1

BUILDING CODE OF AUSTRALIA REPORT

MIXED-USE DEVELOPMENT

25-29 SMALLWOOD AVENUE HOMEBUSH

PREPARED FOR OPTIMAL ENTERPRISES

3 FEBRUARY 2016

ConsultingDesign right

Page 2: BUILDING CODE OF AUSTRALIA REPORT - Strathfield … · 1 building code of australia report mixed-use development 25-29 smallwood avenue homebush prepared for optimal enterprises 3

2

ConsultingDesign right

TABLE OF CONTENTS EXECUTIVE SUMMARY 3  REPORT DETAILS 4  PROPOSED DEVELOPMENT 4  LOCATION 4  REFERENCED DOCUMENTS 4  CURRENT LEGISLATION 4  REPORT PURPOSE 5  EXCLUSIONS AND LIMITATIONS 5  BUILDING CODE OF AUSTRALIA ASSESSMENT 6  BUILDING DESCRIPTION 6  STRUCTURE (SECTION B, BCA) 7  FIRE RESISTANCE AND STABILITY (SECTION C, BCA) 7  ACCESS & EGRESS (SECTION D, BCA) 10  SERVICES AND EQUIPMENT (SECTION E, BCA) 13  HEALTH AND AMENITY (SECTION F, BCA) 15  ANCILLARY PROVISIONS (SECTION G, BCA) 16  ENERGY EFFICIENCY CONSTRUCTION (SECTION J, BCA) 17  RECOMMENDATIONS 19  CONCLUSION 20  APPENDIX A – DOCUMENTATION 21  APPENDIX B – DRAFT PROPOSED FIRE SAFETY SCHEDULE 22  APPENDIX C - FIRE RESISTANCE LEVELS 22  

606/6a Glen Street, Milsons Point 2061

PO BOX 2331, NORTH PARRAMATTA 1750

0405 295 978

[email protected]

www.designrc.com.au

DESIGN RIGHT CONSULTING PTY LTD

Page 3: BUILDING CODE OF AUSTRALIA REPORT - Strathfield … · 1 building code of australia report mixed-use development 25-29 smallwood avenue homebush prepared for optimal enterprises 3

3

ConsultingDesign right

EXECUTIVE SUMMARY

This report has been prepared to identify the extent of compliance achieved by the assessment of the architectural documentation for the proposed development against the relevant provisions of the Building Code of Australia (BCA) 2015 and its adopted standards. The proposed development consists of the construction of a new seven storey mixed-use building containing sole occupancy residential apartment, retail/commercial tenancy and two levels of basement carparking, located at 25-29 Smallwood Avenue Homebush. This report will provide a BCA analysis to assist in the process of design development and to assist the consent authority in the determination of the Development Application relating to the works. The application for Construction Certificate shall be assessed under the relevant provisions of the Environmental Planning & Assessment Act 1979 (As Amended) and the Environmental Planning & Assessment Regulation 2000.

Page 4: BUILDING CODE OF AUSTRALIA REPORT - Strathfield … · 1 building code of australia report mixed-use development 25-29 smallwood avenue homebush prepared for optimal enterprises 3

4

ConsultingDesign right

REPORT DETAILS

PROPOSED DEVELOPMENT The proposed development consists of the construction of a new seven storey mixed-use building containing sole occupancy residential apartment, retail/commercial tenancy and two levels of basement carparking.

LOCATION The subject building is located at 25-29 Smallwood Avenue Homebush, bounded by Smallwood Avenue to the east, Hudson Avenue to the west and residential to the north and south. The site is within the jurisdiction of Strathfield Council for the purposes of development approvals.

REFERENCED DOCUMENTS The following documents have been reviewed, referenced and/or relied upon in the preparation of this report.

• Building Code Of Australia 2015 (BCA) • Architectural Plans as prepared Ghazi Al Ali Architect (Appendix 1) • Environmental Planning and Assessment Act 1979

CURRENT LEGISLATION The applicable legislation governing the design of buildings is the Environmental Planning and Assessment Act 1979. This Act requires that all new building works must be designed to comply with the BCA. However the existing features of an existing building need not to comply with the BCA unless an upgrade is required by other clauses of the legislation The version of the BCA applicable to the development, is the version that in place at the time of the application of the Construction Certificate.

