17
BUILDING ENERGY ANALYSIS REPORT PROJECT: Project Designer: Report Prepared by: Job Number: Date: The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2019 Building Energy Efficiency Standards. This program developed by EnergySoft Software www.energysoft.com. 573 Oak Drive Bernard Parker & Assoc. Sacramento, CA 95000 (415) 256-5555 7188 Pleasant Way ZNE Example Los Angeles, CA 90000 1025 5th St. EnergySoft Martyn Dodd Novato, CA 94945 (415) 897-6400 M52000 11/1/2019

BUILDING ENERGY ANALYSIS REPORT PROJECT: Project … · 11/1/2019  · HSPF/COP Cap47 Cap17 SEER EER HeatPumpSystem1 Groundsource heatpump 1 4.8 47500 40000 14 16 NotZonal Single

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: BUILDING ENERGY ANALYSIS REPORT PROJECT: Project … · 11/1/2019  · HSPF/COP Cap47 Cap17 SEER EER HeatPumpSystem1 Groundsource heatpump 1 4.8 47500 40000 14 16 NotZonal Single

BUILDING ENERGY ANALYSIS REPORT

PROJECT:

Project Designer:

Report Prepared by:

Job Number:

Date:

The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2019 Building Energy Efficiency Standards.

This program developed by EnergySoft Software – www.energysoft.com.

573 Oak DriveBernard Parker & Assoc.

Sacramento, CA 95000(415) 256-5555

7188 Pleasant WayZNE Example

Los Angeles, CA 90000

1025 5th St.EnergySoft

Martyn Dodd

Novato, CA 94945(415) 897-6400

M52000

11/1/2019

Page 2: BUILDING ENERGY ANALYSIS REPORT PROJECT: Project … · 11/1/2019  · HSPF/COP Cap47 Cap17 SEER EER HeatPumpSystem1 Groundsource heatpump 1 4.8 47500 40000 14 16 NotZonal Single

TABLE OF CONTENTS

Project SummaryEnergy Use Summary

Cover PageTable of ContentsForm CF1R-PRF-01-E Certificate of ComplianceForm ECON-2 Energy Upgrade Recommendations

1617

123

15

Page 3: BUILDING ENERGY ANALYSIS REPORT PROJECT: Project … · 11/1/2019  · HSPF/COP Cap47 Cap17 SEER EER HeatPumpSystem1 Groundsource heatpump 1 4.8 47500 40000 14 16 NotZonal Single

This

Cer

tific

ate

of C

ompl

ianc

e is

not

regi

ster

ed CERTIFICATE OF COMPLIANCE CF1R-PRF-01E

Project Name: ZNE Example Calculation Date/Time: 2019-11-01T12:04:38-07:00 (Page 1 of 12)

Calculation Description: Title 24 Analysis Input File Name: ZNE Sample.ribd19x

Registration Number: Registration Date/Time:     HERS Provider:

CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.002Schema Version: rev 20190401

Report Generated: 2019-11-01   12:05:45

GENERAL INFORMATION

01 Project Name ZNE Example

02 Run Title Title 24 Analysis

03 Project Location 7188 Pleasant Way

04 City Los Angeles 05 Standards Version 2019

06 Zip code 90000 07 Software Version EnergyPro 8.0

08 Climate Zone 9 09 Front Orientation (deg/ Cardinal) 90

10 Building Type SingleFamily 11 Number of Dwelling Units 1

12 Project Scope NewConstruction 13 Number of Bedrooms 3

14 New Cond. Floor Area (ft2) 0 15 Number of Stories 2

16 Existing Cond. Floor Area (ft2) n/a 17 Fenestration Average U-factor 0.3

18 Total Cond. Floor Area (ft2) 2000 19 Glazing Percentage (%) 19.50%

20 ADU Bedroom Count 0 21 ADU Conditioned Floor Area 0

COMPLIANCE RESULTS

01 Building Complies with Computer Performance

02 This building incorporates features that require field testing and/or verification by a certified HERS rater under the supervision of a CEC-approved HERS provider.

