Upload
engrfarhanaaa
View
219
Download
0
Embed Size (px)
Citation preview
8/16/2019 Building Defect Reports Sample 1
1/220
8/16/2019 Building Defect Reports Sample 1
2/220
8/16/2019 Building Defect Reports Sample 1
3/220
8/16/2019 Building Defect Reports Sample 1
4/220
8/16/2019 Building Defect Reports Sample 1
5/220
8/16/2019 Building Defect Reports Sample 1
6/220
8/16/2019 Building Defect Reports Sample 1
7/220
8/16/2019 Building Defect Reports Sample 1
8/220
8/16/2019 Building Defect Reports Sample 1
9/220
8/16/2019 Building Defect Reports Sample 1
10/220
8/16/2019 Building Defect Reports Sample 1
11/220
8/16/2019 Building Defect Reports Sample 1
12/220
8/16/2019 Building Defect Reports Sample 1
13/220
8/16/2019 Building Defect Reports Sample 1
14/220
8/16/2019 Building Defect Reports Sample 1
15/220
8/16/2019 Building Defect Reports Sample 1
16/220
8/16/2019 Building Defect Reports Sample 1
17/220
8/16/2019 Building Defect Reports Sample 1
18/220
8/16/2019 Building Defect Reports Sample 1
19/220
8/16/2019 Building Defect Reports Sample 1
20/220
8/16/2019 Building Defect Reports Sample 1
21/220
8/16/2019 Building Defect Reports Sample 1
22/220
8/16/2019 Building Defect Reports Sample 1
23/220
8/16/2019 Building Defect Reports Sample 1
24/220
8/16/2019 Building Defect Reports Sample 1
25/220
8/16/2019 Building Defect Reports Sample 1
26/220
8/16/2019 Building Defect Reports Sample 1
27/220
8/16/2019 Building Defect Reports Sample 1
28/220
8/16/2019 Building Defect Reports Sample 1
29/220
8/16/2019 Building Defect Reports Sample 1
30/220
8/16/2019 Building Defect Reports Sample 1
31/220
8/16/2019 Building Defect Reports Sample 1
32/220
8/16/2019 Building Defect Reports Sample 1
33/220
8/16/2019 Building Defect Reports Sample 1
34/220
8/16/2019 Building Defect Reports Sample 1
35/220
8/16/2019 Building Defect Reports Sample 1
36/220
8/16/2019 Building Defect Reports Sample 1
37/220
8/16/2019 Building Defect Reports Sample 1
38/220
8/16/2019 Building Defect Reports Sample 1
39/220
8/16/2019 Building Defect Reports Sample 1
40/220
8/16/2019 Building Defect Reports Sample 1
41/220
8/16/2019 Building Defect Reports Sample 1
42/220
8/16/2019 Building Defect Reports Sample 1
43/220
8/16/2019 Building Defect Reports Sample 1
44/220
8/16/2019 Building Defect Reports Sample 1
45/220
8/16/2019 Building Defect Reports Sample 1
46/220
8/16/2019 Building Defect Reports Sample 1
47/220
8/16/2019 Building Defect Reports Sample 1
48/220
8/16/2019 Building Defect Reports Sample 1
49/220
8/16/2019 Building Defect Reports Sample 1
50/220
8/16/2019 Building Defect Reports Sample 1
51/220
8/16/2019 Building Defect Reports Sample 1
52/220
8/16/2019 Building Defect Reports Sample 1
53/220
8/16/2019 Building Defect Reports Sample 1
54/220
8/16/2019 Building Defect Reports Sample 1
55/220
8/16/2019 Building Defect Reports Sample 1
56/220
8/16/2019 Building Defect Reports Sample 1
57/220
8/16/2019 Building Defect Reports Sample 1
58/220
8/16/2019 Building Defect Reports Sample 1
59/220
8/16/2019 Building Defect Reports Sample 1
60/220
8/16/2019 Building Defect Reports Sample 1
61/220
8/16/2019 Building Defect Reports Sample 1
62/220
8/16/2019 Building Defect Reports Sample 1
63/220
8/16/2019 Building Defect Reports Sample 1
64/220
8/16/2019 Building Defect Reports Sample 1
65/220
8/16/2019 Building Defect Reports Sample 1
66/220
8/16/2019 Building Defect Reports Sample 1
67/220
8/16/2019 Building Defect Reports Sample 1
68/220
8/16/2019 Building Defect Reports Sample 1
69/220
8/16/2019 Building Defect Reports Sample 1
70/220
8/16/2019 Building Defect Reports Sample 1
71/220
8/16/2019 Building Defect Reports Sample 1
72/220
8/16/2019 Building Defect Reports Sample 1
73/220
8/16/2019 Building Defect Reports Sample 1
74/220
8/16/2019 Building Defect Reports Sample 1
75/220
8/16/2019 Building Defect Reports Sample 1
76/220
8/16/2019 Building Defect Reports Sample 1
77/220
8/16/2019 Building Defect Reports Sample 1
78/220
8/16/2019 Building Defect Reports Sample 1
79/220
8/16/2019 Building Defect Reports Sample 1
80/220
8/16/2019 Building Defect Reports Sample 1
81/220
8/16/2019 Building Defect Reports Sample 1
82/220
8/16/2019 Building Defect Reports Sample 1
83/220
8/16/2019 Building Defect Reports Sample 1
84/220
8/16/2019 Building Defect Reports Sample 1
85/220
8/16/2019 Building Defect Reports Sample 1
86/220
8/16/2019 Building Defect Reports Sample 1
87/220
8/16/2019 Building Defect Reports Sample 1
88/220
8/16/2019 Building Defect Reports Sample 1
89/220
8/16/2019 Building Defect Reports Sample 1
90/220
8/16/2019 Building Defect Reports Sample 1
91/220
8/16/2019 Building Defect Reports Sample 1
92/220
8/16/2019 Building Defect Reports Sample 1
93/220
8/16/2019 Building Defect Reports Sample 1
94/220
8/16/2019 Building Defect Reports Sample 1
95/220
8/16/2019 Building Defect Reports Sample 1
96/220
8/16/2019 Building Defect Reports Sample 1
97/220
8/16/2019 Building Defect Reports Sample 1
98/220
8/16/2019 Building Defect Reports Sample 1
99/220
8/16/2019 Building Defect Reports Sample 1
100/220
8/16/2019 Building Defect Reports Sample 1
101/220
8/16/2019 Building Defect Reports Sample 1
102/220
8/16/2019 Building Defect Reports Sample 1
103/220
8/16/2019 Building Defect Reports Sample 1
104/220
8/16/2019 Building Defect Reports Sample 1
105/220
8/16/2019 Building Defect Reports Sample 1
106/220
8/16/2019 Building Defect Reports Sample 1
107/220
8/16/2019 Building Defect Reports Sample 1
108/220
8/16/2019 Building Defect Reports Sample 1
109/220
8/16/2019 Building Defect Reports Sample 1
110/220
8/16/2019 Building Defect Reports Sample 1
111/220
8/16/2019 Building Defect Reports Sample 1
112/220
8/16/2019 Building Defect Reports Sample 1
113/220
Item Defect Details Photographic Details
340. Location: L6 Corridor
Finding: Incomplete paint finish to skirting
Recommendations: Complete painting works to skirting in corridor
341. Location: L6 water meter cupboard
Finding: Damaged plaster board
Recommendations: Patch, sand and paint area of damage and makegood
342. Location: L6 water meter cupboard
Finding: Incomplete painting, remove wires to gauges
Recommendations:
Finish painting walls and remove unused wires
8/16/2019 Building Defect Reports Sample 1
114/220
Item Defect Details Photographic Details
343. Location: L6 refuse room
Finding: Screw hole in door frame
Recommendations: Fill and sand hole in door frame, paint doorframe
344. Location: L6 refuse room
Finding: Damaged plasterboard
Recommendations: Fill, sand and paint damaged plasterboard andmake good
345. Location: L6 refuse room
Finding: Unsatisfactory wall finish
Recommendations:
Patch, fill, sand and paint wall and make good
8/16/2019 Building Defect Reports Sample 1
115/220
Item Defect Details Photographic Details
346. Location: L6 water meter cupboard
Finding: Plastic still left on pipes from painters
Recommendations: Remove plastic
347. Location: L6 water meter cupboard
Finding: Incomplete painting
Recommendations: Finish painting walls
348. Location: L6 corridor
Finding: Apartment signage to door is falling off
Recommendations:
Re‐stick signage to apartment door
8/16/2019 Building Defect Reports Sample 1
116/220
Item Defect Details Photographic Details
349. Location: L6 water meter cupboard
Finding: Unfinished painting around water metersignage
Recommendations: Paint wall around water meter signage
350. Location: L6 water meter cupboard
Finding: Incomplete painting
Recommendations: Finish painting walls
351. Location: L6 water meter cupboard
Finding: Unused wires left on gauges
Recommendations:
Remove unused wires
8/16/2019 Building Defect Reports Sample 1
117/220
Item Defect Details Photographic Details
