BMVIT-327.120/0060-II/ST2/2010
specification sheet for approval (Translation from the German original has not been certified by any authorities)
Object of approval: ANP – Micropiles SAS 550 with load - bearing elements
made of reinforcing steel bar ARI-G-55 with diameters 20,
25, 26, 28, 30, 32, 36, 40 and 50 mm and S 555/700 diameter
63,5 mm with thread ribs (B550B) for temporary, semi-
permanent (extended short term) or permanent use
Approval holder: ANP - SYSTEMS GMBH
Christophorusstraße 12
5061 Elsbethen/Austria
Manufacturer of load STAHLWERK ANNAHÜTTE
bearing element and Max Aicher GmbH & Co. KG
thread components: 83404 Ainring-Hammerau/Germany
Manufacturer of micropile- ANP - SYSTEMS GMBH
specific components Christophorusstraße 12
and corrosion protection: 5061 Elsbethen/Austria
External quality control: TVFA GmbH TU Wien
Area of validity: Austrian Republic
Road Administration
Reference: ÖNORM EN 14199: 2005
Execution of special geotechnical construction work (special
civil engineering, foundations construction / foundation
engineering) - piles with small diameters (micropiles)
GZ: BMVIT-327.120/0008-II/ST2/2009
Stahlwerk Annahütte:
hot rolled, hardened and tempered reinforcing steel with
left-hand threads ARI-G-55 with diameters 12, 14, 16, 20, 25,
26, 28, 30, 32, 36, 40 and 50mm according to
ÖNORM B 4200-7 (BSt 550) ductility / tensile properties
Agt 5% according to ONR 24200-7
ANP – SYSTEMS GMBH _________________________________________________________________________________________________________________________________________
Reference: GZ: BMVIT-327.120/0017-II/ST2/2009
Stahlwerk Annahütte:
hot rolled, hardened and tempered reinforcing steel with
left-hand threads S 555/700 diameter 63,5 mm according to
ÖNORM B 4200-7 (Bst 550) ductility / tensile
properties Agt 5% according to ONR 24200-7
GZ: BMVIT-327.120/0002-II/ST2/2009
Stahlwerk Annahütte:
threaded sleeve joints and threaded anchorage / anchorage
couplers for reinforcing steel ARI-G-55 with thread ribs, nominal
diameters 12, 14, 16, 20, 25, 26, 28, 30, 32, 36, 40 and 50 mm
based on ISO/FDIS 15835-1,2 and ÖNORM B 4200-7 and
respectively ONR 24200-7
GZ: BMVIT-327.120/0018-II/ST2/2009
Stahlwerk Annahütte:
threaded sleeve joints and threaded anchorage / anchorage
couplers for steel bars S 555/700 (Bst 550) with thread ribs,
nominal diameter 63,5mm based on ISO 15835-1,2 and
ÖNORM B 4200-7 and ONR 24200-7
The approval comprises 12 pages and 17 annexes.
ANP – SYSTEMS GMBH _________________________________________________________________________________________________________________________________________
I General Terms
1 This approval certificate is proof of the usability and applicability of the object of approval in accordance with the state building regulations (BMVIT, Federal Ministry for Transport, Innovation and Technology). The approval is granted and on the basis of non-harmonized technical specifications and without prejudice to third party rights
2 The approval holder is responsible for the building product´s conformity with the ap-proval and data sheet for the approval and guarantees any assured properties.
3 The approval refers only to the approval holder´s and manufacturer´s building product.
4 The BMVIT, Federal Ministry for Transport, Innovation and Technology is authorized to check at the license holder´s expense whether the regulations/provisions of this ap-proval and the data sheet are complied with.
5 The approval is not granted irrevocably. Provisions may be amended due to new techni-cal findings and standards.
6 The approval certificate may only be copied in its entirety. Texts and drawings in adver-tising brochures may not contradict the approval certificate.
II Special Terms
Contents
1 General 2 Reference standards 3 Description of the micropile system 4 Field of application 5 Construction material and construction product
5.1 Micropile 5.1.1 Properties and classification of the load bearing element 5.1.2 Requirements concerning the load capacity of micropile system
5.2 Pile head 5.2.1 Pile head design 5.2.2 Load transfer on to the structure
5.3 Coupling 5.4 Grouting
6 Service life 6.1 Corrosion protection 6.2 Exposure to corrosion 6.3 Types of micropiles
6.3.1 Micropiles for short term use and semi-permanent use 6.3.2 Micropiles for permanent use 6.3.2.1 Micropiles with standard corrosion protection 6.3.2.2 Micropiles with double corrosion protection
7 Installation of micropiles 8 Inspections
8.1 Material tests 8.2 Load tests
17 annexes
ANP – SYSTEMS GMBH _________________________________________________________________________________________________________________________________________
1 General
The planning, dimensioning, construction, inspection and supervision of micropiles may only be carried out by companies with expertise, experience and qualified personnel.
Responsibilities for planning, dimensioning, construction, inspection and supervision have to be agreed on by contract for the implementation of a building project.
The manufacturer guarantees that the micropiles and the corrosion protection are consistent with the approval.