03 This building incorporates one or more Special Features shown below

Page 4: BUILDING ENERGY ANALYSIS REPORT PROJECT: Project … · 11/1/2019  · HSPF/COP Cap47 Cap17 SEER EER HeatPumpSystem1 Groundsource heatpump 1 4.8 47500 40000 14 16 NotZonal Single

This

Cer

tific

ate

of C

ompl

ianc

e is

not

regi

ster

ed CERTIFICATE OF COMPLIANCE CF1R-PRF-01E

Project Name: ZNE Example Calculation Date/Time: 2019-11-01T12:04:38-07:00 (Page 2 of 12)

Calculation Description: Title 24 Analysis Input File Name: ZNE Sample.ribd19x

Registration Number: Registration Date/Time:     HERS Provider:

CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.002Schema Version: rev 20190401

Report Generated: 2019-11-01   12:05:45

ENERGY DESIGN RATING

Energy Design Ratings Compliance Margins

Efficiency¹ (EDR) Total² (EDR) Efficiency¹ (EDR) Total² (EDR)

Standard Design 51.2 28

Proposed Design 49.6 0 1.6 28

RESULT: 3: COMPLIES

¹ Efficiency measures include improvements like a better building envelope and more efficient equipment² Total EDR includes efficiency, photovoltaics and batteries³ Building complies when all efficiency and total margins are greater than or equal to zero

• Standard Design PV Capacity: 2.69 kW• PV kWh output exceeds proposed electric use by 15% which may violate NEM rules. Contact your utility.• EDR is capped at zero

ENERGY USE SUMMARY

Energy Use (kTDV/ft2-yr) Standard Design Proposed Design Compliance Margin Percent Improvement

Space Heating 7.21 7.08 0.13 1.8

Space Cooling 25.02 21.88 3.14 12.5

IAQ Ventilation 2.56 2.56 0 0

Water Heating 12.6 12.45 0.15 1.2

Self Utilization Credit n/a 0 0 n/a

Compliance Energy Total 47.39 43.97 3.42 7.2

REQUIRED PV SYSTEMS

01 02 03 04  05 06 07 08 09 10 11

DC System Size(kWdc) Exception Module Type Array Type Power Electronics CFI Azimuth

(deg)Tilt

InputArray Angle

(deg) Tilt: (x in 12) Inverter Eff.(%)

1.5 NA Standard Fixed (open rack) none true n/a n/a n/a n/a 96

1.5 NA Standard Fixed (open rack) none true n/a n/a n/a n/a 96

Page 5: BUILDING ENERGY ANALYSIS REPORT PROJECT: Project … · 11/1/2019  · HSPF/COP Cap47 Cap17 SEER EER HeatPumpSystem1 Groundsource heatpump 1 4.8 47500 40000 14 16 NotZonal Single

This

Cer

tific

ate

of C

ompl

ianc

e is

not

regi

ster

ed CERTIFICATE OF COMPLIANCE CF1R-PRF-01E

Project Name: ZNE Example Calculation Date/Time: 2019-11-01T12:04:38-07:00 (Page 3 of 12)

Calculation Description: Title 24 Analysis Input File Name: ZNE Sample.ribd19x

Registration Number: Registration Date/Time:     HERS Provider:

CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.002Schema Version: rev 20190401

Report Generated: 2019-11-01   12:05:45

2 NA Standard Fixed (open rack) none true n/a n/a n/a n/a 96

ENERGY DESIGN RATING BATTERY INPUTS

01 02 03 04 05 06

Control Capacity (kWh) Efficiency Rate (kW)Rate (kW) Efficiency Rate (kW)Rate (kW)

Basic 10 0.95 n/a 0.95 n/a

REQUIRED SPECIAL FEATURES

The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.

• PV System: 5 kWdc• Battery System: 10 kWh• Insulation below roof deck• Non-standard duct location (any location other than attic)• Central parallel piping• Northwest Energy Efficiency Alliance (NEEA) rated heat pump water heater; specific brand/model, or equivalent, must be installed

HERS FEATURE SUMMARY

The following is a summary of the features that must be field-verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additionaldetail is provided in the buildng tables below. Registered CF2Rs and CF3Rs are required to be completed in the HERS Registry

Building-level Verifications:• Quality insulation installation (QII)• Building Envelope Air Leakage• IAQ mechanical ventilation• Kitchen range hoodCooling System Verifications:• Minimum Airflow• Fan Efficacy Watts/CFMHeating System Verifications:• -- None --HVAC Distribution System Verifications:• Duct Sealing• Ducts located entirely in conditioned space confirmed by duct leakage testingDomestic Hot Water System Verifications:• -- None --

