biotech of food technology

Embed Size (px)

Citation preview

  • 8/20/2019 biotech of food technology

    1/55

    Plumbing Code inCommercial Kitchens

    NH BOA

    May 9, 2012

  • 8/20/2019 biotech of food technology

    2/55

    Main Topics

    • Grease Interceptors

    • Indirect Waste Receptors

    • Cleaning Chemical Dispensers

    • Thermal Expansion

  • 8/20/2019 biotech of food technology

    3/55

    IPC - Chapter 10

    • Traps

    • Interceptors

    • Separators 

  • 8/20/2019 biotech of food technology

    4/55

    Section 1002 Trap Requirements

    • 1002.1 Fixture Traps. Each fixture shall be

    separately trapped by a liquid-seal trap , except as

    otherwise permitted by this code. The verticaldistance from the fixture outlet to the trap weir shall

    not exceed 24 inches, and the horizontal distance

    shall not exceed 30 inches measured from the

    centerline of the fixture outlet to the centerline of

    the inlet of the trap. The height of a clothes washer

    standpipe above trap shall conform to Section 802.4.

    A fixture shall not be double trapped.

  • 8/20/2019 biotech of food technology

    5/55

    Section 1002.1

    Exception #3  –  A grease interceptor intended to serve as a fixture

    trap in accordance with the manufacturer’s installation

    instructions shall be permitted to serve as the trap for a singlefixture or a combination sink of not more than three

    compartments where the vertical distance from the fixture outlet

    to the inlet of the interceptor does not exceed 30 inches and the

    developed length of the waste pipe from the most upstream

    fixture outlet to the inlet of the interceptor does not exceed 60inches.

  • 8/20/2019 biotech of food technology

    6/55

     

    Zurn Light Commercial Series Grease Interceptors #2700 consist of a interceptor rated at ( ) gpm and a properly sized flow control fitting.

  • 8/20/2019 biotech of food technology

    7/55

    1002.2 Design of traps. Fixture traps shall be self-scouring. Fixture traps

    shall not have interior partitions, except where such traps are integral wih

    the fixture or where such traps are constructed of an approved material that

    is resistant to corrosion and degradation.

    1002.3 Prohibited Traps

    6. Drum traps

    Exception: Drum traps used as solids interceptors and drum traps

    serving chemical waste systems shall not be prohibited.

    1002.4 Trap seals. Each fixture trap shall have a liquid seal of not less than

    2 inches and not more than 4 inches or deeper for for special designs relatingto accessible fixtures.

  • 8/20/2019 biotech of food technology

    8/55

  • 8/20/2019 biotech of food technology

    9/55

    1003.1 Where required.

    • Interceptors and separators shall be provided to

    prevent the discharge of oil, grease, sand and

    other substances harmful or hazardous to thebuilding drainage system, the public sewer, the

    private sewage disposal system or the sewage

    treatment plant or processes.

  • 8/20/2019 biotech of food technology

    10/55

    1003.2 Approval.

    • The size, type and location of each interceptor

    and of each separator shall be designed and

    installed in accordance with the manufacturer ’sinstructions and the requirements of this section

    based on the anticipated conditions of use.

    Wastes that do not require treatment or separation

    shall not be discharged into any interceptor or

    separator.

  • 8/20/2019 biotech of food technology

    11/55

    1003.2 Approval.

    • The size, type and location of each interceptor

    and of each separator shall be designed and

    installed in accordance with the manufacturer ’sinstructions and the requirements of this section

    based on the anticipated conditions of use.

    Wastes that do not require treatment or separation

    shall not be discharged into any interceptor or

    separator.

  • 8/20/2019 biotech of food technology

    12/55

    1003.3.1 Grease Interceptors andAutomatic

    Grease Removal Device required. (cont.)

    Fixtures and equipment shall include:

    • pot sinks

    • pre-rinse sinks

    • soup kettles or similar devices

    • wok stations

    • floor drains or sinks into which kettles are drained

    • automatic hood wash units

    • dishwashers without pre-rinse sinks.

  • 8/20/2019 biotech of food technology

    13/55

     

    1003.3.2 Food Waste Grinders

    • Where food waste grinders connect to grease

    interceptors, a solids interceptor shall separate the

    discharge before connecting to the greaseinterceptor. Solids interceptors and grease

    interceptors shall be sized and rated for the

    discharge of the food waste grinder. Emulsifiers,

    chemicals, enzymes and bacteria shall not

    discharge into the food waste grinder .

  • 8/20/2019 biotech of food technology

    14/55

    ZURN LIGHT COMMERCIAL PLUMBING PRODUCTS 2640 South Work Street Falconer, NY 14733

    Phone: 1-800/906-5060 Fax: 716/665-3126 World Wide Web: www.zurn.com

    ®

    Form # JS2 Date: 3/13/09 C.N. No. 99791 Rev. F Page 1 of 2

    GT2700Grease Interceptor Installation & Cleaning Instructions

    INSTALLATION

    1. Zurn Light Commercial Grease Interceptors

    should be installed as close as possible to the

    fixture being served. Always install where thereis easy access for cover removal and cleaning.