Page 5: BUILDING CODE OF AUSTRALIA REPORT - Strathfield … · 1 building code of australia report mixed-use development 25-29 smallwood avenue homebush prepared for optimal enterprises 3

5

ConsultingDesign rightREPORT PURPOSE

This report has been prepared to identify aspects of the proposed design that require further consideration and to identify aspects of the design that may be altered subsequent to the issue of a Development Consent This report has been prepared on the basis of an assessment of compliance only and should not be construed as being design advice. Further detailed assessment and design documentation will need to be provided prior to the issue of a Construction Certificate

EXCLUSIONS AND LIMITATIONS Except as mentioned in the report, the limitations and exclusions of this report are as follows -

• Structural adequacy; • Fire resistance of primary structural elements; • Design basis or operating capability of the installed electrical, fire, hydraulic or mechanical

services; • Compliance with the Disability Discrimination Act 1992; • Local Government Act and Regulations • Alternative Solution Reports

Page 6: BUILDING CODE OF AUSTRALIA REPORT - Strathfield … · 1 building code of australia report mixed-use development 25-29 smallwood avenue homebush prepared for optimal enterprises 3

6

ConsultingDesign right

BUILDING CODE OF AUSTRALIA ASSESSMENT

BUILDING DESCRIPTION Use/Classification

Class 2 - Residential Class 6 - Retail/commercial Class 7a – Carpark

Rise in Storeys

The development will have a rise of Seven (7) storeys

Floor Area

The maximum floor areas for fire compartments are not applicable to the Class 2 part and Class 7a sprinkler protected areas. Class 6 - Max floor area- 5000m2 Class 6 portions do not exceed the maximum size of fire compartments in part C2.2 of the BCA 2015.

Volume

The maximum volume provisions for fire compartments are not applicable to the Class 2 part and Class 7a sprinkler protected areas. Class 6 - Max floor volume 30000 m3 Class 6 portions do not exceed the maximum size of fire compartments in part C2.2 of the BCA 2015.

Effective Height

The building will have an effective height more than 12m. (20.65m)

Type of Construction (BCA)

The building requires Type A construction throughout

Climate zone

For the purpose of Section J the climate zone is 5

Page 7: BUILDING CODE OF AUSTRALIA REPORT - Strathfield … · 1 building code of australia report mixed-use development 25-29 smallwood avenue homebush prepared for optimal enterprises 3

7

ConsultingDesign right

STRUCTURE (SECTION B, BCA) STRUCTURAL PROVISIONS The development is to be designed so the structure will resist loads determined:

• AS 1170.0/1–2002, AS 1170.2–2011, • AS 1170.3 – 2011, AS 1170.4 – 2007 • AS 2159-2009 - Piling — Design and installation • AS 2870-2011 - Residential slabs and footings — Construction • AS 3700-2011 - Masonry structures • AS 4100-1998 - Steel structures • AS/NZS 4600 - 2005 - Cold-formed steel structures.

Structural engineer’s certification is to be provided confirming that their design meets all the relevant provisions of the BCA as well as all relevant structural standards at the Construction Certificate stage.

FIRE RESISTANCE AND STABILITY (SECTION C, BCA) FIRE RESISTANCE The building is to comply with Clause C1.1 and Clause 2 & 3 of Specification C1.1, for a building required to have Type A construction. Refer to Table 3 of Specification C1.1 for the specific Fire Resistance Levels [FRL’s]. Structural: the ability to maintain stability and adequate load-bearing capacity as determined by AS 1530.4. Integrity: the ability to resist the passage of flames and hot gases specified in AS 1530.4. Insulation: The ability to maintain a temperature on the surface not exposed to the furnace below the limits specified in AS 1530.4. Class FRL Class 2: 90/90/90 Class 6: 180/180/180 Class 7a: 120/120/120

Where lightweight fire rated construction is proposed for walls, the system must comply with Specification C1.8 of BCA and the manufactures tested specification. Furthermore, the system proposed must be consistent with sound and energy efficiency requirements with Part F5 and Part J of BCA. Columns protected with lightweight fire rated construction that are subject to mechanical damage must be protected and/or internally filled in accordance with Clause C1.8(b) of BCA. FRL's to the parking levels may be reduced where compliance with Clause 3.9 of Specification C1.1 is proposed

Page 8: BUILDING CODE OF AUSTRALIA REPORT - Strathfield … · 1 building code of australia report mixed-use development 25-29 smallwood avenue homebush prepared for optimal enterprises 3

8

ConsultingDesign right

COMPARTMENTATIONS AND SEPERATIONS The key areas for consideration with regards to compartmentation and separation are as follows:

• Each sole occupancy unit within the building, being each individual room or suite of rooms, must be separated by construction achieving an FRL of not less than 90/90/90 for load bearing or -/60/60 for non-load bearing.

