RVM/U-L2 Module BASICSFlow Monitor
Operating Instructions
Series RVM/U-L2Typ RVM/U-L20010 thru RVM/U-20525
Read the instructions prior to performing any task!
RVM/U-L2 Module BASICS, 1, en_US
© Meister Strömungstechnik GmbH 2014
Meister Strömungstechnik GmbH
Im Gewerbegebiet 2
63831 Wiesen
Germany
Telephone: +49 6096 9720 - 0
Fax: +49 6096 9720 - 30
Email: [email protected]
Internet: www.meister-flow.com
These instructions were compiled by:
Meister Strömungstechnik GmbH
Subject to change without notice
19.02.2016RVM/U-L2 Module BASICS Flow Monitor2
These instructions facilitate the safeand efficient handling of a flow monitor(referred to as "device" in the fol-lowing). The instructions are an inte-gral part of the device and must bekept within easy reach for the per-sonnel in the immediate vicinity of thedevice at all times. Personnel mustcarefully read and understand theseinstructions before commencing allwork. The basic requirement for safework is adherence to all safety andhandling instructions stipulated inthese instructions. The local accident-prevention regulations and generalsafety standards and regulations forthe field of application of the devicealso apply. Illustrations in theseinstructions are provided to aid generalunderstanding and might deviate fromthe actual model. No claims can bederived from any such differences.
Limitations of liability
All details and instructions in thismanual have been compiled underconsideration of the valid standardsand regulations, the current state-of-technology and our many years ofknowledge and experience. The manu-facturer does not accept any liabilityarising from:
n non-observance of any details inthese instructions
n improper use of the device, or usethat is not in accordance withthese instructions
n use of non-trained personnel
n unauthorized retrofitting or tech-nical changes that have not beenauthorized by the manufacturer
n use of non-approved spare parts
The duties and obligations agreedupon in the delivery contract apply infull, as well as the general terms andconditions, the terms of delivery by themanufacturer and the valid legal regu-lations applicable at the conclusion ofthe contract.
Copyright
These operating instructions are pro-tected by copyright.
Except for internal purposes, transferof these instructions to third-parties,copying them in any way– even in part – as well as dissemina-tion and/or communication of their con-tent is forbidden without prior writtenauthorization from Meister Strömung-stechnik ("manufacturer"). Violationsare subject to claims for indemnifica-tion. The manufacturer reserves theright to assert additional claims.
Copyright is the property of the manu-facturer.
© Meister Strömungstechnik GmbH
Im Gewerbegebiet 2
63831 Wiesen
Germany
Supplemental instructions
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 3
Table of contents1 Overview...................................................................................................... 7
1.1 Short description.................................................................................. 71.2 Warranty and guarantee provisions..................................................... 71.3 Customer service................................................................................. 7
2 Safety........................................................................................................... 82.1 Explanation of symbols........................................................................ 82.2 Correct use in accordance with these instructions............................. 102.3 Special precautions............................................................................ 112.3.1 Hazards from electrical current....................................................... 112.3.2 Mechanical hazards........................................................................ 122.3.3 Hazards from high or low temperatures.......................................... 132.3.4 Radiation hazards........................................................................... 132.3.5 Hazards caused by media............................................................... 142.4 Personnel requirements..................................................................... 142.5 Personal safety equipment................................................................. 152.6 Protective systems............................................................................. 162.7 Replacement parts............................................................................. 162.8 Environmental protection................................................................... 172.9 Responsibility of the owner................................................................ 17
3 Design and function................................................................................. 203.1 Overview............................................................................................ 203.2 Device description.............................................................................. 203.3 Component description...................................................................... 21
4 Transport, packaging and storage.......................................................... 224.1 Safety instructions for transport......................................................... 224.2 Transport inspection........................................................................... 224.3 Packaging.......................................................................................... 224.4 Symbols on the shipping box............................................................. 234.5 Storage............................................................................................... 23
5 Installation and initial startup.................................................................. 255.1 Safety................................................................................................. 25
Table of contents
19.02.2016RVM/U-L2 Module BASICS Flow Monitor4
5.2 Requirements at the place of installation........................................... 255.3 Preparatory work................................................................................ 265.4 Installation in the pipe system............................................................ 295.5 Initial startup....................................................................................... 335.6 Electrical connection.......................................................................... 345.6.1 Switch contact SG-15 with connector in compliance with
EN175301-803................................................................................ 345.6.2 Plug connector M12x1.................................................................... 355.6.3 Cable............................................................................................... 365.6.4 Degree of protection (IP-Code)....................................................... 375.7 Grounding the device......................................................................... 375.8 Plug connection.................................................................................. 375.9 Contact protection measures............................................................. 39
6 Operation................................................................................................... 426.1 Switch point adjustment..................................................................... 426.2 Checking the flow............................................................................... 44
7 Troubleshooting....................................................................................... 457.1 Safety................................................................................................. 457.2 Troubleshooting guide........................................................................ 47
8 Maintenance.............................................................................................. 498.1 Safety................................................................................................. 498.2 Maintenance plan............................................................................... 498.3 Removal from the pipe system........................................................... 508.4 Disassembly....................................................................................... 518.5 Maintenance....................................................................................... 548.5.1 Cleaning.......................................................................................... 548.5.2 Parts replacement........................................................................... 568.5.3 Assembly......................................................................................... 568.5.4 Switch contact replacement............................................................ 588.6 Measures to be taken after maintenance work.................................. 60
9 Disassembly and disposal....................................................................... 619.1 Safety................................................................................................. 619.2 Disassembly....................................................................................... 61
Table of contents
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 5
9.3 Return Materials................................................................................. 629.3.1 Return Materials Authorization........................................................ 629.4 Disposal............................................................................................. 62
10 Technical data........................................................................................... 6310.1 Device data plate............................................................................. 6310.2 Switch contact data plate................................................................. 6310.3 Dimension sheet.............................................................................. 6410.4 General specifications...................................................................... 6510.5 Electrical specifications.................................................................... 6610.6 Measuring ranges............................................................................ 6810.6.1 Standard measuring ranges.......................................................... 6810.7 Operating data................................................................................. 68
11 Appendix................................................................................................... 7011.1 Tightening torque............................................................................. 7011.2 Replacement parts........................................................................... 7011.3 Tools................................................................................................ 7211.4 Sealant............................................................................................. 7211.5 Lubricants......................................................................................... 73
12 Index.......................................................................................................... 74
Table of contents
19.02.2016RVM/U-L2 Module BASICS Flow Monitor6
1 Overview1.1 Short description
Fig. 1: RVM/U-L2 flow monitor
1 Switchpoint adjustment scale2 Switch contact with female socket
or sealed-in cable
The flow monitor RVM/U-L2 monitorsthe continuous flow of gaseous media.It is designed for installation in pipesystems.
