Upload
others
View
0
Download
0
Embed Size (px)
Citation preview
BREATHING LIFE INTO YOUR BUILDING
ACB46, ACB46HACTIVE CHILLED BEAMS
––PRODUCT INFORMATION
Dadanco participates in the ECC programfor the full range of the active chilled beams.
02 | DADANCO | ACTIVE CHILLED BEAMS ACB46
ACB46 2-way active chilled beams incorporate new patented technologies to deliver a breakthrough for higher energy effi ciency perimeter and centre zone air conditioning using lower air quantities.
Dadanco active chilled beams are fully tested to EN15116 to provide effi cient, effective and whisper-quiet air conditioning for almost any application, delivered with comfort in mind in accordance with ISO7730:2005.
ACB46 incorporates 2-way supply air discharge with one
piece perforated return air grille and a single horizontal
secondary cooling coil.
By controlled air volume, pressure and nozzle confi guration,
the primary air generates a low pressure zone above the
cooling coil, inducing warm room air through the coil,
which cools, mixes with the primary air giving an output of
approximately 4 l/s through the air discharge slots below the
beam for every 1l/s of primary air from the main ductwork.
This combined air gently and quietly enters the space,
using the Coanda effect to travel across the ceiling before
diffusing into the occupied zone at low velocity.
ADVANTAGES OF ACTIVE CHILLED BEAMS• Supply cooling, heating and the outdoor air required
for ventilation in the conditioned space.
• Compact dimensions and intrinsically smaller duct sizes
than air based systems offer real savings in ceiling space
requirements for HVAC new construction and
refurbishment projects.
• Lower fan energy required – By effi cient use of the
secondary cooling using chilled water with far higher
thermal capacity than air as the cooling medium. The
quantity of conditioned primary air delivered at pressures
from 70-120Pa is far lower than all air based systems.
The primary air is typically only 25-30% of the total
air supplied by ACB46 units due to the use of effi cient
induction technology to recycle and cool room air.
• Secondary air is induced over the secondary heat
exchanger due to carefully controlled nozzle velocities,
delivering localized cooling driven by air volume/pressure
with no additional fan energy required.
• ACB46 active chilled beams provide 2-way supply air
distribution for perimeter or internal zone applications.
• ACB46 active chilled beams are designed for ‘Lay-In’
installation in ceiling tile systems or in plasterboard
ceilings with builders’ ceiling frames.
• ACB46 active chilled beams deliver more cooling capacity
using less treated air than any all-air system.
• Active chilled beams offer 2-stage capacity control
through control of secondary water fl ow separate from
primary air control.
• Noise radiated from Dadanco active chilled beams is
typically <40dB(A)
• Active chilled beams require minimal maintenance
(no moving parts).
GENERAL INFORMATION––ACB46 ACTIVE CHILLED BEAMS
03 | DADANCO | ACTIVE CHILLED BEAMS ACB46
APPLICATION DATA – ACB46Cooling
Length
Width
Height
Air Connection
Water Connection
Plenum Chamber
Return Air Grille
40 to 167 W/m2
Up to 2400mm available on request for
any application.
600mm
281mm
150mm or 200mm diameter - Side or
End entry primary air connections
2 pipe or 4 pipe, 12.7mm tails or
½” BSP Taper fi ttings (male)
Thermal insulation for the primary
air plenum is available as an
optional extra.
2-way discharge supply air grille with
dot perforated centre return air grille/
underplate, as a one piece hinged for
coil access. A lint screen fi tted in the
return air grille/underplate is available
as an optional extra.
APPLICATIONSACB46 active chilled beams are suitable for perimeter
or internal zone in-ceiling installations and by attaching
Coanda wings can be used in exposed free
hanging installations:
• Commercial offi ce buildings
• HVAC new construction & refurbishment projects
• Schools and institutional buildings
04 | DADANCO | ACTIVE CHILLED BEAMS ACB46
TYPICAL ACB46 AIR DISTRIBUTION The 2-way discharge air fl ow characteristics of active
chilled beam ACB46, created by the induction of secondary
air through the centre of the unit. This produces a unique
air fl ow pattern resulting in thorough purging of air in the
occupied space compared to most conventional all-air
diffusion characteristics.
