SCHAKO | Ferdinand Schad KG Telephone +49 (0) 7463-980-0 Steigstraße 25-27 Fax +49 (0) 7463-980-200 D-78600 Kolbingen www.SCHAKO.de | [email protected] BKA-Ü Fire-resistant damper of special design and use Contents Description .............................................................. 2 Models and dimensions .......................................... 3 Installation details................................................... 6 Installation in solid walls ......................................... 6 Installation in solid ceilings ..................................... 8 Installation in lightweight partition walls with metal posts and panelling on both sides .......................... 9 Installation with mounting frame ER in lightweight partition walls with metal posts and panelling on both sides ...................................................................... 12 Installation in lightweight partition walls with metal posts and single-layer panelling on both sides ..... 16 Installation in fire walls with construction of lightweight partition walls with metal posts and panelling on both sides ......................................... 17 Installation in shaft walls ...................................... 20 Installation information ........................................ 21 Technical data ....................................................... 22 Spring return actuators ......................................... 24 Smoke detection system RMS .............................. 25 Specification texts ................................................. 26 Service................................................................... 27 Foreign branch offices .......................................... 32 Indexes: Figures/Tables ........................................ 34 Technical Documentation "Installation, Mounting and Operating Instructions" General building supervisory approval Z-6.50-2012

BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

  • Upload
    vanngoc

  • View
    218

  • Download
    1

Embed Size (px)

Citation preview

Page 1: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

SCHAKO | Ferdinand Schad KG Telephone +49 (0) 7463-980-0 Steigstraße 25-27 Fax +49 (0) 7463-980-200 D-78600 Kolbingen www.SCHAKO.de | [email protected]

BKA-Ü Fire-resistant damper

of special design and use

Contents Description .............................................................. 2

Models and dimensions .......................................... 3

Installation details................................................... 6

Installation in solid walls ......................................... 6

Installation in solid ceilings ..................................... 8

Installation in lightweight partition walls with metal posts and panelling on both sides .......................... 9

Installation with mounting frame ER in lightweight partition walls with metal posts and panelling on both sides ...................................................................... 12

Installation in lightweight partition walls with metal posts and single-layer panelling on both sides ..... 16

Installation in fire walls with construction of lightweight partition walls with metal posts and panelling on both sides ......................................... 17

Installation in shaft walls ...................................... 20

Installation information ........................................ 21

Technical data ....................................................... 22

Spring return actuators ......................................... 24

Smoke detection system RMS .............................. 25

Specification texts ................................................. 26

Service ................................................................... 27

Foreign branch offices .......................................... 32

Indexes: Figures/Tables ........................................ 34

Technical Documentation "Installation, Mounting and Operating Instructions"

General building supervisory approval Z-6.50-2012

Page 2: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation Description

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 2

DESCRIPTION

Fire-resistant dampers of special design and use are used if, as part of ventilation planning, openings are required in fire-resistant inner walls or ceilings for the air intake, they must be closed in the event of a fire. The competent building supervisory authority will decide whether the opening is admissible, for example because it differs or in connection with the approval of the fire protec-tion concept. The required dampers are fire-resistant dampers which are closed in case of fire driven by a suitable smoke detecting triggering device in the event of a fire, thus, preventing the propagation of fire and smoke through the component opening. Dampers of this type may not be connected to ventilation ducts in connection with RLT sys-tems in buildings. Dampers according to the general building supervisory ap-proval Z-6.50-2012 are neither fire protection dampers nor fire dampers against propagation of fire in ventilation ducts.

The "General and special regulations" of the general building supervisory approval Z-6.50-2012 in its current form, the in-stallation, mounting and operating instructions and the common standards and guidelines must be observed in connection with this technical documentation.

The standard fire-resistant damper BKA-Ü consists of the following components: SCHAKO shut-off damper BKA-EN, according to the re-

quirements of the Declaration of performance no. 09-19-DoP-BKA-EN-2013-07-01, housing made of galvanised sheet steel with electric spring return actuator 24 V.

SCHAKO assembly part type EBT, galvanised sheet steel model. Housing leakage according to DIN EN 1751, class B, at a duct pressure of up to 1000 Pa.

SCHAKO finishing protective grating type ASG on both si-des, galvanised sheet steel model.

SCHAKO extension part type VT, galvanised sheet steel model, required for H ≥ 400.

Identification label (must be attached permanently to the adjacent component by the installing company)

SCHAKO smoke detection system RMS, according to the general building supervisory approval no. Z-78.6-58; con-sisting of: - SCHAKO smoke detector RMSII-L- SCHAKO relay module RM (V4.00)

EBT (with RMS), ASG and, if necessary, VT are mounted on the BKA-EN. RMSII-L and the spring return actuator are wired with the relay module RM (V4.00).

Installation is performed in interior walls (horizontal position of the damper blade axle) and ceilings. In doing so, the gene-ral building supervisory approval no. Z-6.50-2012, the Decla-ration of performance no. 09-19-DoP-BKA-EN-2013-07-01, general building supervisory approval no. Z-78.6-58 and the associated technical documentation must be observed. For the installation in solid ceilings, the dimensions of BKA-Ü are limited to W and H = 500 mm. For wall installation, the smoke detector must always be in-stalled above in the assembly part type EBT with the damper blade axle in the horizontal position.

For maintenance, servicing etc., it may be necessary to pro-vide on-site inspection openings in suspended ceilings, shaft walls etc. A sufficient number and size of these openings must be provided.

MAINTENANCE INFORMATION

We point out that only suitable cleaning materials may be used to clean the fire dampers made of stainless steel!

Page 3: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Models and dimensions

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 3

MODELS AND DIMENSIONS

Dimensions

Figure 1: Dimensions BKA-Ü

1 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT 3 Extension piece type VT 4 Finishing protective grating type ASG 5 Electric spring return actuator 24 V 6 Smoke detector RMSII-L 7 Relay module RM (V4.00) 8 Protective cover

Legend

B [mm] = Width H [mm] = Height L [mm] = Length ρ [kg/m³] = Density min. = at least max. = maximum bzw. = or approx. = approximately EVU = Utility

company

Page 4: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Models and dimensions

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 4

Available sizes [mm]

Width (B) Height (H)

200 200

225 225

250 250

275 275

300 300

325 325

350 350

375 375

400 400

450 450

500 500

550 550

600 600

650 650

700 700

750 750

800 800

900

1000

1100

1200

1300

1400

1500

Table 1: Available sizes

All heights and widths which can be combined are availab-le!

Drive unit always on the H side of the fire damper. Inspection openings always on the B side of the fire dam-

per. On request, the width and height dimensions are available

in steps of 10 mm. For wall installation, the smoke detector must always be

installed above in the assembly part type EBT with the damper blade axle in the horizontal position.

H [mm]

L1 [mm]

L [mm]

L2 [mm]

Total length [mm]

200

180 500

- 680

225

250

275

300

325

350

375

400

180 860

450

500

550

600

650

700

750

800 210 210 920

Table 2: Length specifications

Available at an extra charge

Stainless steel model with material no. 1.4301 (V2A) or 1.4571 (V4A - All replaceable, non-coated parts are made of stainless steel material no. 1.4301 (V2A)).

Model with additional DD coating (solvent-containing two-component top coat based on polyurethane var-nish - RAL 7035 / light-grey) inside / outside available on request;

Page 5: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Models and dimensions

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 5

Use

The fire-resistant damper BKA-Ü can be installed according to the following table.

Use Instalstal-

lation Model/Material

Mini-mum thick-ness [mm]

Minimum dis-tance between

two BKA-Üs to each other

[mm]

WALL 1)

solid; apparent density

≥450 kg/m³

in for example, concrete; masonry according to EN 1996 or DIN 1053; solid plaster wall boards according to EN 12859 or DIN 18163

100 70

Lightweight partition wall

in

in lightweight partition walls with metal posts and pa-nelling on both sides according to classification to EN 13501-2 or comparable national standards; without addi-tional mounting frame ER

100 200

in lightweight partition walls with metal posts and pa-nelling on both sides according to classification to EN 13501-2 or comparable national standards; with additio-nal mounting frame

3)

100 250 5)

in lightweight partition walls with metal posts and pa-nelling on one side according to classification to EN 13501-2 or comparable national standards

4)

125 200

In fire walls with the following general building supervisory test certificates (abP): abP no. P-3391/170/08-MPA BS (Knauf) abP no. P-3020/0109-MPA BS (Rigips) abP no. P-3796/7968-MPA BS (Promat)

116 200

in lightweight partition walls with metal posts and pa-nelling on both sides according to classification to EN 13501-2 or comparable national standards.

75 200

CEILING 2)

solid; apparent density

≥500 kg/m³

in for example, concrete, aerated concrete 125 70

Even considering the installation of the dampers in walls and ceilings mentioned above, they still meet the requirements of the corresponding fire resistance class (resistance duration 90 minutes). 1)

For wall installation, the smoke detector must always be installed above in the assembly part type EBT with the damper blade axle in the horizontal position. 2)

When installing in solid ceilings, the dimensions of the fire-resistant damper BKA-Ü are limited to W and H = 500 mm. 3)

The mounting frame ER can be used exclusively with BKA-EN L=500. 4)

Maximum wall height ≤ 5000 mm 5)

Due to construction Table 3: Usability

Page 6: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Installation details

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 6

General information

Risk of injuries during mounting or installation. To avoid any possible injuries, personal protective equipment (PPE) must be worn.

Fire-resistant dampers must be installed such that exter-nal forces do not impair their continuous functioning. During mounting, it may be necessary to provide rein-forcements for the housing or the like. The requirement of statically load-bearing lintels has to be considered.

