1 3-WAY ISOLATION OF ANALOG SIGNALS UNIVERSAL CONVERSION MODULE - INPUTS AND OUTPUTS SELECTED VIA DIP SWITCH SETTINGS OVER 100 INPUT AND OUTPUT ANALOG CONVERSION COMBINATIONS CHOOSE LINEAR OR SQUARE ROOT EXTRACTION MODEL ALL RANGES ARE FACTORY PRECALIBRATED. CUSTOM FIELD CALIBRATION IS AVAILABLE FOR ALL RANGES WHILE MAINTAINING THE FACTORY CALIBRATION FOR FUTURE USE 11 to 36 VDC AND 24 VAC MODULE POWER GENERAL DESCRIPTION The IAMA – Universal Signal Conditioning Module Series can isolate and convert over 100 combinations of analog signal ranges. The IAMA3535 converts and transmits signals linearly proportional to the input, while the IAMA6262 transmits the scaled square root of the input signal. This allows the IAMA6262 to provide a signal that is linear to flow rate in applications utilizing a differential pressure transducer. DIP switch range selection eliminates the need to order and stock different modules for each input and output signal range, and allows quick and convenient setup for over 100 standard signal conversions. By utilizing the Field mode of calibration, the user can customize the input and output scaling for odd applications, including reversal of the output relative to the input. In addition to the conversion capabilities, the IAMA modules feature optically isolated Input/Output signal circuits and transformer isolated Power to Input, Power to Output circuits. The modules’ overall full scale accuracy typically exceed 0.05% depending upon range selection and scaling. The microprocessor based design provides ease of field scaling and the onboard E 2 PROM stores scaling values for future recall. Both models come factory precalibrated for all input and output ranges. Factory or custom field scaling can be selected by a simple mode switch change. The IAMA can be factory recalibrated in the field if desired. The modules’ environmental operating temperature range is -20°C to +65°C. DIN rail mounting saves time and panel space. The units are equipped with universal mounting feet for attachment to standard DIN style rails, including top hat profile rail according to EN50022 - 35x7.5 and 35 x 15 and G profile rail according to EN50035-G32. SAFETY SUMMARY All safety related regulations, local codes and instructions that appear in the manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. ORDERING INFORMATION MODEL NO. DESCRIPTION PART NUMBER IAMA Linear Universal Signal Conditioning Module IAMA3535 Square Root Universal Signal Conditioning Module IAMA6262 SPECIFICATIONS 1. POWER: 11 to 36 VDC, 3 W max. or 24 VAC, ±10%, 50/60 Hz, 4.8 VA max. 2. INPUT/OUTPUT RANGES: See Tables 2 and 3 3. ZERO/SPAN ADJUSTMENTS: Digital (DIP Switch Transition) 4. MAX INPUT SIGNAL: Current Input: 110 mA DC, 1.1 VDC Voltage Inputs: Terminal 7- 1 VDC +10% Terminal 8- 10 VDC +10% Terminal 9- 100 VDC +10% 5. INPUT RESISTANCE: Current: 10 Voltage: > 100 K 6. INPUT PROTECTION: Surge suppressor diodes 7. OUTPUT: Self-powered (Active) 8. MAX OUTPUT CURRENT: Current Output: 22 mA Voltage Output: 10 mA 9. LOAD RESISTANCE: Current Output: 600 Voltage Output: 1 K10. OUTPUT COMPLIANCE: Current: 4 to 20 mA, 0 to 20 mA: 12 V min (600 ) 0 to 1 mA: 10 V min (10 K) Voltage: 10 VDC across a min. 1 Kload (10 mA). Factory calibrated for loads of > 1 M. 11. ISOLATION LEVEL INPUT TO OUTPUT: 1.5 kV @ 50/60 Hz, 1 min 12. STEP RESPONSE: To within 99% of full scale: 300 msec 4.20 REF 1.08 3.12 (27.5) (106.7) (79.2) 10 9 8 7 5 4 3 OFF = 0 DIP SWITCH SETTINGS: 2 1 ON = 1 MC2279X ON 0 1 1 0 0-1V 0 0-100mA 0-50mA 0-20mA 4-20mA 0-10mA 0-5mA 0-2mA 0-1mA 0-10V 0-100V 0-50V 0-20V 0-5V 1-5V 0-2V 0 0 0 0 0 0 0 0 1 1 1 1 1 1 0 1 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 1 0 1 0 1 0 1 0 1 0 0 0 0 0 1 1 1 1 0 0 0 1 1 0 1 0 1 0 0 0 0 0 0 1 1 1 1 1 0 1 0 0 1 0 0-50mV 0-100mV 0-200mV 0-500mV 0-20mV 0-20mA 4-20mA INPUT 0-5V 0-10V 0-1mA OUTPUT 0 0 1 0 0 9 0 0 0 0 0 0 0 0 0 0 1 0 0 1 1 7 0 6 0 8 0 1 0 0 1 10 0 5 0 0 SWITCH 1 0 0 0 0 0 1 1 0 1 1 3 4 INPUT RANGE OUT FIELD/FACT. IN FIELD/FACT. OUTPUT RANGE 10 I IN 1V OUT+ I OUT- I 11 12 8 7 9 INPUT COMM 10V 100V VDC+ 5 4 6 VDC- 2 1 3 OUT+ OUT- V V 20mA/1mA OUTPUT 11-36VDC STATUS 6 * * T S U MC2290C S A T MADE IN U.S.A. RED LION CONTROLS MODEL IAMA YORK, PA. IAMA MODEL IAMA - UNIVERSAL SIGNAL CONDITIONING MODULE DIMENSIONS In inches (mm) CAUTION: Risk of Danger. Read complete instructions prior to installation and operation of the unit. CAUTION: Risk of electric shock. Bulletin No. IAMA-H Drawing No. LP0413 Released 04/13 Tel +1 (717) 767-6511 Fax +1 (717) 764-0839 www.redlion.net UL Recognized Component, File # E179259