At an induction ratio of approximately 3:1, the mixed
primary air and cooled room air gently and quietly re-enters
the space by Coanda across the ceiling.
Low terminal air velocities are targeted for the occupied
zone of <0.25m/s to meet standard comfort criteria
specifi ed in ISO7730:2005.
0.05 0.125 0.2 0.275 0.35 0.425 0.5
Velocity (m/s)
6m
2.4m
1.8m
05 | DADANCO | ACTIVE CHILLED BEAMS ACB46
GENERAL PRODUCTTECHNICAL DATA
EUROVENT CERTIFIED PRODUCT TO RATING STANDARD EN15116
ACB46 2-Way Discharge Active Chilled Beam
Unit SetupACB46-450
ACB46H-450ACB46-750
ACB46H-750ACB46-1050
ACB46H-1050ACB46-1350
ACB46H-1350ACB46-1650
ACB46H-1650ACB46-2250
Grille Face Size 600 x 600mm 600 x 900mm 600 x 1200mm 600 x 1200mm 600 x 1800mm 600 x 2400mm
Active Coil Length 450mm 750mm 1050mm 1350mm 1650mm 2250mm
Primary Air Range ≤125Pa 7 - 18 L/s 10 - 23 L/s 20 - 30 L/s 28 - 36 L/s 30 - 45 L/s 45 - 60 L/s
Optimum Nozzles 32SN 40SN 52SN 62SN 76SN 106SN
Cooling Rating 600W 850W 1150W 1350W 1750W 2300W
NOTES
1. Nominal cooling capacities based on 24°C room air, 14°C primary air, 14°C entering secondary water temperature and secondary water fl ow rate to achieve best output at <20kPa coil pressure drop minimum water fl ow = 0.03 L/s.
2. Primary air volumes are limited to <25l/s/m of beam to offer high thermal comfort levels in accordance with ISO 7730:2005 PPD<15%. Higher air volumes will give higher cooling outputs but at elevated high draft risk exceeding 0.25m/s in the occupied zone, PPD>15%.
3. General application primary air pressure <125Pa.
4. Different performance results can be achieved for varying secondary water fl ow rates, entering water temperatures, primary air conditions and primary air pressures.
5. For selections at conditions and unit sizes other than those above please contact Reece HVAC for further assistance.
PATENT PROTECTED TECHNOLOGYDadanco Starline™ multi-lobe high performance induction
nozzles and superior fl uid dynamics design are combined
into the new ACB46 active chilled beams for improved
performance and lower noise characteristics.
Rather than relying on natural convection as with passive
chilled beams, ACB46 active chilled beams use primary
air to deliver ventilation air and induce secondary room
air through the secondary cooling coil within the unit.
This delivers an enhanced performance in either a ceiling
mounted package or a fully exposed, free hanging package.
EUROVENT APPROVED TEST FACILITYDadanco headquarters in Adelaide also offers the ability to
fully test and validate beam performance in their state of the
art test facility, to show performance in the specifi c design
conditions to be used at site.
Eurovent approvals confi rm the cooling outputs as per
the calculation tool; this additional testing is to show
performance within the design environment.
06 | DADANCO | ACTIVE CHILLED BEAMS ACB46
PRODUCT DETAILSACB46
DIMENSIONSStandard ACB46 active chilled beams are dimensioned as below based on coil length to determine overall length.
