Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
‘Blue Book’ on Inductive Coordination Task Force Progress Report
Marvin J. Frazier Corr Comp
1415 S. Sunset Dr. Schaumburg, IL 60193
Voice & fax: 630-893-2322
Eilis M. Logan Union Pacific Railroad
1416 Dodge Street Omaha, NE 68179
402-271-2373 fax: 402-271-3298
Brian S. Cramer ComEd/Exelon
1319 S. First Ave. Maywood, IL 60153
708-410-5579 fax: 708-410-5225
ABSTRACT Electric power companies and railroads have found that the characteristics of these
systems, as well as their physical relationship, can introduce compatibility problems that
may require cooperative studies and corrective action. A task force of AREMA Committee
38 has been working on a revision to “Principles and Practices for Inductive Coordination
of Electric Supply and Railroad Communication/Signal Systems”, commonly referred to as
the ‘Blue Book’. The last prior revision was in September 1977. The current revision is
not yet completed.
The Blue Book is being revised to provide clearer objectives for induced voltages, to
include induced current objectives for human safety, and to incorporate induced voltage
objectives for equipment protection. The goal of the document is to provide a framework
for improved cooperation between the electric power and railroad industries to achieve
compatibility. The purpose of this paper is to review the status of the update and to review
some of the key issues being addressed by the task force.
INTRODUCTION
There is a need on the part of both railroad and power engineers for a set of induced
voltage and current objectives on railroad communication/signal circuits. The same
objectives should apply to induced voltages and currents whether the power system is on or
off the railroad right-of-way. They should apply to all railroad communications and signal
circuits, such as open wire or cable systems and to track circuits. These objectives should
serve as a guide to all concerned as to what is reasonable in securing acceptable inductive
coordination goals.
It is reasonable to expect a power system to cause some induced voltage and current. If
such interference is below the susceptibility of the communication/signal systems, then
those systems should continue to operate correctly. Two dominant considerations that
influence the tolerance of coupled voltage and current are:
(1) personnel safety, and
(2) signal equipment compatibility.
These considerations may not result in the same level of acceptable coupled voltage or
current. The maximum level of induction must ensure both personnel safety and operating
communication/signal-system compatibility.
Two broad operating conditions of the power system must be considered. These are the
steady state and the fault conditions. A railroad system must be able to function normally
for steady-state operation of the power system. The voltage and current induced onto the
railroad system can vary over a substantial range, depending on the power-system
conductor spacing, phase arrangement, the load, and other operating conditions.
The power system fault condition generally is of short duration, ranging from
approximately 30 to 250 milliseconds for transmission systems. The induced voltage
and currents for a single-phase to earth fault are typically much higher than for other fault
conditions or the steady state, because of significantly higher unbalanced currents in the
power system. For the faulted power condition, the principal concern is for the
survivability of both personnel and railroad communications/signal equipment. These
factors are summarized in Table 1. The updated ‘Blue Book’ will address both steady
state and fault conditions, but this summary paper will be limited to steady state issues.
PERSONNEL SAFETY
Current-Based Considerations
Quantitative data concerning personnel safety thresholds are generally based on
measurement of the current that results in a particular physiological response. Some of
the important physiological response data are based on animal studies and must be
extrapolated to the human form. The physiological response to a given current
stimulation may be dependent on the size and weight of the subject as well as the current-
conduction duration and path through the body. Relating the available current-based
information to a voltage-based objective is complicated by the need to consider the
impedance of both the electrified object and of the current flow path through the body.
Several different physiological responses to the flow of current through the body are
identified in literature. These responses can be useful for identifying ranges of body
current that are acceptable for different conditions. The responses are generally
dependent on the duration of the current. Different levels of current are acceptable for
steady state and faulted conditions of the power system.
Physiological response to body current is often segregated into the following:
• Threshold of perception, 0.5 (1),(2)
• Startle Reaction, 2.2 to 3.2 mA (3)
• Inability to let go, at 99.5%, 6 mA women, 9 mA men (4)
• Ventricular Fibrillation, >one second, 40-50 mA (1)
A reasonable personnel-safety objective for power-system coupling to railroad-system
conductors, based on the above physiological responses, is to:
• Minimize the chance for body current higher than the let-go threshold for steady
state conditions.
• Minimize the chance for lethal body current for fault-conditions (ventricular
fibrillation).