Improper transport/handling may result in dama-ge/functional impairment. Furthermore, the film of the transport packaging must be removed and the delivery checked for completeness.

In storage, fire-resistant dampers must be protected from dust, dirt, moisture and the effects of temperature (e.g. direct sunlight, heat-emitting light source etc.). They must not be exposed to direct weather influences and must not be stored below -40 °C or above 50 °C.

The fire-resistant dampers must be protected from soi-ling and damage. After installation is complete, any dirt must be removed immediately.

Enough space must be provided for installation, mortar lining, etc.

Perform a functional check of the fire-resistant dampers before and after mounting and ensure ready access.

Electrical installations or work on electrical components may only be carried out by skilled electricians. The supp-ly voltage must be switched off when performing this work.

INSTALLATION DETAILS

Installation in solid walls Installation in solid walls (shaft walls, shafts, ducts and fire

walls) made of, for example, concrete, masonry according to EN 1996 or DIN 1053; solid plaster wall boards accord-ing to EN 12859 or DIN 18163; apparent density ≥ 450 kg/m³ and wall thickness W ≥ 100 mm.

Installation of no more than 2 BKA-Üs next to each other "flange-to-flange" without clearance in solid walls. The cir-cumferential gaps and the gap between the housing of BKA-Ü must be filled completely to the minimum ceiling thickness with mortar of category M15 according to EN 998-2, NM III DIN V 18580 (previously: MG III acc. to DIN 1053) or fire protection mortar of suitable grades.

Circumferential gaps "s" must be completely filled with mortar of category M2.5 to M15 to EN 998-2, NM II to III DIN V 18580 (previously: MG II to III to DIN 1053) or fire protection mortar of suitable grades or with concrete or plaster mortar suitable for the wall type. The minimum gap size smin is 40 mm (maximum gap size smax ≤ 60 mm).

If the fire-resistant damper is installed during the construc-tion of the wall, the gaps "s" can be omitted. The mortar bed depth must be designed according to the minimum wall thickness and may not be less than this thickness. When performing a mortar lining or direct installation, make sure that the housing is not pressed toward the insi-de (reinforcement).

Installation with partial mortar lining on adjacent walls (1-sided mineral wool filling, non-flammable (EN13501-1), melting point ≥ 1000 °C, ρ ≥ 150 kg/m

3). Distance of the

circumferential gaps ≤ 50 mm. The clearance between individual BKA-Üs must be at least

70 mm. The distance from load-carrying, adjacent components is

minimum 40 mm from the wall and (due to the construc-tion) minimum 150 mm from the ceiling.

Installation next to each other without clearance "flange to flange"

Installation of the fire-resistant damper in an existing wall recess or a wall recess to be constructed. It has to be desig-ned in such a way that the minimum gap size between the housing and solid wall smin is 40 mm (maximum gap size smax ≤ 60 mm). The gaps "s" and the void between BKA-Üs must be completely filled with mortar of category M15 to EN 998-2, NM III DIN V 18580 (previously: MG III to DIN 1053) or fire protection mortar of suitable grades in the minimum ceiling thickness. If during the construction of the solid wall, the BKA-Üs are installed, the gaps "s" can be omitted, but the cavity between the BKA-Üs must always be filled as descri-bed above.

Figure 2: Installation next to each other without gap "flan-

ge-to-flange" in solid walls

Page 7: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Installation details

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 7

Minimum gap size with complete mortar lining

Installation of the fire-resistant damper in an existing wall recess or a wall recess to be constructed. It has to be desig-ned in such a way that the minimum gap size between the housing and solid wall smin is 40 mm (maximum gap size smax ≤ 60 mm). The gap "s" must be completely filled with mortar of category M2.5 to M15 to EN 998-2, NM II to III DIN V 18580 (previously: MG II to III to DIN 1053) or fire protection mortar of suitable grades or with concrete suitable for the wall type. If the fire-resistant damper is installed during the construction of the solid wall, the gap "s" can be omitted.

Figure 3: Minimum gap size for complete mortar lining in

solid walls

Installation with partial mortar lining

BKA-Üs may be mounted with partial mortar lining and addi-tional mineral wool packing if the cavity cannot be filled completely due to the gap between the BKA-Ü and the solid wall to be protected. For the BKA-Ü mounting, the following conditions must be fulfilled: Installation of the fire-resistant dampers in an existing wall

recess or a wall recess still to be constructed (walls made of, for example, concrete, masonry according to EN 1996 or DIN 1053; solid plaster wall boards according to EN 12859 or DIN 18163; apparent density ≥ 450 kg/m³ and wall thickness W ≥ 100 mm).

The wall recess has to be designed in such a way that the minimum gap size smin of the gaps to be filled with mortar is 40 mm (maximum gap size smax ≤ 60 mm). The gap "s" must be completely filled with mortar of cate-gory M2.5 to M15 to EN 998-2, NM II to III DIN V 18580 (previously: MG II to III to DIN 1053) or fire protection mortar of suitable grades or with concrete suitable for the wall type. The gap filled with the additional mineral wool packing must be filled with non-flammable mineral wool (EN 13501-1, apparent density ≥ 150 kg/m³, melting point ≥ 1000 °C).

This only applies to installation in solid walls if the distance between the housing of the BKA-Ü and the adjacent wall does not exceed 50 mm.

Figure 4: Installation with partial mortar lining in solid walls

Page 8: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Installation details

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 8

Installation in solid ceilings Installation in solid ceilings made, for example, of concre-

te, aerated concrete, apparent density ≥ 500 kg/m³ and ceiling thickness D ≥ 125 mm.

When installing in solid ceilings, the dimensions of the fire-resistant damper BKA-Ü are limited to W and H = 500 mm.

Installation of no more than 2 BKA-Üs next to each other "flange-to-flange" without clearance in solid walls. The cir-cumferential gaps and the gap between the housing of BKA-Ü must be filled completely to the minimum ceiling thickness with mortar of category M15 according to EN 998-2, NM III DIN V 18580 (previously: MG III acc. to DIN 1053) or fire protection mortar of suitable grades.

Circumferential gaps "s" must be completely filled with mortar of category M2.5 to M15 according to EN 998-2, NM II to III DIN V 18580 (previously: MG II to III to DIN 1053) or fire protection mortar of suitable grades or with concrete suitable for the type of ceiling. The minimum gap size smin is 40 mm (maximum gap size smax ≤ 60 mm). If the fire-resistant damper is installed during the ceiling construction, the gaps "s" can be omitted. The mortar bed depth must be designed according to the minimum ceiling thickness and may not be less than this thickness. When performing a mortar lining or direct installation, make sure that the housing is not pressed toward the inside (rein-forcement).

The clearance between individual BKA-Üs must be at least 70 mm.

The distance to load-bearing, adjacent components (wall) is at least 40 mm.

Installation next to each other without clearance "flange to flange"

Installation of the fire resistant damper in an existing ceiling recess or a ceiling recess to be constructed. It has to be de-signed in such a way that the minimum gap size between the housing and solid ceiling smin is 40 mm (maximum gap size smax ≤ 60 mm). The gaps "s" and the cavity between BKA-Üs must be completely filled with mortar of category M15 ac-cording to EN 998-2, NM III DIN V 18580 (previously: MG III according to DIN 1053) or fire protection mortar of corres-ponding grades in the minimum ceiling thickness. If the BKA-Üs are installed during the construction of the solid ceiling, the gaps "s" can be omitted, but the cavity between the BKA-Üs must always be filled as described above.

Figure 5: Installation next to each other without clearance

"flange-to-flange" in solid ceilings

Minimum gap size with complete mortar lining

Installation of the fire resistant damper in an existing ceiling recess or a ceiling recess to be constructed. It has to be de-signed in such a way that the minimum gap size between the housing and solid ceiling smin is 40 mm (maximum gap size smax ≤ 60 mm). The gap "s" must be completely filled with mortar of category M2.5 to M15 according to EN 998-2, NM II to III DIN V 18580 (previously: MG II to III to DIN 1053) or fire protection mortar of suitable grades or with concrete suitable for the type of ceiling. If the fire-resistant damper is installed during the construction of the solid ceiling, the gap "s" can be omitted.

Figure 6: Minimum gap size for complete mortar lining in

solid ceilings

Page 9: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Installation details

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 9

Installation in lightweight partition walls with metal posts and panelling on both sides

Installation without mounting frame ER in lightweight par-tition walls with metal posts and panelling on both sides (gypsum-bonded wall boards; wall thickness W≥ 100 mm) as classified according to EN 13501-2 or comparable nati-onal standards.

No additional, permanent suspensions or attachments of BKA-Ü are allowed, and installation and mounting aids must be removed.

The distance between individual BKA-Üs must be at least 200 mm.

The minimum distance from load-carrying, adjacent com-ponents must be (due to the construction) at least 90 mm from the wall and at least 150 mm from the solid ceiling. The actual minimum distance may differ slightly from the distances mentioned above and must be designed and adapted according to the wall connection type.

Mounting information: In the overlap area of the exchangeable profiles, they must be riveted, crimped or screwed once on both sides. These connections are only for fastening the individual metal profi-les during mounting.

Figure 7: Metal posts plus required spare parts

*) If reveals are lined with plasterboards, the opening di-

mension of the spare parts or the distances to load-carrying

adjacent components are increased.

Wet installation (circumferential mortar lining)

The general information regarding installation in lightweight

partition walls with metal posts and panelling on both sides

(gypsum-bonded wall boards; wall thickness W≥ 100 mm) as

classified according to EN 13501-2 or comparable national

standards must be observed.

