Product Information
Bulletin 1494V Variable Depth 600A Disconnect Switch(Cat 1494V-DS600 -- Series D)
Additional Resources:1) Go to http://www.literature.rockwellautomation.com 2) Go to Search. Type in publication number: 42052-183-01
Disconnect Switch Installation (Right hand installation shown. For left hand installation follow similar procedure.)1
Disconnect Handle Installation2Install gasket. Install handle and spring bracket. Install defeater lever.1 2 3
Install disconnect switch.7Overlay template F (600 A) over D . Use template D to locate handle holes on mounting plate. 5
IMPORTANT: Apply grease to O-Ring
to retain into handle groove.
A
HOLD FLUSH
TO INSID
E
OF ENCLOSURE
MEASURE TO
INSID
E OF THE
TOP OF ENCLOSURE
TOP
BOTT
6D
HOLD FLUSH
TO INSID
E
OF ENCLOSUREMEASURE TO
INSID
E OF THE
TOP OF ENCLOSURE
TOP HANDLE H
OLE
BOTTOM HANDLE H
OLE
TAP
E HOLD FLUSH
TO INSID
E
OF ENCLOSURE
MEASURE TO
INSID
E OF THE
TOP OF ENCLOSURE
TOP
BOTT
D
113
2
4
90 - 130 lb-in
8-1/4"
4-1/8"
6-5/8"
15"
2-1/16"
6-1/2"
42052-185-01 (1)
Printed in
U.S.A.
F
Disconnect Switc
h Hole Location Template (6
00A)
RIGHT Hand In
stallatio
n
(Use opposite
side for le
ft hand in
stallatio
n)
Switch M
ounting Holes
Center punch and drill
(4) 9
/32" holes fo
r #5/16-18 th
read
forming (T
AP-TITE) screws provided w
ith switc
h
Center punch
and drill (4) holes
for 5/16-18 thread forming
screws provided with switch.
9/32" Dia.
60 - 80 lb-in
7 - 11 lb-in
ATTENTION: Do not install, configure, operate or maintain this product until you have read the product documentation and the documents in the Additional Resources section for installing, configuring, operating or maintaining
equipment. To get the product documentation go to http://www.literature.rockwellautomation.com or contact your local sales office or Rockwell Automation representative.
ATTENTION: Ne pas installer, configurer, exploiter ou maintenir ce produit tant que vous n’avez pas lu sa documentation et les documents de la rubrique Documents connexes pour l’installation, la configuration, l’exploitation et la
maintenance de l’équipement. Pour obtenir de la documentation, rendez-vous sur le site http://www.literature.rockwellautomation.com ou contactez votre agence commerciale Rockwell Automation locale ou son représentant.
ACHTUNG: Für die Installation, Konfiguration, den Betrieb und die Wartung dieses Produkt lesen Sie sich bitte zunächst die Produktdokumentation sowie die Dokumente im Abschnitt „Weitere Informationen“ durch. Die entsprechende
Produktdokumentation finden Sie unter http://www.literature.rockwellautomation.com oder kontaktieren Sie Ihr lokales Vertriebsbüro bzw. einen Rockwell Automation-Mitarbeiter.
ATENCIÓN: No instale, configure, opere ni mantenga este producto hasta que haya leído la documentación del producto y los documentos en la sección Recursos adicionales para la instalación, configuración, operación o mantenimiento
de equipo. Para conseguir la documentación, diríjase a http://www.literature.rockwellautomation.com o póngase en contacto con su oficina regional de ventas o representante de Rockwell Automation.
ATENÇÃO: Não instale, configure, opere ou mantenha este produto até que você leia a documentação do produto e os documentos na seção Recursos adicionais para a instalação, configuração, operação ou manutenção do
equipamento. Para conseguir a documentação, visite http://www.literature.rockwellautomation.com ou entre em contato con seu escritório de vendas regional ou representante da Rockwell Automation.
ATTENZIONE: Non installare, configurare, attivare o riparare questo prodotto senza avere prima letto la relativa documentazione nonchè i documenti indicati nella sezione Ulteriori Risore riguardanti l’installazione, la configurazione,
l’attivazione o la riparazione dell’apparecchiatura. Per la documentazione sul prodotto visitare il sito http://www.literature.rockwellautomation.com o contattare l’ufficio vendite o il rappresentate Rockwell Automation di zona.
WARNING: To prevent electrical shock, disconnect from power source before installing or servicing. Follow NFPA 70E requirements. Install in suitable enclosure. Keep free from contaminants.
The following procedures are critical to the proper operation of the disconnect handle and switch. Failure to follow these steps can result in damage to the equipment and/or serious injury or death to the operator.
Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance shall be carried out by suitably trained personnel in accordance with applicable code of practice. In case of malfunction or damage,
no attempts at repair should be made. The product should be returned to the manufacturer for repair. Do not dismantle the product.
http://www.literature.rockwellautomation.com
http://www.literature.rockwellautomation.com
http://www.literature.rockwellautomation.com
PN-133643DIR 42052-184 (Version 03)
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
ATTENTION: Check for proper operation.
Go to Installation Instruction Sheet 42052-183-01.Trailer Fuse Block Installation5
3
Connecting Rod Installation4
Cutting Connecting Rod (Cut (2) Connecting Rods; first rod connects the handle to the switch, second rod provides
stiffening for the enclosure flange)
Measure working depth of enclosure. Measure, mark and
cut (2) connecting rods.1 2 Remove burrs.3
N minus 3-3/4"
First rod connects the handle to the switch
Second rod provides stiffening for the enclosure flange
N
EnclosureWorking Depth(Inside Flange of Enclosure toMounting Plate)
MountingPlate
Drive Bar
2
Rotate connecting rod into
drive bar 15 turns.
OPEN
4
3
Pull rod up and verify if
rod is 1/2" away from
touching bottom of
spring bracket. (If not,
rotate rod accordingly)
1/2" Clearance
Connecting
Rod
Hitch Pin
Primary Link
5
6
8
7
Verify that disconnect switch and handle are in "OFF"
position. (Switch blades will show “OPEN”)1
9
10
11 150 - 200 lb-in
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1494V-IN103C-EN-E - January 2013
TWO SIDES PRINTEDBODY STOCK BUFF - 20# BOND
BODY INK BLACK
MATERIALNO.
MATERIALFOLD
SIZE
PN-133643 11" W x 8-1/2" H
FLAT
11" W x 17" H
Note: After folding---Printed in (Country where printed)*, instruction sheet SAP numbers and barcodeshould be visible.
* The printing vendor may change the instruction sheet files to show the correct country.
Final Fold
Page Layout
17”11”
PN-133643DIR 42052-184 (Version xx)
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
8 - 1/2”11”
PN-133643DIR 42052-184 (Version xx)
Copyright © 2013 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.