2 Reference standards
ÖRNOM EN 14199: 2005 Execution of special geotechnical construction work (special civil engineering, foundations construction/ foundation engineering) - piles with small diameters (micropiles)
ÖNORM EN 1990: 2003 Eurocode – Basis of structural design
ÖNORM EN 1997-1: 2004 Eurocode 7 – Geotechnical design - Part 1: General rules
ÖNORM B 4707: 2010 Steel for the reinforcement of concrete - Requirements, classification and conformity assessment
ÖNORM EN 1992-1-1: 2005 Eurocode 2: Design of concrete structures - Part 1-1: General rules and rules for buildings
ISO 15835-1,2: 2009 Steels for the reinforcement of concrete – Reinforcement couplers for mechanical splices of bar
Part 1: Requirements
Part 2: Test methods
ÖNORM EN ISO 15630-1: 2002 Steel for the reinforcement and prestressing of concrete - Test methods - Part 1: Reinforcing bars, wire rod and wire
ETAG 013: 2002 Guideline for European technical approval of post-tensioning kits for prestressing of structures
ÖNORM EN 206-1: 2001 Concrete - Part 1: Specification performance, production and conformity
ÖNORM EN ISO 1461: 2000 Hot dip galvanized coatings on fabricated iron and steel articles - Specifications and test methods
ÖNORM EN 1537: 2000 Execution of special geotechnical work - Ground anchors
ÖNORM EN 12501-1,2: 2003 Protection of metallic materials against corrosion - Corrosion likelihood in soil
Part 1: General
Part 2: Low alloyed and non alloyed ferrous materials
ÖNORM EN ISO 9001: 2000 Quality management systems - Requirements
ÖNORM EN 445: 2008 Grout for prestressing tendons - Basic requirements
ÖNORM EN 446: 2008 Grout for prestressing tendons - Test methods
ÖNORM EN 447: 2008 Grout for prestressing tendons - Grouting procedures
ANP – SYSTEMS GMBH _________________________________________________________________________________________________________________________________________
3 Description of the micropile system
The load-bearing element of the ANP – Micropile SAS 550 is a throughout screwable left-hand
reinforcement steel bar with thread ribs ARI-G-55 with diameters 20, 25, 26, 28, 30, 32, 36, 40 and 50mm and S 555/700, diameter 63,5mm
for geotechnical applications.
The use of the reinforcement steel including the screwed coupler and anchorage is derived from the existing BMVIT approval of the system. The reinforcement steel is classified as an B550B according to ÖNORM B 4707.
The micropile is put into the center of a pre-drilled borehole and is then grouted with cement grout.
The pile head is made up of a straight square plate locked with nuts (anchor nut / lock nut) or it’s made up of a nut-locked cylindrical cast steel anchor piece. Coupling is possible with a coupler with or without lock nut.
Service life of micropile systems:
- micropiles for temporary use (service life max. 2 years)
- micropiles for extended short term use in consideration of corrosionrate (service life 2 - 50 years)
- permanent micropiles (service life up to 100 years) with standard corrosion protection by means of cement mortar covering
- permanent micropiles (service life up to 100 years) with double corrosion protection by means of tubing according to ÖNORM EN1537
Following annexes describe further details of the micropile system:
Annex 1: drawing of micropile system for temporary use, pile head options and couplings
Annex 2: drawing of micropile system for semi-permanent use, pile head options and couplings
Annex 3: drawing of permanent piles with standard corrosion protection (cement mortar covering), pile options and couplings
Annex 4: drawing of permanent piles with double corrosion protection according to ÖNORM EN 1537, pile head options and couplings
Annex 5 pile head options with alternative anchorage (anchor piece with nut lock)
Annex 6: center distance and edge distance of the micropile system with pile head plate and anchor piece, additional reinforcement, torque for coupling and anchorage
Annex 7 and 8: data for steel bar with thread ribs ARI-G-55, diameters 20 - 50mm and S555/700, diameter 63,5mm
Annex 9: loss of load capacity of the micropile due to corrosion
Annex 10 to 15: accessories and components of corrosion protection with dimensions and material grade
Annex 16 and 17: production of micropiles, factory-made of corrosion protection, transport and storage, installation
ANP – SYSTEMS GMBH _________________________________________________________________________________________________________________________________________
4 Field of application
Pile foundations serve to transfer building loads to deeper layers of ground and limitation of deformations according to the principles for the execution of geotechnical works. The piles may be used only for axial tension, pressure and alternating load.
The execution principles for construction are stated in ÖNORM EN 14199 and comprise information about pile foundation, soil examination, construction material and products, dimen-sioning as well as the installation of piles including tests and supervision.
The principles according to ÖNORM EN 1990 are to be considered of structural design be adhered to ÖNORM EN 1997-1 contains further geotechnical dimensioning rules.
Compliance with following standards is necessary:
- The foundation has to be calculated with regard to load transfer into the pile head (additional reinforcement, punching).
- With soils which allow lateral deflection of the pile, the buckling safety has to be clarified either by calculation or test loading.
5 Construction material and construction product
5.1 Micropile
5.1.1 Properties and classification of the load bearing element
A heat-treated concrete reinforcing steel bar from the rolling heat ARI-G-55, diameters 20-50 and S555/700, diameter 63,5, with left-hand thread ribs may be used as a load bearing element reinforcement steel B550B according to ÖNORM B 4707.
Weldability and bending property are not relevant for the intended geotechnical use.
Please find the parameters of the reinforcing steel in annex 7 and 8. The reinforcement steel is classified as B550B according to ÖNORM B 4707. The reinforcement steel with thread ribs can also be used for a lower steelgrade than B550B. The reinforcing steel bars fulfill the requirements of ÖNORM EN 1992-1-1, see appendix C.
The requirements concerning ”bond effect” in the pile length of the load bearing element are fulfilled by thread ribs of the steel bar.
For extended short term service life of the micropile system, a hot-dip galvanized surface coating of the steel bar may be carried through according to ÖNORM EN ISO 1461.
5.1.2 Requirements concerning the load capacity of micropile system
The following requirements have to be complied with:
- The micropile´s tensile load capacity, consisting of the components pile (reinforcement steel B550B), pile head and coupler, has an efficiency of 100% in respect of the charac-teristic ultimate load of the support load bearing element according to ÖNORM EN 14199. In case of a failure the system shows ductile forming.
- In case of an anchorage or coupler failure the elongation value measured at the steel bar must not be below Agt = 3,5 %.
ANP – SYSTEMS GMBH _________________________________________________________________________________________________________________________________________
- The rated value for the micropile´s ultimate limit state is, according to ÖNORM EN 1992-1-1, to be set with a partial safety factor of 1,15 when reaching a yield strength Fp0.2. The soil conditions have to be measured in accordance with ÖNORM EN 1997-1. ÖNORM EN 1990 applies to the soil support capability.
- With a torque moment - according to annex 6 - under tensile load of the anchorage´s or coupler´s ultimate limit state a slip 0,1 mm is kept according to ISO 15835- 1. A slip has to be set at up to 1,0 mm on a non-torqued coupler, with a pile diameter of 63,5mm up to 2,0 mm.
