Bristol/IP Driver
Table of Contents
Bristol/ IP Driver 1
Table of Contents 2
Bristol/ IP Driver 4
Overview 4
BSAP Networks 5
Channel Setup 6
Channel Properties — General 6
Channel Properties — Ethernet Communications 7
Channel Properties — Write Optimizations 7
Channel Properties — Advanced 8
Channel Properties — Communication Serialization 9
Channel Properties — Local Port 10
Device Setup 11
Device Properties — General 11
Operating Mode 12
Device Properties — Scan Mode 12
Device Properties — Auto-Demotion 13
Device Properties — Tag Generation 14
Device Properties — Communication 16
Device Properties — Timing 16
Device Properties — Tag Import Properties 17
Device Properties — Redundancy 17
Optimizing Communications 18
Data Types Description 18
Address Descriptions 19
Error Descriptions 20
<Operat ion> on device <device name> signal <signal> caused an overf low. Some data has
been lost. 21
<Operat ion> on device <device name> signal <signal> failed. The device does not contain
this signal. 21
<Operat ion> on device <device name> signal <signal> failed. The device requires higher
level permissions to perform this operat ion. 21
<Operat ion> on device <device name> signal <signal> failed. The request was malformed or
incomplete. 22
A read by address failed because the MSD version for device <device name> changed. The
driver is sending read by name requests to get the updated MSD version from the device. 22
www.ptc.com
2
Bristol/ IP Driver
A write by address failed because the MSD version for device <device name> changed. The
driver is sending a write by name request to the device. 22
Failed to send a request to device <device>. The device is not communicat ing. 23
Failed to send a request to device <device>. The packet is malformed or too large. 23
Failed to stop Winsock communicat ions. 24
Failure to init iate 'winsock.dll' [Error:<error>]. 24
Invalid BSAP funct ion. 24
Read failed on device <device> address <address>. The server expects this address to be of
type <type>, but it is of type <type> in the device. 25
The response received from device <device> contains an invalid sequence number. Review
timing propert ies. 25
The response received from device <device> is malformed. 25
The response received from device <device> is too large (%<count> bytes). The data is lost. 26
The signal was not found. 26
The string writ ten to device <device>, address <address> is too long. The maximum sup-
ported string is <count> characters. The write will cont inue as is, but the device will t runcate
the value. 26
Unable to bind to port <port> on Channel <channel>. 27
Unable to create a socket connect ion for Channel <channel>. 27
Unable to generate a tag database for device <device name>. Reason: Import f ile does not
contain any valid signals. 27
Write to device <device name> signal <signal> failed. The signal's manual inhibit at tribute is
set to false, not allowing writes. 28
Write to device <device name> signal <signal> failed. The signal is read only. 28
Write to device <device name> signal <signal> failed. The write value is invalid. Make sure
the value is within the approved BSAP range. 28
Appendix: Tag Generation 29
Index 32
www.ptc.com
3
Bristol/IP Driver
Bristol/ IP DriverHelp version 1.025
CONTENTS
OverviewWhat is the Bristol/IP Driver?
Channel SetupHow do I configure channels for use with this driver?
Device SetupHow do I configure a device for use with this driver?
Optimizing Communicat ionsHow do I optimize communications on the Bristol/IP Driver?
Data Types Descript ionWhat data types are supported by this driver?
Address Descript ionsHow do I address a data location on the Bristol/IP Driver?
Automat ic Tag Generat ionHow can I easily configure tags for this driver?
Error Descript ionsWhat error messages are produced by the Bristol/IP Driver?
OverviewThe Bristol IP Driver provides a reliable way to communicate with DPC and ControlWave devices. It supports
communications to both Ethernet-enabled Bristol devices and to serial Bristol devices (through an Ethernet-
enabled Bristol device acting as a gateway). It supports Network 3000 Series (DPC 33xx) and ControlWave
devices. For more information, refer to Device Setup.
www.ptc.com
4
Bristol/ IP Driver
BSAP NetworksThe image below displays a typical Bristol IP Driver configuration. The devices are physical devices. The
server channels and devices are not displayed for simplicity.
The Bristol IP Driver communicates to Master or Slave devices using Ethernet (UDP). Communications to
Master devices are direct: the driver sends a request to the device and it responds. Communications to
slave devices are indirect: the driver sends a request through the master device. In most configurations,
slave devices communicate over serial to the master.Note: BSAP allows six levels of hierarchy including the Master device, or five levels of hierarchy below the
Master device. Each level below the Master device can have a maximum of 128 devices.
Channel and Device LimitsThe maximum number of channels supported by this driver is 256. The maximum number of devices sup-
ported by this driver is 8192 per channel.
Operations by Symbolic Name vs. by AddressBristol IP devices support reads and writes by address or by symbolic name. Reads and writes by symbolic
name are usually less efficient because the request contains the signal name in ASCII format. Reads and
writes by address are usually more efficient because the address is only two bytes. The driver will request by
address whenever possible.
Supported BSAP FunctionsThe Bristol IP Driver supports a set of Bristol BSAP functions that are a subset of those available in the
Remote Database Access (RDB) specification. All request types have the ability to request more than one sig-
nal at a time. For efficiency, the driver will include multiple signals in a request whenever possible.Note: Requests can be made using either the signal's symbolic name or the signal's address (which is gen-
erally more efficient).
Operat ion Descript ion
Read Signal By
AddressRead one or more signals using the two byte address.
Read Signal By Sym-
bolic Name
Read one or more signals by signal name. Request the signal's two byte
address in addition to the value.
Write Signal By
AddressWrite one or more signals using the two byte address.
www.ptc.com
5
Bristol/IP Driver
Write Signal By Sym-
bolic NameWrite one or more signals by signal name.
Channel Setup
Network InterfaceThe Network Interface property specifies the Network Interface Controller (NIC) over which the channel will
communicate. Each channel must have a unique NIC and port. For example, two Bristol channels cannot be
bound to the default NIC on Port 1234: only one channel can bind to the port and communicate.Note: The default adapter is the adapter bound to the machine hostname.
