26
03.19.2015 AS NOTED LJM/ AK 26 SSPE DESIGN CHECKED JOB SCALE DATE DRAWN OF SHT DATE DESCRIPTION REV. SHEET TITLE PROJECT SM-WAREHOUSE Engineering By: PHONE: 321.251.6006 SUITE 2072 CA#27371 DBSS, INC. ORLANDO, FL. 32828 SEMINIOLE MASONRY WAREHOUSE BUILIDNG 1 C COVER SHEET & CODE DATA SEMINOLE MASONRY WAREHOUSE BUILDING 3850 E LAKE MARY BLVD. SANFORD, FL 32773 CODE DATA INTERIOR FINISH CLASSIFICATION (TABLE 803.9): B (GROUP S AREA) & A (GROUP B AREA) C (GROUP S AREA) & B (GROUP B AREA) C (GROUP S & GROUP B) A.B. Abv. A/C Adj. A.F.F. A.H.U. ALT. B.C. B.F. Bk Sh Bm. BOT. B.P. Brg. Cir. Clg. Col. Comp. C.T. D Dec. Ded. Dbl. Dia. Disp. Dist. D.S. D.V. D.W. Ea. E.W. Elec. Elev. Ext. Exp. Anchor Bolt Above Air-Conditioner Adjustable Above Finished Floor Air Handler Unit Alternate Base Cabinet Bifold Door Book Shelf Beam Bottom Bypass door Bearing Circle Ceiling Column A/C Compressor Ceramic Tile Dryer Decorative Dedicated Outlet Double Diameter Disposal Distance Drawer Stack Dryer Vent Dishwasher Each Each Way Electrical Elevation Exterior Expansion F.B.C.R. F.F. F.G. Flr. Fnd. Flr. Sys. F/P Ft. Ftg. FX Galv. G.C. G.F.I. G.T. Hdr. Hgt. HB Int. K/Wall K.S. Laun. Lav. L.F. L.T. Mas. Max M.C. Mfgr. Micro. Min. M.L. Mir. Mono N.T.S. Florida Bldg. Code Resid. Finished Floor Fixed Glass Floor Foundation Floor System Fireplace Foot / Feet Footing Fixed Galvanized General Contractor Ground Fault Interrupter Girder Truss Header Height Hose Bibb Interior Kneewall Knee Space Laundry Lavatory Linear Ft. Laundry Tub Masonry Maximum Medicine Cabinet Manufacturer Microwave Minimum Microlam Mirror Monolithic Not to Scale Opn'g. Opt. Pc. Ped. P.L. PLF Plt. Ht. Plt Sh. PSF P.T. Pwd. Rad. Ref. Req'd. Rm. Rnd. R & SH SD. S.F. Sh. SHT S.L. S.P.F. Sq. S.Y.P. Temp. Thik'n. T.O.B. T.O.M. T.O.P. Trans. Typ. UCL U.N.O. VB Vert. V.L. VTR W w/ W.C. W.A. Wd. WP Opening Optional Piece Pedestal Parallam Pounds per linear foot Plate Height Plant Shelf Pounds per square foot Pressure Treated Powder Room Radius Refrigerator Required Room Round Rod and Shelf Smoke Detector Square Ft. Shelves Sheet Side Lights Spruce Pine Fir Square Southern Yellow Pine Tempered Thicken Top of Block Top of Masonry Top of Plate Transom Window Typical Under Cabinet Lighting Unless Noted Otherwise Vanity Base Vertical Versalam Vent through Roof Washer With Water Closet Wedge Anchor Wood Water Proof ABBREVIATIONS VP Vapor Protected INDEX OF DRAWINGS B.F.F. Below Finished Floor F.B.C. Florida Bldg. Code NO. DESCRIPTION x FLORIDA BUILDING CODE 2010 x NFPA-1 (UNIFORM FIRE CODE), 2012 EDITION x NFPA-70 (NEC), 2011 EDITION x NFPA-101 (LIFE SAFETY CODE), 2012 EDITION x FBC 2010 - PLUMBING x FBC 2010 - ELECTRICAL x FBC 2010 - MECHANICAL x FBC 2010 - ACCESSIBILITY PROJECT: SEMINOLE MASONRY, WAREHOUSE BUILDING ADDRESS: NEW ONE STORY WAREHOUSE (CONTAINING CEMENT BAGS, METALS ON WOODED PALLETS AND SIMILAR ORDINARY LOW-HAZARD ITEMS PER NFPA) WITH OFFICE SPACE SCOPE: BUILDING DATA: SEE ALSO LIFE SAFTEY PLAN SHEET 04 FIRE SPRINKLERS: FIRE ALARM SYSTEM: EMERGENCY LIGHTING & EXIT SIGNS LIFE SAFETY: NO NO YES TRAVEL DISTANCE TO EXIT MAX. ALLOWED/ LONGEST ACTUAL: TRAVEL DISTANCES (TABLE 1016.1): ALLOWED/ACTUAL 300 FEET (UNSPRINKLERED)/ 165 FEET MAX. COMMON PATH OF TRAVEL MAX. ALLOWED/ LONGEST ACTUAL: COMMON PATH OF TRAVEL (1014.3): ALLOWED/ACTUAL 75 FEET (UNSPRINKLERED)/ 40 FEET CODES IN EFFECT: TOTAL OCCUPANTS: NUMBER EXITS REQ'D/PROVIDED 118 TOTAL (REFER TO SHEET 04) TWO/FIVE NUMBER OF OCCUPANTS: FIVE/SEVEN THREE/SEVEN NONE/TWO ONE/TWO (HI-LO) ONE/ONE PLUMBING FIXTURES: OTHER EGRESS COMPONENTS - .2 INCHES PER OCCUPANT REQ'D./PROVIDED: EGRESS WIDTH (1005.1): FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (TABLE 602) TYPE IIB, GROUP S-2 & GROUP B EXTERIOR x < 5' EXTERIOR 5' < x < 10' EXTERIOR 10' < x < 20' EXTERIOR 20' < x < 30' EXTERIOR x > 30' 3 HRS 2 HRS 2 HRS 1 HR 0 HR SITE KEY PLAN N.T.S. 3850 E LAKE MARY BLVD. SANFORD, FL 32773 OCCUPANCY (CH 3): BUILDING AREA: CONSTRUCTION TYPE (CH 6): GROUP S-2 (WAREHOUSE) & GROUP B 13,043 S.F. TYPE II B WATER CLOSETS REQ'D./ PROVIDED: LAVATORIES REQ'D./ PROVIDED: URINALS REQ'D./ PROVIDED: DRINKING FOUNTIANS REQ'D./ PROVIDED: SERVICE SINK REQ'D./ PROVIDED: 0.2" /23.6" COVER SHEET, CODE DATA & SITE KEY PLAN C 01.1 01 01.2 ASSEMBLY PLAN (CLASS A: FLAME SPREAD INDEX 0-25; SMOKE -DEVELOPED INDEX 0-450.) (CLASS B: FLAME SPREAD INDEX 26-75; SMOKE -DEVELOPED INDEX 0-450.) (CLASS C: FLAME SPREAD INDEX 76-200; SMOKE -DEVELOPED INDEX 0-450.) CLASS II OR BETTER INTERIOR FLOOR FINISH (804): EXIT ENCLOSURES & EXIST PASSAGEWAYS CORRIDORS ROOMS & ENCLOSED SPACES GENERAL NOTES BOLTS AND THREADED RODS 1. ALL BOLTS & THREADED RODS TO BE ASTM F1554 A36 OR BETTER(U.N.O.) MASONRY WALL CONSTRUCTION 1. HOLLOW LOAD BEARING UNITS SHALL BE NORMAL WEIGHT, GRADE N, TYPE 2, CONFORMING TO ASTM C90, WITH A MINIMUM NET COMPRESSIVE STRENGTH OF 2000 PSI (f'm = 1500 PSI) 2. MORTAR SHALL BE TYPE M OR S, CONFORMING TO ASTM C270 3. HEAD MORTAR JOINTS AT PRECAST WINDOW SILLS TO BE NO MORE THAN 1". 4. COARSE GROUT SHALL CONFORM TO ASTM C476 WITH A MAXIMUM AGGREGATE SIZE OF 3/8" AND A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI. 5. VERTICAL REINFORCEMENT SHALL BE AS NOTED ON THE DRAWINGS WITH CELLS FILLED WITH COARSE GROUT. 6. VERTICAL REINFORCEMENT SHALL BE HELD IN POSITION AT THE TOP AND BOTTOM. REINFORCEMENT SHALL BE PLACED IN THE CENTER OF THE MASONRY CELL TYPICAL UNLESS OTHERWISE NOTED. 7. REINFORCING STEEL SHALL BE LAPPED MINIMUM 25" FOR #5 BAR AND 36" FOR #6 BAR UNLESS NOTED OTHERWISE ON THE DRAWINGS. 8. HOOKS AT TOP & BOTTOM OF VERTICAL REINFORCING BARS TO BOND BEAM AND FOOTING TO BE NO LESS THAN 12 BAR DIAMETERS EXCLUDING BEND 9. EXPANSION TYPE ANCHORS ARE NOT TO BE USED IN BOND BEAM. EMBEDDED ANCHORS OR EPOXY FASTENED STUDS SHALL BE USED. CAST IN PLACE CONCRETE 1. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS OF 3000 PSI FOR FTG. SLAB & 4000 PSI FOR PIERS, A SLUMP OF 4" PLUS OR MINUS 1", AND HAVE 2 TO 4% AIR ENTRAINMENT, AND A MAXIMUM WATER/CEMENT RATIO OF 0.58 U.N.O. 2. ALL REINFORCING STEEL SHALL BE NEW DOMESTIC DEFORMED BILLET STEEL CONFORMING TO ASTM A-615 GRADE 60. 3. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH "THE BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE" ACI 318 LATEST EDITION, AND "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS," ACI 301. 4. HORIZONTAL FOOTING BARS SHALL BE BENT MIN. 48 BAR DIAMETERS (EXCLUDING BEND) AROUND CORNERS OR #5 CORNER BARS WITH MIN. 30" LAP EXCLUDING BEND AT EACH END SHALL BE PROVIDED. 5. MINIMUM LAP SPLICES ON ALL REINFORCING BARS SHALL BE 48 BAR DIAMETERS. (U.N.O.) FOUNDATIONS 1. SOIL TO BE COMPACTED TO AT LEAST 95% UNDER SLABS AND 98% UNDER FOOTINGS OF MAX. DRY DENSITY AS DETERMINED BY ASTM- 1557 (MODIFIED PROCTOR) 2. THE FOUNDATION OF THIS STRUCTURE HAS BEEN DESIGNED TO AN ALLOWABLE BEARING CAPACITY OF 2000 PSF. IT IS THE OWNER/ CONTRACTORS RESPONSIBILITY TO VERIFY THAT THE BUILDING SITE WILL MEET THIS STANDARD WITH REGARDS TO SETTLEMENT AND SUPPORT. 3. PROVIDE TERMITE TREATED SOIL IN ACCORDANCE W/ SECTION 1816 OF THE FLORIDA BUILDING CODE. IN LIEU OF TREATING THE SOIL, BORA-CARE TERMITICIDE MAY BE APPLIED TO WOOD COMPONENTS IN ACCORDANCE TO W/MANUFACTURER'S INSTRUCTIONS, PURSUANT TO SECTION 1816 OF THE FLORIDA BUILDING CODE. DESIGN REQUIREMENTS DESIGN LIVE LOADS(MINIMUM): A. ROOFS - 20 PSF WIND DESIGN LOAD INFORMATION- (PER FBC 2010, REF. ASCE 7-10) BASIC WIND SPEED (V ult) = 140 MPH (3 SECOND GUST) (Vasd) = 108 MPH (3 SECOND GUST) BUILDING CATEGORY = II (ASCE 7-10) WIND EXPOSURE(ALL SIDES) =C (ASCE 7-10) INTERNAL PRESSURE COEFFICIENTS (ASCE 7-10) ENCLOSED BUILDINGS = +/-0.18 PARTIALLY ENCLOSED BUILDINGS = +/-0.55 (NOTE: COEFFICIENTS FOR PARTIALLY ENCLOSED STRUCTURES ARE APPLIED WHEN DESIGN OF MEMBER(S) FALLS UNDER ASCE 7-10 DEFINITIONS CLASSIFYING AS SUCH) ALL COMPONENTS AND CLADDING NOT SPECIFIED ON PLANS SHALL BE DESIGNED TO WITHSTAND THE FOLLOWING PRESSURES (p asd): FOR WALL LOCATIONS: -38.2 PSF, +28.6 PSF DBSS, INC. 3662 AVALON PARK EAST BLVD. SUITE 2072 ORLANDO, FL 32828 PH: 321.251.6006 PRIME PROFESSIONAL S1 SD1 STRUCTURAL DETAILS S2 LINTEL PLAN S3 BUILDING SECTION WAREHOUSE FLOOR PLAN WAREHOUSE/ OFFICE FLOOR PLAN 02 03 04 05 EXTERIOR ELEVATIONS EXTERIOR ELEVATIONS LIFE SAFETY PLAN REFLECTED CEILING PLAN 06 ADA DETAILS & FIRE SEPARATION S4 CEILING FRAMING PLAN STRUCTURAL STEEL 1. FABRICATION AND ERECTION OF STRUCTURAL STEEL SHALL BE IN ACCORDANCE WITH "SPECIFICATION FOR THE DESIGN AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS," AISC, 13TH EDITION, AND THE 2010 FBC. 2. STEEL MEMBERS SHALL CONFORM TO THE FOLLOWING MATERIAL SPECIFICATIONS: A. PLATES, ANGLES, CHANNELS, TUBES - ASTM A36, Fy=36 KSI B. PIPE - ASTM A53 GRADE B, Fy=35 KSI C. W-BEAMS - ASTM A992, Fy=50 KSI D. HSS (RECT.) - ASTM A500 GRADE B, Fy=46 KSI E. HSS (ROUND) - ASTM A500 GRADE B, Fy=42 KSI 3. ALL WELDING SHALL BE PERFORMED BY EXPERIENCED, CERTIFIED WELDERS USING THE ELECTRIC ARC WELDING PROCESS, E70XX SERIES ELECTRODES FOR WELDING STRUCTURAL STEEL, WELDING SHALL CONFORM TO AISC AND AWS STANDARD. 4. ALL WELDS NOT SPECIFIED SHALL BE CONTINUOUS FILLET WELDS, SIZE OF WELD SHALL BE BASED ON ASIC STANDARD FOR THICKER PART JOINED. 5. HOLES FOR BOLTS IN STRUCTURAL STEEL SHALL BE DRILLED OR PUNCHED. BURNING OF HOLES SHALL NOT BE PERMITTED 6. APPLY CORROSIVE RESISTANT PAINT TO ALL WELDS AND STEEL SURFACES. LIGHT GAUGE FRAMING 1. ALL LIGHT GAUGE MEMBERS TO BE MIN. 20ga. U.N.O. (USE 18ga. FOR EXTERIOR) 2. ALL FASTENERS TO BE: SELF-DRILLING, SELF-TAPPING SCREWS; STEEL, COMPLYING WITH ASTM C1002; GALVANIZED COATING, PLATED OR OIL-PHOSPHATE COATED COMPLYING WITH ASTM B 633 AS NEEDED FOR REQUIRED CORROSION RESISTANCE. 3. TOUCH-UP PAINT: ZINC RICH, CONTAINING 95-PERCENT METALLIC ZINC. 4. GALVANIZED COATING TO BE: G60 COATING WEIGHT MINIMUM, COMPLYING WITH ASTM C 955. 5. CUT ALL FRAMING COMPONENTS SQUARELY FOR ATTACHMENT TO FIT AGAINST ABUTTING MEMBERS. HOLD MEMBERS POSITIVELY IN PLACE UNTIL PROPERLY FASTENED. FOUNDATION PLAN SD2 STRUCTURAL DETAILS S1.1 FOUNDATION PLAN ELECTRICAL PLAN E1 E2 ELECTRICAL PLAN 07 FIRE SEPARATION DETAILS SD3 STRUCTURAL DETAILS 08 FIRE SEPARATION DETAILS 09 FIRE PENETRATION DETAILS 10 FIRE PENETRATION DETAILS E3 ELECTRICAL PLAN P2 P1 PLUMBING SUPPLY PLAN PLUMBING WASTE PLAN