Nominal Length “L” (mm) Active Coil Length (mm) Outside Face Length (mm) Unit Weight (kg)
600 450 595 9
900 750 895 15
1200 1050 1195 26
1800 1650 1795 38
2400 2250 2395 50
2-PIPE COOLING COIL CONFIGURATION
STANDARD FEATURES• Vertical water outlets
• One piece perforated return air grille
• 150mm round primary air spigot
• Interpon MA124A “Satin White” powder coated fi nish
4-PIPE COOLING COIL CONFIGURATION
OPTIONAL FEATURES• Insulated air plenum
• 200mm ovalised primary air spigot
• Lint screen
• Other colours are available upon request at extra cost
593 593
333
375
21
375
8282 103
282 282
70
70
70
70
24 24
70333
07 | DADANCO | ACTIVE CHILLED BEAMS ACB46
AIRSIDE AND WATERSIDE CONFIGURATIONS• Side entry primary air – 150mm
diameter round spigot, left or right
hand waterside fi ttings as viewed
from primary air spigot side.
• Side entry primary air – 200mm
diameter ovalised spigot,
left or right hand waterside
fi ttings as viewed from
primary air spigot side.
• Waterside connections can be
12.7mm plain tails or with ½” BSP
Taper fi ttings (male).
Ø150 SPIGOT
1/2” BSP MALE
FLAT FACE
TAPERED THREAD
134134
90130
5151 5151
23
08 | DADANCO | ACTIVE CHILLED BEAMS ACB46
GUIDE SPECIFICATIONACB46
SCOPEProvide Dadanco 2-way discharge ACB46, ceiling integrated Active Chilled Beam units, fi tted with
low noise, high effi ciency patented STARLINE™ nozzles, with capacities as listed in the equipment
schedule. The confi guration of the units is shown on the drawings.
INSTALLATIONTo ensure the performance of the active chilled beam, allow for the following:
• Ensure the unit is mounted level and
secure from independent suspension
materials (by others). It must not be
supported from the ceiling system.
• Connect the main primary air duct
using a short length of fl exible
ductwork (not included), one size
larger than the 150mm diameter or
200mm diameter ovalised duct, as
straight as possible or with gentle
radius bends, make all joints air tight.
• If the air coil is equipped with four
pipe tails then connect the outer
pipes to the secondary chilled water
fl ow (CHW) and return piping (by
others).
• If required, connect the inner two
pipe tails to the heated water (HTW)
fl ow and return piping.
CONSTRUCTIONCasing to be from 0.8mm galvanised steel panels to provide
a compact unit with a primary air plenum, secondary air
cooling coil, 2 entrainment and discharge chambers and
mounting provision.
Plenum; Fit 2 rows of the specifi ed number and size of
STARLINE™ induction nozzles to the primary air plenum
to discharge into the air entrainment chambers. Provide a
round 150mm diameter / ovalised 200mm diameter sheet
metal spigot located centrally on the long side of the
primary air plenum, to permit connection of the primary air
Bradfl o™ fl exible ductwork to the unit plenum.
If primary air temperatures are selected below CBCA* limits
of 14°C (which is not recommended), plenum insulation is
available as a self-adhesive, fi re retardant thermal insulation
applied on the inside of the primary air plenum to prevent
condensation forming on the outer casing of the unit.
Nozzles; Fit multi lobed patented STARLINE™ induction
nozzles of pliable fi re retardant polymer, designed for low
noise generation and rapid secondary air entrainment.
Provide the number and size of nozzles required to provide
the primary airfl ow capacity for each unit as specifi ed, to
achieve the primary (airside) sensible cooling.
Secondary Cooling Coil; Fit a single 2 row (2 pipe or 4
pipe) secondary air cooling coil of the specifi ed length
as required to achieve the specifi ed sensible secondary
(waterside) cooling capacity. Coils shall be constructed of
galvanised steel end plates and frames, with ½” copper
tubes mechanically expanded into 0.145mm thickness
rippled edge aluminium fi ns. Provide either plain 12.7mm
copper tails or ½” BSP male fl at face tapered thread fi ttings
for CHW coil connections. Tails/fi ttings are to be in a vertical
arrangement to ensure no water pipes or connections
overhang the overall length and width dimension of the unit.