Bulletin No. IAMA-H Drawing No. LP0413 Tel +1 (717) 767 ... · The IAMA can be factory recalibrated in the field if desired. The modules’ environmental operating temperature range

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Bulletin No. IAMA-H Drawing No. LP0413 Tel +1 (717) 767 ... · The IAMA can be factory recalibrated in the field if desired. The modules’ environmental operating temperature range

1

3-WAY ISOLATION OF ANALOG SIGNALS

UNIVERSAL CONVERSION MODULE - INPUTS AND OUTPUTS SELECTED VIA DIP SWITCH SETTINGS

OVER 100 INPUT AND OUTPUT ANALOG CONVERSION COMBINATIONS

CHOOSE LINEAR OR SQUARE ROOT EXTRACTION MODEL

ALL RANGES ARE FACTORY PRECALIBRATED. CUSTOM FIELD CALIBRATION IS AVAILABLE FOR ALL RANGES WHILE MAINTAINING THE FACTORY CALIBRATION FOR FUTURE USE

11 to 36 VDC AND 24 VAC MODULE POWER

GENERAL DESCRIPTIONThe IAMA – Universal Signal Conditioning Module Series can isolate and

convert over 100 combinations of analog signal ranges. The IAMA3535 converts and transmits signals linearly proportional to the input, while the IAMA6262 transmits the scaled square root of the input signal. This allows the IAMA6262 to provide a signal that is linear to flow rate in applications utilizing a differential pressure transducer.

DIP switch range selection eliminates the need to order and stock different modules for each input and output signal range, and allows quick and convenient setup for over 100 standard signal conversions. By utilizing the Field mode of calibration, the user can customize the input and output scaling for odd applications, including reversal of the output relative to the input.

In addition to the conversion capabilities, the IAMA modules feature optically isolated Input/Output signal circuits and transformer isolated Power to Input, Power to Output circuits.

The modules’ overall full scale accuracy typically exceed 0.05% depending upon range selection and scaling. The microprocessor based design provides ease of field scaling and the onboard E2PROM stores scaling values for future recall. Both models come factory precalibrated for all input and output ranges. Factory or custom field scaling can be selected by a simple mode switch change. The IAMA can be factory recalibrated in the field if desired.

The modules’ environmental operating temperature range is -20°C to +65°C. DIN rail mounting saves time and panel space. The units are equipped with universal mounting feet for attachment to standard DIN style rails, including top hat profile rail according to EN50022 - 35x7.5 and 35 x 15 and G profile rail according to EN50035-G32.

SAFETY SUMMARYAll safety related regulations, local codes and instructions that appear in the

manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

ORDERING INFORMATIONMODEL NO. DESCRIPTION PART NUMBER

IAMALinear Universal Signal Conditioning Module IAMA3535

Square Root Universal Signal Conditioning Module IAMA6262

SPECIFICATIONS1. POWER: 11 to 36 VDC, 3 W max. or 24 VAC, ±10%, 50/60 Hz, 4.8 VA max.2. INPUT/OUTPUT RANGES: See Tables 2 and 33. ZERO/SPAN ADJUSTMENTS: Digital (DIP Switch Transition)4. MAX INPUT SIGNAL:

Current Input: 110 mA DC, 1.1 VDCVoltage Inputs: Terminal 7- 1 VDC +10%

Terminal 8- 10 VDC +10% Terminal 9- 100 VDC +10%

5. INPUT RESISTANCE:Current: 10 ΩVoltage: > 100 K

6. INPUT PROTECTION: Surge suppressor diodes7. OUTPUT: Self-powered (Active)8. MAX OUTPUT CURRENT:

Current Output: 22 mAVoltage Output: 10 mA

9. LOAD RESISTANCE:Current Output: ≤ 600 ΩVoltage Output: ≥ 1 KΩ

10. OUTPUT COMPLIANCE:Current: 4 to 20 mA, 0 to 20 mA: 12 V min (≤ 600 Ω)

0 to 1 mA: 10 V min (≤10 KΩ)Voltage: 10 VDC across a min. 1 KΩ load (10 mA). Factory calibrated for

loads of > 1 MΩ.11. ISOLATION LEVEL INPUT TO OUTPUT: 1.5 kV @ 50/60 Hz, 1 min12. STEP RESPONSE: To within 99% of full scale: 300 msec

4.20

RE

F

1.083.12(27.5)

(106

.7)

(79.2)

10987543

OFF = 0

DIP

SW

ITCH

SE

TTING

S:

21

ON

= 1

MC2279X

ON

01

10

0-1V0

0-100mA

0-50mA

0-20mA

4-20mA

0-10mA

0-5mA

0-2mA

0-1mA

0-10V

0-100V0-50V0-20V

0-5V1-5V0-2V

0 0 0 0

0 0 0 0

1 1 1 1

11

01

0 00 1 1 1

1 0 0 0

01

11

1 1

0 1 0 1 0 1 0 10 0 0

00

11 1 1

0 0 0

11

01

0

1 0 0

0 0 0

01

11

1

10 1 0 0 1 0

0-50mV

0-100mV

0-200mV

0-500mV

0-20mV

0-20mA

4-20mA

INP

UT

0-5V0-10V0-1m

A

OU

TPU

T

00

1

0 0 90

00

00 00

00 01 0 0

1 1

70

60

80100 1 100

50 0

SW

ITCH

1

00000

11

011

34

INP

UT R

AN

GE

OU

T FIELD

/FAC

T.IN

FIELD

/FAC

T.