BOLTS AND THREADED RODS SEMINOLE MASONRY … · Anchor Bolt Above Air-Conditioner Adjustable Above Finished Floor Air Handler Unit Alternate Base Cabinet Bifold Door Book Shelf Beam

Embed Size (px)

Citation preview

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

1

C

CO

VE

R S

HE

ET

&

CO

DE

D

AT

A

SEMINOLE MASONRY

WAREHOUSE BUILDING

3850 E LAKE MARY BLVD.

SANFORD, FL 32773

CODE DATA

INTERIOR FINISH

CLASSIFICATION

(TABLE 803.9):

B (GROUP S AREA) & A (GROUP B AREA)

C (GROUP S AREA) & B (GROUP B AREA)

C (GROUP S & GROUP B)

A.B.

Abv.

A/C

Adj.

A.F.F.

A.H.U.

ALT.

B.C.

B.F.

Bk Sh

Bm.

BOT.

B.P.

Brg.

Cir.

Clg.

Col.

Comp.

C.T.

D

Dec.

Ded.

Dbl.

Dia.

Disp.

Dist.

D.S.

D.V.

D.W.

Ea.

E.W.

Elec.

Elev.

Ext.

Exp.

Anchor Bolt

Above

Air-Conditioner

Adjustable

Above Finished Floor

Air Handler Unit

Alternate

Base Cabinet

Bifold Door

Book Shelf

Beam

Bottom

Bypass door

Bearing

Circle

Ceiling

Column

A/C Compressor

Ceramic Tile

Dryer

Decorative

Dedicated Outlet

Double

Diameter

Disposal

Distance

Drawer Stack

Dryer Vent

Dishwasher

Each

Each Way

Electrical

Elevation

Exterior

Expansion

F.B.C.R.

F.F.

F.G.

Flr.

Fnd.

Flr. Sys.

F/P

Ft.

Ftg.

FX

Galv.

G.C.

G.F.I.

G.T.

Hdr.

Hgt.

HB

Int.

K/Wall

K.S.

Laun.

Lav.

L.F.

L.T.

Mas.

Max

M.C.

Mfgr.

Micro.

Min.

M.L.

Mir.

Mono

N.T.S.

Florida Bldg. Code Resid.

Finished Floor

Fixed Glass

Floor

Foundation

Floor System

Fireplace

Foot / Feet

Footing

Fixed

Galvanized

General Contractor

Ground Fault Interrupter

Girder Truss

Header

Height

Hose Bibb

Interior

Kneewall

Knee Space

Laundry

Lavatory

Linear Ft.

Laundry Tub

Masonry

Maximum

Medicine Cabinet

Manufacturer

Microwave

Minimum

Microlam

Mirror

Monolithic

Not to Scale

Opn'g.

Opt.

Pc.

Ped.

P.L.

PLF

Plt. Ht.

Plt Sh.

PSF

P.T.

Pwd.

Rad.

Ref.

Req'd.

Rm.

Rnd.

R & SH

SD.

S.F.

Sh.

SHT

S.L.

S.P.F.

Sq.

S.Y.P.

Temp.

Thik'n.

T.O.B.

T.O.M.

T.O.P.

Trans.

Typ.

UCL

U.N.O.

VB

Vert.

V.L.

VTR

W

w/

W.C.

W.A.

Wd.

WP

Opening

Optional

Piece

Pedestal

Parallam

Pounds per linear foot

Plate Height

Plant Shelf

Pounds per square foot

Pressure Treated

Powder Room

Radius

Refrigerator

Required

Room

Round

Rod and Shelf

Smoke Detector

Square Ft.

Shelves

Sheet

Side Lights

Spruce Pine Fir

Square

Southern Yellow Pine

Tempered

Thicken

Top of Block

Top of Masonry

Top of Plate

Transom Window

Typical

Under Cabinet Lighting

Unless Noted Otherwise

Vanity Base

Vertical

Versalam

Vent through Roof

Washer

With

Water Closet

Wedge Anchor

Wood

Water Proof

ABBREVIATIONS

VPVapor Protected

INDEX OF DRAWINGS

B.F.F. Below Finished Floor

F.B.C. Florida Bldg. Code

NO.DESCRIPTION

FLORIDA BUILDING CODE 2010

NFPA-1 (UNIFORM FIRE CODE), 2012 EDITION

NFPA-70 (NEC), 2011 EDITION

NFPA-101 (LIFE SAFETY CODE), 2012 EDITION

FBC 2010 - PLUMBING

FBC 2010 - ELECTRICAL

FBC 2010 - MECHANICAL

FBC 2010 - ACCESSIBILITY

PROJECT: SEMINOLE MASONRY, WAREHOUSE BUILDING

ADDRESS:

NEW ONE STORY WAREHOUSE (CONTAINING CEMENT

BAGS, METALS ON WOODED PALLETS AND SIMILAR

ORDINARY LOW-HAZARD ITEMS PER NFPA) WITH

OFFICE SPACE

SCOPE:

BUILDING DATA:

SEE ALSO LIFE SAFTEY PLAN SHEET 04

FIRE SPRINKLERS:

FIRE ALARM SYSTEM:

EMERGENCY LIGHTING & EXIT SIGNS

LIFE SAFETY:

NO

NO

YES

TRAVEL DISTANCE TO EXIT

MAX. ALLOWED/ LONGEST ACTUAL:

TRAVEL

DISTANCES

(TABLE 1016.1):

ALLOWED/ACTUAL

300 FEET (UNSPRINKLERED)/ 165 FEET

MAX. COMMON PATH OF TRAVEL

MAX. ALLOWED/ LONGEST ACTUAL:

COMMON PATH

OF TRAVEL

(1014.3):

ALLOWED/ACTUAL

75 FEET (UNSPRINKLERED)/ 40 FEET

CODES IN

EFFECT:

TOTAL OCCUPANTS:

NUMBER EXITS REQ'D/PROVIDED

118 TOTAL (REFER TO SHEET 04)

TWO/FIVE

NUMBER OF

OCCUPANTS:

FIVE/SEVEN

THREE/SEVEN

NONE/TWO

ONE/TWO (HI-LO)

ONE/ONE

PLUMBING

FIXTURES:

OTHER EGRESS COMPONENTS -

.2 INCHES PER OCCUPANT REQ'D./PROVIDED:

EGRESS WIDTH

(1005.1):

FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING

ELEMENTS (TABLE 602)

TYPE IIB, GROUP S-2 & GROUP B

EXTERIOR x < 5'

EXTERIOR 5' < x < 10'

EXTERIOR 10' < x < 20'

EXTERIOR 20' < x < 30'

EXTERIOR x > 30'

3 HRS

2 HRS

2 HRS

1 HR

0 HR

SITE KEY PLAN

N.T.S.

3850 E LAKE MARY BLVD.

SANFORD, FL 32773

OCCUPANCY (CH 3):

BUILDING AREA:

CONSTRUCTION TYPE (CH 6):

GROUP S-2 (WAREHOUSE) & GROUP B

13,043 S.F.

TYPE II B

WATER CLOSETS REQ'D./ PROVIDED:

LAVATORIES REQ'D./ PROVIDED:

URINALS REQ'D./ PROVIDED:

DRINKING FOUNTIANS REQ'D./ PROVIDED:

SERVICE SINK REQ'D./ PROVIDED:

0.2" /23.6"

COVER SHEET, CODE DATA & SITE KEY PLANC

01.1

01

01.2

ASSEMBLY PLAN

(CLASS A: FLAME SPREAD INDEX 0-25; SMOKE -DEVELOPED INDEX 0-450.)

(CLASS B: FLAME SPREAD INDEX 26-75; SMOKE -DEVELOPED INDEX 0-450.)

(CLASS C: FLAME SPREAD INDEX 76-200; SMOKE -DEVELOPED INDEX 0-450.)

CLASS II OR BETTER

INTERIOR FLOOR

FINISH (804):

EXIT ENCLOSURES & EXIST PASSAGEWAYS

CORRIDORS

ROOMS & ENCLOSED SPACES

GENERAL NOTES

BOLTS AND THREADED RODS

1. ALL BOLTS & THREADED RODS TO BE ASTM F1554 A36 OR BETTER(U.N.O.)

MASONRY WALL CONSTRUCTION

1. HOLLOW LOAD BEARING UNITS SHALL BE NORMAL WEIGHT, GRADE N,

TYPE 2, CONFORMING TO ASTM C90, WITH A MINIMUM NET COMPRESSIVE

STRENGTH OF 2000 PSI (f'm = 1500 PSI)

2. MORTAR SHALL BE TYPE M OR S, CONFORMING TO ASTM C270

3. HEAD MORTAR JOINTS AT PRECAST WINDOW SILLS TO BE NO MORE THAN

1".

4. COARSE GROUT SHALL CONFORM TO ASTM C476 WITH A MAXIMUM

AGGREGATE SIZE OF 3/8" AND A MINIMUM COMPRESSIVE STRENGTH OF

3000 PSI.

5. VERTICAL REINFORCEMENT SHALL BE AS NOTED ON THE DRAWINGS WITH

CELLS FILLED WITH COARSE GROUT.

6. VERTICAL REINFORCEMENT SHALL BE HELD IN POSITION AT THE TOP AND

BOTTOM. REINFORCEMENT SHALL BE PLACED IN THE CENTER OF THE

MASONRY CELL TYPICAL UNLESS OTHERWISE NOTED.

7. REINFORCING STEEL SHALL BE LAPPED MINIMUM 25" FOR #5 BAR AND 36"

FOR #6 BAR UNLESS NOTED OTHERWISE ON THE DRAWINGS.

8. HOOKS AT TOP & BOTTOM OF VERTICAL REINFORCING BARS TO BOND

BEAM AND FOOTING TO BE NO LESS THAN 12 BAR DIAMETERS EXCLUDING

BEND

9. EXPANSION TYPE ANCHORS ARE NOT TO BE USED IN BOND BEAM.

EMBEDDED ANCHORS OR EPOXY FASTENED STUDS SHALL BE USED.

CAST IN PLACE CONCRETE

1. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH AT

28 DAYS OF 3000 PSI FOR FTG. SLAB & 4000 PSI FOR PIERS, A SLUMP OF

4" PLUS OR MINUS 1", AND HAVE 2 TO 4% AIR ENTRAINMENT, AND A

MAXIMUM WATER/CEMENT RATIO OF 0.58 U.N.O.

2. ALL REINFORCING STEEL SHALL BE NEW DOMESTIC DEFORMED BILLET

STEEL CONFORMING TO ASTM A-615 GRADE 60.

3. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH "THE BUILDING

CODE REQUIREMENTS FOR REINFORCED CONCRETE" ACI 318 LATEST

EDITION, AND "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR

BUILDINGS," ACI 301.

4. HORIZONTAL FOOTING BARS SHALL BE BENT MIN. 48 BAR DIAMETERS

(EXCLUDING BEND) AROUND CORNERS OR #5 CORNER BARS WITH MIN.

30" LAP EXCLUDING BEND AT EACH END SHALL BE PROVIDED.

5. MINIMUM LAP SPLICES ON ALL REINFORCING BARS SHALL BE 48 BAR

DIAMETERS. (U.N.O.)

FOUNDATIONS

1. SOIL TO BE COMPACTED TO AT LEAST 95% UNDER SLABS AND 98% UNDER

FOOTINGS OF MAX. DRY DENSITY AS DETERMINED BY ASTM- 1557

(MODIFIED PROCTOR)

2. THE FOUNDATION OF THIS STRUCTURE HAS BEEN DESIGNED TO AN

ALLOWABLE BEARING CAPACITY OF 2000 PSF. IT IS THE OWNER/

CONTRACTORS RESPONSIBILITY TO VERIFY THAT THE BUILDING SITE WILL

MEET THIS STANDARD WITH REGARDS TO SETTLEMENT AND SUPPORT.

3. PROVIDE TERMITE TREATED SOIL IN ACCORDANCE W/ SECTION 1816 OF

THE FLORIDA BUILDING CODE. IN LIEU OF TREATING THE SOIL,

BORA-CARE TERMITICIDE MAY BE APPLIED TO WOOD COMPONENTS IN

ACCORDANCE TO W/MANUFACTURER'S INSTRUCTIONS, PURSUANT TO

SECTION 1816 OF THE FLORIDA BUILDING CODE.