Mortar lining: circumferential gaps "s" must be completely filled with mortar of category M15 to EN 998-2, NM III DIN V 18580 (previously: MG III to DIN 1053) or fire protection mortar of suitable grades. The minimum gap size (housing / spare part) smin is 40 mm (max. gap size smax ≤ 60 mm). The mortar bed depth may not be less than minimum wall thickness. For mortar lining or direct installation, make su-re that the housing is not pressed inwards (reinforce-ment).

Section A-A

Detail XA

Figure 8: Wet installation in lightweight partition wall

Page 10: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Installation details

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 10

Section A-A

Detail YA

Figure 9: Wet installation in lightweight partition wall with

reveal

Installation procedure

Mount the metal posts and the wall according to the spe-cifications of the wall manufacturer and the required spare parts as shown in Figure 7.

Provide a recess for the wet installation of BKA-Ü (pos. 1) On both B sides of the exchange profiles (in ⅓ of the

points), 2 bent perforated plates each (t ≥ 0.5 mm; width x length = 40 x 70 mm), must be fastened as mortar anchor (pos. 14). They must be screwed to the metal profiles in the wall centre, using one dry-wall screw each, and cast in concrete.

Insert BKA-Ü into the wall recess (operating side - observe the installation dimension of 210 mm). Average out the circumferential annular gap evenly between the wall and BKA-Ü. Mounting of BKA-Ü with the help of mounting sus-pensions etc.

Insert mortar (pos. 13) into the circumferential gap 40-60 mm wide between the housing of BKA-Ü and the circum-ferential metal profiles (pos. 10). If reveals (pos. 16) are used, a mortar bed depth of 100 mm is sufficient. If reveals are used, the spare parts must be adjusted to the installa-tion opening dimension.

After the mortar has set, the mounting aids (mounting suspensions etc.) must be removed.

Page 11: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Installation details

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 11

Dry installation

The general information regarding installation without

mounting frame ER in lightweight partition walls with metal

posts and panelling on both sides (gypsum-bonded wall

boards; wall thickness W≥ 100 mm) as classified according to

EN 13501-2 or comparable national standards must be ob-

served.

The dry installation must be carried out during the assembly

of the wall. Lining of the reveals is not permissible.

Section A-A

Detail ZA

Figure 10: Dry installation in lightweight partition wall

Installation procedure

Mount the metal posts of the wall in accordance with the specifications of the wall manufacturer and the required spare parts as shown in Figure 7.

Insert BKA-Ü (pos. 1) into the wall recess (operating side - observe the installation dimension of 210 mm). Average out the circumferential annular gap evenly between the wall and BKA-Ü. Mounting of BKA-Ü with the help of mounting suspensions etc.

Insert mineral wool (pos. 18) (nonflammable acc. to EN 13501-1, packing density 80 kg/m³, melting point ≥ 1000°C) into the circumferential gap 40 mm wide between the housing of BKA-Ü and circumferential metal profiles (pos. 10).

Mount the wall panellings on both sides (pos. 12) and the double-board layers on the non-operating side (pos. 19). The connection and butt joints must be filled with the join-ting material of the wall.

Remove mounting aids (mounting suspensions etc.) 1 Fire damper BKA-EN (component of BKA-Ü) 9 Profile CW 50/50/0.6 (with wall thickness = 100 mm, for larger wall thicknesses, the profiles must be adapted accord-ingly). 10 Profile UW 50/40/0.6 (with wall thickness = 100 mm, for larger wall thicknesses, the profiles must be adapted accord-ingly). 11 Mineral wool (according to the specifications of the wall manufacturer) 12 Panelling of the lightweight partition wall made of gyp-sum-bonded wall boards 13 Mortar of category M15 according to EN 998-2, NM III DIN V 18580 (previously: MG III to DIN 1053) 14 Mortar anchor (perforated plate t≥0.5 mm; width x length = 40 x 70 mm) 15 Thermal insulation 16 Reveal, optional (for the wet installation) 17 Fill plaster cavities with jointing material of the wall, max. gap width 5 mm, perform filling operation as part of as-sembly. 18 Mineral wool (nonflammable according to EN13501-1, packing density approx. 80 kg/m³, melting point ≥ 1000°C, thickness 40 mm) 19 Double-board layer (plaster boards GKF, 2 x d=12.5 mm)

- First double-board layer, fastening: Dry-wall screws ø3.5x55, a ≤ 250 mm, or at least 2 screws per side, connection or butt joints of the double-board lay-ers must be filled with the jointing material of the wall. - Second double-board layer, fastening: dry-wall screws ø 4.5x70, a ≤ 250 mm, or at least 2 screws per side, connection and butt joints of the double-board layers must be filled with the jointing material of the wall.

Page 12: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Installation details

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 12

Installation with mounting frame ER in light-weight partition walls with metal posts and pa-nelling on both sides

Installation with mounting frame ER (use only with BKA-EN

L=500) in lightweight partition walls with metal posts and panelling on both sides (gypsum-bonded wall boards; wall thickness W≥ 100 mm) as classified according to EN 13501-2 or comparable national standards.

No additional permanent suspensions or attachments of the BKP-Ü are allowed, and installation and mounting aids must be removed (corner plates are no installation and mounting aids and must remain mounted).

The distance of the fire dampers to each other must be at least 250 mm (construction-related).

The minimum distance from load-carrying adjacent com-ponents with a wall thickness = 100 mm is minimum 150 mm from the solid ceiling and minimum 135 mm from the wall. The actual minimum distance may differ slightly from the distances mentioned above and must be designed and adapted according to the wall connection type.

The minimum distance from load-carrying adjacent com-ponents with a wall thickness > 100 mm is minimum 150 mm from the solid wall and solid ceiling. The actual mini-mum distance may differ slightly from the distances men-tioned above and must be designed and adapted according to the wall connection type.

Mounting frame ER Consisting of silicate structural panels, incl. fastening materi-al and glue on waterglass base. A circumferential intu-mescent seal is located in the centre of the mounting frame ER. The mounting frame ER can be delivered loose as a mounting kit or mounted ex works at an extra charge. If the mounting frame ER has already been mounted ex works on BKA-Ü, the installation can take place immediately. If the mounting frame ER has been ordered or delivered loo-se as a mounting kit, it must be mounted according to the following mounting procedure. To avoid damage to the components when mounting the mounting frame ER, BKA-Ü must be placed on a suitable surface (e.g. cardboard, pallet etc.) during mounting. All holes required for screw mounting have been predrilled on the mounting frame ER ex works, so that no further holes must be drilled. The mounting frame ER may not be screw-connected directly to the housing of BKA-Ü. The individual parts of the mounting frame ER are positioned circumferen-tially between the thermal insulation and the corner of the wall.

Mounting procedure

Position BKA-Ü upright while making sure that no add-on parts, cables etc. are damaged. Place the first B part (pos. 21.1) against the housing of

BKA-Ü (pos. 1). Place the first H part (pos. 21.2) likewise against BKA-Ü

(pos. 1) and screw it to the first B part (pos. 21.1) in the overlapping area using the delivered countersunk head screws (pos. 21.5).

Place the second B part (pos. 21.3) against BKA-Ü (pos. 1) and screw, first, the H part (pos. 21.2) to the second B part (pos. 21.3).

Finally, place second H part (pos. 21.4) against BKA-Ü (pos. 1) and screw it to both the first (pos. 21.1) and the second B part (pos. 21.3).

Figure 11: BKA-Ü with mounting frame ER (loose)

Installation in a wall thickness = 100 mm

Mounting information: In the overlapping area of the exchangeable profiles, they must be riveted, crimped or screwed once on both sides. These connections are only for fastening the individual metal profiles during mounting.

Figure 12: Metal posts with required spare parts for BKA-Ü with mounting frame ER (wall thickness = 100 mm)

Page 13: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Installation details

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 13

Installation procedure: (wall thickness = 100 mm)

Mount the metal posts and the wall in accordance with the specifications of the wall manufacturer and the required spare parts as shown in Figure 12. Leave a recess for the installation of BKA-Ü with mounting frame ER. For wall thicknesses > 100 mm, make sure that the recess has a size different from that for a wall thickness = 100 mm.

Insert BKA-Ü (pos. 1) into the wall recess (operating side - observe the installation dimension of 210 mm). Average out the circumferential annular gap evenly between the wall and the mounting frame ER. Mount the BKA-Ü with the help of mounting suspensions, wedges etc.

Place the corner plates (pos. 22) on the operator side of the BKA-Ü flush with the housing and with the mounting frame ER (pos. 21) and fasten them on the mounting frame ER using the delivered screws (pos. 23) and to the metal posts, using the dry-wall screws (pos. 24 -on site-; Figure 13). The length of the dry-wall screws must be selected such that they are fastened to the metal posts (e.g. ø 3.9 x 55 mm).

Fill the annular gap circumferentially on both sides of the wall with the delivered glue on water glass base (pos. 25; min. 108 g/lfm).

Remove mounting aids (suspensions, wedges, etc.)

Detail XB

Figure 13: BKA-Ü with mounting frame and mounted corner

plates (wall thickness = 100 mm)

Section B-B Detail YB

Figure 14: BKA-Ü installed with mounting frame ER (wall

thickness = 100 mm)

Page 14: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Installation details

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 14

Installation in a wall thickness = 100 mm

Mounting information: In the overlapping area of the exchangeable profiles, they must be riveted, crimped or screwed once on both sides. These connections are only for fastening the individual metal profiles during mounting.

Figure 15: Metal posts with required spare parts for BKA-Ü with mounting frame ER (wall thickness > 100 mm)

Installation procedure (wall thickness > 100 mm)

Mount the metal posts and the wall in accordance with the specifications of the wall manufacturer and the required spare parts as shown in Figure 15. Leave a recess for the installation of BKA-Ü with mounting frame ER. For wall thicknesses > 100 mm, make sure that the recess has a size different from that for a wall thickness = 100 mm.