OU

TPU

T RA

NG

E10

IIN 1V

OU

T+I O

UT-

I

1112

87

9

INP

UT

CO

MM

10V100V

VD

C+

54

6

VD

C-

21

3

OU

T+

OU

T-

VV

20mA

/1mA

OU

TPU

T

11-36VD

C

STA

TUS

6

**

T

SU

MC2290C

S

AT

MAD

E IN U

.S.A.RED

LION

CON

TRO

LS

MO

DE

L IAM

AYO

RK, PA.

IAMA

MODEL IAMA - UNIVERSAL SIGNAL CONDITIONING MODULE

DIMENSIONS In inches (mm)

CAUTION: Risk of Danger.Read complete instructions prior

to installation and operation of the unit.

CAUTION: Risk of electric shock.

Bulletin No. IAMA-H

Drawing No. LP0413

Released 04/13

Tel +1 (717) 767-6511

Fax +1 (717) 764-0839

www.redlion.net

UL Recognized Component, File # E179259

Page 2: Bulletin No. IAMA-H Drawing No. LP0413 Tel +1 (717) 767 ... · The IAMA can be factory recalibrated in the field if desired. The modules’ environmental operating temperature range

2

13. ACCURACY (INCLUDING LINEARITY): Factory: ±0.1% of span max. for all ranges except 1 mA, 2 mA, and 20 mV. These ranges are accurate to ±0.2% of span max. All ranges can be field calibrated to 0.1% of span max.

14. RESOLUTION: 0.01% full scale input, 0.01% full scale output15. ENVIRONMENTAL CONDITIONS:

Operating Temperature Range: -20 to +65 °CStorage Temperature Range: -40 to +85 °COperating and Storage Humidity: 85% max. relative humidity (non-

condensing) from -20 to +65 °CTemperature Coefficient: ± 0.01%/°C (100 PPM/°C) max.Vibration to IEC 68-2-6: Operational 5 to 150 Hz, 2 g.Shock to IEC 68-2-27: Operational 30 gAltitude: Up to 2000 meters

16. CERTIFICATIONS AND COMPLIANCES:CE Approved

EN 61326-1 Immunity to Industrial LocationsEmission CISPR 11 Class AIEC/EN 61010-1

UL Recognized Component: File #E179259Refer to EMC Installation Guidelines section of this bulletin for additional

information.17. CONSTRUCTION: Case body is black high impact plastic18. CONNECTIONS: 14 AWG max19. MOUNTING: Standard DIN top hat (T) profile rail according to EN50022

- 35x7.5 and 35 x 15 and G profile rail according to EN50035-G32.20. WEIGHT: 4.5 oz. (127.57 g)

MODULE ISOLATIONIAMA modules feature “3-Way” Signal Isolation. The 3-Way isolation is a

combination of optical and transformer isolation. The optical isolation provides common mode voltage (CMV) isolation up to 1.5 kV between the sensor input and the process signal output. The IAMA’s power is isolated from the sensor signal input and the process signal output by a DC/DC transformer isolation circuit.

OVERVIEWThe IAMA3535 continuously monitors a voltage or current input and

provides a linearly proportional voltage or current output, while the IAMA6262 transmits the scaled square root of the input signal. This allows the IAMA6262 to provide a signal that is linear to flow rate in applications utilizing a differential pressure transducer. Both units have two modes of operation known as Factory and Field modes. Factory mode is used when the default input and output ranges are suitable. Field mode can be independently selected for both the input and output, and allows the user to custom calibrate, or scale the signal. If Factory mode is selected, the IAMAs use factory presets for the selected input or output range. If Field mode is selected, the IAMAs can be custom scaled within a selected input or output range. Field mode also allows the IAMA to reverse its output in relation to its input.

The units are factory precalibrated for minimum and full scale for all input and output ranges. The factory calibration values are permanently stored in E2PROM and should not be changed in the field, unless unacceptable error or a factory checksum error occurs. See Factory Recalibration for details. Field scaling is achieved by applying minimum and full scale values from a calibration source and storing the values by a single DIP switch transition. Field scaling is available for all input and output ranges and the values are permanently stored in E2PROM until reprogramming occurs.

After field scaling, the IAMAs can be changed between Factory and Field modes for a particular range, which restores the respective setting. The Factory and Field E2PROM locations contain the same calibration values when the

IAMA is received from the factory. Therefore, until the IAMA is field scaled, factory and field modes perform identically. See SCALING PROCEDURE for detailed instructions on field programming the IAMA.

The units can be scaled to any minimum scale and full scale values within the extent of the selected range. The closer together the minimum and full scale values are to each other, the less accurate the signal will be. For example, if the 0 to 1 V input range is selected, and the unit is scaled for 0 to 0.5 V, the signal has the same resolution as the 0 to 1 V range. Since this resolution will be two times the percentage of span for 0.5 V, more accuracy can be achieved by using the 0 to 0.5 V range.

The input may exceed the full scale value for the selected range by 10% of span, but the IAMA will not update the output beyond 10% over range.

The red and green LED’s indicate the status of the modules during scaling and normal operation. Table 1, LED Indications, details the LED indications for various unit conditions.

The IAMA – Signal Conditioning Module Series is designed for use in industrial environments. Suppressor diodes protect both input and output circuits from wiring errors and transient high voltage conditions.

INPUTSThe IAMAs accept a full range of process signal inputs and isolate and

convert these signals to common industrial control signals. The input signal combinations are configured by making specific DIP switch selections on the 10 position DIP switch.

OUTPUTSAs with the input choices, the process signal output of the modules is DIP

switch selectable. A 1 position DIP switch is used to select between the 1 mA/20 mA output ranges. The maximum output current signal is 22 mA with ≤600 Ω output resistance and the maximum output voltage signal is 11 V with ≥1 KΩ output resistance.

ZERO AND SPANThe input zero and span are set by first applying the minimum value then

transitioning S1-2 to store that value. Next, the full scale value is applied and the DIP switch transition stores the value. The output scaling is performed in a similar manner but the output is driven to the desired minimum and full scale values by the calibration source applied to the input. S1-1 is used to store the minimum and full scale output values.