As fatigue strength parameter a stress range Rsk for load N = 2 × 106 cycles with a stress value of 0,6 Rp0.2 is proven:
- Ø 20 to 32 mm: 90 N/mm²
- Ø 36 and 40 mm: 80 N/mm²
- Ø 50 and 63,5 mm: 60 N/mm²
- When a corrosion rate is intended then the loss of cross section has to be considered with proof of load capacity. Please refer to annex 9.
5.2 Pile head
5.2.1 Pile head design
The pile head design is either made up of pile head plate fixed by nuts (anchor nut / locknut) or
a torqued cylindrical anchor piece with or without bursting reinforcement. When an anchor piece
is used, a additional bond length has to be complied with according to annex 5.
The connection from the micropile in the foundation body demands both with semi-permanent
and permanent piles with standard corrosion protection a pile neck sheating by means of a
plastic corrugated sheathing to seal a possible construction joint.
Details about the corrosion protection system´s parameters, accessories, components and
materials see annex 10 to 14. The torque moments are listed in annex 6.
5.2.2 Load transfer on to the structure
Load transmission from the foundation body to the pile head can be carried out with or without
additional reinforcement (bursting reinforcement). Design criteria are the requirements accord-
ing to ETAG 013. With the following values an efficiency of 110% with additional reinforcement
and an efficience of 130% without additional reinforcement is achieved related to the character-
istic breaking force of the load bearing element:
- concrete compressive strength at time of applied load 25 N/mm² (cube 150 mm)
- minimum concrete quality C 20/25 according to ÖNORM EN 206-1
- center distance and edge distance of the micropile system with end anchorage by means pile head plate or anchor piece, with or without additional reinforcement (bursting reinforcement) according to annex 6
ANP – SYSTEMS GMBH _________________________________________________________________________________________________________________________________________
5.3 Coupling
The load bearing element can be coupled by couplers. The coupler has to be locked with nuts in case of tensile and alternating load. In case of compression load the coupler has to be secured against unscrewing with heat shrink sleeve.
When temporary and permanent piles with sheathing in accordance with ÖNORM EN 1537 are used, locking might be dispensed with in case of tensile loads. A locking device to prevent unscrewing is required.
Data concerning coupler parameters and material see annex 12.The torque moments are listed in annex 6.
5.4 Cement grout
An outer cement grout cover of installed micropiles to the borehole wall is conditional of manu-facturing. ÖNORM EN 1992-1-1 comprises approaches for the required minimum covering al-lowing for the aggressiveness classes (see ÖNORM EN 206-1).
Spacers are used to position the pile concentrically. Cement grout is used to build the outer body (see ÖNORM EN 14199). The water-cement ratio has to be adapted to the building site conditions.
The corrosion protection of the permanent pile with double corrosion protection (DCP) is build up by a corrugated sheathing with minimum wall thickness 1,0 mm and an inner cement grout cover between corrugated sheathing and pile of at least 5 mm. This equates the corrosion protection of the permanent anchor´s bond length according to ÖNORM EN 1537. The pile is positioned concentrically either with a cord or a mat spacer.
Both the corrosion protection and the inner cement grout cover are applied in the factory. The cement grout used complies with the standards of ÖNORM EN 445, ÖNORM EN 446 and ÖNORM EN 447.
6 Service life of the micropile construction
6.1 Corrosion protection
The micropile system at hand uses the following methods to reach the desired service life:
- no separate measures for temporary use (max. 2 years) - allowance for corrosion rate in case of limited use for semi-permanent service life - surface coating by hot dip galvanizing - encapsulation is due to the system by designing an grout body (standard corrosion
protection) for permanent use with the required minimum covering - sheathing (double corrosion protection - according to ÖNORM EN 1537) for
permanent use
Further requirements concerning the corrosion protection of semi-permanent micropiles and micropiles with standard corrosion protection have to be derived from a critical assessment of the building and ambient conditions. Even with an early breakdown of single elements the bearing capacity of the micropile foundation has to be assured. The application of single elements is not intended.
Corrosion protection by means of corrosion rate may only be used with a statistically secured number of elements (redundant system - to increase the reliability of the system).
ANP – SYSTEMS GMBH _________________________________________________________________________________________________________________________________________
6.2 Exposure to corrosion
To evaluate exposure to corrosion of metallic material in soil according to ÖNORM EN 12501 - 1,2 shall be used. Exposure to corrosion is classified as:
- low
- medium
- high
The most important physical and chemical parameters of soil and foundation materials are dealt with in ÖNORM EN 12501-2. Appendix B of the norm contains detailed data for soil classification.
An evaluation of the different exposures to corrosion is done by means of an informative table with essential soil parameters. These parameters are the basis for the indication of size con-cerning the respective corrosion rate of the micropile.
Criteria for exposure to erosion in soils
soil parameters exposure to corrosion in soil
Low medium high
ventilation moderate to very good
bad to moderate
very bad to bad
soil properties / composition
predominantly sand, gravel, weathered rock (coarse or medium dis-
persed/mixed: rock, sand, clay)
high percentage of, silt (medium dispersed to
finely dispersed)
High percentage of clay (finely dispersed) industrial waste,
de-icing salt
soil moisture low
(drainageable) generally medium
(moist) generally high,
floodplain
neutral salt concentration
Low Possibly
increased Possibly high
ph-value 5 to 8 5 to 8 5 to 8
specific resistance [ m]
> 70 10 to 70 < 10
with ph- values < 5 and > 8 an upgrade is necessary:
low medium
medium high
high limited use DCP according ÖNORM EN 1537
6.3 Types of micropiles
6.3.1 Micropiles for short term use and semi-permanent use
Annex 1 contains a schematic drawing of the temporary micropile. The micropile has to be center positioned in the borehole. For temporary use no further measures for corrosion protection have to be taken. If exposure to corrosion is high, corrosion is avoided by a cement grout cover 15 mm.