Selection of more than one objective may be warranted if different levels of personnel
awareness and precaution are incorporated. For example, informed maintenance
personnel, using special procedures may tolerate higher levels of available current than
maintenance personnel who expect a 'non-energized' circuit with no special precautions,
or if the general public has ready access to the conductor.
Voltage-Based Objective Considerations
The current-based thresholds reviewed above reflect the present state of knowledge and
are the most effective indicators, since the physiological response appears to be current or
current density dependent. Transforming to corresponding voltage-based thresholds adds
an additional level of complexity, uncertainty, and variability that can be contributed by:
• Body Impedance
• Conductor Circuit Impedance
• Coupling Mechanism
These factors suggest that care is necessary in interpreting a voltage-based guideline or
objective. The following provides a brief review of the above factors.
Body Impedance
Body impedance can depend on several factors including:
• path through the body
• conductor/skin contact area
• pressure of the conductor/skin contact
• wetness of the skin
• voltage applied
The impedance to current flow through the human body can vary over a wide range, with
a dominant factor being associated with the interface between the conductor and the skin.
The contact area and skin moisture conditions for common field maintenance situations
in which railroad-system conductors can be energized by power line system coupling can
not be readily determined. However, the IEC (1) results of Figure 1 should provide a
conservative range of total body impedance for use in identifying railroad safety
objectives for lower voltage, large contact-area exposures. It is seen that the body
impedance increases for contact to lower voltage sources. Induced rail voltage will
transfer to a locomotive or rail car on the energized segment of track, resulting in a
voltage between grab bars and the earth near the track. Safe contact voltage, for either
the rails or the rolling stock, may be relatively low due to the larger contact area.
Various sources (UL)(5), IEC (6) have identified body impedance for evaluating leakage
current or touch current over a broad range of frequencies. At 60 Hz the resistance is in
the range of 1500 to 2000 ohms to simulate the resistance for a person grasping a handle
or other grippable conductor.
Conductor Circuit Impedance
The impedance of the energized conductor circuit can have a significant effect on the
current that will flow through a person who contacts the conductor. The equivalent
source impedance of railroad-signal conductors energized by 60-Hz power coupling can
range from less than one ohm for rails to thousands of ohms for signal pole-line
conductors. Thus, measuring or calculating the voltage of the conductor for normal
conditions does not provide a good indication of the shock current that can flow through
a person who touches the conductor. The current that flows through a person contacting
an energized conductor depends not only on the voltage but also on the resistance of the
person and the impedance of the conductor circuit.
Coupling Mechanism
The conductor voltage and the current that can be drawn from the conductor will be
influenced by the coupling mechanism (inductive coupling, capacitive coupling or earth
conduction) between the power system and a signal-system conductor. Capacitive
coupling is typically only important for high-impedance circuits like pole-line signal
circuits, while inductive coupling is generally more important for low-impedance circuits
such as rails.
Existing Guidelines
Steady-State
This Blue Book in its earlier editions (last revised 1977) has given 60 V ac rms as the
acceptable level for steady state interference under normal conditions. The 60 V ac rms
value appears to have been based on telecommunication inductive coordination standards
such as promulgated by the CCITT (7). The current ITU-CCITT standard (8) also
recommends a 60 volt guideline for telecommunications. However, other current
Standards, such as IEEE Std. 776 (9) and the Canadian Standards Association (CSA) (10)
recommend an induced longitudinal voltage of 50 volts rms for personal contact with
telecommunications conductors. The anticipated energized conductor for the telephone
industry is a small-diameter conductor, namely conductors in a cable or open-wire line.
OSHA (11) also recommends a 50 volt limit for live parts of electrical equipment that are
not screened or only accessible to qualified persons.
The CSA (10) also recommends 50 volts for longitudinally induced voltages in railway
signaling and communications circuits, under normal power line conditions. For track
circuits, they include the special note: “For adjacent track sections of equal length
separated by a pair of insulated joints, the ac voltage developed across each insulated rail
joint is twice the maximum voltage of each rail with respect to remote earth. To limit the
voltage across insulated rail joints to 50 V, the maximum rail-to-remote earth voltage
should not exceed 25V.”
