Boiler and Pressure Vessel Engineering - Vessel Nozzle Loading

Embed Size (px)

Citation preview

  • 6/20/2014 Boiler and Pressure Vessel engineering - vessel nozzle loading

    http://www.eng-tips.com/viewthread.cfm?qid=162558 1/7

    Smart questionsSmart answersSmart people

    Go Find A Forum Go

    JoinDirectorySearchTell A FriendWhitepapersJobs

    Home > Forums > Mechanical Engineers > Activities > Boiler and Pressure Vessel engineering Forum

    vessel nozzle loading thread794-162558

    heaterguy (Mechanical) (OP) 14Aug06

    17:33

    If a customer gives Fx-500 pounds, Fx-500 pounds, Fz-500 pounds, Mx-1,500 foot-pounds, My-1,500 foot-pounds, and Mz-1,500 foot-pounds, do weapply all six forces at once, one at a time or just F or M forces?

    "Each vessel nozzle shall be designed for the following loads"

    JStephen (Mechanical) 14Aug06

    17:36

    If you have a simple way to check the loads, apply all at once and see if it affects the design- if not, it doesn't matter. If so, check with the customer tosee what's intended.

    SnTMan (Mechanical) 14Aug06

    21:49

    This sounds like a typical WRC-107 / WRC-297 calculation, with the exception of the coordinate system. All load and moments are applied simultaneously.WRC-107 uses a vessel coordinate system, with shear forces and moments in vessel longitudinal, circumferential and radial directions rather than x,x,zcoordinates. Forces and moments given in x,y,z have to be translated to the vessel coordinate system before performing the calculations. In practicethese are often just tables given in specs as per your example and no one really knows the true orientation. Often, the magnitudes for the threedirections are the same also per your example and true orientation makes no difference.

    These calculations can be performed in various commercial programs such as Codecalc or many companies have their own software. It's pretty difficultto do by hand. You may be able to find "freeware" spreadsheet calcs but I can't point you to any.

    The allowables are often based on whether or not a large component of the loading is thermal, and therefore "self -relieving" or sustained. Again, whenworking from tables in specs, nobody really knows and it is best to assume they are sustained and use an allowable of something like 80% of yield attemperature.

    Regards,

    Mike

    prex (Structural) 15Aug06

    2:18

    (5)

    Kuwait Construction Jobsgulftalent.com

    Job Opportunities in Construction. Apply now!

    Read More Threads Like This One

    Share This

  • 6/20/2014 Boiler and Pressure Vessel engineering - vessel nozzle loading

    http://www.eng-tips.com/viewthread.cfm?qid=162558 2/7

    Can't fully agree with the well documented position of SnTMan.Also do not fully agree with JStephen: please do not ask your customer, these loads are generic tabulated ones that nobody knows where they comefrom, so it's no use asking.The meaning of such tables is an old issue. A point that's never made clear is whether they include the pressure end effect or not, so its normal toassume it is not. Hence the pressure end load should be added to the axial one.Concerning the superposition, the issue is not only whether they should act simultaneously or separately, also their sign is normally specified as + or -,but its unclear whether they should be assumed to vary between the + and - orientations (and that's makes a lot difference!).It's usual to take them as varying between 0 and the tabulated value, but to combine their signs in order to get the worst combination.Concerning the allowables, membrane stresses should be classified as local membrane and limited to 1.5S and membrane+bending stresses should beclassified as secondaries and limited to 3S (PD5500 has a fairly more conservative treatment). The origin of the loading (thermal or other) is unrelevant,as these are external loads for the vessel, so they must be treated as mechanical loads (unless the vessel-piping combination is analyzed as a whole, butcodes are not ready for that).In the site below there is a sheet for WRC297 calculations.

    prex

    http://www.xcalcs.comOnline tools for structural design

    heaterguy (Mechanical) (OP) 15Aug06

    9:35

    Do the values above seem excessive for a 1.5" 150# flanged nozzle into a 3" sch 40 pipe body?

    arto (Mechanical) 15Aug06

    13:32

    They'll bend the pipe big timea quick check:for 1.5" s/80 Z =0.412in^3

    1500ft#x12in'ft/.412in^3 = 44ksi

    sounds like the old "moment to yield"

    also check the nozzle load on the shell [Bednar is a quick way]& the equivalent pressure vs the flange rating [Kellogg]

    SnTMan (Mechanical) 15Aug06

    13:45

    heaterguy, they seem kind of high to me, many exchanger specs don't require nozzle loading to be considered below 2" NPS. You can go run it xcalcs, ifno problem, fine. If so, clarification may be in order.

    prex, I agree that pressure stresses should be added to tabluated loads. As for signs, I have not noticed great differences (this is REALLY TOUGH togeneralize about) except when the radial force is directed outward from the nozzle, in which case it is additive with the hoop stress due to pressure.HEATERGUY: make sure you understand the sign conventions your software is using.

