Upload
others
View
31
Download
0
Embed Size (px)
Citation preview
Draka BS7889 - Industrial Single Core CableUnamroured industrial single core wiring cable with cross linked polyethylene insulation and PVC sheath. Suitable for installation in areas with reduced risk of mechanical damage; on tray, in free air or clipped direct. Suitable also for conduit and wiring installations when mechanical protection is required.
Construction Manufacturing standard: BS 7889
Conductors: Stranded plain annealed copper wire (Class 2) to BS EN 60228
Insulation: XLPE
Sheath: PVC
Core colours: Brown or Blue
Sheath colour: Black
Physical CharacteristicsVoltage rating (Uo/U): 600/1000V
Max. conductor temp: 90°C Note: Where a conductor operates at a temperature exceeding 70°C it shall be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature (see regulation 512-1-5 of BS7671, the 17th Edition of IEE Wiring Regulations)
Min. bending radius: 4D (up to and including 185mm²)6D (240mm² and larger)
Curent rating: Refer to tables 4E1A & 4E1B in BS7671
BS7889
Other colours available on request
Prysmian Group,Chickenhall Lane,Eastleigh,SO50 6YU
Sales Telephone01332 345431 www.drakauk.com
BS7889Nominal area of
conductor
mm²
Insulation thickness
mm
Insulationsheath
thickness
mm
Mean overall diameter
(upper limit)
mm
Approx. weight of
cable
kg/km
Maximum conductor resistance
@ 20°CΩ/km
1.5 0.7 1.4 5.9 50 12.102.5 0.7 1.4 6.4 65 7.414 0.7 1.4 6.8 80 4.616 0.7 1.4 7.5 105 3.0810 0.7 1.4 8.4 150 1.8316 0.7 1.4 9.0 200 1.1525 0.9 1.4 10.6 295 0.72735 0.9 1.4 11.6 390 0.52450 1.0 1.4 13.2 515 0.38770 1.1 1.4 14.9 715 0.26895 1.1 1.5 16.7 970 0.193120 1.2 1.5 18.9 1235 0.153150 1.4 1.6 20.9 1510 0.124185 1.6 1.6 22.9 1860 0.0991240 1.7 1.7 25.4 2410 0.0754300 1.8 1.8 28.1 3010 0.0601400 2.0 1.9 32.0 3030 0.0470500 2.2 2.0 36.0 4915 0.0366630 2.4 2.2 40.7 6320 0.0283800 2.6 2.3 45.8 8210 0.02211000 2.8 2.4 50.8 10290 0.0176
Drak
aBS7
8893
0102
013
Single core 6U81SH