54
Bulletin 1609 UPS Network Management Card Catalog Number 1609-ENET User Manual Original Instructions

Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Bulletin 1609 UPS Network Management CardCatalog Number 1609-ENET

User ManualOriginal Instructions

Page 2: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Important User Information

Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.

Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.

If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

Labels may also be on or inside the equipment to provide specific precautions.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.

ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).

Page 3: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Table of ContentsManual Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Who Should Use This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Terms and Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Chapter 1Introduction Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Chapter 2Configuration Initial Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Network with BOOTP/DHCP Server . . . . . . . . . . . . . . . . . . . . . . . 9Network without BOOTP/DHCP Server. . . . . . . . . . . . . . . . . . . . 9

Configuration Methods. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10EzSetting Configuration Instructions . . . . . . . . . . . . . . . . . . . . . . . 10COM Port Configuration Instructions. . . . . . . . . . . . . . . . . . . . . . 12Telnet Configuration Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Text Mode Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13User Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14TCP/IP Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Network Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Time Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Soft Restart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Reset All To Default . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Exit Without Save . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Save And Exit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Chapter 3Web Interface Login. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Monitor Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20UPS Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Battery Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20In/Out Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Status Indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Monitor History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Event Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Data Log. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Configure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Device Management. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Configure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Weekly Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Specific Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 3

Page 4: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Table of Contents

Event Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26System Administration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

User Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26TCP/IP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Web. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Console. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29FTP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Time Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Syslog. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Batch Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

System Notification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33SNMP Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33SNMPv3 USM (User-based Security Management) . . . . . . . . . . 34SNMP Trap. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34Mail Server. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35Wake On LAN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

EtherNet/IP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Chapter 4Specifications Technical and Environmental Specifications. . . . . . . . . . . . . . . . . . . . . 39

Chapter 5Troubleshooting Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

Appendix AEtherNet/IP Object Service Object Descriptions and Service Support . . . . . . . . . . . . . . . . . . . . . . . . 43

Return Codes and Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

Appendix BEtherNet/IP Parameters Object Attributes and Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Appendix CEtherNet/IP IO Data Mapping Configuration Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Consumed (Output) Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51Produced (Input) Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

4 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 5: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Preface

Manual Objectives The purpose of this manual is to provide you with the necessary information to install and configure the Network Management Card for the 1609 UPS. Described in this manual are methods for installing, configuring, and troubleshooting.

Who Should Use This Manual This manual is intended for qualified personnel responsible for setting up and servicing these devices. You must have previous experience with and a basic understanding of communications technology, configuration procedures, required equipment, and safety precautions.

Terms and Abbreviations

Additional Resources These documents contain additional information concerning related products from Rockwell Automation

You can view or download publications athttp:/www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.

Term/Abbreviation Definition

IP Internet Protocol

LAN Local Area Network

MAC Address, MAC ID Media Access Control Address

SNMP Simple Network Management Protocol

TCP Transmission Control Protocol

USM User-based Security Management

Resource Description

Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1

Provides general guidelines for installing a Rockwell Automation industrial system.

Product Certifications website, http://www.ab.com Provides declarations of conformity, certificates, and other certification details.

Publication Number: 1609-UM007_-EN-P Bulletin 1609 UPS Management SoftwareUser Manual

Publication Number: 1609-UM009_-EN-P Bulletin 1609-B, -D UPS User Manual

Publication Number: 1609-IN012_-EN-P Bulletin 1609-D Installation Instructions

Publication Number: 1609-IN013_-EN-P Bulletin 1609-B Installation Instructions

Publication Number: 1609-IN014_-EN-P Surge Protective Device (Cat. No. 1609-SPD) Installation Instructions

Publication Number: 1609-IN015_-EN-P Network Management Card (Cat. No. 1609-ENET) Installation Instructions

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 5

Page 6: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Preface

Notes:

6 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 7: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 1

Introduction

The 1609 Network Management Card (Cat. No. 1609-ENET) provides an interface between a Uninterruptible Power Supply (UPS) and a network. It can communicate with a UPS and acquire its information and remotely manage it through a network system.

The network card supports two protocols for user access: SNMP and HTTP. Through the SNMP NMS and a Web Browser, you can easily obtain UPS status and through a network, you can configure the network management card.

Features • Remote monitoring and system configuration capabilities.• Event log and metering data— provides historical data of UPS battery

voltage and the event log of UPS status.• Notifications via SNMP Trap and email.• Log in via RADIUS and local authentication.• Supports:

– Network Time Protocol– Telnet configuration– BOOTP/DHCP– Security protocol - HTTPS, SSH, SFTP, and SNMPv3– Syslog for keeping the event log remotely– IPv4 and IPv6– EtherNet/IP protocol

Contents The 1609 Network Management Card package contains the following items.

Table 1 - Package Contents

Quantity Item

1 1609 Network Management Card

1 1609-ENET Installation Instructions

1 1609-ENET Cover

2 Screws

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 7

Page 8: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 1 Introduction

8 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Components This section describes the components of the 1609 Network Management Card.

Table 2 - Ports

Table 3 - Status Indicators

Table 4 - DIP Switch Settings

DIP switch

Reset

Console Port

Network Port Status Indicators

Item Description

Network port Connect to the Ethernet Network

Console port Connect to a VT100 terminal to configure the system or connect to an EnviroProbe to monitor the environmental parameter

Status indicators Indicate operation status

DIP Switch Configure operation mode

Reset Reset the 1609 Network Management Card only, which does not, affect the UPS.

Default IP Address 192.168.1.100

Host name 1609 Network

No. Yellow Light-emitting Diode Green Light-emitting Diode Description

1 --- OFF Hardware or network error

2 Updating (1 sec) --- UPS disconnected

Without EnviroProbe

3 Updating (50 ms) ON Normal operation

With EnviroProbe

4 Updating (50 ms) Updating (50 ms) Normal operation

5 Updating (50 ms) ON EnviroProbe disconnected

No. Dip1 Dip2 Description

1 OFF OFF Normal operation

2 OFF ON Pass Through Mode

3 ON OFF Sensor Mode (with EnviroProbe)

4 ON ON Console Mode

Page 9: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 2

Configuration

Initial Configuration To follow the appropriate instructions, check your network environment to see whether there is a BOOTP/DHCP server on your LAN.

Network with BOOTP/DHCP Server 1. Connect the 1609 Network Management Card to a network with a

networking cable.

2. Open a Web Browser and link the 1609 Network Management Card by typing the IP address or the default host name, 192.168.1.100 or 1609Network in the address bar.

3. Log in as administrator with admin for default account and password for default password.

4. To manage your account and password, go to the System Tab >User Manager.

5. On the User Manager page, select whether to restrict login user to the same LAN or not. Select Only in this LAN to restrict this login account to the same LAN, or select Allow Any to allow this login account to log in from anywhere.

6. Go to the TCP/IP page and change the default host name in the System window.

7. Configure the IP address, Subnet Mask, Gateway IP for the 1609 Network Management Card. If there is no DNS server and you want to receive a notification email, assign an IP address to the mail server.

8. We recommend you to disable the BOOTP/DHCP option and assign a valid static IP address to the 1609 Network Management Card.