Pressure testing; Coil shall be factory pressure tested to
25 bar (2500kPa) with an advisory operating pressure of
16 bar (1600kPa).
Grille; Provide an integral powder coat satin white fi nished
dot perforated return air grille for each unit placed centrally
to form 2 linear discharge slots along each longitudinal side.
The grille is to be hinged on one side, retained on the other,
to allow the under plate to be swung down for coil cleaning
and access to the optional lint screen (if selected).
The unit shall incorporate a commissioning tube to measure
the static pressure in the plenum, made from fl exible clear
plastic tube, sealed air tight to the plenum casing and
accessible from below for commissioning purposes.
Lint Screen; If selected fi tted to the frame of the secondary
heat exchanger above the open able return air grille. This is
to be fabricated from fi ne plastic fi bre mesh secured onto a
rectangular aluminium extrusion frame. This is secured with
fi xing clips to the secondary coil frame.
*Chilled Beam and Ceiling Association
09 | DADANCO | ACTIVE CHILLED BEAMS ACB46
HEALTHCARE ACTIVE CHILLED BEAMS - ACB46H
HINGED COILSuitable for use in non-invasive areas in healthcare applications, Dadanco have a sealed, closed case
solution with drop down battery feature to facilitate cleaning during the routine annual deep clean operations
seen in hospitals and other healthcare institutions.
For use in all areas except for invasive treatment rooms, active chilled beams are the obvious long life choice
for cooling, heating and ventilation requirements offering the best indoor comfort climate available at the point
where it is needed most.
Key Features
• Lowest energy consumption HVAC system
for Healthcare use.
• Low air velocities in the occupied zone.
• Whisper quiet operation.
• Sealed casing ensuring no uncontrolled void
air contamination into the space below.
• Drop down battery feature for cleaning;
- To vacuum the fi ncoil battery.
- To wipe down internal surfaces.
Previous Healthcare Projects
• St John of God Hospital, Perth
• Mercy Hospital, Melbourne
• Geelong Hospital, Geelong
• Queensland Children’s Hospital, Brisbane
• Mt Isa Hospital, QLD
• Fiona Stanley Hospital, Perth
• Royal Hobart Hospital, Tasmania
• Midland Health Campus, WA
Lower the openable
grille plate/underplate
Pivot the drop down battery to access
all sides for vacuum cleaning and casing wipe
down
10 | DADANCO | ACTIVE CHILLED BEAMS ACB46
EXPOSED CEILINGSAdjustable air distribution vanes
Under certain circumstances it is desirable to be able
to adjust the airfl ow distribution pattern to achieve even
higher levels of indoor thermal comfort and reduce draft
risks in the occupied zone below the beams.
Offering standard “long” throw bullet shape airfl ow profi le,
the Dadanco offer can be used to widely disperse both
cooling primary air and mixed secondary cooled room air
induced through the fi ncoil battery.
By fi tting adjustable vanes this pattern can be shortened
in length and push the air distribution wider, keeping
the primary air and conditioned room air locally within
the space below the ACB46 unit. This is important where
beams are placed in close proximity to each other at 3m
centres to avoid colliding air paths from two adjacent
ACB units.
Depending on the design condition, this can marginally
reduce the induction ratio with a very minor reduction in
the secondary cooling output. The effect of which should
be considered whilst selecting beams against the cooling
duty required for the space.
Key Features
• Provide divergent air fl ows locally around the ACB unit.
• Reduce the chance for colliding air paths and give
resulting lower air velocities in the occupied zone.
• Maintain a whisper quiet operation.
• Offer a degree of adjustability in service if different air
fl ow patterns/ effects are required.
