Building Defect Reports Sample 1

Embed Size (px)

Citation preview

  • 8/16/2019 Building Defect Reports Sample 1

    1/220

  • 8/16/2019 Building Defect Reports Sample 1

    2/220

  • 8/16/2019 Building Defect Reports Sample 1

    3/220

  • 8/16/2019 Building Defect Reports Sample 1

    4/220

  • 8/16/2019 Building Defect Reports Sample 1

    5/220

  • 8/16/2019 Building Defect Reports Sample 1

    6/220

  • 8/16/2019 Building Defect Reports Sample 1

    7/220

  • 8/16/2019 Building Defect Reports Sample 1

    8/220

  • 8/16/2019 Building Defect Reports Sample 1

    9/220

  • 8/16/2019 Building Defect Reports Sample 1

    10/220

  • 8/16/2019 Building Defect Reports Sample 1

    11/220

  • 8/16/2019 Building Defect Reports Sample 1

    12/220

  • 8/16/2019 Building Defect Reports Sample 1

    13/220

  • 8/16/2019 Building Defect Reports Sample 1

    14/220

  • 8/16/2019 Building Defect Reports Sample 1

    15/220

  • 8/16/2019 Building Defect Reports Sample 1

    16/220

  • 8/16/2019 Building Defect Reports Sample 1

    17/220

  • 8/16/2019 Building Defect Reports Sample 1

    18/220

  • 8/16/2019 Building Defect Reports Sample 1

    19/220

  • 8/16/2019 Building Defect Reports Sample 1

    20/220

  • 8/16/2019 Building Defect Reports Sample 1

    21/220

  • 8/16/2019 Building Defect Reports Sample 1

    22/220

  • 8/16/2019 Building Defect Reports Sample 1

    23/220

  • 8/16/2019 Building Defect Reports Sample 1

    24/220

  • 8/16/2019 Building Defect Reports Sample 1

    25/220

  • 8/16/2019 Building Defect Reports Sample 1

    26/220

  • 8/16/2019 Building Defect Reports Sample 1

    27/220

  • 8/16/2019 Building Defect Reports Sample 1

    28/220

  • 8/16/2019 Building Defect Reports Sample 1

    29/220

  • 8/16/2019 Building Defect Reports Sample 1

    30/220

  • 8/16/2019 Building Defect Reports Sample 1

    31/220

  • 8/16/2019 Building Defect Reports Sample 1

    32/220

  • 8/16/2019 Building Defect Reports Sample 1

    33/220

  • 8/16/2019 Building Defect Reports Sample 1

    34/220

  • 8/16/2019 Building Defect Reports Sample 1

    35/220

  • 8/16/2019 Building Defect Reports Sample 1

    36/220

  • 8/16/2019 Building Defect Reports Sample 1

    37/220

  • 8/16/2019 Building Defect Reports Sample 1

    38/220

  • 8/16/2019 Building Defect Reports Sample 1

    39/220

  • 8/16/2019 Building Defect Reports Sample 1

    40/220

  • 8/16/2019 Building Defect Reports Sample 1

    41/220

  • 8/16/2019 Building Defect Reports Sample 1

    42/220

  • 8/16/2019 Building Defect Reports Sample 1

    43/220

  • 8/16/2019 Building Defect Reports Sample 1

    44/220

  • 8/16/2019 Building Defect Reports Sample 1

    45/220

  • 8/16/2019 Building Defect Reports Sample 1

    46/220

  • 8/16/2019 Building Defect Reports Sample 1

    47/220

  • 8/16/2019 Building Defect Reports Sample 1

    48/220

  • 8/16/2019 Building Defect Reports Sample 1

    49/220

  • 8/16/2019 Building Defect Reports Sample 1

    50/220

  • 8/16/2019 Building Defect Reports Sample 1

    51/220

  • 8/16/2019 Building Defect Reports Sample 1

    52/220

  • 8/16/2019 Building Defect Reports Sample 1

    53/220

  • 8/16/2019 Building Defect Reports Sample 1

    54/220

  • 8/16/2019 Building Defect Reports Sample 1

    55/220

  • 8/16/2019 Building Defect Reports Sample 1

    56/220

  • 8/16/2019 Building Defect Reports Sample 1

    57/220

  • 8/16/2019 Building Defect Reports Sample 1

    58/220

  • 8/16/2019 Building Defect Reports Sample 1

    59/220

  • 8/16/2019 Building Defect Reports Sample 1

    60/220

  • 8/16/2019 Building Defect Reports Sample 1

    61/220

  • 8/16/2019 Building Defect Reports Sample 1

    62/220

  • 8/16/2019 Building Defect Reports Sample 1

    63/220

  • 8/16/2019 Building Defect Reports Sample 1

    64/220

  • 8/16/2019 Building Defect Reports Sample 1

    65/220

  • 8/16/2019 Building Defect Reports Sample 1

    66/220

  • 8/16/2019 Building Defect Reports Sample 1

    67/220

  • 8/16/2019 Building Defect Reports Sample 1

    68/220

  • 8/16/2019 Building Defect Reports Sample 1

    69/220

  • 8/16/2019 Building Defect Reports Sample 1

    70/220

  • 8/16/2019 Building Defect Reports Sample 1

    71/220

  • 8/16/2019 Building Defect Reports Sample 1

    72/220

  • 8/16/2019 Building Defect Reports Sample 1

    73/220

  • 8/16/2019 Building Defect Reports Sample 1

    74/220

  • 8/16/2019 Building Defect Reports Sample 1

    75/220

  • 8/16/2019 Building Defect Reports Sample 1

    76/220

  • 8/16/2019 Building Defect Reports Sample 1

    77/220

  • 8/16/2019 Building Defect Reports Sample 1

    78/220

  • 8/16/2019 Building Defect Reports Sample 1

    79/220

  • 8/16/2019 Building Defect Reports Sample 1

    80/220

  • 8/16/2019 Building Defect Reports Sample 1

    81/220

  • 8/16/2019 Building Defect Reports Sample 1

    82/220

  • 8/16/2019 Building Defect Reports Sample 1

    83/220

  • 8/16/2019 Building Defect Reports Sample 1

    84/220

  • 8/16/2019 Building Defect Reports Sample 1

    85/220

  • 8/16/2019 Building Defect Reports Sample 1

    86/220

  • 8/16/2019 Building Defect Reports Sample 1

    87/220

  • 8/16/2019 Building Defect Reports Sample 1

    88/220

  • 8/16/2019 Building Defect Reports Sample 1

    89/220

  • 8/16/2019 Building Defect Reports Sample 1

    90/220

  • 8/16/2019 Building Defect Reports Sample 1

    91/220

  • 8/16/2019 Building Defect Reports Sample 1

    92/220

  • 8/16/2019 Building Defect Reports Sample 1

    93/220

  • 8/16/2019 Building Defect Reports Sample 1

    94/220

  • 8/16/2019 Building Defect Reports Sample 1

    95/220

  • 8/16/2019 Building Defect Reports Sample 1

    96/220

  • 8/16/2019 Building Defect Reports Sample 1

    97/220

  • 8/16/2019 Building Defect Reports Sample 1

    98/220

  • 8/16/2019 Building Defect Reports Sample 1

    99/220

  • 8/16/2019 Building Defect Reports Sample 1

    100/220

  • 8/16/2019 Building Defect Reports Sample 1

    101/220

  • 8/16/2019 Building Defect Reports Sample 1

    102/220

  • 8/16/2019 Building Defect Reports Sample 1

    103/220

  • 8/16/2019 Building Defect Reports Sample 1

    104/220

  • 8/16/2019 Building Defect Reports Sample 1

    105/220

  • 8/16/2019 Building Defect Reports Sample 1

    106/220

  • 8/16/2019 Building Defect Reports Sample 1

    107/220

  • 8/16/2019 Building Defect Reports Sample 1

    108/220

  • 8/16/2019 Building Defect Reports Sample 1

    109/220

  • 8/16/2019 Building Defect Reports Sample 1

    110/220

  • 8/16/2019 Building Defect Reports Sample 1

    111/220

  • 8/16/2019 Building Defect Reports Sample 1

    112/220

  • 8/16/2019 Building Defect Reports Sample 1

    113/220

    Item Defect Details Photographic Details

    340. Location: L6 Corridor

    Finding: Incomplete paint finish to skirting

    Recommendations: Complete painting works to skirting in corridor

    341. Location: L6 water meter cupboard

    Finding: Damaged plaster board

    Recommendations: Patch, sand and paint area of damage and makegood

    342. Location: L6 water meter cupboard

    Finding: Incomplete painting, remove wires to gauges

    Recommendations:

    Finish painting walls and remove unused wires

  • 8/16/2019 Building Defect Reports Sample 1

    114/220

    Item Defect Details Photographic Details

    343. Location: L6 refuse room

    Finding: Screw hole in door frame

    Recommendations: Fill and sand hole in door frame, paint doorframe

    344. Location: L6 refuse room

    Finding: Damaged plasterboard

    Recommendations: Fill, sand and paint damaged plasterboard andmake good

    345. Location: L6 refuse room

    Finding: Unsatisfactory wall finish

    Recommendations:

    Patch, fill, sand and paint wall and make good

  • 8/16/2019 Building Defect Reports Sample 1

    115/220

    Item Defect Details Photographic Details

    346. Location: L6 water meter cupboard

    Finding: Plastic still left on pipes from painters

    Recommendations: Remove plastic

    347. Location: L6 water meter cupboard

    Finding: Incomplete painting

    Recommendations: Finish painting walls

    348. Location: L6 corridor

    Finding: Apartment signage to door is falling off

    Recommendations:

    Re‐stick signage to apartment door

  • 8/16/2019 Building Defect Reports Sample 1

    116/220

    Item Defect Details Photographic Details

    349. Location: L6 water meter cupboard

    Finding: Unfinished painting around water metersignage

    Recommendations: Paint wall around water meter signage

    350. Location: L6 water meter cupboard

    Finding: Incomplete painting

    Recommendations: Finish painting walls

    351. Location: L6 water meter cupboard

    Finding: Unused wires left on gauges

    Recommendations:

    Remove unused wires

  • 8/16/2019 Building Defect Reports Sample 1

    117/220

    Item Defect Details Photographic Details

    352. Location: L6 water meter cupboard

    Finding: Incomplete painting

    Recommendations: Finish painting walls

    353. Location: L6 water meter cupboard

    Finding: Unused wires left on gauges

    Recommendations: Remove unused wires

    354. Location: L6 Services cupboard

    Finding: Missing caulking along plaster and door frame

    Recommendations:

    Caulk along plaster edge and door frame

  • 8/16/2019 Building Defect Reports Sample 1

    118/220

    Item Defect Details Photographic Details

    355. Location: L7 Corridor

    Finding: Damaged skirting beside passenger lifts

    Recommendations: Remove damaged skirting and replace

    356. Location: L7 Electrical room

    Finding: Generally dirty

    Recommendations: Builders clean required

    357. Location: L7 Electrical room

    Finding: Excess plasterboard stuck to wall aroundpenetrations

    Recommendations: Remove excess plasterboard, patch and fill allholes as required

  • 8/16/2019 Building Defect Reports Sample 1

    119/220

  • 8/16/2019 Building Defect Reports Sample 1

    120/220

    Item Defect Details Photographic Details

    361. Location: L7 electrical room

    Finding: Painting to door incomplete, spacers left in atdoor frame, caulking incomplete

    Recommendations: Paint door, remove spacers and caulk edges ofdoor frame

    362. Location: L7 electrical room

    Finding: Builders marking visible on floor

    Recommendations: Builders clean required

    363. Location: L7 water meter cupboard

    Finding: Unused wires left on gauges

    Recommendations:

    Remove unused wires

  • 8/16/2019 Building Defect Reports Sample 1

    121/220

    Item Defect Details Photographic Details

    364. Location: L7 refuse room

    Finding: Unsatisfactory wall finish

    Recommendations: Patch, fill, sand and paint wall and make good

    365. Location: L7 refuse room

    Finding: Unsealed penetration

    Recommendations: Correctly seal penetrations in concrete slab inline with building code for fire preventionthrough floors

    366. Location: L7 refuse room

    Finding: Grey paint left on door

    Recommendations:

    Builders clean required

  • 8/16/2019 Building Defect Reports Sample 1

    122/220

    Item Defect Details Photographic Details

    367. Location: L7 refuse room

    Finding: Protective sticker on door hardware

    Recommendations: Remove sticker from door hardware

    368. Location: L7 water meter cupboard

    Finding: Concrete splatter and generally dirty

    Recommendations: Builders clean required

    369. Location: L7 water meter cupboard

    Finding: Unused wires left on gauges and roomgenerally dirty

    Recommendations: Remove unused wires and builders cleanrequired

  • 8/16/2019 Building Defect Reports Sample 1

    123/220

  • 8/16/2019 Building Defect Reports Sample 1

    124/220

    Item Defect Details Photographic Details

    373. Location: L7 water meter cupboard

    Finding: Unused wires left on gauges and roomgenerally dirty

    Recommendations: Remove unused wires and builders cleanrequired

    374. Location: L7 water meter cupboard

    Finding: Unused cables hanging from gauges and roomgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

    375. Location: L7 water meter cupboard

    Finding: Unused cables hanging from gauges

    Recommendations:

    Remove unused cables

  • 8/16/2019 Building Defect Reports Sample 1

    125/220

    Item Defect Details Photographic Details

    376. Location: L7 water meter cupboard

    Finding: Concrete splatter on wall

    Recommendations: Builders clean required

    377. Location: L7 services cupboard

    Finding: Adhesive stuck on wall

    Recommendations: Remove excess adhesive and clean as required

    378. Location: L8 Electrical room

    Finding: Building materials stored and generally dirty

    Recommendations:

    Dispose of building materials appropriately andbuilders clean required

  • 8/16/2019 Building Defect Reports Sample 1

    126/220

    Item Defect Details Photographic Details

    379. Location: L8 Electrical room

    Finding: Building materials stored and generally dirty

    Recommendations: Dispose of building materials appropriately andbuilders clean required

    380. Location: L8 Electrical room

    Finding: 1 x unsealed penetration

    Recommendations: Correctly seal penetrations in concrete slab inline with building code for fire preventionthrough floors

    381. Location: L8 Electrical room

    Finding: Steel stud fixed to door frame and missingcaulking to edge of door frame to wall

    Recommendations: Remove steel stud, and caulk along edge ofdoor frame

  • 8/16/2019 Building Defect Reports Sample 1

    127/220

    Item Defect Details Photographic Details

    382. Location: L8 Electrical room

    Finding: Uneven floor level

    Recommendations: Fill and make level with rest of electrical roomfloor

    383. Location: L8 Electrical room

    Finding: Carpet tiles falling too short at threshold

    Recommendations: Install new carpet tiles at the correct size toensure no gaps at threshold

    384. Location: L8 Electrical room

    Finding: Paint on door frame

    Recommendations:

    Builders clean required

  • 8/16/2019 Building Defect Reports Sample 1

    128/220

  • 8/16/2019 Building Defect Reports Sample 1

    129/220

    Item Defect Details Photographic Details

    388. Location: L8 water meter cupboard

    Finding: Building materials on floor

    Recommendations: Builders clean required

    389. Location: L8 water meter cupboard

    Finding: Unused cables hanging from gauges

    Recommendations: Remove unused cables

    390. Location: L8 water meter cupboard

    Finding: Unused cables hanging from gauges

    Recommendations:

    Remove unused cables

  • 8/16/2019 Building Defect Reports Sample 1

    130/220

    Item Defect Details Photographic Details

    391. Location: L8 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

    392. Location: L8 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

    393. Location: L8 water meter cupboard

    Finding: Overspray evident on floor

    Recommendations:

    Builders clean required

  • 8/16/2019 Building Defect Reports Sample 1

    131/220

    Item Defect Details Photographic Details

    394. Location: L8 services cupboard

    Finding: Generally dirty

    Recommendations: Builders clean required

    395. Location: L8 lobby

    Finding: Signage is bent

    Recommendations: Replace with new sign

    396. Location: L9 electrical room

    Finding: Concrete splatter on wall

    Recommendations:

    Builders clean required

  • 8/16/2019 Building Defect Reports Sample 1

    132/220

    Item Defect Details Photographic Details

    397. Location: L9 Electrical room

    Finding: 2 x unsealed penetrations

    Recommendations: Correctly seal penetrations in concrete slab inline with building code for fire preventionthrough floors

    398. Location: L9 Electrical room

    Finding: Steel stud fixed to door frame and missingcaulking to edge of door frame to wall