    As for allowables, again agreed, that was just deeper than I wanted to go at the time. I have seen specs that specify differing allowables based onwhether loading was "primarily" thermal or not. Not that they always tell you which way it is.

    Nozzle loading gets to be a messy business at times.

    Regards,

    Mike

    JStephen (Mechanical) 15Aug06

  • 6/20/2014 Boiler and Pressure Vessel engineering - vessel nozzle loading

    http://www.eng-tips.com/viewthread.cfm?qid=162558 3/7

    17:27

    "If so, clarification may be in order."- that sounds a lot like asking the customer to me.

    My point was that these do sound like standard-spec loads, not actual calculated loads, and if they seem to be unreasonable, it is quite likely they can bedone away with or reduced by the customer.

    NozzleTwister (Mechanical) 23Aug06

    14:14

    heaterguy,

    Speaking as a customer, I can tell you how we expect you consider these loads. I provide such tables and loads to venders to design by. For the record, Ido agree these loads seem high for a 1 1/2" 150# nozzle. Consider these loads as follows.

    1. The loads are strictly Forces and Moments imposed on your nozzle by the attached piping.

    2. They DO NOT INCLUDE any axial forces in the nozzle due to pressure.

    3. The loads are to be considered as acting simultaneously on your nozzle.

    4. They are given in absolute format for simplicity. The actual loads can be either negative or positive in sign. The load range can actually be double theloads given. If Fy = -500 lbs in the sustained case (dead weight) and +500 lbs in the operating (hot) case, the nozzle load would be consideredacceptable.

    5. It's the Venders responsibility to design using the load directions (-/+) that give the most conservative results.

    With that being said, hopefully the customer has provided you with the coordinate system (though in this case the loads are all the same) and hasestablished whether the loads are to be taken at the flange face or at the nozzle to shell juncture.

    For vessels and exchangers, I prefer the axis nomenclature of P, Fl, Fc, Mr, Ml, & Mc.

    I provide a table with nozzle force and moment allowables increasing with nozzle size.

    Don't be afraid to go back to your customer and tell him the loads are excessive and establish some new numbers. Maybe he has actual values he canprovide. If he insists on this high of moments, ask if he's considered flange leakage.

    The sizes given make me think this is probably a "hair pin" exchanger. Hopefully you're not considering a stub-in nozzle connection, but are considering a3 x 1 1/2 welding tee with a weld-neck flange for this nozzle.

    That's my 2 cents, maybe more.

    Good luck,

    NozzleTwisterHouston, Texas

    prex (Structural) 24Aug06

    2:14

    NozzleTwister,your post does not solve a very important issue.A point that's not often known to many designers is that the acceptability of some stresses (the secondary stresses) does not depend on the absolutevalue of the load, but on the range (the variation or change) of the load between different states of loading. So, in your example, the effective load is1000 lbs, even if the two loading conditions are not occuring at the same time.Normally the limiting stresses for nozzle loads are the secondaries. So if you take all the nozzle loads as varying between a minus value and the plus one,you'll effectively double all your loads!

    prex

    http://www.xcalcs.comOnline tools for structural design

    (2)

  • 6/20/2014 Boiler and Pressure Vessel engineering - vessel nozzle loading

    http://www.eng-tips.com/viewthread.cfm?qid=162558 4/7

    zjliang (Mechanical) 24Aug06

    12:40

    Nozzle checking is really a controversial and nasty topic, and sometimes a lot of tricks in it. If the piping designer/analyst could work together with vesseldesigner, that will make it much easier. I used to play a dual roles. Here below is my experience.

    1. Before applying these load numbers, check or try to find the piping layout connected to the nozzle, even a hand sketch would help, then make aguess/assumption about the loading combination.