2
ACB46 COANDA WINGS AND DIRECTIONAL VANES
Adjustable vanes feature showing 3 position adjustment to
deliver different air throw patterns for divergent air streams
13
873
282
For active chilled beams mounted in exposed ceiling spaces we offer the Coanda wing which can be fi tted over the ACB46 to facilitate horizontal air throw and improve the natural air diffusion.
11 | DADANCO | ACTIVE CHILLED BEAMS ACB46
800
700
600
500
400
300
200
100
010 302015 25
Octave Band Centre Frequency (Hz)
Unit Setup 63 125 250 500 1000 2000 4000 8000 Combined
68SN, 39L/sLW (dB) 37 38 39 39 34 28 22 19 NC-34
LWA (dBA) 11 22 31 36 34 29 23 18 40 dB(A)
8
6
7
3
4
5
1
2
0121198 10
Sen
sib
le c
oo
ling
En
erg
y (
J/L
)
Primary Air Cooling Capacity Primary AirLatent Capacity Maximum Secondary/Water Cooling(per unit of length)
Late
nt
Co
olin
g E
nerg
y (
J/L
)
Sen
sib
le C
oo
ling
(J/L
)
PRIMARY AIRThe primary air cooling chart is based on specifi c heat cooling potential of ducted
conditioned air. The standard technical data tables use 8 and 10°K reductions for
the supply air and water temperatures.
To determine the sensible cooling capacity multiply required fl ow rate by cooling
energy as determined on the chart y-axis.
If the primary air dew point temperature is available and assuming the room air
condition is 24°C, 50%RH the second chart indicates the available latent cooling.
SOUND POWER DATASound power is also listed in the technical data.
SECONDARY WATERThe bottom chart shows the maximum
secondary/water cooling for a typical
primary air fl ow range per unit length
of chilled beam. This chart data is
based on a typical room temperature
24°C, water fl ow 14°C and water
return 16°C.
ACB46, ACB46H ACTIVE CHILLED BEAM QUICK SELECTION
16
14
12
10
8
6
4
2
05 12119876 10
Sound power profi le from an active chilled beam with 125Pa plenum pressure, db re 10-12 (W).
ACB46, ACB46HQUICK SELECTION
Room - Primary Air: ΔTPA
(°K)
Room at 24°C, 50%rh. ΔTsca
= 10°K | ΔTW = 2°K
Primary Air Dew Point: (°Cdp
) Nominal Primary Air Flow (L/s per m)
12 | DADANCO | ACTIVE CHILLED BEAMS ACB46
TECHNICAL DATAACB46, ACB46H
HIGH WATER FLOW (ΔTW=2ºK)
Primary AirSupply
Air
Water CoolingWater
Heating
ΔTSCA = 8K ΔTSCA = 10KΔTSHA = 14KWater Flow =
0.05l/s
Length ModelNozzleConfi g
FlowL/s
PPa
LwdB(A)
FlowL/s
FlowL/s
ΔPkPa
QSCW
QTOTW
FlowLs
ΔPkPa
QSCW
QTOTW
kPaQsh (W)
600mm ACB46-450.482
18SN8 73 29 31 0.03 1.6 -188 -265 0.03 1.6 -233 -330 1.4 217
10 114 34 43 0.03 1.6 -234 -332 0.03 1.6 -291 -412 1.4 259
26SN12 78 30 47 0.03 1.6 -228 -345 0.03 1.6 -284 -430 1.4 250
