IJT BLOW DOWN QUANTITY CALCULATIONEWS - 024/0
Sheet 01 of 01
1. Boiler Steaming capacity at MCR TPH E
2. Solids content in feed water
(Refer feed water quality from contract) ppm S3. Maximum permitted concentration of solids in
boiler water ppm C
4. Continuous blow down rate as percentage of
evaporation rate
B1 = S X 100 = X 100
C - S - .
% B1
5. Continuous blow down quantity
W2 = E x B1 X1000 = X X 1000.
100 100 Kg/hr W2
6. Water content of boiler m3 V
7. Duration of intermittent blowdown (1/2 hour) hrs d
8. Interval between completion of one blow downoperation and completion of the next (8 hrs.) hrs. t
9. Intermittent blow down rate as percentage of
evaporation rate
B2 = 100 x t x S x V .
d x (C x V - 0.5 x S x E x (t-d) - V x S)
= 100 x x x .
x ( x - 0.5x x x( - )- x )
% B2
10. Quantity of boiler water discharged during each
intermittent blow down
Q = E x t x S x V .
C x V - 0.5 x S x Ex (t-d) - V x S
= x x x .
x - 0.5 x x x ( - )- x m3 Q
11. Concentration of solids in boiler water on
completion of intermittent blowdown
C1= C - (t-d) x S x E
V
= - ( - )x x .
ppm C1
12. Average intermittent blow down rate as
percentage of evaporation rate
B A = Q x 100 = x 100
t x E x
% B A
Project : Contract No. : Rev. No. :
Prepared by : Approved by : Date :