Page 6: BUILDING ENERGY ANALYSIS REPORT PROJECT: Project … · 11/1/2019  · HSPF/COP Cap47 Cap17 SEER EER HeatPumpSystem1 Groundsource heatpump 1 4.8 47500 40000 14 16 NotZonal Single

This

Cer

tific

ate

of C

ompl

ianc

e is

not

regi

ster

ed CERTIFICATE OF COMPLIANCE CF1R-PRF-01E

Project Name: ZNE Example Calculation Date/Time: 2019-11-01T12:04:38-07:00 (Page 4 of 12)

Calculation Description: Title 24 Analysis Input File Name: ZNE Sample.ribd19x

Registration Number: Registration Date/Time:     HERS Provider:

CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.002Schema Version: rev 20190401

Report Generated: 2019-11-01   12:05:45

BUILDING - FEATURES INFORMATION

01 02 03 04 05 06 07

Project Name Conditioned Floor Area (ft2)Number of Dwelling

Units Number of Bedrooms Number of Zones Number of VentilationCooling Systems

Number of WaterHeating Systems

ZNE Example 2000 1 3 2 0 1

ZONE INFORMATION

01 02 03 04  05 06 07

Zone Name Zone Type HVAC System Name Zone Floor Area (ft2) Avg. Ceiling Height Water Heating System 1 Water Heating System 2

1st Floor Zone Conditioned Ground Coupled HP1 1200 8 DHW Sys 1 N/A

2nd Floor Zone Conditioned Ground Coupled HP1 800 8 DHW Sys 1 N/A

OPAQUE SURFACES

01 02 03 04 05 06 07 08

Name Zone Construction Azimuth Orientation Gross Area (ft2)Window and Door

Area (ft2) Tilt (deg)

Front Wall 1st Floor Zone R-19 Wall w/1 XPS 270 Right 320 81 90

Left Wall 1st Floor Zone R-19 Wall w/1 XPS 0 Front 240 40 90

Back Wall 1st Floor Zone R-19 Wall w/1 XPS 90 Left 320 88.7 90

Right Wall 1st Floor Zone R-19 Wall w/1 XPS 180 Back 240 32 90

Front Wall 2 2nd Floor Zone R-19 Wall w/1 XPS 270 Right 320 60 90

Left Wall 2 2nd Floor Zone R-19 Wall w/1 XPS 0 Front 240 24 90

BackWall 2nd Floor Zone R-19 Wall w/1 XPS 90 Left 320 70 90

Right Wall 2 2nd Floor Zone R-19 Wall w/1 XPS 180 Back 240 32 90

Wall to Garage 1st FloorZone>>__Garage__ R-13 Wall n/a n/a 100 20 n/a

R-38 Roof 1st Floor Zone R-38+13 HP Attic n/a n/a 500 n/a n/a

R-38 Roof 2 2nd Floor Zone R-38+13 HP Attic n/a n/a 800 n/a n/a

GarageRoof __Garage__ R-30 Roof Attic n/a n/a 340 n/a n/a

Page 7: BUILDING ENERGY ANALYSIS REPORT PROJECT: Project … · 11/1/2019  · HSPF/COP Cap47 Cap17 SEER EER HeatPumpSystem1 Groundsource heatpump 1 4.8 47500 40000 14 16 NotZonal Single

This

Cer

tific

ate

of C

ompl

ianc

e is

not

regi

ster

ed CERTIFICATE OF COMPLIANCE CF1R-PRF-01E

Project Name: ZNE Example Calculation Date/Time: 2019-11-01T12:04:38-07:00 (Page 5 of 12)

Calculation Description: Title 24 Analysis Input File Name: ZNE Sample.ribd19x

Registration Number: Registration Date/Time:     HERS Provider:

CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.002Schema Version: rev 20190401

Report Generated: 2019-11-01   12:05:45

OPAQUE SURFACES

01 02 03 04 05 06 07 08

Name Zone Construction Azimuth Orientation Gross Area (ft2)Window and Door

Area (ft2) Tilt (deg)