Construct an additional circumferential reveal (pos 16) with 12.5-mm plasterboards and screw them centrally to the circumferential metal profile frame (fastening: e.g. drywall screws ø 3.5x25, screw distance = 250 mm, but at least 2 screws per side).

Insert the BKA-Ü (pos. 1) into the wall recess (operating si-de - observe the installation dimension of 210 mm). Avera-ge out the circumferential annular gap evenly between the wall and the mounting frame ER. Mount the BKA-Ü with the help of mounting suspensions, wedges etc.

Place the corner plates (pos. 22) on the operator side of the BKA-Ü flush with the housing and with the mounting frame ER (pos. 21) and fasten them on the mounting frame ER using the delivered screws (pos. 23) and to the metal posts, using the drywall screws (pos. 24 -on site-; Figure 16). The length of the dry-wall screws must be selected such that they are fastened to the metal posts (e.g. ø 3.9 x 55 mm).

Fill the annular gap circumferentially on both sides of the wall with the delivered glue on water glass base (pos. 25; min. 108 g/lfm).

Remove mounting aids (suspensions, wedges etc.)

Detail XC

4

Figure 16: BKA-Ü with mounting frame ER and mounted

corner plates (wall thickness > 100 mm)

Page 15: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Installation details

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 15

Section C-C Detail YC

Figure 17: BKA-Ü installed with mounting frame ER (wall

thickness > 100 mm)

1 Fire damper BKA-EN (component of BKA-Ü) 9 Profile CW 50/50/0.6 (with wall thickness = 100 mm, for larger wall thicknesses, the profiles must be adapted accord-ingly). 10 Profile UW 50/40/0.6 (with wall thickness = 100 mm, for larger wall thicknesses, the profiles must be adapted accord-ingly). 11 Mineral wool (according to the specifications of the wall manufacturer) 12 Panelling of the lightweight partition wall made of gyp-sum-bonded wall boards 16 Reveal, circumferential (-on site- 12.5-mm plasterboards) 21 Mounting frame ER (BKA-EN; L=500) 22 Corner plate (-on site- 4 pieces/ mounting frame ER) 23 Countersunk head screws ø5x40 mm (-ex works- 2 pieces / corner plate) 24 Dry-wall screws (-on site- 3 pieces / corner plate; e.g. ø3.9x55 mm 25 Waterglass-based glue (-ex works- min. 108 g/lfm ≙ a minimum filling depth of approx. 15 mm with an an-nular gap of 4 mm)

Page 16: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Installation details

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 16

Installation in lightweight partition walls with metal posts and single-layer panelling on both sides

Installation in lightweight partition walls with metal posts

and panelling on both sides (gypsum-bonded wall boards; wall thickness W ≥ 75 mm) according to classification to EN 13501-2 or comparable national standards.

No additional suspensions or attachments of BKA-Ü are al-lowed, and installation and mounting aids must be remo-ved.

The minimum distance of BKA-Ü from one another must be at least 200 mm.

The minimum distance from load-carrying, adjacent com-ponents must be (due to the construction) minimum 150 mm from the wall and minimum 90 mm from the solid cei-ling. The actual minimum distance may differ slightly from the distances mentioned above and must be designed and adapted according to the wall connection type.

Mounting information: In the overlapping area of the exchangeable profiles, they must be riveted, crimped or screwed once on both sides. These connections are only for fastening the individual metal profiles during mounting.

Figure 18: Metal posts plus required spare parts

Section D-D Detail XD

Figure 19: Simple wall panelling and double-board layers

Installation procedure

Mount the metal posts and the wall in accordance with the specifications of the wall manufacturer and the required spare parts as shown in Figure 18.

Insert BKA-Ü (pos. 1) into the wall recess (operating side - observe the installation dimension of 210 mm). Average out the circumferential annular gap evenly between the wall and BKA-Ü. Mounting of BKA-Ü with the help of mounting suspensions etc.

Insert mineral wool (pos. 26) (nonflammable to EN 13501-1, apparent/packing density 30 kg/m³, melting point ≥ 1000°C) into the circumferential gap 40 mm wide between the housing of BKA-Ü and the circumferential metal profi-les (pos. 10).

Mount the wall panellings on both sides (pos. 12) and the double-board layers on the non-operating side (pos. 27). The connection and butt joints must be filled with the join-ting material of the wall.

Remove mounting aids (mounting suspensions etc.) 1 Fire damper BKA-EN (component of BKA-Ü) 9 Profile CW 50/50/0.6 10 Profile UW 50/40/0.6 11 Mineral wool (according to the specifications of wall ma-nufacturer) 12 Panelling of the lightweight partition wall made of gyp-sum-bonded wall boards 15 Thermal insulation 17 Fill plaster cavities with jointing material of the wall, max. gap width 5 mm, perform filling operation as part of as-sembly. 26 Mineral wool, (nonflammable acc. to EN 13501-1, appa-rent/packing density approx. 30 kg/m³, melting point ≥ 1000 °C, hickness 40 mm) 27 Double-board layer (plaster boards GKF, 2 x d=12.5 mm)

- First double-board layer, fastening: Dry-wall screws ø3.9x55, a ≤ 250 mm, or at least 2 screws per side, connection or butt joints of the double-board lay-ers must be filled with the jointing material of the wall. - Second double-board layer, fastening: dry-wall screws ø 3.9x55, a ≤ 250 mm, or at least 2 screws per side, connection and butt joints of the double-board layers must be filled with the jointing material of the wall.

Page 17: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Installation details

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 17

Installation in fire walls with construction of lightweight partition walls with metal posts and panelling on both sides

Installation in fire walls with the construction of light-

weight partition walls with metal post and panelling on both sides and inside sheet steel inlay with the following general building supervisory test certificates (abP):

abP no. P-3391/170/08-MPA BS (Knauf) abP no. P-3020/0109-MPA BS (Rigips) abP no. P-3796/7968-MPA BS (Promat)

No additional suspensions or attachments of BKA-Ü are al-lowed, and installation and mounting aids must be remo-ved.

The minimum distance of BKA-Ü from one another must be at least 200 mm.

The minimum distance from load-carrying adjacent com-ponents is at least 150 mm from a solid ceiling and at least 90 mm from the wall. The actual minimum distance may differ slightly from the distances mentioned above and must be designed and adapted according to the wall connection type.

Mounting information: In the overlapping area of the exchangeable profiles, they must be riveted, crimped or screwed once on both sides. These connections are only for fastening the individual metal profiles during mounting.

Figure 20: Metal posts plus required spare parts (fire wall)

Installation of the BKA-Ü after finishing the fire wall

BKA-Ü retracted after assembly of the wall, assembly of the wall according to abP:

Knauf P-3391/170/08-MPA BS or Rigips P-3020/0109-MPA BS

Section E-E

Figure 21: Wall panelling and double-board layers (after fi-

nishing the fire wall - Knauf or Rigips)

Installation procedure

Mount the metal posts and the wall in accordance with the specifications of the wall manufacturer and the required spare parts as shown in Figure 20.

Insert the mineral wool of the wall (pos. 11 according to the specifications of the wall manufacturer). Mount the wall panelling (pos. 33) with sheet steel inlay and the in-stallation opening for the installation of BKA-Ü. When de-signing the external layer of the wall panelling, make sure that the panel layers are offset.

Insert the BKA-Ü (pos. 1) into the wall recess (operating si-de - observe the installation dimension of 210 mm for double-board layer). Average out the annular gap evenly between the circumferential UA-profiles (pos. 28) of the wall and housing of BKA-Ü. Mounting of the BKA-Ü with the help of mounting suspensions etc.

Insert mineral wool (pos. 31) (nonflammable acc. to EN 13501-1, apparent/packing density 100 kg/m³, melting point ≥ 1000°C) into the circumferential gap 40 mm wide between the housing of the BKA-Ü and the circumferential UA-profiles (pos. 28).

Mount the circumferential wall panelling strips on both si-des (pos. 33.1) and the double-board layers (pos. 32) both on the non-operating and operating sides. The connection and butt joints must be filled with the jointing material of the wall (pos. 34).

Remove mounting aids (mounting suspensions etc.)

Page 18: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Installation details

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 18

Promat P-3796/7968-MPA BS

Section E-E

Figure 22: Wall panelling and double-board layers (after fi-

nishing the fire wall - Promat)

Installation procedure

Mount the metal posts and the wall in accordance with the specifications of the wall manufacturer and the required spare parts as shown in Figure 20.

Insert the mineral wool of the wall (pos. 11 according to the specifications of the wall manufacturer). Mount the wall panelling (pos. 33) with inside sheet steel inlay and the installation opening for the installation of the BKA-Ü. When constructing the outer layer of the wall panelling, make sure that the panel layers are offset.

Insert the BKA-Ü (pos. 1) into the wall recess (operating si-de - observe the installation dimension of 210 mm for double-board layer). Average out the annular gap evenly between the circumferential UA-profiles (pos. 28) of the wall and housing of BKA-Ü. Mounting of BKA-Ü with the help of mounting suspensions etc.

Insert mineral wool (pos. 11) (nonflammable acc. to EN 13501-1, apparent/packing density 100 kg/m³, melting point ≥ 1000°C) into the circumferential gap 40 mm wide between the housing of BKA-Ü and the circumferential UA-profiles (pos. 28).

Mount the circumferential wall panelling strips on both si-des (pos. 33.1) and the double-board layers (pos. 32) both on the non-operating and operating sides. The connection and butt joints must be filled with the jointing material of the wall (pos. 34).