15 122 35 66 0.03 1.6 -289 -435 0.03 1.6 -361 -543 1.4 289
32SN15 81 30 59 0.03 1.6 -258 -404 0.03 1.6 -323 -504 1.4 251
18 116 35 78 0.03 1.6 -313 -488 0.03 1.6 -390 -608 1.4 277
900mm ACB46-750.482
36SN17 82 32 67 0.04 3.0 -349 -514 0.05 4.0 -445 650 1.5 407
21 125 37 93 0.05 4.7 -459 -663 0.07 7.2 -582 -836 1.5 474
38SN18 83 33 71 0.04 3.1 -361 -536 0.06 5.5 -470 -687 1.5 414
22 123 37 97 0.06 4.9 -468 -682 0.07 7.1 -591 -857 1.5 477
40SN19 83 33 75 0.04 3.3 -374 -559 0.06 5.5 -482 -711 1.5 419
23 122 37 101 0.06 5.0 -477 -701 0.07 7.1 -600 877 1.5 478
1200mm ACB46-1050.482
48SN22 77 33 85 0.05 5.2 -458 -672 0.07 8.0 -592 -857 1.6 548
28 125 38 124 0.07 9.0 -625 -897 0.10 14.1 -756 -1094 1.6 656
52SN24 78 33 94 0.06 5.7 -482 -715 0.08 9.2 -629 -919 1.6 565
30 122 38 132 0.08 9.5 -645 -937 0.10 14.8 -820 -1182 1.6 663
56SN26 79 34 102 0.06 6.2 -507 -760 0.80 10.0 -654 -968 1.6 578
32 120 38 140 0.08 10.0 -663 -974 0.10 15.3 -837 -1223 1.6 666
1500mm ACB46-1350.482
62SN29 80 34 114 0.06 6.7 -597 -880 0.08 11.4 -767 -1117 1.7 717
35 117 38 152 0.08 11.4 -746 -1087 0.10 17.1 -957 -1379 1.7 824
66SN31 76 34 116 0.07 8.9 -604 -896 0.08 11.4 -791 -1165 1.7 733
37 122 39 167 0.09 14.1 -797 -1167 0.10 17.1 -979 -1425 1.7 833
70SN32 77 35 124 0.08 11.4 -634 -945 0.09 14.1 -802 -1188 1.7 731
40 120 39 175 0.09 11.4 -801 -1191 0.11 20.3 -1039 -1522 1.7 853
1800mm ACB46-1650.482
72SN33 77 35 128 0.08 13.8 -706 -1027 0.11 22.8 -923 -1323 1.8 847
41 119 39 179 0.11 23.1 -928 -1327 WaterΔP>25kPa 1.8 999
76SN35 78 35 136 0.09 14.6 -727 -1068 0.11 24.4 -955 -1380 1.8 867
43 118 39 187 0.11 24.1 -949 -1367 WaterΔP>25kPa 1.8 1010
80SN37 79 35 144 0.09 15.5 -750 -1110 0.12 25.9 -988 -1436 1.8 884
46 122 40 181 0.12 26.4 -997 -1445 WaterΔP>25kPa 1.8 1035
2400mm ACB46-2250.482
92SN43 80 36 169 0.11 5.7 -979 1395 0.15 9.0 -1255 -1774
Cooling only
53 122 41 233 0.15 8.9 -1253 -1765 0.19 14.4 -1613 -2253
100SN47 81 37 185 0.12 6.1 -1026 -1480 0.16 10.3 -1324 -1891
57 120 41 249 0.15 9.5 -1289 -1840 0.20 15.0 -1681 -2369
108SN50 79 37 195 0.12 6.3 -1042 -1525 0.16 10.3 -1352 -1955
61 117 41 265 0.16 10.0 -1338 -1928 0.2 15.3 -1725 -2461
QSC
: Secondary Air Cooling Room Air 24°C Room Air 24°C
QTOT
: Primary & Secondary Air Cooling Primary Air 16°C Primary Air 14°C
QSH
: Secondary Air Heating Water Supply 16°C Water Supply 14°C
ΔTSC
& ΔTSC
= (TROOM
-TWATER INLET TEMPERATURE
) Water Return 18°C Water Return 16°C
13 | DADANCO | ACTIVE CHILLED BEAMS ACB46
MEDIUM FLOW (ΔTW=2ºK)
Primary AirSupply
Air
Water CoolingWater
Heating
ΔTSCA = 8K ΔTSCA = 10KΔTSHA = 14KWater Flow =
0.05l/s