    2. Ask yourself a question: what case do you need to take care? Sustain or thermal Expansion? Primary load or secondary load?

    3. Then based on the assumed load cases, pick the load value from your table apply them into your model, do not forget the sign.

    4. Depending on what method you use, if WRC107/297, do what prex/SnTMan/NozzleTwister recommended. If FE, make sure to eliminate the effect ofloading boundary condition. Besides, the allowable for secondary + primary is SPS, not 3Sm.

    Actually, most customers don't want to take too much time to provide accurate load cases, in most cases it is impossible to find it in the begining stage ofthe project before the piping layout is done. So quite conservative absolute values were put forward. From the years experience in manufactures, I feelquite confident that most vessel nozzles are strong enough to handle the real loads even though it can't pass the crazy numbers in the design stage.Especially for the thermal loads from piping.

    BTW, I totally disgree the design philosophy "do not treat vessel as a pipe support". Sometimes it will drive the designer nuts.

    Thanks,

    zjliang

    rmartin00 (Mechanical) 25Aug06

    17:11

    zjliang, I have to disagree with your opinion on treating the vessel as a support. I have designed large vessels with nozzles, say 18" diameter, with hugetablulated loads as Nozzletwister discusses, but with design pressures of 15 psig. What happens is that the shell and nozzle thicknesses aredisproportionately thick compared to what they need to be for pressure alone. This costs a lot of money when the vessel is made of, say C-276. And forwhat? So the vessel can perform the action of a hunk of cheap structural steel (aka pipe support) attached to the building steel? The only one that loseswhen 1)using the vessel as a support and 2)tabulating nozzle loads based on size, is the owner, because they'll end up paying more for the vessel due tothe need for more material.

    zjliang (Mechanical) 25Aug06

    17:38

    Good comments, rmartin00.

    But just a little clarification of my point. In most cases, changing the shell/header thickness to handle the piping loads is always the last resort except forsome special governing loading cases per UG-22, like cyclic or dynamic loads per UG-22(e).

    My point is that without changing the shell design (thickness from pressure calc), or just by introducing proper repads/attachment, a nozzle with enoughflexibility could actually resist quite high secondary loads, specifically for thermal piping loads. Without considering plastic analysis, just fully takingadvantage of the redistribution of the secondary stress around a nozzle, you will find a vessel could reasonably be a pipe support in some sense. Strongenough.

    Certainly, I totally agree that it is silly to increase the thickness of whole vessel to be a "Pipe Support". :)

    Another point is if model a vessel and connected piping in together, or just by introducing accurate local flexibility instead of an assumed anchor point, thepiping loads will drop dramatically.

    Cheers.

    johnnymist2003 (Mechanical) 30Aug06

    10:50

    (2)

  • 6/20/2014 Boiler and Pressure Vessel engineering - vessel nozzle loading

    http://www.eng-tips.com/viewthread.cfm?qid=162558 5/7

    Hi,this issue of including pressure thrust on nozzles for WRC-107/297 analyses...If one takes a blanked manway nozzle, is it necessary to do WRC-107/297nozzle load calculations?Certainly there is a pressure thrust on the blanked nozzle.This pressure thrust would create a substantial radial force actingoutward.However I have yet to come across a WRC-107/297 analysis on a manway nozzle.I have tried out this calculation just to see the results and ifone designs the manway correctly to Code rules for reinforcement, etc, then one checks the configuration in WRC-107/297 using the radial pressurethrust, the vessel shell and any reinforcement is horribly overstressed.Thus, to follow the logic, in my opinion it is not necessary to add pressure thrust into the radial force component of a WRC-107/297 analysis.I believe that the purpose of WRC-107 is to deal with the mechanical loads from attached piping(of whatever source) and to include pressure thrust in addition to the radial force is unnecessary.I welcome any responses.John

    prex (Structural) 30Aug06

    11:23

    johnnymist2003,if you have the pressure end thrust alone, then you don't need to check per WRC, as the opening reinforcement will take care of that.But when you are required to do such checks (normally manways and non process nozzles are excluded) you need to include all the loadings, also thepressure thrust.

