Digital Inputs: Main Breaker, Start, Normal Stop, Emergency Stop, Rapid Stop, Increase WG Set Point, Decrease WG Set Point, Prepairing the Start, WG blocked/unblocked Signalization for oil filter clogging Digital Outputs: opening/closing isolating valve, Commands for the emergency units from the both servovalves (WG and Runner), Governor’s Status, WG Closed, WG at 20% opening, Governor Ready to Start DIGITAL SPEED GOVERNOR For Hydro Turbines Digital Speed Governor for Kaplan, Francis, bulb, Pelton turbines Hydro-mechanical system equipped with: HRV servosolenoid valves with OBE (Bosch/Moog) (NG 10, 16, 25, 32) Oil filter: 10 μm, 25 μm (Hydac) Isolating valve (Bosch) Oil pressure unit: Oil: TBA57E or similar Nominal Pressure: 30-60 bar Transducers for: Downstream, Upstream water levels (MJK), 4-20 mA Flow – Differential Pressure (Siemens), 4-20 mA Speed – proximity, sinusoidal voltage (Omron), 4-20 mA Wicket Gate position – magnetostrictive (Baluff), 4-20 mA Runner blades position – magnetostrictive, 4-20 mA Governing system’s pressure (Turck), 4-20 mA Active Power – (Turck), 4-20 mA Digital Command Equipment Power Supply: 220 Vdc/24 Vdc PLC: R3xi (GE Fanuc), 300 Mhz, Quantum (Schneider), 166 MHz High Speed Counter: 80-150 kHz Analog Inputs: 16 channels curr., 12 bit, Analog Outputs: 8 channels curr/volt, 12 bit Digital Inputs: 32 channels, 24 Vcc Digital Outputs: 32 channels, 24 Vcc Data Panel: Touchscreen 6-7 inch, 256 colors Communications: Ethernet, CAN, Modbus/RTU, Modbus Plus etc., RS-232, RS-485 GPS: hour and date updating Analog Inputs: Frequency (pulses) Wicked Gate Position Runner Blades’ Opening Angle WG Distributing Valve’s Position (Diagnosis) Runner Distributing Valve’s Position (Diagnosis) Oil Pressure in Governing System Active Power Water Level in Upstream Netto Head Water Flow (optimization of the turbine’s efficiency) Analog Outputs: Command for WG servovalve (±10 Vdc) Command for Runner servovalve (±10 Vdc) Indicating parameters for measurements in 0..10 Vdc: frequency, WG position, Runner position, Active Power, WG’s Set Point, Netto Head etc.

Brochure Hydro Turbine Governor

Embed Size (px)

Citation preview

Page 1: Brochure Hydro Turbine Governor

Digital Inputs: Main Breaker, Start, Normal Stop, Emergency Stop, Rapid Stop, Increase WG Set Point, Decrease WG Set Point, Prepairing the Start, WG blocked/unblocked Signalization for oil filter clogging Digital Outputs: opening/closing isolating valve, Commands for the emergency units from the both servovalves (WG and Runner), Governor’s Status, WG Closed, WG at 20% opening, Governor Ready to Start

DIGITAL SPEED GOVERNOR

For Hydro Turbines

Digital Speed Governor for Kaplan, Francis, bulb, Pelton turbines Hydro-mechanical system equipped with: HRV servosolenoid valves with OBE (Bosch/Moog) (NG 10, 16, 25, 32) Oil filter: 10 µm, 25 µm (Hydac) Isolating valve (Bosch) Oil pressure unit: Oil: TBA57E or similar Nominal Pressure: 30-60 bar Transducers for: Downstream, Upstream water levels (MJK), 4-20 mA Flow – Differential Pressure (Siemens), 4-20 mA Speed – proximity, sinusoidal voltage (Omron), 4-20 mA Wicket Gate position – magnetostrictive (Baluff), 4-20 mA Runner blades position – magnetostrictive, 4-20 mA Governing system’s pressure (Turck), 4-20 mA Active Power – (Turck), 4-20 mA

Digital Command Equipment Power Supply: 220 Vdc/24 Vdc PLC: R3xi (GE Fanuc), 300 Mhz, Quantum

(Schneider), 166 MHz High Speed Counter: 80-150 kHz Analog Inputs: 16 channels curr., 12 bit, Analog Outputs: 8 channels curr/volt, 12 bit Digital Inputs: 32 channels, 24 Vcc Digital Outputs: 32 channels, 24 Vcc Data Panel: Touchscreen 6-7 inch, 256 colors Communications: Ethernet, CAN, Modbus/RTU,

Modbus Plus etc., RS-232, RS-485 GPS: hour and date updating

Analog Inputs: Frequency (pulses) Wicked Gate Position Runner Blades’ Opening Angle WG Distributing Valve’s Position (Diagnosis) Runner Distributing Valve’s Position (Diagnosis) Oil Pressure in Governing System Active Power Water Level in Upstream Netto Head Water Flow (optimization of the turbine’s efficiency) Analog Outputs: Command for WG servovalve (±10 Vdc) Command for Runner servovalve (±10 Vdc) Indicating parameters for measurements in 0..10 Vdc: frequency, WG position, Runner position, Active Power, WG’s Set Point, Netto Head etc.