9. Go to the Time Server page to synchronize the 1609 Network Management Card and the time server.

Network without BOOTP/DHCP Server

1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, or 7).

2. Use the provided RJ45 to DB9 serial cable to connect the 1609 Network Management Card COM port with the workstation COM port.

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 9

Page 10: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 2 Configuration

3. Set both of the DIP switches of the 1609 Network Management Card to OFF position (normal mode) to enable the network transmission.

4. For the Windows 2000, 2003, 2008, or XP, workstation click the HyperTerminal icon in the Accessories Program Group. For the Windows Vista or Windows 7 workstation, download the Putty software from the Internet to execute the configuration

5. Configure the COM port parameters - 2400 bps, 8 data bits, no parity, 1 stop bit, and no flow control.

6. Set both of the DIP switches of the 1609 Network Management Card to ON position (configuration mode).

A message displays on the screen that prompts you for the account and password.

7. Enter your account (default account is admin) and password (default password is password).

The 1609-ENET card Main Menu shows on the screen. See Configure the 1609 Network Management Card via Text Mode for more information.

Configuration Methods The best way to configure the 1609 Network Management Card is to run the EzSetting software, which you can find in the CD. If you have configured the essential network parameters successfully, you can launch a Web Browser or telnet to the 1609 Network Management Card to execute more detailed configuration. The first thing is to open the User Manager page to change your account and password.

EzSetting Configuration Instructions

1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed).

2. To enable the network transmission, make sure both of the DIP switches of the 1609 Network Management Card are set to OFF position (normal mode).

3. Make sure that the workstation and the 1609 Network Management Card are on the same LAN.

4. Put the provided CD in the CD-ROM drive and find the EzSetting software to launch it.

5. To search all of the 1609 Network devices on the LAN, press the Discover button and then all 1609 Network devices are listed in the Device List as shown in Figure 1.

10 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 11: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Configuration Chapter 2

Figure 1 - Device List

To search all 1609 Network devices in another domain network, change the Subnet and Subnet Mask addresses and then press the Discover button to list them.

If the 1609 Network Management Card cannot be found, check the networking port UDP 3456 in the OS. Open it if it is blocked.

6. To configure the network parameters, select 1609-ENET card device in the Device lists.

7. Click the Modify button

8. Key in your account and password. The default account and password are admin and password respectively. See Figure 2.

Figure 2 - IP and Account Information

9. Click the Configuration button and configure the essential network parameters as shown in Figure 3.

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 11

Page 12: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 2 Configuration

Figure 3 - Configuration

COM Port Configuration Instructions

1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, or 7).

2. Use the provided RJ45 to DB9 serial cable to connect the 1609 Network Management Cards COM port with the workstations COM port.

3. To enable the network transmission, set both of the DIP switches of the 1609 Network Management Card to the OFF position (normal mode) .

4. Windows 2000, 2003, 2008, or XP; Click the HyperTerminal icon in the Accessories Program Group. Windows Vista or 7: To execute the configuration, download the Putty software from the Internet.

5. Configure the COM ports parameters - 2400 bps, 8 data bits, no parity, 1 stop bit and no flow control.

6. Set both of the DIP switches of the 1609 Network Management Card to ON position (configuration mode).

Login message displays on the screen

7. Key in the account (default account is admin) and password (default password is password).

The 1609-ENET card Main Menu shows on the screen.See Text Mode Configuration on page 13 for more information.

12 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 13: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Configuration Chapter 2

Telnet Configuration Instructions

1. Connect the 1609 Network Management Card to a network.

2. Prepare a workstation (Microsoft Windows, Max OSX, or Linux already installed) that has already connected to the same LAN.

3. Set both of the DIP switches of the 1609 Network Management Card to the OFF position (normal mode).

4. For the Windows workstation running DOS Prompt, type telnet HostName or IP to open the telnet connection with the 1609 Network Management Card. For other operating systems, run the OS shell and type the same command.

A login message displays.

5. Enter the account (default account is admin) and password (default password is password).

The 1609-ENET card Main Menu shows on the screen. See Text Mode Configuration on page 13 for more information.

Text Mode Configuration You can configure the 1609 Network Management Card via text mode by using a Telnet utility or through the COM port.

Main Menu

Each item in this 1609-ENET card Main Menu item is described on the following pages.

Figure 4 - Main Menu Screen

IMPORTANT The 1609 Network Management Card terminates the telnet connection if there is not any data transmission within 1 minute.

+========================+| Web Card Main Menu |+========================+Web Card Version 01.00.00MAC Address 00-30-ab-25-e9-1e[1].User Manager[2].TCP/IP Setting[3].Network Parameter[4].Time Server[5].Soft Restart[6].Reset All To Default[z].Exit Without Save[0].Save And Exit

Enter Your Choice =>

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 13

Page 14: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 2 Configuration

User Manager

Table 5 - User Manager Items

+========================+| User Manager |+========================+RADIUS[1].RADIUS Auth: Disable[2].Server: [3].Secret: [4].Port: 1812----------------Local Auth Administrator[5].Account: admin[6].Password: ********[7].Limitation: Only in This LAN Device Manager[8].Account: device[9].Password: ********[a].Limitation: Only in This LAN Read Only User[b].Account: user[c].Password: ********[d].Limitation: Allow Any[0].Back To Previous Menu

Enter Your Choice =>

Item Function Description Default

[1]. RADIUS Auth: Obtain the login authentication from a RADIUS server

Disable

[2]. Server: The RADIUS server name

[3]. Secret: The RADIUS secret

[4]. Port: The RADIUS port number 1812

[5]. Administrator Account Administrator has sole right to modify the 1609 Network settings

admin

[6]. Administrator Password password

[7]. Administrator Limitation Restrict login area for the administrator Only in this LAN

[8]. Device Account Device Manager is not permitted to change the network settings but has the ability to configure the UPS settings

device

[9]. Device Password password

[a]. Device Limitation Restrict login area for the device manager Only in this LAN

[b]. User Account Read Only. User can observe the UPS information only

user

[c]. User Password password

[d]. User Limitation Restrict login area for the user Allow Any

14 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 15: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Configuration Chapter 2

TCP/IP Setting

Figure 5 - TCP/Setting Screen

Table 6 - TCP/IP Setting Items

+========================+| TCP/IP Setting |+========================+[1].IPv4 Address: 192.168.001.100[2].IPv4 Subnet Mask: 255.255.255.000[3].IPv4 Gateway IP: 192.168.001.254[4].IPv4 DNS or WINS IP:192.168.001.001[5].DHCPv4 Client: Enable[6].IPv6 Address: fe80::230:abff:fe25:900[7].IPv6 Prefix Length: 64[8].IPv6 Gateway IP: ::[9].IPv6 DNS IP: ::[a].DHCPv6: Enable[b].Host Name(NetBIOS): 1609Network[c].System Contactor: [d].System Location: [e].Auto-Negotiation: Enable[f].Speed: 100M[g].Duplex: Full[h].Status Stable: 3[0].Back To Previous Menu