DESIGN REQUIREMENTS

DESIGN LIVE LOADS(MINIMUM):

A. ROOFS - 20 PSF

WIND DESIGN LOAD INFORMATION-

(PER FBC 2010, REF. ASCE 7-10)

BASIC WIND SPEED (Vult) = 140 MPH (3 SECOND GUST)

(Vasd) = 108 MPH (3 SECOND GUST)

BUILDING CATEGORY = II (ASCE 7-10)

WIND EXPOSURE(ALL SIDES) =C (ASCE 7-10)

INTERNAL PRESSURE COEFFICIENTS (ASCE 7-10)

ENCLOSED BUILDINGS = +/-0.18

PARTIALLY ENCLOSED BUILDINGS = +/-0.55

(NOTE: COEFFICIENTS FOR PARTIALLY ENCLOSED STRUCTURES ARE

APPLIED WHEN DESIGN OF MEMBER(S) FALLS UNDER ASCE 7-10

DEFINITIONS CLASSIFYING AS SUCH)

ALL COMPONENTS AND CLADDING NOT SPECIFIED ON PLANS SHALL BE

DESIGNED TO WITHSTAND THE FOLLOWING PRESSURES (p asd):

FOR WALL LOCATIONS: -38.2 PSF, +28.6 PSF

DBSS, INC.

3662 AVALON PARK EAST BLVD.

SUITE 2072

ORLANDO, FL 32828

PH: 321.251.6006

PRIME PROFESSIONAL

S1

SD1STRUCTURAL DETAILS

S2

LINTEL PLAN S3

BUILDING SECTION

WAREHOUSE FLOOR PLAN

WAREHOUSE/ OFFICE FLOOR PLAN

02

03

04

05

EXTERIOR ELEVATIONS

EXTERIOR ELEVATIONS

LIFE SAFETY PLAN

REFLECTED CEILING PLAN

06 ADA DETAILS & FIRE SEPARATION

S4

CEILING FRAMING PLAN

STRUCTURAL STEEL

1. FABRICATION AND ERECTION OF STRUCTURAL STEEL SHALL BE IN

ACCORDANCE WITH "SPECIFICATION FOR THE DESIGN AND ERECTION OF

STRUCTURAL STEEL FOR BUILDINGS," AISC, 13TH EDITION, AND THE 2010 FBC.

2. STEEL MEMBERS SHALL CONFORM TO THE FOLLOWING MATERIAL

SPECIFICATIONS:

A. PLATES, ANGLES, CHANNELS, TUBES - ASTM A36, Fy=36 KSI

B. PIPE - ASTM A53 GRADE B, Fy=35 KSI

C. W-BEAMS - ASTM A992, Fy=50 KSI

D. HSS (RECT.) - ASTM A500 GRADE B, Fy=46 KSI

E. HSS (ROUND) - ASTM A500 GRADE B, Fy=42 KSI

3. ALL WELDING SHALL BE PERFORMED BY EXPERIENCED, CERTIFIED WELDERS

USING THE ELECTRIC ARC WELDING PROCESS, E70XX SERIES ELECTRODES

FOR WELDING STRUCTURAL STEEL, WELDING SHALL CONFORM TO AISC AND

AWS STANDARD.

4. ALL WELDS NOT SPECIFIED SHALL BE CONTINUOUS FILLET WELDS, SIZE OF

WELD SHALL BE BASED ON ASIC STANDARD FOR THICKER PART JOINED.

5. HOLES FOR BOLTS IN STRUCTURAL STEEL SHALL BE DRILLED OR PUNCHED.

BURNING OF HOLES SHALL NOT BE PERMITTED

6. APPLY CORROSIVE RESISTANT PAINT TO ALL WELDS AND STEEL SURFACES.

LIGHT GAUGE FRAMING

1. ALL LIGHT GAUGE MEMBERS TO BE MIN. 20ga. U.N.O. (USE 18ga. FOR EXTERIOR)

2. ALL FASTENERS TO BE: SELF-DRILLING, SELF-TAPPING SCREWS; STEEL,

COMPLYING WITH ASTM C1002; GALVANIZED COATING, PLATED OR

OIL-PHOSPHATE COATED COMPLYING WITH ASTM B 633 AS NEEDED FOR

REQUIRED CORROSION RESISTANCE.

3. TOUCH-UP PAINT: ZINC RICH, CONTAINING 95-PERCENT METALLIC ZINC.

4. GALVANIZED COATING TO BE: G60 COATING WEIGHT MINIMUM, COMPLYING

WITH ASTM C 955.

5. CUT ALL FRAMING COMPONENTS SQUARELY FOR ATTACHMENT TO FIT AGAINST

ABUTTING MEMBERS. HOLD MEMBERS POSITIVELY IN PLACE UNTIL PROPERLY

FASTENED.

FOUNDATION PLAN

SD2STRUCTURAL DETAILS

S1.1

FOUNDATION PLAN

ELECTRICAL PLANE1

E2 ELECTRICAL PLAN

07 FIRE SEPARATION DETAILS

SD3STRUCTURAL DETAILS

08 FIRE SEPARATION DETAILS

09 FIRE PENETRATION DETAILS

10 FIRE PENETRATION DETAILS

E3 ELECTRICAL PLAN

P2

P1 PLUMBING SUPPLY PLAN

PLUMBING WASTE PLAN

123456789

A

H

F

D

A

H

G

E

C

B

A

A

A

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

01

2

ASSEMBLY FLOOR PLAN

1/8"=1'-0"

REMARKS LEGEND:

1. PROVIDE ADA COMPLIANT LEVER HARDWARE

2. SELF- OR AUTOMATIC CLOSING

3. 45 MIN. FIRE RATED DOOR PER FBC TABLE 715.4

SEE MFG.S.C. WOOD3070 WD. 7'-0"

SQ.FT. CALC'S

WAREHOUSE

PARTS/ TOOL ROOM

OFFICE (A/C AREA)

COVERED REBAR PREFAB.

TOTAL UNDER ROOF

9,076 SQ. FT.

769 SQ. FT.

2,405 SQ. FT.

900 SQ. FT.

13,150 SQ. FT.

DOOR SCHEDULE

MARK TYPE

ROUGH

OPENINGFRAME REMARKS

SEE MFG.3070

MATERIAL

DOOR

HD. HGT.

7'-0"

1

ROLL UP

SEE MFG. 16'-0"

NOTE:

G.C TO FIELD VERIFY WINDOW/

DOOR SIZES PRIOR TO

WINDOW/ DOOR PURCHASE.

140160STEEL STEEL

SEE MFG. 16'-0"180160

STEEL STEEL

ROLL UP

1

REFER TO SHEET 01.1

FOR ENLARGED PLAN

REFER TO SHEET 01.2

FOR ENLARGED PLAN

AS

SE

MB

LY

F

LO

OR

PL

AN

1. WINDOW AND DOOR SUPPLIERS SHALL PROVIDE

CURRENT ROUGH OPENING INFO WHICH SHALL

HAVE PRECEDENCE OVER THE WINDOW AND DOOR

SCHEDULES ON PLAN.

2. DO NOT SCALE PLANS. DIMENSIONS ARE TO BE

FOLLOWED AS NOTED.

3. G.C. TO VERIFY ALL DIMENSIONS WITH FIXTURES

TO BE INSTALLED TO ENSURE COMPLIANCE

4. THE CONTRACTOR SHALL VERIFY ALL CONDITIONS

& DIMENSIONS ON THE SITE PRIOR TO

COMMENCING WORK. ALL INQUIRES &

DISCREPANCIES SHOULD BE DIRECTED TO THE

ENGINEER.

5. ALL APPLIANCE & EQUIPMENT SHOWN ON THE

DRAWINGS ARE BY THE OWNER UNLESS

OTHERWISE NOTED.

6. SEE LIFE SAFTEY PLAN ON SHEET 04 FOR EXIT

LIGHTS AND FIRE EXTINGUISHERS.

7. ALL MILLWORK TO BE FIELD MEASURED/VERIFIED

BEFORE FABRICATION.

8. DOOR OPENINGS WHICH OCCUR CLOSE TO INSIDE

CORNERS SHALL BE 6" FROM CORNERS.

GENERAL NOTES:

LEGEND

HATCH INDICATES NEW CMU WALL

T.O.W. @10'-0" A.F.F.

COMPONENT DESIGN PRESSURE (p asd)

INDICATES GROUT FILLED CELL WITH

(1) VERT. REINF. CONT. FTG. TO BOND

BEAM (SPACING & BAR SIZE PER PLAN)

(REFER TO NOTES ON COVER SHEET)

HATCH INDICATES NEW 6" CMU

PARTITION WALL T.O.W. @ 6'-8" A.F.F.

HATCH INDICATES NEW CMU WALL

T.O.W. @11'-4" A.F.F.

STEEL STEEL

SEE MFG.3070 7'-0"

1,2,3

STEEL STEEL

HATCH INDICATES NEW CMU WALL

T.O.W. @11'-4" A.F.F. 2 HOUR

SEPARATION, REFER DETAIL 4/06

SEE MFG.S.C. WOOD(2) 3070 WD. 7'-0"

1

SEE MFG.STEEL3060 STEEL 6'-0"

STALL DOOR

SEE MFG.STEEL2060 STEEL 6'-0"

STALL DOOR

A

56789

A

I

G

E

C

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

01.1

3

FLOOR PLAN

1/4"=1'-0"

NOTE:

REFER TO SHEET 01 FOR NOTES,

LEGENDS AND DOOR SCHEDULE

RE

FE

R T

O S

HE

ET

01.2 F

OR

C

ON

TIN

UA

TIO

N O

F F

LO

OR

P

LA

N

WAREHOUSE

WA

RE

HO

US

E

FL

OO

R P

LA

N

A

A

1234

I

H

F

D

B

A

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

4

NOTE:

REFER TO SHEET 01 FOR NOTES,

LEGENDS AND DOOR SCHEDULE

RE

FE

R T

O S

HE

ET

01.1 F

OR

C

ON

TIN

UA

TIO

N O

F F

LO

OR

P

LA

N

FLOOR PLAN

1/4"=1'-0"

OFFICE

WA

RE

HO

US

E/ O

FF

IC

E

FL

OO

R P

LA

N

WAREHOUSE/

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

REAR ELEVATION

1/8"=1'-0"

LEFT ELEVATION

1/4"=1'-0"

5

02

EX

TE

RIO

R

EL

EV

AT

IO

NS

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

FRONT ELEVATION

1/8"=1'-0"

RIGHT ELEVATION

1/4"=1'-0"

6

03

EX

TE

RIO

R

EL

EV

AT

IO

NS

123456789

A

H

F

D

A

H

G

E

C

B

A

A

A

1

33" 33"

33"

2

3

3

4

3

33"

33"

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

04

7

LIF

E S

AF

ET

Y P

LA

N

LIFE SAFETY PLAN

1/8"=1'-0"

LIFE SAFTEY PLAN LEGEND

#CLEAR WIDTH OF EGRESS DOOR (IN INCHES)

#

GENERAL NOTES:

1. THE LIFE SAFETY PLANS ARE "DIAGRAMMATIC ONLY".

THEIR PURPOSE IS SOLELY TO REPRESENT THE LIFE

SAFETY COMPONENTS FOR THE PROJECT. THE

GENERAL CONTRACTOR SHALL USE THE

CONSTRUCTION DOCUMENTS (NOT THE LIFE SAFETY

PLANS) FOR THE IMPLEMENTATION OF THE

REQUIRED LIFE SAFETY COMPONENTS INTO THE

PROJECT.

2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR

FIELD VERIFYING THAT THE REQUIRED VISIBILITY

FOR EACH INDIVIDUALLY INSTALLED EXIST LIGHT IS

NOT IN ANY WAY DIMINISHED DUE TO VIDAL

INTERFERENCE CAUSE BY ANY OTHER LIGHT

FIXTURE, DEVICE, SIGN, ETC.

3. EMERGENCY LIGHTING TO BE CONNECTED TO A

LOCAL LIGHTING CIRCUIT.

4. FIRE EXTINGUISHER TO BE CLASS "A" MINIMUM FIRE

EXTINGUISHER. THE TOP OF THE EXTINGUISHER

SHALL NOT BE MORE THAN 5 FT. ABOVE THE FLOOR

AND THE BOTTOM OF THE EXTINGUISHER SHALL

NOT BE LESS THAN 4 INCHES ABOVE THE FLOOR.

PROVIDE CLASS, RATING AND DISTRIBUTION IN

ACCORDANCE WITH NFPA 10.

TACTILE EXIT SIGN

EXIT

48

" M

IN

.

60

" M

AX

.

TO

F

IN

. F

LR

.

CORRESPONDING

GRADE II BRAILLE

C

L

FONT & SIGN IN

ACCORDANCE w/

ICC/ANSI A117.1

SECTION 703

40

" M

IN

.

60

" M

AX

.

TO

F

IN

. F

LR

.

C

L

CALCULATIONS FOR OCCUPANT LOADS

AREA

DESIGNATION

AREA

(SQ. FT.)

OCCUPANT LOAD

FACTOR

#

1

OCCUPANT

LOAD

FUNCTION OF

SPACE

9077

TOTAL11,936 SF

N/A 118

500 18

2

733 300 3

3

1257 100 13 BUSINESS

NOTES:

1. WITHOUT FIXED SEATS- LESS CONCENTRATED (TABLES AND CHAIRS)

STORAGE

NEW 11'-4" WALL PER FLOOR PLAN

FIRE EXTINGUISHER

TRAVEL DISTANCE TO EXIT DOOR

EXIT LIGHT

DIRECTIONAL EXIT LIGHT

EMERGENCY LIGHT FIXTURE

4

859 15 57

ASSEMBLY

(REFER TO NOTE 1)

NEW 10'-0" WALL PER FLOOR PLAN

WAREHOUSE

NEW FIRE SEPARATION PER PLAN

A

H

G

E

C

B

A

A

A

B

C

D

A

A

B

B

C

C

C

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

05

8

REFLECTED CEILING PLAN

1/4"=1'-0"

RE

FL

EC

TE

D

CE

IL

IN

G P

LA

N

2'x4' FLUORESCENT FIXTURE EXHAUST FAN

LEGEND

1

CEILING GRID SUPPORT

DETAIL

N.T.S.