The span is defined by: span = (full scale - minimum scale).

ILLEGAL RANGE SELECTIONS AND CHANGESThe ranges should only be selected before power is applied. If an invalid input

or output range is selected when power is applied the output is set to approximately 0 VDC and the red LED indicates the error according to Table 1. Power must be removed and valid ranges selected for the IAMA to operate properly.

If S1 switches 3 through 10 are changed while the IAMA is operating, the red LED indicates a range change according to Table 1, LED Indications and the output goes to the previously stored range minimum scale value. Normal operation will be resumed if the switches are placed back in the previous positions or power is removed and restored.

CHECKSUM ERRORSA checksum is performed every time power is applied to the IAMA. If a

checksum error occurs, the LEDs will indicate where the error occurred according to Table 1, LED Indications. Operation with a checksum error is not recommended but can be done in critical situations. If an error occurs, re-calibration of the field or factory ranges to be used must be performed.

If a field checksum error occurs, the IAMA will operate only in factory mode. If a factory checksum occurs, the IAMA will operate only in a previously calibrated field mode. Do not perform a field scaling until the factory checksum is cleared. Since a checksum error is a high priority LED indication, the LEDs will indicate the error until it is cleared. This will exclude other LED information.

*

10

12

VARIABLEGAINAMP

V/FCONVERTER

PROCESSCIRCUITY

6

5

1

4

PWMCIRCUITRY

V

V

I

I

3

2

POWERSUPPLY

V

IINPUT

COMMON

IN

IN

+

-

11-36VDC OUT+

OUT-

OUT+

OUT-

BLOCK DIAGRAM

* Terminal number is dependent on max. input voltage.

Page 3: Bulletin No. IAMA-H Drawing No. LP0413 Tel +1 (717) 767 ... · The IAMA can be factory recalibrated in the field if desired. The modules’ environmental operating temperature range

3

TABLE 1, LED INDICATIONS

GETTING STARTEDOne method for the Input (1 or 2 below) should be configured, and one

method for the Output (3 or 4 below) should be configured.1. FACTORY preprogrammed settings for the Input, see Section 1.02. FIELD scaling method for the Input, see Section 2.03. FACTORY preprogrammed setting for the Output, see Section 3.04. FIELD scaling method for the Output, see Section 4.0

Note: The ranges should only be changed while power is removed from the IAMA.

TABLE 2, OUTPUT RANGE SETTINGS

TABLE 3, INPUT RANGE SETTINGS

FIELD OR FACTORY MODE SELECTIONSELECTING FIELD MODE (2 Methods):1. Scale the input or output according to SCALING PROCEDURE 2.0 or 4.02. Before applying power, set the input or output (or both) field/factory switch

to the up (field) position. Field calibration values will be restored upon power-up. If the IAMA has not been previously field calibrated, the E2PROM will contain the factory calibration values which will be restored.

SELECTING FACTORY MODE (2 Methods):1. Before applying power to the IAMA set the input or output (or both) field/

factory switch to the down (factory) position. Factory calibration values will

be restored upon power-up.2. While power is applied to the IAMA and it is operating in the field input and/

or output mode, set the desired field/factory switch(s) to the down (factory) position. The factory calibration values will be restored.

EMC INSTALLATION GUIDELINESAlthough Red Lion Controls Products are designed with a high degree of

immunity to Electromagnetic Interference (EMI), proper installation and wiring methods must be followed to ensure compatibility in each application. The type of the electrical noise, source or coupling method into a unit may be different for various installations. Cable length, routing, and shield termination are very important and can mean the difference between a successful or troublesome installation. Listed are some EMI guidelines for a successful installation in an industrial environment.1. A unit should be mounted in a metal enclosure, which is properly connected

to protective earth.2. Use shielded cables for all Signal and Control inputs. The shield connection

should be made as short as possible. The connection point for the shield depends somewhat upon the application. Listed below are the recommended methods of connecting the shield, in order of their effectiveness.a. Connect the shield to earth ground (protective earth) at one end where the

unit is mounted.b. Connect the shield to earth ground at both ends of the cable, usually when

the noise source frequency is over 1 MHz.3. Never run Signal or Control cables in the same conduit or raceway with AC

power lines, conductors, feeding motors, solenoids, SCR controls, and heaters, etc. The cables should be run through metal conduit that is properly grounded. This is especially useful in applications where cable runs are long and portable two-way radios are used in close proximity or if the installation is near a commercial radio transmitter. Also, Signal or Control cables within an enclosure should be routed as far away as possible from contactors, control relays, transformers, and other noisy components.

4. Long cable runs are more susceptible to EMI pickup than short cable runs.5. In extremely high EMI environments, the use of external EMI suppression

devices such as Ferrite Suppression Cores for signal and control cables is effective. The following EMI suppression devices (or equivalent) are recommended:

Fair-Rite part number 0443167251 (RLC part number FCOR0000)Line Filters for input power cables:

Schaffner # FN2010-1/07 (Red Lion Controls # LFIL0000)6. To protect relay contacts that control inductive loads and to minimize radiated

and conducted noise (EMI), some type of contact protection network is normally installed across the load, the contacts or both. The most effective location is across the load.a. Using a snubber, which is a resistor-capacitor (RC) network or metal oxide

varistor (MOV) across an AC inductive load is very effective at reducing EMI and increasing relay contact life.

b. If a DC inductive load (such as a DC relay coil) is controlled by a transistor switch, care must be taken not to exceed the breakdown voltage of the transistor when the load is switched. One of the most effective ways is to place a diode across the inductive load. Most RLC products with solid state outputs have internal zener diode protection. However external diode protection at the load is always a good design practice to limit EMI. Although the use of a snubber or varistor could be used.RLC part numbers: Snubber: SNUB0000 Varistor: ILS11500 or ILS23000

7. Care should be taken when connecting input and output devices to the instrument. When a separate input and output common is provided, they should not be mixed. Therefore a sensor common should NOT be connected to an output common. This would cause EMI on the sensitive input common, which could affect the instrument’s operation.