Remove mounting aids (mounting suspensions etc.)

Installation of BKA-Ü during the assembly of the wall

BKA-Ü installed during wall mounting, assembly of the wall according to abP:

Knauf P-3391/170/08-MPA BS or Rigips P-3020/0109-MPA BS

Section E-E

Figure 23: Wall panelling and double-board layers (during

construction of the fire wall - Knauf or Rigips)

Installation procedure

Mount the metal posts and the wall in accordance with the specifications of the wall manufacturer and the required spare parts as shown in Figure 20.

Insert the BKA-Ü (pos. 1) into the installation opening of the wall (operating side - observe the installation dimensi-on of 210 mm for wall panelling). Average out the annular gap evenly between the circumferential UA-profiles (pos. 28) of the wall and housing of BKA-Ü. Mounting of BKA-Ü with the help of mounting suspensions etc.

Insert mineral wool (pos. 31) (nonflammable acc. to EN 13501-1, apparent/packing density 100 kg/m³, melting point ≥ 1000°C) into the circumferential gap 40 mm wide between the housing of BKA-Ü and the circumferential UA-profiles (pos. 28).

Insert the mineral wool of the wall (pos. 11 according to the specifications of the wall manufacturer). Mount the wall panelling (pos. 33) with inside sheet steel inlay and the double-board layer on the non-operating side (pos. 32). The connection and butt joints must be filled with the jointing material of the wall (pos.34).

Remove mounting aids (mounting suspensions etc.)

Page 19: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Installation details

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 19

Promat P-3796/7968-MPA BS Section E-E

Figure 24: Wall panelling and double-board layers (during

construction of the fire wall - Promat)

Installation procedure

Mount the metal posts and the wall in accordance with the specifications of the wall manufacturer and the required spare parts as shown in Figure 20.

Insert the BKA-Ü (pos. 1) into the installation opening of the wall (operating side - observe the installation dimensi-on of 210 mm for wall panelling). Average out the annular gap evenly between the circumferential UA-profiles (pos. 28) of the wall and housing of BKA-Ü. Mounting of BKA-Ü with the help of mounting suspensions etc.

Insert mineral wool (pos. 31) (nonflammable acc. to EN 13501-1, apparent/packing density 100 kg/m³, melting point ≥ 1000°C) into the circumferential gap 40 mm wide between the housing of BKA-Ü and the circumferential UA-profiles (pos. 28).

Insert the mineral wool of the wall (pos. 11 according to the specifications of the wall manufacturer). Mount the wall panelling (pos. 33) with inside sheet steel inlay and the double-board layer on the non-operating side (pos. 32). The connection and butt joints must be filled with the jointing material of the wall (pos.34).

Remove mounting aids (mounting suspensions etc.)

1 Fire damper BKA-EN (component of BKA-Ü) 11 Mineral wool (according to the wall manufacturer's spe-cifications) 15 Thermal insulation 28 Profile UA 50/75/100 (selected according to wall thickness/wall manufacturer) 29 Profile CW 50/75/100 (selected according to wall thickness/wall manufacturer) 30 Profile UW 50/75/100 (selected according to wall thickness/wall manufacturer) 31 Mineral wool, (non-flammable to EN 13501-1, apparent/ packing density 100 kg/m³, melting point ≥ 1000 °C, thickness 40 mm) 32 Doubling 33 Wall panelling 33.1 Wall panelling strips 34 Plaster joint filling with jointing material of the wall, gap width approx. 10 mm

Page 20: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Installation details

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 20

Installation in shaft walls Installation in lightweight partition walls with metal posts

and panelling on one side (gypsum-bonded wall boards; wall thickness ≥ 125 mm, maximum wall height ≤ 5000 mm) according to classification to EN 13501-2 or compa-rable national standards.

No additional suspensions or attachments of BKA-Ü are al-lowed, and installation and mounting aids must be remo-ved.

The minimum distance of BKA-Ü from one another must be at least 200 mm.

The minimum distance from load-carrying, adjacent com-ponents is (due to the construction) min. 90 mm from the wall and min. 150 mm from the solid ceiling. The actual minimum distance may differ slightly from the distances mentioned above and must be designed and adapted ac-cording to the wall connection type.

Mounting information: In the overlapping area of the exchangeable profiles, they must be riveted, crimped or screwed once on both sides. These connections are only for fastening the individual metal profiles during mounting.

Figure 25: Metal posts plus required spare parts (shaft wall) Section F-F Detail XF

Figure 26: Wall panelling and double-board layers (shaft

wall)

Installation procedure

Mount the metal posts and the wall in accordance with the specifications of the wall manufacturer and the required spare parts as shown in Figure 25.

Mount the wall panelling (pos. 38) and double-board layer (pos. 37) and the installation opening for the installation of BKA-Ü.

If required, mount a filling stop on the non-operating side of BKA-Ü (pos. 1) (must not be screwed to the housing of BKA-Ü!). The filling stop is not required by fire protection regulations).

Mounting of BKA-Ü with the help of mounting suspensions etc.

Insert the BKA-Ü into the wall recess (operating side - ob-serve the installation dimension of 210 mm for double-board layer). Average out the annular gap evenly between the circumferential metal profiles of the wall and housing of BKA-Ü.

Carry out the joint filling with the jointing material of the wall (pos. 39). The connection and butt joints of the dou-ble-board layers must also be filled with the jointing mate-rial of the wall.

Remove mounting aids (mounting suspensions etc.) 1 Fire damper BKA-EN (component of BKA-Ü) 15 Thermal insulation 35 Profile UW 75/40/0.6 - 150 profiles 36 Profile CW 75/50/0.6 - 150 profiles 37 Double-board layer (gypsum-bonded wall boards, d=25 mm)

- Fastening: dry-wall screws ø 4.2x90, a ≤ 300 mm, or at least 2 screws per side, connection and butt joints of the double-board layers must be filled with the jointing ma-terial of the wall.

38 Panelling of the shaft wall made of gypsum-bonded wall boards. The specifications of the wall manufacturer must be observed. 39 Plaster jointing, gap completely filled with plaster

Page 21: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Installation information

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 21

INSTALLATION INFORMATION

Connection of ventilation ducts

Fire-resistant dampers must not be connected to ventilation ducts in connection with ventilation systems in buildings. See section 1.2.1 of the general building supervisory authority (abZ) no. Z-6.50-2012. Fire-resistant dampers of special de-sign and use can be used if, as part of ventilation planning, openings are required in fire-resistant inner walls or ceilings for air intake, they must be closed in the event of a fire.

Minimum distances

The given dimensions must be considered as spacing

recommendation for BKA-EN and may differ, depending on

the local situation. The installation must be performed ac-

cording to the technical documentation, installation,

mounting and operating instructions in combination with the

current valid abZ. Pay attention to the accessibility when in-

stalling 2 BKA-Üs next to each other or in the direct vicinity

of load-carrying adjacent components. For wall installation,

the smoke detector must always be installed above in the

assembly part type EBT with the damper blade axle in the

horizontal position.

Figure 27: Minimum distances of BKA-Ü

1.) Minimum distances recommended by SCHAKO with re-gard to later maintenance 2.) The distance between BKA-Ü and load-carrying adjacent component (wall/ceiling) must be determined according to the particular installation situation or adjusted to the dimen-sions of the projecting ends. 3.) Max. 2 BKA-Üs can be installed next to each other wit-hout "flange-to-flange" clearance in solid walls and solid cei-lings. This may lead to a situation in which the inspection openings are no longer accessible. In other installation situa-tions, the distance may become larger as a result of construction. Sufficient distance between the mounted components must be guaranteed. The dimension x is: - approx. 80 mm with spring return actuators - approx. 95 mm with relay module RM (V4.00) The dimension y is: - approx. 110 mm with smoke detector RMSII-L

Page 22: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Technical data

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 22

TECHNICAL DATA

Free cross-section [m²]

Table 4: Free cross-section [m²]

Width (mm)

200 225 250 275 300 325 350 375 400 450 500 550

He

igh

t (m

m)

200 0.029 0.033 0.036 0.040 0.044 0.047 0.051 0.054 0.058 0.065 0.073 0.080

225 0.034 0.038 0.043 0.047 0.051 0.055 0.060 0.064 0.068 0.077 0.085 0.094

250 0.039 0.044 0.049 0.054 0.059 0.063 0.068 0.073 0.078 0.088 0.098 0.107

275 0.044 0.050 0.055 0.061 0.066 0.072 0.077 0.083 0.088 0.099 0.110 0.121

300 0.049 0.055 0.061 0.067 0.074 0.080 0.086 0.092 0.098 0.110 0.123 0.135

325 0.054 0.061 0.068 0.074 0.081 0.088 0.095 0.101 0.108 0.122 0.135 0.149

350 0.059 0.066 0.074 0.081 0.089 0.096 0.103 0.111 0.118 0.133 0.148 0.162

375 0.064 0.072 0.080 0.088 0.096 0.104 0.112 0.120 0.128 0.144 0.160 0.176

400 0.069 0.078 0.086 0.095 0.104 0.112 0.121 0.129 0.138 0.155 0.173 0.190

450 0.079 0.089 0.099 0.109 0.119 0.128 0.138 0.148 0.158 0.178 0.198 0.217

500 0.089 0.100 0.111 0.122 0.134 0.145 0.156 0.167 0.178 0.200 0.223 0.245

550 0.099 0.111 0.124 0.136 0.149 0.161 0.173 0.186 0.198 0.223 0.248 0.272

600 0.109 0.123 0.136 0.150 0.164 0.177 0.191 0.204 0.218 0.245 0.273 0.300

650 0.119 0.134 0.149 0.164 0.179 0.193 0.208 0.223 0.238 0.268 0.298 0.327

700 0.129 0.145 0.161 0.177 0.194 0.210 0.226 0.242 0.258 0.290 0.323 0.355

750 0.139 0.156 0.174 0.191 0.209 0.226 0.243 0.261 0.278 0.313 0.348 0.382

800 0.149 0.168 0.186 0.205 0.224 0.242 0.261 0.279 0.298 0.335 0.373 0.410

Width (mm)