NOTE:

REFER TO LIFE SAFETY PLAN (SHEET 04) FOR

EMERGENCY LIGHT AND EXIT LIGHT LOCATIONS.

LIGHT FIXTURE, HANGING OUTLET 110-115, CEILING MOUNTED

GRAB BAR

ATTACHMENT

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

9

06

DE

TA

IL

S

2

ADA RESTROOM

DETAILS

N.T.S.

1

ADA BATHROOM

LAYOUT

3/4"=1'-0"

3

ADA DRINKING

FOUNTAIN

N.T.S.

Design No. U905

May 19, 2014

Bearing Wall Rating -- 2 HR.

Nonbearing Wall Rating -- 2 HR

1. Concrete Blocks* -- Various designs. Classification D-2 (2 hr). See Concrete

Blocks category for list of eligible manufacturers.

2. Mortar -- Blocks laid in full bed of mortar, nom. 3/8 in. thick, of not less than 2-1/4 and not more than

3-1/2 parts of clean sharp sand to 1 part Portland cement (proportioned by volume) and not more than 50

percent hydrated lime (by cement volume). Vertical joints staggered.

3. Portland Cement Stucco or Gypsum Plaster -- Add 1/2 hr to classification if used. Where combustible

members are framed in wall, plaster or stucco must be applied on the face opposite framing to achieve a

max. Classification of

1-1/2 hr. Attached to concrete blocks (Item 1).

4. Loose Masonry Fill -- If all core spaces are filled with loose dry expanded slag, expanded clay or shale

(Rotary Kiln Process), water repellant vermiculite masonry fill insulation, or silicone treated perlite loose fill

insulation add 2 hr to classification.

5. Foamed Plastic* -- (Optional-Not Shown) -- 1-1/2 in. thick max, 4 ft wide sheathing attached to concrete blocks

(Item 1).

ATLAS ROOFING CORP -- "EnergyShield Pro Wall Insulation" and "EnergyShield Pro 2 Wall Insulation."

HUNTER PANELS -- Type Xci-Class A, Xci 286

THE DOW CHEMICAL CO -- Type Thermax Sheathing, Thermax Light Duty Insulation, Thermax Heavy

Duty Insulation, Thermax Metal Building Board, Thermax White Finish Insulation, Thermax ci Exterior

Insulation, Thermax IH Insulation, Thermax Plus Liner Panel and Thermax Heavy Duty Plus (HDP)

*Bearing the UL Classification Mark

4

UL RATED ASSEMBLY

2 HR. RATED - BEARING WALL

N.T.S.

12

3

4

HORIZONTAL SECTION

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

10

07

FIR

E S

EP

AR

AT

IO

N

DE

TA

IL

S

1

UL RATED ASSEMBLY

2 HR. RATED - NON- BEARING WALL

N.T.S.

Design No. U411February 25, 2015

Nonbearing Wall Rating -- 2 HR.* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions

employing the UL or cUL Certification (such as Canada), respectively.

1. Floor and Ceiling Runner -- (Not Shown) -- Min. 25 MSG galv steel, 1 in. return legs,2-1/2 in. deep (min), attached to floor and ceiling with fasteners 24 in. OC max.1A. Framing Members*-- Floor and Ceiling Runners -- (Not shown) -- As an alternateto Item 1 - For use with Item 2A, channel shaped, min 2-1/2 in. deep, attached to floor andceiling with fasteners 24 in. OC. max.ALLSTEEL & GYPSUM PRODUCTS INC -- Type SUPREME Framing System

CALIFORNIA EXPANDED METAL PRODUCTS CO -- Viper20™ Track

CONSOLIDATED FABRICATORS CORP, BUILDING PRODUCTS DIV -- TypeSUPREME Framing System

MARINO/WARE, DIV OF WARE INDUSTRIES INC -- Viper20™ Track

PHILLIPS MFG CO L L C -- Viper20™ Track

QUAIL RUN BUILDING MATERIALS INC -- Type SUPREME Framing System

SCAFCO STEEL STUD MANUFACTURING CO -- Type SUPREME Framing System

STEEL CONSTRUCTION SYSTEMS INC -- Type SUPREME Framing System

UNITED METAL PRODUCTS INC -- Type SUPREME Framing System

1B. Floor and Ceiling Runners -- (Not shown)--For use with Item 2B- Channel shaped,fabricated from min 20 MSG corrosion-protected or galv steel, min width to accommodatestud size, with min 1 in. long legs, attached to floor and ceiling with fasteners spaced max24 in. OC.1C. Framing Members*-- Floor and Ceiling Runners -- (Not shown) -- As an alternate toItem 1 - For use with Item 2C, channel shaped, min 2-1/2 in. wide fabricated from min0.015 in. thick galv steel, attached to floor and ceiling with fasteners 24 in. OC. max.CLARKDIETRICH BUILDING SYSTEMS -- CD ProTRAK

DMFCWBS L L C -- ProTRAK

MBA METAL FRAMING -- ProTRAK

RAM SALES L L C -- Ram ProTRAK

STEEL STRUCTURAL SYSTEMS L L C -- Tri-S ProTRAK

1D. Framing Members*-- Floor and Ceiling Runners -- (Not shown) -- As an alternateto Item 1 - For use with Item 2D, channel shaped, min 2-1/2 in. wide fabricated from min0.018 in. thick galv steel, attached to floor and ceiling with fasteners 24 in. OC. max.TELLING INDUSTRIES L L C -- TRUE-TRACK™

1E. Framing Members*-- Floor and Ceiling Runners -- (Not shown) -- As an alternate toItem 1 - For use with Item 2E, channel shaped, min 2-1/2 in. wide fabricated from min 25MSG steel, attached to floor and ceiling with fasteners 24 in. OC. max.KIRII (HONG KONG) LTD -- Type KIRII

1F. Floor and Ceiling Runners -- (Not shown) -- Channel shaped, fabricated from min0.02 in. galv steel, min width to accommodate stud size, with min 1 in. long legs, for usewith studs specified below and fabricated from min 0.02 in. galv steel or thicker, attached tofloor and ceiling with fasteners spaced max 24 in. OC.MARINO/WARE, DIV OF WARE INDUSTRIES INC -- Viper20™ Track VT100.

1G. Framing Members*-- Floor and Ceiling Runners -- (Not shown) -- As an alternateto Item 1 - For use with Item 2G, channel shaped, min 2-1/2 in. deep, attached to floor andceiling with fasteners 24 in. OC. max.TELLING INDUSTRIES L L C -- Viper20™ Track

2. Steel Studs -- Min 2-1/2 in. deep, formed of min 25 MSG galv steel max stud spacing 24in. OC. Studs to be cut 3/4 in. less than assembly height.2A. Framing Members*-- Steel Studs -- As an alternate to Item 2 - For use with Item 1G,channel shaped studs, min 2-1/2 in. deep, spaced a max of 24 in. OC. Studs to be cut 3/4 in.less than assembly height.ALLSTEEL & GYPSUM PRODUCTS INC -- Type SUPREME Framing System

CALIFORNIA EXPANDED METAL PRODUCTS CO -- Viper20™

CONSOLIDATED FABRICATORS CORP, BUILDING PRODUCTS DIV -- TypeSUPREME Framing System

MARINO/WARE, DIV OF WARE INDUSTRIES INC -- Viper20™

PHILLIPS MFG CO L L C -- Viper20™

QUAIL RUN BUILDING MATERIALS INC -- Type SUPREME Framing System

SCAFCO STEEL STUD MANUFACTURING CO -- Type SUPREME Framing System

STEEL CONSTRUCTION SYSTEMS INC -- Type SUPREME Framing System

UNITED METAL PRODUCTS INC -- Type SUPREME Framing System

2B. Steel Studs -- (As an alternate to Item 2, For use with Item 4D) Channel shaped,fabricated from min 20 MSG corrosion-protected or galv steel, 3-1/2 in. min depth, spaced amax of 16 in. OC. Studs friction-fit into floor and ceiling runners. Studs to be cut 5/8 to 3/4in. less than assembly height.2C. Framing Members*-- Steel Studs -- As an alternate to Item 2 - For use with Item 1C,channel shaped studs, min 2-1/2 in. wide fabricated from min 0.015 in. thick galv steel,spaced a max of 24 in. OC. Studs to be cut 3/4 in. less than assembly height.CLARKDIETRICH BUILDING SYSTEMS -- CD ProSTUD

DMFCWBS L L C -- ProSTUD

MBA METAL FRAMING -- ProSTUD

RAM SALES L L C -- Ram ProSTUD

STEEL STRUCTURAL SYSTEMS L L C -- Tri-S ProSTUD

2D. Framing Members*-- Steel Studs -- As an alternate to Item 2 - For use with Item 1D,channel shaped studs, min 2-1/2 in. wide fabricated from min 0.018 in. thick galv steel,spaced a max of 24 in. OC. Studs to be cut 3/4 in. less than assembly height.TELLING INDUSTRIES L L C -- TRUE-STUD™

2E. Framing Members*-- Steel Studs -- As an alternate to Item 2 - For use with Item 1E,channel shaped studs, min 2-1/2 in. wide fabricated from min 25 MSG steel, spaced a maxof 24 in. OC. Studs to be cut 3/4 in. less than assembly height.KIRII (HONG KONG) LTD -- Type KIRII

2F. Framing Members*-- Steel Studs -- As an alternate to Item 2 - For use with Item 1G,channel shaped studs, min 2-1/2 in. deep, spaced a max of 24 in. OC. Studs to be cut 3/4 in.less than assembly height.TELLING INDUSTRIES L L C -- Viper20™

2G. Framing Members*-- Steel Studs -- As an alternate to Item 2 - For use with Item 1,channel shaped studs, Min 2-1/2 in. deep, formed of min 25 MSG galv steel max studspacing 24 in. OC. Studs to be cut 3/4 in. less than assembly height.E.B. METAL INC -- EB Stud

2H. Framing Members*-- Steel Studs -- As an alternate to Item 2 - For use with Item 1,channel shaped studs, Min 2-1/2 in. deep, formed of min 25 MSG galv steel max studspacing 24 in. OC. Studs to be cut 3/4 in. less than assembly height.OLMAR SUPPLY INC -- PRIMESTUD

3. Batts and Blankets* -- (Optional) -- Mineral wool or glass fiber batts partially orcompletely filling stud cavity.See Batts and Blankets (BZJZ) category for names of manufacturers.3A. Fiber, Sprayed* -- As an alternate to Batts and Blankets (Item 3) -- (100% BorateFormulation) -- Spray applied cellulose material. The fiber is applied with water tocompletely fill the enclosed cavity in accordance with the application instructions suppliedwith the product with a nominal dry density of 2.7 lb/ft3. Alternate Application Method:The fiber is applied without water or adhesive at a nominal dry density of 3.5 lb/ft3, inaccordance with the application instructions supplied with the product.U S GREENFIBER L L C -- INS735& INS745 for use with wet or dry application.INS765LD and INS770LD are to be used for dry application only.

3B. Fiber, Sprayed* -- As an alternate to Batts and Blankets (Item 3) and Item 3A - Sprayapplied cellulose insulation material. The fiber is applied with water to interior surfaces inaccordance with the application instructions supplied with the product. Applied tocompletely fill the enclosed cavity. Minimum dry density of 4.3 pounds per cubic ft.NU-WOOL CO INC -- Cellulose Insulation

3C. Fiber, Sprayed* -- As an alternate to Batts and Blankets (Item 3) - Spray appliedcellulose fiber. The fiber is applied with water to completely fill the enclosed cavity inaccordance with the application instructions supplied with the product. The minimum drydensity shall be 4.30 lbs/ft3.INTERNATIONAL CELLULOSE CORP -- Celbar-RL

4. Gypsum Board* -- 5/8 in. thick, outer layer paper, glass mat or vinyl surfaced.(Laminated System) Gypsum board applied vertically in two layers. Inner layer attached tostuds with 1 in. long Type S steel screws spaced 8 in. OC along vertical edges, and 12 in.OC in the field and outer layer laminated to inner layer with joint compound, applied with anotched spreader producing continuous beads of compound about 3/8 in. in diameter,spaced not greater than 2 in. OC. Joints of laminated outer layer offset 12 in. from innerlayer joints Outer layer gypsum board attached to floor and ceiling runner track with 1-5/8in. long Type S steel screws spaced 12 in. OC.Optional, (Direct Attached System), Inner layer attached to studs with 1 in. long Type Ssteel screws spaced 16 in. OC in the field and along the vertical edges. Outer layer attachedto the studs over the inner layer with 1-5/8 in. long Type S steel screws spaced 16 in. OC inthe field and along the vertical edges and 12 in. OC to the floor and ceiling runners. Jointsof screw-attached outer layer offset from inner layer joints. Joints of outer layer may betaped or untaped.Nom 3/32 in. thick gypsum veneer plaster may be applied to the entire surface of Classifiedveneer baseboard. Joints reinforced.ACADIA DRYWALL SUPPLIES LTD -- Type X, 5/8 Type X, Type Blueglass ExteriorSheathing

AMERICAN GYPSUM CO -- Types AG-C, AGX-1, M-Glass, AGX-11.

BEIJING NEW BUILDING MATERIALS PUBLIC LTD CO -- Type DBX-1.

CERTAINTEED GYPSUM INC -- Types 1, FRPC, EGRG, GlasRoc, Type X or Type C,5/8" Easi-Lite Type X.

CGC INC -- Type AR, C, IP-AR, IP-X1, IP-X2, IPC-AR, SCX, SHX, WRC or WRX.

CONTINENTAL BUILDING PRODUCTS OPERATING CO, L L C -- TypesLGFC2A, LGFC6A, LGFC-C/A, LGFC-WD, LGLLX.

GEORGIA-PACIFIC GYPSUM L L C -- Types 5, 6, 9, C, DAP, DD, DA, DAPC, DGG,DS, GPFS6, LS, TG-C, Type X, Veneer Plaster Base-Type X, Water Rated-Type X,Sheathing Type-X, Soffit-Type X, GreenGlass Type X, Type X ComfortGuard SoundDeadening Gypsum Board, Type LWX, Veneer Plaster Base-Type LWX, WaterRated-Type LWX, Sheathing Type-LWX, Soffit-Type LWX, Type DGLW, WaterRated-Type DGLW, Sheathing Type- DGLW, Soffit-Type DGLW, Type LW2X, VeneerPlaster Base - Type LW2X, Water Rated - Type LW2X, Sheathing - Type LW2X, Soffit -Type LW2X, Type DGL2W, Water Rated - Type DGL2W, Sheathing - Type DGL2W.