ANP – SYSTEMS GMBH _________________________________________________________________________________________________________________________________________
The coupler must be secured against unscrewing by means of a heat shrink sleeve under tensile and compression load. Optionally, a contact coupler may be used only under compres-sion load. Under alternating load the coupler has to be secured with lock nuts.
Annex 2 contains a schematic drawing of the semi-permanent micropile. Pile neck sheathing and plastic corrugated sheathing are used for the connection between the micropile and the foundation body.
The coupler must be secured with lock nuts under tensile and alternating load. (a fixing with lock nuts is required). Under compressive load the coupler has to be fixed against unscrewing by means of a heat shrink sleeve. Optionally, a contact coupler may be used only under compres-sion load.
The planned service life and the soil´s exposure to corrosion determine the size of the corrosion rate. The cement grout cover is at least 15 mm.
The reference values for the corrosion of the micropile in soil are derived from results of long-term storage. The corrosion rate is stated for a low, medium and high exposure to corro-sion and a service life of 2, 7, 30 and 50 years. The Rounding parameter is 0,1 mm.
The corrosion rates mentioned here for blank steel and galvanized steel are not relevant in this case because the micropile is center positioned in the borehole and then grouted with cement mortar. However, the corrosion rates are mentioned here are a relevant output variable for the corrosion of steel.
With consideration of a cement grout cover of at least 15 mm a slowing down of the carbonation process dependent on exposure to corrosion in soil of steel is achieved and the corrosion rate is reduced.
Reference value for corrosion rate under soil aggressiveness
service life in years pile type
corrosion rate in mm under exposure to corrosion
low medium high
2
A B A+C B+C
0 0 0 0
0 0 0 0
0,2 0 0 0
7
A B A+C B+C
0,2 0 0 0
0,2 0 0 0
0,5 0,4 0 0
30
A B A+C B+C
0,4 0
0,2 0
0,6 0,2 0,4 0
DCP
50
A B A+C B+C
0,5 0,2 0,4 0
DCP DCP
A blank steel, not grouted
B galvanized steel, zinc coating layer thickness 150µm, not grouted
C cement grout cover 15 mm
DCP double corrosion protection according to ÖNORM EN 1537
ANP – SYSTEMS GMBH _________________________________________________________________________________________________________________________________________
Annex 9 contains details concerning the loss of a micropile´s load-bearing capacity due to corrosion. Therewith also the corrosion at the coupling is covered when the coupler´s cement grout cover is 15 mm.
6.3.2 Micropile for permanent use
6.3.2.1 Micropile with standard corrosions protection by means under cement grout cover
Annex 3 contains a drawing of the permanent micropile with standard corrosion protection. The pile neck has to be provided with a pile neck casing as with the semi-permanent pile. For the coupling the same set up shall be applied as with the semi-permanent micropile.
The permanent pile´s corrosion protection is achieved by means of encapsulation in a grout body. The required cement grout cover is dependent on soil class and is specified in relevant european geotechnical standards. The crack width under tensile load is limited to 0,2 mm.
For micropiles with coupling the required minimum cement grout cover shall correspond to the coupler´s external diameter (including heat shrink sleeve).
Reference values for the required minimum covering
exposure to corrosion in soil
cement grout cover in mm
compression load tension load
low 25 35
medium 30 40
high DCP according to ÖNORM EN 1537
6.3.2.2 Micropile with double corrosions protection (DCP) according to ÖNORM EN 1537
Annex 4 contains a schematic drawing of the permanent micropile with DCP according to
ÖNORM EN 1537. The essential corrosion protection components are:
pile shaft: Corrugated sheathing 1,0 mm with internal cement grout thickness 5 mm - distance between load - bearing element and corrugated
sheathing.
External cement grout covering 10 mm to the borehole wall. The ground - facing pile end is enclosed by a plastic cap.
coupling: The coupler has to be torqued with nuts only with alternating load. With compression load a contact coupler may be used instead.
pile neck: The load - bearing element is sealed against the corrugated sheathing with tape via an end or injection cap. The corrugated sheathing of the pile shaft is lead into the foundation body.
ANP – SYSTEMS GMBH _________________________________________________________________________________________________________________________________________
7 Installation of micropiles
Instructions for installation of micropiles and for the production of the factory-made corrosion protection can be found in annex 15 and 16.
Micropiles may only be installed by professional staff in compliance with the listed procedural requirements and installation instructions of the approval holder.
8 Inspections
8.1 Material tests
The manufacturer of micropiles has to carry out internal production and quality control regulated
by ÖNORM EN ISO 9001.
These norms refer to the:
- production of micropile components
- production of the corrosion protection system
Internal and external quality and production control of the micropile components are regulated
by BMVIT approvals (see reference approvals on page 1 and 2.
The production of the pile head plate may also be carried out by the manufacturer of the corrosion protection system according to specific dimensions. The manufacturer is then involved in internal quality control for the plates.
The external control has to be carried out by an accredited inspection authority based on a supervision contract. Additionally, the scope of internal control is specified in the supervision contract. The approval holder and the external inspection authority have to conclude a supervision contract. External control has to be executed once a year. The results have to be submitted in a report.
8.2 Load tests
Load tests have to be made and documented at the building site where required in accordance
with ÖNORM EN 14199.