• The car parking areas must be separated from the remainder of the building by construction having an FRL not less than 120/120/120.

• The retail/commercial areas must be separated from the remainder of the building by construction having an FRL not less than 180/180/180.

• The lift shaft must be constructed with an FRL not less than 120/120/120 to the basement carpark levels, and 90/90/90 to residential levels.

Construction of firewalls and openings must comply with Part C2.7, C2.8 and Specification C1.1 of BCA. Please note that intervening floors between different classes are required to have a potential increase in FRL, the greater FRL of the two is required in compliance with Clause C2.9 of BCA. The proposed development is capable of achieving the required FRL’s, and is to be confirmed by the structural engineer at the Construction Certificate phase.

PROTECTION OF OPENINGS All openings that require protection will be address via the deemed to satisfy provisions contained within Part C3 of the BCA. Openings with 3m of the northern and southern boundaries require protection in accordance with Clause C3.4 of BCA or via an alternative solution Bounding construction between residential sole occupant units (SOU), doorway, openings and external walls along the path of travel to an exit, from all levels is to comply with the provisions of Specification C1.1, and Clause C3.11 of BCA. All entry doors to residential units must be protected by self-closing -/60/30 fire doors. VERTICAL SEPARATION OF OPENINGS Spandrel separation and horizontal slab construction of external openings are required in accordance with Clause C2.6 of BCA. FIRE HAZARD PROPERTIES The wall and floor linings must achieve the fire hazard properties stipulated in BCA Specifications C1.10 of the BCA.

Page 9: BUILDING CODE OF AUSTRALIA REPORT - Strathfield … · 1 building code of australia report mixed-use development 25-29 smallwood avenue homebush prepared for optimal enterprises 3

9

ConsultingDesign right

FIRE SEALING OF PENETRATIONS All service penetrations must be sealed to the requirements of Clause C3.12 and C3.15 of BCA Garbage room and garbage service shafts, (including walls, floors, ceilings. doors and shutters) must be protected in accordance with C3.12, C3.13 as per BCA. CLASS 2 CORRIDOR LENGTHS Public corridors do not exceed 40m in length and comply C2.14 of BCA.

BOUNDING CONSTRUCTION Bounding construction between residential sole occupant units( SOU) are required to comply with the provisions of SpecificationC1.1, and Clause C3.11 of BCA. Proposed window openings located to the internal bounding walls between the residential and the public corridors must not reduce the fire-resisting performance of the wall as per C3.11 of BCA. Any windows or other openings protected internally in accordance with C3.4 or located at least 1.5 m above the floor of the balcony, landing or the like.

PROTECTION OF EQUIPTMENT

The following equipment is to be fire separated with construction complying with Clause C2.12 (d) of BCA.

(i) lift motors and lift control panels; or (ii) emergency generators used to sustain emergency equipment operating in the emergency

mode; or (iii) central smoke control plant; or (iv) boilers; or (v) a battery or batteries installed in the building that have a voltage exceeding 24 volts and a

capacity exceeding 10 ampere hours. Separation of on-site fire pumps must comply with the requirements of AS 2419.1-2005. ELECTRICAL SUPPLY SYSTEM Electrical equipment is to be separated from the building in accordance with Clause C2.13 of BCA Any substation and/or main switchboard is to be constructed to achieve a fire resistance level of 120/120/120 with the door being -/120/30 fire rated, unless higher FRL’s required by electrical providers

Page 10: BUILDING CODE OF AUSTRALIA REPORT - Strathfield … · 1 building code of australia report mixed-use development 25-29 smallwood avenue homebush prepared for optimal enterprises 3

10

ConsultingDesign right

ACCESS & EGRESS (SECTION D, BCA) NUMBER OF EXITS REQUIRED The minimum number of exits in both the basement above ground levels complies with D 1.2 of the BCA. EXIT TRAVLE DISTANCE Exit travel distances to a required exit or a point of choice between exits does not comply with BCA Clauses D1.4 and D1.5 in the following locations:

• Travel distance to a exit on levels 1 to 4 from is greater than 6m permitted (up to 12m) The non-compliance with the Deemed To Satisfy provisions will be subject to an alternate solution to address the relevant Performance Requirements of the BCA, as advised by the Client. DISTANCE BETWEEN ALTERNATIVE EXITS The distance between alternative exits generally comply with clause D1.5 of BCA. TRAVEL VIA FIRE/NON FIRE ISOLATED EXITS The fire-isolated stairway as a required exit must provide a continuous means of travel by its own flights and landings from every storey served to the level at which egress to a road or open space is provided. DIMENSIONS OF EXITS Exits and paths of travel to exits are to comply with D1.6 of BCA. Minimum dimensions of 1000mm and 2000mm height to be provided within exits, with the paths of travel should provide a minimum width of 1000mm (note that all maintenance access, cat walks, etc may comply with AS1657 in which case a 600mm clear width is required). Doorways are permitted to contain a clear opening width of the required width of the exit minus 250mm, with a height of 1980mm as part of egress requirements. Access for persons with disabilities however requires a clear doorway opening width of 850mm (i.e minimum 870 mm doors). ELECTRICAL DISTRIBUTION BOARDS Electrical distribution boards located in the path of travel to an exit must be enclosed in a non-combustible enclosure and sealed to prevent the escape of smoke.

Page 11: BUILDING CODE OF AUSTRALIA REPORT - Strathfield … · 1 building code of australia report mixed-use development 25-29 smallwood avenue homebush prepared for optimal enterprises 3

11

ConsultingDesign right

CONSTRUCTION OF STAIRWAYS Goings and Risers Goings and risers are to be designed to comply with the provisions of Clause D2.13 of BCA. Landings Landings are to be designed to comply with the provisions of Clause D2.14 of BCA. Thresholds Thresholds are to be designed to comply with the provisions of Clause D2.15 of BCA. Please note D2.15(c) which requires a threshold ramp complying with AS 1428.1-2009. EGRESS DOORS All required exit doorways are either swinging or automatic doors complying with the provisions of BCA Clause D2.19. All doors acting, as exits are required to swing in the direction of egress are also required to be provided with the appropriate hardware in accordance with Clauses D2.20 & D2.21 of the BCA. Final discharge doors on the ground floor are to swing in the path of egress. Also 1m clearances are required for the path to the exit. BALUSTRADES Balustrades must be provided for all areas where it is possible to fall more than 1m. Balustrades are to be designed in accordance with Clauses D2.16 of the BCA. Balustrades protecting a difference in levels of over 4m must not have horizontal elements between 150mm and 760mm of the floor that facilitate climbing. HANDRAILS Handrails are to be provided to stairways as required by Clause D2.17 of the BCA, including internal stairs within a residential SOU SIGNAGE Signage must be provided to all fire safety doors (except those doorways providing access to sole occupancy units) and to doors leading from enclosed stairways as required Clause D2.23 and D3.6 of the BCA. PROTECTION OF OPENABLE WINDOWS Windows in bedrooms where the floor is more than 2 m above the surface beneath require restricted openings or protection in accordance with D2.24 of BCA. All other parts of the buildings that are not part of the Class 2 portion of the building must also be protected with D2.24 of BCA.

Page 12: BUILDING CODE OF AUSTRALIA REPORT - Strathfield … · 1 building code of australia report mixed-use development 25-29 smallwood avenue homebush prepared for optimal enterprises 3

12

ConsultingDesign right

ACCESS FOR PEOPLE WITH DISABILITIES. The building will be capable of providing disabled access compliant with Part D3 of the BCA and Access to Premises Standards. The proposed building is required to comply with the following: • The Disability Discrimination Act 1992 (Commonwealth); • The Disability (Access to Premises — Buildings), Standards 2010; • Part D3 of BCA; • Australian Standard AS 1428.1-2009. Buildings and parts of buildings must be accessible as required by Table D3.1, unless exempted by D3.4, which requires access as follows: Class 2 – Common areas. From a pedestrian entrance required to be accessible to at least 1 floor containing sole-occupancy units and to the entrance doorway of each sole-occupancy unit located on that level. To and within not less than 1 of each type of room or space for use in common by the residents, including a cooking facility, sauna, gymnasium, swimming pool, common laundry, games room, individual shop, eating area, or the like. Where a ramp complying with AS 1428.1 or a passenger lift is installed—

a) to the entrance doorway of each sole-occupancy unit; and b) to and within rooms or spaces for use in common by the residents, located on the levels

served by the lift or ramp Class 6 – To and within all areas normally used by the occupants Class 7a - To and within any level containing accessible carparking spaces. Review prior to the issue of the CC is required to demonstrate compliance with all mentioned applicable provisions. It is recommended that a separate report by a professional access consultant is needed.