Communication SerializationThe Bristol IP Driver supports Communication Serialization, which specifies whether data transmissions
should be limited to one channel at a time. For more information, refer to Channel Properties — Advanced.
Local PortThe Local Port property group specifies the port that all devices under the channel will use for com-
munications.
UDP Port : This property specifies the local port to which the channel will be bound. The default setting for
most Bristol devices is 1234. Users that change the UDP Port may also need to change the device con-
figuration to communicate with the port.
Channel Propert ies — GeneralThis server supports the use of simultaneous multiple communications drivers. Each protocol or driver used
in a server project is called a channel. A server project may consist of many channels with the same com-
munications driver or with unique communications drivers. A channel acts as the basic building block of an
OPC link. This group is used to specify general channel properties, such as the identification attributes and
operating mode.
Identification
Name: User-defined identity of this channel. In each server project, each channel name must be unique.
Although names can be up to 256 characters, some client applications have a limited display window when
browsing the OPC server's tag space. The channel name is part of the OPC browser information. The prop-
erty is required for creating a channel.For information on reserved characters, refer to "How To... Properly Name a Channel, Device, Tag, and Tag
Group" in the server help.
www.ptc.com
6
Bristol/ IP Driver
Description: User-defined information about this channel.
Many of these properties, including Description, have an associated system tag.
Driver: Selected protocol / driver for this channel. This property specifies the device driver that was selected
during channel creation. It is a disabled setting in the channel properties. The property is required for cre-
ating a channel.Note: With the server's online full-time operation, these properties can be changed at any time. This
includes changing the channel name to prevent clients from registering data with the server. If a client has
already acquired an item from the server before the channel name is changed, the items are unaffected. If,
after the channel name has been changed, the client application releases the item and attempts to re-
acquire using the old channel name, the item is not accepted. With this in mind, changes to the properties
should not be made once a large client application has been developed. Utilize the User Manager to prevent
operators from changing properties and restrict access rights to server features.
Diagnostics
Diagnostics Capture: When enabled, this option makes the channel's diagnostic information available to
OPC applications allows the usage of statistics tags that provide feedback to client applications regarding
the operation of the channel. Because the server's diagnostic features require a minimal amount of over-
head processing, it is recommended that they be utilized when needed and disabled when not. The default is
disabled.Note: This property is not available if the driver does not support diagnostics.For more information, refer to "Communication Diagnostics" and "Statistics Tags" in the server help.
Channel Propert ies — Ethernet CommunicationsEthernet Communication can be used to communicate with devices.
Ethernet Settings
Network Adapter: Specify the network adapter to bind. When left blank or Default is selected, the oper-
ating system selects the default adapter.
Channel Propert ies — Write OptimizationsAs with any server, writing data to the device may be the application's most important aspect. The server
intends to ensure that the data written from the client application gets to the device on time. Given this goal,
the server provides optimization properties that can be used to meet specific needs or improve application
responsiveness.
www.ptc.com
7
Bristol/IP Driver
Write Optimizations
Optimization Method: Controls how write data is passed to the underlying communications driver. The
options are:
l Write All Values for All Tags: This option forces the server to attempt to write every value to the
controller. In this mode, the server continues to gather write requests and add them to the server's
internal write queue. The server processes the write queue and attempts to empty it by writing data
to the device as quickly as possible. This mode ensures that everything written from the client applic-
ations is sent to the target device. This mode should be selected if the write operation order or the
write item's content must uniquely be seen at the target device.
l Write Only Latest Value for Non-Boolean Tags: Many consecutive writes to the same value can
accumulate in the write queue due to the time required to actually send the data to the device. If the
server updates a write value that has already been placed in the write queue, far fewer writes are
needed to reach the same final output value. In this way, no extra writes accumulate in the server's
queue. When the user stops moving the slide switch, the value in the device is at the correct value at
virtually the same time. As the mode states, any value that is not a Boolean value is updated in the
server's internal write queue and sent to the device at the next possible opportunity. This can greatly
improve the application performance.
Note: This option does not attempt to optimize writes to Boolean values. It allows users to optimize
the operation of HMI data without causing problems with Boolean operations, such as a momentary
push button.
l Write Only Latest Value for All Tags: This option takes the theory behind the second optimization
mode and applies it to all tags. It is especially useful if the application only needs to send the latest
value to the device. This mode optimizes all writes by updating the tags currently in the write queue
before they are sent. This is the default mode.
Duty Cycle: is used to control the ratio of write to read operations. The ratio is always based on one read for
every one to ten writes. The duty cycle is set to ten by default, meaning that ten writes occur for each read
operation. Although the application is performing a large number of continuous writes, it must be ensured
that read data is still given time to process. A setting of one results in one read operation for every write
operation. If there are no write operations to perform, reads are processed continuously. This allows optim-
ization for applications with continuous writes versus a more balanced back and forth data flow.Note: It is recommended that the application be characterized for compatibility with the write optimization
enhancements before being used in a production environment.
Channel Propert ies — AdvancedThis group is used to specify advanced channel properties. Not all drivers support all properties; so the
Advanced group does not appear for those devices.
Non-Normalized Float Handling: A non-normalized value is defined as Infinity, Not-a-Number (NaN), or as
a Denormalized Number. The default is Replace with Zero. Drivers that have native float handling may
default to Unmodified. Non-normalized float handling allows users to specify how a driver handles non-nor-
malized IEEE-754 floating point data. Descriptions of the options are as follows:
www.ptc.com
8
Bristol/ IP Driver
l Replace with Zero: This option allows a driver to replace non-normalized IEEE-754 floating point val-
ues with zero before being transferred to clients.
l Unmodified: This option allows a driver to transfer IEEE-754 denormalized, normalized, non-num-
ber, and infinity values to clients without any conversion or changes.
Note: This property is not available if the driver does not support floating point values or if it only supports
the option that is displayed. According to the channel's float normalization setting, only real-time driver tags
(such as values and arrays) are subject to float normalization. For example, EFM data is not affected by this
setting.
For more information on the floating point values, refer to "How To ... Work with Non-Normalized Floating
Point Values" in the server help.
Inter-Device Delay: Specify the amount of time the communications channel waits to send new requests to
the next device after data is received from the current device on the same channel. Zero (0) disables the
delay.