600 650 700 750 800 900 1000 1100 1200 1300 1400 1500

He

igh

t (m

m)

200 0.087 0.094 0.102 0.109 0.116 0.131 0.145 0.160 0.174 0.189 0.203 0.218

225 0.102 0.111 0.119 0.128 0.136 0.153 0.170 0.187 0.204 0.221 0.238 0.255

250 0.117 0.127 0.137 0.146 0.156 0.176 0.195 0.215 0.234 0.254 0.273 0.293

275 0.132 0.143 0.154 0.165 0.176 0.198 0.220 0.242 0.264 0.286 0.308 0.330

300 0.147 0.159 0.172 0.184 0.196 0.221 0.245 0.270 0.294 0.319 0.343 0.368

325 0.162 0.176 0.189 0.203 0.216 0.243 0.270 0.297 0.324 0.351 0.378 0.405

350 0.177 0.192 0.207 0.221 0.236 0.266 0.295 0.325 0.354 0.384 0.413 0.443

375 0.192 0.208 0.224 0.240 0.256 0.288 0.320 0.352 0.384 0.416 0.448 0.480

400 0.207 0.224 0.242 0.259 0.276 0.311 0.345 0.380 0.414 0.449 0.483 0.518

450 0.237 0.257 0.277 0.296 0.316 0.356 0.395 0.435 0.474 0.514 0.553 0.593

500 0.267 0.289 0.312 0.334 0.356 0.401 0.445 0.490 0.534 0.579 0.623 0.668

550 0.297 0.322 0.347 0.371 0.396 0.446 0.495 0.545 0.594 0.644 0.693 0.743

600 0.327 0.354 0.382 0.409 0.436 0.491 0.545 0.600 0.654 0.709 0.763 0.818

650 0.357 0.387 0.417 0.446 0.476 0.536 0.595 0.655 0.714 0.774 0.833 0.893

700 0.387 0.419 0.452 0.484 0.516 0.581 0.645 0.710 0.774 0.839 0.903 0.968

750 0.417 0.452 0.487 0.521 0.556 0.626 0.695 0.765 0.834 0.904 0.973 1.043

800 0.447 0.484 0.522 0.559 0.596 0.671 0.745 0.820 0.894 0.969 1.043 1.118

Page 23: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Technical data

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 23

Weight table [kg]

Table 5: Weight table [kg]

Width (mm)

200 225 250 275 300 325 350 375 400 450 500 550

He

igh

t (m

m)

200 20 21 22 23 23 24 25 26 27 28 30 32

225 21 22 23 24 24 25 26 27 28 29 31 33

250 22 23 24 24 25 26 27 28 29 31 32 34

275 23 24 24 25 26 27 28 29 30 32 34 35

300 23 24 25 26 27 28 29 30 31 33 34 36

325 24 25 26 27 28 29 30 31 32 34 36 38

350 25 26 27 28 29 30 31 32 33 35 37 39

375 26 27 28 29 30 31 32 33 34 36 38 40

400 30 31 33 34 35 36 38 39 40 42 45 47

450 34 35 36 38 39 40 42 43 44 47 49 52

500 36 37 38 40 41 43 44 45 46 49 52 54

550 37 39 40 42 43 45 46 47 49 52 54 57

600 39 40 42 44 45 47 48 49 51 54 56 59

650 41 42 44 46 47 49 50 52 53 56 59 62

700 43 44 46 48 49 51 52 54 55 58 62 65

750 45 46 48 50 51 53 55 56 58 61 64 67

800 48 49 51 53 55 57 58 60 62 65 68 72

Width (mm)

600 650 700 750 800 900 1000 1100 1200 1300 1400 1500

He

igh

t (m

m)

200 33 35 36 38 40 44 47 51 54 57 60 63

225 34 36 38 40 41 46 49 53 56 59 63 66

250 36 38 39 41 43 48 51 56 58 62 65 68

275 37 39 41 43 44 49 53 56 60 64 67 71

300 38 40 42 44 46 51 54 58 62 65 69 73

325 39 41 43 45 47 52 56 60 64 68 71 75

350 41 43 45 47 49 54 58 62 66 70 74 78

375 42 44 46 48 50 56 60 64 68 72 76 80

400 49 52 54 57 59 65 70 74 79 84 89 93

450 54 57 59 62 64 69 74 79 84 89 94 99

500 57 60 62 65 67 73 78 83 88 94 99 104

550 60 63 65 68 71 76 82 87 93 98 104 109

600 62 65 68 71 73 79 85 90 96 102 107 113

650 65 68 71 74 77 82 88 94 100 106 112 118

700 68 71 74 77 80 86 92 98 104 110 117 123

750 70 74 77 80 83 90 96 102 109 115 121 128

800 75 79 82 85 89 95 102 109 116 122 129 136

Page 24: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Spring return actuators

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 24

SPRING RETURN ACTUATORS

Assignment of the actuator types B10/B20/B30 according to the dimensions

Table 6: Assignment of the actuator types

Table 7: Technical data of 24 V spring return actuators

Width

200 225 250 275 300 325 350 375 400 450 500 550 600 650 700 750 800 900 1000 1100 1200 1300 1400 1500

He

igh

t

200

225

250

275

300

325

350

375

400

440

450

500

550

600

650

700

750

800

B10 (BFL24-T-ST SO) B20 (BFN24-T-ST SO) B30 (BF24-T-ST SO)

Actuator type B10 (BFL24-T-ST SO) B20 (BFN24-T-ST SO) B30 (BF24-T-ST SO)

Rated voltage [V] AC/DC 24

Rated voltage frequency [Hz] 50/60

Functional range [V] AC 19.2…28.8 / DC 21.6…28.8

Power consumption during operation [W]

2.5 4 7

Power consumption in idle position [W]

0.8 1.4 2

Power consumption/dimensioning 4 VA / Imax 8.3 A 5 ms 6 VA / Imax 8.3 A 5 ms 10 VA / Imax 8.3 A 5 ms

Auxiliary switch 2 x EPU

Switching capacity of auxiliary switch 1 mA…3 (0.5 inductive) A, AC 250 V 1 mA…6 (3) A, DC 5 V…AC 250 V

Connection of supply / control Cable 1 m, 2 x 0.75 mm² (halogen-free), with 3-pin connector

Auxiliary switch connection Cable 1 m, 6 x 0.75 mm² (halogen-free), with 6-pin connector

Running time Motor <60 s /90° <120 s /90°

Spring return runtime 20 s -10…55°C / <60 s -30…-10°C ̴16 s (tamb = 20°C)

Protection class IEC/EN III Safety extra low voltage

Protection class auxiliary switch IEC/EN II protective insulation

Protection type IEC/EN IP54

Ambient temperature normal operati-on

-30…55°C -30…50°C

Storage temperature -40…55°C -40…50°C

Ambient humidity 95% r.h., non-condensing

Page 25: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Smoke detection system RMS

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 25

Electric spring return actuators B10/B20/B30

Electric spring return actuator with thermoelectric re-lease device BAT (B10/B20) or BAE72B-S (B30)

Release temperature 72°C Operating position (damper "OPEN") is approached au-

tomatically and return spring is tensioned by applying the supply voltage to the relay module RM (V4.00). It supplies the spring return actuator with supply voltage. ! Thus, the safety function is ensured. Safety position (damper "CLOSED") through spring force when supply voltage is interrupted by smoke de-tection system RMS or the temperature fuses (ambient temperature or internal duct temperature) of the spring return actuator respond. A response of the thermal fuses will interrupt

SMOKE DETECTION SYSTEM RMS

Figure 28: Circuit diagram Relay module RM (V4.00)

1.) Smoke detector RMSII-L 2.) Relay module RM (V4.00) 3.) Mains connection - 230V AC 50Hz (on-site) 4.) Reset button 5.) Manual release 6.) LED fault 7.) LED alarm 8.) LED operation 9.) Connection RMSII-L 10.) AMP plug for 24V AC/DC spring return actuator 11.) Selector switch 1; potential-free changeover contact (1) foot contact (24V / 230V) 12.) Selector switch 2; potential-free changeover contact (2) foot contact (24V / 230V) 13.) Contact load of the selector switches 14.) Spring return actuator 24V AC/DC 15.) Limit switch spring return actuator (connection is fitted in a T-piece socket on-site)

the supply voltage permanently and irrevocably.

Display of the damper end positions is possible by me-ans of integrated micro switches via potential-free changeover contacts (connected on-site) (S1 – S3 "CLOSED" indicates the closed position; S4 – S6 "OPEN" indicates the opened position.

Manual actuation and fixing in any position is possible in the de-energised state. It is unlocked manually.

On-site function control is possible by means of the control key of BAT or BAE72-B-S.

Spare parts: thermal fuse for temperature inside the duct (ZBAT72 or ZBAE72); for any other damage etc., the entire "drive/thermal release device" unit must be replaced completely.

Contact assignment Smoke detector RMSII-L: 1 GND 2 Work contact 3 Centre contact 4 Rest contact 5 Test switch / RST 6 Rest contact 7 Centre contact 8 Work contact 9 +24V 10 Fault 11 Alarm Ö = NC contact Mi = Centre contact S = NO contact The de-energised state is shown. For relay module RM (V4.00), also the alarm and fault condition.