Enter Your Choice =>

Item Function Description Default

[1]. IPv4 Address The 1609Network IPv4 address 192.168.001.100

[2]. IPv4 Subnet Mask The IPv4 sub-net mask setting 255.255.255.000

[3]. IPv4 Gateway IP The IPv4 network default gateway 192.168.001.254

[4]. IPv4 DNS IP IPv4 Domain Name Server IP address 192.168.001.001

[5]. DHCPv4 Client Enable/Disable DHCPv4 protocol Enable

[6]. IPv6 Address The 1609Network IPv6 address

[7]. IPv6 Subnet Mask The IPv6 sub-net mask setting

[8]. IPv6 Gateway IP The IPv6 network default gateway

[9]. IPv6 DNS IP IPv6 Domain Name Server IP address

[a]. DHCPv6 Client Enable/Disable DHCPv6 protocol Enable

[b]. Host Name 1609Network

[c]. System Contactor

[d]. System Location

[e]. Auto-Negotiation The network link operation Enable

[f]. Speed 100M

[g]. Duplex Full

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 15

Page 16: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 2 Configuration

Network Parameter

Figure 6 - Network Parameter Screen

Table 7 - Network Parameter Item

+========================+| Network Parameter |+========================+[1].HTTP Server: Enable[2].HTTPS Server: Enable[3].Telnet Server: Enable[4].SSH/SFTP Server: Enable[5].FTP Server: Enable[6].Syslog: Enable[7].HTTP Server Port: 80[8].HTTPS Server Port: 443[9].Telnet Server Port: 23[a].SSH Server Port: 22[b].FTP Server Port: 21[c].Syslog Server1:[d].Syslog Server2:[e].Syslog Server3:[f].Syslog Server4:[g].SNMP Get,Set Port: 161[0].Back To Previous Menu

Enter Your Choice =>

Item Function Description Default

[1]. HTTP Server Enable/Disable HTTP protocol Enable

[2]. HTTPS Server Enable/Disable HTTPS protocol Enable

[3]. Telnet Server Enable/Disable telnet protocol Enable

[4]. SSH/SFTP Server Enable/Disable SSH/SFTP protocol Enable

[5]. FTP Server Enable/Disable FTP protocol Enable

[6]. syslog Enable/Disable remote syslog Disable

[7]. HTTP Server Port HTTP networking port 80

[8]. HTTPS Server Port HTTP networking port 443

[9]. Telnet Server Port Telnet networking port 23

[a]. SSH Server Port SSH networking port 22

[b]. FTP Server Port FTP networking port 21

[c]. Syslog Server1 The remote syslog host name

[d]. Syslog Server2 The remote syslog host name

[e]. Syslog Server3 The remote syslog host name

[f]. Syslog Server4 The remote syslog host name

[g]. SNMP Get, Set Port The SNMP networking port 161

16 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 17: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Configuration Chapter 2

Time Server

There are two ways to set the 1609 Network Management Cards current time and date. One is to set the system time manually. The second and ideal way is to set up a time server for the 1609 Network Management Card. The 1609 Network Management Card can support SNTP, which is supported by MS Windows XP.

To configure a Windows PC to act as a time server, install the Simple TCP/IP Services from the Add/Remove Windows Components.

Table 8 - Time Server Item

Soft Restart

Simply restart the 1609 Network Management Card. It doesn't affect to the UPS.

Reset All To Default

Set all of the settings back to the original default settings.

Exit Without Save

Exit and disregard any change.

+========================+| Time Server |+========================+[1].Time Selection: SNTP[2].Time Zone: +0 hr[3].1st Time Server: POOL.NTP.ORG[4].2nd Time Server:[5].Manual Date: 01/01/2000 (MM/DD/YYYY)[6].Manual Time: 00:00:00 (hh:mm:ss)[0].Back To Previous Menu

Enter Your Choice =>

Item Function Description Default

[1]. Time Selection Select SNTP or manually SNTP

[2]. Time Zone Select time zone +0 hr

[3]. 1st Time Server The first time server for SNTP POOL.NTP.ORG

[4]. 2nd Time Server The second time server for SNTP

[5]. Manual Date Assign the date manually if the Time Selection is selected to Manual

01/01/2000

[6]. Manual Time Assign the time manually if the Time Selection is selected to MAnual

00:00:00

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 17

Page 18: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 2 Configuration

Save And Exit

Preserve your change(s) and exit.

18 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 19: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 3

Web Interface

Login 1. Verify that you have a TCP/IP network already installed.

2. Launch your web browser.

3. Enter http: //host_name or http: //ip_address in the address bar for the plain text web transmission or https: //host_name or https: //ip_address for the encrypted web transmission.

4. Enter your account and password.

The home page appears.

IMPORTANT If the login page can be displayed but you are unable to log in with the correct account and password, it can be because that the login in IP address differs from the 1609-ENET cards subnet, see Troubleshooting Topic 3 on page 41

TIP The 1609 Network Management Card logs the user out automatically if there is not any data transmission through HTTP/HTTPS for more than 30 minutes.

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 19

Page 20: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 3 Web Interface

Monitor Information This section includes the information of identification, battery voltage, battery status, and operation status. The web pages can vary depending on the UPS.

UPS Properties

This page gives a snapshot of all principal UPS parameters. The values update automatically.

Figure 7 - UPS Properties

Battery Parameters

Battery parameters menu lists the battery status and specifications.

Figure 8 - Battery Parameters

TIP To set the refresh time, select the menu Administration >Web >Web Refresh Period.

20 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 21: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Web Interface Chapter 3

In/Out Parameters

Select In/Out Parameters from the UPS Information on the main menu to get a list of the UPS input, output, and bypass parameters

Figure 9 - In/Out Parameters.

Identification

Select Identification from the UPS Information menu of the home page to get a list of the UPS Identification Parameters.

Figure 10 - Identification

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 21

Page 22: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 3 Web Interface

Status Indication

This page lists all UPS events and indicates which event occurs by turning the lamp on or off.

Figure 11 - Status Indication

Monitor History Event Log

This table lists all events that have occurred. The existing values are overwritten when the maximum number of entries (rows) has been reached. You can also download all event log to your computer.

Figure 12 - Event Log

• Date: The date when the UPS event occurred• Time: The time when the UPS event occurred• Level: The event level of the UPS event occurred• Event Log: The description of the UPS event occurred

22 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 23: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Web Interface Chapter 3

• Download Event Log from UPS: The 1609-ENET card first sends the request to the UPS to collect the event log kept in the UPS, then repliesto the user through the network. (1)

Data Log

This table lists all saved UPS data. The existing values are overwritten when the maximum number of entries has been reached. You can also download the assigned period of the data log to your computer.

• Date: Date on which the recording was made.• Time: Time on which the recording was made.• Battery Voltage: The battery voltage in Volts at the time of recording.

Configure

This page lets the Device Manager clear the event log, data log and assign the time period to save data log.

• Clear History Data: Clear the event log• Clear Event Log: Clear the data log• Save Data Interval: To assign the time period to save to the data log.

Device Management The following lists and describes the functions under Device Management.(2)

Configure

The configure web page is designed to set the configuration values to the UPS or 1609-ENET card. Those values are kept in the UPS or 1609-ENET card to change the behavior or reaction of the UPS.