352. Location: L6 water meter cupboard
Finding: Incomplete painting
Recommendations: Finish painting walls
353. Location: L6 water meter cupboard
Finding: Unused wires left on gauges
Recommendations: Remove unused wires
354. Location: L6 Services cupboard
Finding: Missing caulking along plaster and door frame
Recommendations:
Caulk along plaster edge and door frame
8/16/2019 Building Defect Reports Sample 1
118/220
Item Defect Details Photographic Details
355. Location: L7 Corridor
Finding: Damaged skirting beside passenger lifts
Recommendations: Remove damaged skirting and replace
356. Location: L7 Electrical room
Finding: Generally dirty
Recommendations: Builders clean required
357. Location: L7 Electrical room
Finding: Excess plasterboard stuck to wall aroundpenetrations
Recommendations: Remove excess plasterboard, patch and fill allholes as required
8/16/2019 Building Defect Reports Sample 1
119/220
8/16/2019 Building Defect Reports Sample 1
120/220
Item Defect Details Photographic Details
361. Location: L7 electrical room
Finding: Painting to door incomplete, spacers left in atdoor frame, caulking incomplete
Recommendations: Paint door, remove spacers and caulk edges ofdoor frame
362. Location: L7 electrical room
Finding: Builders marking visible on floor
Recommendations: Builders clean required
363. Location: L7 water meter cupboard
Finding: Unused wires left on gauges
Recommendations:
Remove unused wires
8/16/2019 Building Defect Reports Sample 1
121/220
Item Defect Details Photographic Details
364. Location: L7 refuse room
Finding: Unsatisfactory wall finish
Recommendations: Patch, fill, sand and paint wall and make good
365. Location: L7 refuse room
Finding: Unsealed penetration
Recommendations: Correctly seal penetrations in concrete slab inline with building code for fire preventionthrough floors
366. Location: L7 refuse room
Finding: Grey paint left on door
Recommendations:
Builders clean required
8/16/2019 Building Defect Reports Sample 1
122/220
Item Defect Details Photographic Details
367. Location: L7 refuse room
Finding: Protective sticker on door hardware
Recommendations: Remove sticker from door hardware
368. Location: L7 water meter cupboard
Finding: Concrete splatter and generally dirty
Recommendations: Builders clean required
369. Location: L7 water meter cupboard
Finding: Unused wires left on gauges and roomgenerally dirty
Recommendations: Remove unused wires and builders cleanrequired
8/16/2019 Building Defect Reports Sample 1
123/220
8/16/2019 Building Defect Reports Sample 1
124/220
Item Defect Details Photographic Details
373. Location: L7 water meter cupboard
Finding: Unused wires left on gauges and roomgenerally dirty
Recommendations: Remove unused wires and builders cleanrequired
374. Location: L7 water meter cupboard
Finding: Unused cables hanging from gauges and roomgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
375. Location: L7 water meter cupboard
Finding: Unused cables hanging from gauges
Recommendations:
Remove unused cables
8/16/2019 Building Defect Reports Sample 1
125/220
Item Defect Details Photographic Details
376. Location: L7 water meter cupboard
Finding: Concrete splatter on wall
Recommendations: Builders clean required
377. Location: L7 services cupboard
Finding: Adhesive stuck on wall
Recommendations: Remove excess adhesive and clean as required
378. Location: L8 Electrical room
Finding: Building materials stored and generally dirty
Recommendations:
Dispose of building materials appropriately andbuilders clean required
8/16/2019 Building Defect Reports Sample 1
126/220
Item Defect Details Photographic Details
379. Location: L8 Electrical room
Finding: Building materials stored and generally dirty
Recommendations: Dispose of building materials appropriately andbuilders clean required
380. Location: L8 Electrical room
Finding: 1 x unsealed penetration
Recommendations: Correctly seal penetrations in concrete slab inline with building code for fire preventionthrough floors
381. Location: L8 Electrical room
Finding: Steel stud fixed to door frame and missingcaulking to edge of door frame to wall
Recommendations: Remove steel stud, and caulk along edge ofdoor frame
8/16/2019 Building Defect Reports Sample 1
127/220
Item Defect Details Photographic Details
382. Location: L8 Electrical room
Finding: Uneven floor level
Recommendations: Fill and make level with rest of electrical roomfloor
383. Location: L8 Electrical room
Finding: Carpet tiles falling too short at threshold
Recommendations: Install new carpet tiles at the correct size toensure no gaps at threshold
384. Location: L8 Electrical room
Finding: Paint on door frame
Recommendations:
Builders clean required
8/16/2019 Building Defect Reports Sample 1
128/220
8/16/2019 Building Defect Reports Sample 1
129/220
Item Defect Details Photographic Details
388. Location: L8 water meter cupboard
Finding: Building materials on floor
Recommendations: Builders clean required
389. Location: L8 water meter cupboard
Finding: Unused cables hanging from gauges
Recommendations: Remove unused cables
390. Location: L8 water meter cupboard
Finding: Unused cables hanging from gauges
Recommendations:
Remove unused cables
8/16/2019 Building Defect Reports Sample 1
130/220
Item Defect Details Photographic Details
391. Location: L8 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
392. Location: L8 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
393. Location: L8 water meter cupboard
Finding: Overspray evident on floor
Recommendations:
Builders clean required
8/16/2019 Building Defect Reports Sample 1
131/220
Item Defect Details Photographic Details
394. Location: L8 services cupboard
Finding: Generally dirty
Recommendations: Builders clean required
395. Location: L8 lobby
Finding: Signage is bent
Recommendations: Replace with new sign
396. Location: L9 electrical room
Finding: Concrete splatter on wall
Recommendations:
Builders clean required
8/16/2019 Building Defect Reports Sample 1
132/220
Item Defect Details Photographic Details
397. Location: L9 Electrical room
Finding: 2 x unsealed penetrations
Recommendations: Correctly seal penetrations in concrete slab inline with building code for fire preventionthrough floors
398. Location: L9 Electrical room
Finding: Steel stud fixed to door frame and missingcaulking to edge of door frame to wall
Recommendations: Remove steel stud, and caulk along edge ofdoor frame
399. Location: L9 Electrical room
Finding: Concrete floor is dirty and contains high spotsin various locations
Recommendations: Grind floor and remove concrete splatter
8/16/2019 Building Defect Reports Sample 1
133/220
Item Defect Details Photographic Details
400. Location: L9 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
401. Location: L9 lobby
Finding: Unsatisfactory paint finish to lobby corridorceiling
Recommendations: Apply another coat of paint to lobby ceiling
402. Location: L9 lobby
Finding: Damaged plasterboard wall behind level 9signage
Recommendations: Remove signage, make good plater wall and re‐ apply signage
8/16/2019 Building Defect Reports Sample 1
134/220
Item Defect Details Photographic Details
403. Location: L9 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
404. Location: L9 water meter cupboard
Finding: Hole in plasterboard wall
Recommendations: Patch, sand and paint plasterboard wall andmake good
405. Location: L9 water meter cupboard
Finding: Cupboard generally dirty
Recommendations:
Builders clean required
8/16/2019 Building Defect Reports Sample 1
135/220
Item Defect Details Photographic Details
406. Location: L9 water meter cupboard
Finding: Rough plaster finish above water meter signage