Length ModelNozzleConfi g
FlowL/s
PPa
LwdB(A)
FlowL/s
FlowL/s
ΔPkPa
QSCW
QTOTW
FlowLs
ΔPkPa
QSCW
QTOTW
kPaQsh (W)
600mm ACB46-450.482
18SN8 73 30 31 0.025 1.2 -185 -262 0.025 1.2 -229 -326 1.4 217
10 114 34 43 0.025 1.2 -229 -326 0.025 1.2 -285 -406 1.4 259
26SN12 78 30 47 0.025 1.2 -223 -339 0.025 1.2 -279 -423 1.4 250
15 122 35 66 0.025 1.2 -285 -430 0.025 1.2 -357 -538 1.4 289
32SN15 81 31 59 0.025 1.2 -258 -402 0.025 1.2 -323 -503 1.4 251
18 116 36 78 0.025 1.2 -313 -487 0.025 1.2 -390 -607 1.4 277
900mm ACB46-750.482
36SN17 83 32 67 0.025 1.3 -332 -496 0.03 1.7 -421 -626 1.5 407
21 125 37 93 0.03 1.9 -406 -610 0.04 2.8 -538 -792 1.5 474
38SN18 83 33 71 0.025 1.3 -340 -514 0.03 1.7 -433 -650 1.5 414
22 123 37 97 0.03 1.7 -427 -640 0.04 2.8 -550 -815 1.5 477
40SN19 83 33 75 0.025 1.3 -350 -533 0.04 2.8 -458 -687 1.5 419
23 122 37 101 0.03 1.7 -437 -660 0.05 4 -575 -852 1.5 478
1200mm ACB46-1050.482
48SN22 77 33 85 0.03 1.8 -438 -651 0.04 3 -559 -825 1.6 548
28 125 38 124 0.04 3.0 -569 -840 0.06 6.1 -742 -1079 1.6 656
52SN24 78 33 94 0.03 1.8 -453 -685 0.05 4.5 -593 -883 1.6 565
30 122 38 132 0.05 4.5 -599 -889 0.06 6.1 -763 -1125 1.6 663
56SN26 79 34 102 0.04 3.0 -483 -734 0.05 4.5 -618 -932 1.6 578
32 120 38 140 0.05 4.5 -618 -927 0.06 6.1 -787 -1173 1.6 666
1500mm ACB46-1350.482
62SN29 80 35 114 0.04 3.2 -577 -858 0.05 4.8 -734 -1084 1.7 717
35 117 38 152 0.05 4.8 -709 -1047 0.06 6.7 -901 -1323 1.7 824
66SN30 76 35 116 0.04 3.2 -572 -862 0.06 6.7 -741 -1103 1.7 733
38 122 38 167 0.05 4.8 -745 -1112 0.07 8.9 -963 -1421 1.7 833
70SN32 77 36 124 0.05 4.8 -600 -910 0.06 6.7 -765 -1151 1.7 731
40 120 39 175 0.06 6.7 -776 -1163 0.07 8.9 -986 -1469 1.7 853
1800mm ACB46-1650.482
72SN33 77 35 128 0.05 5.2 -683 -1002 0.07 9.7 -873 -1271 1.8 847
41 119 39 179 0.06 7.3 -854 -1250 0.09 15.6 -1108 -1602 1.8 999
76SN35 78 35 136 0.05 5.2 -696 -1035 0.07 9.7 -893 -1316 1.8 867
43 118 39 187 0.07 9.7 -880 -1296 0.09 15.6 -1128 -1647 1.8 1010
80SN37 79 35 144 0.05 5.2 -711 -1069 0.07 9.7 -915 -1362 1.8 884
46 122 40 202 0.07 9.7 -917 -1361 0.09 15.6 -1176 -1731 1.8 1035
2400mm ACB46-2250.482
92SN43 80 36 169 0.07 2.3 -945 -1360 0.09 3.7 -1197 -1715
Cooling only
53 122 41 233 0.09 3.7 -1174 -1686 0.12 6.1 -1507 -2146
100SN47 81 37 185 0.07 2.3 -970 -1424 0.09 3.7 -1237 -1804
57 120 41 249 0.09 3.7 -1201 -1751 0.12 6.1 -1548 -2235
108SN50 79 37 195 0.07 2.3 -1004 -1488 0.09 3.7 -1254 -1857
61 117 41 265 0.09 3.7 -1232 -1822 0.12 6.1 -1590 -2326
QSC
: Secondary Air Cooling Room Air 24°C Room Air 24°C
QTOT
: Primary & Secondary Air Cooling Primary Air 16°C Primary Air 14°C