Figure 13 - Configure

(1) Note that this option appears only when the UPS supports this function and the event log in the UPS differs from the event log in the 1609-ENET card.

(2) UPS configuration options vary.

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 23

Page 24: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 3 Web Interface

Auto Restart

Send the command to the UPS to configure the auto restart function.

UPS Buzzer

Send the command to the UPS to configure the buzzer function.

Transfer Voltage

Send the command to the UPS to set the range of transfer voltage.

Low Battery

Keep the setup values in the card then compare with the received value from the UPS. If the received battery level is lower than the assigned value, then the card sends out the Low Battery alarm.

UPS Shutdown Action

Keep the setup values in the card then check the received status from the UPS. If a Power Fail or Battery Low event occurs, then send the assigned shutdown delay time to the UPS.

Smart Shutdown

Used to shut down all connected computers and the UPS safely by one click.

Battery Replacement Date

After the battery replacement dates are assigned, the card then send the command to store these date information in the UPS.

Control

This menu lets you send the control commands to the UPS

Figure 14 - Control.

24 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 25: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Web Interface Chapter 3

Battery Test

Send the command to the UPS to perform the battery test.

Shutdown and Restart UPS Only

Send the command to the UPS to perform the shutdown and/or restart UPS immediately.

• To shut down the UPS, check UPS Shutdown Delay and choose the delay time.

• To restart the UPS, check the UPS Restart Delay and choose the delay time.

• To shut down and then restart the UPS, check UPS Shutdown Delay, and UPD Restart Delay and choose both of the delay times.

Smart Shutdown

The Smart Shutdown mechanism is used to shut down all connected computers and the UPS safely with one click.

Power Fail/Restore Simulation

Power fail/restore simulation causes the card to simulate the UPS power fail or power restore event. Based on this function, we can test all connected software to verify whether they work properly or not.

The UPS remains in its original state and not go into battery mode.

Weekly Schedule

Modify the parameters of the shutdown/restore/test events that are associated with the days of the week

Figure 15 - Weekly Schedule.

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 25

Page 26: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 3 Web Interface

Specific Schedule

Modify the parameters of the shutdown/restore/test events that are associated with certain days of the year

Figure 16 - Specific Schedule.

Event Level

The event level can be changed in this web page. You can change the event report through email or SNMP trap by modifying the event level.

Figure 17 - Event Level

System Administration User Manager

The 1609 Network Management Card supports the RADIUS. You can assign your RADIUS server to the card for the login authentication through HTTP,

26 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 27: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Web Interface Chapter 3

Telnet, SSH, FTP, SFTP, and EzSetting. If the RADIUS option is disabled, manage the login authentication locally by assigning three different levels of users account and password

Figure 18 - User Manager.

TCP/IP

This menu lets the administrator set the local network configuration parameters in 1609 Network Management Card.

Figure 19 - TCP/IP

IPv4 Settings• DHCP Client: Enable/Disable DHCP to get the IP address from

DHCP server.

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 27

Page 28: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 3 Web Interface

• IP address: The IP address of the card in dotted format (for example, 192.168.1.100).

• Subnet Mask. The Subnet Mask for your network (for example, 255.255.255.0).

• Gateway IP: The IP address of the network gateway in dotted format (for example, 192.168.1.254).

• DNS IP: The IP address of the domain name server in dotted format (for example, 192.168.1.1).

• Search Domain: The system domain name, if the host name you provided cannot be searched then the system appends the search domain to your Host name.

IPv 6 Settings• DHCP Client: Enable/Disable DHCP to get the IP address from the

DHCP server. • IP address: The IPv6 address of the card. • Prefix Length. The prefix length for the IPv6 address.• Gateway V6IP: The IP address of the IPv6 network gateway.• DNS V6IP: The IP address of the IPv6 domain name server.

System Settings• Host Name: The SNMP host name in the network.• System Contact: The system contactor information for SNMP

network administration string.• System Location: The system installed location for SNMP network

administrator string.

Web

Enable or disable the HTTP/HTTPS communication protocols available in the 1609 Network Management Card with this menu.

Figure 20 - Web

28 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 29: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Web Interface Chapter 3

Web Settings• HTTP: Enable or disable the HTTP connection with the 1609

Network Management Card.• HTTPS: Enable or disable the HTTPS connection with the 1609

Network Management Card.• HTTP Port: The user can configure HTTP protocol to use a port

number other than standard HTTP port (80).• HTTPS Port: The user can configure HTTPS protocol to use a port

number other than standard HTTPS port (443).• Web Refresh Period: The period that the web page updates.

SSL Certificate Settings• Certificate File: This option is used to replace your own SSL certificate

file. The 1609 Network-SSL 1609-ENET card supports PEM format that the Open SSL generates. See Troubleshooting item 12 on page 42

Console

The administrator can enable or disable the Telnet/SSH communication protocols available in the 1609 Network Management Card with this menu

Figure 21 - Console.

Console Settings• Telnet: Enable or disable the Telnet connection with the 1609 Network

Management Card.• SSH/SFTP: Enable or disable the SSH/SFTP connection with the

1609 Network Management Card.• Telnet Port: You can configure Telnet protocol to use a port number

other than standard Telnet port (23).

SSH Port: You can configure SSH protocol to use a port number other than standard SSH port (22).

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 29

Page 30: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 3 Web Interface

Host Key Settings• DSA/RSA Key: These options are used to replace your own SSH keys.

The 1609Network-SSL 1609-ENET card supports the key files the OpenSSH generates. Refer to Upload the DSA and RSA key files to the 1609 Network Management Card through the web page. on page 42 for more information

FTP

The administrator can enable or disable the FTP communication protocols available in the 1609 Network Management Card with this menu.

Figure 22 - FTP

FTP Settings• FTP: Enabling or disabling the FTP connection with the 1609

Network Management Card.• FTP Port: You can configure FTP protocol to use a port number other

than standard FTP port (21).

Time Server

You set the 1609 Network Management Card internal date and time with this menu. There are two ways to set the date and time. Synchronize with SNTP server or set the date and time by manual.

If the SNTP is enabled but cannot get any reply from the assigned time server then the event log and data log do not function.

30 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 31: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Web Interface Chapter 3

Figure 23 - Time Server

Simple Network Time Server• Time Zone: Select the time zone where the 1609 Network

Management Card is installed.• Primary/Secondary Time Server: The 1609 Network Management

Card searches both of the time servers and follows the first reply servers time. The card synchronizes with the time server every hour.

• Enable Daylight Saving: This option is used to set up Daylight Saving Time. During the period of Daylight Saving Time, the 1609 Network Management Card adds 1 hour automatically.

Manual• If it is not possible to connect to a time server, then the only way to

adjust the system time is to manually configure the date and time. The system date and time is back to the assigned date/time if the 1609 Network Management Card is restarted.

Syslog

This menu lets the administrator set the 1609 Network Management Card syslog. The syslog feature is used to store the event log to the remote syslog servers. This feature does not affect to the local event log

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 31

Page 32: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 3 Web Interface

Figure 24 - Syslog.