Interior Floor 2nd Floor Zone R-0 Floor No Crawlspace n/a n/a 700 n/a n/a

Floor over Garage 2nd Floor Zone R-19 Floor No Crawlspace n/a n/a 100 n/a n/a

GarageWallFront __Garage__ Garage Ext Wall 270 Right 180 128 90

GarageWallLeft __Garage__ Garage Ext Wall 0 Front 198 0 90

GarageWallRight __Garage__ Garage Ext Wall 180 Back 108 0 90

ATTIC

01 02 03 04 05 06 07 08

Name Construction Type Roof Rise (x in 12) Roof Reflectance Roof Emittance Radiant Barrier Cool Roof

Attic __Garage__ Attic Garage Roof Cons Ventilated 4 0.1 0.85 Yes No

Attic 1st Floor Zone Attic Roof1st FloorZone Ventilated 4 0.1 0.85 Yes No

Attic 2nd Floor Zone Attic Roof2nd FloorZone Ventilated 4 0.1 0.85 Yes No

FENESTRATION / GLAZING

01 02 03 04 05 06 07 08 09 10 11 12 13 14

Name Type Surface Orientation Azimuth Width (ft) Height (ft) Mult.Area(ft2)

U-factor U-factorSource SHGC SHGC

SourceExteriorShading

Front Windows Window Front Wall Right 0 1 60 0.3 NFRC 0.23 NFRC Insect Screen(default)

Left Windows Window Left Wall Front 90 1 40 0.3 NFRC 0.23 NFRC Insect Screen(default)

Back Windows Window Back Wall Left 180 1 72 0.3 NFRC 0.23 NFRC Insect Screen(default)

Right Windows Window Right Wall Back 270 1 32 0.3 NFRC 0.23 NFRC Insect Screen(default)

Page 8: BUILDING ENERGY ANALYSIS REPORT PROJECT: Project … · 11/1/2019  · HSPF/COP Cap47 Cap17 SEER EER HeatPumpSystem1 Groundsource heatpump 1 4.8 47500 40000 14 16 NotZonal Single

This

Cer

tific

ate

of C

ompl

ianc

e is

not

regi

ster

ed CERTIFICATE OF COMPLIANCE CF1R-PRF-01E

Project Name: ZNE Example Calculation Date/Time: 2019-11-01T12:04:38-07:00 (Page 6 of 12)

Calculation Description: Title 24 Analysis Input File Name: ZNE Sample.ribd19x

Registration Number: Registration Date/Time:     HERS Provider:

CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.002Schema Version: rev 20190401

Report Generated: 2019-11-01   12:05:45

FENESTRATION / GLAZING

01 02 03 04 05 06 07 08 09 10 11 12 13 14

Name Type Surface Orientation Azimuth Width (ft) Height (ft) Mult.Area(ft2)

U-factor U-factorSource SHGC SHGC

SourceExteriorShading

Front Windows2 Window Front Wall 2 Right 0 1 60 0.3 NFRC 0.23 NFRC Insect Screen

(default)

Left Windows 2 Window Left Wall 2 Front 90 1 24 0.3 NFRC 0.23 NFRC Insect Screen(default)

Back Windows2 Window BackWall Left 180 1 70 0.3 NFRC 0.23 NFRC Insect Screen

(default)

Right Windows2 Window Right Wall 2 Back 270 1 32 0.3 NFRC 0.23 NFRC Insect Screen

(default)

OPAQUE DOORS

01 02 03 04

Name Side of Building Area (ft2) U-factor

Entry Door Front Wall 21 0.5

Back Door Back Wall 16.7 0.5

Door Wall to Garage 20 0.5

GarageCarDoorFront GarageWallFront 128 0.7

SLAB FLOORS

01 02 03 04 05 06 07

Name Zone Area (ft2) Perimeter (ft) Edge Insul. R-value& Depth Carpeted Fraction Heated

Covered Slab 1st Floor Zone 1200 90 None 80% No

GarageSlab __Garage__ 440 54 None 0% No

Page 9: BUILDING ENERGY ANALYSIS REPORT PROJECT: Project … · 11/1/2019  · HSPF/COP Cap47 Cap17 SEER EER HeatPumpSystem1 Groundsource heatpump 1 4.8 47500 40000 14 16 NotZonal Single

This

Cer

tific

ate

of C

ompl

ianc

e is

not

regi

ster

ed CERTIFICATE OF COMPLIANCE CF1R-PRF-01E

Project Name: ZNE Example Calculation Date/Time: 2019-11-01T12:04:38-07:00 (Page 7 of 12)