Recommendations: Make good plaster board wall behind signage
407. Location: L9 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
408. Location: L9 water meter cupboard
Finding: Sticky tape left behind on all hinges
Recommendations:
Remove sticky tape from all hinges
8/16/2019 Building Defect Reports Sample 1
136/220
8/16/2019 Building Defect Reports Sample 1
137/220
Item Defect Details Photographic Details
412. Location: L9 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
413. Location: L9 water meter cupboard
Finding: Unsatisfactory paint finish and generally dirty
Recommendations: Re‐paint walls and builders clean required
414. Location: L9 corridor
Finding: Unsatisfactory paint finish around EWIS speaker
Recommendations:
Patch, sand and re‐paint around EWIS speakerand make good
8/16/2019 Building Defect Reports Sample 1
138/220
Item Defect Details Photographic Details
415. Location: L9 water meter cupboard
Finding: Sticky tape left behind on all hinges
Recommendations: Remove sticky tape from all hinges
416. Location: L9 water meter cupboard
Finding: Missing caulking between plasterboard anddoor frame
Recommendations: Caulk between plasterboard and door frame
417. Location: L9 water meter cupboard
Finding: Sticky tape left behind on all hinges
Recommendations: Remove sticky tape from all hinges
8/16/2019 Building Defect Reports Sample 1
139/220
Item Defect Details Photographic Details
418. Location: L10 Electrical room
Finding: Uneven floor level
Recommendations: Fill and make level with rest of electrical roomfloor
419. Location: L10 Electrical room
Finding: Building materials left in room
Recommendations: Dispose of building materials appropriately andarea requires builders clean
420. Location: L10 Electrical room
Finding: 1 x unsealed penetrations
Recommendations:
Correctly seal penetrations in concrete slab inline with building code for fire preventionthrough floors
8/16/2019 Building Defect Reports Sample 1
140/220
Item Defect Details Photographic Details
421. Location: L10 Electrical room
Finding: Room generally dirty
Recommendations: Builders clean required
422. Location: L10 Electrical room
Finding: Steel stud fixed to door frame and missingcaulking to edge of door frame to wall
Recommendations: Remove steel stud, and caulk along edge ofdoor frame
423. Location: L10 Electrical room
Finding: 2 x unsealed penetrations
Recommendations:
Correctly seal penetrations in concrete slab inline with building code for fire preventionthrough floors
8/16/2019 Building Defect Reports Sample 1
141/220
Item Defect Details Photographic Details
424. Location: L10 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
425. Location: L10 refuse room
Finding: Unsatisfactory paint finish to wall
Recommendations: Patch, sand and re‐paint wall and make good
426. Location: L10 corridor near passenger lifts
Finding: Incomplete paint finish to skirtings
Recommendations:
Finish painting skirting
8/16/2019 Building Defect Reports Sample 1
142/220
Item Defect Details Photographic Details
427. Location: L10 corridor
Finding: Paint patches to ceiling
Recommendations: Apply another coat of paint to lobby ceiling
428. Location: L10 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
429. Location: L10 water meter cupboard
Finding: Sticky tape left behind on all hinges
Recommendations:
Remove sticky tape from all hinges
8/16/2019 Building Defect Reports Sample 1
143/220
Item Defect Details Photographic Details
430. Location: L10 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
431. Location: L10 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
432. Location: L10 water meter cupboard
Finding: 2 x screws missing from hinge
Recommendations:
Install 2 x new screws into hinge
8/16/2019 Building Defect Reports Sample 1
144/220
Item Defect Details Photographic Details
433. Location: L10 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
434. Location: L10 water meter cupboard
Finding: Unsatisfactory sealing of penetration
Recommendations: Remove material inside penetration and re‐seal with an appropriate sealant to prevent firethrough concrete slab
435. Location: L10 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
8/16/2019 Building Defect Reports Sample 1
145/220
Item Defect Details Photographic Details
436. Location: L10 services cupboard
Finding: Building materials stored inside cupboard
Recommendations: Builders clean required
437. Location: L10 services cupboard
Finding: Tape on hinges
Recommendations: Remove tape from hinges
438. Location: L11 electrical room
Finding: Door hardware left on ground
Recommendations:
Install door hardware or remove. Builders cleanrequired
8/16/2019 Building Defect Reports Sample 1
146/220
Item Defect Details Photographic Details
439. Location: L11 electrical room
Finding: Area generally dirty
Recommendations: Builders clean required
440. Location: L11 electrical room
Finding: Unsatisfactory wall finish
Recommendations: Patch, fill and paint wall and make good incorner
441. Location: L11 Electrical room
Finding: Unsealed penetrations visible
Recommendations:
Correctly seal penetrations in concrete slab inline with building code for fire preventionthrough floors
8/16/2019 Building Defect Reports Sample 1
147/220
Item Defect Details Photographic Details
442. Location: L11 Electrical room
Finding: Steel stud fixed to door frame and missingcaulking to edge of door frame to wall
Recommendations: Remove steel stud, and caulk along edge ofdoor frame
443. Location: L11 Electrical room
Finding: Painting incomplete
Recommendations: Finish off painting to wall
444. Location: L11 Electrical room
Finding: No trim on carpet tile threshold
Recommendations:
Install trim to edge of carpet tiles into electricalroom
8/16/2019 Building Defect Reports Sample 1
148/220
Item Defect Details Photographic Details
445. Location: L11 Electrical room
Finding: Unable to close door as striker plate is blocked
Recommendations: Un block/remove debris from striker plate
446. Location: L11 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
447. Location: L11 water meter cupboard
Finding: Unsatisfactory sealing of penetration
Recommendations:
Remove material inside penetration and re‐seal with an appropriate sealant to prevent firethrough concrete slab
8/16/2019 Building Defect Reports Sample 1
149/220
Item Defect Details Photographic Details
448. Location: L11 water meter cupboard
Finding: 2 x screws missing from hinge
Recommendations: Install 2 x new screws into hinge
449. Location: L11 water meter cupboard
Finding: Unsatisfactory sealing of penetration
Recommendations: Remove material inside penetration and re‐seal with an appropriate sealant to prevent firethrough concrete slab
450. Location: L11 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
8/16/2019 Building Defect Reports Sample 1
150/220
Item Defect Details Photographic Details
451. Location: L11 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
452. Location: L11 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
453. Location: L11 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
8/16/2019 Building Defect Reports Sample 1
151/220
Item Defect Details Photographic Details
454. Location: L11 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty. Unsatisfactory penetrationsealant
Recommendations: Remove unused cables and builders cleanrequired. Remove material inside penetrationand re‐seal with an appropriate sealant toprevent fire through concrete slab
455. Location: L11 corridor
Finding: Gas shut off valve grille is not sitting correctly
Recommendations: Re‐fix grille into place
456. Location: L11 water meter cupboard
Finding: Unsatisfactory sealing of penetration
Recommendations:
Remove material inside penetration and re‐seal with an appropriate sealant to prevent firethrough concrete slab
8/16/2019 Building Defect Reports Sample 1
152/220
Item Defect Details Photographic Details
457. Location: L11 services cupboard
Finding: Caulking missing to edges of door frames
Recommendations: Caulk edges of door frames
458. Location: L11 services cupboard
Finding: Unsatisfactory paint finish to services cupboarddoor frames
Recommendations: Re‐paint door frames to services cupboard
459. Location: L11 corridor
Finding: Paint on sign
Recommendations:
Builders clean required
8/16/2019 Building Defect Reports Sample 1
153/220
Item Defect Details Photographic Details
460. Location: L12 electrical room
Finding: Builders materials stored on ground
Recommendations: Dispose of hard waste appropriately
461. Location: L12 electrical room
Finding: Unsatisfactory wall finish
Recommendations: Patch, fill and paint wall and make good
462. Location: L12 electrical room
Finding: Concrete splatter to wall
Recommendations:
Builders clean required
8/16/2019 Building Defect Reports Sample 1
154/220
Item Defect Details Photographic Details
463. Location: L12 electrical room
Finding: 3 x conduits protruding through concrete floorslab
Recommendations: Cut back conduit and apply an appropriatesealant in void
464. Location: L12 electrical room
Finding: NBN wiring not secure
Recommendations: Securely fix conduit containing NBN
465. Location: L12 Electrical room
Finding: Steel stud fixed to door frame and missingcaulking to edge of door frame to wall
Recommendations: Remove steel stud, and caulk along edge ofdoor frame
8/16/2019 Building Defect Reports Sample 1
155/220
Item Defect Details Photographic Details
466. Location: L12 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
467. Location: L12 refuse
Finding: Damaged plasterboard wall behind sign
Recommendations: Patch and paint and make good plasterboardwall
468. Location: L12 refuse
Finding: Electrical conduit protruding from concrete slab
Recommendations:
Terminate electrical conduit and fill hole asrequired
8/16/2019 Building Defect Reports Sample 1
156/220
Item Defect Details Photographic Details
469. Location: L12 refuse
Finding: Unused brackets still on slab soffit
Recommendations: Remove unused bracket and fill hole
470. Location: L12 refuse
Finding: Concrete splatter on wall
Recommendations: Builders clean required
471. Location: L12 refuse
Finding: Unsatisfactory plasterboard finish aboveskirting
Recommendations: Patch, sand and paint wall above skirting andmake good
8/16/2019 Building Defect Reports Sample 1
157/220
Item Defect Details Photographic Details
472. Location: L12 water meter cupboard
Finding: Red paint found on wall
Recommendations: Re‐paint back wall
473. Location: L11 water meter cupboard
Finding: Unsatisfactory sealing of penetration
Recommendations: Remove material inside penetration and re‐seal with an appropriate sealant to prevent firethrough concrete slab
474. Location: L12 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
8/16/2019 Building Defect Reports Sample 1
158/220
Item Defect Details Photographic Details
475. Location: L12 water meter cupboard
Finding: Redundant PVC pipework
Recommendations: Investigate redundant PVC pipework andremove
476. Location: L12 water meter cupboard
Finding: Two screws missing from door hinge
Recommendations: Install 2 new screws into hinge
477. Location: L12 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
8/16/2019 Building Defect Reports Sample 1
159/220
Item Defect Details Photographic Details
478. Location: L12 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
479. Location: L12 water meter cupboard
Finding: Redundant PVC pipework, incompletepaintwork
Recommendations: Investigate redundant PVC pipework andremove. Finish painting wall
480. Location: L12 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
8/16/2019 Building Defect Reports Sample 1
160/220
Item Defect Details Photographic Details
481. Location: L12 water meter cupboard
Finding: Unused cables hanging from gauges andgenerally dirty
Recommendations: Remove unused cables and builders cleanrequired
482. Location: L12 water meter cupboard
Finding: Unsatisfactory sealing of penetration
Recommendations: Remove material inside penetration and re‐seal with an appropriate sealant to prevent firethrough concrete slab
483. Location: L12 services cupboard
Finding: Caulking missing to edges of door frames
Recommendations:
Caulk edges of door frames
8/16/2019 Building Defect Reports Sample 1
161/220
Item Defect Details Photographic Details
484. Location: L13 lobby
Finding: Redundant bracket
Recommendations: Remove unused bracket
485. Location: L13 lobby
Finding: Emergency evacuation plan is incorrect
Recommendations: Re‐print emergency evacuation plan to showcorrect orientation
486. Location: L13 lobby
Finding: No seal under plant room door
Recommendations:
Install weather seal to underside of plant roomdoor
8/16/2019 Building Defect Reports Sample 1
162/220
Item Defect Details Photographic Details
487. Location: L13 lobby
Finding: Unused bracket on door frame at floor level
Recommendations: Remove unused bracket
488. Location: L13 roof
Finding: Unsatisfactory discharge of pipe from roofplumbing
Recommendations: Extend pipework to discharge away fromdoorway
489. Location: L13 roof
Finding: Missing hold down bolts to hot water unitstructure
Recommendations: Install bolts in holes provided
8/16/2019 Building Defect Reports Sample 1
163/220
Item Defect Details Photographic Details
490. Location: L13 roof
Finding: Threads have not been cut off to be flush withnut
Recommendations: Trim down all threads
491. Location: L13 roof
Finding: Threads have not been cut off to be flush withnut
Recommendations: Trim down all threads
492. Location: L13 roof
Finding: Threads have not been cut off to be flush withnut
Recommendations: Trim down all threads
8/16/2019 Building Defect Reports Sample 1
164/220
Item Defect Details Photographic Details
493. Location: L13 roof
Finding: Threads have not been cut off to be flush withnut
Recommendations: Trim down all threads
494. Location: L13 roof
Finding: Threads have not been cut off to be flush withnut
Recommendations: Trim down all threads
495. Location: L13 roof
Finding: Threads have not been cut off to be flush withnut
Recommendations: Trim down all threads
8/16/2019 Building Defect Reports Sample 1
165/220
Item Defect Details Photographic Details
496. Location: L13 roof
Finding: Building materials stored on roof
Recommendations: Remove all builders materials and clean area
497. Location: East side external canopy
Finding: Gutters blocked
Recommendations: Remove all foliage and debris from gutters
498. Location: East side external canopy
Finding: Gutters blocked
Recommendations:
Remove all foliage and debris from gutters
8/16/2019 Building Defect Reports Sample 1
166/220
Item Defect Details Photographic Details
499. Location: East side external canopy
Finding: Gutters blocked
Recommendations: Remove all foliage and debris from gutters
500. Location: L13 roof
Finding: Pathway along east elevation is generally dirty
Recommendations: Builders clean required
501. Location: L13 roof
Finding: Water pooling on roof
Recommendations:
Re‐level area to correct falls
8/16/2019 Building Defect Reports Sample 1
167/220
Item Defect Details Photographic Details
502. Location: L13 roof
Finding: Balustrade missing
Recommendations: Investigate if balustrade is required in this area
503. Location: L13 roof
Finding: Window seals are dirty and deteriorating
Recommendations: Replace window seals
504. Location: L13 roof
Finding: Window seals are dirty and deteriorating