Batch Configuration

If you are the administrator and you have finished one site configuration of the 1609 Network Management Card, you can copy the same configuration to the other 1609-ENET cards by distributing the configuration files.

Only delete the lines that you dont want to distribute. If the IP address is static, you must delete the line of IP= xxx.xxx.xxx in the [System] section. The batch configuration can work through the FTP, too.

Figure 25 - Batch Configuration

Upgrade

1609 Network Management Card provides the easiest way to upgrade the 1609-ENET card firmware through the web interface. Assign the firmware file from your local disk then press the Upload button to transmit the specific

32 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 33: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Web Interface Chapter 3

firmware file to the 1609-ENET card for upgrading. For the latest 1609-ENET and 1609-D firmware update, visit http://www.ab.com.

Figure 26 - Upgrage

System Notification SNMP Access

The 1609 Network Management Card supports the SNMP protocol. You can use the SNMP NMS to manage a UPS through a network. You must enter the IP address of the workstation in the SNMP Access Table to help prevent any unauthorized users from configuring the 1609 Network Management Card via SNMP protocol. The maximum number of IP is 256

Figure 27 - SNMP Access.

To use a workstation with SNMP Manager installed, or set a more restrictive access to the management card, you can use the SNMP Access to add the IP address of the PC that you want to modify the access permission.

If the IP address is set as 0.0.0.0, it means the IP address can be ignored. The 1609 Network Management Card will check the community string first to identify if the incoming packet is read only. If identical, the 1609 Network Management Card will respond to the inquiry.

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 33

Page 34: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 3 Web Interface

SNMPv3 USM (User-based Security Management)

There are 8 SNMPv3 users list for the 1609 Network Management Card. After configuring the account parameters you can access the card through the SNMPv3 protocol. This user table is related to the SNMPv3 Trap, too

Figure 28 - SNMPv3 USM (User Based Management).

SNMP Trap

If you use a PC and perform the SNMP Manager Trap function to manage a UPS through the 1609 Network Management Card, you must add the IP address of the PC to the SNMP Trap list. The maximum number of SNMP trap target is 256

Figure 29 - SNMP Trap.

The Event Level field is used to decide what kind of power events notification should be sent to the target address. There are 3 levels of power events: Information, Warning and Alarm. If you select Information, the notification of all power events will be sent to the target address; if you select Warning, the notification of Warning event as well as Alarm event will be sent to the target

34 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 35: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Web Interface Chapter 3

address; if you choose Alarm, only the notification of Alarm event will be sent to the target address.

The 1609 Network Management Card provides SNMPv1, v2c and v3 trap to satisfy most of customers environment. If you select to use the SNMPv3 trap then provide one of the user names in the SNMPv3 USM table.

Mail Server

The administrator can set up the SMTP Server and the e-mail receiver so the designated recipient can receive the e-mail notification from the 1609 Network Management Card whenever a power event occurs. The maximum number of e-mail user is 256.

Figure 30 - Mail Server

• SMTP Server Name or IP This is the host name of a SMTP Mail Server used to send the email message from the 1609 Network Management Card. When entering a host name, you are also required to enter the DNS IP in the TCP/IP.

• Account: Mail Servers login account.• Password: Mail Servers login password. • Receiver: Enter the email address for the 1609 Network Management

Card to send an e-mail.• Event Level: Select the event level that you wish to send the

corresponding e-mail notification to the recipient. – Information: the notification of all power events will be sent to the

target address– Warning: the notification of Warning event as well as Alarm event

will be sent to the target address.

TIP You can change the event level from UPS Management – Event Level.

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 35

Page 36: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 3 Web Interface

– Alarm: only the notification of Alarm event will be sent to the target address.

Wake On LAN

Wake On LAN function could start up client PC from network by MAC address. From this page, you can set 256 MAC addresses of clients to be awakened after power restore or the 1609-ENET card startup.

Figure 31 - Wake On Lan

EtherNet/IP Ethernet/IP is a real time Ethernet protocol based on the standard TCP/IP protocols. For further information on Ethernet/IP see: http://www.odva.org

The basic configuration for an EtherNet/IP System includes the 1609-ENET card, a switching hub, a PC or a PLC.

Figure 32 - EtherNet/IP

TIP You can change the event level from UPS Management – Event Level.

36 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 37: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Web Interface Chapter 3

Use the following parameters in TCP/IP web page for the EtherNet/IP configuration.

Figure 33 - TCP/IP Settings

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 37

Page 38: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 3 Web Interface

Notes:

38 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 39: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 4

Specifications

Technical and Environmental Specifications

Table 9 - Technical Specifications

Table 10 - Environmental Specifications

Attribute 1609-ENET

Network Connection RJ45 connector

Temperature, operating 0 …40 °C (32 …104 °F)

Humidity, operating 10… 80 %

Power Input 9…24V DC

Power Consumption, Max 2 W

Dimensions (L x W), Aprox 130 x 60 mm (5.12 x 2.36 in.)

Weight, Aprox 75 g (0.17 lb)

Part Name(1)

(1) The Environmental Protection Use Period (EPUP) of the product is marked on the rating label found on the UPS.

Toxic and Hazardous Substances or Elements(3) (4)

(3) O:Indicates the content of toxic and hazardous substance (at the homogeneous material level) is lower than the MCV defined by the standard of SJ/T11363-2006.

(4) X: Indicates the content of toxic and hazardous substance (at the homogeneous material level) is over the MCV defined by the standard of SJ/T11363-2006.

Lead (Pb)

Mercury (Hg)

Cadmium (Cd)

HexavalentChromium(Cr 6+)

Poly-brominated Biphenyls (PBB)

Poly-brominated Diphenyl Ethers (PBDE)

Metal Shell O O O O O O

Plastic Shell O O O O O O

Printed Circuit Board(2)

(2) Printed circuit board includes empty printed circuit boards and their components

X O O O O O

Receptacle X O O O O O

Cable and Wire X O O O O O

Connector and Breaker

O O X O O O

Sealed Lead Acid Battery

X O O O O O

Transformer O O O O O O

Others X O O O O O

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 39

Page 40: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 4 Specifications

Notes:

40 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 41: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 5

Troubleshooting

Troubleshooting Guide Table 11 - Issue Descriptions and Corrective Actions

No. Issue Description Possible Solution or Corrective Action

1 How to provide an SNTP (Simple Network Time Protocol) server for the 1609 Network Management Card?

Windows XP operating system:1. Click Start 2. Click Control Panel 3. Click Add/ Remove Programs4. Click Add / Remove Windows Components 5. Click Networking Services 6. Check Simple TCP/IP Services7. Click OK to finish the installation of Simple TCP/IP Services.

After that, key in the hosts IP Address on the Time Server page.

2 How to make sure that the network connection is established between my workstation and the 1609 Network Management Card?

• Check the network connection by typing the following command ping HostName or IP at your workstation.

3 In the Web Browser, I can see the Login page but cannot log in.

• Check the IP Addresses of the 1609-ENET card and the Personal Computer you try to log in. If both of the IP Addresses are not on the same LAN, run the EzSetting to configure the User Limitation to:

4 How to refresh the NetBIOS™ table in Windows operating system?

• Sometimes the IP Address of the 1609 Network Management Card is changed but the host name remains the same. Although Windows updates its NetBIOS table periodically, you can force it to purge its cache immediately by typing the command nbtstat –R in the shell. After that, you can connect to the 1609 Network Management Card by its host name.