Note: This property is not available for all drivers, models, and dependent settings.
Channel Propert ies — Communication Serializat ionThe server's multi-threading architecture allows channels to communicate with devices in parallel. Although
this is efficient, communication can be serialized in cases with physical network restrictions (such as Eth-
ernet radios). Communication serialization limits communication to one channel at a time within a virtual net-
work.
The term "virtual network" describes a collection of channels and associated devices that use the same
pipeline for communications. For example, the pipeline of an Ethernet radio is the master radio. All channels
using the same master radio associate with the same virtual network. Channels are allowed to communicate
each in turn, in a "round-robin" manner. By default, a channel can process one transaction before handing
communications off to another channel. A transaction can include one or more tags. If the controlling chan-
nel contains a device that is not responding to a request, the channel cannot release control until the trans-
action times out. This results in data update delays for the other channels in the virtual network.
Channel-Level Settings
Virtual Network: This property specifies the channel's mode of communication serialization. Options
include None and Network 1 - Network 500. The default is None. Descriptions of the options are as follows:
l None: This option disables communication serialization for the channel.
l Network 1 - Network 500: This option specifies the virtual network to which the channel is
assigned.
www.ptc.com
9
Bristol/IP Driver
Transactions per Cycle: This property specifies the number of single blocked/non-blocked read/write trans-
actions that can occur on the channel. When a channel is given the opportunity to communicate, this is the
number of transactions attempted. The valid range is 1 to 99. The default is 1.
Global Settings
l Network Mode: This property is used to control how channel communication is delegated. In Load
Balanced mode, each channel is given the opportunity to communicate in turn, one at a time. In Pri-
ority mode, channels are given the opportunity to communicate according to the following rules
(highest to lowest priority):l Channels with pending writes have the highest priority.
l Channels with pending explicit reads (through internal plug-ins or external client interfaces)
are prioritized based on the read's priority.
l Scanned reads and other periodic events (driver specific).
The default is Load Balanced and affects all virtual networks and channels.
Devices that rely on unsolicited responses should not be placed in a virtual network. In situations where
communications must be serialized, it is recommended that Auto-Demotion be enabled.
Due to differences in the way that drivers read and write data (such as in single, blocked, or non-blocked
transactions); the application's Transactions per cycle property may need to be adjusted. When doing so,
consider the following factors:
l How many tags must be read from each channel?
l How often is data written to each channel?
l Is the channel using a serial or Ethernet driver?
l Does the driver read tags in separate requests, or are multiple tags read in a block?
l Have the device's Timing properties (such as Request timeout and Fail after x successive timeouts)
been optimized for the virtual network's communication medium?
Channel Propert ies — Local PortThe Local Port property group specifies the port that all devices under the channel use for communications.
Local Port
l UDP Port : Specify the local port to which the channel is bound. The default for most Bristol devices is
1234. Changing the UDP Port may also require a change to the device configuration to communicate
with the port.
This driver supports additional channel properties. For more information, refer to "What is a Channel?" in the
server help file.
www.ptc.com
10
Bristol/ IP Driver
Device Setup
Supported Devices
l Network 3000 Series (DPC 33xx) devices with BSAP IP (Ethernet) support. 386EX Protected Mode
DPC3330 and DPC 3335 with PES03/PEX03 or newer Firmware is required.
l ControlWave devices with BSAP IP (Ethernet) support. ControlWave Micro CWP/LPS/CWR02.00 or
newer Firmware is required.
Communication ProtocolBristol BSAP IP Protocol (UDP)
Device Propert ies — GeneralA device represents a single target on a communications channel. If the driver supports multiple controllers,
users must enter a device ID for each controller.
Identification
Name: This property specifies the name of the device. It is a logical user-defined name that can be up to
256 characters long, and may be used on multiple channels.
Note: Although descriptive names are generally a good idea, some OPC client applications may have a
limited display window when browsing the OPC server's tag space. The device name and channel name
become part of the browse tree information as well. Within an OPC client, the combination of channel name
and device name would appear as "ChannelName.DeviceName".For more information, refer to "How To... Properly Name a Channel, Device, Tag, and Tag Group" in server
help.
Description: User-defined information about this device.
Many of these properties, including Description, have an associated system tag.
Channel Assignment : User-defined name of the channel to which this device currently belongs.
Driver: Selected protocol driver for this device.
Model: This property specifies the specific type of device that is associated with this ID. The contents of the
drop-down menu depends on the type of communications driver being used. Models that are not supported
by a driver are disabled. If the communications driver supports multiple device models, the model selection
can only be changed when there are no client applications connected to the device.Note: If the communication driver supports multiple models, users should try to match the model selec-
tion to the physical device. If the device is not represented in the drop-down menu, select a model that con-
forms closest to the target device. Some drivers support a model selection called "Open," which allows users
www.ptc.com
11
Bristol/IP Driver
to communicate without knowing the specific details of the target device. For more information, refer to the
driver help documentation.
ID: This property specifies the device's driver-specific station or node. The type of ID entered depends on
the communications driver being used. For many communication drivers, the ID is a numeric value. Drivers
that support a Numeric ID provide users with the option to enter a numeric value whose format can be
changed to suit the needs of the application or the characteristics of the selected communications driver.
The format is set by the driver by default. Options include Decimal, Octal, and Hexadecimal.Note: If the driver is Ethernet-based or supports an unconventional station or node name, the device's
TCP/IP address may be used as the device ID. TCP/IP addresses consist of four values that are separated by
periods, with each value in the range of 0 to 255. Some device IDs are string based. There may be additional
properties to configure within the ID field, depending on the driver. For more information, refer to the driver's
help documentation.
Operating Mode
Data Collection: This property controls the device's active state. Although device communications are
enabled by default, this property can be used to disable a physical device. Communications are not attemp-
ted when a device is disabled. From a client standpoint, the data is marked as invalid and write operations
are not accepted. This property can be changed at any time through this property or the device system tags.