Page 13: BUILDING CODE OF AUSTRALIA REPORT - Strathfield … · 1 building code of australia report mixed-use development 25-29 smallwood avenue homebush prepared for optimal enterprises 3

13

ConsultingDesign right

SERVICES AND EQUIPMENT (SECTION E, BCA) HYDRANT SYSTEMS The building will be provided with a hydrant system in accordance with the provisions of Clause E1. 3 of the BCA and AS 2419.1- 2005 The location of the fire booster assembly is within 10m of the building is required to separate from the building by a wall with construction of fire resistance wall rating of not less than FRL 90/90/90 for a distance of not less than 2 m each side of and 3 m above the upper hose connections in the booster assembly. The design of the service will be subject to review by a hydraulic consultant and confirmed compliance prior to the issue of the Construction Certificate stage HOSE REEL SYSTEMS The car parking level and commercial tenancy will be provided with a fire hose reel system in accordance with the provisions of Clause E1.4 of the BCA and AS 2441 - 2005. Locations of fire hose reels are required to be located 4m from an exit. The design of the service will be subject to review by the hydraulic services consultant. PORTABLE FIRE EXTINGUISHERS Fire extinguishers will be provided in accordance the provisions of Clause E1.6 of the BCA and AS2444 - 2001. SMOKE HAZARD MANAGEMENT The building will be provided with a smoke management system in accordance with the provisions of Table E2.2a and Specification E2.2a of the BCA. The building will require:

• Class 2: An automatic smoke detection and alarm system in accordance with Clause 3 and 4 of Specification E2.2a and AS 3786-1993.

• Class 6: An automatic smoke detection and alarm system complying with Specification E2.2a

• Class 7a: Basement carpark requires mechanical ventilation system in accordance with AS 1668.2 and Clause 5.5 of AS/NZS 1668.1.

The design of the service will be subject to review by a fire services consultant. Evidence with compliance with E2.2 of BCA is required prior to the issue of the Construction Certificate.

Page 14: BUILDING CODE OF AUSTRALIA REPORT - Strathfield … · 1 building code of australia report mixed-use development 25-29 smallwood avenue homebush prepared for optimal enterprises 3

14

ConsultingDesign right

EMERGENCY LIGHTING. Emergency lighting will be provided throughout the building in accordance with Clauses E4.2 & E4.4 of the BCA and AS2293.1 - 2005. The design of the service will be subject to review by the electrical services consultant. EXIT SIGNS. Exit signs will be provided throughout the building in accordance with Clauses E4.5, E4.6 & E4.8 of the BCA and AS2293.1- 2005 The design of the service will be subject to review by the electrical services consultant. LIFTS A stretcher facility in the lift will be required in accordance with Clause E3.2 of the BCA, as the building has an effective height of greater than 12m. A sign must be provided in accordance with Clause E3.3 of the BCA warning against the use of lifts in a fire. The proposed lifts shall also comply with all requirements nominated by AS1735.12 and Clause E3.6 of the BCA, with regards to facilities for people with disabilities. SPRINKLERS The development will require a sprinkler system to the basement carpark levels of the building complying with Spec E1.5 of the BCA and AS2118.1- 1999. The design of the service will be subject to review by a fire services consultant.

Page 15: BUILDING CODE OF AUSTRALIA REPORT - Strathfield … · 1 building code of australia report mixed-use development 25-29 smallwood avenue homebush prepared for optimal enterprises 3

15

ConsultingDesign right

HEALTH AND AMENITY (SECTION F, BCA) DAMP & WEATHERPROOFING. Adequate measures will be employed to ensure compliance Part F1 of the BCA is achieved in terms of damp and weatherproofing. SANITARY & OTHER FACILITIES. Facilities will be provided in accordance with the provisions of Clause/Table F2.3 of the BCA. All sanitary compartments that have proposed in-swinging doors are required to be 1.2m from the WC pan, or lift off hinges are provided as per F2.5 of BCA. A sanitary compartment is provided on the ground floor for employees in accordance with Table F2.1 of the BCA (cleaners room). CEILING HEIGHT The following minimum building ceiling heights must be maintained. • Common kitchen, laundry or the like – 2.1m • Corridor, passageway or the like – 2.1m • Bathroom, shower, sanitary compartment or the like – 2.1m • Habitable rooms including common areas – 2.4m • Stairways – 2.0m • Car parking areas – 2.2m • Disabled car parks – 2.5m including a 2.3m path of travel height VENTILATION The building is required to be provided with ventilation in accordance with the provisions of Clause F4.5 of the BCA. Ventilation may be provided by a natural means or a mechanical system complying with AS 1668.2- 1991. LIGHTING Natural lighting to sole occupancy units and artificial lighting must be provided throughout the building in accordance with F4.2 and F4.4 of the BCA and AS/NZS1680.0-1998. Artificial lighting may be provided throughout the remained of the building in accordance with the provisions of Clause F4.4 of the BCA and AS1680.1.