Calculation Description: Title 24 Analysis Input File Name: ZNE Sample.ribd19x

Registration Number: Registration Date/Time:     HERS Provider:

CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.002Schema Version: rev 20190401

Report Generated: 2019-11-01   12:05:45

OPAQUE SURFACE CONSTRUCTIONS

01 02 03 04  05 06 07 08

Construction Name Surface Type Construction Type Framing Total CavityR-value

Interior / ExteriorContinuous

R-valueU-factor Assembly Layers

Garage Ext Wall Exterior Walls Wood Framed Wall 2x4 @ 16 in. O. C. Noinsulation n/a 0.361

Inside Finish: Gypsum BoardCavity / Frame: no insul. / 2x4Exterior Finish: 3 Coat Stucco

R-19 Wall w/1 XPS Exterior Walls Wood Framed Wall 2x6 @ 16 in. O. C. R 18 n/a 0.051

Inside Finish: Gypsum BoardCavity / Frame: R-19 in 5-1/2 in. (R-18) /

2x6Sheathing / Insulation: R5 Sheathing

Exterior Finish: 3 Coat Stucco

R-13 Wall Interior Walls Wood Framed Wall 2x4 @ 16 in. O. C. R-13 n/a 0.092Inside Finish: Gypsum BoardCavity / Frame: R-13 / 2x4

Other Side Finish: Gypsum Board

Attic Garage Roof Cons Attic Roofs Wood FramedCeiling 2x4 @ 24 in. O. C. No

insulation n/a 0.644

Cavity / Frame: no insul. / 2x4Roof Deck: Wood

Siding/sheathing/deckingRoofing: Light Roof (Asphalt Shingle)

Attic Roof1st Floor Zone Attic Roofs Wood FramedCeiling 2x4 @ 24 in. O. C. R-13 n/a 0.078

Around Roof Joists: R-0.0 insul.Cavity / Frame: R-13.0 / 2x4

Roof Deck: WoodSiding/sheathing/decking

Roofing: Light Roof (Asphalt Shingle)

Attic Roof2nd FloorZone Attic Roofs Wood Framed

Ceiling 2x4 @ 24 in. O. C. R-13 n/a 0.078

Around Roof Joists: R-0.0 insul.Cavity / Frame: R-13.0 / 2x4

Roof Deck: WoodSiding/sheathing/decking

Roofing: Light Roof (Asphalt Shingle)

R-30 Roof Attic Ceilings (belowattic)

Wood FramedCeiling 2x4 @ 24 in. O. C. R-30 n/a 0.032

Inside Finish: Gypsum BoardCavity / Frame: R-9.1 / 2x4

Over Ceiling Joists: R-20.9 insul.

Page 10: BUILDING ENERGY ANALYSIS REPORT PROJECT: Project … · 11/1/2019  · HSPF/COP Cap47 Cap17 SEER EER HeatPumpSystem1 Groundsource heatpump 1 4.8 47500 40000 14 16 NotZonal Single

This

Cer

tific

ate

of C

ompl

ianc

e is

not

regi

ster

ed CERTIFICATE OF COMPLIANCE CF1R-PRF-01E

Project Name: ZNE Example Calculation Date/Time: 2019-11-01T12:04:38-07:00 (Page 8 of 12)

Calculation Description: Title 24 Analysis Input File Name: ZNE Sample.ribd19x

Registration Number: Registration Date/Time:     HERS Provider:

CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.002Schema Version: rev 20190401

Report Generated: 2019-11-01   12:05:45

OPAQUE SURFACE CONSTRUCTIONS

01 02 03 04  05 06 07 08

Construction Name Surface Type Construction Type Framing Total CavityR-value

Interior / ExteriorContinuous

R-valueU-factor Assembly Layers

R-38+13 HP Attic Ceilings (belowattic)

Wood FramedCeiling 2x4 @ 24 in. O. C. R-38 n/a 0.025

Inside Finish: Gypsum BoardCavity / Frame: R-9.1 / 2x4

Over Ceiling Joists: R-28.9 insul.