However, some personnel safety guidelines limit the steady state touch voltage to less
than 50 volts. A recent pipeline industry standard by NACE (12) has set this level at 15
Volts. The Foreword states,
“Some controversy has arisen in the latest issue of this standard regarding the shock
hazard stated in Section 5, Paragraph 5.2.1.1 and elsewhere in this standard. The reason
for a more conservative value in this revision of the standard is that early work by George
Bodier at Columbia University and by other investigators has shown that the average
hand-to-hand or hand-to-foot resistance for an adult male human body can range between
600 ohms and 10,000 ohms.(1) A reasonable safe value for the purpose of estimating
body currents is 1,500 ohms hand-to-hand or hand-to-foot. In other work by K.S. Gelges
and C.F. Dalziel on muscular contraction, the inability to release contact would occur in
the range of 6 to 20 milliamperes for adult males.(2) Ten milliamperes hand-to-hand or
hand-to-foot is generally established as the absolute maximum safe let-go current.
Conservative design would use an even lower value. Fifteen volts AC impressed across a
1,500-ohm load would yield a current flow of 10 milliamperes, thus the criterion within
this standard is set at 15 volts. Prudent design would suggest an even lower value under
certain circumstances.
(1) George Bodier, Bulletin de la Societe Francaise Des Electriciens,
October 1947.
(2) C.F. Dalziel, “The Effects of Electrical Shock on Man,”
Transactions on Medical Electronics, PGME-5, Institute of Radio
Engineers, 1956.”
Similarly, the CSA (13) also identifies a 15 volt value for pipeline induced voltage
personnel safety. As explanation, they note:
“The value of 15 V has been selected as a practical mitigation level that falls within
generally accepted guidelines for exposure of the general public to continuous 60 Hz rms
voltage. Some industries may accept different voltage levels where trained personnel or
other technical factors are involved.”
The ‘Blue Book’ Task Force has no information concerning any fatalities below 50 V ac
rms.
SIGNAL EQUIPMENT COMPATIBILITY CONSIDERATIONS
Overview
The question of railroad communication and signal equipment interference and damage is
at least as complex as the human safety issue. The variety of railroad system types,
manufacturers, and susceptibilities makes it difficult to produce a guideline for acceptable
induction. It is just this confusion that makes it important to set target levels so that
railroad and utility engineers, and manufacturers of equipment have common design
targets. The acceptable induced-voltage for any given application will be driven by the
existing or available signal equipment, and requires agreement of all parties. In all cases
the lower value for acceptable interference, equipment susceptibility, or human safety, will
be the required level. A goal for future compatibility is to have the equipment
susceptibility and personnel safety induced voltage criteria be the same. That is, if the
voltage induced onto the railroad conductors meets personnel safety guidelines, the signal
equipment connected to those same conductors should also be compatible with the induced
voltage.
The personnel safety issues are generally associated with voltage that appears from
conductor to earth (longitudinal mode voltage). However, equipment interference is
generally the result of coupled voltage that appears between the conductors,for example
rail-to-rail for a track circuit (also called metallic or differential-mode voltage).
The rail-to-rail induced 60 Hz voltage tolerance for several types of track signal systems
are specifically identified in AREMA Manual Parts (14). Table 2 summarizes the target
interference-tolerance voltages for several types of track signal equipment. It is seen that
these voltages are considerably less than the personnel safety voltages that were
discussed in the previous sections. Because the two conductors of a track signal circuit
are generally exposed to nominally the same exciting field of the power system, the two
conductors typically have nominally the same longitudinal induced voltage. Therefore
for normal conditions, the inherent balance of the rail system normally results in rail-to-
rail voltages that are less than the values of Table 2.
Interference susceptibility testing of track signal systems for realistic conditions is not
straightforward. Susceptibility has been noted to depend on the operating conditions and
the signal devices must operate as a system to produce reliable susceptibility results. To
satisfy those needs, the AAR and EPRI jointly commissioned the development of a Track
Simulator for Interference Testing (15). The Track Simulator, was designed for testing
signal units as a system by approximating key track-circuit electrical parameters such as:
• input impedance of the track at the signal system location,
• signal attenuation and distortion,
• rail impedance skin effect,
• ballast-resistance variation over a realistic range,
• track-storage effects.
The simulator consists of two variable-length signal blocks, with interference testing
using a low-distortion 60-Hz sinusoid or a 60-Hz harmonically rich waveform. Testing
for important static conditions, with or without superimposed interference such as:
• unoccupied circuit,
• occupied circuit,
• broken rail,
• shorted insulator,
• one grounded track lead.