    Recommendations: Remove steel stud, and caulk along edge ofdoor frame

    399. Location: L9 Electrical room

    Finding: Concrete floor is dirty and contains high spotsin various locations

    Recommendations: Grind floor and remove concrete splatter

  • 8/16/2019 Building Defect Reports Sample 1

    133/220

    Item Defect Details Photographic Details

    400. Location: L9 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

    401. Location: L9 lobby

    Finding: Unsatisfactory paint finish to lobby corridorceiling

    Recommendations: Apply another coat of paint to lobby ceiling

    402. Location: L9 lobby

    Finding: Damaged plasterboard wall behind level 9signage

    Recommendations: Remove signage, make good plater wall and re‐ apply signage

  • 8/16/2019 Building Defect Reports Sample 1

    134/220

    Item Defect Details Photographic Details

    403. Location: L9 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

    404. Location: L9 water meter cupboard

    Finding: Hole in plasterboard wall

    Recommendations: Patch, sand and paint plasterboard wall andmake good

    405. Location: L9 water meter cupboard

    Finding: Cupboard generally dirty

    Recommendations:

    Builders clean required

  • 8/16/2019 Building Defect Reports Sample 1

    135/220

    Item Defect Details Photographic Details

    406. Location: L9 water meter cupboard

    Finding: Rough plaster finish above water meter signage

    Recommendations: Make good plaster board wall behind signage

    407. Location: L9 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

    408. Location: L9 water meter cupboard

    Finding: Sticky tape left behind on all hinges

    Recommendations:

    Remove sticky tape from all hinges

  • 8/16/2019 Building Defect Reports Sample 1

    136/220

  • 8/16/2019 Building Defect Reports Sample 1

    137/220

    Item Defect Details Photographic Details

    412. Location: L9 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

    413. Location: L9 water meter cupboard

    Finding: Unsatisfactory paint finish and generally dirty

    Recommendations: Re‐paint walls and builders clean required

    414. Location: L9 corridor

    Finding: Unsatisfactory paint finish around EWIS speaker

    Recommendations:

    Patch, sand and re‐paint around EWIS speakerand make good

  • 8/16/2019 Building Defect Reports Sample 1

    138/220

    Item Defect Details Photographic Details

    415. Location: L9 water meter cupboard

    Finding: Sticky tape left behind on all hinges

    Recommendations: Remove sticky tape from all hinges

    416. Location: L9 water meter cupboard

    Finding: Missing caulking between plasterboard anddoor frame

    Recommendations: Caulk between plasterboard and door frame

    417. Location: L9 water meter cupboard

    Finding: Sticky tape left behind on all hinges

    Recommendations: Remove sticky tape from all hinges

  • 8/16/2019 Building Defect Reports Sample 1

    139/220

    Item Defect Details Photographic Details

    418. Location: L10 Electrical room

    Finding: Uneven floor level

    Recommendations: Fill and make level with rest of electrical roomfloor

    419. Location: L10 Electrical room

    Finding: Building materials left in room

    Recommendations: Dispose of building materials appropriately andarea requires builders clean

    420. Location: L10 Electrical room

    Finding: 1 x unsealed penetrations

    Recommendations:

    Correctly seal penetrations in concrete slab inline with building code for fire preventionthrough floors

  • 8/16/2019 Building Defect Reports Sample 1

    140/220

    Item Defect Details Photographic Details

    421. Location: L10 Electrical room

    Finding: Room generally dirty

    Recommendations: Builders clean required

    422. Location: L10 Electrical room

    Finding: Steel stud fixed to door frame and missingcaulking to edge of door frame to wall

    Recommendations: Remove steel stud, and caulk along edge ofdoor frame

    423. Location: L10 Electrical room

    Finding: 2 x unsealed penetrations

    Recommendations:

    Correctly seal penetrations in concrete slab inline with building code for fire preventionthrough floors

  • 8/16/2019 Building Defect Reports Sample 1

    141/220

    Item Defect Details Photographic Details

    424. Location: L10 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

    425. Location: L10 refuse room

    Finding: Unsatisfactory paint finish to wall

    Recommendations: Patch, sand and re‐paint wall and make good

    426. Location: L10 corridor near passenger lifts

    Finding: Incomplete paint finish to skirtings

    Recommendations:

    Finish painting skirting

  • 8/16/2019 Building Defect Reports Sample 1

    142/220

    Item Defect Details Photographic Details

    427. Location: L10 corridor

    Finding: Paint patches to ceiling

    Recommendations: Apply another coat of paint to lobby ceiling

    428. Location: L10 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

    429. Location: L10 water meter cupboard

    Finding: Sticky tape left behind on all hinges

    Recommendations:

    Remove sticky tape from all hinges

  • 8/16/2019 Building Defect Reports Sample 1

    143/220

    Item Defect Details Photographic Details

    430. Location: L10 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

    431. Location: L10 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

    432. Location: L10 water meter cupboard

    Finding: 2 x screws missing from hinge

    Recommendations:

    Install 2 x new screws into hinge

  • 8/16/2019 Building Defect Reports Sample 1

    144/220

    Item Defect Details Photographic Details

    433. Location: L10 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

    434. Location: L10 water meter cupboard

    Finding: Unsatisfactory sealing of penetration

    Recommendations: Remove material inside penetration and re‐seal with an appropriate sealant to prevent firethrough concrete slab

    435. Location: L10 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

  • 8/16/2019 Building Defect Reports Sample 1

    145/220

    Item Defect Details Photographic Details

    436. Location: L10 services cupboard

    Finding: Building materials stored inside cupboard

    Recommendations: Builders clean required

    437. Location: L10 services cupboard

    Finding: Tape on hinges

    Recommendations: Remove tape from hinges

    438. Location: L11 electrical room

    Finding: Door hardware left on ground

    Recommendations:

    Install door hardware or remove. Builders cleanrequired

  • 8/16/2019 Building Defect Reports Sample 1

    146/220

    Item Defect Details Photographic Details

    439. Location: L11 electrical room

    Finding: Area generally dirty

    Recommendations: Builders clean required

    440. Location: L11 electrical room

    Finding: Unsatisfactory wall finish

    Recommendations: Patch, fill and paint wall and make good incorner

    441. Location: L11 Electrical room

    Finding: Unsealed penetrations visible

    Recommendations:

    Correctly seal penetrations in concrete slab inline with building code for fire preventionthrough floors

  • 8/16/2019 Building Defect Reports Sample 1

    147/220

    Item Defect Details Photographic Details

    442. Location: L11 Electrical room

    Finding: Steel stud fixed to door frame and missingcaulking to edge of door frame to wall

    Recommendations: Remove steel stud, and caulk along edge ofdoor frame

    443. Location: L11 Electrical room

    Finding: Painting incomplete

    Recommendations: Finish off painting to wall

    444. Location: L11 Electrical room

    Finding: No trim on carpet tile threshold

    Recommendations:

    Install trim to edge of carpet tiles into electricalroom

  • 8/16/2019 Building Defect Reports Sample 1

    148/220

    Item Defect Details Photographic Details

    445. Location: L11 Electrical room

    Finding: Unable to close door as striker plate is blocked

    Recommendations: Un block/remove debris from striker plate

    446. Location: L11 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

    447. Location: L11 water meter cupboard

    Finding: Unsatisfactory sealing of penetration

    Recommendations:

    Remove material inside penetration and re‐seal with an appropriate sealant to prevent firethrough concrete slab

  • 8/16/2019 Building Defect Reports Sample 1

    149/220

    Item Defect Details Photographic Details

    448. Location: L11 water meter cupboard

    Finding: 2 x screws missing from hinge

    Recommendations: Install 2 x new screws into hinge

    449. Location: L11 water meter cupboard

    Finding: Unsatisfactory sealing of penetration

    Recommendations: Remove material inside penetration and re‐seal with an appropriate sealant to prevent firethrough concrete slab

    450. Location: L11 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

  • 8/16/2019 Building Defect Reports Sample 1

    150/220

    Item Defect Details Photographic Details

    451. Location: L11 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

    452. Location: L11 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

    453. Location: L11 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

  • 8/16/2019 Building Defect Reports Sample 1

    151/220

    Item Defect Details Photographic Details

    454. Location: L11 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty. Unsatisfactory penetrationsealant

    Recommendations: Remove unused cables and builders cleanrequired. Remove material inside penetrationand re‐seal with an appropriate sealant toprevent fire through concrete slab