R-0 Floor No Crawlspace Interior Floors Wood Framed Floor 2x12 @ 16 in. O. C. Noinsulation n/a 0.196

Floor Surface: CarpetedFloor Deck: Wood

Siding/sheathing/deckingCavity / Frame: no insul. / 2x12

Ceiling Below Finish: Gypsum Board

R-19 Floor NoCrawlspace Interior Floors Wood Framed Floor 2x10 @ 16 in. O. C. R-19 n/a 0.045

Floor Surface: CarpetedFloor Deck: Wood

Siding/sheathing/deckingCavity / Frame: R-19 / 2x10

Ceiling Below Finish: Gypsum Board

BUILDING ENVELOPE - HERS VERIFICATION

01 02 03 04

Quality Insulation Installation (QII) Quality Installation of Spray Foam Insulation Building Envelope Air Leakage CFM50

Required Not Required Required 533.3

WATER HEATING SYSTEMS

01 02 03 04  05 06 07 08

Name System Type Distribution Type Water Heater Number ofHeaters

SolarFraction (%) Compact Distribution HERS Verification

DHW Sys 1 Domestic Hot Water(DHW) Parallel Piping DHW Heater 1 1 0 None n/a

Page 11: BUILDING ENERGY ANALYSIS REPORT PROJECT: Project … · 11/1/2019  · HSPF/COP Cap47 Cap17 SEER EER HeatPumpSystem1 Groundsource heatpump 1 4.8 47500 40000 14 16 NotZonal Single

This

Cer

tific

ate

of C

ompl

ianc

e is

not

regi

ster

ed CERTIFICATE OF COMPLIANCE CF1R-PRF-01E

Project Name: ZNE Example Calculation Date/Time: 2019-11-01T12:04:38-07:00 (Page 9 of 12)

Calculation Description: Title 24 Analysis Input File Name: ZNE Sample.ribd19x

Registration Number: Registration Date/Time:     HERS Provider:

CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.002Schema Version: rev 20190401

Report Generated: 2019-11-01   12:05:45

WATER HEATERS

01 02 03 04  05 06 07 08 09 10 11 12

NameHeatingElement

TypeTank Type #

Units

TankVol.(gal)

EnergyFactor orEfficiency

Input Ratingor Pilot

TankInsulation

R-value(Int/Ext)

Standby Lossor Recovery

Eff.

1st Hr. Ratingor Flow Rate

NEEA Heat PumpBrand or Model /

Other

Tank Location orAmbient Condition

DHW Heater 1 Heat PumpBoiler n/a 1 50 NEEA Rated n/a n/a 82 80\ AOSmith\AOSmith

HP1050 Garage

WATER HEATING - HERS VERIFICATION

01 02 03 04

Name Pipe Insulation Parallel Piping Compact Distribution

DHW Sys 1 - 1/1 Not Required Not Required Not Required

SPACE CONDITIONING SYSTEMS

01 02 03 04 05 06 07

Name System Type Heating Unit Name Cooling Unit Name Fan Name Distribution Name Required ThermostatType

Ground Coupled HP1 Heat pump heatingcooling Heat Pump System 1 Heat Pump System 1 HVAC Fan 1 Air Distribution System 1 Setback

HVAC - HEAT PUMPS

01 02 03 04  05 06 07 08 09 10 11

Name System Type Number of UnitsHeating Cooling Zonally

ControlledCompressor

Type HERS VerificationHSPF/COP Cap 47 Cap 17 SEER EER

Heat Pump System 1 Ground sourceheat pump 1 4.8 47500 40000 14 16 Not Zonal Single

SpeedHeat Pump System

1-hers-htpump

Page 12: BUILDING ENERGY ANALYSIS REPORT PROJECT: Project … · 11/1/2019  · HSPF/COP Cap47 Cap17 SEER EER HeatPumpSystem1 Groundsource heatpump 1 4.8 47500 40000 14 16 NotZonal Single

This

Cer

tific

ate

of C

ompl

ianc

e is

not

regi

ster

ed CERTIFICATE OF COMPLIANCE CF1R-PRF-01E

Project Name: ZNE Example Calculation Date/Time: 2019-11-01T12:04:38-07:00 (Page 10 of 12)

Calculation Description: Title 24 Analysis Input File Name: ZNE Sample.ribd19x

Registration Number: Registration Date/Time:     HERS Provider:

CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.002Schema Version: rev 20190401

Report Generated: 2019-11-01   12:05:45

HVAC HEAT PUMPS - HERS VERIFICATION

01 02 03 04 05 06 07 08 09

Name Verified Airflow Airflow Target Verified EER Verified SEER Verified RefrigerantCharge Verified HSPF Verified Heating