Page 2: Brochure Hydro Turbine Governor

Speed Governing Parameters A/D conversion time: (<0,1 ms) Permanent speed drop: 1-10% Time constant: Td=0-99 sec Frequency set point: 47.5-52.4 Hz Frequency dead band: 0.05 Hz Frequency accuracy: <5 mHz Digital WG Set Point resolution: <10 mHz Governor’s insensibility <10 mHz Digital cam (spatial type) Load/Unload/Power gov. parameters settable WG, ϕ limits, settable Power Supply: 220 Vcc Overvoltage protection, by-pass protections Checksum, watchdog Input signal: 0-10 VDC, 4-20 mA Complete diagnosis of the system Governing Loops: frequency-opening, frequency-power, frequency-upstream water level, water flow Auto-adaptive transfer functions

E ISO-128

Proiectat

Desenat

Data

Scara: Material: Greutate:

Verificat

Aprobat

Nr. inv.

Rev.

UCMResita A3

A

B

C

D

E

F

G

H

I

J

A

B

C

D

E

F

G

H

I

J

DEPARTAMENT PROIECTARE

Error : ucmrlogo.JPG file not found.

Kd

-

+

Kp

fg

FP

AD_Sp

Bloc PID

T i (1/sT i)

F/AD/P

+

P_SP

Pa

Comutare Automata a Parametrilor

Man

_SP

Bloc reglare

DB

F/AD/P

Dom

F/AD/P

+(-)

+

P

Kf

1.6

Kbpp

0.08xbpp

Kbp

0.08xbp

Bias

SUM4

Dfc [Hz]

+

-

-

+

Td (sTd)

*

+PV

-SP

-

+

Reactie Frecv. generator

Tip reglaj

Mers in gol (Reglaj f) Sarcina reglaj f/AD

Parametri principali de acordareSarcina reglaj f/P

f_P

/f_A

D

*

f_P/f_AD

f_P/f_AD

Tip Reglaj

Aut/Man

CV

-

+

Sta

rt_S

P

Man

._S

P

Sto

p_S

P

CCN

BL_CCNTfR

1/0.5s

+

-

SP

PV

-

+

-

+

Ham_SP

TdH

1/sTdH

*Kh2

BLP1

+

+Kh1

BLP1

Reactie Ham.

Consemn Ham.

Bloc cama combinatorica si reglaj Nive l

Re

gHam

Bloc pozitionare R

SM_RKa

10

Svr+/-8Yr

HA

D

**

*

IO

*

I P

TPA

MW/mA

CC

/Sta

rt

Aut

/Ma

n

Fu

nct/

Opr

ire

RegHam

Aut/Man

Ham

Hnet

Hnet_SP

-

+TfH

1/20s

SP

PV

Reactie Hnet

Aut

/Man

_H

*

Aut

/Man

H

SD

Ksdr

S

+

Bloc comanda R

+

-

Bloc poz itionare R

SM_ADKa

10

SvAD+/-8Y

SD_AD

Ksd

S

+

Bloc comanda AD

Q2

Q2

T iQ

1/sTiQ

+

-

Qm/Qc

*

Q=f(a0,H)

Q_SP

Re

g.Q

Qm

Q-CV

dfS

P

CV

CV

CV

Digital Speed Governor for Hydro Turbines Block Diagram

Design: CATIA, AutoCAD Programming: ladder logic, HMI Central Concept: TRIDENT own UCMR’s Hydro Digital Control System Concept Acreditation: UCTE normatives for energy distribution

Page 3: Brochure Hydro Turbine Governor

Digital Speed Governor HEPP Implementation Mounting and starting within HEPP Performance tests Qualification for System Services Measurements Real time data acquisition equipment (LabVIEW software VIs)

CHE Zavideni HA1Pornire, sincronizare, cuplare, incarcare stimulentabp=7% ora 15:17

t0,8=223.6 s, 40 Hz

t0=205 s

tS=265 s

tSR=261.3 s, 49.75 Hz

0

10

20

30

40

50

60

70

80

90

100

200 210 220 230 240 250 260 270 280 290 300 310 320 330 340

t[sec]

Yad

[%],

Yr[

%],

P[M

W],

f[H

z],

TP

[%]

45

46

47

48

49

50

51

52

53

54

55

f[H

z]

Yad[%] Yr[%] P[MW] F[Hz] TP[%] f[Hz]

CHE Zavideni HA1Aruncare de sarcina de la P=19 MW, reglaj frecventa-puterebpp=8% ora 15:43

0

10

20

30

40

50

60

70

80

90

100

550 560 570 580 590 600 610 620 630 640 650

t[sec]

f[H

z],

Yad

[%],

Yr[

%],

P[M

W],

f[H

z]

Yad[%] Yr[%] P[MW] f[Hz]