R E N E W A B L E E N E R G Y - H Y B R I D T E C H N O L O G Y - E N V I R O N M E N T - C O M F O R T - P L U G & P L A Y - P E R F O R M A N C E - W A T E R H E A T E R - E R P
R E N E W A B L E E N E R G Y - H Y B R I D T E C H N O L O G Y - E N V I R O N M E N T - C O M F O R T - P L U G & P L A Y - P E R F O R M A N C E - W A T E R H E A T E R - E R P - E N E R G Y S A V I N G S - S A F E T Y - R E N E W A B L E E N E R G Y - H Y B R I D T E C H N O L O G Y - E N V I R O N M E N T - C O M F O R T - P L U G & P L A Y - P E R F O R M A N C E
WWW.COTHERM.COM
BTS3-pole combistat
FEATURES> Combined control and safety function> Independent non self resetting safety> Available as single control or safety only > Double pole single throw version (DPST)> Multiple mounting, electrical connection, adjustment, and reset knob confi gurations> Factory pre-set fi xed temperature, OEM adjustable or end-user adjustable temperature
OPERATIONA rise in temperature causes the expansion of liquid within the bulb and capillary. The liquid acts on a bellows assembly within the plastic housing to open and close electrical contacts with temperature variation. In case of abnormal rise in temperature, liquid expansion in a separate bulb capillary assembly will break independent contacts to insure safety operation. The limiter is manually resettable.
3-pole temperature regulation and capillary safety limiter with manual reset
WWW.COTHERM.COM
TECHNICAL CHARACTERISTICS
DO
CC
OM
A04
2 –
02 -
-
CO
THER
M r
eser
ves
the
righ
t to
brin
g an
y m
odifi
cati
ons
to o
ur p
rodu
cts.
We
man
ufac
ture
pro
duct
s ac
cord
ing
to d
raw
ings
whi
ch s
erve
as
cont
ract
ual d
ocum
ents
. We
are
not r
espo
nsib
le fo
r da
mag
e re
sult
ing
from
inap
prop
riat
e in
stal
lati
on o
r us
e of
our
pro
duct
.BTS GPC
Type 20A triple pole single throw (TPST) adjustable or fi xed temperature control with 3-pole safety limiter
30A triple pole single throw (TPST) adjustable or fi xed temperature control with 3-pole safety limiter
Temperature range -35°C to 300°C / -31°F to 572°F
Differential Approx. 5% of the temperature range
Safety limiter function Temperature: fi xed 70°C – 300°C / 158°F – 572°F Available with fail-safe capillary = BSDP range
Rating BTS 20A – 240V / 15A – 400V ; GPC 30A – 240V / 20A – 400V
Material Bulb and capillary in copper, nickel-plated copper or stainless steel
Capillary length 150 to 2000mm / 6 to 79”
Sensing element diameters Copper: 4, 5, 6, 6.5 and 8mm / 5/32, 3/16, ¼ and 5/16” Stainless steel: 3, 5 and 6mm / 1/1, 3/16 and ¼”
Maximum head temperature 105°C / 221°F
Connections Brass or nickel plated faston terminals, screw terminals
Approvals CE conformity, ENEC MARK according to EN-60730-1, EN 67130-2-9, ROHS conformity
BTS
Weight: approx. 250g