Cap 47Verified Heating

Cap 17

Heat Pump System1-hers-htpump Required 350 Not Required Not Required No No No No

HVAC - DISTRIBUTION SYSTEMS

01 02 03 04 05 06 07 08 09 10 11 12

Duct Ins.R-value Duct Location Surface Area

Name Type Design Type Suppy Return Supply Return Supply Return BypassDuct Duct Leakage HERS Verification

Air DistributionSystem 1

Conditionedspace-entirely Non-Verified R-8 R-8 Conditioned

ZoneConditioned

Zone 0 0No

BypassDuct

Sealed andTested

Air Distribution System1-hers-dist

HVAC DISTRIBUTION - HERS VERIFICATION

01 02 03 04 05 06 07 08 09

Name Duct LeakageVerification

Duct leakage target(%)

Verified DuctLocation

Verified DuctDesign Buried Ducts Deeply Buried

DuctsLow-leakage Air

Handler

Low Leakage DuctsEntirely in

Conditioned Space

Air DistributionSystem 1-hers-dist Yes 5 Required Not Required Not Required Credit not taken Required No

HVAC - FAN SYSTEMS

01 02 03 04

Name Type Fan Power (Watts/CFM) Name

HVAC Fan 1 Single speed PSC furnace fan 0.45 HVAC Fan 1-hers-fan

Page 13: BUILDING ENERGY ANALYSIS REPORT PROJECT: Project … · 11/1/2019  · HSPF/COP Cap47 Cap17 SEER EER HeatPumpSystem1 Groundsource heatpump 1 4.8 47500 40000 14 16 NotZonal Single

This

Cer

tific

ate

of C

ompl

ianc

e is

not

regi

ster

ed CERTIFICATE OF COMPLIANCE CF1R-PRF-01E

Project Name: ZNE Example Calculation Date/Time: 2019-11-01T12:04:38-07:00 (Page 11 of 12)

Calculation Description: Title 24 Analysis Input File Name: ZNE Sample.ribd19x

Registration Number: Registration Date/Time:     HERS Provider:

CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.002Schema Version: rev 20190401

Report Generated: 2019-11-01   12:05:45

HVAC FAN SYSTEMS - HERS VERIFICATION

01 02 03

Name Verified Fan Watt Draw Required Fan Power(Watts/CFM)

HVAC Fan 1-hers-fan Required 0.45

IAQ (INDOOR AIR QUALITY) FANS

01 02 03 04 05 06

Dwelling Unit IAQ CFM IAQ Watts/CFM IAQ Fan Type IAQ Recovery Effectiveness (%) HERS Verification

SFam IAQVentRpt 88 0.25 Default 0 Yes

Page 14: BUILDING ENERGY ANALYSIS REPORT PROJECT: Project … · 11/1/2019  · HSPF/COP Cap47 Cap17 SEER EER HeatPumpSystem1 Groundsource heatpump 1 4.8 47500 40000 14 16 NotZonal Single

This

Cer

tific

ate

of C

ompl

ianc

e is

not

regi

ster

ed CERTIFICATE OF COMPLIANCE CF1R-PRF-01E

Project Name: ZNE Example Calculation Date/Time: 2019-11-01T12:04:38-07:00 (Page 12 of 12)

Calculation Description: Title 24 Analysis Input File Name: ZNE Sample.ribd19x

Registration Number: Registration Date/Time:     HERS Provider:

CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.002Schema Version: rev 20190401

Report Generated: 2019-11-01   12:05:45

DOCUMENTATION AUTHOR'S DECLARATION STATEMENT

1. I certify that this Certificate of Compliance documentation is accurate and complete.Documentation Author Name: Documentation Author Signature:

Company: Signature Date:

Address: CEA/ HERS Certification Identification (If applicable):

City/State/Zip: Phone:

RESPONSIBLE PERSON'S DECLARATION STATEMENTI certify the following under penalty of perjury, under the laws of the State of California:

1. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance.2. I certify that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations.3. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets,

calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.Responsible Designer Name: Responsible Designer Signature:

Company: Date Signed:

Address: License:

City/State/Zip: Phone:

 

Martyn Dodd

EnergySoft

1025 5th St.