Visit RLC’s web site at http://www.redlion.net/Support/InstallationConsiderations.html for more information on EMI guidelines, Safety and CE issues as they relate to Red Lion Controls products.

WIRING CONNECTIONSAll conductors should meet voltage and current ratings for each terminal.

Also cabling should conform to appropriate standards of good installation, local codes and regulations. It is recommended that power supplied to the unit be protected by a fuse or circuit breaker. When wiring the unit, use the numbers on the label to identify the position number with the proper function. Strip the wire, leaving approximately 1/4" (6 mm) of bare wire exposed. Insert the wire into the terminal, and tighten the screw until the wire is clamped tightly.

RANGE DIP SWITCHES

3 4 5

OUTPUT RANGE

0 - 5 V 0 0 0VOLTAGE OUTPUTS 0 - 10 V 0 0 1

0 - 1 mA 0 1 04 - 20 mA 0 1 1CURRENT

OUTPUTS0 - 20 mA 1 0 0

Note: DIP switch settings 0 = OFF 1 = ON

Note: DIP switch settings 0 = OFF 1 = ON

RANGERANGE DIP SWITCHES

6 7 8 9 10

INPUT VOLTAGE

0 - 20 mV 0 0 0 0 00 - 50 mV 0 0 0 0 1

0 - 100 mV 0 0 0 1 00 - 200 mV 0 0 0 1 10 - 500 mV 0 0 1 0 0

0 - 1 V 0 0 1 0 10 - 2 V 0 0 1 1 01 - 5 V 0 0 1 1 10 - 5 V 0 1 0 0 0

0 - 10 V 0 1 0 0 10 - 20 V 0 1 0 1 00 - 50 V 0 1 0 1 1

0 - 100 V 0 1 1 0 00 - 1 mA 0 1 1 0 10 - 2 mA 0 1 1 1 00 - 5 mA 0 1 1 1 1

0 - 10 mA 1 0 0 0 04 - 20 mA 1 0 0 0 10 - 20 mA 1 0 0 1 00 - 50 mA 1 0 0 1 1

INPUT CURRENT

0 - 100 mA 1 0 1 0 0

CONDITION GREEN LED RED LED

Normal Operation On OffScaling Mode Alternate with Red Alternate with GreenUnder Range Off Slow Flash (0.8 sec rate)Over Range Off Fast Flash (0.4 sec rate)Invalid Range Off OnIllegal Range Change Off OnFactory Checksum Off On, short offField Checksum On, short off OffUser Factory Calibration Fast Flash for 2 sec Off

Page 4: Bulletin No. IAMA-H Drawing No. LP0413 Tel +1 (717) 767 ... · The IAMA can be factory recalibrated in the field if desired. The modules’ environmental operating temperature range

4

POWER AND OUTPUT CONNECTIONSPower

Primary power is connected to terminals 2 and 3 (labeled VDC- and VDC+). For best results, the Power should be relatively “clean” and within the specified variation limits. Drawing power from heavily loaded circuits or from circuits that also power loads that cycle on and off, should be avoided.

Current OutputWiring for a current output is connected to terminals 1 (IOUT-) and 4 (IOUT+).

DIP switch S2 should be set for the desired full scale output current. (20 mA = ON; 1 mA = OFF).

Voltage OutputWiring for a voltage output is connected to terminals 5 (VOUT-) and 6

(VOUT+).

Note: Although signals are present at voltage and current outputs at the same time, only the selected range is in calibration at any one time.Example: A 0 to 10 VDC output is selected. The voltage level present at the

voltage output terminals is in calibration, but the signal appearing at the current output terminals does not conform to any of the current output ranges.

INPUT CONNECTIONSCurrent Input

Wiring for a current input is connected to terminals 10 (IIN) and 12 (INPUT COMMON).

Voltage InputWiring for a voltage input is

connected to terminal 12 (INPUT COMMON) and one of the three available voltage terminals listed below, depending on maximum input voltage.

Terminal 7: 1 VDC max.Terminal 8: 10 VDC max.Terminal 9: 100 VDC max.

OUT-

OUT+

10V

COMMINPUTI IN

OUT-

OUT+

1V

V

V

I

I

S

MC2290D

A

UT

TS

100V

1 2 3

654

7 8 9

1210

~-DC+~- (AC)

DC-(AC)

IAMA

1.1 Remove power.

1.2 Connect signal wires to the correct input terminals based on the maximum signal input.

Terminal 7: max. signal input 1 VDCTerminal 8: max. signal input 10 VDCTerminal 9: max. signal input 100 VDCTerminal 10: max. signal input 100 mATerminal 12: signal common

1.3 Set Input Range switches (S1 switches 6 through 10) to the desired Input Range (See Table 3). (0 to 10 VDC range shown).

1.4 Set Input Field/Fact. switch (S1 switch 2) to the off position.

1.5 Apply power to the IAMA.Solid illumination of Green LED if signal is within the minimum and maximum

limits of the selected input range.Slow blinking of Red LED if signal decreases below minimum limit of selected input

range.Rapid blinking of Red LED if signal increases above maximum limit of selected

input range.