The AAR/EPRI research also developed testing procedures and performed demonstration
tests on Low Frequency Electronic Track Circuits for comparison to field test results.
Recently, the Blue-Book Task Force prepared Track Simulator initial testing procedures
for highway grade crossing equipment for 60-Hz and harmonic interference (16).
Track Unbalancing Mechanisms
An important element of inductive coordination is to identify if existing railroad signal
equipment is compatible with the rail-to-rail voltage resulting from normal rail-system
unbalance, when personnel-safety guidelines are met. The conductor-to-conductor
voltage, for example between two rails, is typically in the range of a few percent of the
induced rail-to-ground voltage for nominally balanced track conditions, but can be
considerably higher for some unbalancing conditions. Important unbalancing conditions
should be evaluated in a compatibility investigation and for mitigation design.
Unbalancing conditions may include a shorted insulated joint, an earthed lead-in
conductor (with or without a train within the affected track region), or a locomotive
within the stagger region at an insulated-joint location.
Many in the railroad industry consider a single degraded insulating joint to be a normal
operating condition. That is because when no significant induced voltage is present,
many signal systems will function properly with a single degraded joint. Of course, the
signal systems also function properly when a single joint is shorted by a train-shunt
within the stagger region.
However, in the presence of significant induced rail-ground voltage, shorted or degraded-
resistance joint can result in non-negligible rail-to-rail voltage that may influence or
interfere with the normal operation of the signal system.
Figure 4 illustrates the measured insulated-joint resistances for an approximately 13-mile
segment of track, using a commercial IJ resistance test instrument. The average IJ
resistance is 40.4 ohms. While the resistance varies over approximately a 3:1 range, it is
seen that the unbalance of joint-pairs is relatively small. Thus for this measurement set,
the small existing unbalance may not result in interfering conditions, depending on the
induced rail-ground voltage and the types of signal equipment.
Figure 5 quantifies how the degradation of joint resistance affects the voltage that appears
rail-to-rail for a calculated example with all 100-ohm joints except for the one degraded
joint. The figure shows the calculated percentage of induced rail-to-ground voltage, with
all good joints, that is converted to rail-rail voltage by the degraded resistance of a single
joint. The figure shows that a degraded joint resistance of approximately 15 ohms results
in 20% of the normal rail-to-ground voltage appearing rail-to-rail. If the induced rail-to-
ground voltage satisfies a 25 volt personnel safety condition, conversion of 20% or more
to rail-to-rail voltage is 5-volts or more. For this condition, some equipment that meets
the 5-volt susceptibility guidelines of Table 2 may experience interference.
The rail-to-rail voltage caused by a degraded insulated joint can be made worse by the
presence of a train in the block, as is illustrated in Figure 6 and Figure 7. Figure 6
illustrates a segment of track with insulating joint locations A, B, and C. One shorted
insulator exists at location B, which is also the site of highway grade-crossing equipment
connected on both sides of the insulating joint. The voltage induced rail-to-rail on the
west and east sides of the (B) joints are designated as VBw and VBe. Successive sketches
in Figure 6 show the location of a train proceeding from west to east at Times 1 through
5.
Figure 7 shows sketches of power-line induced 60-Hz voltage envelopes VBw and VBe
that were recorded on a strip chart as a train moved through the two-block region of
Figure 6. A low-pass filter was used to reject the grade-crossing detector signals from the
strip chart input. Times 1 through 5 are also shown in Figure 7, along with a description
of the event at each time that relates to a change in the recorded envelope. The
waveforms illustrate that a train that bridges the pair of insulating joints adjacent to a
shorted IJ location can increase the rail-to-rail interference voltage relative to when the
train is not present. Therefore, to assess the effect of a shorted insulating joint on track
signal systems the influence of the occupied condition should be considered.
The above examples illustrate that a common corridor that is designed to satisfy a
personnel safety criterion of 25 volts rail-to-ground, may not be compatible with
commonly used signal equipment for track unbalance conditions that may occur.
Compatibility assurance necessitates knowledge of the range of unbalance conditions that
will occur, and the susceptibility thresholds of the equipment for those conditions.
Without that knowledge, the compatibility of the signal system and the power system can
not be assured, except on a trial and error basis.