Page 16: BUILDING CODE OF AUSTRALIA REPORT - Strathfield … · 1 building code of australia report mixed-use development 25-29 smallwood avenue homebush prepared for optimal enterprises 3

16

ConsultingDesign right

SOUND INSULATION The floor separating the residential units and separating the sole occupancy units from public areas must achieve a sound insulation rating of Rw+Ctr (airborne) of not less than 50 and an Ln,w+Ci (impact) not more than 62. Walls separating units must achieve a sound insulation rating of Rw+Ctr (airborne) of not less than 50. Walls separating units from plant rooms, lift shafts, stairways corridors or other public areas must have an insulation rating of Rw (airborne) not less than 50. Walls separating a bathroom, sanitary compartment, laundry or kitchen in one sole occupancy unit from a habitable room in another or separating a unit from a lift shaft must be of discontinuous construction. The doorway separating to sole occupancy unit from the public area must have an Rw not less than 30 Soil, waste & stormwater services must be separated by construction having an Rw+Ctr (airborne) not less than

• 40 if the room is a habitable room • 25 if the room is a non-habitable room

ANCILLARY PROVISIONS (SECTION G, BCA) CLEANING OF WINDOWS As per NSW Clause G1.101 a building must provide for a safe manner of cleaning any windows located 3 or more storeys above ground level. This is satisfied where—

i. the windows can be cleaned wholly from within the building; or ii. provision is made for the cleaning of the windows by a method complying with the Work

Health and Safety Act 2011 and regulations made under that Act.

Page 17: BUILDING CODE OF AUSTRALIA REPORT - Strathfield … · 1 building code of australia report mixed-use development 25-29 smallwood avenue homebush prepared for optimal enterprises 3

17

ConsultingDesign right

ENERGY EFFICIENCY CONSTRUCTION (SECTION J, BCA) Note 1: The residential Class 2 part of the building is to be designed to comply with the requirements of two MANDATORY points for energy efficiency. They are as follows:

• A, BASIX assessment and a BASIX certificate will be required to be lodged with the development application.

• The building is required to comply with the BCA Section J & Appendix NSW J(B) Energy Efficiency – Class 3 and Class 5 to 9 buildings. The relevant/applicable sections of NSW J (B) are to be complied with. The clauses within Section J are listed below. NOTE: All definitions in Part A1 that are applicable to the national Section J are also applicable to NSW Section J. NSW J(B)1 Compliance with BCA provisions Class 3 and Class 5 to 9 buildings must comply with all of the provisions of the national Section J that are applicable to the relevant classifications, except as varied by NSW J3.1 Application of Part and NSW J8.2 Access for maintenance.

BUILDING FABRIC Parts of the building forming an envelope to a conditioned space are to achieve the minimum construction requirements for insulation R-Values required by BCA Part J1 GLAZING The energy efficiency of the selected glazing must comply with Part J2 of the BCA as appropriate to Climate Zone 6 and the orientation, exposure and shading of the window. BUILDING SEALING Openings in the building such as doors, windows, exhaust fans and ventilation systems must be sealed to the requirements of Part J3 of the BCA as appropriate to Climate Zone 6. In that regard, all external doorways must be fitted with a draft seal. This requirement does not apply to fire doors fitted between the fire-isolated stairways and the conditioned areas of the building. AIR-CONDITIONING AND VENTILATION SYSTEM The design of all mechanical air-conditioning and ventilation systems must achieve compliance with Part J5 of the BCA with regard to input power and efficiency features.