Page 26: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Specification texts

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 26

SPECIFICATION TEXTS

Fire-resistant dampers of special design and use are used if, as part of ventilation planning, openings are required in fire-resistant inner walls or ceilings for the air intake, they must be closed in the event of a fire. The competent building supervisory authority will decide whether the opening is admissible, for example because it differs or in connection with the approval of the fire protec-tion concept. The required dampers are fire-resistant dampers which are closed in case of fire driven by a suitable smoke detecting triggering device in the event of a fire, thus preventing the propagation of fire and smoke through the component ope-ning. Dampers of this type may not be connected to ventila-tion ducts in connection with RLT systems in buildings. Dampers according to the general building supervisory ap-proval Z-6.50-2012 are neither fire protection dampers nor fire dampers against propagation of fire in ventilation ducts. The "General and Special Conditions" of the general building supervisory approval Z-6.50-2012 in its current form, the in-stallation, mounting and operating instructions and the rele-vant standards and directives must be observed. The standard fire-resistant damper BKA-Ü consists of the following components: SCHAKO fire damper BKA-EN, according to the require-

ments of the Declaration of performance no. 09-19-DoP-BKA-EN-2013-07-01, housing made of galvanised sheet steel with electric spring return actuator 24 V.

SCHAKO assembly part type EBT, galvanised sheet steel model (painted black matt on the inside), housing leaka-ge according to DIN EN 1751, class B, at a duct pressure of up to 1000 Pa.

SCHAKO finishing protective grating type ASG on both si-des, galvanised sheet steel model.

SCHAKO extension part type VT, galvanised sheet steel model, required for H ≥ 400.

Identification label (must be attached permanently to the adjacent component by the installing company)

SCHAKO smoke detection system RMS, according to the general building supervisory approval no. Z-78.6-58; con-sisting of: - SCHAKO smoke detector RMSII-L - SCHAKO relay module RM (V4.00)

EBT (with RMS), ASG and, if present, VT are mounted to the BKA-EN. RMSII-L and the spring return actuator are wired with the relay module RM (V4.00).

Installation is performed in interior walls (horizontal position of the damper blade axle) and ceilings. In doing so, the gene-ral building supervisory approval no. Z-6.50-2012, the Decla-ration of performance no. 09-19-DoP-BKA-EN-2013-07-01, general building supervisory approval no. Z-78.6-58 and the associated technical documentation must be observed. For the installation in solid ceilings, the dimensions of BKA-Ü are limited to W and H = 500 mm. For wall installation, the smo-ke detector must always be installed above in the assembly part type EBT with the damper blade axle in the horizontal position. Make: SCHAKO type BKA-Ü General building supervisory approval no. Z-6.50-2012 Dimensions Width (B): .................... mm Height (H): .................... mm Length (L): 500 mm (standard length refers to BKA-EN) Alternative designs or accessories (select as required) Extra charge for anticorrosive paint - inside/outside -

- DD coating (two-component top coat based on po-lyurethane varnish -RAL 7035 / light-grey)

Extra charge for stainless steel version: - Material no. 1.4301 (V2A) - Material no. 1.4571 (V4A - All replaceable, non-coated parts are made of stainless steel material no. 1.4301 (V2A))

Page 27: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation Service

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 27

SERVICE FUNCTIONAL TEST, MAINTENANCE/CLEANING, REPAIR

The type of use and installation situation must be checked for the first time during commissioning and then after modi-fication. After the commissioning of the fire-resistant dam-per, its function must be checked every six months. If two consecutive functional tests show no defects, the fire-resistant dampers only have to be tested once a year. If maintenance agreements are made, for example for ventila-tion installations, it is recommended including the functional tests of the fire-resistant damper in these maintenance ag-reements. Observe the notes in the general building supervisory appro-val (abZ) no. Z-6.50-2012 section 5.

1. Electric spring return actuator 1.1. Visual inspection

Check BKA-Ü for damage and contamination. Performing necessary cleaning work

1.2 Thermoelectric trigger – Closing BKA-Ü

Press switch (pos. 5.2) on the thermoelectric relea-se device (pos. 5.1), thus, removing the electric power from the spring return actuator (pos. 5) (al-ternatively: interrupt on-site power supply).

BKA-Ü must close automatically, locking is perfor-med by blocking the spring return actuator.

1.3 Replacement of the thermoelectric trigger device (if ne-cessary)

Exchange takes place by unscrewing the two screws of the thermoelectric trigger device (pos. 5.1). Remove the thermoelectric trigger device from the drive unit. Remove the internal duct temperature fuse (pos. 5.3) from the thermoelectric trigger de-vice and replace it with a new internal duct tempe-rature fuse (ZBAT72). Screw the thermoelectric trigger device back onto the drive unit. Carry out a functional check

Figure 29: Side view BKA-Ü (spring return actuator)

Figure 30: Front view BKA-Ü (spring return actuator)

Page 28: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation Service

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 28

2. Smoke alarm system RMS Note Installation and wiring must be carried out by authorised electricians only. The agreed regulations of the technic, sa-fety and accident prevention regulations as well as the VDE guidelines, regulations of the local EVU's and the wiring in-structions and connection plans of the manufacturer, must be adhered to when installing, wiring and commissioning. When wiring the junction boxes, make sure to earth the shielding. The smoke detector must be used according to these instructions. Maintenance instructions The SCHAKO smoke detector type RMSII-L permanently mo-nitors itself and sends an error warning to the central unit if there is a mechanical or electrical defect or if it is too heavily soiled. If a power failure of the smoke detector occurs, a fault message is also sent to the central unit. This permanent self-monitoring allows a yearly maintenance interval.

2.1 External check 2.1.1 Visual inspection

The electrical connections must be checked for correct connection and perfect condition.

Checking whether the diode on the installed smoke detector or relay module RM (V4.00) flashes green, thus, signalling its ready-for-operation state.

2.1.2 Electrical functionality control

The power supply of the smoke detector must be disconnected by removing the 9-pin Sub-D plug. This causes the smoke detector to send an alarm to the connected fire damper, which will close au-tomatically. The diode on the smoke detector or relay module RM (V4.00) is no longer lit. As soon as the power supply has been restored and the alarm has been acknowledged by pressing the reset but-ton, the smoke detector must return to the ready operating state, and the diode on the smoke de-tector and / or relay module RM (V4.00) must flash green.

2.2 Internal check 2.2.1 Fault control

On the smoke detector RMSII-L, the transmitter and receiver sensors must be covered. The diode on the smoke detector lights up permanently in orange. The fault contact reports a fault. After that, the cover must be removed again. The smoke detector must again return to the ready operating state, and the fault message is reset at the central unit.

2.2.2 Functionality control using test aerosols

A test aerosol must be applied to the smoke detec-tor in the installed state. This must be done by applying the test aerosol to the smoke detector in-creasingly in pulsed form for about 10 sec. If the alarm threshold values are exceeded, an alarm message will be triggered, and the connected fire dampers must close automatically. The diode on the smoke detector or on the relay module RM

(V4.00) must light up in red. After the aerosol components in the surrounding air of the smoke detector have decomposed to such an extent that the value drops again below the alarm threshold value, the alarm message is still displayed on the smoke detector or the relay module RM (V4.00). This is why the smoke detector must be activated again by pressing the reset button. As soon as the diode on the smoke detector type RMSII-L flashes in green again, the smoke detector is ready for operation again.

Elimination of defects If defects have been detected during maintenance, they must be eliminated immediately. Defective components may only be replaced with original parts delivered by SCHAKO KG. Repair of the smoke detector must be carried out only by the appliance manufacturer. If any of the connected fire dampers are not closing, even when the smoke detector operates faultlessly, then the fire dampers themselves must be checked. Inspection instructions The SCHAKO smoke detector type RMSII-L permanently mo-nitors itself and gives an error warning to the central unit if there is a mechanical or electrical defect or if it is too heavily soiled. In case of a power failure of the smoke detector, a fault mes-sage is also sent to the central unit.

Page 29: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation Service

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 29

SAMPLE TEMPLATES

SAMPLE OF FUNCTIONAL TEST PROTOCOL

SCHAKO Ferdinand Schad KG Steigstrasse 25-27 D-78600 Kolbingen Phone: +49- (0)7463 / 980-0 Fax: +49- (0)7463 / 980-200 E-mail: infoschako.de

Web: www.schako.de

Sample Functional test protocol for____________________ Cons. No. ____________________ Usability certificate:

Series:

Release device:

The following function steps have been carried out according to the documents installation, mounting and operating instructions

Prior to com-missioning

Next functional test in test in: _____________

Next functional test in: _____________

Next functional test in: _____________

Next functional test in: _____________

External check:

System: _____________________

Item: _______________________

Internal check:

System: _____________________

Item: _______________________

Additional check:

System: _____________________

Item: _______________________

without defects Date / tester

with defects (see back) Date / tester

without defects Date / tester

Page 30: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation Service

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 30

SCHAKO Ferdinand Schad KG Steigstrasse 25-27 D-78600 Kolbingen Phone: +49- (0)7463 / 980-0 Fax: +49- (0)7463 / 980-200 E-mail: infoschako.de

Web: www.schako.de

Sample Functional test protocol for____________________

Cons. No. ____________________

Defects found during the test on: ________________________________________

Sluggishness due to soiling.

Any remaining mortar must be removed.