    2. A flow control must be installed as close aspossible to the underside of the fixture. The

    flow control must be installed with the vent or (air intake) on the downstream side of the orifice

    plate. The vent connection is positioned to the

    top of the flow control fitting and piped upwardhigher than source of water, or to building vent

    system3. It is recommended that a cleanout tee be

    installed before the flow control to access theflow control orifice and clear debris.

    4. The cleanout plug should be installed over the

    outlet of the interceptor.

    5. The interceptor is to be installed using no-hubcouplings.

    6. Outlet piping should be connected to thesanitary drain, and pipe size should be equal

    to or larger than the inlet piping. Outlet pipeshould also be vented so the interceptor is not

    siphoned.

    7. Solid waste should not go into an interceptor.Food grinder waste and other solids should

    be captured in the sink or by a solids interceptor before reaching the grease interceptor.

    Zurn Light Commercial Series Grease Interceptors #2700 consist of a interceptor rated at

     ( ) gpm and a properly sized flow control fitting.

  • 8/20/2019 biotech of food technology

    15/55

  • 8/20/2019 biotech of food technology

    16/55

  • 8/20/2019 biotech of food technology

    17/55

  • 8/20/2019 biotech of food technology

    18/55

  • 8/20/2019 biotech of food technology

    19/55

  • 8/20/2019 biotech of food technology

    20/55

    In compliance?

  • 8/20/2019 biotech of food technology

    21/55

    1003.3.4.2 Rate of flow controls

    • Grease interceptors shall be equipped with

    devices to control the rate of water flow so that the

    water flow does not exceed the rated flow. Theflow- control device shall be vented and terminate

    not less than 6 inches (152 mm) above the flood

    rim level or be installed in accordance with the

    manufactures instructions.

  • 8/20/2019 biotech of food technology

    22/55

  • 8/20/2019 biotech of food technology

    23/55

    ZURN LIGHT COMMERCIAL PLUMBING PRODUCTS 2640 South Work Street Falconer, NY 14733

    Phone: 1-800/906-5060 Fax: 716/665-3126 World Wide Web: www.zurn.com

    ®

    Form # JS2 Date: 3/13/09 C.N. No. 99791 Rev. F Page 1 of 2

    GT2700Grease Interceptor Installation & Cleaning Instructions

    INSTALLATION

    1. Zurn Light Commercial Grease Interceptors

    should be installed as close as possible to the

    fixture being served. Always install where thereis easy access for cover removal and cleaning.

    2. A flow control must be installed as close aspossible to the underside of the fixture. The

    flow control must be installed with the vent or (air intake) on the downstream side of the orifice

    plate. The vent connection is positioned to the

    top of the flow control fitting and piped upwardhigher than source of water, or to building vent

    system3. It is recommended that a cleanout tee be

    installed before the flow control to access theflow control orifice and clear debris.

    4. The cleanout plug should be installed over theoutlet of the interceptor.

    5. The interceptor is to be installed using no-hubcouplings.

    6. Outlet piping should be connected to thesanitary drain, and pipe size should be equal

    to or larger than the inlet piping. Outlet pipeshould also be vented so the interceptor is not

    siphoned.

    7. Solid waste should not go into an interceptor.Food grinder waste and other solids should

    be captured in the sink or by a solids interceptor before reaching the grease interceptor.

    Zurn Light Commercial Series Grease Interceptors #2700 consist of a interceptor rated at ( ) gpm and a properly sized flow control fitting.

  • 8/20/2019 biotech of food technology

    24/55

    1003.3.3 Grease interceptors and automatic

    grease removal devices not required.

    •  A Grease interceptor or an automatic grease

    removal device shall not be required for individual

    dwelling units or any private living quarters.

  • 8/20/2019 biotech of food technology

    25/55

    Chapter 8

    • Indirect/Special Waste

  • 8/20/2019 biotech of food technology

    26/55

    802.1 Where Required. 

    • Food-handling equipment and clear-water waste

    shall discharge through an indirect waste pipe as

    specified in Sections 802.1.1 through 802.1.8.

  • 8/20/2019 biotech of food technology

    27/55

    Section 802.1.1 Food Handling.

    • Equipment and fixtures utilized for the storage,

    preparation and handling of food shall discharge

    through an indirect waste pipe by means of an airgap.

  • 8/20/2019 biotech of food technology

    28/55

    802.2.1 Air gap.

    • The air gap between the indirect waste pipe and the

    flood level rim of the waste receptor shall be a

    minimum of twice the effective opening of the indirect

    waste pipe.