Recommendations:
Replace window seals
8/16/2019 Building Defect Reports Sample 1
168/220
8/16/2019 Building Defect Reports Sample 1
169/220
Item Defect Details Photographic Details
508. Location: L13 roof
Finding: High spots on ground surrounding floor waste
Recommendations: Re‐align falls so that water can flow easily intofloor waste
509. Location: L13 roof
Finding: Water pooling in corner
Recommendations: Re‐align falls so that water can flow easily intofloor waste
510. Location: L13 roof
Finding: Markings on external cladding
Recommendations:
Builders clean required
8/16/2019 Building Defect Reports Sample 1
170/220
Item Defect Details Photographic Details
511. Location: L13 roof
Finding: Aluminium capping is coming away fromstructure
Recommendations: Re‐fix aluminium so as to not allow wateringress
512. Location: East side external canopy
Finding: Zoomed out photo of location of blockedgutters
Recommendations: Remove all foliage and debris from gutters
513. Location: East side external canopy
Finding: Zoomed out photo of location of blockedgutters
Recommendations: Remove all foliage and debris from gutters
8/16/2019 Building Defect Reports Sample 1
171/220
Item Defect Details Photographic Details
514. Location: L13 roof
Finding: Water pooling in corner
Recommendations: Re‐align falls so that water can flow easily intofloor waste
515. Location: L13 roof
Finding: Water pooling in corner and capping missing
Recommendations: Re‐align falls so that water can flow easily intofloor waste
516. Location: L13 roof, top floor external windows
Finding: Large gaps between window sections
Recommendations:
Investigate if within tolerance
8/16/2019 Building Defect Reports Sample 1
172/220
Item Defect Details Photographic Details
517. Location: L13 roof
Finding: Capping piece of parapet to roof level
Recommendations: Caulk to underside of capping
518. Location: L13 roof, top floor external windows
Finding: Large gaps between window sections
Recommendations: Investigate if within tolerance
519. Location: L13 roof, top floor external windows
Finding: Large gaps between window sections
Recommendations:
Investigate if within tolerance
8/16/2019 Building Defect Reports Sample 1
173/220
Item Defect Details Photographic Details
520. Location: South east side external canopy
Finding: Zoomed out photo of location of blockedgutters
Recommendations: Remove all foliage and debris from gutters
521. Location: L13 roof
Finding: No waterproofing membrane present
Recommendations: Investigate construction drawings to determineif this is required
522. Location: L13 roof
Finding: No waterproofing membrane present
Recommendations:
Investigate construction drawings to determineif this is required
8/16/2019 Building Defect Reports Sample 1
174/220
Item Defect Details Photographic Details
523. Location: L13 roof
Finding: Edges of zincalume decking roof are not sealed
Recommendations: Seal edges /caulk from concrete to roofstructure
524. Location: L13 roof
Finding: End capping of roof coming away fromzincalume
Recommendations: Re‐fix capping piece so as to avoid wateringress through exposed edges
525. Location: L13 roof
Finding: Long threads protruding from cladding supportstructure
Recommendations: Trim down all threads appropriately
8/16/2019 Building Defect Reports Sample 1
175/220
Item Defect Details Photographic Details
526. Location: L13 roof
Finding: No waterproofing membrane present
Recommendations: Investigate construction drawings to determineif this is required
527. Location: L13 roof
Finding: No waterproofing membrane present
Recommendations: Investigate construction drawings to determineif this is required
528. Location: Fire stairs
Finding: Light not working
Recommendations:
Replace globe
8/16/2019 Building Defect Reports Sample 1
176/220
Item Defect Details Photographic Details
529. Location: L8 fire stairs
Finding: Sign is not sitting flush
Recommendations: Re‐stick signage to ensure it is flush with wall
530. Location: Street level external paving
Finding: Caulking missing to window frames
Recommendations: Install caulking as required
531. Location: Street level external paving
Finding: Areas of paving uneven and dropping in someareas
Recommendations: Ensure all paving is at the same level
8/16/2019 Building Defect Reports Sample 1
177/220
Item Defect Details Photographic Details
532. Location: Street level external paving
Finding: Areas of paving uneven and dropping in someareas
Recommendations: Ensure all paving is at the same level
533. Location: Street level external paving
Finding: Cracked pavers
Recommendations: Replace as required
534. Location: Street level external paving
Finding: Areas of paving uneven and dropping in someareas
Recommendations: Ensure all paving is at the same level
8/16/2019 Building Defect Reports Sample 1
178/220
Item Defect Details Photographic Details
535. Location: Street level east side
Finding: Bent metal screen
Recommendations: Replace as required
536. Location: Street level external paving
Finding: Cracked pavers
Recommendations: Replace as required
537. Location: Street level
Finding: Generally dirty in service cupboards
Recommendations:
Builders clean required
8/16/2019 Building Defect Reports Sample 1
179/220
Item Defect Details Photographic Details
538. Location: Street level – north side
Finding: Generally dirty in service cupboards, concretesplatter evident on door frames
Recommendations: Builders clean required
539. Location: Street level – north side
Finding: 2 x unsealed penetrations
Recommendations: Apply appropriate sealant at penetrationlocations
540. Location: Street level
Finding: Generally dirty in service cupboards
Recommendations:
Builders clean required
8/16/2019 Building Defect Reports Sample 1
180/220
Item Defect Details Photographic Details
541. Location: Street level – north side service cupboards
Finding: Unfinished painting
Recommendations: Finish off painting to bare material
542. Location: North side windows
Finding: Still dirty and paint splatter evident
Recommendations: Builders clean required
543. Location: North side windows
Finding: Still dirty and paint splatter evident
Recommendations:
Builders clean required
8/16/2019 Building Defect Reports Sample 1
181/220
Item Defect Details Photographic Details
544. Location: West elevation
Finding: Timber screens not fixed securely
Recommendations: Investigate fixing details and rectify accordingly
545. Location: West side stairs at street level
Finding: Missing stair nosing
Recommendations: Install new stair nosing
546. Location: Underside of walkway at ground floor betweenbuilding
Finding: Rough finish to cladding
Recommendations: Re‐paint and make good cladding to undersideof walkway roof
8/16/2019 Building Defect Reports Sample 1
182/220
Item Defect Details Photographic Details
547. Location: Street level
Finding: Missing caulking between pavers and windowframes
Recommendations: Install appropriate caulking between paversand window frame
548. Location: Street level
Finding: Missing caulking between pavers and windowframes
Recommendations: Install appropriate caulking between paversand window frame
549. Location: Street level
Finding: Missing caulking between pavers and windowframes
Recommendations: Install appropriate caulking between paversand window frame
8/16/2019 Building Defect Reports Sample 1
183/220
Item Defect Details Photographic Details
550. Location: South side of building
Finding: Un painted concrete
Recommendations: Apply appropriate paint finish to bare concrete
551. Location: Street level – West side near train station
Finding: Large gaps visible between 2 adjoining buildingmaterials
Recommendations: Install appropriate caulking to gaps