Defects found during the test on: ________________________________________

Defects found during the test on: ________________________________________

Defects found during the test on: ________________________________________

Page 31: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation Service

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 31

SAMPLE OF A CERTIFICATE OF CONFORMITY

Certificate of conformity

- Name and address of the company which has manufactured and installed the fire-resistant damper/dampers of special de-

sign

and use (BKA-Ü):

- Construction site or building:

- Date of manufacture:

Hereby we confirm that

- the object(s) of approval have been manufactured and labeled in compliance with all regulations of the general building su-

pervisory certificate no.: Z-6.50-2012 by German Institute for Building Technology (Deutsches Institut für Bautechnik)

of ............................... (and, if relevant, all the regulations of revisions and amendments of ..................................)

and

- the construction products used for manufacturing of the object(s) of approval comply with the regulations

of the general building supervisory approval and they have been labeled as required. This also applies to

the parts of the object(s) of approval for which the certificate contains

accordingly saved definitions.

…………………………………………………………………… ………………………………………………………………………..

(Place, Date) (Company/Signed)

(This certificate has to be submitted to the owner for possible forwarding to the responsible building supervision authority.)

Page 32: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Foreign branch offices

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 32

FOREIGN BRANCH OFFICES

Belgien Dänemark England Frankreich

SCHAKO S.A.R.L. Venti AS LONDON & SOUTH SCHAKO SARL

165, rue des Pommiers Banevaegnet 3 PAUL JONES 16 boulevard de la croix rousse

L-2343 Luxembourg DK-8362 Hornig Index House F-69001 Lyon

Tel. +352 / 403 157 1 Tel. +45 / 86 / 92 22 66 St Georges Lane Tel. +33 / 4 / 783 49734

Fax: +352 / 403 157 66 Fax: +45 / 86 / 92 22 26 Ascot, Berkshire Fax: +33 / 4 / 783 49731

[email protected] [email protected] SL5 7EU [email protected]

www.schako.be www.venti.dk Tel. +44 / 1 / 344 636 389 www.schako.fr

Fax: +44 / 1 / 344 874 658

[email protected]

www.schako.co.uk

Griechenland Israel Italien Kroatien

EUROPERSIS Insupco Industrial Supply Ltd. SCHAKO Italia S.r.l. Intel Trade

Odisea Androutsou 2 40 Hayarkon St. Via XXV Aprile, 17 DrAnte Mandica 10 - Volosko

GR-56224 Evosmos/Tessaloniki Yavne 811 00 I-20097 S. Donato Milanese-MI 51410 Opatija

Tel. +30 / 310 / 685779 Tel. +972 / 8 / 9420080 Tel. +39 / 02 / 51640201 Tel. +385 / 51 / 741 100

Fax: +30 / 310 / 757 613 Fax: +972 / 8 / 9420311 Fax: +39 / 02 / 51620946 Fax: +385 / 51 / 701 470

[email protected] [email protected] [email protected] [email protected]

www.europersis.gr www.insupco.com www.schako.it www.intel-trade.hr

Luxembourg Niederlande Österreich Polen

SCHAKO S.A.R.L. SCHAKO S.A.R.L. SCHAKO Vertriebs GmbH SCHAKO Polska Sp. z o.o

165, rue des Pommiers 165, rue des Pommiers Mariahilfer Str. 103/2/46a ul. Pulawska 38

L-2343 Luxembourg L-2343 Luxembourg A-1060 Wien PL-05-500 Piaseczno

Tel. +352 / 403 157 1 Tel. +352 / 403 157 1 Tel. +43 / 1 / 890 24 62 Tel. +48 / 22 / 7263570

Fax: +352 / 403 157 66 Fax: +352 / 403 157 66 Fax: +43 / 1 / 890 24 62 50 Fax: +48 / 22 / 7263571

[email protected] [email protected] [email protected] [email protected]

www.schako.lu www.schako.lu www.schako.at www.schako.pl

Rumänien Schweden Schweiz Serbien & Montenegro

SCHAKO Klima Luft SRL EXOTHERM AB SCHAKO Suisse SA TERMOMEHANIKA d.o.o.

Str. Elena Caragiani nr.21 Box 60036 Rue Jean-Prouvé 28 Koste Glavinica 2

014212 Bucuresti, SE-21610 Limhamn CH-1762 Givisiez 11000 BEOGRAD

Tel. +40 / 0 / 21 / 232 13 75 Tel. +46 / 40 / 631 61 16 Case Postale Tel. +381 / 11 / 369 99 93

Fax: +40 / 0 / 21 / 232 13 75 Fax: +46 / 40 / 15 60 95 CH-1763 Granges-Paccot Fax: +381 / 11 / 369 09 93

[email protected] [email protected] Tel. +41 / 26 / 460 88 00 [email protected]

www.schako.ro www.exotherm.se Fax: +41 / 26 / 460 88 05 www.termomehanika.rs

[email protected]

www.schako.ch

Page 33: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Foreign branch offices

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 33

Slowakei Spanien Tschechien Türkei

SCHAKO SK s.r.o. SCHAKO IBERIA S.L. SCHAKO s.r.o. EMO-SCHAKO Klima

Vajanského 1955/58 Departamento de Ventas Pred skalkami II. 184/5 Havalandirma

SK-921 01 Piestany Pol. Ind. Río Gállego, CZ - 10600 Praha 10-Zabehlice San. ve Tic. Ltd. Sti.

Tel. +421 / 337 / 741 843 Calle B, nave 3 Tel. +42 / 02 / 727 680 43 Pursaklar Sanayi Sitesi,

Fax: +421 / 337 / 741 843 E-50840 San Mateo de Gállego Fax: +42 / 02 / 727 693 93 Karacaören Mah.1638.Cad. No:98

[email protected] / Zaragoza [email protected] TR-06145 Altindag - Ankara

www.schako.sk Tel. +34 / 976 / 531 999 www.schako.cz Tel. +90 / 312 527 16 05

Fax: +34 / 976 / 690 709 Fax: +90 / 312 527 16 08

[email protected] [email protected]

www.schako.com/sp www.emo-schako.com.tr

Ungarn

SCHAKO Kft.

Tó Park 6

H-2045 Törökbálint

Tel. +36 / 23 / 445670

Fax: +36 / 23 / 445679

[email protected]

www.schako.hu

Page 34: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Indexes: Figures/Tables

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 34

INDEXES: FIGURES/TABLES

List of figures

Figure 1: Dimensions BKA-Ü ......................................... 3

Figure 2: Installation next to each other without gap

"flange-to-flange" in solid walls .................................... 6

Figure 3: Minimum gap size for complete mortar lining

in solid walls .................................................................. 7

Figure 4: Installation with partial mortar lining in solid

walls .............................................................................. 7

Figure 5: Installation next to each other without

clearance "flange-to-flange" in solid ceilings ................ 8

Figure 6: Minimum gap size for complete mortar lining

in solid ceilings .............................................................. 8

Figure 7: Metal posts plus required spare parts ........... 9

Figure 8: Wet installation in lightweight partition wall 9

Figure 9: Wet installation in lightweight partition wall

with reveal .................................................................. 10

Figure 10: Dry installation in lightweight partition wall

.................................................................................... 11

Figure 11: BKA-Ü with mounting frame ER (loose) ..... 12

Figure 12: Metal posts with required spare parts for

BKA-Ü with mounting frame ER (wall thickness = 100

mm) ............................................................................. 12

Figure 13: BKA-Ü with mounting frame and mounted

corner plates (wall thickness = 100 mm) .................... 13

Figure 14: BKA-Ü installed with mounting frame ER

(wall thickness = 100 mm) .......................................... 13

Figure 15: Metal posts with required spare parts for

BKA-Ü with mounting frame ER (wall thickness > 100

mm) ............................................................................. 14

Figure 16: BKA-Ü with mounting frame ER and

mounted corner plates (wall thickness > 100 mm) .... 14

Figure 17: BKA-Ü installed with mounting frame ER

(wall thickness > 100 mm) .......................................... 15

Figure 18: Metal posts plus required spare parts ....... 16

Figure 19: Simple wall panelling and double-board

layers .......................................................................... 16

Figure 20: Metal posts plus required spare parts (fire

wall) ............................................................................ 17

Figure 21: Wall panelling and double-board layers

(after finishing the fire wall - Knauf or Rigips) ............ 17

Figure 22: Wall panelling and double-board layers

(after finishing the fire wall - Promat) ........................ 18

Figure 23: Wall panelling and double-board layers

(during construction of the fire wall - Knauf or Rigips)

.................................................................................... 18

Figure 24: Wall panelling and double-board layers

(during construction of the fire wall - Promat) .......... 19

Figure 25: Metal posts plus required spare parts (shaft

wall) ............................................................................ 20

Figure 26: Wall panelling and double-board layers

(shaft wall) .................................................................. 20

Figure 27: Minimum distances of BKA-Ü .................... 21

Figure 28: Circuit diagram Relay module RM (V4.00) 25

Figure 29: Side view BKA-Ü (spring return actuator) . 27

Figure 30: Front view BKA-Ü (spring return actuator) 27

Page 35: BKA-Ü · PDF file · 2018-02-071 Fire damper BKA-EN (component of BKA-Ü) 2 Assembly part type EBT ... for example, concrete; masonry according to EN 1996 or DIN 1053; ... mortar

Fire-resistant damper model BKA-Ü Technical documentation

Indexes: Figures/Tables

Construction subject to change No return possible Version: 2015-08-17 | Document: 09/20 | Page 35

List of tables

Table 1: Available sizes ................................................. 4

Table 2: Length specifications ....................................... 4

Table 3: Usability .......................................................... 5

Table 4: Free cross-section [m²] ................................. 22

Table 5: Weight table [kg] ........................................... 23

Table 6: Assignment of the actuator types ................. 24

Table 7: Technical data of 24 V spring return actuators

.................................................................................... 24