Page 18: BUILDING CODE OF AUSTRALIA REPORT - Strathfield … · 1 building code of australia report mixed-use development 25-29 smallwood avenue homebush prepared for optimal enterprises 3

18

ConsultingDesign right

ARTIFICIAL LIGHTING AND POWER The building is to maintain maximum lighting power levels and control systems as applicable. The design of lighting systems must comply with BCA Part J6. The following maximum lighting power loads (W/m²) are applicable to the building

• Car park - 6 • Car park entry zone (20m) - 25 • Common rooms, corridors - 8 • Control room, switch room - 9 • Plant room - 5 • Service areas & store rooms – 5

These rates are able to be adjusted as detailed in BCA Clause Table J6.2 where daylight or motion sensors or dimming systems are provided or in particularly small rooms. BASIX will also impose efficiency measures to the building HOT WATER SUPPLY Hot water supply systems will be installed in accordance with Part J7 of the BCA and AS/NZS 3500.4. ACCESS FOR MAINTENANCE AND ENERGY MONITORING The building is to have facilities for maintenance and energy monitoring in compliance with BCA Part J8 and the NSW variations.

Page 19: BUILDING CODE OF AUSTRALIA REPORT - Strathfield … · 1 building code of australia report mixed-use development 25-29 smallwood avenue homebush prepared for optimal enterprises 3

19

ConsultingDesign right

RECOMMENDATIONS Subsequent to our assessment of the proposed development, it is recommended that the following matters are to be addressed to comply with the BCA utilising either as the ‘deemed to satisfy’ provisions or via an alternate solution under the performance requirements (as advised by the client):

• Intervening floors between different classes are required to have a potential increase in FRL, the greater FRL of the two is required in compliance with Clause C2.9 of BCA.

• Openings with 3m of the northern and southern boundaries require protection in accordance with Clause C3.4 of BCA or via an alternative solution

• Travel distances to a required exit or a point of choice between exits does not comply with BCA Clauses D1.4.

• The location of the fire booster assembly unit requires protection as per E1.3 of BCA and AS 2419.1 2005.

• The development will require a sprinkler system to the basement carpark levels complying with Spec E1.5 of the BCA and AS2118.1- 1999.

• The development is subject to requirements contained within Part D3 of the BCA, AS 1428.1-2009 and the Premises Standards. It is recommended that a separate report from a suitable qualified access consultant would be suggested to demonstrate compliance with all mentioned applicable provisions

Page 20: BUILDING CODE OF AUSTRALIA REPORT - Strathfield … · 1 building code of australia report mixed-use development 25-29 smallwood avenue homebush prepared for optimal enterprises 3

20

ConsultingDesign right

CONCLUSION It is the opinion of this office that, on satisfaction of the above recommendation, the proposed building is capable of achieving compliance with the requirements of the Building Code of Australia (BCA) 2015 Volume 1, and relevant adopted standards without undue modification to the design or appearance of the building. Whilst the above recommendation have been made as a means of achieving compliance with the various provisions of BCA Performance Requirements their acceptability has not been verified at this time. It will be necessary for the design to be reviewed by an appropriately qualified person prior to the issue of a Construction Certificate for the works.

ALEKS STOJCEVIC DIRECTOR DESIGN RIGHT CONSULTING PTY LTD 2 February 2016.

Page 21: BUILDING CODE OF AUSTRALIA REPORT - Strathfield … · 1 building code of australia report mixed-use development 25-29 smallwood avenue homebush prepared for optimal enterprises 3

21

ConsultingDesign right

APPENDIX A – DOCUMENTATION The following documentation was used in the assessment and preparation of this report:

Drawing

No. Title Date Revision

A1200 Basement 2 02.02.2016 A

A1201 Basement 1 02.02.2016 A

A1202 Ground Floor 02.02.2016 A

A1203 Level 1 02.02.2016 A

A1204 Level 2 02.02.2016 A

A1205 Level 3 02.02.2016 A

A1206 Level 4 02.02.2016 A

A1207 Level 5 02.02.2016 A

A1208 Level 6 02.02.2016 A

A1209 Roof Plan 02.02.2016 A

A1500 Elevation 02.02.2016 A

A1501 Elevation 02.02.2016 A

A1502 Elevation 02.02.2016 A

A1503 Elevation 02.02.2016 A

A1700 Section BB 02.02.2016 A

A1701 Section AA 02.02.2016 A

Page 22: BUILDING CODE OF AUSTRALIA REPORT - Strathfield … · 1 building code of australia report mixed-use development 25-29 smallwood avenue homebush prepared for optimal enterprises 3