1.6 Input set-up complete. Go to Step 3.0 or Step 4.0.

1.0 INPUT SET-UP USING FACTORY CONFIGURATION

OUT-

OUT+

10V

COMMINPUTI IN

OUT-

OUT+

1V

V

V

I

I

S

MC2290D

A

UT

TS

100V

1 2 3

654

7 8 9

1210

~-DC+~- (AC)

DC-(AC)

IAMA

SCALING PROCEDUREThe accuracy of the IAMA is dependent on the accuracy of the calibration source and the voltage

or current meter used in the scaling process.If an out of range (see Table 1 for LED indications) or illegal (full scale less than minimum scale)

scaling is attempted, the factory calibration values will be stored in place of the field values. This will prohibit erroneous operation of the IAMA. The scaling procedure will have to be repeated.

The final storage of the zero and full scale values to E2PROM is not done until the last transition of the mode/calibration DIP switches (S1-1 or S1-2). Therefore, the scaling can be aborted any time before the full scale value is saved. This is accomplished by cycling power to the IAMA. The IAMA will restore the factory or previous field scaling values at power up depending on the setting of the DIP switches. See Mode Selection for more detailed instructions for selecting factory and field modes at power up. See Table 2 and 3 for the input and output range DIP switch settings.

ON21 3 54 6

S187 9 10 1

S2

Step 1.3

ON21 3 54 6

S187 9 10 1

S2

Step 1.4

1 2 43 65 87 109

OUTPUTRANGE RANGE

INPUT

S1 S2

OUTPUT

20mA1mA

ON

FIE

LD/FA

CTO

RY

INP

UT

OU

TPU

T

OUTPUT RANGE

INPUT RANGE20mA/1mA OUTPUT

IN FIELD/FACT.

OUT FIELD/FACT.

7

ON

1

65432

1098

IAMASTATUS

GREENLED

REDLED

Page 5: Bulletin No. IAMA-H Drawing No. LP0413 Tel +1 (717) 767 ... · The IAMA can be factory recalibrated in the field if desired. The modules’ environmental operating temperature range

5

2.1 Remove power.

2.2 Connect signal source to the correct input terminals based on the maximum signal input.

Terminal 7: max. signal input 1 VDCTerminal 8: max. signal input 10 VDCTerminal 9: max. signal input 100 VDCTerminal 10: max. signal input 100 mATerminal 12: signal common

2.3 Set Input Range switches (S1 switches 6 through 10) to the desired input range (See Table 3). Select the lowest possible range that will support the desired maximum signal. Example: if the desired span is 20 mV to 85 mV, the best range selection is 0 to 100 mV. The 0 to 200 mV will also suffice, but the accuracy will be reduced. (0 to 10 VDC range shown).

2.4 Set Input Field/Fact. switch (S1 switch 2) to the off position.

2.5 Apply power to the IAMA and allow a warm up period of five minutes. Follow the manufacturer’s warm up procedure for the calibration source.

2.6 Set Input Field/Fact. switch (S1 switch 2) to the on position.The Red and Green LEDs will alternately blink.

2.7 Apply desired minimum scale signal.

2.8 Set Input Field/Fact. switch (S1 switch 2) to the off position.The Red and Green LEDs will alternately blink.If the signal is equal or below the minimum limit of the selected range, the Red LED

blinks slowly and the Green LED turns off. Removing power aborts scaling, begin at Step 2.1.

2.9 Apply maximum scale input.The Red and Green LEDs will alternately blink.

2.10 Set Input Field/Fact. switch (S1 switch 2) to the on position.Red LED extinguishes and Green LED becomes solid. Your scaled values are now

saved and recalled if the Input Field/Fact. switch (S1 switch 2) is in the on position when power is applied.

Red LED will blink slowly if signal is equal to or below minimum limit and blinks rapidly if signal increases above maximum limit.

2.11 Input scaling complete. Go to Step 3.0 or Step 4.0.

3.1 Remove power.

3.2 For voltage output values, go to Step 3.4For current output values, continue at Step 3.3

3.3 Set 20 mA/1 mA switch (S2) to desired full scale output.(20 mA - on; 1 mA - off)

3.4 Set Output Field/Fact. switch (S1 switch 1) to the off position.

3.5 Set Output Range switches (S1 switches 3, 4, and 5) to the desired Output Range (See Table 2). (4 to 20 mA range shown)

3.6 Connect external device to appropriate IAMA output terminals.Terminal 6: + VoltageTerminal 5: - VoltageTerminal 4: + CurrentTerminal 1: - Current

3.7 Apply power to the IAMA and allow a warm up period of five minutes. Output set-up complete.

2.0 INPUT SCALING USING FIELD CONFIGURATION

3.0 OUTPUT SET-UP USING FACTORY CONFIGURATION

ON21 3 54 6

S187 9 10 1

S2

Step 2.3

ON21 3 54 6

S187 9 10 1

S2

Step 2.4

ON21 3 54 6

S187 9 10 1

S2

Step 2.6

ON21 3 54 6

S187 9 10 1

S2

Step 2.8

ON21 3 54 6

S187 9 10 1

S2

Step 3.5

ON21 3 54 6

S187 9 10 1

S2

Step 2.10

ON21 3 54 6

S187 9 10 1

S2

Step 3.3 & 3.4

OUT-

OUT+

10V

COMMINPUTI IN

OUT-

OUT+

1V

V

V

I

I

S

MC2290D

A

UT

TS

100V

1 2 3

654

7 8 9

1210

~-DC+~- (AC)

DC-(AC)

IAMA

OUT-

OUT+

10V

COMMINPUTI IN

OUT-

OUT+

1V

V

V

I

I

S

MC2290D

A

UT

TS

100V

1 2 3

654

7 8 9

1210

~-DC+~- (AC)

DC-(AC)

IAMA

OUTPUT RANGE

INPUT RANGE20mA/1mA OUTPUT

IN FIELD/FACT.

OUT FIELD/FACT.