AB
0 0
2
0,20 00 0
0 0
00
0
Ø
1
11
11
13
1
8
3
14
1
11
6
11
13
1
8
3
14
1
11
6
11
13
1
5
5
3
14
t1R
t1R
t1R
2 / 2a
4 / 4a
4 / 4a
2 / 2a
2 / 2a
2 / 2a
compression load alternating loadtension load
min. borehole - Ø
26
532025 59
28303236405063,5
646671758699
6670757580829095110132
6062
withcoupler
without coupler
micropile for temporary use
[mm]
low medium high
up to
service life
in years
steel bar
6 or 7
corrosion rate in mm
under exposure to corrosion
type of
pile
A - blank steel, not groutedB - galvanized steel, zinc coating layer thickness 150 µm, not groutedC - cement grout covering 15 mm
A + CB + C
t1R
150 mm [ Ø 20 - 32 ]
t1R
200 mm [ Ø 40 - 63,5 ]
1 steel bar with thread ribs
2 hex nut
2a hex nut - cast iron
3 pile head plate
4 lock nut, short
4a lock nut, short - cast iron
5 lock nut, long
6 coupler
7 contact coupler
8 heat shrink sleeve
11 spring basket spacer
13 cement grout cover
14 additional reinforcement
ANP - SYSTEMS
GmbHAnnex 1
ANP - Micropile SAS 550steel bar ARI-G-55 Ø 20-50 and steel bar S 555/700 Ø 63,5 with thread ribstemporary micropile
1
11
11
13
1
17
8
3
14
1
11
6
11
13
1
17
3
14
1
11
6
11
13
1
5
5
3
14
17
t1R
t1R t1R
2 / 2a
4 / 4a
4 / 4a
2 / 2a
2 / 2a
2 / 2a
4 / 4a
4 / 4a
compression load alternating loadtension load
6 or 7
service life
in years
26
532025 59
28303236405063,5
646671758699
6670757580829095110132
6062
Ø
min. borehole - Ø
withcoupler
without coupler[mm]
steel bar
AB
A+CB+C
0,2 0,2
2 - 7
0,50 00 0
0 0
0,40
0
AB
A+CB+C
0,4 0,6
7 - 300 0
0,2 0,4
0 0AB
A+CB+C
0,5
30 - 500,20,4
0
DCP
DCP
DCP
low medium high
corrosion rate in mm
under exposure to corrosionmicropile for semi-permanent use
type of
pile
1 steel with thread ribs
2 hex nut
2a hex nut - cast iron
3 pile head plate
4 lock nut, short
4a lock nut, short - cast iron
5 lock nut, long
6 coupler
7 contact coupler
8 heat shrink sleeve
11 spring basket spacer
13 cement grout cover
14 additional reinforcement
17 pile neck sheathing
t1R
150 mm [ Ø 20 - 32 ]
t1R
200 mm [ Ø 40 - 63,5 ]
A - blank steel bar, not groutedB - galvanized steel, zinc coating layer thickness 150 µm, not groutedC - cement grout covering 15 mmDCP - double corrosion protection acc. to ÖNORM EN 1537
ANP - SYSTEMS
GmbHAnnex 2
ANP - Micropile SAS 550steel bar ARI-G-55 Ø 20-50 and steel bar S 555/700 Ø 63,5 with thread ribssemipermanent micropile
73 86 93 106 83 96 103 11620
79 90 99 110 89 100 109 12025
80 95 100 115 90 105 110 12526
82 95 102 115 92 105 112 12528
84 100 104 120 94 110 114 13030
86 102 106 122 96 112 116 13232
91 110 111 130 101 120 121 14036
95 115 115 135 105 125 125 14540
106 130 126 150 116 140 136 16050
119 152 139 172 129 162 149 18263,5
25
30
35
40
t1R
1
11
11
13
1
17
8
3
14
t1R
1
11
6
11
13
1
5
5
17
3
14
t1R
1
11
6
11
13
1
17
3
14
2 / 2a
4 / 4a 2 / 2a
4 / 4a 2 / 2a
2 / 2a
4 / 4a
4 / 4a
compression load alternating loadtension load
6 or 7
DCP according to ÖNORM EN 1537
tension loadcompression load
low
medium
high
withoutcoupler[mm]
withcoupler[mm]
withoutcoupler[mm]
withcoupler[mm]
withoutcoupler[mm]
withcoupler[mm]
withoutcoupler[mm]
withcoupler[mm]
compression tension compression tension
min. borehole - Ø
permanent micropile for service life up to 100 years
low exposure to corrosion medium exposure to corrosion
exposure to
corrosion in soil
min. grout covering in mm
Ø
steel bar
[mm]
t1R
150 mm [ Ø 20 - 32 ] t1R
200 mm [ Ø 40 - 63,5 ]
1 steel bar with 6 coupler
thread ribs 7 contact coupler
2 hexnut 8 heat shrink sleeve
2a hexnut - cast iron 11 spring basket spacer
3 pile head plate 13 cement grout cover
4 lock nut, short 14 additional
4a lock nut, short - cast iron reinforcement
5 lock nut, long 17 pile neck sheathing
ANP - SYSTEMS
GmbHAnnex 3
ANP - Micropile SAS 550steel bar ARI-G-55 Ø 20-50 and steel bar S 555/700 Ø 63,5 with thread ribspermanent micropile with standard corrosion protection
t1Rt1R
t1R
1
3
14
16
15
1
3
1
3
16
15
14 14
16
15
13
11
8
11
10
1615
13
11
8
11
10
1615
13
11
8
11
10
1615
6 6
5
2 / 2a
4 / 4a
4 / 4a
2 / 2a
2 / 2a
2 / 2a
5
1
9
1313
1
9
13
1
9
compression load alternating loadtension load
6 or 7
26
2025
28303236405063,5
Ø
min. borehole - Ø
withcoupler
without coupler[mm]
steel bar
7070 70
7070
7070707676
7676
8585
85
100120 125
10388
micropile for permanent use
t1R
150 mm [ Ø 20 - 32 ]
t1R
200 mm [ Ø 40 - 63,5 ]
1 steel bar with thread ribs 8 heat shrink sleeve
2 hex nut 9 corrugated sheathing
2a hex nut - cast iron 10 inside spacer
3 pile head plate 11 spring basket spacer
4 lock nut, short 13 cement grout cover
4a lock nut, short - cast iron 14 additional reinforcement
5 lock nut, long 15 injection- and endcap
6 coupler 16 adhesive tape
7 contact coupler
ANP - SYSTEMS
GmbHAnnex 4