    455. Location: L11 corridor

    Finding: Gas shut off valve grille is not sitting correctly

    Recommendations: Re‐fix grille into place

    456. Location: L11 water meter cupboard

    Finding: Unsatisfactory sealing of penetration

    Recommendations:

    Remove material inside penetration and re‐seal with an appropriate sealant to prevent firethrough concrete slab

  • 8/16/2019 Building Defect Reports Sample 1

    152/220

    Item Defect Details Photographic Details

    457. Location: L11 services cupboard

    Finding: Caulking missing to edges of door frames

    Recommendations: Caulk edges of door frames

    458. Location: L11 services cupboard

    Finding: Unsatisfactory paint finish to services cupboarddoor frames

    Recommendations: Re‐paint door frames to services cupboard

    459. Location: L11 corridor

    Finding: Paint on sign

    Recommendations:

    Builders clean required

  • 8/16/2019 Building Defect Reports Sample 1

    153/220

    Item Defect Details Photographic Details

    460. Location: L12 electrical room

    Finding: Builders materials stored on ground

    Recommendations: Dispose of hard waste appropriately

    461. Location: L12 electrical room

    Finding: Unsatisfactory wall finish

    Recommendations: Patch, fill and paint wall and make good

    462. Location: L12 electrical room

    Finding: Concrete splatter to wall

    Recommendations:

    Builders clean required

  • 8/16/2019 Building Defect Reports Sample 1

    154/220

    Item Defect Details Photographic Details

    463. Location: L12 electrical room

    Finding: 3 x conduits protruding through concrete floorslab

    Recommendations: Cut back conduit and apply an appropriatesealant in void

    464. Location: L12 electrical room

    Finding: NBN wiring not secure

    Recommendations: Securely fix conduit containing NBN

    465. Location: L12 Electrical room

    Finding: Steel stud fixed to door frame and missingcaulking to edge of door frame to wall

    Recommendations: Remove steel stud, and caulk along edge ofdoor frame

  • 8/16/2019 Building Defect Reports Sample 1

    155/220

    Item Defect Details Photographic Details

    466. Location: L12 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

    467. Location: L12 refuse

    Finding: Damaged plasterboard wall behind sign

    Recommendations: Patch and paint and make good plasterboardwall

    468. Location: L12 refuse

    Finding: Electrical conduit protruding from concrete slab

    Recommendations:

    Terminate electrical conduit and fill hole asrequired

  • 8/16/2019 Building Defect Reports Sample 1

    156/220

    Item Defect Details Photographic Details

    469. Location: L12 refuse

    Finding: Unused brackets still on slab soffit

    Recommendations: Remove unused bracket and fill hole

    470. Location: L12 refuse

    Finding: Concrete splatter on wall

    Recommendations: Builders clean required

    471. Location: L12 refuse

    Finding: Unsatisfactory plasterboard finish aboveskirting

    Recommendations: Patch, sand and paint wall above skirting andmake good

  • 8/16/2019 Building Defect Reports Sample 1

    157/220

    Item Defect Details Photographic Details

    472. Location: L12 water meter cupboard

    Finding: Red paint found on wall

    Recommendations: Re‐paint back wall

    473. Location: L11 water meter cupboard

    Finding: Unsatisfactory sealing of penetration

    Recommendations: Remove material inside penetration and re‐seal with an appropriate sealant to prevent firethrough concrete slab

    474. Location: L12 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

  • 8/16/2019 Building Defect Reports Sample 1

    158/220

    Item Defect Details Photographic Details

    475. Location: L12 water meter cupboard

    Finding: Redundant PVC pipework

    Recommendations: Investigate redundant PVC pipework andremove

    476. Location: L12 water meter cupboard

    Finding: Two screws missing from door hinge

    Recommendations: Install 2 new screws into hinge

    477. Location: L12 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

  • 8/16/2019 Building Defect Reports Sample 1

    159/220

    Item Defect Details Photographic Details

    478. Location: L12 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

    479. Location: L12 water meter cupboard

    Finding: Redundant PVC pipework, incompletepaintwork

    Recommendations: Investigate redundant PVC pipework andremove. Finish painting wall

    480. Location: L12 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

  • 8/16/2019 Building Defect Reports Sample 1

    160/220

    Item Defect Details Photographic Details

    481. Location: L12 water meter cupboard

    Finding: Unused cables hanging from gauges andgenerally dirty

    Recommendations: Remove unused cables and builders cleanrequired

    482. Location: L12 water meter cupboard

    Finding: Unsatisfactory sealing of penetration

    Recommendations: Remove material inside penetration and re‐seal with an appropriate sealant to prevent firethrough concrete slab

    483. Location: L12 services cupboard

    Finding: Caulking missing to edges of door frames

    Recommendations:

    Caulk edges of door frames

  • 8/16/2019 Building Defect Reports Sample 1

    161/220

    Item Defect Details Photographic Details

    484. Location: L13 lobby

    Finding: Redundant bracket

    Recommendations: Remove unused bracket

    485. Location: L13 lobby

    Finding: Emergency evacuation plan is incorrect

    Recommendations: Re‐print emergency evacuation plan to showcorrect orientation

    486. Location: L13 lobby

    Finding: No seal under plant room door

    Recommendations:

    Install weather seal to underside of plant roomdoor

  • 8/16/2019 Building Defect Reports Sample 1

    162/220

    Item Defect Details Photographic Details

    487. Location: L13 lobby

    Finding: Unused bracket on door frame at floor level

    Recommendations: Remove unused bracket

    488. Location: L13 roof

    Finding: Unsatisfactory discharge of pipe from roofplumbing

    Recommendations: Extend pipework to discharge away fromdoorway

    489. Location: L13 roof

    Finding: Missing hold down bolts to hot water unitstructure

    Recommendations: Install bolts in holes provided

  • 8/16/2019 Building Defect Reports Sample 1

    163/220

    Item Defect Details Photographic Details

    490. Location: L13 roof

    Finding: Threads have not been cut off to be flush withnut

    Recommendations: Trim down all threads

    491. Location: L13 roof

    Finding: Threads have not been cut off to be flush withnut

    Recommendations: Trim down all threads

    492. Location: L13 roof

    Finding: Threads have not been cut off to be flush withnut

    Recommendations: Trim down all threads

  • 8/16/2019 Building Defect Reports Sample 1

    164/220

    Item Defect Details Photographic Details

    493. Location: L13 roof

    Finding: Threads have not been cut off to be flush withnut

    Recommendations: Trim down all threads

    494. Location: L13 roof

    Finding: Threads have not been cut off to be flush withnut

    Recommendations: Trim down all threads

    495. Location: L13 roof

    Finding: Threads have not been cut off to be flush withnut

    Recommendations: Trim down all threads

  • 8/16/2019 Building Defect Reports Sample 1

    165/220

    Item Defect Details Photographic Details

    496. Location: L13 roof

    Finding: Building materials stored on roof

    Recommendations: Remove all builders materials and clean area

    497. Location: East side external canopy

    Finding: Gutters blocked

    Recommendations: Remove all foliage and debris from gutters

    498. Location: East side external canopy

    Finding: Gutters blocked

    Recommendations:

    Remove all foliage and debris from gutters

  • 8/16/2019 Building Defect Reports Sample 1

    166/220

    Item Defect Details Photographic Details

    499. Location: East side external canopy

    Finding: Gutters blocked

    Recommendations: Remove all foliage and debris from gutters

    500. Location: L13 roof

    Finding: Pathway along east elevation is generally dirty

    Recommendations: Builders clean required

    501. Location: L13 roof

    Finding: Water pooling on roof

    Recommendations:

    Re‐level area to correct falls

  • 8/16/2019 Building Defect Reports Sample 1

    167/220

    Item Defect Details Photographic Details

    502. Location: L13 roof

    Finding: Balustrade missing

    Recommendations: Investigate if balustrade is required in this area

    503. Location: L13 roof

    Finding: Window seals are dirty and deteriorating

    Recommendations: Replace window seals

    504. Location: L13 roof

    Finding: Window seals are dirty and deteriorating

    Recommendations:

    Replace window seals

  • 8/16/2019 Building Defect Reports Sample 1

    168/220

  • 8/16/2019 Building Defect Reports Sample 1

    169/220

    Item Defect Details Photographic Details

    508. Location: L13 roof

    Finding: High spots on ground surrounding floor waste

    Recommendations: Re‐align falls so that water can flow easily intofloor waste

    509. Location: L13 roof

    Finding: Water pooling in corner

    Recommendations: Re‐align falls so that water can flow easily intofloor waste

    510. Location: L13 roof

    Finding: Markings on external cladding

    Recommendations:

    Builders clean required

  • 8/16/2019 Building Defect Reports Sample 1

    170/220

    Item Defect Details Photographic Details

    511. Location: L13 roof

    Finding: Aluminium capping is coming away fromstructure

    Recommendations: Re‐fix aluminium so as to not allow wateringress

    512. Location: East side external canopy

    Finding: Zoomed out photo of location of blockedgutters

    Recommendations: Remove all foliage and debris from gutters

    513. Location: East side external canopy

    Finding: Zoomed out photo of location of blockedgutters

    Recommendations: Remove all foliage and debris from gutters

  • 8/16/2019 Building Defect Reports Sample 1

    171/220

    Item Defect Details Photographic Details

    514. Location: L13 roof

    Finding: Water pooling in corner

    Recommendations: Re‐align falls so that water can flow easily intofloor waste

    515. Location: L13 roof

    Finding: Water pooling in corner and capping missing

    Recommendations: Re‐align falls so that water can flow easily intofloor waste

    516. Location: L13 roof, top floor external windows

    Finding: Large gaps between window sections

    Recommendations:

    Investigate if within tolerance

  • 8/16/2019 Building Defect Reports Sample 1

    172/220

    Item Defect Details Photographic Details

    517. Location: L13 roof

    Finding: Capping piece of parapet to roof level

    Recommendations: Caulk to underside of capping

    518. Location: L13 roof, top floor external windows

    Finding: Large gaps between window sections

    Recommendations: Investigate if within tolerance

    519. Location: L13 roof, top floor external windows

    Finding: Large gaps between window sections

    Recommendations:

    Investigate if within tolerance

  • 8/16/2019 Building Defect Reports Sample 1

    173/220

    Item Defect Details Photographic Details

    520. Location: South east side external canopy

    Finding: Zoomed out photo of location of blockedgutters

    Recommendations: Remove all foliage and debris from gutters

    521. Location: L13 roof

    Finding: No waterproofing membrane present

    Recommendations: Investigate construction drawings to determineif this is required

    522. Location: L13 roof

    Finding: No waterproofing membrane present

    Recommendations:

    Investigate construction drawings to determineif this is required

  • 8/16/2019 Building Defect Reports Sample 1

    174/220

    Item Defect Details Photographic Details

    523. Location: L13 roof

    Finding: Edges of zincalume decking roof are not sealed

    Recommendations: Seal edges /caulk from concrete to roofstructure

    524. Location: L13 roof

    Finding: End capping of roof coming away fromzincalume

    Recommendations: Re‐fix capping piece so as to avoid wateringress through exposed edges

    525. Location: L13 roof

    Finding: Long threads protruding from cladding supportstructure

    Recommendations: Trim down all threads appropriately

  • 8/16/2019 Building Defect Reports Sample 1

    175/220

    Item Defect Details Photographic Details

    526. Location: L13 roof

    Finding: No waterproofing membrane present

    Recommendations: Investigate construction drawings to determineif this is required

    527. Location: L13 roof

    Finding: No waterproofing membrane present

    Recommendations: Investigate construction drawings to determineif this is required

    528. Location: Fire stairs

    Finding: Light not working

    Recommendations:

    Replace globe

  • 8/16/2019 Building Defect Reports Sample 1

    176/220

    Item Defect Details Photographic Details

    529. Location: L8 fire stairs

    Finding: Sign is not sitting flush

    Recommendations: Re‐stick signage to ensure it is flush with wall

    530. Location: Street level external paving

    Finding: Caulking missing to window frames

    Recommendations: Install caulking as required

    531. Location: Street level external paving

    Finding: Areas of paving uneven and dropping in someareas

    Recommendations: Ensure all paving is at the same level

  • 8/16/2019 Building Defect Reports Sample 1

    177/220

    Item Defect Details Photographic Details

    532. Location: Street level external paving

    Finding: Areas of paving uneven and dropping in someareas

    Recommendations: Ensure all paving is at the same level

    533. Location: Street level external paving

    Finding: Cracked pavers

    Recommendations: Replace as required

    534. Location: Street level external paving

    Finding: Areas of paving uneven and dropping in someareas

    Recommendations: Ensure all paving is at the same level

  • 8/16/2019 Building Defect Reports Sample 1

    178/220

    Item Defect Details Photographic Details

    535. Location: Street level east side

    Finding: Bent metal screen

    Recommendations: Replace as required

    536. Location: Street level external paving

    Finding: Cracked pavers

    Recommendations: Replace as required

    537. Location: Street level

    Finding: Generally dirty in service cupboards

    Recommendations:

    Builders clean required

  • 8/16/2019 Building Defect Reports Sample 1

    179/220

    Item Defect Details Photographic Details

    538. Location: Street level – north side

    Finding: Generally dirty in service cupboards, concretesplatter evident on door frames

    Recommendations: Builders clean required

    539. Location: Street level – north side

    Finding: 2 x unsealed penetrations

    Recommendations: Apply appropriate sealant at penetrationlocations

    540. Location: Street level

    Finding: Generally dirty in service cupboards

    Recommendations:

    Builders clean required

  • 8/16/2019 Building Defect Reports Sample 1

    180/220

    Item Defect Details Photographic Details

    541. Location: Street level – north side service cupboards

    Finding: Unfinished painting

    Recommendations: Finish off painting to bare material

    542. Location: North side windows

    Finding: Still dirty and paint splatter evident

    Recommendations: Builders clean required

    543. Location: North side windows

    Finding: Still dirty and paint splatter evident

    Recommendations:

    Builders clean required

  • 8/16/2019 Building Defect Reports Sample 1

    181/220

    Item Defect Details Photographic Details

    544. Location: West elevation

    Finding: Timber screens not fixed securely

    Recommendations: Investigate fixing details and rectify accordingly

    545. Location: West side stairs at street level

    Finding: Missing stair nosing

    Recommendations: Install new stair nosing

    546. Location: Underside of walkway at ground floor betweenbuilding

    Finding: Rough finish to cladding

    Recommendations: Re‐paint and make good cladding to undersideof walkway roof

  • 8/16/2019 Building Defect Reports Sample 1

    182/220

    Item Defect Details Photographic Details

    547. Location: Street level

    Finding: Missing caulking between pavers and windowframes

    Recommendations: Install appropriate caulking between paversand window frame

    548. Location: Street level

    Finding: Missing caulking between pavers and windowframes

    Recommendations: Install appropriate caulking between paversand window frame

    549. Location: Street level

    Finding: Missing caulking between pavers and windowframes

    Recommendations: Install appropriate caulking between paversand window frame

  • 8/16/2019 Building Defect Reports Sample 1

    183/220

    Item Defect Details Photographic Details

    550. Location: South side of building

    Finding: Un painted concrete

    Recommendations: Apply appropriate paint finish to bare concrete

    551. Location: Street level – West side near train station

    Finding: Large gaps visible between 2 adjoining buildingmaterials

    Recommendations: Install appropriate caulking to gaps

  • 8/16/2019 Building Defect Reports Sample 1

    184/220

    Part 2: Thermal Leak Detection

  • 8/16/2019 Building Defect Reports Sample 1

    185/220

    1/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]

    Ar1 Max 18.0

    Min 16.7

    Average 17.6

    Emissivity 0.86 Refl. temp. 20 °C

    Measurements °C 13/10/2014 9:54:10 PM °C 18.9

    Parameters Ar1

    14.9 FLIR0458.jpg FLIR E6 63931855

    13/10/2014 9:54:10 PM

    FLIR0458.jpg FLIR E6 63931855

    mailto:[email protected]:[email protected]:[email protected]

  • 8/16/2019 Building Defect Reports Sample 1

    186/220

    Measurements °C 13/10/2014 11:18:40 PM °C

    32/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]

    Ar1 Max 16.4

    Min 14.5

    Average 15.6

    Emissivity 0.86 Refl. temp. 20 °C

    17.3

    Parameters Ar1

    13.2 FLIR0514.jpg FLIR E6 63931855

    13/10/2014 11:18:40 PM

    FLIR0514.jpg FLIR E6 63931855

    mailto:[email protected]:[email protected]:[email protected]

  • 8/16/2019 Building Defect Reports Sample 1

    187/220

    Measurements °C 13/10/2014 11:19:35 PM °C

    33/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]