NATIONAL GYPSUM CO -- Types eXP-C, FSK, FSK-C, FSW, FSW-3, FSW-5, FSW-6,FSW-8, FSW-C, FSW-G, FSMR-C, FSL, SoundBreak XP Type X Gypsum Board.

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

11

08

FIR

E S

EP

AR

AT

IO

N

DE

TA

IL

S

1

UL RATED ASSEMBLY

2 HR. RATED - NON- BEARING WALL

N.T.S.

PABCO BUILDING PRODUCTS L L C, DBA PABCO GYPSUM -- Type C, PG-3,PG-5, PG-9, PG-11, PG-C, PGS-WRS.

PANEL REY S A -- Types GREX, PRX, RHX, MDX, ETX or PRC.

SIAM GYPSUM INDUSTRY (SARABURI) CO LTD -- Type EX-1

THAI GYPSUM PRODUCTS PCL -- Type C or Type X

UNITED STATES GYPSUM CO -- Type AR, C, FRX-G, IP-AR, IP-X1, IP-X2, IPC-AR,SCX, SGX, SHX, WRC, WRX, USGX.

USG MEXICO S A DE C V -- Type AR, C, IP-AR, IP-X1, IP-X2, IPC-AR, SCX, SHX,WRC or WRX.

4A. Gypsum Board* -- (As an alternate to Item 4) -- Nom 3/4 in. thick, installed asdescribed in Item 4 with 1-1/4 in. long Type S screws for inner layer and 2-1/4 in. longType S screws for outer layer.CGC INC -- Types AR, IP-AR.

UNITED STATES GYPSUM CO -- Types AR, IP-AR.

USG MEXICO S A DE C V -- Types AR, IP-AR.

4B. Gypsum Board* -- (As an alternate to Item 4 and 4A) --5/8 in. thick, 24 to 54 in. wide,applied horizontally as the outer layer to one side of the assembly. Horizontal joints neednot be backed by steel framing. Secured as described in Item 4 for the direct attachedsystem. When used in widths other than 48 in., gypsum panels to be installed horizontally.CERTAINTEED GYPSUM INC -- Type X, Type C.

CGC INC -- Type SHX.

THAI GYPSUM PRODUCTS PCL -- Type X, Type C.

UNITED STATES GYPSUM CO -- Type SHX, FRX-G.

USG MEXICO S A DE C V -- Type SHX.

4C. Gypsum Board* -- (As an alternate to Items 4, 4A and 4B) -- Two layers of 5/8 in.thick gypsum board applied horizontally or vertically. Inner layer attached to studs with No.6 by 1 in. long Type S bugle head screws spaced 24 in. OC along the top and bottom tracksstarting 2 in. and then 12 in. from the vertical edge. Inner layer screws spaced 24 in. OCalong the studs, starting 2 in. and then 12 in. from the top and bottom of the studs andstarting 1-1/4 in. from the horizontal joints when installed horizontally. Outer layer attachedto studs with 1-5/8 in. long Type S bugle head screws spaced 16 in. OC along the top andbottom tracks starting 1-3/4 in. from the vertical edge. Outer layer screws spaced 16 in. OCalong the studs, starting 1-3/4 in. and then 8 in. from the top and bottom of the studs andstarting 1-1/4 in. and then 8 in. from the horizontal joints when installed horizontally.Vertical joints centered over studs and staggered one stud cavity on opposite sides of studs.Vertical joints in adjacent layers staggered one stud cavity. Horizontal joints need not bebacked by steel framing. Horizontal edge joints and horizontal butt joints on opposite sidesof studs need not be staggered. Horizontal edge joints and horizontal butt joints in adjacentlayers staggered a min of 12 in. When outer layers are installed horizontally, vinyl or casein,dry or premixed joint compound shall be applied in two coats to joints and screw heads ofouter layer. Paper tape, nom 2 in. wide, embedded in first layer of compound over all jointsof outer layer panels. Nom 3/32 in. thick gypsum veneer plaster may be applied to the entiresurface of Classified veneer baseboard. Joints reinforced.GEORGIA-PACIFIC GYPSUM L L C -- Types 5, 6, 9, C, DAP, DD, DA, DAPC, DGG,DS, GPFS6, LS, TG-C, Type X, Veneer Plaster Base-Type X, Water Rated-Type X,Sheathing Type-X, Soffit-Type X, GreenGlass Type X, Type X ComfortGuard SoundDeadening Gypsum Board, Type LWX, Veneer Plaster Base-Type LWX, WaterRated-Type LWX, Sheathing Type-LWX, Soffit-Type LWX, Type DGLW, WaterRated-Type DGLW, Sheathing Type- DGLW, Soffit-Type DGLW, Type LW2X, VeneerPlaster Base - Type LW2X, Water Rated - Type LW2X, Sheathing - Type LW2X, Soffit -Type LW2X, Type DGL2W, Water Rated - Type DGL2W, Sheathing - Type DGL2W.

4D. Gypsum Board* -- (Not Shown) - (As an alternate to Item 4 when used as the baselayer on one or both sides of wall. For direct attachment only to steel studs Item 2B) - Nom5/8 in. thick lead backed gypsum panels with beveled, square or tapered edges, appliedvertically. Vertical joints centered over studs and staggered min 1 stud cavity on oppositesides of studs. Gypsum board secured to studs with 1-1/4 in. long Type S-12 steel screws

spaced 8 in. OC at perimeter and 12 in. OC in the field.RAY-BAR ENGINEERING CORP -- Type RB-LBG

4E. Gypsum Board* -- (As an alternate to Items 4 through 4D) -- Nominal 5/8 in. thick, 4ft wide panels, applied vertically and secured as described in Item 4.PABCO BUILDING PRODUCTS L L C, DBA PABCO GYPSUM -- Types QuietRockES.

4F. Gypsum Board* -- (As an alternate to Items 4 through 4E ) - 5/8 in. thick, 4 ft. wide,paper surfaced, applied vertically and secured as described in Item 4.CERTAINTEED GYPSUM INC -- Type SilentFX

4G. Gypsum Board* -- As an alternate to Item 4- Nom. 5/8 in. thick, inner layer attachedvertically to studs with 1 in. long Type S steel screws spaced 16 in. OC in the field andalong the vertical edges. Outer layer attached to the studs horizontally over the inner layerwith 1-5/8 in. long Type S steel screws spaced 16 in. OC in the field and along the verticaledges and 12 in. OC to the floor and ceiling runners. Joints of outer layer must be taped.Nom 3/32 in. thick gypsum veneer plaster may be applied to the entire surface of Classifiedveneer baseboard.ACADIA DRYWALL SUPPLIES LTD -- Type Blueglass Exterior Sheathing

PABCO BUILDING PRODUCTS L L C, DBA PABCO GYPSUM -- Types C, PG-11,PGS-WRS.

4H. Gypsum Board* -- (Not Shown) - (As an alternate to Items 4) For Direct Applicationto Studs Only- For use as the base layer on one or both sides of the wall. Nom 5/8 in. thicklead backed gypsum panels with beveled, square or tapered edges, applied vertically.Vertical joints centered over studs and staggered min 1 stud cavity on opposite sides ofstuds. Wallboard secured to studs with 1-5/8 in. long Type S 12 steel screws spaced 8 in.OC at perimeter and 12 in OC in the field. Lead batten strips required behind vertical jointsof lead backed gypsum wallboard and optional at remaining stud locations. Fasteners forface layer gypsum panels when installed over lead backed board to be min 2-1/2 in. TypeS-12 bugle head steel screws spaced as described in Item 4. To be used with Lead BattenStrips (see Item 5A) or Lead Discs (see Item 6A).MAYCO INDUSTRIES INC -- Type X-Ray Shielded Gypsum

4I. Gypsum Board* -- (As an alternate to Item 4, not for use with Items 1C and 2C) - Nom.5/8 in. thick gypsum panels with beveled, square or tapered edges installed as described inItem 4.CGC INC -- Type ULX

UNITED STATES GYPSUM CO -- Type ULX.

USG MEXICO S A DE C V -- Type ULX

4J. Gypsum Board* -- (As an alternate to Item 4 when used as the base layer on one orboth sides of wall. For direct attachment only to steel studs Item 2B). Nom 5/8 in. thick leadbacked gypsum panels with beveled, square or tapered edges, applied vertically. Verticaljoints centered over studs and staggered min 1 stud cavity on opposite sides of studs.Wallboard secured to studs with 1-1/4 in. long Type S-12 steel screws gypsum panel steelscrews spaced 8 in. OC at perimeter and 12 in. OC in the field. Lead batten strips requiredbehind vertical joints of lead backed gypsum wallboard and optional at remaining studlocations. Lead batten strips, min 2 in. wide, max 8 ft long with a max thickness of 0.14 in.placed on the face of studs and attached to the stud with construction adhesive and two 1 in.long Type S-12 pan head steel screws, one at the top of the strip and one at the bottom ofthe strip. Lead discs, nominal 3/8 in. diam by max 0.085 in. thick. Compression fitted oradhered over the screw heads. Lead batten strips and discs to have a purity of 99.9%meeting the Federal specification QQ-L-201f, Grade "C".RADIATION PROTECTION PRODUCTS INC -- Type RPP - Lead Lined Drywall

4K. Gypsum Board -- (As an alternate to Items 4 through 4J, not for use with Items 1C and2C). Two layers of nominal 15 mm thick gypsum board applied vertically. Inner layerattached to studs with No. 3.5 x 1-3/8 in. long bugle head, self-drilling screws spaced 23-5/8in. OC in the field and 15-3/4 in. OC in the perimeter, with the first screw 2 in. from theedge. Outer layer attached to the studs over the inner layer with No. 3.5 x 1-3/4 in. longbugle head, self-drilling screws spaced 11-13/16 in. OC in the field and 7-7/8 in. OC in theperimeter, with the first screw 3/4 in. from the edge. Outer layer screws staggered frominner layer screws. Vertical joints centered over studs and staggered one stud cavity onopposite sides of studs. Vertical joints in adjacent layer staggered one stud cavity.Self-adhesive fiberglass mesh (9x9 mesh) tape, nom 2 in. wide, applied over all joints of

outer layer panels. Dry or premixed joint compound applied in two coats to joints over themesh tape and screw heads of outer layer.GYPSEMNA CO LLC -- Types MRFW, FW, TF.

4L. Gypsum Board* -- (As an alternate to Items 4 through 4K) - Two layers of 5/8 in.thick gypsum board applied vertically or horizontally. Inner layer attached to studs with #6x 1 in. long bugle head screws spaced 12 in. OC along the top and bottom tracks and 16 in.OC in the field and along the vertical edges. Outer layer attached to studs with #6 x 1-5/8 in.long bugle head screws spaced 12 in. OC along the top and bottom tracks and 16 in. OC inthe field and along the vertical edges. Vertical joints are centered over studs and staggeredbetween layers and on opposite sides of the wall. Horizontal joints on the face layer arestaggered 12 in. from the base layer. Horizontal joints need not to be backed by steelframing.CONTINENTAL BUILDING PRODUCTS OPERATING CO, L L C -- TypeLGFC6A, LGFC-C/A.

4M. Wall and Partition Facings and Accessories* -- (As an alternate to Items 4 through4L) -- Nominal 5/8 in. thick, 4 ft wide panels, applied vertically and secured as described inItem 4.PABCO BUILDING PRODUCTS L L C, DBA PABCO GYPSUM -- Type QuietRock527.

4N. Gypsum Board* -- (As an alternate to Item 4 through 4M) - For direct application tostuds only - Four layers nom. 5/16 in. thick gypsum panels applied vertically orhorizontally. When applied horizontally, base layer secured to studs with 1 in. Type Sscrews spaced 24 in. OC. Second layer installed with joints offset 12 in. from base layer andsecured with 1 in. Type S screws spaced 24 in. OC. Third layer installed with joints in linewith base layer and secured with 1-1/2 in. Type S screws spaced 16 in. OC. Fourth layerinstalled with joints in line with second layer and secured with 1-5/8 in. Type S screwsspaced 12 in. OC. For all layers, screws offset 4 in. from previous layer. When appliedvertically, base layer secured with 1 in. Type S screws spaced 24 in. OC. Second layersecured with joints offset one stud cavity and secured with 1 in. Type S screws spaced 24 in.OC. Third layer installed with joints in line with base layer and secured with 1-1/2 in. TypeS screws spaced 12 in. OC. Fourth layer secured with joints in line with second layer andsecured with 1-5/8 in. Type S screws spaced 8 in. OC along vertical edges and 12 in. OC inthe field. For all layers, screws offset 4 in. from previous layer.NATIONAL GYPSUM CO -- Type FSW

5. Lead Batten Strips -- (Not Shown, For Use With Item 4D) - Lead batten strips, min1-1/2 in. wide, max 10 ft long with a max thickness of 0.125 in. Strips placed on the interiorface of studs and attached from the exterior face of the stud with two 1 in. long Type S-12pan head steel screws, one at the top of the strip and one at the bottom of the strip. Leadbatten strips to have a purity of 99.9% meeting the Federal specification QQ-L-201f, Grade"C". Lead batten strips required behind vertical joints of lead backed gypsum board (Item4D) and optional at remaining stud locations. Required behind vertical joints.5A. Lead Batten Strips -- (Not Shown, for use with Item 4H) Lead batten strips, 2 in.wide, max 10 ft long with a max thickness of0.140 in. Strips placed on the face of studs andattached to the stud with two min. 1 in. long min. Type S-8 pan head steel screws, one at thetop of the strip and one at the bottom of the strip or with one min. 1 in. long min. Type S-8pan head steel screw at the top of the strip. Lead batten strips to have a purity of 99.5%meeting the Federal specification QQ-L-201f, Grades "B, C or D". Lead batten stripsrequired behind vertical joints of lead backed gypsum wallboard (Item 6) and optional atremaining stud locations.6. Lead Discs or Tabs -- (Not Shown, For Use With Item 4D) - Used in lieu of or inaddition to the lead batten strips (Item 5) or optional at other locations - Max 3/4 in. diamby max 0.125 in. thick lead discs compression fitted or adhered over steel screw heads ormax 1/2 in. by 1-1/4 in. by max 0.125 in. thick lead tabs placed on gypsum boards (Item4D) underneath screw locations prior to the installation of the screws. Lead discs or tabs tohave a purity of 99.9% meeting the Federal specification QQ-L-201f, Grade "C".6A. Lead Discs -- (Not Shown, for use with Item 4H) Max 5/16 in. diam by max0.140 in.thick lead discs compression fitted or adhered over steel screw heads. Lead discs to have apurity of 99.5% meeting the Federal Specification QQ-L-201f, Grades "B, C or D".7. Mineral and Fiber Board* -- (Optional, Not shown) -- For optional use as an additionallayer on one side of wall. Nom 1/2 in. thick, 4 ft wide with long dimension parallel andcentered over studs. Attached to studs and floor and ceiling runners with 1-5/8 in. long TypeS steel screws, spaced 12 in. OC. The required UL Classified gypsum board layer(s) is/areto be installed as indicated as to fastener type and spacing, except that the required fastenerlength shall be increased by a minimum of 1/2 in. Not evaluated or intended as a substitutefor the required layer(s) of UL Classified Gypsum Board.HOMASOTE CO -- Homasote Type 440-32

* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictionsemploying the UL or cUL Certification (such as Canada), respectively.