ANP - Micropile SAS 550steel bar ARI-G-55 Ø 20-50 and steel bar S 555/700 Ø 63,5 with thread ribspermanent micropile with DCP - double corrosion protection
14
1
17t1R
1
17t1R
14
1
17t1R
14
12
12 12
LV
LV
LV
4 / 4a
4 / 4a 2 / 2a
14
1 1
t1R
14
1
t1R
14
12
12 12
9 99
151515
10
13
10
13
10
13
LV
LV
LV
t1R
2 / 2a4 / 4a
4 / 4a
16 16 16
26
2025
28303236405063,5
Ø
[mm]
200250260280300320360400500635
tension load compression load alternating load
tension load compression load alternating load
permanent micropile with - DCP(tubing acc. to ÖNORM EN 1537)
* min. concrete strenght 25N/mm²
additional bond lenght *
Lv 10 ds[mm]
steel bar
LV - additional bond length
LV - additional bond length
t1R
150 mm [ Ø 20 - 32 ]
t1R
200 mm [ Ø 40 - 63,5 ]
semipermanent- and permanent micropile with standard corrosion protection
1 steel bar with thread ribs 12 anchor piece
2 hexnut 13 cement grout cover
2a hexnut - cast iron 14 additional reinforcement
4 lock nut, short 15 injection- and endcap
4a lock nut, short - cast iron 16 adhesive tape
9 corrugated sheathing 17 pile neck sheathing
10 inside spacer
note: - for temporary micropiles no pile neck sheathing is neccesary acc. to 17
- embedment length t1R
is valid for pile neck sheathing as well as
micropiles with DCP
ANP - SYSTEMS
GmbHAnnex 5
ANP - Micropile SAS 550steel bar ARI-G-55 Ø 20-50 and steel bar S 555/700 Ø 63,5 with thread ribspile head design with additional bond length
1 ) distances is vaild for anchor piece and for anchorage
2 ) without additional reinforcement the value for center - and edge distance is to double
c...concrete cover of constructive reinforcement according to valid standards, regulations at the
place of application and exposure classes according to ÖNORM EN 206-1 where required
torquecoupling and anchorages
center - and edge distances, additional reinforcementconcrete compressive strength at time of aplied load 25 N/mm² (cube 150 mm)min. concrete quality C 20/25 acc. to ÖNORM En 201-1
mechanical anchorage with additional reinforcement, (reinforcing steel, Re 500N/mm²)
type load bearing element
Ø[mm]
torque[kNm]
20 0,4
25 0,7
26 0,8
28 1,0
30 1,2
32 1,6
36 2,7
40 3,7
50 8,0
anchorage 63,5 8,0
coupling 63,5 12,0
coupling / anchorage
quantityn
Ø[mm]
a[mm]
c[mm]
20 130 3 6 100 30
25 150 4 6 130 40
26 150 4 6 130 40
28 165 4 6 145 40
30 180 3 8 155 45
32 180 3 8 155 50
36 220 3 10 180 45
40 250 3 10 220 45
50 270 5 10 250 45
63,5 380 4 16 350 70
load bearingelement
Ø[mm]
center -
distance 1)
A[mm]
edge -
distance 1)
R[mm]
additional reinforcement 2) (BSt 550)
A × 0,5 + nom c
ANP - SYSTEMS
GmbH
ANP - Micropile SAS 550steel bar ARI-G-55 Ø 20-50 and steel bar S 555/700 Ø 63,5 with thread ribscenter- and edge distances, additional reinforcement, torque
Annex 6
R c bs
a
dh
dv
a
A
cross section
1) tolerance to nominal mass ± 4,5%
detail A
1 steel bar with thread ribs
geometry
nominal dimensions and mass, rib geometry
dh
[mm]
dv
[mm]
heightmin. a[mm]
width
bs
[mm]
pitchc
[mm]
angle
[grad]
radiusR
[mm]
20 2,47 314 19,5 19,1 1,0 4,8 10,0 81,5 2,0
25 3,85 491 24,4 23,9 1,3 5,8 12,5 81,5 2,0
26 4,17 531 25,4 24,9 1,4 6,0 13,0 81,5 2,0
28 4,83 616 27,3 26,8 1,5 6,7 14,0 81,5 2,5
30 5,55 707 29,3 28,8 1,7 7,1 15,0 81,5 2,5
32 6,31 804 31,2 30,9 1,8 7,6 16,0 81,5 2,5
36 7,99 1020 35,2 34,7 1,9 8,5 18,0 81,5 2,5
40 9,87 1260 39,1 38,5 2,1 9,5 20,0 81,5 2,5
50 15,40 1960 48,9 48,3 2,3 12,0 26,0 81,0 2,5
63,5 24,86 3167 62,4 61,6 2,7 10,8 21,0 84,0 4,0
nominaldiameter
ds
[mm]
Mass
per meter1)
G[kg/m]
nominalcross
sectionA
[mm²]
core diameter threaded ribs (left handed)
ANP - SYSTEMS
GmbHAnnex 7
ANP - Micropile SAS 550steel bar ARI-G-55 Ø 20-50 and steel bar S 555/700 Ø 63,5 with thread ribsnominal dimensions and mass, rib geometry
1 steel bar with thread ribs
properties and requirements
nominaldiameter
characteristic
ultimate force 5)
ds Fm
[mm] [kN]
20 187
25 292
26* 316
28 367
30* 421
32 478
36* 605
40 747
50 1167
63,5 1882
Re N/mm²
Rm/Re -
Agt %
N/mm²
560
691
1080
1742
5) acc. to yield strength ratio
550
1,08
5,0
487
300maximum stress max
939
601
1515
elongation at ultimate load 3)
characteristic yield strength 1), 2)
270
292
339
389
442
* dimension only available on request
1) 5% - fractile value2) Re corresponds to Rp0,2 – yield strength3) 10% - fractile value
120
100
fatigue range for 2×106
cyclesN/mm²
4) partial factor for steel acc. to ÖNORM EN 1992-1-1
steel barsØ > 36 mm
steel barsØ 20 bis 36 mm
ratio 3)
design resistancevalue of micropile
R = Fe /1,15 4)
characteristicyield force
Fe
[kN]
338
384
295
150
235
254
[kN]
173
ANP - SYSTEMS
GmbHAnnex 8
ANP - Micropile SAS 550steel bar ARI-G-55 Ø 20-50 and steel bar S 555/700 Ø 63,5 with thread ribsmechanical - technological characteristics acc. ÖNORM B 4707
1 steel bar with thread ribs