8/16/2019 Building Defect Reports Sample 1
184/220
Part 2: Thermal Leak Detection
8/16/2019 Building Defect Reports Sample 1
185/220
1/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]
Ar1 Max 18.0
Min 16.7
Average 17.6
Emissivity 0.86 Refl. temp. 20 °C
Measurements °C 13/10/2014 9:54:10 PM °C 18.9
Parameters Ar1
14.9 FLIR0458.jpg FLIR E6 63931855
13/10/2014 9:54:10 PM
FLIR0458.jpg FLIR E6 63931855
mailto:[email protected]:[email protected]:[email protected]
8/16/2019 Building Defect Reports Sample 1
186/220
Measurements °C 13/10/2014 11:18:40 PM °C
32/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]
Ar1 Max 16.4
Min 14.5
Average 15.6
Emissivity 0.86 Refl. temp. 20 °C
17.3
Parameters Ar1
13.2 FLIR0514.jpg FLIR E6 63931855
13/10/2014 11:18:40 PM
FLIR0514.jpg FLIR E6 63931855
mailto:[email protected]:[email protected]:[email protected]
8/16/2019 Building Defect Reports Sample 1
187/220
Measurements °C 13/10/2014 11:19:35 PM °C
33/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]
Ar1 Max 16.1
Min 13.4
Average 15.0
Emissivity 0.86 Refl. temp. 20 °C
16.6
Parameters Ar1
12.5 FLIR0516.jpg FLIR E6 63931855
13/10/2014 11:19:35 PM
FLIR0516.jpg FLIR E6 63931855
mailto:[email protected]:[email protected]:[email protected]
8/16/2019 Building Defect Reports Sample 1
188/220
Measurements °C 13/10/2014 11:19:45 PM °C
35/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]
Ar1 Max 16.7
Min 14.9
Average 16.0
Emissivity 0.86 Refl. temp. 20 °C
16.6
Parameters Ar1
12.5 FLIR0518.jpg FLIR E6 63931855
13/10/2014 11:19:48 PM
FLIR0518.jpg FLIR E6 63931855
mailto:[email protected]:[email protected]:[email protected]
8/16/2019 Building Defect Reports Sample 1
189/220
Measurements °C 13/10/2014 11:20:07 PM °C
36/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]
Ar1 Max 16.9
Min 15.4
Average 16.4
Emissivity 0.86 Refl. temp. 20 °C
17.4
Parameters Ar1
13.3 FLIR0520.jpg FLIR E6 63931855
13/10/2014 11:20:07 PM
FLIR0520.jpg FLIR E6 63931855
mailto:[email protected]:[email protected]:[email protected]
8/16/2019 Building Defect Reports Sample 1
190/220
Measurements °C 13/10/2014 11:20:15 PM °C
37/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]
Ar1 Max 17.2
Min 14.7
Average 16.3
Emissivity 0.86 Refl. temp. 20 °C
17.5
Parameters Ar1
13.4 FLIR0522.jpg FLIR E6 63931855
13/10/2014 11:20:15 PM
FLIR0522.jpg FLIR E6 63931855
mailto:[email protected]:[email protected]:[email protected]
8/16/2019 Building Defect Reports Sample 1
191/220
Measurements °C 13/10/2014 11:20:32 PM °C
38/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]
Ar1 Max 16.4
Min 14.0
Average 15.6
Emissivity 0.86 Refl. temp. 20 °C
16.6
Parameters Ar1
12.5 FLIR0524.jpg FLIR E6 63931855
13/10/2014 11:20:32 PM
FLIR0524.jpg FLIR E6 63931855
mailto:[email protected]:[email protected]:[email protected]
8/16/2019 Building Defect Reports Sample 1
192/220
Measurements °C 13/10/2014 11:21:15 PM °C
39/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]
Ar1 Max 16.8
Min 14.8
Average 16.2
Emissivity 0.86 Refl. temp. 20 °C
17.4
Parameters Ar1
13.4 FLIR0526.jpg FLIR E6 63931855
13/10/2014 11:21:15 PM
FLIR0526.jpg FLIR E6 63931855
mailto:[email protected]:[email protected]:[email protected]
8/16/2019 Building Defect Reports Sample 1
193/220
Measurements °C 13/10/2014 11:22:09 PM °C
40/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]
Ar1 Max 16.5
Min 14.3
Average 15.7
Emissivity 0.86 Refl. temp. 20 °C
16.8
Parameters Ar1
12.7 FLIR0528.jpg FLIR E6 63931855
13/10/2014 11:22:09 PM
FLIR0528.jpg FLIR E6 63931855
mailto:[email protected]:[email protected]:[email protected]
8/16/2019 Building Defect Reports Sample 1
194/220
Measurements °C 14/10/2014 12:30:45 AM °C
41/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]
Ar1 Max 22.5
Min 19.8
Average 20.7
Emissivity 0.86 Refl. temp. 20 °C
22.3
Parameters Ar1
18.2 FLIR0530.jpg FLIR E6 63931855
14/10/2014 12:30:45 AM
FLIR0530.jpg FLIR E6 63931855
mailto:[email protected]:[email protected]:[email protected]
8/16/2019 Building Defect Reports Sample 1
195/220
Measurements °C 14/10/2014 12:36:24 AM °C
42/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]
Ar1 Max 18.7
Min 16.9
Average 17.9
Emissivity 0.86 Refl. temp. 20 °C
19.3
Parameters Ar1
15.2 FLIR0532.jpg FLIR E6 63931855
14/10/2014 12:36:24 AM
FLIR0532.jpg FLIR E6 63931855
mailto:[email protected]:[email protected]:[email protected]
8/16/2019 Building Defect Reports Sample 1
196/220
Measurements °C 14/10/2014 12:36:55 AM °C
43/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]
Ar1 Max 18.5
Min 17.9
Average 18.2
Emissivity 0.86 Refl. temp. 20 °C
18.4
Parameters Ar1
14.4 FLIR0534.jpg FLIR E6 63931855
14/10/2014 12:36:55 AM
FLIR0534.jpg FLIR E6 63931855
mailto:[email protected]:[email protected]:[email protected]
8/16/2019 Building Defect Reports Sample 1
197/220
Measurements °C 14/10/2014 12:38:10 AM °C
45/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]
Ar1 Max 17.4
Min 14.6
Average 16.4
Emissivity 0.86 Refl. temp. 20 °C
17.7
Parameters Ar1
13.7 FLIR0538.jpg FLIR E6 63931855
14/10/2014 12:38:10 AM
FLIR0538.jpg FLIR E6 63931855
mailto:[email protected]:[email protected]:[email protected]
8/16/2019 Building Defect Reports Sample 1
198/220
Measurements °C 14/10/2014 12:38:51 AM °C
46/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]
Ar1 Max 18.1
Min 15.0
Average 17.2
Emissivity 0.86 Refl. temp. 20 °C
22.5
Parameters Ar1
14.1 FLIR0540.jpg FLIR E6 63931855
14/10/2014 12:38:51 AM
FLIR0540.jpg FLIR E6 63931855
mailto:[email protected]:[email protected]:[email protected]
8/16/2019 Building Defect Reports Sample 1
199/220
Measurements °C 14/10/2014 12:39:08 AM °C
47/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]
Ar1 Max 18.0
Min 16.9
Average 17.5
Emissivity 0.86 Refl. temp. 20 °C
17.7
Parameters Ar1
13.7 FLIR0542.jpg FLIR E6 63931855
14/10/2014 12:39:08 AM
FLIR0542.jpg FLIR E6 63931855
mailto:[email protected]:[email protected]:[email protected]
8/16/2019 Building Defect Reports Sample 1
200/220
Measurements °C 14/10/2014 12:39:28 AM °C
48/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]
Ar1 Max 17.2
Min 14.0
Average 15.8
Emissivity 0.86 Refl. temp. 20 °C
16.9
Parameters Ar1
12.8 FLIR0544.jpg FLIR E6 63931855
14/10/2014 12:39:28 AM
FLIR0544.jpg FLIR E6 63931855
mailto:[email protected]:[email protected]:[email protected]
8/16/2019 Building Defect Reports Sample 1
201/220
Measurements °C 14/10/2014 12:39:47 AM °C
49/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]
Ar1 Max 17.4
Min 14.9
Average 16.1
Emissivity 0.86 Refl. temp. 20 °C
17.7
Parameters Ar1
13.7 FLIR0546.jpg FLIR E6 63931855
14/10/2014 12:39:47 AM
FLIR0546.jpg FLIR E6 63931855
mailto:[email protected]:[email protected]:[email protected]
8/16/2019 Building Defect Reports Sample 1
202/220
Measurements °C 14/10/2014 12:39:57 AM °C
50/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]
Ar1 Max 18.5
Min 15.1
Average 17.4
Emissivity 0.86 Refl. temp. 20 °C
18.3
Parameters Ar1
13.9 FLIR0548.jpg FLIR E6 63931855
14/10/2014 12:39:57 AM
FLIR0548.jpg FLIR E6 63931855
mailto:[email protected]:[email protected]:[email protected]
8/16/2019 Building Defect Reports Sample 1
203/220
Measurements °C 14/10/2014 12:41:30 AM °C
51/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]
Ar1 Max 18.3
Min 17.5
Average 17.9
Emissivity 0.86 Refl. temp. 20 °C
19.9
Parameters Ar1
15.8 FLIR0550.jpg FLIR E6 63931855
14/10/2014 12:41:30 AM
FLIR0550.jpg FLIR E6 63931855
mailto:[email protected]:[email protected]:[email protected]
8/16/2019 Building Defect Reports Sample 1
204/220
Measurements °C 14/10/2014 12:43:02 AM °C
53/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]
Ar1 Max 15.9
Min 14.4
Average 15.3
Emissivity 0.86 Refl. temp. 20 °C
17.1