    Ar1 Max 16.1

    Min 13.4

    Average 15.0

    Emissivity 0.86 Refl. temp. 20 °C

    16.6

    Parameters Ar1

    12.5 FLIR0516.jpg FLIR E6 63931855

    13/10/2014 11:19:35 PM

    FLIR0516.jpg FLIR E6 63931855

    mailto:[email protected]:[email protected]:[email protected]

  • 8/16/2019 Building Defect Reports Sample 1

    188/220

    Measurements °C 13/10/2014 11:19:45 PM °C

    35/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]

    Ar1 Max 16.7

    Min 14.9

    Average 16.0

    Emissivity 0.86 Refl. temp. 20 °C

    16.6

    Parameters Ar1

    12.5 FLIR0518.jpg FLIR E6 63931855

    13/10/2014 11:19:48 PM

    FLIR0518.jpg FLIR E6 63931855

    mailto:[email protected]:[email protected]:[email protected]

  • 8/16/2019 Building Defect Reports Sample 1

    189/220

    Measurements °C 13/10/2014 11:20:07 PM °C

    36/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]

    Ar1 Max 16.9

    Min 15.4

    Average 16.4

    Emissivity 0.86 Refl. temp. 20 °C

    17.4

    Parameters Ar1

    13.3 FLIR0520.jpg FLIR E6 63931855

    13/10/2014 11:20:07 PM

    FLIR0520.jpg FLIR E6 63931855

    mailto:[email protected]:[email protected]:[email protected]

  • 8/16/2019 Building Defect Reports Sample 1

    190/220

    Measurements °C 13/10/2014 11:20:15 PM °C

    37/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]

    Ar1 Max 17.2

    Min 14.7

    Average 16.3

    Emissivity 0.86 Refl. temp. 20 °C

    17.5

    Parameters Ar1

    13.4 FLIR0522.jpg FLIR E6 63931855

    13/10/2014 11:20:15 PM

    FLIR0522.jpg FLIR E6 63931855

    mailto:[email protected]:[email protected]:[email protected]

  • 8/16/2019 Building Defect Reports Sample 1

    191/220

    Measurements °C 13/10/2014 11:20:32 PM °C

    38/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]

    Ar1 Max 16.4

    Min 14.0

    Average 15.6

    Emissivity 0.86 Refl. temp. 20 °C

    16.6

    Parameters Ar1

    12.5 FLIR0524.jpg FLIR E6 63931855

    13/10/2014 11:20:32 PM

    FLIR0524.jpg FLIR E6 63931855

    mailto:[email protected]:[email protected]:[email protected]

  • 8/16/2019 Building Defect Reports Sample 1

    192/220

    Measurements °C 13/10/2014 11:21:15 PM °C

    39/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]

    Ar1 Max 16.8

    Min 14.8

    Average 16.2

    Emissivity 0.86 Refl. temp. 20 °C

    17.4

    Parameters Ar1

    13.4 FLIR0526.jpg FLIR E6 63931855

    13/10/2014 11:21:15 PM

    FLIR0526.jpg FLIR E6 63931855

    mailto:[email protected]:[email protected]:[email protected]

  • 8/16/2019 Building Defect Reports Sample 1

    193/220

    Measurements °C 13/10/2014 11:22:09 PM °C

    40/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]

    Ar1 Max 16.5

    Min 14.3

    Average 15.7

    Emissivity 0.86 Refl. temp. 20 °C

    16.8

    Parameters Ar1

    12.7 FLIR0528.jpg FLIR E6 63931855

    13/10/2014 11:22:09 PM

    FLIR0528.jpg FLIR E6 63931855

    mailto:[email protected]:[email protected]:[email protected]

  • 8/16/2019 Building Defect Reports Sample 1

    194/220

    Measurements °C 14/10/2014 12:30:45 AM °C

    41/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]

    Ar1 Max 22.5

    Min 19.8

    Average 20.7

    Emissivity 0.86 Refl. temp. 20 °C

    22.3

    Parameters Ar1

    18.2 FLIR0530.jpg FLIR E6 63931855

    14/10/2014 12:30:45 AM

    FLIR0530.jpg FLIR E6 63931855

    mailto:[email protected]:[email protected]:[email protected]

  • 8/16/2019 Building Defect Reports Sample 1

    195/220

    Measurements °C 14/10/2014 12:36:24 AM °C

    42/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]

    Ar1 Max 18.7

    Min 16.9

    Average 17.9

    Emissivity 0.86 Refl. temp. 20 °C

    19.3

    Parameters Ar1

    15.2 FLIR0532.jpg FLIR E6 63931855

    14/10/2014 12:36:24 AM

    FLIR0532.jpg FLIR E6 63931855

    mailto:[email protected]:[email protected]:[email protected]

  • 8/16/2019 Building Defect Reports Sample 1

    196/220

    Measurements °C 14/10/2014 12:36:55 AM °C

    43/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]

    Ar1 Max 18.5

    Min 17.9

    Average 18.2

    Emissivity 0.86 Refl. temp. 20 °C

    18.4

    Parameters Ar1

    14.4 FLIR0534.jpg FLIR E6 63931855

    14/10/2014 12:36:55 AM

    FLIR0534.jpg FLIR E6 63931855

    mailto:[email protected]:[email protected]:[email protected]

  • 8/16/2019 Building Defect Reports Sample 1

    197/220

    Measurements °C 14/10/2014 12:38:10 AM °C

    45/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]

    Ar1 Max 17.4

    Min 14.6

    Average 16.4

    Emissivity 0.86 Refl. temp. 20 °C

    17.7

    Parameters Ar1

    13.7 FLIR0538.jpg FLIR E6 63931855

    14/10/2014 12:38:10 AM

    FLIR0538.jpg FLIR E6 63931855

    mailto:[email protected]:[email protected]:[email protected]

  • 8/16/2019 Building Defect Reports Sample 1

    198/220

    Measurements °C 14/10/2014 12:38:51 AM °C

    46/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]

    Ar1 Max 18.1

    Min 15.0

    Average 17.2

    Emissivity 0.86 Refl. temp. 20 °C

    22.5

    Parameters Ar1

    14.1 FLIR0540.jpg FLIR E6 63931855

    14/10/2014 12:38:51 AM

    FLIR0540.jpg FLIR E6 63931855

    mailto:[email protected]:[email protected]:[email protected]

  • 8/16/2019 Building Defect Reports Sample 1

    199/220

    Measurements °C 14/10/2014 12:39:08 AM °C

    47/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]

    Ar1 Max 18.0

    Min 16.9

    Average 17.5

    Emissivity 0.86 Refl. temp. 20 °C

    17.7

    Parameters Ar1

    13.7 FLIR0542.jpg FLIR E6 63931855

    14/10/2014 12:39:08 AM

    FLIR0542.jpg FLIR E6 63931855

    mailto:[email protected]:[email protected]:[email protected]

  • 8/16/2019 Building Defect Reports Sample 1

    200/220

    Measurements °C 14/10/2014 12:39:28 AM °C

    48/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]

    Ar1 Max 17.2

    Min 14.0

    Average 15.8

    Emissivity 0.86 Refl. temp. 20 °C

    16.9

    Parameters Ar1

    12.8 FLIR0544.jpg FLIR E6 63931855

    14/10/2014 12:39:28 AM

    FLIR0544.jpg FLIR E6 63931855

    mailto:[email protected]:[email protected]:[email protected]

  • 8/16/2019 Building Defect Reports Sample 1

    201/220

    Measurements °C 14/10/2014 12:39:47 AM °C

    49/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]

    Ar1 Max 17.4

    Min 14.9

    Average 16.1

    Emissivity 0.86 Refl. temp. 20 °C

    17.7

    Parameters Ar1

    13.7 FLIR0546.jpg FLIR E6 63931855

    14/10/2014 12:39:47 AM

    FLIR0546.jpg FLIR E6 63931855

    mailto:[email protected]:[email protected]:[email protected]

  • 8/16/2019 Building Defect Reports Sample 1

    202/220

    Measurements °C 14/10/2014 12:39:57 AM °C

    50/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]

    Ar1 Max 18.5

    Min 15.1

    Average 17.4

    Emissivity 0.86 Refl. temp. 20 °C

    18.3

    Parameters Ar1

    13.9 FLIR0548.jpg FLIR E6 63931855

    14/10/2014 12:39:57 AM

    FLIR0548.jpg FLIR E6 63931855

    mailto:[email protected]:[email protected]:[email protected]