5 How to get the IP Address and Media Access Control Address from my computer?

• For Windows system, type ipconfig /all in DOS prompt. For UNIX system, key in ifconfig in the shell

6 Unable to ping or connect to the 1609 Network Management Card?

• Check all network connections. Verify that your Personal Computer and the 1609 Network Management Card are in the same network segment. If you don't have a router, they must be in the same network segment.

• You can connect to the 1609 Network Management Card only if your Personal Computer and the 1609 Network Management Card is using the IP Addresses from the same address block. Normally, private LANs use the IP Addresses from one of the following blocks.

• 10.0.0.0 ~ 10.255.255.255172.16.0.0 ~ 172.31.255.255192.168.0.0 ~ 192.168.255.255

• The 1609 Network Management Cards default IP Address (192.168.1.100) is from the last block. If your LAN is using another address block, you won’t be able to connect to the 1609 Network Management Card via the LAN. Under such situation, you can choose to: Use the Terminal Mode to reset the 1609 Network Management Cards IP Address.Change your Personal Computer's IP Address to allow connection via the LAN.

7 Unable to perform SNMP Get operation?

• Check the SNMP settings that are stored in the 1609 Network Management Card. The IP Address of the Personal Computer you are using must be entered in one of the SNMP Access Control NMS IP fields, with Read or Read/Write permission. The community string on the Personal Computer and the 1609 Network Management Card must match.

8 Unable to perform SNMP Set operation?

• Check the SNMP settings that are stored in the 1609 Network Management Card. The IP Address of the Personal Computer you are using must be entered in one of the SNMP Access Control NMS IP fields, with Read/Write permission. The community string on the Personal Computer and the 1609 Network Management Card must match.

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 41

Page 42: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Chapter 5 Troubleshooting

9 Unable to receive traps at my management station?

• Check the SNMP Trap settings on the 1609 Network Management Card. The IP Address of the Personal Computer you are using must be entered in one of the Target IP fields.

10 Forgot the administrators account and password?

• Connect the RJ45 to DB9 serial cable to the console port and set both of the DIP switches of the 1609 Network Management Card to ON position (configuration mode). Key in rstadmin within 30 seconds while the account and password are prompted. After that, the administrators account and password are now reset to default values.

11 About IPv6 support? • For every device that supports IPv6, it has an LLA (Link Local Address) generated according to its own Media Access Control Address (MAC ID) and the EUI-64 standard algorithm. For example, if the MAC ID is 00:11:22:33:44:55, the LLA is fe80::211:22ff:fe33:4455. As this Insight-Power1609-ENET card can support IPv6, you can directly link the 1609-ENET card via LLA without any additional configuration. According to RFC-4862, the IPv6 interface automatically shuts down if the same LLA has previously existed on the LAN.

• If both of the IPv4 and IPv6 DNS configurations co-exist, the IPv4 DNS configuration has the top priority.• If your operating system is Windows XP, enable IPv6 first (select RUN from START and enter ipv6 install).• To know more about IPv6 compatibility information, see RFC documents (1981, 2460, 4861, 4862, and 4443) on IETF

Website (http://tools.ietf.org/html), or see IPv6 Ready Logo Website (http://www.ipv6ready.org).

12 How to generate a private SSL certificate file (PEM format) for HTTPS?

• Download the openssl from http://www.openssl.org and install it in the Linux.• Open the command shell and key in the following command to create your own certificate file:• Openssl req –x509 –nodes –days 3650 –newkey rsa:1024 –keyout cert.pem –out cert.pem• Answer to the questions, once it is completed the cert.pem is created in the current working directory. • Upload the cert.pem file to the 1609 Network Management Card through the web page.

13 How to generate the SSH DSA and RSA keys for SSH?

For Linux Version:

• Download and install the openssh from http://www.openssh.org .• Open the command shell and key in the following command to create your own keys: Ignore to provide the key

passphrase while it ask.• DSA Key:ssh-keygen –t dsa• RSA Key:ssh-keygen –t rsa• Upload the DSA and RSA key files to the 1609 Network Management Card through the web page.

For Windows Version:

• Download and install the Putty from http://www.putty.org.• Run the puttygen.exe in the putty installed directory.• Select SSH-2 RSA from the Parameters area and select the Generate key pair from the Key menu to generate the RSA key• Select Export OpenSSH Key from the Conversions menu and assign a file name for the RSA key. Ignore to provide the key

passphrase while it ask.• Select SSH-2 DSA from the Parameters area and select the Generate key pair from the Key menu to generate the DSA key.• Select Export OpenSSH Key from the Conversions menu and assign a file name for the DSA key. Ignore to provide the key

passphrase while it ask.• Upload the DSA and RSA key files to the 1609 Network Management Card through the web page.

No. Issue Description Possible Solution or Corrective Action

42 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 43: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Appendix A

EtherNet/IP Object Service

EtherNet/IP is an object orientated protocol. The Object Oriented structure therefore allows for classes, instances, attributes and services. The ‘data types’ listed below are to be considered as the objects supported in the protocol. Each of these has attributes that have been supported to differing degrees.

Object Descriptions and Service Support

Table 12 - Object Descriptions and Service Support

Object Name Class Code Description Service Support

Identity 0x01 Attributes Supported: One instance supported (0x01) Attributes List: Details  such as Appendix B

Services Supported: Get_Attribute_All Get_Attribute_Single Reset

Message Router 0x02 Attributes Supported: One instance supported (0x01) Attribute List: Max Connections

Services Supported: Get_Attribute_Single

Assembly 0x04 Attributes Supported: Class Instance Support (0x00) Class Attributes: 0x02 (Max Instance) three instances supported (Input 0x30,Output 0x31 and Configure 0x32)

Services Supported:Get_Attribute_SingleCreate (Instance)Delete (Instance)Insert_MemberRemove_Member

Connection Manager 0x06 Forward Open Service Forward Close Service

TCP/IP Interface Object 0xF5 Attributes Supported: One instance supported (0x01) Attribute List: Details  such as, Appendix B

Services Supported: Get_Attribute_AllGet_Attribute_Single Set_Attribute_Single

Ethernet Link Object 0xF6 Attributes Supported: One instance supported (0x01) Attribute List: Details  such as Parameters Table Physical Address

Services Supported: Get_Attribute_AllGet_Attribute_Single

UPS Object 0x377 Attributes Supported: One instance supported (0x01) Attribute List:Details  such as Appendix B

Services Supported: Get_Attribute_SingleSet_Attribute_Single

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 43

Page 44: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Appendix A EtherNet/IP Object Service

Return Codes and Descriptions

Table 13 - Return Codes and Descriptions

Return Code Name Description

Service

  0x00 Success Service was successfully performed by the object specified.

0x0F Privilege violation A permission/privilege check failed

0x08 Service not supported The requested service was not implemented or was not defined for this Object Class/Instance.

Forward

Open 0x01 Connection failure A connection related service failed along the connection path.