Parameters Ar1
12.1 FLIR0552.jpg FLIR E6 63931855
14/10/2014 12:43:02 AM
FLIR0552.jpg FLIR E6 63931855
mailto:[email protected]:[email protected]:[email protected]
8/16/2019 Building Defect Reports Sample 1
205/220
8/16/2019 Building Defect Reports Sample 1
206/220
Measurements °C 14/10/2014 12:46:54 AM °C
55/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]
Ar1 Max 18.5
Min 16.7
Average 17.8
Emissivity 0.86 Refl. temp. 20 °C
19.4
Parameters Ar1
15.4 FLIR0556.jpg FLIR E6 63931855
14/10/2014 12:47:53 AM
FLIR0556.jpg FLIR E6 63931855
mailto:[email protected]:[email protected]:[email protected]
8/16/2019 Building Defect Reports Sample 1
207/220
Measurements °C 14/10/2014 12:48:21 AM °C
56/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]
Ar1 Max 19.0
Min 16.7
Average 18.1
Emissivity 0.86 Refl. temp. 20 °C
19.0
Parameters Ar1
14.8 FLIR0558.jpg FLIR E6 63931855
14/10/2014 12:48:21 AM
FLIR0558.jpg FLIR E6 63931855
mailto:[email protected]:[email protected]:[email protected]
8/16/2019 Building Defect Reports Sample 1
208/220
Part 3: Videos Videos
8/16/2019 Building Defect Reports Sample 1
209/220
Part 4 : Marked up Plan of Defect Locations
8/16/2019 Building Defect Reports Sample 1
210/220
5 6
3 2 1
4
8
9
10
11
12 7
13
14
15
16
25
24
23
26
22
21 17
19
18
20
8/16/2019 Building Defect Reports Sample 1
211/220
67 60 61
66 56
38
68 59
57 37
55 62
63
64
65
69
53 70
54 71
51 72
52 47
58 50
46
45 49
44
36
43 35
42 34 48
33 41
32
31
40
39
30 29
28 27
8/16/2019 Building Defect Reports Sample 1
212/220
n
m
190-210 Switchboard room
149 & 150
162
140
141
134 & 135 136
137
138
139
161
151
152
132
133
127
128 131
124 73 144
123
122
124
125
126
129
142
145
146
147 & 148 153
163 & 164
117
130
116 74
115
114
154
155
156
165
166, 167, 168 & 169
172
170 143
173
171
174
175
176
182, 183
& 184
110
109
108
118
106
105
104
113
112
111
103
102
75
157
158
159
160
180
179
177
97
96
178
107
95
181
94
119, 120 & 121
76
77
78
79
188
91
89
88
185 & 186
187 93
92
189
80
81
101
100 99
98
82
87 86 83 84
90 85
8/16/2019 Building Defect Reports Sample 1
213/220
244 243
211 212
245
241 242
239 240 249
238
248
246
236 213
237
252 - 258 Lobby 235
232 214 247
215
234
230 233
229
228
227
223 216, 217, 218 & 219
225 226
224 231
221 222 220
BASEMENT 02UPPER
8/16/2019 Building Defect Reports Sample 1
214/220
278 277
267
268
265
266
264
274 259 & 260
269 262
276 270 261 263
272 & 273
275
271
8/16/2019 Building Defect Reports Sample 1
215/220
280
281 282
279
8/16/2019 Building Defect Reports Sample 1
216/220
Part 5: Terms and Conditions The following information is very important and forms an integral part of this report.
Before you decide to purchase this property you should read and understand the following important information. Itwill help explain what is involved in a Standard Property Inspection, the difficulties faced by an inspector and why it isnot possible to guarantee that a property is free of defects, latent or otherwise. This information forms an integral partof the report. The general adequacy of site drainage is not included in the Standard Property Inspection Report.Comments on surface water drainage are limited as where there has been either little or no rainfall for a period of time,surface water drainage may appear to be adequate but then during periods of heavy rain, may be found to beinadequate. Any comments made in this section are relevant only in light of the conditions present at the time ofinspection. It is recommended that a Smoke Test be obtained to determine any illegal connections, blocked or brokendrains.
1. This is a Visual Inspection only and in Accordance with AS4349.1
This visual inspection is limited to those areas and sections of the property fully accessible and visible to the Inspector at thetime and on the date of Inspection. The inspection DID NOT include breaking apart, dismantling, removing or movingobjects including, but not limited to, foliage, mouldings, roof insulation/sarking membrane , floor or wall coverings,sidings, ceilings, floors, furnishings, appliances or personal possessions. The Inspector CANNOT see inside walls,between floors, inside skillion roofing, inside the eaves, behind stored goods in cupboards, or other areas that areconcealed or obstructed. The inspector DID NOT dig, gouge, force or perform any invasive procedures. In an occupiedproperty it must be understood that furnishings or household items may conceal defects which may only be revealedwhen the items are removed. No detailed inspection is inferred to external areas over 3.6 metres above the naturalground level.
2. Scope of Report The Standard Property Report is not intended as a certificate of compliance of the property within the requirements ofany Act, regulation, ordinance or by ‐law, or, as a warranty or an insurance policy against problems developing with thebuilding in the future.
3. Limitations Nothing contained in the Report implies that any inaccessible or partly inaccessible area(s) or section(s) of the property beinginspected by the Inspector on the date of the inspection were free from defects latent or otherwise.
No responsibility can be accepted for defects which are latent or otherwise not reasonably detected on a visual inspectionwithout interference with or removal of any of the structure including fixtures or fittings within the building.
This Standard Property Report does not contain any assessment or opinion in relation to any item, which is the subject of aSpecial Purpose Property Report (as defined in AS4349.1), or any matter where the inspection or assessment of which is
solely regulated by Statute. Special Purpose Property Reports include comment on the following: Common property areas,environmental concerns such as sunlight, privacy, streetscape and views. Proximity of property to flight paths, railways andbusy traffic or other neighbourhood issues. Noise levels, health and safety issues including the presence of asbestos or lead.Heritage concerns. Security or fire protection. Analysis of site drainage apart from surface water drainage. Swimming poolsand spas. Detection and identification of illegal and unauthorised building and plumbing work. Durability of exposedfinishes.
4. Important Information Any person who relies upon the contents of this Report does so acknowledging that the above clauses, definitions anddisclaimers that follow define the Scope and Limitations of the inspection and form an integral part of the report.
8/16/2019 Building Defect Reports Sample 1
217/220
5. Disclaimer of Liability No liability shall be accepted on account of failure of the Report to notify any problems in any area(s) or section(s) of thesubject property physically inaccessible for inspection, or to which access for Inspection is denied by or to the Inspector(including but not limited to any area(s) or section(s) so specified by the Report.
6. Disclaimer of Liability to Third Parties This report is made solely for the use and benefit of the Client named on the front of this report. No liability orresponsibility whatsoever, in contract or tort, is accepted to any third party who may rely on the Report wholly or in part.Any third party acting or relying on this Report, in whole or in part does so at their own risk.
7. Report Definition This report is limited to a visual inspection of areas where reasonable access is available at the time of inspection. Itdoes not purport to be geological as to foundation integrity or soil conditions, engineering as to structural, nor does it cover the
condition of electrical, plumbing, gas or motorised appliances. It is strongly recommended that an appropriatelyqualified contractor check these services prior to purchase.