table loss of load capacity under exposure of corrosion
Fp0,2 yield strength under exposure for corrosion R design resistance value of micropile * dimension only available on request
0,0 0,2 0,4 0,5 0,6
Fp0,2 kN 173 166 160 156 153
R kN 150 144 139 136 133
Fp0,2 kN 270 261 253 249 245
R kN 235 227 220 217 213
Fp0,2 kN 292 283 274 270 266
R kN 254 246 238 235 231
Fp0,2 kN 339 329 320 315 310
R kN 295 286 278 274 270
Fp0,2 kN 389 378 369 364 358
R kN 338 329 321 317 311
Fp0,2 kN 442 431 421 415 410
R kN 384 375 366 361 357
Fp0,2 kN 560 547 535 529 523
R kN 487 476 465 460 455
Fp0,2 kN 691 677 664 657 650
R kN 601 589 577 571 565
Fp0,2 kN 1080 1063 1046 1037 1029
R kN 939 924 910 902 895
Fp0,2 kN 1742 1720 1698 1687 1677
R kN 1515 1496 1477 1467 1458
Ø 40
Ø 50
Ø 63,5
Ø 26*
Ø 28
Ø 30*
Ø 32
Ø 36*
micropile valuecorrosion rate in mm
Ø 20
Ø 25
ANP - SYSTEMS
GmbHAnnex 9
ANP - Micropile SAS 550steel bar ARI-G-55 Ø 20-50 and steel bar S 555/700 Ø 63,5 with thread ribsloss of load capacity under exposure of corrosion
Ø 63,5
LS
W
Ø
Ø 20 - 50 Ø 63,5
LL
SW
Ø
Ø 20 - 50
LS
WS
W
SW
Ø
L
2 hexnut material: Ø 25 - 50 : S355J2
Ø 63,5 : 20MnV6+U acc. to ÖNORM EN 10025
2a hexnut - cast iron material: Ø 40 - 63,5: EN-GJS-500-7 acc. to ÖNORM EN 1563,
G34CrMo4 acc. to ÖNORM EN 10293
4 lock nut, short material: S355J2 acc. to ÖNORM EN 10025
load bearing
elementØ
[mm]SW
[mm]L
[mm]Ø
[mm]
20 32 20 -
25 41 20 -
26 41 25 -
28 41 25 -
30 50 30 -
32 50 30 -
36 55 30 -
40 60 35 -
50 80 50 -
63,5 90 75 102
load bearing element
Ø[mm]
SW[mm]
L[mm]
Ø[mm]
20 36 45 -
25 41 50 -
26 46 50 -
28 46 55 -
30 50 60 -
32 55 60 -
36 60 65 -
40 65 70 -
50 80 90 -
63,5 100 115 108
load bearing element
Ø[mm]
SW[mm]
L[mm]
Ø[mm]
40 65 70 85
50 80 85 100
63,5 100 115 125
ANP - SYSTEMS
GmbHAnnex 10
ANP - Micropile SAS 550steel bar ARI-G-55 Ø 20-50 and steel bar S 555/700 Ø 63,5 with thread ribscomponents: hexnut, lock nut short
Ø 20 - 50 Ø 63,5
L L
SW
SW
Ø
L
L
Ø
SW
SW
Ø
4a lock nut, short - cast ironmaterial: Ø 40 - 63,5: EN-GJS-500-7 acc. to ÖNORM EN 1563
GE 300, G34CrMo4 acc. to ÖNORM EN 10293
5 lock nut , long material: S355J2 acc. to ÖNORM EN 10025
12 anchor piece material: EN-GJS-500-7
acc. to ÖNORM EN 1563
load bearing element
Ø[mm]
SW[mm]
L[mm]
Ø[mm]
40 60 35 69
50 80 50 92
63,5 90 75 104
load bearing element
Ø[mm]
SW[mm]
L[mm]
Ø[mm]
20 32 40 -
25 41 40 -
26 41 45 -
28 41 45 -
30 50 50 -
32 50 50 -
36 55 55 -
40 60 65 -
50 80 80 -
63,5 90 115 102
load bearing element
Ø[mm]
SW[mm]
L[mm]
Ø[mm]
20 36 40 65
25 41 45 70
26 41 50 90
28 46 50 90
30 50 55 95
32 50 60 100
36 60 65 110
40 65 70 120
50 80 85 150
63,5 100 115 250
ANP - SYSTEMS
GmbHAnnex 11
ANP - Micropile SAS 550steel bar ARI-G-55 Ø 20-50 and steel bar S 555/700 Ø 63,5 with thread ribscomponents: lock nut short, lock nut long, anchor piece
Ø
L
Ø
a
a
c
Ø
L
3 pile head plate material: S235JR acc. to ÖNORM EN 10025
6 coupler material: S355J2 acc. to ÖNORM EN 10025-2
7 contact coupler material: S355J2 acc. to ÖNORM EN 10025-2
load bearing element
Ø[mm]
L[mm]
Ø[mm]
20 105 36
25 115 40
26 120 45
28 125 45
30 135 50
32 140 52
36 150 60
40 160 65
50 200 80
63,5 260 102
load bearing element
Ø[mm]
L[mm]
Ø[mm]
20 70 32
25 80 36
26 80 36
28 85 40
30 90 45
32 90 45
36 110 50
40 120 52
50 160 65
63,5 200 90
load bearing element
Ø[mm]
a[mm]
c[mm]
Ø[mm]
20 70 10 25
25 70 10 30
26 70 10 33
28 100 12 33
30 120 20 36
32 120 20 40
36 150 30 44
40 150 30 47
50 190 45 58
63,5 245 50 70
ANP - SYSTEMS
GmbHAnnex 12
ANP - Micropile SAS 550steel bar ARI-G-55 Ø 20-50 and steel bar S 555/700 Ø 63,5 with thread ribscomponents: pile head plate, coupler, contact coupler
da di
L
L
Ø i
t
8 heat shrink sleeve
9 corrugated sheathing material: PVC-U acc. to DIN 8061/8062
material: PE acc. to DIN 8074/8075
load bearing element
Ø
Øi
bevor shrinking /after shrinking
tbevor shrinking /after shrinking
L
[mm] [mm] [mm] [mm]
63,5 115 / 34
min. 0,50 / min. 1,0as
required *
* overlapping heat shrink sleeve / corrugated sheating min. 7,5 cm bevor shrinking
95 / 29
20 - 32
36 - 50
75 / 22
min. da / min. di min. t L
[mm] [mm] [mm] [mm]
20
25
26
28
30
32
36
40
50 80 / 71 1,0
63,5 100 / 90 1,5
load bearing element
Ø
dimensions
as required
49 / 43 1,0
1,0
1,0
56 / 48
65 / 56
ANP - SYSTEMS
GmbHAnnex 13
ANP - Micropile SAS 550steel bar ARI-G-55 Ø 20-50 and steel bar S 555/700 Ø 63,5 with thread ribscomponents: heat shrink sleeve, corrugated sheating
A
sd
L
L1
L2
h
d
10 inside spacer material: PE-HD acc. to ÖNORM EN ISO 1872-1;2
PE - cord mat spacer
11 spring basket spacer material: PVC-U acc. to DIN 8061/8062
d × s min. A L d × s min. A L
[mm] [mm] [mm] [mm] [mm] [mm] [mm]
20 25 × 1,8 70
25
26
28
30
32
36
40
50 63 × 3,0 125 90 × 3,6 135
63,5 75 × 3,6 210 110 × 3,2 140
load bearing element