Attribute Single

Get/Set 0x14 Attribute not supported

The attribute specified in the request is not supported

Get 0x2C Attribute not get table A request to read a non-readable attribute was received

Set 0x13 Not enough data The service did not supply enough data to perform the specified operation.

Set 0x15 Too much data The service supplied more data than was expected

Set 0x0E Attribute not settable A request to modify a non-modifiable attribute was received.

Set 0x03 Invalid parameter value

See Status Code 0x20, which is the preferred value to use for this condition.

Assembly

MemberInsert / Remove

0x05 Path destination unknown

The path is referencing an object class, instance or structure element that is not known or is not contained in the processing node. Path processing shall stop when a path destination unknown error is encountered.

InstanceCreate/Delete

0x03 Invalid parameter value

See Status Code 0x20, which is the preferred value to use for this condition.

44 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 45: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Appendix B

EtherNet/IP Parameters

Object Attributes and Descriptions Table 14 - Identity Object (0x01)

Attribute ID Rule Name Data Type Description of Attribute

1 Get Vendor ID UINT Identification of each vendor by number

2 Get Device Type UINT Indication of general type of product

3 Get Product Code UINT Identification of a particular product of an individual vendor

4 Get Revision STRUCT of Revision of the item the Identity Object represents

Major USINT —

Minor USINT —

5 Get Status WORD Summary status of device

6 Get Serial Number UDINT Serial number of device

7 Get Product Name SHORT_STRING Human readable identification

8 Get State USINT Present state of the device as represented by the state transition diagram

Table 15 - TCP/IP Interface Object (0xF5)

Attribute ID Rule Name Data Type Description of Attribute

1 Get Status DWORD Interface status

2 Get Configuration Capability DWORD Interface capability flags

3 Set Configuration Control DWORD Interface control flags

4 Get Physical Link Object STRUCT of Path to physical link object

Path size UINT Size of Path

Path Padded EPATH Logical segments identifying the physical link object

5 Set Interface Configuration STRUCT of TCP/IP network interface configuration.

IP Address UDINT The device's IP address.

Network Mask UDINT The device's network mask

Gateway Address UDINT Default gateway address

Name Server UDINT Primary name server

Name Server 2 UDINT Secondary name server

Domain Name STRING Default domain name

6 Get/Set Host Name STRING Host name

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 45

Page 46: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Appendix B EtherNet/IP Parameters

Table 16 - Ethernet Link Object (0xF6)

Attribute ID Rule Name Data Type Description of Attribute

1 Get Interface Speed UDINT Interface speed currently in use

2 Get Interface Flags DWORD Interface status flags

3 Get Physical Address ARRAY of 6 USINTs MAC layer address

Table 17 - UPS Object (0x377)

Attribute ID

Need Access Rule NV Name Data Type Description of Attribute Semantics of value

1 Required Get NV Output Rating STRUCT of: The magnitude of the nominal output —

NV VA INT VA rating —

NV Voltage INT Voltage rating —

NV Frequency INT Frequency rating —

2 Required Get NV Input Rating STRUCT of: The magnitude of the nominal input —

NV Voltage INT Voltage rating —

NV Frequency INT Frequency rating —

3 Required Get NV RatingBatteryVoltage INT The magnitude of the nominal battery voltage rating

4 Required Get NV LowTransferVoltage STRUCT of: The Setup of low line input voltage that allowed the UPS system transfers to the battery source

NV UpBound INT The maximum voltage limited for the LowTransferVoltage

NV LowBound INT The minimum voltage limited for the LowTransferVoltage

5 Required Get NV HighTransferVoltage Array ofSTRUCT of:

The Setup of high line input voltage that allowed the UPS system transfers to the battery source

NV UpBound INT The maximum voltage limited for the HighTransferVoltage

NV LowBound INT The minimum voltage limited for the HighTransferVoltage

6 Required Get NV UPS Type INT Indicate the UPS type on-line(1)off-line(2),line-interactive(3),three-phase(4),splite-phase(5)All other values reserved

7 Required Get/Set NV AutoReboot INT In backup mode, the UPS may shutdown normally by SDA command, dry-contact remote shutdown signal or low battery shutdown. This command is used to determine the unit should restart or not next time when the power restores

on(1),off(2)All other values reserved

8 Required Get/Set V ShutdownAction INT If the value is greater than 0 the UPS performs shutdown action that defined by ShutdownType after the seconds. 0, aborted

9 Required Get/Set V RestartAction INT UPS will restart after the indicated number of minutes. -1, aborted

10 Required Get/Set NV BuzzerAlarm UINT UPS will keep silence but will alarm again when next power event is occurred

alarm(1),silence(2)

11 Required Get/Set NV BuzzerState INT If it is disabled then the UPS is always muted enable(1),disable(2)

12 Required Get/Set NV Sensitivity INT The sensitivity of the UPS to utility line abnormalities or noises

normal(0),reduced(1),low(2)

46 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 47: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

EtherNet/IP Parameters Appendix B

13 Required Get/Set NV LowVoltageTransferPoint INT The input minimum line voltage allowed before the UPS system transfers to battery backup

14 Required Get/Set NV HighVoltageTransferPoint INT The input maximum line voltage allowed before the UPS system transfers to battery backup

15 Required Get/Set V ShutdownOSDelay INT The operating system shutdown delay time when the input power fail

16 Required Get/Set NV UPSBootDelay UINT Delay the UPS startup after power restores. The power quality may not stable when power restores, this feature let the UPS wait a period of time to startup the system

17 Required Get/Set NV ExternalBatteryPack INT Indicate the number of external battery pack —

18 Required Get V InputNumLines INT The number of input lines utilized in this device Limited 1

19 Required Get V Input Line Value STRUCT of: The current input values for up to InputNumLines —

Frequency INT Line frequency to the UPS system in 1/10 Hz

Voltage 1 INT Line voltage of the UPS system in 1/10 V

20 Required Get V OutputSource INT The present source of output power. The enumeration none(7) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker

normal(0),battery(1),bypass(2),reducing(3),boosting(4),manualBypass(5),other(6),none(7)

21 Required Get V OutputFrequency INT The present output frequency in 1/10 Hz —

22 Required Get V OutputNumLines INT The number of output lines utilized in this device —

23 Required Get V

Output Line Status Array ofSTRUCT of:

The Output Line values for up to OutputNumLines

Voltage INT line voltage of the UPS system in 1/10V

Current INT line current of the UPS system in 1/10 A

Power INT line eal power of the UPS system in watts

Load INT line load expressed in percent of rated capacity

24 Required Get V BatteryCondition INT The indication of the capacity remaining in the UPS system's batteries when AC normal.

good(0),weak(1),replace(2)

25 Required Get V BatteryStatus INT

The indication of the capacity remaining in the UPS system's batteries when AC failed. A value of ok indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of low indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of depleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).

ok(0),low(1),depleted(2)

Table 17 - UPS Object (0x377)

Attribute ID

Need Access Rule NV Name Data Type Description of Attribute Semantics of value

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 47

Page 48: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Appendix B EtherNet/IP Parameters