Novato, CA 94945

KKJII

(415) 897-6400

11/1/2019

Rob Parker

Bernard Parker & Assoc.

573 Oak Drive

Sacramento, CA 95000 (415) 256-5555

Page 15: BUILDING ENERGY ANALYSIS REPORT PROJECT: Project … · 11/1/2019  · HSPF/COP Cap47 Cap17 SEER EER HeatPumpSystem1 Groundsource heatpump 1 4.8 47500 40000 14 16 NotZonal Single

Energy Upgrade Recommendations ECON-2 Project Name Documentation Author Project Address Author Address

Recommended Improvements Description

Annual Savings

Est. Cost to Install

Savings

Site TDV

Annual Results Energy Cost

Electricity (kWh)

Fossil Fuel (therms)

End Use Existing Improved Savings Existing Improved Savings Existing Improved Savings

Space Heating

Space Cooling

Fans

Pumps

Domestic Hot Water

Indoor Lighting

Outdoor Lighting

Plug Loads

Appliances/Ancillary

TOTAL

CO2 (metric tons/year) Existing Improved Savings Climate Zone:

Electricity Electric Rate:

Fossil Fuel Gas Rate:

TOTAL Floor Area:

Type:

Average Demand (kW)

TDV Energy (kBtu/ft2-yr)

The estimated operating costs shown in this report are dependent upon many factors. The construction and conservation features of the project clearly are important. Equally important is the thermostat setting. How the thermostat is used, appliance use, and occupant interaction all influence the annual operating cost. The estimates provided in this report are based on typical conditions; your actual usage will vary.

7188 Pleasant WayLos Angeles, CA 90000

ZNE Example

$14

$0

$51$23

$72

$59$121

($720)

$247$243

$110

ID: M52000 Page 15 of 17EnergyPro 8.0.1.1 by EnergySoft User Number: 0000

1025 5th St.Novato, CA 94945

EnergySoft

0

0

00

0

00

0

00

0

114

0

420192

588

487993

-7,895

2,0261,994

-1,080

0.07

0.070.00

6.23

Electric Alameda HGas PG&E P

9

2,000Single Family

-5.98

Photovoltaic+Battery

Page 16: BUILDING ENERGY ANALYSIS REPORT PROJECT: Project … · 11/1/2019  · HSPF/COP Cap47 Cap17 SEER EER HeatPumpSystem1 Groundsource heatpump 1 4.8 47500 40000 14 16 NotZonal Single

Project Summary

Date of Audit: House Type:

Conditioned Floor Area: Foundation Type:

Number of Stories: Climate Zone:

Number of Bedrooms: Weather Data:

WHERE THE ENERGY IS USED

This pie chart estimates the energy cost for the

various types of end uses in the home. Data has

been calculated using software that uses typical

profiles of usage to estimate end use cost. Your

costs may vary from these numbers depending

upon how the home is operated.

This all electric home was evaluated with QII and a significant solar system and battery included as well as mostfeatures needed to comply with the 2019 Title 24 code requirements.

1

2,000

3

9

Single Family

Slab-on-Grade

CZ09_wy3.bin

Los Angeles, CA 90000

7188 Pleasant Way

EnergyPro 8.0 by EnergySoft Page 16 of 17User Number: 0000 ID: M52000

Page 17: BUILDING ENERGY ANALYSIS REPORT PROJECT: Project … · 11/1/2019  · HSPF/COP Cap47 Cap17 SEER EER HeatPumpSystem1 Groundsource heatpump 1 4.8 47500 40000 14 16 NotZonal Single

Energy Use Summary

ELECTRICITY

End Use kWh/yr

Space Heating

Space Cooling

Fans

Pumps

Domestic Hot Water

Indoor Lighting

Outdoor Lighting

Plug Loads

Appliances/Ancillary

Renewables

TOTAL

FOSSIL FUEL

End Use Therms/yr

Space Heating

Domestic Hot Water

Appliances

Ancillary

TOTAL

The tables and graphs below summarize the major energy uses in the home for both electricity and fossil fuels. Ancillary

uses include swimming pools and spas.

Los Angeles, CA 90000

7188 Pleasant Way

114

588

420

192

0

993

487

2,026

1,994

-1,080

0

0

0

0

-7,895

0

EnergyPro 8.0 by EnergySoft Page 17 of 17User Number: 0000 ID: M52000