7

ON

1

65432

1098

IAMASTATUS

GREENLED

REDLED

Page 6: Bulletin No. IAMA-H Drawing No. LP0413 Tel +1 (717) 767 ... · The IAMA can be factory recalibrated in the field if desired. The modules’ environmental operating temperature range

6

4.1 Remove power.

4.2 For voltage output scaling, go to Step 4.4. For current output scaling, continue at Step 4.3.

4.3 Set 20 mA/1 mA switch (S2) to desired full scale output.(20 mA - on; 1 mA - off)

4.4 Set Output Field/Fact. switch (S1 switch 1) to the off position.

4.5 Set Output Range switches (S1 switches 3, 4, and 5) to the desired Output Range (See Table 2). Select the lowest possible range that will support the desired full scale output. Example: if the desired span is 1 V to 4 V, the best range selection is 0 to 5 V. (0 to 5 VDC range shown)

4.6 Connect volt or current meter to appropriate IAMA output terminals.Terminal 6: + VoltageTerminal 5: - VoltageTerminal 4: + CurrentTerminal 1: - Current

4.7 An input signal is required to complete output scaling. If previous scaled input is used (completed in Step 2.0), Input Field/Fact. switch (S1 switch 2) and Input Range switches (S1 switches 6 through 10) must remain in the same positions. If another signal source is used, set Input Field/Fact. switch (S1 switch 2) to off position and Input Range switches (S1 switches 6 through 10) to the desired input range (See Table 3).

4.8 Connect input signal source to the correct input terminals based on the maximum signal input.

Terminal 7: max. signal input 1 VDCTerminal 8: max. signal input 10 VDCTerminal 9: max. signal input 100 VDCTerminal 10: max. signal input 100 mATerminal 12: signal common

4.9 Apply power to the IAMA and allow a warm up period of five minutes.

4.10 Set Output Field/Fact. switch (S1 switch 1) to the on position.The Red and Green LEDs will alternately blink.If Red LED blinks slowly, increase signal until Red and Green LEDs alternately

blink.

4.11 Adjust the input signal until the desired * minimum output level is displayed on the volt or current meter.The Red and Green LEDs will alternately blink.

4.12 Set Output Field/Fact. switch (S1 switch 1) to the off position. The Red and Green LEDs alternately blink.If the signal is equal to or below the minimum limit of the selected range, the Red

LED blinks slowly and the Green LED turns off. Removing power aborts scaling. Start over at Step 4.1.

4.13 Adjust the input signal until the desired * maximum output level is displayed on the volt or current meter.

4.14 Set Output Field/Fact. switch (S1 switch 1) to the on position. Red LED extinguishes and Green LED becomes solid. Your scaled values are now

saved and will be recalled if the Output Field/Fact. switch (S1 switch 1) is in the on position when power is applied.

4.15 Output scaling is complete.

* If the minimum output is higher than the maximum output the module reverses its output behaviour accordingly.

4.0 OUTPUT SCALING USING FIELD CONFIGURATION

ON21 3 54 6

S187 9 10 1

S2

Step 4.4

ON21 3 54 6

S187 9 10 1

S2

Step 4.5

ON21 3 54 6

S187 9 10 1

S2

Step 4.10

ON21 3 54 6

S187 9 10 1

S2

Step 4.12

ON21 3 54 6

S187 9 10 1

S2

Step 4.14

OUT-

OUT+

10V

COMMINPUTI IN

OUT-

OUT+

1V

V

V

I

I

S

MC2290D

A

UT

TS

100V

1 2 3

654

7 8 9

1210

~-DC+~- (AC)

DC-(AC)

IAMA

OUTPUT RANGE

INPUT RANGE20mA/1mA OUTPUT

IN FIELD/FACT.

OUT FIELD/FACT.

7

ON

1

65432

1098

IAMASTATUS

GREENLED

REDLED

Page 7: Bulletin No. IAMA-H Drawing No. LP0413 Tel +1 (717) 767 ... · The IAMA can be factory recalibrated in the field if desired. The modules’ environmental operating temperature range

7

The following list outlines conditions that are unique to factory recalibration:1. Unlike the field scaling procedures, there are no software under and over

range indications while performing a factory recalibration. Therefore, care must be taken to insure the selected range extents are not exceeded. The minimum scale and full scale calibration values must be set to the extents of the range being calibrated.For example: If the Input Range DIP switches are set for the 4-20 mA

range, minimum scale must be set at 4 mA, and full scale must be set at 20 mA.

2. At least one input calibration must be completed before calibrating any output range. When calibrating the input voltage range, it is recommended that a range above 1 V be used to provide better accuracy.

3. If multiple input or output ranges are to be calibrated, DO NOT REMOVE POWER TO CHANGE THE RANGE. Place the appropriate Field/Fact. DIP switch; S1-1 for outputs, and S1-2 for inputs to the down position, and set the remaining DIP switches for the range to be calibrated. Note: Be sure to change the terminal wiring to match the Input or Output range DIP switch settings before performing the calibration procedure. Set calibration source to 0 V or 0 mA before changing wiring.

INPUT RECALIBRATION1. To enter the factory calibration mode, set switches S1-1 and S1-2 down, S1-3

through S1-5 up, and S1-6 through S1-10 down.2. Connect a signal source to the correct input terminals based on the maximum

signal input to be calibrated. If an output range will be calibrated after the input range is calibrated, connect a voltage or current meter to the appropriate output terminals at this time.

3. Apply power to the IAMA. After the version number indication, the green LED will flash rapidly for 2 seconds indicating the factory calibration mode has been entered. Allow the IAMA to warm up for 5 minutes minimum and follow the manufacturer’s warm up procedure for the calibration source.

4. Set the Input Range DIP switches to the desired input range according to Table 3.

5. Complete Steps 2.6 through 2.10 of Input Scaling Using Field Configuration. Note: There will be no over or under range indication of the LED’s during this procedure, so use care not to exceed the range extents.

