Upload
kamal-arab
View
262
Download
1
Embed Size (px)
Citation preview
7/28/2019 Boiler Penthouse Ash Accumulation
1/2
Boiler Penthouse Ash Accumulation
written by: Dr V T Sathyanathan edited by: Lamar Stonecypher updated: 7/16/2010
Ash accumulation the boiler penthouse is a very clear indication of deviation in operatingparameters of the boiler, ID fan overloading due to air ingress in the system, and many other
reasons.
Ash accumulation in boiler penthouse can be caused both due to operational deviations and dueto boiler performance deterioration or maintenance. The main factor which results in ash
accumulation in penthouse is the positive pressure created at the top of the boiler furnace. The
rate of ash accumulation depends on the amount of pressurization and the furnace roof sealingeffectiveness. The upper furnace can get pressurized if the furnace vacuum maintained is not
adequate. Normally it is a practice to maintain minus 10 millimeter of water column one meter
below the furnace roof. This ensures that the pressure just below the furnace roof is negative
which means no ash can penetrate the roof sealing and find its way to the penthouse.
The pressure in the boiler furnace just below the roof can become positive when the induceddraft fan get loaded fully and more of the combustion air is send to the furnace. The combustion
air requirement depends on the amount of fuel being burnt to carry the load in the boiler. One
should not mistake this for the weight of fuel being sent to the furnace, but it is the million
calories being supplied by the fuel. This can happen when the boiler is being consciously overloaded due to any reason.
The induced draft fan can get fully loaded when in such boilers the air ingress to the boilerincreases above a limit. A large amount of air ingress in boilers happens at many locations,
starting from furnace to induced draft fan inlet. In furnace one of the major areas is the bottomash hopper design and the sealing system provided and maintained. The peep holes provided inthe furnace at various locations to view the flame condition inside the furnace is also a source of
air ingress if they are not properly closed.
In the other areas of second pass, economizer outlet flue gas duct, air pre-heater, air pre-heater
flue gas outlet duct to electrostatic precipitator, the electrostatic precipitator and the flue gas duct
from electrostatic precipitator outlet to induced draft fan are locations prone for air ingress to the
boiler and over load the induced draft fan. The air ingress into the boiler at any location can be
evaluated by doing oxygen measurement in the inlet and outlet of the sections. The percentageair ingress can be worked out from the equation (O
2outletO
2inlet) divided by (21O
2outlet).
It is normally seen that the expansion bellows given at various locations are a cause of concern
for air ingress into the system.
Ash accumulation in the penthouse of the boiler can also be caused from improper combustionleading to pressurization of the furnace near the roof. It is seen that when the primary air flow in
pulverized coal fired boiler is just near the settling velocity, then it can lead to coal particles
7/28/2019 Boiler Penthouse Ash Accumulation
2/2
settling in the coal pipe very near the burner and getting puffed into the furnace. This leads to
furnace pressure oscillation enabling the ash particle to get pushed to the penthouse of the boiler.
Inspection and maintenance of the furnace roof sealing is another important factor which can
avoid ash ingress into the boiler penthouse.