Simulated: This option places the device into Simulation Mode. In this mode, the driver does not attempt to
communicate with the physical device, but the server continues to return valid OPC data. Simulated stops
physical communications with the device, but allows OPC data to be returned to the OPC client as valid data.
While in Simulation Mode, the server treats all device data as reflective: whatever is written to the simulated
device is read back and each OPC item is treated individually. The item's memory map is based on the group
Update Rate. The data is not saved if the server removes the item (such as when the server is reinitialized).
The default is No.Notes:
1. This System tag (_Simulated) is read only and cannot be written to for runtime protection. The System
tag allows this property to be monitored from the client.
2. In Simulation mode, the item's memory map is based on client update rate(s) (Group Update Rate for
OPC clients or Scan Rate for native and DDE interfaces). This means that two clients that reference
the same item with different update rates return different data.
Simulation Mode is for test and simulation purposes only. It should never be used in a production envir-
onment.
Device Propert ies — Scan ModeThe Scan Mode specifies the subscribed-client requested scan rate for tags that require device com-
munications. Synchronous and asynchronous device reads and writes are processed as soon as possible;
unaffected by the Scan Mode properties.
www.ptc.com
12
Bristol/ IP Driver
Scan Mode: Specifies how tags in the device are scanned for updates sent to subscribing clients. Descrip-
tions of the options are:
l Respect Client-Specified Scan Rate: This mode uses the scan rate requested by the client.l Request Data No Faster than Scan Rate: This mode specifies the value set as the maximum scan
rate. The valid range is 10 to 99999990 milliseconds. The default is 1000 milliseconds.
Note: When the server has an active client and items for the device and the scan rate value is
increased, the changes take effect immediately. When the scan rate value is decreased, the changes
do not take effect until all client applications have been disconnected.
l Request All Data at Scan Rate: This mode forces tags to be scanned at the specified rate for sub-
scribed clients. The valid range is 10 to 99999990 milliseconds. The default is 1000 milliseconds.
l Do Not Scan, Demand Poll Only: This mode does not periodically poll tags that belong to the
device nor perform a read to get an item's initial value once it becomes active. It is the client's
responsibility to poll for updates, either by writing to the _DemandPoll tag or by issuing explicit device
reads for individual items. For more information, refer to "Device Demand Poll" in server help.
l Respect Tag-Specified Scan Rate: This mode forces static tags to be scanned at the rate specified
in their static configuration tag properties. Dynamic tags are scanned at the client-specified scan
rate.
Initial Updates from Cache: When enabled, this option allows the server to provide the first updates for
newly activated tag references from stored (cached) data. Cache updates can only be provided when the
new item reference shares the same address, scan rate, data type, client access, and scaling properties. A
device read is used for the initial update for the first client reference only. The default is disabled; any time a
client activates a tag reference the server attempts to read the initial value from the device.
Device Propert ies — Auto-DemotionThe Auto-Demotion properties can temporarily place a device off-scan in the event that a device is not
responding. By placing a non-responsive device offline for a specific time period, the driver can continue to
optimize its communications with other devices on the same channel. After the time period has been
reached, the driver re-attempts to communicate with the non-responsive device. If the device is responsive,
the device is placed on-scan; otherwise, it restarts its off-scan time period.
Demote on Failure: When enabled, the device is automatically taken off-scan until it is responding again.Tip: Determine when a device is off-scan by monitoring its demoted state using the _AutoDemoted sys-
tem tag.
Timeouts to Demote: Specify how many successive cycles of request timeouts and retries occur before the
device is placed off-scan. The valid range is 1 to 30 successive failures. The default is 3.
www.ptc.com
13
Bristol/IP Driver
Demotion Period: Indicate how long the device should be placed off-scan when the timeouts value is
reached. During this period, no read requests are sent to the device and all data associated with the read
requests are set to bad quality. When this period expires, the driver places the device on-scan and allows for
another attempt at communications. The valid range is 100 to 3600000 milliseconds. The default is 10000
milliseconds.
Discard Requests when Demoted: Select whether or not write requests should be attempted during the
off-scan period. Disable to always send write requests regardless of the demotion period. Enable to discard
writes; the server automatically fails any write request received from a client and does not post a message
to the Event Log.
Device Propert ies — Tag GenerationThe automatic tag database generation features make setting up an application a plug-and-play operation.
Select communications drivers can be configured to automatically build a list of tags that correspond to
device-specific data. These automatically generated tags (which depend on the nature of the supporting
driver) can be browsed from the clients.
Not all devices and drivers support full automatic tag database generation and not all support the same data
types. Consult the data types descriptions or the supported data type lists for each driver for specifics.
If the target device supports its own local tag database, the driver reads the device's tag information and
uses the data to generate tags within the server. If the device does not natively support named tags, the
driver creates a list of tags based on driver-specific information. An example of these two conditions is as fol-
lows:
1. If a data acquisition system supports its own local tag database, the communications driver uses the
tag names found in the device to build the server's tags.
2. If an Ethernet I/O system supports detection of its own available I/O module types, the com-
munications driver automatically generates tags in the server that are based on the types of I/O mod-
ules plugged into the Ethernet I/O rack.
Note: Automatic tag database generation's mode of operation is completely configurable. For more inform-
ation, refer to the property descriptions below.
On Property Change: If the device supports automatic tag generation when certain properties change, the
On Property Change option is shown. It is set to Yes by default, but it can be set to No to control over when
tag generation is performed. In this case, the Create tags action must be manually invoked to perform tag
generation.
On Device Startup: This property specifies when OPC tags are automatically generated. Descriptions of the
options are as follows:
www.ptc.com
14
Bristol/ IP Driver
l Do Not Generate on Startup: This option prevents the driver from adding any OPC tags to the tag
space of the server. This is the default setting.
l Always Generate on Startup: This option causes the driver to evaluate the device for tag inform-
ation. It also adds tags to the tag space of the server every time the server is launched.
l Generate on First Startup: This option causes the driver to evaluate the target device for tag
information the first time the project is run. It also adds any OPC tags to the server tag space as
needed.
Note: When the option to automatically generate OPC tags is selected, any tags that are added to the
server's tag space must be saved with the project. Users can configure the project to automatically save
from the Tools | Options menu.