    Of course in doing that you'll see the secondary stresses, that are normally out of the scope of ASME VIII Div.1 (see UG-23(c)): it is customary to limitthem to 3S under Div.1 coverage, but in my opinion it would be more consistent to simply not limit them. However in that case most WRC107/297analyses would not be very useful.

    prex

    http://www.xcalcs.comOnline tools for structural design

    zjliang (Mechanical) 30Aug06

    13:51

    Hi John,

    Not sure on which your thrust is based, design pressure or operating pressure? As we know, the design pressure is always about 10% higher than themost critcal operating pressure (plus static head) for some conservative margin. So if the thrust is calculated from design pressure, I would say the thrustis too conservative.

    BTW, I found the same results when I tried to introduce the thrust loads in WRC 107/297 check. The nozzles always relentlessly fail. But insteads, byusing FE method, the same nozzle in the same loading might pass the code.

    So I suggest using FE whenever WRC 107/297 fails. To be honest, I don't trust WRC 107/297.

    Comments?Thanks,

    gvc99 (Mechanical) 5Oct06

    7:46

    I have an opposite problem. How would you calculate limit loads for a vessel that you could give to a customer who hasn't designed his piping systemyet? I'm designing a vessel right now where the customer has not specified nozzle loads, but he knows there will be such loads and wants us to specify"not to exceed" loads for P, Mt, Vc, Mc, Vl, Ml (nomenclature per WRC 107/297).

    I can generate a matrix of stress effects from each loading by specifying a "unit" loading, say 1000 lb or 1000 in-lb and using CodeCalc to produce stressresults for a particular loading case. Does anybody have a rationale for using this information to produce a reasonable set of limit loads?

    NozzleTwister (Mechanical) 6 Oct06

    13:11

    gvc99,

    Several companies that I have worked for have had Nozzle Load Charts that show minimum allowable nozzle loads for each for all six directions. Nozzles

  • 6/20/2014 Boiler and Pressure Vessel engineering - vessel nozzle loading

    http://www.eng-tips.com/viewthread.cfm?qid=162558 6/7

    are to be designed to handle all loads simultaniously.

    The magnitude of the loads are such that they are reasonable for most vessels and reasonably achievable for reactions from most piping situations.

    For a vessel, you would choose loads for a reinforcd nozzle.

    Many companies have such charts, you can probably find a go-by from searching the net.

    NozzleTwisterHouston, Texas

    waskillywabbit (Mechanical) 6 Oct06

    16:31

    gvc99,

    IMO, this should not be your problem, it should be the customer's. Seems likes your customer wants the cart before they have a horse, and you are on aroad to possible trouble. Since the customer probably gave you a set of specs to design the pressure vessel, they should also provide you with a set ofspecs on nozzle loads, if they want the nozzles reinforced for piping loads. Not you provide them with a set of allowable loads so they can design theirpiping. Sounds like someone in the company you are working with/for isn't on the ball, as any company worth anything is going to have a pre-establishednozzle loading chart as twister mentions above.

    Brian

    lbower (Mechanical) 20Dec06

    17:21

    gvc99,

    When I have to provide 'not-to-exceed' loads, I provide a maximum resultant moment and a maximum resultant force. I calcuate the maximum forcevalue by finding the maximum radial force (concurrent with design pressure) and I find the maximum moment value by finding the minimum value ofeither the maximum circumferential moment or the maximum longitudinal moment (both also concurrent with design pressure). The actual resultantforce Fr = sqrt(Fx^2+Fy^2+Fz^2) and the actual resultant moment Mr = sqrt(Mx^2+My^2+Mz^2). The combination of forces and moments is Fr/Frmax+ Mr/Mrmax

  • 6/20/2014 Boiler and Pressure Vessel engineering - vessel nozzle loading

    http://www.eng-tips.com/viewthread.cfm?qid=162558 7/7

    all loads and inertias into account. Unusal only by scale. No prizes for guessing which load was used for the HD bolts and civil design.

    Vessels don't fall over very often so its only a real problem if you have to prove it. However, even that is never a problem - in my 30 years insurers andpublic inspectors only ever look at what they paid to look at - never the big picture.

    Join | Indeed Jobs | Advertise | About Us | Contact Us | Site Policies

    Copyright 1998-2014 Tecumseh Group, Inc. All rights reserved.Unauthorized reproduction or linking forbidden without express written permission.

    Read More Threads Like This One

    opensooq.com/_

    - - -