6. If an output is to be calibrated, continue from #2 of Output Recalibration below. If no further input or output calibration is to be completed, return S1-1 and S1-2 to the down position and remove power from the IAMA. Apply power and check for accurate operation of the newly calibrated range or ranges.

OUTPUT RECALIBRATION1. Complete 1 through 5 of the input recalibration procedure for at least

one range.2. For current output, set 20 mA/1 mA switch (S2) to desired full scale output.

(20 mA - on; 1 mA - off)3. Set Output Field/Fact. switch (S1 switch 1) to the off position.4. Set the Output Range DIP switches to the desired output range according to

Table 2.5. Complete Steps 4.10 through 4.14 of Output Scaling Using Field

Configuration. Note: There will be no over or under range indication of the LED’s during this procedure, so use care not to exceed the range extents.

6. If no further calibration is to be completed, return S1-1 and S1-2 to the down position and remove power from the IAMA. Apply power and check for accurate operation of the newly calibrated range or ranges.

RECALIBRATING FACTORY STORED VALUES

WARNING: Read the complete procedure at least once before attempting to recalibrate the factory values. This procedure should only be performed due to factory checksum error or unacceptable error. This procedure should be performed by qualified technicians using accurate calibration equipment.

TROUBLESHOOTINGFor further technical assistance, contact technical support at the appropriate company numbers listed.

INSTALLATIONThe unit is equipped with a universal mounting foot for attachment to standard DIN style mounting rails, including G profile rail

according to EN50035 - G32 , and top hat (T) profile rail according to EN50022 - 35 x 7.5 and 35 x 15. The unit should be installed in a location that does not exceed the maximum operating temperature and provides good air circulation. Placing the unit near devices that generate excessive heat should be avoided.

G Rail InstallationTo install the IAMA on a “G”

style DIN rail, angle the module so that the upper groove of the “foot” catches under the lip of the top rail. Push the module toward the rail until it snaps into place. To remove a module from the rail, push up on the bottom of the module while pulling out and away from the rail.

T Rail InstallationTo install the IAMA on a “T”

style rail, angle the module so that the top groove of the “foot” is located over the lip of the top rail. Push the module toward the rail until it snaps into place. To remove a module from the rail, insert a screwdriver into the slot on the bottom of the “foot”, and pry upwards on the module until it releases from the rail.

Page 8: Bulletin No. IAMA-H Drawing No. LP0413 Tel +1 (717) 767 ... · The IAMA can be factory recalibrated in the field if desired. The modules’ environmental operating temperature range

MODEL I

AMA

OUTPU

T RANGE

INPUT RANGE20m

A/1mA

OUTPUT

IN FIE

LD/FAC

T.

OUT F

IELD/FAC

T.

7

ON

1

65432

1098

IAMASTATUS

IAMAA

ST

TUS

MODEL I

AMA

ON

109

20mA/1

mA OUTPUT

INPUT RANGE

1

5432

76

8

OUTPU

T RANGE

IN FIE

LD/FAC

T.

OUT F

IELD/FAC

T.

20mA/1

mA OUTPUT

UT

TS

A

IAMA

ON

OUT F

IELD/FAC

T.

IN FIE

LD/FAC

T.OUTPU

T RANGE

8

67

2345

1

INPUT RANGE

910

MODEL I

AMA

S

20mA/1

mA OUTPUT

UT

TS

A

IAMA

ON

OUT F

IELD/FAC

T.

IN FIE

LD/FAC

T.OUTPU

T RANGE

8

67

2345

1

INPUT RANGE

910

MODEL I

AMA

S

APPLICATIONCost efficiency measurements of a printing company included the

reduction of bulk stock of the various inks used in their printing processes. The company currently had various ink flow and level devices with different current and voltage outputs and wanted to record these measurements into a control room PC. Several IAMA Universal Signal Conditioning Modules were the answer. The IAMA’s universal input allowed for easy signal conditioning of the various output signals to the required PC’s Bus Board 0 to 10 VDC input signal. The factory calibration settings of the IAMA could be used with the devices in which the flow and level pressure was linear to the signal. The IAMA could also be scaled utilizing the field calibration method with the devices where pressure affected the signal slope specifications. In this case, the IAMA’s re-transmitted 0 to 10 VDC output was field calibrated, negating the expense and time required to rewrite the PC’s software parameters. In addition to accepting multiple signal types and field calibration features, the IAMA also provides the necessary electrical isolation between the control room PC and the hazards of the printing floor electrical noise.

LIMITED WARRANTYThe Company warrants the products it manufactures against defects in materials and workmanship for a period limited to two years from the date of shipment, provided the products have been stored, handled, installed, and used under proper conditions. The Company’s liability under this limited warranty shall extend only to the repair or replacement of a defective product, at The Company’s option. The Company disclaims all liability for any affirmation, promise or representation with respect to the products.The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries, deaths, property damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be to any extent liable, including without limitation penalties imposed by the Consumer Product Safety Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty Act (P.L. 93-637), as now in effect or as amended hereafter.No warranties expressed or implied are created with respect to The Company’s products except those expressly contained herein. The Customer acknowledges the disclaimers and limitations contained herein and relies on no other warranties or affirmations.

Red Lion ControlsHeadquarters20 Willow Springs CircleYork PA 17406Tel +1 (717) 767-6511Fax +1 (717) 764-0839

Red Lion ControlsChina

Unit 302, XinAn PlazaBuilding 13, No.99 Tianzhou Road

ShangHai, P.R. China 200223Tel +86 21 6113 3688Fax +86 21 6113 3683

Red Lion ControlsEurope

Softwareweg 9NL - 3821 BN AmersfoortTel +31 (0) 334 723 225Fax +31 (0) 334 893 793

Red Lion ControlsIndia

201-B, 2nd Floor, Park CentraOpp 32 Mile Stone, Sector-30

Gurgaon-122002 Haryana, IndiaTel +91 984 487 0503