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

12

09

FIR

E S

EP

AR

AT

IO

N

DE

TA

IL

S

System No. W-L-2059

F Ratings - 1 and 2 Hr (See Items 2 and 3)

T Ratings - 3/4, 1, 1-1/2 and 2 Hr (See Items 2 and 3)

L Rating At Ambient - 1 CFM/sq ft

L Rating At 400 F - Less Than 1 CFM/sq ft

1. Wall Assembly - The 1 or 2 h fire rated gypsum board/stud wall assembly shall be constructed

of the materials and in the manner described in the individual U300, U400 and V400 Series

Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following

construction features:

A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs

to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel

studs to be min 2-1/2 in. (64 mm) wide and spaced max 24 in. (610 mm) OC.

B. Gypsum Board* - 5/8 in. (16 mm) thick, 4 ft (1219 mm) wide with square or tapered edges.

The gypsum board type, thickness, number of layers, fastener type and sheet orientation

shall be as specified in the individual U300, U400 or V400 Series Design in the UL Fire

Resistance Directory. Max diam of opening is 5 in. (127 mm).

2. Through-Penetrants - One nonmetallic pipe or conduit to be centered within the firestop

system. The annular space shall be max 1/4 in. (6 mm). Pipe or conduit to be rigidly supported

on both sides of the wall assembly. The following types and sizes of nonmetallic pipes or

conduits may be used:

A. Polyvinyl Chloride (PVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 or 80

solid or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste

or vent) piping systems. When Schedule 80 PVC pipe is used, the F and T Ratings are 1

hr. When Scheduled 80 PVC pipe is used in closed (process or supply) piping

systems, the F and T Ratings are equal to the assembly rating of the wall in which it

is installed.

B. Rigid Nonmetallic Conduit+ - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 or 80

PVC conduit installed in accordance with Article 347 of the National Electrical Code (NFPA

No. 70). When Schedule 80 PVC conduit is used, the F and T Ratings are 1 hr.

C. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 4 in. (102 mm) diam (or smaller)

SDR 13.5 CPVC pipe for use in closed (process or supply) piping systems.

D. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 4 in. (102 mm) diam (or smaller)

Schedule 40 solid or foamed core ABS pipe for use in closed (process or supply) or vented

(drain, waste or vent) piping systems.

E. Fire Retardant Polypropylene (FRPP) Pipe - Nom 4 in. (102 mm) diam (or smaller)

Schedule 40 FRPP pipe for use in closed (process or supply) or vented (drain, waste or

vent) piping systems.

F. Polyvinylidene Fluoride (PVDF) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule

40 PVDF pipe for use in closed (process or supply) or vented (drain, waste or vent) piping

systems.

G. Fiberglass Reinforced Pipe (FRP) Pipe - Nom 4 in. (102 mm) diam (or smaller) glass

fiber reinforced thermosetting resin pipe for use in closed (process or control) or vented

(drain, waste or vent) piping systems. When FRP pipe is used, T Rating is 3/4 hr.

H. High Density Polyethylene (HDPE) Pipe - Nom 4 in. (102 mm) diam (or smaller)

Schedule 40 HDPE pipe for use in closed (process or supply) piping systems.

3. Firestop System - The firestop system shall consist of the following:

A. Fill, Void or Cavity Material* - Sealant - Fill material forced into annular space to max

extent possible. Caulk shall be installed flush with both surfaces of wall assembly.

SPECIFIED TECHNOLOGIES INC - SpecSeal 100, 101, 102, 105, 120 or 129 Sealant,

SpecSeal LCI Sealant, Pensil 300 Sealant or SpecSeal Series SIL300 Sealant

B. Fill, Void or Cavity Material - Wrap Strip - Nom 1/8 or 3/16 in. (3.2 or 4.8 mm) thick

intumescent material faced on both sides with a plastic film, supplied in 2 in. (51 mm) wide

strips or nom 1/4 in. (6 mm) thick intumescent material faced on both sides with a plastic

film, supplied in 1-1/2 in. (38 mm) wide strips. The layers of wrap strips are individually

wrapped around the through-penetrant with ends butted and held in place with masking

tape. Butted ends in successive layers shall be aligned.

Except as noted in Item 2, the F and T Rating of the firestop system is dependent upon the

fire rating of wall, diam of through penetrant and the number of wrap strips as tabulated

below:

SPECIFIED TECHNOLOGIES INC - SpecSeal BLU Wrap Strip, SpecSeal BLU2 Wrap Strip

or SpecSeal RED Wrap Strip

C. Steel Collar - Collar fabricated from coils of precut 0.016 in. (0.4 mm) thick (30 MSG) galv

sheet steel available from wrap strip manufacturer. Collar shall be min 1-1/2 in. (38 mm)

deep with 1 in. (25 mm) wide by 2 in. (51 mm) long anchor tabs for securement to the

concrete floor or wall. Retainer tabs, 3/4 in. (19 mm) wide tapering down to 1/4 in. (6 mm)

wide and located opposite the anchor tabs, are folded 90 degree toward pipe surface to

maintain the annular space around the pipe and to retain the wrap strips. Steel collar

wrapped around wrap strips and pipe with a 1 in. (25 mm) wide overlap along its perimeter

joint and secured together by means of a min 1/2 in. (13 mm) wide by 0.028 in. (0.7 mm)

thick stainless steel hose clamp installed at mid-depth of the steel collar. As an alternate to

the steel hose clamp, the steel collar may be secured together by means of three No. 8 by

1/4 in. (6 mm) long steel sheet metal screws when more than one layer of wrap strip is

used.

Wrap strip/collar assembly is slid along the through-penetrant until abuts the surface of the

wall. Collar secured to wall by 1/8 in. (3.2 mm) diam by 1-3/4 in. (44 mm) long steel molly

bolts in conjunction with 1-1/4 in. (32 mm) diam steel fender washers. The number of molly

bolts used is dependent upon the nom diam of the through penetrant. Two molly bolts,

symmetrically located, are required for nom 1-1/2 in. (38 mm) and 2 in. (51 mm) diam

through penetrants. Three molly bolts, symmetrically located, are required for nom 2-1/2 in.

(64 mm) and 3 in. (76 mm) diam through penetrants. Four molly bolts, symmetrically

located, are required for nom 3-1/2 in. (89 mm) and 4 in. (102 mm) diam through

penetrants. Steel collars are installed on each side of wall.

D. Firestop Device* - (Optional, Not Shown) - As an alternate to Item 3B and 3C, galv steel

collar lined with an intumescent material sized to fit the specific diam of the

through-penetrant. Device shall be installed around through-penetrant in accordance with

accompanying installation instructions. Device incorporates anchor tabs for securement to

each surface of wall assembly by means of 1/8 in. (3 mm) diam by 1-3/4 in. (45 mm) long

steel molly bolts in conjunction with 1/4 in. (6 mm) diam by 1-1/2 in. (38 mm) diam steel

fender washers.

SPECIFIED TECHNOLOGIES INC - SpecSeal Firestop Collar, SpecSeal LCC Collar or

SpecSeal SSC Collar . When SpecSeal LCC Collar or SpecSeal SSC Collar are used, the

max annular space shall be 1/8 in. (3 mm) for max 2-1/2 in. (64 mm) diam pipe and shall be

max 1/4 in. (6 mm) for pipe larger than 2-1/2 in. (64 mm) diam.

*Bearing the UL Classification Mark

1

UL RATED ASSEMBLY

1 & 2 HR. RATED - WALL PENET.

N.T.S.

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

13

10

FIR

E S

EP

AR

AT

IO

N

DE

TA

IL

S

System No. W-L-2093

F Ratings - 1 & 2 Hr. (See Item 1)

T Ratings - 1 and 1-1/2 Hr.(See Item 2)

1. Wall Assembly - The 1 or 2 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of

the materials and in the manner described in the individual U300 or U400 Series Wall or Partition Design

in the UL Fire Resistance Directory and shall include the following construction features:

A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist

of nom 2 by 4 in. lumber spaced 16 in. O.C. with nom 2 by 4 in. lumber end plates and cross braces.

Steel studs to be min 3-5/8 in. wide and spaced max 24 in. O.C.

B. Gypsum Board* - 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type,

thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual

U300 or U400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 3 in.

The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in

which it is installed.

2. Through Penetrants - One nonmetallic pipe, conduit or raceway to be centered within the firestop

system. A nom annular space of 5/16 in. is required within the firestop system. Pipe, conduit or raceway

to be rigidly supported on both sides of the floor or wall assembly. The following types and sizes of

nonmetallic pipes, conduits or raceway may be used:

A. Polyvinyl Chloride (PVC) Pipe - Nom 2 in. diam (or smaller) Schedule 40 cellular or solid core PVC

pipe for use in closed (process or supply) piping systems.

B. Rigid Nonmetallic Conduit+ - Nom 2 in. diam (or smaller) Schedule 40 PVC conduit installed in

accordance with Article 347 of the National Electrical Code (NFPA No. 70).

C. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 2 in. diam (or smaller) SDR17 CPVC pipe for

use in closed (process or supply) piping systems.

D. Optical Fiber Raceway+ - Nom 2 in. diam (or smaller) optical fiber raceway formed from polyvinyl

chloride (PVC) or nom 1-1/4 in. diam (or smaller) optical fiber raceway formed from polyvinylidene

fluoride (PVDF). Raceway to be installed in accordance with Article No. 770 of the National Electrical

Code. Raceway to be rigidly supported on both sides of wall assembly.

See Optical Fiber Raceway (QAZM) category in the Electrical Construction Materials Directory for

names of manufacturers.

E. Electrical Nonmetallic Tubing+ - Nom 2 in. diam (or smaller) PVC tubing installed in accordance

with Article 331 of the National Electrical Code (NFPA No. 70). See Electrical Nonmetallic Tubing

(FKHU) category in the Electrical Construction Materials Directory for names of manufacturers.

The hourly T Rating of the firestop system is dependent upon the hourly fire rating of the wall and the

diam of the through-penetrant as shown below:

3. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. thickness of fill material applied within annulus, flush

with both surfaces of wall. Additional fill material to be installed such that a min 1/4 in. thick crown is

formed around the penetrating item and lapping 1 in. beyond the periphery of the opening.

SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant

+Bearing the UL Listing Mark

*Bearing the UL Classification Mark

1

UL RATED ASSEMBLY

1 & 2 HR. RATED - WALL PENET.

N.T.S.

2

3

1A

2

31B

A

A

1234

A

H

G

F

C

B

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

FO

UN

DA

TIO

N

PL

AN

FOUNDATION PLAN

3/16"=1'-0"

RE

FE

R T

O S

HE

ET

S

1 F

OR

C

ON

TIN

UA

TIO

N O

F F

OU

ND

AT

IO

N P

LA

N

15

INDICATES GROUT FILLED CELL WITH (1) VERT. BAR

CONT. FTG. TO BOND BEAM (REFER TO NOTES)

1. PROVIDE MIN. 10 MIL. APPROVED VAPOR BARRIER. ALL

JOINTS TO BE LAPPED MIN. 6" AND SEALED.

2. VERT. BAR TO BE HOOKED AT TOP & BOTTOM (FTG. &

BOND BEAM ENDS) W/ MIN. 12 BAR DIAMETER LEGS

EXCLUDING BEND @ EA. END. LAP SPLICES SHALL BE

NO LESS THAN 25" FOR #5 BAR AND 36" FOR #6 BAR.

3. EXTERIOR SLABS SHALL SLOPE 1/4" PER FOOT AWAY

FROM STRUCTURE.

4. CONTROL JOINTS ARE NOT REQUIRED BY CODE BUT

ARE SUGGESTED. CONTROL JOINTS TO BE SAW CUT A

DEPTH OF 1/4 OF THE THICKNESS OF THE SLAB. FILL

CUT W/ APPROVED JOINT MATERIAL OR USE

ALTERNATE APPROVED METHOD.

FOUNDATION NOTES:

FOOTING SCHEDULE

NUMBERLENGTH x WIDTH

DEPTH

REINFORCING STEEL

2'-8" x 2'-8"1'-8"

(4) #5 EA. WAY

5'-8" x 5'-8"2'-4"

(10) #5 EA. WAY

TOP & BOT.

A

56789

A

H

F

D

A

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

S1

FO

UN

DA

TIO

N

PL

AN

FOUNDATION PLAN

3/16"=1'-0"

14

INDICATES GROUT FILLED CELL WITH (1) VERT. BAR

CONT. FTG. TO BOND BEAM (REFER TO NOTES)

1. PROVIDE MIN. 10 MIL. APPROVED VAPOR BARRIER. ALL

JOINTS TO BE LAPPED MIN. 6" AND SEALED.

2. VERT. BAR TO BE HOOKED AT TOP & BOTTOM (FTG. &

BOND BEAM ENDS) W/ MIN. 12 BAR DIAMETER LEGS

EXCLUDING BEND @ EA. END. LAP SPLICES SHALL BE

NO LESS THAN 25" FOR #5 BAR AND 36" FOR #6 BAR.

3. EXTERIOR SLABS SHALL SLOPE 1/4" PER FOOT AWAY

FROM STRUCTURE.