  • 8/16/2019 Building Defect Reports Sample 1

    203/220

    Measurements °C 14/10/2014 12:41:30 AM °C

    51/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]

    Ar1 Max 18.3

    Min 17.5

    Average 17.9

    Emissivity 0.86 Refl. temp. 20 °C

    19.9

    Parameters Ar1

    15.8 FLIR0550.jpg FLIR E6 63931855

    14/10/2014 12:41:30 AM

    FLIR0550.jpg FLIR E6 63931855

    mailto:[email protected]:[email protected]:[email protected]

  • 8/16/2019 Building Defect Reports Sample 1

    204/220

    Measurements °C 14/10/2014 12:43:02 AM °C

    53/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]

    Ar1 Max 15.9

    Min 14.4

    Average 15.3

    Emissivity 0.86 Refl. temp. 20 °C

    17.1

    Parameters Ar1

    12.1 FLIR0552.jpg FLIR E6 63931855

    14/10/2014 12:43:02 AM

    FLIR0552.jpg FLIR E6 63931855

    mailto:[email protected]:[email protected]:[email protected]

  • 8/16/2019 Building Defect Reports Sample 1

    205/220

  • 8/16/2019 Building Defect Reports Sample 1

    206/220

    Measurements °C 14/10/2014 12:46:54 AM °C

    55/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]

    Ar1 Max 18.5

    Min 16.7

    Average 17.8

    Emissivity 0.86 Refl. temp. 20 °C

    19.4

    Parameters Ar1

    15.4 FLIR0556.jpg FLIR E6 63931855

    14/10/2014 12:47:53 AM

    FLIR0556.jpg FLIR E6 63931855

    mailto:[email protected]:[email protected]:[email protected]

  • 8/16/2019 Building Defect Reports Sample 1

    207/220

    Measurements °C 14/10/2014 12:48:21 AM °C

    56/67 Roscon Property Services Pty. Ltd. ACN 108 876 697 ABN 66 433 979 405 Australia House 150 Sydney Road Coburg (Vic) 3058 I Level 50, 120 Collins Street Melbourne (Vic) 3000 24/7: 1800 767 266 T: (03) 9385 0040 F: (03) 9386 8199 E: [email protected]

    Ar1 Max 19.0

    Min 16.7

    Average 18.1

    Emissivity 0.86 Refl. temp. 20 °C

    19.0

    Parameters Ar1

    14.8 FLIR0558.jpg FLIR E6 63931855

    14/10/2014 12:48:21 AM

    FLIR0558.jpg FLIR E6 63931855

    mailto:[email protected]:[email protected]:[email protected]

  • 8/16/2019 Building Defect Reports Sample 1

    208/220

    Part 3: Videos Videos

  • 8/16/2019 Building Defect Reports Sample 1

    209/220

    Part 4 : Marked up Plan of Defect Locations

  • 8/16/2019 Building Defect Reports Sample 1

    210/220

    5 6

    3 2 1

    4

    8

    9

    10

    11

    12 7

    13

    14

    15

    16

    25

    24

    23

    26

    22

    21 17

    19

    18

    20

  • 8/16/2019 Building Defect Reports Sample 1

    211/220

    67 60 61

    66 56

    38

    68 59

    57 37

    55 62

    63

    64

    65

    69

    53 70

    54 71

    51 72

    52 47

    58 50

    46

    45 49

    44

    36

    43 35

    42 34 48

    33 41

    32

    31

    40

    39

    30 29

    28 27

  • 8/16/2019 Building Defect Reports Sample 1

    212/220

    n

    m

    190-210 Switchboard room

    149 & 150

    162

    140

    141

    134 & 135 136

    137

    138

    139

    161

    151

    152

    132

    133

    127

    128 131

    124 73 144

    123

    122

    124

    125

    126

    129

    142

    145

    146

    147 & 148 153

    163 & 164

    117

    130

    116 74

    115

    114

    154

    155

    156

    165

    166, 167, 168 & 169

    172

    170 143

    173

    171

    174

    175

    176

    182, 183

    & 184

    110

    109

    108

    118

    106

    105

    104

    113

    112

    111

    103

    102

    75

    157

    158

    159

    160

    180

    179

    177

    97

    96

    178

    107

    95

    181

    94

    119, 120 & 121

    76

    77

    78

    79

    188

    91

    89

    88

    185 & 186

    187 93

    92

    189

    80

    81

    101

    100 99

    98

    82

    87 86 83 84

    90 85

  • 8/16/2019 Building Defect Reports Sample 1

    213/220

    244 243

    211 212

    245

    241 242

    239 240 249

    238

    248

    246

    236 213

    237

    252 - 258 Lobby 235

    232 214 247

    215

    234

    230 233

    229

    228

    227

    223 216, 217, 218 & 219

    225 226

    224 231

    221 222 220

    BASEMENT 02UPPER

  • 8/16/2019 Building Defect Reports Sample 1

    214/220

    278 277

    267

    268

    265

    266

    264

    274 259 & 260

    269 262

    276 270 261 263

    272 & 273

    275

    271

  • 8/16/2019 Building Defect Reports Sample 1

    215/220

    280

    281 282

    279

  • 8/16/2019 Building Defect Reports Sample 1

    216/220

    Part 5: Terms and Conditions The following information is very important and forms an integral part of this report.

    Before you decide to purchase this property you should read and understand the following important information. Itwill help explain what is involved in a Standard Property Inspection, the difficulties faced by an inspector and why it isnot possible to guarantee that a property is free of defects, latent or otherwise. This information forms an integral partof the report. The general adequacy of site drainage is not included in the Standard Property Inspection Report.Comments on surface water drainage are limited as where there has been either little or no rainfall for a period of time,surface water drainage may appear to be adequate but then during periods of heavy rain, may be found to beinadequate. Any comments made in this section are relevant only in light of the conditions present at the time ofinspection. It is recommended that a Smoke Test be obtained to determine any illegal connections, blocked or brokendrains.

    1. This is a Visual Inspection only and in Accordance with AS4349.1

    This visual inspection is limited to those areas and sections of the property fully accessible and visible to the Inspector at thetime and on the date of Inspection. The inspection DID NOT include breaking apart, dismantling, removing or movingobjects including, but not limited to, foliage, mouldings, roof insulation/sarking membrane , floor or wall coverings,sidings, ceilings, floors, furnishings, appliances or personal possessions. The Inspector CANNOT see inside walls,between floors, inside skillion roofing, inside the eaves, behind stored goods in cupboards, or other areas that areconcealed or obstructed. The inspector DID NOT dig, gouge, force or perform any invasive procedures. In an occupiedproperty it must be understood that furnishings or household items may conceal defects which may only be revealedwhen the items are removed. No detailed inspection is inferred to external areas over 3.6 metres above the naturalground level.

    2. Scope of Report The Standard Property Report is not intended as a certificate of compliance of the property within the requirements ofany Act, regulation, ordinance or by ‐law, or, as a warranty or an insurance policy against problems developing with thebuilding in the future.

    3. Limitations Nothing contained in the Report implies that any inaccessible or partly inaccessible area(s) or section(s) of the property beinginspected by the Inspector on the date of the inspection were free from defects latent or otherwise.

    No responsibility can be accepted for defects which are latent or otherwise not reasonably detected on a visual inspectionwithout interference with or removal of any of the structure including fixtures or fittings within the building.

    This Standard Property Report does not contain any assessment or opinion in relation to any item, which is the subject of aSpecial Purpose Property Report (as defined in AS4349.1), or any matter where the inspection or assessment of which is

    solely regulated by Statute. Special Purpose Property Reports include comment on the following: Common property areas,environmental concerns such as sunlight, privacy, streetscape and views. Proximity of property to flight paths, railways andbusy traffic or other neighbourhood issues. Noise levels, health and safety issues including the presence of asbestos or lead.Heritage concerns. Security or fire protection. Analysis of site drainage apart from surface water drainage. Swimming poolsand spas. Detection and identification of illegal and unauthorised building and plumbing work. Durability of exposedfinishes.

    4. Important Information Any person who relies upon the contents of this Report does so acknowledging that the above clauses, definitions anddisclaimers that follow define the Scope and Limitations of the inspection and form an integral part of the report.