Ø
standard corrosion protection double corrosion protection
55 × 3,0
63 × 3,0
32 × 1,9
40 × 3,0
80175
270
270
125
100
75 × 3,650 × 3,0
h L1 L2quantityof ribs
[mm] [mm] [mm] [mm] n
40 6 112 124 3
50 8 132 124 3
63,5 11 218 166 5
load bearing element
Ø
dimensionsload bearing element
Ø
PE - cordmin. Ø
[mm] [mm]
63,5 9
620 - 50
ANP - SYSTEMS
GmbHAnnex 14
ANP - Micropile SAS 550steel bar ARI-G-55 Ø 20-50 and steel bar S 555/700 Ø 63,5 with thread ribscomponents: PE-cord, mat spacer, spring basket spacer
da di
L
alternative design
15 injection- and endcap
17 pile neck sheathing(plastic corrugated sheathing)
material: PVC-U acc. to DIN 8061/8062
material: PE acc. to DIN 8074/8075
min. da / min. di min. t L
[mm] [mm] [mm] [mm]
20
25
26
28
30
32
36
40
50 80 / 71 1
63,5 100 / 90 1,5
load bearing element
Ø
dimensions
49 / 43 1
60056 / 48 1
65 / 56 1
ANP - SYSTEMS
GmbHAnnex 15
ANP - Micropile SAS 550steel bar ARI-G-55 Ø 20-50 and steel bar S 555/700 Ø 63,5 with thread ribscomponents: injection- and endcap, pile neck sheating
ANP - SYSTEMS
GmbHAnnex 16
ANP - Micropile SAS 550steel bar ARI-G-55 Ø 20-50 and steel bar S 555/700 Ø 63,5 with thread ribscorrosion protection
Corrosion protection by hot dip galvanising
The galvanising is done in galvanising plants according to ÖNORM EN ISO
1461. The average thickness of the zinc coating layer has to be at least 150 m.
Particular attention shall be paid to the threadability of accessories.
Permanent corrosion protection - DCP
The steel bar is cut to length and is provided with spacers by means of a
PE - cord or mat spacers and a corrugated sheathing on its entire length,
excluding the thread part for the pile head. At the pile foot an injection cap is
arranged and at the pile head a vent flap is fixed. A tape is used to seal it against
the corrugated sheathing.
If parts with sleeve joints are used, either vent flaps are mounted at both ends of
each piece, or a full length of bar is grouted and cut to pieces after hardening of
the grout.
The annulus between steel bar and corrugated sheathing is grouted with cement
on an inclined platform. The grouted micropile must not be removed from the
injection platform and loaded before 24h have passed, provided that suitable
temperature conditions for injection and hardening are given.
To ensure the centric position of micropile in the borehole, spring basket spacers
are mounted on the building site and, if required, post-grouting systems.
ANP - SYSTEMS
GmbHAnnex 17
ANP - Micropile SAS 550steel bar ARI-G-55 Ø 20-50 and steel bar S 555/700 Ø 63,5 with thread ribstransport, storage and installation
Transport and storage
Significant for the effectiveness of the permanent corrosion protection is that the
corrugated sheating is not damaged by incorrect handling during transport,
storage and mounting.
The micropiles have to be stored off-floor. The support points must be positioned
at an appropriate distance to avoid deflection and must not be sharp-edged.
The stacking of micropiles is only permissible either parallel, side-by-side or on
top of each other. The weight of micropiles must not result in the damage of the
lower layers of stacked micropiles.
Installation
The production of the borehole depends on the soil conditions and takes place
uncased, cased or partly cased. The borehole has to be cleaned properly for the
installation of a micropile.
An appropriate borehole diameter has to be chosen so that the micropile and the
spring basket spacer can be inserted without damaging the corrugated
sheathing, e.g. by sharp edges of the casing pipe. If necessary the diameter of
the drilling hole has to be adjusted to the coupler’s diameter.
Whenever a pile is transported to the borehole or when a pile is inserted,
deflections should be avoided. If a crane is used to transport the pile, a traverse
with multiple suspension points should be used.
When the pile is installed in parts, a coupling has to be fitted during installation. If
the micropile is used with alternating loads couplers must be locked with nuts.
For compressive loads a contact coupler can be used. In this case a heat shrink
sleeve must be used to assure the coupler is secured against unscrewing.
With permanent micropiles the coupling´s corrosion protection is carried out by
means of a heat shrink sleeve. Thereby a sufficient overlapping to the permanent
protection´s corrugated sheathing is necessary.
The micropile is installed centrically into the cleaned borehole and is then grouted
with cement grout or the borehole has already been filled with cement grout and
grouted afterwards.
With permanent micropiles the corrugated sheathing of the permanent corrosion
protection must be embeded into the foundation body.