4. CONTROL JOINTS ARE NOT REQUIRED BY CODE BUT

ARE SUGGESTED. CONTROL JOINTS TO BE SAW CUT A

DEPTH OF 1/4 OF THE THICKNESS OF THE SLAB. FILL

CUT W/ APPROVED JOINT MATERIAL OR USE

ALTERNATE APPROVED METHOD.

FOUNDATION NOTES:

FOOTING SCHEDULE

NUMBERLENGTH x WIDTH

DEPTH

REINFORCING STEEL

2'-8" x 2'-8"1'-8"

(4) #5 EA. WAY

5'-8" x 5'-8"2'-4"

6'-0" x 6'-0"2'-4"

(10) #5 EA. WAY

TOP & BOT.

(10) #5 EA. WAY

TOP & BOT.

RE

FE

R T

O S

HE

ET

S

1.1 F

OR

C

ON

TIN

UA

TIO

N O

F F

OU

ND

AT

IO

N P

LA

N

A

A

1234

A

I

H

F

D

B

CEILING FRAMING PLAN

1/4"=1'-0"

CONNECTOR LEGEND

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

16

S2

CE

IL

IN

G

FR

AM

IN

G P

LA

N

18 GA ANGLE @ 48" O.C. MAX. PROVIDE 1/2" DIA.

A.B. TO BOND BEAM & (3) #10 TEKs TO TRACK.

REFER TO DETAIL 7.1/SD2

(4)#10 TEKs JOIST TO JOIST (WHERE APPLICABLE)

PRECAST NOTES:

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

S3

17

CAST-CRETE, QUALITY PRECAST CO., WEKIWA CONCRETE, LOTT'S CONCRETE, AND FLORIDA ROCK IND.

LOADS LISTED BELOW HAVE BEEN CALCULATED OR COMPILED FROM DATA FROM THE FOLLOWING APPROVED MAN.

PRECAST LINTEL LOAD TABLE(COMPSITE W/(1)#5 TOP & BOTTOM GROUT FILLED SOLID)

24" DEEP

L21

L22

L18

L20

L16

L14

L13

L12

L11

L10

MARK

L6

L9

L8

L4

L3

L2

L1

X

X

X

X

X

X

X

X

X

X

X

X

X

2000

X

X

X

22" DEEP

N/A

N/A

N/A

N/A

N/A

N/A

N/A

MAX. CLR. OPENING

524

128

171

212

293

340

1025

1384

2745

3984

6" DEEP

419 1053X

130

183

183

272

240

334

X

X

X

X

X

X

470

610

611

610

611

842

419

488

483

483

635

1055

1060

1974

3166

3166

8" DEEP

X

X

X

X

X

X

2000

38" DEEP

X

X

X

2542

1053

1224

1170

1170

1534

2483

4616

6039

6039

16" DEEP

23411692

18311250

1400

1300

1300

988

1352

1980

1831

1831

1380

1879

50474029

1857

1692

1966

1857

2436

2555

2341

2721

2404

3127

32" DEEP

3913

7269

9004

9004

5350

9924

10000

10000

14" DEEP

3665

3665

3665

3960

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

1) FOR HEADER DEPTHS DEEPER THAN 32", USE VALUES FOR 32" DEEP HEADER

2) FOR HEADER DEPTHS NOT LISTED ON CHART, USE THE VALUES FOR THE NEXT DEPTH DOWN.

(ex. L3F12 = L3F8)

L5 XX 1261X 2653 4049 4849X

PROVIDE FULL MORTAR HEAD AND BED JOINTS.1.

SHORE FILLED LINTELS AS REQUIRED.2.

INSTALLATION OF LINTEL MUST COMPLY WITH THE ARCHITECTURAL

AND/OR STRUCTURAL DRAWINGS.

3.

LINTELS ARE MANUFACTURED WITH 5-1/2" LONG NOTCHES AT THE ENDS

TO ACCOMMODATE VERTICAL CELL REINFORCING AND GROUTING.

4.

ALL LINTELS MEET OR EXCEED L/360 VERTICAL DEFLECTION, EXCEPT LINTELS 17'-4" AND

LONGER WITH A NOMINAL HEIGHT OF 8" MEET OR EXCEED L/180.

5.

BOTTOM FIELD ADDED REBAR TO BE LOCATED AT THE BOTTOM OF THE LINTEL CAVITY.6.

7/32" DIAMETER WIRE STIRRUPS ARE WELDED TO THE BOTTOM STEEL FOR MECHANICAL

ANCHORAGE.

7.

CAST-IN-PLACE CONCRETE MAY BE PROVIDED IN COMPOSITE LINTEL IN LIEU OF

CONCRETE MASONRY UNITS.

8.

SAFE LOAD RATINGS BASED ON RATIONAL DESIGN ANALYSIS PER ACI 318 AND ACI 5309.

ALL VALUES BASED ON MINIMUM 4" BEARING. EXCEPTION: SAFE LOADS

FOR UNFILLED LINTELS MUST BE REDUCED BY 20% IF BEARING LENGTH IS

LESS THAN 6-1/2". SAFE LOADS FOR ALL RECESSED LINTELS BASED ON 8"

NOMINAL BEARING.

1.

N.R. = NOT RATED.2.

SAFE LOADS ARE TOTAL SUPERIMPOSED ALLOWABLE LOAD ON THE SECTION SPECIFIED.3.

SAFE LOADS BASED ON GRADE 40 OR GRADE 60 FIELD REBAR.4.

ADDITIONAL LATERAL LOAD CAPACITY CAN BE OBTAINED BY THE

DESIGNER BY PROVIDING ADDITIONAL REINFORCED MASONRY ABOVE

THE PRECAST LINTEL.

5.

ONE #7 REBAR MAY BE SUBSTITUTED FOR TWO #5 REBARS IN 8" LINTELS ONLY.6.

THE DESIGNER MAY EVALUATE CONCENTRATED LOADS FROM THE SAFE LOAD

TABLES BY CALCULATING THE MAXIMUM RESISTING MOMENT AND SHEAR AT

D-AWAY FROM THE FACE OF SUPPORT.

7.

FOR COMPOSITE LINTEL HEIGHTS NOT SHOWN, USE SAFE LOAD FROM NEXT LOWER

HEIGHT.

8.

ALL SAFE LOADS IN UNITS OF POUNDS PER LINEAR FOOT.9.

SAFE LOAD TABLE NOTES

LINTEL PLAN

3/16"=1'-0"

LIN

TE

L P

LA

N

LXFX-XB

NOMINAL HEIGHT

LINTEL MARK

TYPE DESIGNATION

U = UNFILLED

F = FILLED WITH GROUT

1-1/2" CLEAR

C.M.U.

8" NOMINAL WIDTH

7-5/8"ACTUAL

GROUT (PER PLAN)

PRECAST LINTEL

#5 REBAR AT BOTTOM OF

LINTEL CAVITY (PER PLAN)

BOTTOM REINFORCING

PROVIDED IN LINTEL

(VARIES)

#5 REBAR AT TOP

MIN. (1) REQ'D

# OF BARS @ BOT.

BLOCK MASON TO VERIFY LINTEL DEPTHS W/ R.O. PRIOR TO INSTALLATION.

CONTACT E.O.R. IF DISCREPANCY EXIST.

10.

12'-8"

22'-8"

18'-0"

20'-8"

20'-0"

16'-0"

13'-4"

6'-4"

10'-0"

12'-0"

11'-0"

9'-0"

8'-4"

4'-8"

3'-4"

2'-8"

1'-6"

5'-4"

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

18

S4

BU

IL

DIN

G S

EC

TIO

N

A BUILDING SECTION

1/4"=1'-0"

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

SD1

DE

TA

IL

S

1

MONOLITHIC FOOTING

DETAIL

3/4"=1'-0"

2

MONOLITHIC A/C CHASE

DETAIL

3/4"=1'-0"

5

INTERIOR CMU WALL

FOOTING DETAIL

3/4"=1'-0"

19

3

COL. HAIRPIN

DETAIL

3/4"=1'-0"

4

CORNER COL. HAIRPIN

DETAIL

3/4"=1'-0"

LENGTH/SIDE

LESS THAN 12"

12" - 24"

24" - 36"

NO. OF ANCHORS/SIDE

ONE/SIDE

TWO/SIDE

THREE/SIDE

36" UP & 5 TONS & UP FOUR/SIDE

ANCHOR SPACING TABLE

ELEVATION

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

20

SD2

DE

TA

IL

S

1

COMPRESSOR ANCHOR

DETAIL

N.T.S.

5

TOP OF EXT. CMU WALL

CONNECTION DETAIL

3/8"=1'-0"

3

TYP. CORNER

WALL REINFORCING

3/4"=1'-0"

2

BOND BEAM DETAIL

1-1/2"=1'-0"

9

CMU END WALL SECTION

@ OFFICE AREA

3/4"=1'-0"

10

CMU SIDE WALL SECTION

@ OFFICE AREA

3/4"=1'-0"

6

ANCHOR/WEB STIFFENER

CONNECTION DETAIL

N.T.S.

7

TRACK BLOCKING

CONNECTION DETAIL

N.T.S.

8

KNEE WALL

DETAIL

3/4"=1'-0"

11

INTERIOR CMU WALL

SECTION

3/4"=1'-0"

4

A/C CHASE

DETAIL

3/4"=1'-0"

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

21

SD3

DE

TA

IL

S

1

INTERIOR CMU WALL

SECTION

3/4"=1'-0"

2

INTERIOR CMU WALL

SECTION

3/4"=1'-0"

3

T.O.W. CONNECTION

DETAIL

3/8"=1'-0"

4

CLG. JOIST.

CONN. DETAIL

3/8"=1'-0"

A

E

C

B

A

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

P1

22

PLUMBING SUPPLY PLAN

1/4"=1'-0"

PL

UM

BIN

G

SU

PP

LY

P

LA

N

WATER RISER DIAGRAM

1. COORDINATE ALL PIPE ROUTING WITH ALL OTHER TRADES PRIOR TO INSTALLATION.

ROUTE ALL PIPING TO AVOID DUCTWORK, ELECTRICAL RACEWAYS AND BUILDING

STRUCTURE. IF PENETRATIONS THROUGH STRUCTURAL MEMBERS ARE REQUIRED

FOR PLUMBING INSTALLATIONS, NOTIFY STRUCTURAL ENGINEER PRIOR TO

INSTALLATION TO INSURE THAT STRUCTURAL INTEGRITY IS MAINTAINED.

2. ROUTE ALL PIPING CONCEALED ABOVE CEILINGS, WITHIN WALLS OR CHASES

EXCEPT AS SPECIFICALLY NOTED.

3. PIPE ROUTING IS DIAGRAMMATIC AND IS INTENDED TO INDICATE GENERAL ROUTING.

PLUMBING CONTRACTOR SHALL PROVIDE ANY ADDITIONAL OFFSETS AND FITTINGS

REQUIRED FOR PROPER INSTALLATION AND TO MAINTAIN CLEARANCES AS

ENCOUNTERED IN FIELD.

4. ALL PLUMBING WORK SHALL CONFORM TO THE FLORIDA PLUMBING CODE 2010 AND

ADA STANDARDS, FLORIDA STATE SANITARY CODE, FLORIDA ENERGY EFF'Y CODE,

AND LOCAL JURISDICTION REQUIREMENTS.

5. PROVIDE ACCESS PANELS TO ALL VALVES WITHIN CHASES OR ABOVE

NON-ACCESSIBLE CEILINGS.

6. DRAINAGE PIPING 3” AND LARGER SHALL SLOPE NO LESS THAN 1/8” FALL PER FOOT.

PIPING LESS THAN 3” SHALL SLOPE A MINIMUM OF 1/4” PER FOOT.

7. VERIFY INVERT ELEVATIONS AND EXACT LOCATIONS AND SIZES OF ALL UTILITIES

WHICH ARE TO BE CONNECTED BEFORE INSTALLATION.

8. ALL VENTS THROUGH ROOF SHALL BE MINIMUM 10'-0” FROM AIR INTAKES.

9. PLUMBING CONTRACTOR SHALL INSTALL DIELECTRIC UNIONS AT ALL CONNECTIONS

OF DISSIMILAR MATERIALS.

10. INSTALL ISOLATION VALVES AT EACH DOMESTIC WATER BRANCH TAKEOFF AND

INSTALL UNION AT EACH PIECE OF EQUIPMENT, FIXTURE AND APPLIANCE SERVICE

POINT CONNECTION.

11. INSTALL PRESSURE REDUCING VALVES ON BRANCH LINES SERVING FIXTURES

AND/OR EQUIPMENT, WHEN WATER PRESSURE EXCEEDS 60 PSI.

12. WASTE, TRAP AND VENT SIZES SHALL BE IN ACCORDANCE WITH APPLICABLE CODES.

13. SOIL, WASTE AND VENT PIPING SHALL BE SCHEDULE 40 PVC. ALL MATERIALS AND

INSTALLATION PRACTICES SHALL BE IN STRICT ACCORDANCE WITH THE LATEST

APPLICABLE STATE AND LOCAL CODES.

14. ABOVE GROUND AND UNDERGROUND DOMESTIC WATER PIPING SHALL BE

“FLOGUARD GOLD” CPVC DOMESTIC WATER PIPE WITH SOLVENT WELDED FITTINGS.

15. SUPPORT ALL PIPING SYSTEMS IN ACCORDANCE WITH APPLICABLE CODES AND

WITH INDUSTRY STANDARDS FOR HANGER AND WALL MOUNTED SUPPORT

SYSTEMS.

16. INSTALL WATER HAMMER ARRESTORS AS REQUIRED.

17. INSULATE ALL HOT WATER PIPING SYSTEMS WITH MINIMUM 1” THINK R=6.8 CLOSED

CELL FOAM INSULATION. ARMAFLEX, IMOCA, OR EQUAL.

18. WORK INCLUDES BUT IS NOT NECESSARILY LIMITED TO: WATER SUPPLY PIPING;

SOIL, WASTE AND VENT PIPING, ROOF DRAINS, AND DOWN SPOUTS.

19. TEST ALL POTABLE WASTE AND VENT PIPES FOR LEAKS TO ASSURE WATER

TIGHTNESS FOR REQUIRED SERVICES.

20. ALL PIPES SHALL BE CAPPED DURING CONSTRUCTION FOR PROTECTION FROM

VANDALISM AND CONSTRUCTION WASTE SPILLAGE. TEMPORARILY GLUE PVC CAPS

ON ALL VENTS.