  • 8/16/2019 Building Defect Reports Sample 1

    217/220

    5. Disclaimer of Liability No liability shall be accepted on account of failure of the Report to notify any problems in any area(s) or section(s) of thesubject property physically inaccessible for inspection, or to which access for Inspection is denied by or to the Inspector(including but not limited to any area(s) or section(s) so specified by the Report.

    6. Disclaimer of Liability to Third Parties This report is made solely for the use and benefit of the Client named on the front of this report. No liability orresponsibility whatsoever, in contract or tort, is accepted to any third party who may rely on the Report wholly or in part.Any third party acting or relying on this Report, in whole or in part does so at their own risk.

    7. Report Definition This report is limited to a visual inspection of areas where reasonable access is available at the time of inspection. Itdoes not purport to be geological as to foundation integrity or soil conditions, engineering as to structural, nor does it cover the

    condition of electrical, plumbing, gas or motorised appliances. It is strongly recommended that an appropriatelyqualified contractor check these services prior to purchase.

    As the date if this report we have identified the items as listed herein, we do not accept any responsibility for itemswhich may be damaged after the inspection has been completed.

    As a matter of course, and in the interests of safety, all prospective purchasers should have an electrical report carriedout by a suitably qualified contractor. This report is limited to (unless otherwise noted) the main structure on the siteand any other building, structure or outbuilding specifically named within the report.

    This Report attempts to assist in judging a building according to its age and level of maintenance and in providingrelative comparisons. This inspection and report is not to be considered all ‐encompassing dealing with a building fromevery aspect. Rather it should be seen as a reasonable attempt to identify any significant defects visible at the time ofthe inspection. It is unrealistic to expect comment on minor defects or imperfections in the Standard Property Report. Ifthis is required, a Special Purpose Property Report is recommended.

    Whilst buildings may have many pleasing features there are few without defects and many are due naturally to agedeterioration. Subject to the level of maintenance on the building it is common for the number of faults to haveincreased with age.

    All items that are considered to be concealed or latent defects are excluded.

    Shower Recesses: Tests may be made on shower recesses to detect leaks (if water is connected). The tests may notreveal leaks or show incorrect waterproofing if silicone liquid or masonry sealant has been applied prior to theinspection. Such application is a temporary waterproofing measure and may last for some months before breakingdown. The tests on shower recesses are limited to running water within the recesses and visually checking for leaks. As showersare only checked for a short period of time, prolonged use may reveal leaks that were not detected at the time of inspection.

    If there is no evidence of a current leak during inspection that does not necessarily mean that the shower does not leak. Glass Caution: Glazing in older houses (built before 1978) may not necessarily comply with current glass safety standardsAS1288. In the interests of safety, glass panes in doors and windows especially in trafficable areas should be replacedwith safety glass or have shatterproof film installed unless they already comply with the current standard.

    Stairs & Balustrades: Specifications have been laid down by the Australian Building Code ‐ Section 3.9 covering stairs,landings and balustrades to ensure the safety of all occupants and visitors in a building. Many balustrades and stairsbuilt before 1996 may not comply with the current standard. You must upgrade all such items to the current standardto improve safety.

    Swimming Pools: If a swimming pool is present it should be the subject of a Special Purpose Property Report. A detailedinspection on the status or serviceability of any swimming pool or associated pool equipment has not been carried outand is not within the scope of this report. Additionally, to adequately inspect a swimming pool, the water must be

    completely drained and all internal surfaces must be fully accessible. This report may contain notable observations, together with what is considered to be helpful information and advice.

  • 8/16/2019 Building Defect Reports Sample 1

    218/220

    This report does not identify timber ‐destroying pests. A timber pest inspection report should be obtained from a qualified timber pest inspector.

    If any cost of work estimates is given, these are merely opinions and should be taken as a general guide only. In the

    building industry, experience has shown that prices vary considerably and you must obtain independent quotations onany significant notable item from several contractors prior to purchase.

    The operation of fireplaces, chimneys, alarm systems, intercom systems, electrical and mechanical appliances, airconditioning systems, smoke detectors and residual current devices have not been tested and are the subject of aSpecial Purpose Property Report. Should you require an inspection to be carried out on any item not specificallycovered by this report, please request a Special Purpose Property Report on the specific item required.

    No report is made on the presence, operation, installation or cabling of any free to air or pay television system.

    8. Lighting Installations It should be noted that this inspection was done during daylight hours and therefore the adequacy of lighting indarkness could not be directly assessed.

    9. Electrical Installations We have carried out a thorough visual inspection of the common property and assets visible from the commonproperty areas. If there were any visible electrical installation issues they have been included in this section of the report.We have not carried out a thorough inspection of electrical installation and the main switchboard, as we are notqualified to do so, please ensure that a suitably qualified electrical contractor carries out a thorough visual inspection atleast every 2 years, this inspection can be incorporated with the testing of the Residual Current Device if CommunityCircuits are present.

    10. Plumbing, Gutters & Downpipes and Roofs We have carried out a thorough visual inspection of the common property and assets visible from the commonproperty areas. If there were any visible plumbing, gutters and downpipes or roof issues they have been included in thissection of the report. We have not carried out a thorough inspection of the plumbing, gutters and downpipes and roof, aswe are not qualified to do so, please ensure that a suitably qualified plumbing contractor (who is qualified to undertake roofinspections) carries out a thorough regular inspection. We will recommend a qualified plumber to inspect if an issue isfound.

    11. Lifts Please ensure that if lifts are in the building(s) that regular maintenance programs are in place. This report does notcover lifts.

    12. Painting Painting surfaces not exposed to the elements/corrosion should be included in the next painting cycle. Painting foraesthetic purposes is not included in this report.

    13. Air Conditioning Only a general external inspection of air conditioning units is carried out where installed, therefore please ensure that ifthe Owners Corporation has air conditioner(s) in the building(s) they have regular maintenance programs in place. Thisreport does not cover air conditioning units and air condition cooling towers.

    14. Glass This report only addresses glass requiring obvious replacement. It does not cover the Building Code,Australian Standard and safety requirements of glass installed in the common property.

  • 8/16/2019 Building Defect Reports Sample 1

    219/220

    15. Plant and Equipment Please ensure that if the Owners Corporation has plant and equipment in the building(s) that regular maintenanceprograms are in place for each piece of plant and equipment. This report does not cover plant and equipment.

    16. Balcony Balustrades Wherever balcony balustrades are installed, please be advised that a comprehensive inspection of balcony railings wasnot carried out as part of this report. Also this report is only a visual inspection of areas accessible from the commonproperty; therefore all balcony balustrades are not viewed. If there are any visible signs of corrosion on the balustradeincluding fixings and/or if the balustrades are over 10 years old a detailed inspection and testing of balustrades shouldbe undertaken.

    17. Pest Reports If there are any visible signs of termite damage it is included in this report. We have not carried out a pest inspection of

    the site; as we are not qualified to do so, please ensure that a suitably qualified pest inspection contractor carries outthorough regular inspections.

    18. Fire Fighting Equipment and Statutory Requirements It has been assumed that any building needing fire fighting equipment to meet legislative requirements such as theBuilding Code of Australia 1996 did meet those requirements at the time of construction. We have not examined thefire safety requirements for the building and make no comment as to the adequacy of the measures found in thecomplex. We have not and do not assess the condition of any fire fighting equipment within the complex. If the BodiesCorporate wishes to ascertain its position with respect to fire safety compliance it may carry out its own assessment.These guidelines should be placed on the Owners Corporation notice board. We have visually inspected the fire fightingequipment but have not carried out any testing and therefore cannot determine if the equipment has been tampered

    with or will be effective in case of fire. Rooms below ground level: If there are any rooms under the house or below ground level (whether they be habitableor non ‐habitable rooms), these may be subject to dampness and water penetration. Drains are not always installedcorrectly or could be blocked. It is common to have damp problems and water entry into these types of rooms,especially during periods of heavy rainfall and this may not be evident upon initial inspection. These rooms may nothave council approval. The purchaser should make their own enquiries with the Council to ascertain if approval wasgiven. Where the property is covered by an Owners Corporation (Strata Title), we strongly recommend that an OwnersCorporation search be conducted to ascertain the financial position, the level of maintenance and any other relevantinformation available through the conduct of such an inspection.

    19. Services Important Notes: In regard to plumbing or electrical, it should be noted that we are not plumbers or electricians andany comment made is not that of a qualified plumber or electrician. We recommend that a qualified contractor be engagedto make comment.