The capabilities and characteristics of railroad signaling equipment, including induced-
voltage tolerance are rapidly evolving. The equipment manufacturer is in a unique position
to assess the compatibility of equipment that is applicable for a specific signaling function
with an expected induced voltage environment. Therefore, the resources and knowledge of
the manufacturer should be used to the full extent possible in helping to ensure the
compatibility of available equipment for an anticipated induced-voltage environment.
Railroad signal equipment can be susceptible to interference from rail-to-rail ac induction.
Grade crossing train detection equipment is susceptible to a greater degree than most other
railroad systems. It is imperative for future successful rail operations that utilities,
equipment suppliers and railroads address this issue in development of equipment, design
of power systems, and design of railroad signal systems. Cooperative efforts needed are:
• Utilities must make reduction of rail induced voltage a top priority in design of power
systems and mitigation.
• Equipment suppliers must make reduction of operational susceptibility a top priority in
design of new equipment and application of systems.
• Railroads must do their best to maintain balanced rail impedances, and where possible
to adapt signal systems to maintain reliable operation.
EXCITATION OF TRACK SYSTEM BY POWER SYSTEM
Thus far, we have discussed the effects of induced voltage onto the railroad system in
terms of personnel safety and interference to signal equipment without regard to the
details of the power system. The most prevalent cause of rail-system induced voltage is
the current that flows in the power-system conductors. The current in the power-system
conductors couples voltage onto the railroad system by magnetic-field induction, similar
to a simple single-turn transformer. Two important power-system parameters that
influence the induced rail-system voltage are:
• the spacing between the power conductors.
• the unbalance of the current in the three power phase conductors,
The unbalance of the power line currents is influenced by the spacing of the power
conductors to each other and to the earth and the loading of the line. Recent
measurement on many power lines characterized the unbalance of several voltage classes,
for many lines of each voltage, using phase current values recorded by the SCADA
systems (17). Figure 8 shows a plot of the average unbalance data as a deviation, δ, from
the mean circuit current magnitude, expressed as a percentage. The line shown in the
figure provides the trend of the data and permits extrapolation to line voltages not
measured.
Although the results of Figure 8 may not be representative of all power systems, it is
representative of one major system, and similar data is not known to be available for
other systems. Therefore, those data have been used to assess the voltage induced on a
representative 1.5-mile long track block as a function of phase-conductor spacing.
Figure 9 shows the average phase current for a vertical power line that will result in 25
volts rail-ground for a 1.5 mile block circuit versus the phase-to-phase separation. For
each voltage class analyzed, the unbalance of Figure 8 was assumed and was converted to
an equivalent residual current, by multiplying by √3. As a worst-case, the induced
voltage caused by the balanced current and residual current were assumed to add directly
in phase. Other representative conditions shown in the figure were assumed for the
calculations. The effect of separation between the power circuit and the track is also
shown as separate curves in the figure. The figure also shows the spacing for common
voltage-class power lines.
For block-lengths in the 1.5-mile length range, Figure 9 can be used to estimate the line
currents which may cause 25 volts or more rail-ground and thus require more detailed
investigation to assure personnel safety. As noted above, evaluation of signal equipment
compatibility may require lower values of power line current, more detailed evaluation of
track unbalance conditions, and the development of mitigation measures.
CONCLUSIONS
Table 3 summarizes the values most likely to be recommended to the full AREMA
Committee 38 by the Blue-Book Task Force. However, since full Committee review has
not been made, the levels are subject to change.
A common corridor that is designed to satisfy a rail-to-ground personnel-safety criterion
may not be compatible with commonly used signal equipment for track unbalance
conditions that may occur. It is imperative for future successful rail operations that
utilities, equipment suppliers, and railroads address this issue in development of
equipment, design of power systems, and design of railroad signal systems.
REFERENCES
1. IEC 479-1, Effects of current on human beings and livestock - Part 1: General Aspects, 1994,
International Electrotechnical Commission, Geneva, Switzerland.
2. Cabanes J., Physiological Effects of Electric Currents on Living Organisms,in Electrical Shock
Safety Criteria, Proceedings of the First International Symposium on Electrical Shock Safety
Criteria, Edited by Bridges,J.E., et al, Pergamon Press, 1985, ISBN 0-08-25399-7.
3. Electrical Stimulation and Electropathology, Reilly, J.P. Editor, Cambridge University Press,
1992, ISBN 0-521-41791-0,in Ch. 7.
4. Dalziel, C.F., Reevaluation of Lethal Electric Currents. IEEE Transactions Inductrial
Applications IGA-4(5), 1968, 467-476.