21. FLOW RESTRICTORS SHALL BE FURNISHED AND INSTALLED IN ALL LAVATORY HOT

WATER FAUCETS TO LIMIT FLOW TO 0.5 GPM MAXIMUM.

22. WATER HEATERS THERMOSTATS SHALL BE SET TO LIMIT MAXIMUM WATER

TEMPERATURE TO 110°F.

23. INSULATE HORIZONTAL RAIN LEADER RUNS UNLESS EXPOSED OUT-OF-DOORS.

PLUMBING NOTES:

A

E

C

B

A

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

P2

23

PL

UM

BIN

G

WA

ST

E P

LA

N

PLUMBING WASTE PLAN

1/4"=1'-0"

WASTE RISER DIAGRAM

NOTE:

REFER TO SHEET P1 FOR PLUMBING NOTES.

123456

A

H

G

E

C

B

A

A

A11

VD=0.5%

TVD=1.76%

A21

VD=2.2%

TVD=3.6%

A18

VD=1.2%

TVD=2.6%

A14

A16

VD=1.8%

TVD=3.06%

VD=0.5%

TVD=1.76%

A22

VD=2.0%

TVD=3.26%

A20

VD=1.8%

TVD=3.1%

A24

VD=0.91%

TVD=1.26%

A12

S

A15

VD=1.8%

TVD=3.1%

VD=2.2%

TVD=3.5%

A33

VD=1.8%

TVD=3.06%

A10

VD=1.8%

TVD=3.1%

A5

VD=1.0%

TVD=2.3%

A30

VD=1.8%

TVD=3.1%

A9

VD=0.5%

TVD=1.76%

A29

USE #10 WIRE

VD=1.9%

TVD=3.2%

S S

B2 B4 B6

SS

A28

A26

A27

A23 A25

A12

VD=1.8%

TVD=3.1%

A5 A7

USE #6 WIRE

w/ #10 GND.

VD=1.0%

TVD=2.3%

A6 A8

USE #6 WIRE

w/ #10 GND.

VD=1.0%

TVD=2.3%

A13

A17

VD=0.5%

TVD=1.76%

A1

USE #10 WIRE

VD=1.5%

TVD=2.8%

A3

A19

VD=1.2%

TVD=2.6%

A2 A4

USE #10 WIRE

VD=1.5%

TVD=2.8%

USE #8 CU w/ #10 CU GND.

VD=.6%

TVD=3.0%

USE #10 WIRE

VD=1.9%

TVD=3.2%

USE #10 WIRE

VD=1.9%

TVD=3.2%

USE #10 WIRE

VD=1.8%

TVD=4.1%

USE #10 WIRE

VD=1.9%

TVD=4.2%

A31 VD=1.0%

TVD=2.26%

W D

A32 A34

USE #10 WIRE

W/ #10 GND

VD=0.8%

TVD=2.1%

A35

VD=0.5%

TVD=1.76%

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

E1

24

ELECTRICAL PLAN

3/16"=1'-0"

EL

EC

TR

IC

AL

P

LA

N

2'x4' FLUORESCENT LAY-IN FIXTURE

EXHAUST FAN (MAX. 75 WATTS)

EMERGENCY BATTERY UNIT LIGHTING

FIXTURE - WALL MOUNTED. CONNECT AHEAD

OF ROOM LIGHTING SWITCH

DIRECTIONAL EXIT LIGHT

EXIT LIGHT

LIGHTING NOTES:

1. LIFE SAFETY LIGHTING AND SIGNS SHALL BE PROVIDED

WITH UNIT BATTERY EQUIPMENT AND CONNECTED TO THE

ROOM OR AREA LIGHTING CIRCUIT AHEAD OF ALL

SWITCHING.

2. EMERGENCY LIGHTING TO BE CONNECTED TO A LOCAL

LIGHTING CIRCUIT.

3. ALL INTERIOR LIGHTING TO BE ATTACHED TO AN

AUTOMATICALLY CONTROL DEVICE IN COMPLIANCE WITH

FBC CHAPTER 13, SECTION 13-415.ABC.1.1

4. ALL EXTERIOR LIGHTING TO BE PROVIDED WITH AUTOMATIC

CONTROLS IN COMPLIANCE WITH FBC CHAPTER 13,

SECTION 13-415.1.ABC.1.4

5. PROVIDE TIMECLOCK WITH OVERRIDE SWITCH TO

AUTOMATICALLY TURN OFF LIGHTS IN NO MORE THAN FOUR

HOURS FOR LIGHTING CIRCUITS IN WAREHOUSE AREA.

6. PROVIDE PHOTOSENSORS FOR EXTERIOR LIGHTING.

7. PROVIDE OCCUPANCY SENSORS FOR OFFICE AREA

LIGHTING.

NOTES:

1. FIXTURE IS CONSIDERED GENERIC. EQUAL ARE APPROVED.

LIGHTING FIXTURE SCHEDULE

LAMPS

NO TYPE

DESCRIPTION

2 x 4 LENSED LAYIN

MANUF.SYMBOL NOTES

1

9W

EMERGENCY BATTERY

UNIT WALL OR CLG. MTG

LEDSLIM LED EXIT

2

S

SINGLE POLE TOGGLE SWITCH WITH OCCUPANCY

SENSOR

LIGHT FIXTURE, WALL MOUNTED

6 32WT8

ELECTRICAL LEGEND

OUTLET 110-115

SINGLE POLE TOGGLE SWITCH

S

COMMUNICATIONS OUTLET - TYPICAL RUN

3/4" CONDUIT TO ACCESSIBLE CEILING

SPACE. PROVIDE 2 GANG BOX WITH ONE

GANG RING (TYP.)

OUTLET 110-115, GROUND FAULT CIRCUIT

INTERRUPTER

1. ALL ELECTRICAL WORK AND APPLIANCES SHALL CONFORM

TO NEC 2008.

2. VERIFY EXACT LOCATION OF ALL MECHANICAL EQUIPMENT

WITH MECHANICAL INSTALLER PRIOR TO ROUGH-IN.

3. ALL EMPTY CONDUITS SHALL BE PROVIDED WITH PULL

STRINGS IN THEM.

4. ALL CONDUIT TO BE CONCEALED UNLESS IMPOSSIBLE DUE

TO EXISTING CONDITIONS (I.E. EXPOSED STRUCTURAL

CEILINGS, BUILDING EXTERIOR WALLS). CONCEAL ALL

CONDUITS ABOVE CEILINGS OR WITHIN WALLS AND

COUNTERS.

5. INSTALL ALL MATERIALS AND FIXTURES PER

MANUFACTURER'S RECOMMENDATIONS.

6. ELECTRICAL CONTRACTOR TO COORDINATE ALL POWER

REQUIREMENTS WITH EQUIPMENT SUPPLIER FOR

INSTALLATION - INSTALL IN ACCORDANCE WITH

MANUFACTURER'S RECOMMENDATIONS.

7. ALL CONDUCTORS SHALL CONFORM TO THE CURRENT ISSUE

OF THE NEC AND SHALL MEET ASTM SPECIFICATIONS.

8. MINIMUM WIRE SIZE SHALL BE NO. 12 AND SHALL BE SOFT

DRAWN COPPER, SOLID WITH THWN/THHN INSULATION IN

SIZES THROUGH NO. 10 AND STRANDED WITH THWN/THHN

INSULATION FOR NO. 8 AND LARGER.

9. ELECTRICAL CONTRACTOR TO VERIFY ALL BREAKER AND

WIRE SIZES WITH EQUIPMENT TO BE ATTACHED PRIOR TO

INSTALLATION.

10. ALL DUPLEX RECEPTACLES AND TOGGLE SWITCHES TO BE

15 AMP U.N.O.

11. ALL DEDICATED DUPLEX RECEPTACLES TO BE 20 AMP

12. SEE SHEET E3 FOR ELECTRICAL LOAD CALCULATIONS.

13. FEEDER AND BRANCH CIRCUIT CONDUCTORS HAVE BEEN

SIZED IN ACCORDANCE WITH FBC ENERGY CONSERVATION,

SECTION 505.7.3.1

14. LARGER WIRE SIZES MAY BE REDUCED TO #12 CU DIRECTLY

AHEAD OF SWITCHES OR RECEPTACLES ON 20 AMP

CIRCUITS ONLY. EC TO PROVIDE JUNCTION BOX AT

LOCATIONS WHERE STEP DOWN OCCURS.

ELECTRICAL NOTES:

QUAD OUTLET 110-115

ELECTRICAL PANEL

JUNCTION BOX

RE

FE

R T

O S

HE

ET

E

2 F

OR

C

ON

TIN

UA

TIO

N O

F E

LE

CT

RIC

AL P

LA

N

NOTE:

REFER TO SHEET E3 FOR PANEL

SCHEDULES

FLUORESCENT LIGHT FIXTURE, HANGING

LITHONIAFLUORESCENT HIGH BAY

3 32WT8 LITHONIA

1 LED TBDLED CANOPY LIGHT

1

1

1

1

TBD

TBD

VD=

VOLTAGE DROP FOR BRANCH

TVD=

TOTAL VOLTAGE DROP

SSWITCH, THREE WAY

OUTLET 110-115, SPLIT WIRED

OUTLET 110-115, CEILING MOUNTED

1 LED TBDLIGHT FIXTURE, HANGING

1

LIGHT FIXTURE, HANGING

DISCONNECT SWITCH

OUTLET 110-115, FLOOR MOUNTED

OUTLET 220-240, SPECIAL PURPOSE

6789

A

H

F

D

A

B1

USE #8 CU w/ #10 CU GND

VD=0.6%

TVD=3.0%

B3 B5

B2 B4 B6

USE #8 CU w/

#10 CU GND

VD=0.6%

TVD=3.0%

A28

USE #10

WIRE

VD=1.8%

TVD=4.1%

A28

A26

USE #10

WIRE

VD=1.9%

TVD=4.2%

A26

2 4 6

VD=1.08%

TVD=2.34%

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

E2

25

ELECTRICAL PLAN

3/16"=1'-0"

EL

EC

TR

IC

AL

P

LA

N

NOTE:

REFER TO SHEETS E1 & E3 FOR

NOTES, LEGENDS AND SCHEDULES

RE

FE

R T

O S

HE

ET

E

2 F

OR

C

ON

TIN

UA

TIO

N O

F E

LE

CT

RIC

AL P

LA

N

1. AFTER GROUNDING SYSTEM IS INSTALLED, GROUND RESISTANCE SHALL BE MEASURED, TO

ASSURE THAT GROUND VALUE OF 25 OHM MAXIMUM RESISTANCE IS ACHIEVED. IF NOT,

ADDITIONAL GROUNDING SHALL BE PROVIDED TO MEET THE SPECIFIED VALUE.

2. ALL CONNECTIONS TO GROUND RODS SHALL BE EXOTHERMIC WELD CONNECTIONS. IF

CONNECTION WILL REMAIN ACCESSIBLE, ACORN STALE GROUNDING CLAMPS MAY BE USED.

3. GROUND CONDUCTOR SHALL BE LOCATED WITHIN OR NEAR BOTTOM OF CONCRETE FOUNDATION

OR FOOTING THAT IS IN DIRECT CONTACT WITH THE EARTH, AND SHALL CONSIST OF AT LEAST 20

FEET OF ONE OR MORE STEEL REINFORCING BARS OR RODS OF NOT LESS THAN 1/2 INCH

DIAMETER, OR OF AT LEAST 20 FEET OF BARE COPPER CONDUCTOR.

03.19.2015

AS NOTED

LJM/ AK

26

SSPE

DESIGN

CHECKED

JOB

SCALE

DATE

DRAWN

OFSHT

DA

TE

DE

SC

RIP

TIO

NR

EV

.

SH

EE

T T

IT

LE

PR

OJE

CT

SM-WAREHOUSE

En

gin

ee

rin

g B

y:

PH

ON

E: 3

21

.2

51

.6

00

6

SU

IT

E 2

07

2

CA

#2

73

71

DB

SS

, IN

C.

OR

LA

ND

O, F

L. 3

28

28

SE

MIN

IO

LE

M

AS

ON

RY

WA

RE

HO

US

E B

UILID

NG

E3

26

EL

EC

TR

IC

AL

P

LA

N

1

GROUNDING ELECTRODE

DETAIL

N.T.S.

ELECTRICAL RISER DIAGRAM

N.T.S.

(2) SETS OF 4" PVC

CONDUIT W/ (4) 500 KCMIL

ALUM. & (1) #2/0 CU GND

FROM METER CENTER

3/4" PVC CONDUIT w/ #2/0

CU GND. TO GROUNDING

ELECTRODE

600 AMP 208V 3P 4W FUSED

DISC. IN NEMA3R ENCLOSURE

w/ 600 AMP CLASS "L" FUSES

SIM TO GE TG3326R w/ TNI66

AFC= 23.5 KVA

VD= 0.35%

(2) SETS OF 4" PVC

CONDUIT W/ (4) 500 KCMIL

ALUM. & (1) #2/0 CU GND

EXTERIOR

(2) SETS OF 3" PVC

CONDUIT W/ (4) 300 KCMIL

ALUM. & (1) #2 CU GND TO

PANEL "WAREHOUSE-B"

600 AMP PANEL

"WAREHOUSE DIST."

208V 3PH 4W SIM. TO

GE SPECTRA SERIES

AFC= 17 KVA

VD= 0.91%

TVD= 1.26%

(2) SETS OF 4" PVC

CONDUIT W/ (4) 500 KCMIL

ALUM. & (1) #2/0 CU GND

FROM MAIN DISCONNECT

INTERIOR

(2) SETS OF 3" PVC

CONDUIT W/ (4) 300

KCMIL ALUM. & (1) #2

CU GND FROM PANEL

"WAREHOUSE DIST."

ELECTRICAL RISER DIAGRAM

N.T.S.

(2) SETS OF 3" PVC

CONDUIT W/ (4) 250 KCMIL

ALUM. & (1) #3 CU GND

400 AMP PANEL

"WAREHOUSE-A"

208V 3PH 4W

SIM. TO GE "A" SERIES

400 AMP PANEL

"WAREHOUSE-B"

208V 3PH 4W

SIM. TO GE "A" SERIES

AFC= 17 KVA

VD= 1.08%

TVD= 2.34%