26 Required Get V BatteryCharge INT —

floating(0),charging(1),resting(2),discharging(3)

27 Required Get V BatteryEstimatedTime INT Estimated time from backup to low battery shutdown —

28 Required Get V BatteryVoltage INT The magnitude of the present battery voltage in 1/10 V —

29 Required Get V BatteryCapacity INT An estimate of the battery charge remaining expressed as a percent of full charge —

30 Required Get V Battery Temperature INT The ambient temperature at or near the UPS Battery casing °C

31 Required Get/Set V TestType INT Perform the UPS Test procedure

abort(0),generalTest(1),batteryTest(2),testFor10sec(3),testUntilBattlow(4)

32 Required Get V TestResultsSummary INT

The results of the current or last UPS diagnostics test performed. The values for donePass(1), generalTestFail(3), and batteryTestFail(4) indicate that the test completed either successfully, with a warning, or with an error, respectively. Tests which have not yet concluded are indicated by inProgress(2). The value noTestsInitiated(0) indicates that no previous test results are available.

noTestsInitiated(0),donePass(1),inProgress(2),generalTestFail(3),batteryTestFail(4),deepBatteryTestFail(5)

Table 17 - UPS Object (0x377)

Attribute ID

Need Access Rule NV Name Data Type Description of Attribute Semantics of value

48 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 49: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

EtherNet/IP Parameters Appendix B

33 Required

Get V Alarm DWORD UPS Alarm status

off(0),on(1)— —

Disconnect bit 0 Does the UPS disconnect?

PowerFail bit 1 Does the input power fail?

BatteryLow bit 2 Are the UPS batteries low?

LoadWarning bit 3 Does the UPS load percent over the load warning value?

TestInProgress bit 4 Does the UPS test in progress?

BatteryTestFail bit 5 Does the UPS test fail?

OutputOverload bit 6 Does the UPS output overload?

InverterAbnormal bit 7 Does the UPS inverter abnormal?

ReserveAbnormal bit 8 Does the UPS reserve abnormal?

OverTemperature bit 9 Does the UPS overheat?

OutputBad bit 10 Is the UPS output abnormal?

UPSOff bit 11 Is the UPS in standby mode?

ChargerFail bit 12 Does the UPS charger fail?

FanFail bit 13 Does the UPS fan fail?

OutputOff bit 14 Indicates whether the UPS output is turned off or not

SmartShutdown bit 15 Indicates whether the Smart Shutdown is in progress

UPSShutdown bit 16 UPS shutdown

Reserved bit 17-31 Reserved for future use and shall be set to zero

Table 17 - UPS Object (0x377)

Attribute ID

Need Access Rule NV Name Data Type Description of Attribute Semantics of value

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 49

Page 50: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Appendix B EtherNet/IP Parameters

Notes:

50 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 51: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Appendix C

EtherNet/IP IO Data Mapping

If you want to control the UPS device just over the UDP (I/O Connection) Interface, it is sufficient to use the mapping described. This section describes the mapping. The different mappings over different instances are selected in the assembly class.

Configuration Assembly Table 18 - Configuration Assembly

Consumed (Output) Assembly Table 19 - Consumed (Output) Assembly

Instance 0x64 – Configure Assembly (14 Bytes)

Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

0 Configuration Revision Number

1 — — — — Sensitivity High Bit

Sensitivity Low Bit

Buzzer Enable

AutoReboot

2 Low Voltage Transfer Point (low byte)

3 Low Voltage Transfer Point (high byte)

4 High Voltage Transfer Point (low byte)

5 High Voltage Transfer Point (high byte)

6 Shutdown Delay (low byte)

7 Shutdown Delay (high byte)

8 Boot Delay (low byte)

9 Boot Delay (high byte)

10 External Battery Pack (low byte)

11 External Battery Pack (high byte)

Instance 0x65 –Consumed (Output) Assembly

Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

0 — — — — — Restart Bit ShutDown Bit SilenceAlarm

1 Perform Test Procedure

2 Shutdown Seconds (low byte)

3 Shutdown Seconds (high Byte)

4 Restart Seconds (low byte)

5 Restart Seconds (high byte)

Rockwell Automation Publication 1609-UM008A-EN-P - June 2017 51

Page 52: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Appendix C EtherNet/IP IO Data Mapping

Produced (Input) Assembly Table 20 - Produced (Input) Assembly

Instance 0x66 describes another input (produced) assembly for the 1609-UPS.

Instance 0x66 – Produced (Input) Assembly

Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

0

Reserved for Logix (Logix sets to 0xffff whenever the connection is not established. UPS sets to 0x0000.)1

2

3

4 Reserved UPSShutDown OutputOff UPSOff Output Source Boosting

Output Source Reducing

Output Source Battery

Output Source Normal

5 ReservedAC Failed Battery

Depleted

AC Failed BatteryLow

AC Failed Battery OK

AC Normal Battery Replace

AC Normal Battery Weak

AC Normal Battery Good

6 — — — — Battery Discharging Battery Resting Battery

Charging Battery Floating

7 — — — OutputBad OverTemperature OutputOverLoad Load Warning Power Fail

8 — — — Smart Shutdown Disconnect InverterAbnormal FanFail ChargerFail

9 — — — Battery Deep Test Fail Battery Test Fail General Test Fail Test Passed Test In Progress

10 OutputVoltage (low byte)

11 OutputVoltage (high Byte)

12 OutputCurrent (low byte)

13 OutputCurrent (high byte)

14 OutputPower (low byte)

15 OutputPower (high byte)

16 OutputLoad (low byte)

17 OutputLoad (high byte)

18 OutputFrequency (low byte)

19 OutputFrequency (high byte)

20 BatteryVoltage (low byte)

21 BatteryVoltage (high byte)

22 BatteryCapacity (low byte)

23 BatteryCapacity (high byte)

24 BatteryEstimatedTime (low byte)

25 BatteryEstimatedTime (high byte)

26 BatteryTemperature (low byte)

27 BatteryTemperature (high byte)

52 Rockwell Automation Publication 1609-UM008A-EN-P - June 2017

Page 53: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,
Page 54: Bulletin 1609 UPS Network Management Card...1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or later installed). 2. To enable the network transmission,

Publication 1609-UM008A-EN-P - June 2017Copyright © 2017 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

Rockwell Automation SupportUse the following resources to access support information.

Documentation FeedbackYour comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.

Technical Support Center Knowledgebase Articles, How-to Videos, FAQs, Chat, User Forums, and Product Notification Updates. https://rockwellautomation.custhelp.com/

Local Technical Support Phone Numbers Locate the phone number for your country. http://www.rockwellautomation.com/global/support/get-support-now.page

Direct Dial Codes Find the Direct Dial Code for your product. Use the code to route your call directly to a technical support engineer. http://www.rockwellautomation.com/global/support/direct-dial.page

Literature Library Installation Instructions, Manuals, Brochures, and Technical Data. http://www.rockwellautomation.com/global/literature-library/overview.page

Product Compatibility and Download Center (PCDC)

Get help determining how products interact, check features and capabilities, and find associated firmware. http://www.rockwellautomation.com/global/support/pcdc.page

.

Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.

Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.