5. In Reference (3), in Ch. 11 by Skuggevig, W. of UL
6. IEC 990 Methods of measurement of touch-current and protective conductor current, 1990
7. Directives Concerning the Protection of Telecommunication Lines Against Harmful Effects
from Electricity Lines, International Telegraph and Telephone Consultative Committee
(CCITT), published by the International Telecommunication Union, 1963, Chapter IV
8. ITU, Directives concerning the protection of telecommunication lines against harmful effects
from electric power and electrified railway lines, Volume VI, Danger and Disturbance, Geneva
1989, ISBN 92-61-04041-3.
9. IEEE Std 776-1992, IEEE Recommended Practice for Inductive Coordination of Electric
Supply and Communications Lines, IEEE, Inc., 345 East 47th Street, New York, NY 10017-
2394.
10. Electrical Coordination, Canadian Electrical Code, Part III, Canadian Standards Association
(CSA), C22.3 No. 3-98, August 1998.
11. OSHA Title 29, Volume 5, CFR Ch. XVII (7-1-98 Edition) Sec. 1910.303, Page 826-831, U.S.
Government Printing Office.
12. NACE (National Association of Corrosion Engineers) Standard RP0177-95, Mitigation of
Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control
Systems
13. Principles and Practices of Electrical Coordination Between Pipelines and Electric Supply
Lines, CAN/CSA-C.22.3, No. 6-M91, Canadian Standards Association, 178 Rexdale Blvd,
Etobicoke, Ontario, Canada M9W 1R3
14. AREMA Communication & Signal Manual Parts, 2000.
15. Mutual Design: Overhead Transmission Lines and Railroad Facilities - Susceptibility Program
Phase II, Vol's 1, 2, and 3, Final Report, M. Frazier Principal Investigator, RP 1902-7, Electric
Power Research Institute, June 1994.
16. Cramer, B.S. for Working Group F2, “Selecting Highway-Rail Grade Crossing Train Detection
Electronics in an AC Power Interference Environment”. Proceedings of the 1998 AREMA
C&S Annual Technical Conference, September 14-16, St. Louis, MO
17. Cramer, B.S., “Phase Imbalance on ComEd’s Transmission and Distribution Systems”,
Proceedings Of The American Power Conference, April 1995
Table 1. Summary of Compatibility Considerations.
Principal Considerations Power Condition Personnel Safety Equipment Compatibility
Steady State Let Go* Non-Degraded Operation Faulted Survivability Survivability *Startle reaction may be more appropriate in certain circumstances.
Table 2. AREMA Guidelines for Interference Tolerance of Selected Signal Equipment.
C&S Manual Part Equipment Type Interference Tolerance 3.1.20 Motion Sensitive Systems to Control
Highway Grade Crossings 5 V rms 60 Hz
3.1.26 Constant Warning Time Systems to Control Highway Grade Crossings
5 V rms 60 Hz
8.2.1 Audio Frequency Track Circuits 10 V rms, 60-180 Hz
Table 3. Voltage and Current Limits Being Considered for Personnel Safety.
Condition Current (milliamperes) Voltage (volts)
Rails & Attachments 10[2] 25[2] Steady State
Other Signal Conductors 10[1] 50[3]
Fault All Conductors IEEE Std-80 methods
[1] For well-isolated signal conductors that are subjected to electrostatic induction the conductor to earth current through a low impedance, (2000 ohms) is the most appropriate indicator. For those conditions do not rely on measure of the conductor voltage. [2] Generally caused by magnetic -field induction. The voltage is to ground, and is consistent with a 2500-ohm body resistance between the conductor and ground. Those conditions are consistent with the10 milliamperes body current (through the resistor) shown in the current column. This will result in a maximum of 50 volts across an IJ. [3] Generally caused by magnetic -field induction. The voltage is the accessible voltage, which can be to ground or to another conductor. The voltage is consistent with higher contact resistance to smaller conductors.
Figure 1. Values of total body impedance hand-hand or hand-foot for ac 50/60 Hz.
100
1,000
10,000
10 100 1,000
Touch Voltage (Volts rms)
To
tal B
od
y Im
ped
ance
(o
hm
s)
95%
50%
5%
Large area contact:8000mm2 (12.4 in2),Dry skin.
Percentage population with resistance not exceeding value of curve.