As the date if this report we have identified the items as listed herein, we do not accept any responsibility for itemswhich may be damaged after the inspection has been completed.
As a matter of course, and in the interests of safety, all prospective purchasers should have an electrical report carriedout by a suitably qualified contractor. This report is limited to (unless otherwise noted) the main structure on the siteand any other building, structure or outbuilding specifically named within the report.
This Report attempts to assist in judging a building according to its age and level of maintenance and in providingrelative comparisons. This inspection and report is not to be considered all ‐encompassing dealing with a building fromevery aspect. Rather it should be seen as a reasonable attempt to identify any significant defects visible at the time ofthe inspection. It is unrealistic to expect comment on minor defects or imperfections in the Standard Property Report. Ifthis is required, a Special Purpose Property Report is recommended.
Whilst buildings may have many pleasing features there are few without defects and many are due naturally to agedeterioration. Subject to the level of maintenance on the building it is common for the number of faults to haveincreased with age.
All items that are considered to be concealed or latent defects are excluded.
Shower Recesses: Tests may be made on shower recesses to detect leaks (if water is connected). The tests may notreveal leaks or show incorrect waterproofing if silicone liquid or masonry sealant has been applied prior to theinspection. Such application is a temporary waterproofing measure and may last for some months before breakingdown. The tests on shower recesses are limited to running water within the recesses and visually checking for leaks. As showersare only checked for a short period of time, prolonged use may reveal leaks that were not detected at the time of inspection.
If there is no evidence of a current leak during inspection that does not necessarily mean that the shower does not leak. Glass Caution: Glazing in older houses (built before 1978) may not necessarily comply with current glass safety standardsAS1288. In the interests of safety, glass panes in doors and windows especially in trafficable areas should be replacedwith safety glass or have shatterproof film installed unless they already comply with the current standard.
Stairs & Balustrades: Specifications have been laid down by the Australian Building Code ‐ Section 3.9 covering stairs,landings and balustrades to ensure the safety of all occupants and visitors in a building. Many balustrades and stairsbuilt before 1996 may not comply with the current standard. You must upgrade all such items to the current standardto improve safety.
Swimming Pools: If a swimming pool is present it should be the subject of a Special Purpose Property Report. A detailedinspection on the status or serviceability of any swimming pool or associated pool equipment has not been carried outand is not within the scope of this report. Additionally, to adequately inspect a swimming pool, the water must be
completely drained and all internal surfaces must be fully accessible. This report may contain notable observations, together with what is considered to be helpful information and advice.
8/16/2019 Building Defect Reports Sample 1
218/220
This report does not identify timber ‐destroying pests. A timber pest inspection report should be obtained from a qualified timber pest inspector.
If any cost of work estimates is given, these are merely opinions and should be taken as a general guide only. In the
building industry, experience has shown that prices vary considerably and you must obtain independent quotations onany significant notable item from several contractors prior to purchase.
The operation of fireplaces, chimneys, alarm systems, intercom systems, electrical and mechanical appliances, airconditioning systems, smoke detectors and residual current devices have not been tested and are the subject of aSpecial Purpose Property Report. Should you require an inspection to be carried out on any item not specificallycovered by this report, please request a Special Purpose Property Report on the specific item required.
No report is made on the presence, operation, installation or cabling of any free to air or pay television system.
8. Lighting Installations It should be noted that this inspection was done during daylight hours and therefore the adequacy of lighting indarkness could not be directly assessed.
9. Electrical Installations We have carried out a thorough visual inspection of the common property and assets visible from the commonproperty areas. If there were any visible electrical installation issues they have been included in this section of the report.We have not carried out a thorough inspection of electrical installation and the main switchboard, as we are notqualified to do so, please ensure that a suitably qualified electrical contractor carries out a thorough visual inspection atleast every 2 years, this inspection can be incorporated with the testing of the Residual Current Device if CommunityCircuits are present.
10. Plumbing, Gutters & Downpipes and Roofs We have carried out a thorough visual inspection of the common property and assets visible from the commonproperty areas. If there were any visible plumbing, gutters and downpipes or roof issues they have been included in thissection of the report. We have not carried out a thorough inspection of the plumbing, gutters and downpipes and roof, aswe are not qualified to do so, please ensure that a suitably qualified plumbing contractor (who is qualified to undertake roofinspections) carries out a thorough regular inspection. We will recommend a qualified plumber to inspect if an issue isfound.
11. Lifts Please ensure that if lifts are in the building(s) that regular maintenance programs are in place. This report does notcover lifts.
12. Painting Painting surfaces not exposed to the elements/corrosion should be included in the next painting cycle. Painting foraesthetic purposes is not included in this report.
13. Air Conditioning Only a general external inspection of air conditioning units is carried out where installed, therefore please ensure that ifthe Owners Corporation has air conditioner(s) in the building(s) they have regular maintenance programs in place. Thisreport does not cover air conditioning units and air condition cooling towers.
14. Glass This report only addresses glass requiring obvious replacement. It does not cover the Building Code,Australian Standard and safety requirements of glass installed in the common property.
8/16/2019 Building Defect Reports Sample 1
219/220
15. Plant and Equipment Please ensure that if the Owners Corporation has plant and equipment in the building(s) that regular maintenanceprograms are in place for each piece of plant and equipment. This report does not cover plant and equipment.
16. Balcony Balustrades Wherever balcony balustrades are installed, please be advised that a comprehensive inspection of balcony railings wasnot carried out as part of this report. Also this report is only a visual inspection of areas accessible from the commonproperty; therefore all balcony balustrades are not viewed. If there are any visible signs of corrosion on the balustradeincluding fixings and/or if the balustrades are over 10 years old a detailed inspection and testing of balustrades shouldbe undertaken.
17. Pest Reports If there are any visible signs of termite damage it is included in this report. We have not carried out a pest inspection of
the site; as we are not qualified to do so, please ensure that a suitably qualified pest inspection contractor carries outthorough regular inspections.
18. Fire Fighting Equipment and Statutory Requirements It has been assumed that any building needing fire fighting equipment to meet legislative requirements such as theBuilding Code of Australia 1996 did meet those requirements at the time of construction. We have not examined thefire safety requirements for the building and make no comment as to the adequacy of the measures found in thecomplex. We have not and do not assess the condition of any fire fighting equipment within the complex. If the BodiesCorporate wishes to ascertain its position with respect to fire safety compliance it may carry out its own assessment.These guidelines should be placed on the Owners Corporation notice board. We have visually inspected the fire fightingequipment but have not carried out any testing and therefore cannot determine if the equipment has been tampered
with or will be effective in case of fire. Rooms below ground level: If there are any rooms under the house or below ground level (whether they be habitableor non ‐habitable rooms), these may be subject to dampness and water penetration. Drains are not always installedcorrectly or could be blocked. It is common to have damp problems and water entry into these types of rooms,especially during periods of heavy rainfall and this may not be evident upon initial inspection. These rooms may nothave council approval. The purchaser should make their own enquiries with the Council to ascertain if approval wasgiven. Where the property is covered by an Owners Corporation (Strata Title), we strongly recommend that an OwnersCorporation search be conducted to ascertain the financial position, the level of maintenance and any other relevantinformation available through the conduct of such an inspection.
19. Services Important Notes: In regard to plumbing or electrical, it should be noted that we are not plumbers or electricians andany comment made is not that of a qualified plumber or electrician. We recommend that a qualified contractor be engagedto make comment.
Roscon Property Services Offices 150 Sydney Road Coburg VIC 3058 I Level 50, 120 Collins Street Melbourne VIC 3000Tel 1800 767 266 I Email [email protected] Web roscon.com.au