On Duplicate Tag: When automatic tag database generation is enabled, the server needs to know what to
do with the tags that it may have previously added or with tags that have been added or modified after the
communications driver since their original creation. This setting controls how the server handles OPC tags
that were automatically generated and currently exist in the project. It also prevents automatically gen-
erated tags from accumulating in the server.
For example, if a user changes the I/O modules in the rack with the server configured to Always Generate
on Startup, new tags would be added to the server every time the communications driver detected a new
I/O module. If the old tags were not removed, many unused tags could accumulate in the server's tag space.
The options are:
l Delete on Create: This option deletes any tags that were previously added to the tag space before
any new tags are added. This is the default setting.
l Overwrite as Necessary: This option instructs the server to only remove the tags that the com-
munications driver is replacing with new tags. Any tags that are not being overwritten remain in the
server's tag space.
l Do not Overwrite: This option prevents the server from removing any tags that were previously gen-
erated or already existed in the server. The communications driver can only add tags that are com-
pletely new.
l Do not Overwrite, Log Error: This option has the same effect as the prior option, and also posts an
error message to the server's Event Log when a tag overwrite would have occurred.
Note: Removing OPC tags affects tags that have been automatically generated by the com-
munications driver as well as any tags that have been added using names that match generated tags.
Users should avoid adding tags to the server using names that may match tags that are automatically
generated by the driver.
Parent Group: This property keeps automatically generated tags from mixing with tags that have been
entered manually by specifying a group to be used for automatically generated tags. The name of the group
can be up to 256 characters. This parent group provides a root branch to which all automatically generated
tags are added.
Allow Automatically Generated Subgroups: This property controls whether the server automatically cre-
ates subgroups for the automatically generated tags. This is the default setting. If disabled, the server gen-
erates the device's tags in a flat list without any grouping. In the server project, the resulting tags are named
with the address value. For example, the tag names are not retained during the generation process.Note: If, as the server is generating tags, a tag is assigned the same name as an existing tag, the system
automatically increments to the next highest number so that the tag name is not duplicated. For example, if
the generation process creates a tag named "AI22" that already exists, it creates the tag as "AI23" instead.
www.ptc.com
15
Bristol/IP Driver
Create: Initiates the creation of automatically generated OPC tags. If the device's configuration has been
modified, Create tags forces the driver to reevaluate the device for possible tag changes. Its ability to be
accessed from the System tags allows a client application to initiate tag database creation.Note: Create tags is disabled if the Configuration edits a project offline.
Device Propert ies — CommunicationThe Communication property group specifies the device's communication properties.
Communication
l RTU Global Address: This property specifies the hex address of the device. For Master devices, the
default setting is 0. For Slave devices, the default setting is non-zero. To find the address in OpenBSI
NetView, right-click on the device and select Properties | BSAP.
Note: Although Master devices can also have a non-zero global address, users should follow con-
vention and use the zero global address for communications.
l RTU IP Address: This property specifies the IP address of the RTU. For Master devices, this is the IP
of the Master. For Slave devices, this is the IP of the Master.
Note: In the BSAP IP protocol, the Master device passes requests to the Slaves using the Global
Address.
l RTU UDP Port Number: This property specifies the port number of the Master device. For Slave
devices, this is the port number of the Master.
l Maximum Bytes Per Request : This property specifies the maximum number of bytes that will be
sent to the device per request. The amount specified should depend on the device's bandwidth and
performance requirements.
Note: If communications with a device are fast and bandwidth is available, users should specify a
larger number of bytes per request. If communications are slow or bandwidth is limited, users should
specify a smaller amount of bytes per request.
Device Propert ies — TimingThe Timing group controls the device's timeout properties.
www.ptc.com
16
Bristol/ IP Driver
Level: Specify the device's network level. The valid range is 1 to 6. The default is 1.
Note: Level One devices are Masters and have a Global Address of 0. Level Two devices are Slaves. Level
Three devices are Slaves of Slaves. The higher the level, the more latency when communicating with the
device. This setting updates the "Request timeout" property.
Request Timeout : Specify the number of milliseconds that the driver will wait for a response from the
device. The default is 1000 milliseconds.
Note: If a response is not received within this period, the driver will resend the request depending on the
"Fail after successive timeouts" property. If the driver receives a malformed response, it will resend the
request right away. Failure recovery improves when the device sends a valid response that is corrupted by
network noise.
Fail After Successive Timeouts: Specify how many request timeouts can occur before the request is failed.
The valid range is 1 to 10. The default is 3.
Device Propert ies — Tag Import Propert iesThe Tag Import Properties property group specifies the tag import file that will be used in automatic tag gen-
eration.
Tag import file: Specify the device's tag import file. It must be a valid signal (* .sig) file.
For more information, refer to Automatic Tag Generation.
Device Propert ies — Redundancy
Redundancy is available with the Media-Level Redundancy Plug-In.Consult the website, a sales representative, or the user manual for more information.
www.ptc.com
17
Bristol/IP Driver
Optimizing CommunicationsThis driver supports communications with underlying BSAP child devices through a Master Ethernet device.
Due to the nature of the BSAP protocol, communications to lower-level BSAP devices may be slower. As
such, users may need to make special design considerations in the server configuration to attain optimal
communication performance.
Channel and Device SetupCommunication to multiple devices on a channel is serialized. When communications with one device is
slow, the performance of the other devices on the channel will decrease. To avoid degradation in per-
formance, users can place slower devices on separate channels.
Note: Devices located on a common BSAP level should be grouped under the same channel in the server.
Multi-Home NICSeparating devices onto different channels effectively improves performance, but is limited in that each
channel requires a unique port and NIC combination. To eliminate the limitation, users can multi-home an
NIC card and bind multiple channels to the same port.
Request SizeThe device's Request Size directly impacts performance. For maximum performance, 256 bytes is generally
recommended; however, a lower request size may increase performance in situations where bandwidth is
limited. Lower request sizes are also generally recommended for non-Master devices. The valid range is 64
to 256 bytes.
Request FrequencyFrequently asking slower devices for data will slow down a channel's communications. To better control this,
users can limit the rate at which data is requested from the device with the Scan Mode property.
