Utilities Within Highway Right-of-Way, A Policy on the Accommodation of Utilities Within Freeway Right-of- Way, Guidance on Sharing Freeway and Highway Rights-of-Way for

Telecommunications, Highway/Utility Guide.

Consistent with AASHTO & FHWA Recommendations*

• Belowground lines• Access and Upgradability• Joint Usage of Infrastructure & Facilities

Page 14: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

BDN Concept/Design

PS

C

Hybrid system; combines

• Advantages of underground conduit (upgradability)

with

• Advantages of direct-buried construction (low cost)

Page 15: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

BDN Concept/Design

Specify standard, optimized, cost-effective Buried Duct Network:

• Initially installed distribution cables are selected, sized and directly-buried in joint-use trench, following present recommended (cost-effective) practices

• Two large diameter (e.g., 4-in.) main distribution ducts, initially vacant, accessed at common handholes, also placed as an overlay in the same joint-use trench

Page 16: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

BDN Strategy*• Add minimum duct network for

insurance for atypical (but not uncommon) cases when need upgrade

• Consistent with shared/joint-usage philosophy

• Space-efficient

• Cost-effective* Does not apply to applications that warrant full-scale underground

conduit systems (e.g., banks of conduits, manholes, …)

PS

C

Page 17: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

BDN Detail

power

CATV

tele

three individual service ducts

common (joint) service trench

common (joint) main trench along ROW

two vacant large (e.g., 4-in.) ducts through handhole

initial distribution cables(direct-buried, w/o duct)

handhole

initial primary power distribution cables(direct-buried, w/o duct)

Note: for thoroughfare application, possibly omit service lines

utility terminals/equipment/hardware(power, telephony, CATV)

patent pending

Page 18: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

(Nominal 2 ft. wide x 3 ft. long x 36+ inches deep)

mouseholes(e.g., 4-in. duct)

flared sides(avoid uplift -- frost, duct, …)

bottomless

lid

6 knockouts(both sides)

Not to Scale

patent pending

Page 19: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Direct-Buried Initial Cables plus Vacant Main Ducts thru Handhole

initial distribution cables(direct buried, w/o duct)

two vacant main ducts (HDPE, PVC, …) (future distribution cables)handhole

express duct (alternative)

cut/sealed duct

same (joint) trench

e.g., communications (telephone, CATV)

e.g., power (primary and/or secondary)

patent pending

Page 20: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

• Main distribution ducts are initially vacant

BDN Concept/Design

• Future Use of main distribution ducts efficiently allocated, as necessary (telephone, CATV, power)

• Individual, smaller diameter, service wire ducts are routed from terminals to residence or small business, to provide protection for initial service wires, and facilitate future upgrade or replacement

PS

C

Page 21: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

BDN Concept/Design

• Handhole NOT intended for routine maintenance (no terminals, splices, ... ) -- avoids exposure of communications workers to high voltages

• Accessed only if and when the need arises for future addition of cable(s)

PS

C

Page 22: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Alternatives

Page 23: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

PS

C

Page 24: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

PS

C

Page 25: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

PS

C

Page 26: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Phase I (Feasibility) 6 Months

Page 27: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Phase II (R&D)

24 Months

Page 28: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Phase II Effort

Develop design, construction, maintenance, and management guidelines and practices

• ASCE Pipeline Division•“ASCE Manual of Practice for Belowground Pipeline Networks for Utility Cables”

•Anticipated availability Summer 2009

PS

C

Page 29: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Phase II Effort

Ensure availability of prototype hardware for future applications, field trials, ...

• Handholes (load ratings, ...)• Ducts, conduits• Security system (locks, …)• …..

PS

C

Page 30: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Handholes (TIER 15)

Polymer Concrete (Quazite®)

Page 31: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Handholes (“20K”)

HDPE(Pencell Plastics)

Page 32: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Phase II Effort

Arrange appropriate full-scale field trials• Permanent installation• e.g., 1 kft• Road, highway, residential, …

• Identify & address various issues• Leverage for future introduction into utility and transportation industry practices

PS

C

Page 33: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Phase II Effort

Completed or planned field trials•Arlington, Texas – November 2008

•Monroe, NC – March 2009

•Danvers, MA – June 2009•........

PS

C

Page 34: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Monroe, NCRoad Widening SR1223 (NCDOT)

• Moving Verizon and Time Warner Cable• Outer edge of ROW• Tier 15 handholes (NC DOT)• Open-cut trenching• Conventional PVC (adhesive joints)• 1 kft (<800 ft.)• Conduits (and innerduct) for future (and initial) cables

Page 35: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Monroe, NC

Thanks, Gus !

Page 36: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Not to Scale

Handhole Locations for Verizon BDN /Time Warner Installation (Monroe, NC)

390 ft. 330 ft.

2 Time Warner Cable innerducts(outside handholes)

two 4-in. conduits(e.g., Schedule 40 PVC)

All conduits plugged at all exposed ends

30” x 48” x 36-in deep handholes(Quazite PG3048)

36” width trench

increase trench width in vicinity of handholes

initial Verizon cables through one conduit

Verizon equipment/pedestal

Time Warner Cable mini-vault

Page 37: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Not to Scale

surface

36”

Trench Cross-Section for Verizon BDN /Time Warner Cable Installation (Monroe, NC)

two 4” (Verizon) conduits

two 2” (Time Warner Cable) innerducts,including tracer wire

fiber cable + 600 pr copper cable (+ vacant path ?)

fiber cable + pull rope

pull rope

36”+

Page 38: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Martin Luther King, Jr. Blvd (SR 1223)

Page 39: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Trenching & Conduit/Handholes

video

Page 40: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Installed BDN Conduit & Handholes

Page 41: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

video

Time Warner Cable Direct-Buried Innerduct

Page 42: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Installed Innerduct

Page 43: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Backfilling & Compacting

video

Page 44: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Backfilling & Compacting

Page 45: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Finishing

video

Page 46: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Finishing

Page 47: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Phase II Effort

Implementation issues• Ownership• Joint-usage agreements (compensation, …)

• Road and construction permits• ...

PS

C

Page 48: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

HOWYOUCANHELP

Page 49: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

How You Can Help (Permits, ...)

•Encourage (require ?) use of upgradable networks (BDN, other, ...)

•Stricter specifications

•Uniformity (across states, ...)

PS

C

Page 50: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

How You Can Help (Permits, ...)

PS

C

Suggestions• Existing related efforts ?

• Individual states ?• Nationally ?

• How to proceed ?• .......

Page 51: Buried Duct Network for Upgrading Utility Cables – Recent Field Trials P S C Outside Plant Consulting Services, Inc. Dr. Lawrence M. Slavin Outside Plant

Thank You !