QSH
: Secondary Air Heating Water Supply 16°C Water Supply 14°C
ΔTSC
& ΔTSC
= (TROOM
-TWATER INLET TEMPERATURE
) Water Return 18°C Water Return 16°C
14 | DADANCO | ACTIVE CHILLED BEAMS ACB46
25
20
15
10
5
0
0.00 0.08
2250 1650 1350
750
2250(282 coil cooling only - inc. manifold)
Coil Lengths(mm)
0.10 0.12 0.14 0.160.040.02 0.06
Water Resistance Cooling Circuit - 482
Water Flow Rate (L/s)
Pres
sure
Dro
p (kP
a)
2250
1650
1350
1050
750
Coil Lengths(mm)
25
20
15
10
5
0
0.00 0.08 0.10 0.12 0.14 0.160.040.02 0.06
Pres
sure
Dro
p (kP
a)
Water Resistance Heating Circuit - 482
Water Flow Rate (L/s)
WATER PIPE COIL RESISTANCE
15 | DADANCO | ACTIVE CHILLED BEAMS ACB46
CLIMATIC TESTING FACILITY
Australia’s only “Scenario Analysis Facility”, state of the art Climatic Test Laboratories
are the fl agship of Dadanco R&D Technical Centre based in Salisbury, SA.
Capable of Project Specifi c Testing including:
• Thermal Capacity Validation in accordance with
EN15116:2008
• Project specifi c testing for occupied zone thermal
comfort parameters according to ISO7730:2005.
• Solar heat gains including corner offi ce simulation
(having 2 radiant walls).
• Perimeter zone up to (and exceeding) 170W/m2.
• Centre zone 35-75W/m2 using Din men “thermal
mannequins”.
• Thermal and air velocity topographies at
- 1.8m AFFL
- 0.8m AFFL (working plane)
- 0.2m AFFL
• Smoke visualisation testing.
• Acoustic data collection.
This provides a local key tool for Consultant Engineers to model space behaviour under strictly
controlled conditions prior to any site installation, assisting to refi ne designs and avoid poor thermal
comfort problems occurring at site once the building is fully occupied.
WITNESS TEST FACILITY
B B
F
C
D
A
EE
A. Active Chilled Beam
B. Radiant Wall
C. Acoustic Metre
D. Air Velocity Metre
E. Temperature Sensors
F. Din Man
VictoriaReece HVAC Docklands(03) 8387 [email protected]
New South WalesReece HVAC Artarmon(02) 9437 5744 [email protected]
Queensland Reece HVAC Woolloongabba(07) 3392 [email protected]
South Australia Reece HVAC Wingfi eld(08) 8161 4730 Wingfi [email protected]
Western AustraliaReece HVAC Belmont(08) 9373 2230 [email protected]
Tasmania Reece HVAC Derwent Park(03) 6271 [email protected]
Exclusively distributed by Reece HVAC.
Visit reece.com.au for your nearest branch.
While every effort is made to ensure the details contained herein are kept up to date, in the interests of ongoing product research and development DADANCO reserves the right to alter the information without notice. E. & O.E.
[BROCHURE CODE 108158]