Cached DataThe Bristol IP Driver does not maintain cached tag data after the client removes the tag from the server.
Every time the server adds or re-adds a tag on behalf of the requesting client, the server will request the
data from the device and send it to the client. This behavior ensures data freshness. Applications that
require the reading of cached values should do so at the client level. Techniques for caching are as follows:
1. Have the client add the tag as inactive. Then, perform reads when fresh data is needed.
2. Have the client add the tag as active and configure the device's Scan Mode property to poll the
device. Then perform cached reads when data is needed.
Data Types Descript ion
Data Type Descript ion
Boolean 1 byte
Float 4-byte floating point
String Zero-terminated ASCII character array
www.ptc.com
18
Bristol/ IP Driver
Address Descript ionsBristol addresses depend on the model. For more information, refer to the subtopics below.
Network 3000 Series DevicesThe syntax for Network 3000 Series devices is as follows: <Base>.<Ext>.<Att>.
l Base: This element must be 1 to 8 characters in length and begin with a letter or pound sign (#). The
remaining characters will consist of letters and numbers.
l Ext : This element must be 0 to 6 characters in length, and consist of letters or numbers.
l Att : This element must be 0 to 4 characters in length, and consist of letters or numbers.
Note: An example of the syntax is "#DIAL.001.Val".
ControlWave DevicesThe syntax for ControlWave devices is as follows: <Access>.<Signal Name>.
l Access: This element is the Bristol program name for local variables (or "%GV" for global and system
variables).
l Signal Name: This element must contain letters, numbers, or a period and start with a letter or
underscore. Signal names that start with an underscore are system variables.
Note: An example of the syntax is "%GV.MYSIGNAL".
www.ptc.com
19
Bristol/IP Driver
Error Descript ionsThe following messages may be generated. Click on the link for a description of the message.
<Operat ion> on device <device name> signal <signal> caused an overflow. Some data has
been lost .
<Operat ion> on device <device name> signal <signal> failed. The device does not contain
this signal.
<Operat ion> on device <device name> signal <signal> failed. The device requires higher
level permissions to perform this operat ion.
<Operat ion> on device <device name> signal <signal> failed. The request was malformed
or incomplete.
A read by address failed because the M SD version for device <device name> changed.
The driver is sending read by name requests to get the updated M SD version from the
device.
A write by address failed because the M SD version for device <device name> changed.
The driver is sending a write by name request to the device.
Failed to send a request to device <device>. The device is not communicat ing.
Failed to send a request to device <device>. The packet is malformed or too large.
Failed to stop Winsock communicat ions.
Failure to init iate 'winsock.dll' [Error:<error>].
Invalid BSAP funct ion.
Read failed on device <device> address <address>. The server expects this address to be
of type <type>, but it is of type <type> in the device.
The response received from device <device> contains an invalid sequence number.
Review t iming propert ies.
The response received from device <device> is malformed.
The response received from device <device> is too large (%<count> bytes). The data is
lost .
The signal was not found.
The string writ ten to device <device>, address <address> is too long. The max supported
string is <count> characters. The write will cont inue as is, but the device will t runcate
the value.
Unable to bind to port <port> on Channel <channel>.
Unable to create a socket connect ion for Channel <channel>.
Unable to generate a tag database for device <device name>. Reason: Import file does
not contain any valid signals.
Write to device <device name> signal <signal> failed. The signal's manual inhibit at t rib-
ute is set to false, not allowing writes.
Write to device <device name> signal <signal> failed. The signal is read only.
Write to device <device name> signal <signal> failed. The write value is invalid. M ake
sure the value is within the approved BSAP range.
www.ptc.com
20
Bristol/ IP Driver
<Operation> on device <device name> signal <signal> caused an overflow.Some data has been lost.
Error Type:Error
Possible Cause:A read or write operation on a signal caused a data overflow. The operation completed, but only part of the
data was read or written to the device.
Solution:
1. If writing data to the device, verify that the data is in the correct format for the data type.
2. Verify that the String being written to the device is within the 64 character limit and is null terminated.
Note: Boolean Tags take up one byte, Float Tags take up four bytes, and String Tags can be up to 64 char-
acters (and must be null terminated).
<Operation> on device <device name> signal <signal> failed. The devicedoes not contain this signal.
Error Type:Error
Possible Cause:
1. An operation was performed on a signal that is not in the device.
2. An attempt was made to write an out-of-range value to a tag in a ControlWave device.
Solution:
1. Check the tag address, and ensure that it matches the signal name in the device.
2. Check the data type of the tag in the ControlWave device. Then, ensure the value that will be written
is within the range of values for that data type.
<Operation> on device <device name> signal <signal> failed. The devicerequires higher level permissions to perform this operation.
Error Type:Error
Possible Cause:The device does not have sufficient permissions to perform the operation.
Solution:Check the permission settings for the signal in the device configuration. Then, ensure that the signal allows
the operation to be performed with the highest level of permissions.
www.ptc.com
21
Bristol/IP Driver
Note: The permission level is sent by the driver as part of the request, and is set to the highest level by
default. This error is uncommon.
<Operation> on device <device name> signal <signal> failed. The requestwas malformed or incomplete.
Error Type:Error
Possible Cause:
1. The driver is attempting to communicate with a device that is not supported.
2. Communications between the driver and device are noisy and causing malformed packets.
Solution:
1. Ensure that the device with which the driver is communicating is supported.
2. Ensure that the communication line between the driver and device is reliable.
Note: This error may indicate a problem in the driver. If the solutions listed above fail, contact Technical
Support.
A read by address failed because the MSD version for device <devicename> changed. The driver is sending read by name requests to get theupdated MSD version from the device.
Error Type:Warning
Possible Cause:A configuration change occurred in the device that caused the MSD version to update. This changed the
MSD address for all signals and caused the read to fail.
Solution:The driver will reissue the read as a read-by-name and will automatically update the MSD information. No
action is necessary.
Note: It is not recommended that configuration changes be made to the physical device while the driver is
connected and receiving data. Users should disconnect the driver, make the configuration changes, and
reconnect.