    • Chapter 2 Definitions:

    • Air Gap (Drainage System): The unobstructed vertical

    distance through the free atmosphere between the outlet

    of the waster pipe and the flood level rim of the receptacleinto which the waste pipe is discharging.

    • Floor Level Rim: The edge of the receptacle from which

    water overflows.

  • 8/20/2019 biotech of food technology

    29/55

  • 8/20/2019 biotech of food technology

    30/55

    2 x D

    Waste

    Receptor

  • 8/20/2019 biotech of food technology

    31/55

    802.3 Waste Receptors.

    • Every waste receptor shall be of an approved

    type. A removable strainer or basket shall cover

    the waste outlet of waste receptors. Wastereceptors shall be installed in ventilated spaces.

    Waste receptors shall not be installed in

    bathrooms or toilet rooms or in any inaccessible or

    unventilated space such as a closet or storeroom.

    Ready access shall be provided to wastereceptors.

  • 8/20/2019 biotech of food technology

    32/55

    802.3.1 Size of Receptors.

    •  A waste receptor shall be sized for the maximum

    discharge of all indirect waste pipes served by the

    receptor. Receptors shall be installed to preventsplashing or flooding.

  • 8/20/2019 biotech of food technology

    33/55

    802.3.2 Open hub waste receptors.

    • Waste receptors shall be permitted in the form of a

    hub or pipe extending not less than 1 inch (25.4

    mm) above a water-impervious floor and are notrequired to have a strainer.

  • 8/20/2019 biotech of food technology

    34/55

    The 3 Bay Sink  

  • 8/20/2019 biotech of food technology

    35/55

  • 8/20/2019 biotech of food technology

    36/55

  • 8/20/2019 biotech of food technology

    37/55

  • 8/20/2019 biotech of food technology

    38/55

  • 8/20/2019 biotech of food technology

    39/55

  • 8/20/2019 biotech of food technology

    40/55

    802 1 8 F d Ut il Di h P t d

  • 8/20/2019 biotech of food technology

    41/55

     802.1.8 Food Utensils, Dishes, Pots and

    Pan Sinks

    • Sinks used for the washing, rinsing or sanitizing of

    utensils, dishes, pots, pans, or service ware used in

    the preparation, servicing or eating of food shall

    discharge indirectly through an air gap or an air breakor directly connect to the drainage system.

  • 8/20/2019 biotech of food technology

    42/55

  • 8/20/2019 biotech of food technology

    43/55

    WASH RINSE SANITIZE WITH GREASE

  • 8/20/2019 biotech of food technology

    44/55

    WASH RINSE SANITIZE WITH GREASE

    INTERCEPTION, DIRECTLY

    CONNECTED 

  • 8/20/2019 biotech of food technology

    45/55

    Wash, rinse and sanitize with grease interception,

    indirectly connected using an approved waste receptor

  • 8/20/2019 biotech of food technology

    46/55

    CHEMICAL DISPENSERS

    AT THE MOP SINK  

  • 8/20/2019 biotech of food technology

    47/55

  • 8/20/2019 biotech of food technology

    48/55

  • 8/20/2019 biotech of food technology

    49/55

  • 8/20/2019 biotech of food technology

    50/55

  • 8/20/2019 biotech of food technology

    51/55

  • 8/20/2019 biotech of food technology

    52/55

  • 8/20/2019 biotech of food technology

    53/55

  • 8/20/2019 biotech of food technology

    54/55

    Expansion Tanks Required?

    Section 607 Hot Water Supply System

    607.3 Thermal expansion control. A means of controlling increased pressure

    caused by thermal expansion shall be provided where required in accordance with

    Sections 607.3.1 and 607.3.2.

    607.3.1 Pressure-reducing valve. For water service system sizes up to and

    including 2 inches, a device for controlling pressure shall be installed where, because of thermal expansion, the pressure on the downstream side of a

    pressure-reducing valve exceeds the pressure – reducing valve setting.

    607.3.1. Backflow prevention device or check valve. Where a backflow

    prevention device, check valve or other device is installed on a water supply

    system utilizing storage water heating equipment such that thermal expansioncauses an increase in pressure, a device for controlling pressure shall be

    installed.

    IRC – P2903.4

    Pl bi S f & Li i

  • 8/20/2019 biotech of food technology

    55/55

    Plumbing Safety & Licensing

    Inspectors

    • Ron Lemere 603-223-4289 Ext. 25269

    [email protected];

    Sam Zannini Jr. 603 223-4289 Ext. 25271• [email protected];

    • Earl Middlemiss 603-223-4289 Ext. 25270

    [email protected] 

    • Contact Jeff Cyr 603-223-4289 Ext. 25241

    [email protected];

    mailto:[email protected]:[email protected]