22

ConsultingDesign right

APPENDIX B – DRAFT PROPOSED FIRE SAFETY SCHEDULE

Essential Fire Safety Measures

Standard of Performance

Access panels, Doors and Hoppers to Fire-resisting shafts

BCA Clause C3.13

Automatic fail safe devices BCA Clause C3.4, D2.21, AS 1670.1-2004 Automatic fire detection and alarm system BCA Spec E2.2a, AS 1670.1-2004 , AS 3786-

1993 Automatic fire suppression system (sprinkler) BCA Clause E1.5, AS 2118.1-1999 Emergency lighting BCA Clause E4.2 & E4.4, AS 2293.1-2005 Emergency lifts BCA Clause E3.4, AS 1735.2-2001 Exit signs BCA Clause E4.5 & E4.8, AS 2293.1-2005 Fire dampers AS 1668.1-1999 Fire doors BCA Spec C3.4, AS 1905.1-2005 Fire Engineering TBA Fire Engineer Guidelines Fire hose reel systems BCA Clause E1.4, AS 2441-2005 Fire hydrant systems BCA Clause E1.3, AS 2419.1-2005 Fire seals (protecting openings in fire resisting components of the building)

BCA Clause C3.15

Lightweight fire rated construction BCA Clause C1.8, BCA Spec C1.8 Mechanical air handling system AS 1668.1-1999, AS 1668.2-1991 Stand-by power system BCA Spec G3.8 Smoke doors AS 1905.1-2005 Portable fire extinguishers BCA Clause E1.6, AS 2444-2001 Warning and operational signage (e.g. stairway notices)

BCA Clause D2.23 & E3.3, EP&A Act Form 15B

APPENDIX C - FIRE RESISTANCE LEVELS The table below represents the Fire resistance levels required in accordance with BCA 2014:

Page 23: BUILDING CODE OF AUSTRALIA REPORT - Strathfield … · 1 building code of australia report mixed-use development 25-29 smallwood avenue homebush prepared for optimal enterprises 3

23

ConsultingDesign right

Building element Class of building — FRL : (in minutes)

Structural adequacy/Integrity/Insulation

2, 3 or 4 part 5, 7a or 9 6 7b or 8

EXTERNAL WALL (including any column and other building element incorporated therein) or other external building element, where the distance from any fire-source feature to which it is exposed is—

For loadbearing parts—

less than 1.5 m 90/ 90/ 90 120/120/120 180/180/180 240/240/240

1.5 to less than 3 m 90/ 60/ 60 120/ 90/ 90 180/180/120 240/240/180

3 m or more 90/ 60/ 30 120/ 60/ 30 180/120/ 90 240/180/ 90

For non-loadbearing parts—

less than 1.5 m –/ 90/ 90 –/120/120 –/180/180 –/240/240

1.5 to less than 3 m –/ 60/ 60 –/ 90/ 90 –/180/120 –/240/180

3 m or more –/–/– –/–/– –/–/– –/–/–

EXTERNAL COLUMN not incorporated in an external wall—

For loadbearing columns—

90/–/– 120/–/– 180/–/– 240/–/–

For non-loadbearing columns—

–/–/– –/–/– –/–/– –/–/–

COMMON WALLS and FIRE WALLS—

90/ 90/ 90 120/120/120 180/180/180 240/240/240

INTERNAL WALLS—

Fire-resisting lift and stair shafts—

Loadbearing 90/ 90/ 90 120/120/120 180/120/120 240/120/120

Non-loadbearing –/ 90/ 90 –/120/120 –/120/120 –/120/120

Bounding public corridors, public lobbies and the like—

Loadbearing 90/ 90/ 90 120/–/– 180/–/– 240/–/–

Non-loadbearing –/ 60/ 60 –/–/– –/–/– –/–/–

Between or bounding sole-occupancy units—

Loadbearing 90/ 90/ 90 120/–/– 180/–/– 240/–/–

Non-loadbearing –/ 60/ 60 –/–/– –/–/– –/–/–

Ventilating, pipe, garbage, and like shafts not used for the discharge of hot products of combustion—

Loadbearing 90/ 90/ 90 120/ 90/ 90 180/120/120 240/120/120

Non-loadbearing –/ 90/ 90 –/ 90/ 90 –/120/120 –/120/120

OTHER LOADBEARING INTERNAL WALLS, INTERNAL BEAMS, TRUSSES

and COLUMNS— 90/–/– 120/–/– 180/–/– 240/–/–

FLOORS 90/ 90/ 90 120/120/120 180/180/180 240/240/240

ROOFS 90/ 60/ 30 120/ 60/ 30 180/ 60/ 30 240/ 90/ 60