A write by address failed because the MSD version for device <devicename> changed. The driver is sending a write by name request to thedevice.
Error Type:Warning
Possible Cause:
www.ptc.com
22
Bristol/ IP Driver
A configuration change occurred in the device that caused the MSD version to update. This changed the
MSD address for all signals and caused the write to fail.
Solution:The driver will reissue the write as a write-by-name. This will complete the write, but will not update the
device's MSD information. Future writes will be write-by-name until a read occurs.
Note: It is not recommended that configuration changes be made to the physical device while the driver is
connected and receiving data. Users should disconnect the driver, make the configuration changes, then
reconnect.
Failed to send a request to device <device>. The device is not com-municating.
Error Type:Error
The communication timed out.
Possible Cause:
1. The device is offline or the driver is not configured to communicate with the device properly.
2. The device is not supported.
Solution:
1. Ensure that the device can be reached by the driver by attempting to ping the device's IP address.
2. Ensure that the device is supported.
Failed to send a request to device <device>. The packet is malformed ortoo large.
Error Type:Error
Possible Cause:
1. The driver is attempting to communicate with a device that is not supported.
2. Communications between the driver and device are noisy and are causing malformed packets.
3. The driver is attempting to write to a tag whose address length plus data length exceeds the max-
imum message size that is supported by the Bristol BSAP IP protocol.
Solution:
1. Ensure that the device with which the driver is communicating is supported.
2. Ensure that the communication line between the driver and device is reliable.
www.ptc.com
23
Bristol/IP Driver
3. Perform a device read on the tag, then attempt a write. If the error persists, shorten the address in
the device and then try again.
Note: This error may indicate a problem in the driver. If the solutions listed above fail, contact Technical
Support.
Failed to stop Winsock communications.
Error Type:Error
Winsock was placed in an invalid state. This may cause the next startup to fail.
Possible Cause:
1. Failed to cleanup Winsock while the driver was shutting down.
2. Winsock was never initialized.
3. A blocking socket call was in progress while the driver was shutting down.
Solution:
1. Restart the server and connect to a Bristol device.
2. Ensure that the operating system has the latest patches.
Failure to init iate 'winsock.dll' [Error:<error>].
Error Type:Error
The driver cannot communicate over Ethernet without Winsock.
Possible Cause:
1. The underlying system is not ready to initialize network communications.
2. The version of Winsock requested is not supported.
3. A Winsock operation is already in progress.
Solution:
1. Restart the server.
2. Ensure that the operating system has the latest patches.
Invalid BSAP function.
Error Type:Error
www.ptc.com
24
Bristol/ IP Driver
Possible Cause:
1. The BSAP function code sent to the device is invalid. The operation failed.
2. The device is not officially supported. The operation failed.
3. Communications between the driver and device are unreliable. The operation failed.
Solution:
1. Ensure that the device is supported.
2. Ensure that the communication line between the driver and device is reliable.
Read failed on device <device> address <address>. The server expects thisaddress to be of type <type>, but it is of type <type> in the device.
Error Type:Error
Possible Cause:The client requested a Float Tag, but the actual type is a String. The tag read failed and the tag was set to
Bad quality.
Solution:For Static Tags, match the client-requested type to the device type by changing the tag type in the con-
figuration. For Dynamic Tags, the client must change the request type.
Note: This error can occur any time that the client type does not match the device type. The device read
succeeds, but the server cannot convert the device type to the client type.
The response received from device <device> contains an invalid sequencenumber. Review timing propert ies.
Error Type:Warning
Possible Cause:A response was received from the device, but the sequence number in the response packet does not match
the sequence number issued in the request.The response will be ignored. The driver will continue waiting for a valid response (depending on the Timing
properties specified in Device Properties).
Solution:
1. Increase the value specified in the device's Request Timeout property.
2. Increase the value specified in the device's Fail After Successive Timeouts property.
The response received from device <device> is malformed.
Error Type:
www.ptc.com
25
Bristol/IP Driver
Error
Possible Cause:
1. The device is not supported. The response will be ignored. A new request will be sent, depending on
the device's timeout configuration.
2. The communications line between the driver and the device is unreliable.
Solution:
1. Ensure that the device is supported.
2. Verify that the communication line between the driver and device is reliable.
The response received from device <device> is too large (%<count> bytes).The data is lost.
Error Type:Error
Possible Cause:The size of the device’s response is too large for the driver. The driver ignored the response.
Solution:
1. Ensure that the device with which the driver is communicating is supported.
2. Limit the size of the requests by changing the Maximum Bytes Per Request property. This will also
limit the size of the response.
Note: This error is uncommon.
The signal was not found.
Error Type:Error
Possible Cause:The signal was not in the device. The operation on the signal failed.
Solution:Check the device configuration and ensure that the signal is in the device and matches the tag address.
The string written to device <device>, address <address> is too long. Themaximum supported string is <count> characters. The write will continueas is, but the device will truncate the value.
Error Type:Warning
www.ptc.com
26
Bristol/ IP Driver
Possible Cause:The String being written to the device is too large. The device ignored the excess characters in the String or
ignored the write entirely.
Solution:Check the maximum String size allowed for the address in the device. Then, ensure that the write does not
exceed this size.
Note: The default String size is 64 characters (including the null terminator).
Unable to bind to port <port> on Channel <channel>.
Error Type:Error
Possible Cause:The port is already in use or is unavailable. There are no communications on the channel.
Solution:Verify that no other processes are using the port and Network Interface Controller. To do so, run the "net-
stat" command in Windows. Then, change the port or network interface if possible.
Note: This error is most common in cases where channels have duplicate Network Interface Controllers
and ports. This can occur between any channels; it is not limited to channels for this driver. Other programs
on the machine can also be using the port.
Unable to create a socket connection for Channel <channel>.
Error Type:Error
Possible Cause:While initializing a channel, the driver failed to get a valid socket from the system.There are no communications on the channel.
Solution:Restart the server or reconnect the clients.
Note: This failure usually indicates that there is something wrong with the system (which could be out of
sockets or in a Bad state).
Unable to generate a tag database for device <device name>. Reason:Import file does not contain any valid signals.