(Trend lines through data values presented in IEC 479-1)
Figure 2. IEEE Std-80 Fault Touch-Potential Model.
V
Ib1000 ohm
6” Soil ρ (ohm·m)
( )ρ+=
5.11000V
Ib
Figure 3. IEEE Std 80-1986 Guideline for 99.5% Safe Touch Potential.
100
1,000
10,000
0.01 0.1 1
Shock Duration (seconds)
Saf
e T
ou
ch P
ote
nti
al (
volt
s)
Soil Resistivity (ohm-m)
1000
500
100
70 kg (155 lb) person
Figure 4. In-Situ Measured Resistance of Rail Insulated Joints.
450 455 460 465 470
Milepost
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150IJ
Res
ista
nce
(oh
ms)
N Rail IJ RS Rail IJ R
Figure 5. Conversion of Rail-Ground Voltage to Rail-Rail Voltage vs. Resistance of Single Degraded IJ.
1
10
100
1 10 100
Degraded IJ Resistance (ohms)
Per
cent
Vol
tage
Con
vers
ion
At Adjacent IJ Location
At Degraded IJ Location
Analysis Assumptions: 1.5 mile Blocks; Soil resistivity = 100ohm-m,Ballast = 100 ohms; Good IJ R's = 100 ohms;Rail-connected signal-equipment impedance=j10 ohms
Vw Ve
BA C
Shorted IJ
Train
Time 5
Time 4
Time 3
Time 2
Time 1
Train
Train
Train
Train
Direction of Motion
InsulatedJoint
.
.
Figure 6. Geometry of Moving Train and Degraded Rail Insulator.
Vw
Ve
Time1 2 3 4 5
Fro
nt C
ross
es IJ
A
Fro
nt C
ross
es IJ
B
End
Cro
sses
IJ B
Fro
nt C
ross
es IJ
C
End
Cro
sses
IJ C
.
. Figure 7. Induced 60 Hz Rail-to-Rail Voltage Measured at Degraded IJ Site.
Figure 8. Measured Phase Current Deviation from the Circuit Mean.
1
10
100
1 10 100 1000
Line-to-Line Voltage (kV)
Ave
rag
e D
evia
tio
n, %
of
Mea
n C
ircu
it C
urr
ent
Mag
nit
ud
e
Average Measured PhaseCurrent Deviation from theMean for Each Voltage Class,Cramer (17)
Trendline: Average Deviation, d (%) = 23.04V-0.3653
d = {|Ia-avg| + |Ib-avg| + |Ic-avg|}/3V in kilovolts, line-to-line.
Figure 9. Maximum Average Line Current for 25V Induced Rail Voltage, Vertical Circuit with Unbalance.
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
0 5 10 15 20 25 30 35
Phase Separation (ft)
Ave
rag
e P
has
e C
urr
ent
Mag
nit
ud
e (k
A)
800 ft
500 ft
300 ft
200 ft
150 ft
100 ft
50 ft
Po
wer
-to
-Tra
ck D
ista
nce
(ft
)
500 kV230 kV 345 kV138 kV115 kV34 kV
1.5-mile Track BlocksEarth Resistivity = 1000 ohm-mBallast Resistivity = 100 ohm-kftAlumoweld OHSW,Unbalance of Figure 8.
TABLE CAPTIONS Table 1. Summary of Compatibility Considerations. Table 2. AREMA Guidelines for Interference Tolerance of Selected Signal Equipment. Table 3. Voltage and Current Limits Being Considered for Personnel Safety. FIGURE CAPTIONS Figure 1. Values of total body impedance hand-hand or hand-foot for ac 50/60 Hz. Figure 2. IEEE Std-80 Fault Touch-Potential Model. Figure 3. IEEE Std 80-1986 Guideline for 99.5% Safe Touch Potential. Figure 4. In-Situ Measured Resistance of Rail Insulated Joints. Figure 5. Conversion of Rail-Ground Voltage to Rail-Rail Voltage vs. Resistance of Single Degraded IJ.
Figure 6. Geometry of Moving Train and Degraded Rail Insulator.
Figure 7. Induced 60 Hz Rail-to-Rail Voltage Measured at Degraded IJ Site.
Figure 8. Measured Phase Current Deviation from the Circuit Mean. Figure 9. Maximum Average Line Current for 25V Induced Rail Voltage, Vertical Circuit with Unbalance.