Error Type:Error
Possible Cause:A corrupted .sig file was imported. The tag database was not generated.
Solution:
www.ptc.com
27
Bristol/IP Driver
Verify that the .sig file is valid. Then, re-import the file.
Write to device <device name> signal <signal> failed. The signal's manualinhibit attribute is set to false, not allowing writes.
Error Type:Error
Possible Cause:The signal is configured not to allow manual changes during Runtime; as such, write operations are also not
allowed.
Solution:Check the device configuration's manual inhibit setting for the signal, then change it accordingly. Users may
want to change the Server Tag's access to read only.
Write to device <device name> signal <signal> failed. The signal is readonly.
Error Type:Error
Possible Cause:The driver attempted to write to a device signal that is read only.
Solution:Check the device configuration to see if the signal is read only. If it is, then change the server tag to read
only. This will cause the server to stop writes before they make it to the device.
Write to device <device name> signal <signal> failed. The write value isinvalid. Make sure the value is within the approved BSAP range.
Error Type:Error
Possible Cause:
1. The String, Float, or Boolean written to the device is malformed or is too large.
2. The type being written is different than the device data type (such as when writing a String to a Float
signal).
Solution:
1. Ensure that the signal data type in the device matches the write.
2. If the signal is a String, ensure that the length does not exceed the device's 64-character limitation
and is null terminated.
www.ptc.com
28
Bristol/ IP Driver
Appendix: Tag GenerationThe Bristol IP Driver can automatically generate tags using a signal (* .sig) file, which is created by Bristol
OpenBSI software. The procedure for creating the signal file is different for DPC 33xx devices and Con-
trolWave devices.
DPC33xx Devices
1. To start, open the ACCOL Workbench. Then, define a signal.
2. In Signal Properties, ensure that Mark as Global is enabled.
3. Next, launch the BBI Signal Extraction Utility. Then, locate Mark All Signals as Alarms and
ensure that it is disabled.
4. In Load File, browse for and specify the load file.
5. In Output File, browse for and specify the output file.
6. Once finished, click Start to extract the signals.
ControlWave Devices
www.ptc.com
29
Bristol/IP Driver
1. To start, open ControlWave Designer. Then, ensure that the OPC column property box is enabled
for all signals that will be exported.
2. Next, open the controller's Resource Properties.
3. Locate PDD, then ensure that the Marked Variables property is enabled.
www.ptc.com
30
Bristol/ IP Driver
Note: All Global Variables is optional.
4. Once finished, click OK.
5. Choose Start| All Programs| OpenBSI Tools| Common Tools| Signal Extractor.
6. Select the Browse (...) button next to the "Load File:" and locate and select the .mwt project with the
tags
7. If desired, select a different output directory by using the Browse (...) button next to the "Output File:"
and locate the desired location
8. Select Start and the tag file is exported to the selected folder.
9. Place the exported signal file where the server can access it.
10. Enter the signal file into the "Tag import file" field in the Tag Import Properties property group of
the device properties.
11. The signals can now be created with the database creation functionality.
www.ptc.com
31
Bristol/IP Driver
Index
A
A read by address failed because the MSD version for device <device name> changed. The driver is send-
ing read by name requests to get the updated MSD version from the device. 22
A write by address failed because the MSD version for device <device name> changed. The driver is send-
ing a write by name request to the device. 22
Address Descriptions 19
Allow Sub Groups 15
Auto-Demotion 13
Automatic Tag Generation 29
B
BSAP Networks 5
C
Channel Assignment 11
Channel Setup 6
Communication 16
Create 16
D
Data Collection 12
Data Types Description 18
Delete 15
Demote on Failure 13
Demotion Period 14
Device Properties — Tag Generation 14
Discard Requests when Demoted 14
Do Not Scan, Demand Poll Only 13
Driver 11
www.ptc.com
32
Bristol/ IP Driver
E
Error Descriptions 20
F
Failed to send a request to device <device>. The device is not communicating. 23
Failed to send a request to device <device>. The packet is malformed or too large. 23
Failed to stop Winsock communications. 24
Failure to initiate winsock.dll [Error <error>]. 24
G
General 11
Generate 15
I
ID 12
Identification 11
Initial Updates from Cache 13
Invalid BSAP function. 24
L
Local Port 10
M
Model 11
N
Name 11
www.ptc.com
33
Bristol/IP Driver
O
On Device Startup 14
On Duplicate Tag 15
On Property Change 14
Operating Mode 12
Operation on device <device name> signal <signal> caused an overflow. Some data has been lost. 21
Operation on device <device name> signal <signal> failed. The device does not contain this signal. 21
Operation on device <device name> signal <signal> failed. The device requires higher level permissions
to perform this operation. 21
Operation on device <device name> signal <signal> failed. The request was malformed or
incomplete. 22
Optimizing Communications 18
Overview 4
Overwrite 15
P
Parent Group 15
R
Read failed on device <device> address <address>. The server expects this address to be of type <type>,
but it is of type <type> in the device. 25
Redundancy 17
Respect Tag-Specified Scan Rate 13
S
Scan Mode 13
Setup 11
Simulated 12
T
Tag Generation 14
Tag Import Properties 17
The response received from device <device> contains an invalid sequence number. Review timing prop-
erties. 25
www.ptc.com
34
Bristol/ IP Driver
The response received from device <device> is malformed. 25
The response received from device <device> is too large (%<count> bytes). The data is lost. 26
The signal was not found. 26
The string written to device <device>, address <address> is too long. The max supported string is
<count> characters. The write will continue as is, but the device will truncate the value. 26
Timeouts to Demote 13
Timing 16
U
Unable to bind to port <port> on Channel <channel>. 27
Unable to create a socket connection for Channel <channel>. 27
Unable to generate a tag database for device <device name>. Reason - Import file does not contain any
valid signals. 27
W
Write to device <device name> signal <signal> failed. The signal's manual inhibit attr ibute is set to false,
not allowing writes. 28
Write to device <device name> signal <signal> failed. The signal is read only. 28
Write to device <device name> signal <signal> failed. The write value is invalid. Make sure the value is
within the approved BSAP range. 28