A float inside the device is moved bythe medium flowing through it. Thedesired switch point can be set on theswitchpoint adjustment scale, wherebythe arrow on the switch contact isaligned to the desired volume flowvalue on the switchpoint adjustmentscale.
External measuring devices can beconnected at the socket.
1.2 Warranty and guar-antee provisions
Warranty and guarantee provisions arecontained in the general terms andconditions of the manufacturer.
1.3 Customer serviceFor technical information, please con-tact our customer service department(for contact details, see Page 2).
Furthermore, our staff is always inter-ested in receiving new information andexperiences gained from application ofthe device, which may be useful inimproving our products.
OverviewCustomer service
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 7
2 SafetyThis chapter provides an overview ofimportant safety aspects required foroptimum protection of personnel aswell as for safe installation and safeoperation of the device.
Non-observance of the handling andsafety instructions listed in this manualmay result in hazardous/dangerousconditions and in damage to property.
2.1 Explanation of sym-bols
Safety instructions
Safety instructions in this manual aremarked by symbols. The safety instruc-tions are preceeded by signal wordsthat indicate the level of danger/hazard.
To prevent accidents or injury to per-sons as well as damage to property,always observe the safety instructionsand proceed carefully.
DANGER!
This combination of symbol andsignal word indicates an imme-diate, dangerous condition thatresults in death or serious injury ifit is not avoided.
WARNING!
This combination of symbol andsignal word indicates a possiblydangerous condition that mightresult in death or serious injury if itis not avoided.
SafetyExplanation of symbols
19.02.2016RVM/U-L2 Module BASICS Flow Monitor8
CAUTION!
This combination of symbol andsignal word indicates a possiblydangerous condition that mightresult in minor or slight injury if it isnot avoided.
NOTICE!
This combination of symbol andsignal word indicates a possiblydangerous condition that mightresult in damage to property and tothe environment if it is not avoided.
Tips and recommendations
This symbol emphasizes usefultips and recommendations as wellas information for efficient andfailure-free operation.
Signs used in these instructions
The following signs and highlightingare used in these instructions to iden-tify handling instructions, the descrip-tion of results, lists/enumerations, ref-erences and other elements:
Designates step-by-step han-dling instructions
ð Designates a state or anautomatic sequence as aresult of a specific operatingstep
n Designates randomly ordered enu-merations and list entries
Ä “Signs used in these instructions”on page 9, designates references tochapters in these instructions
SafetyExplanation of symbols
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 9
2.2 Correct use inaccordance withthese instructions
The device is designed and con-structed exclusively for the intendeduse described herein.
Correct use in non-hazard areas
The flow monitor serves exclusivelyto monitor the continuous flow ofgaseous media within a temperaturerange of -20 °C to 120 °C (optional:160 °C) at a maximum operatingpressure of 300 bar (brass version)and 350 bar (stainless steel version).
Correct use in explosion-hazard zones
For employment in explosion-hazardzones, changed conditions apply forthe intended use.
The intended use in explosion-hazardzones is described in the OperatingInstructions for "RVM/U-L2 ModuleATEX".
Intended use in explosion-hazardzones includes the observance of allspecifications in these OperatingInstructions, as well as those for "RVM/U-L2 Module ATEX ".
Any additional or different application,above and beyond the correct use inaccordance with these instructions, isdeemed as incorrect use.
WARNING!
Danger due to incorrect use!Incorrect use of the flow monitormay result in dangerous condi-tions.
– Use the flow monitor onlywithin the stipulated perform-ance limits
– Do not subject the flow mon-itor to severe temperature fluc-tuations
– Do not use the flow monitorwith quick acting valves
– Do not use the flow monitorwith solenoid valves
– Do not subject the flow mon-itor to vibrations
– Do not subject the flow mon-itor to pressure surges
– Do not use the flow monitorwith media containing solids orabrasives
– Only use the flow monitor withmedia previously approved bythe manufacturer
– Do not use the flow monitor asthe sole monitoring device toprevent dangerous conditions
– Do not install the flow monitoras a load bearing part within apipeline system
– The flow monitor must beinstalled so that it is protectedfrom damage by mechanicalforce. If necessary, install anappropriate impact protectiondevice.
SafetyCorrect use in accordance with these instructions
19.02.2016RVM/U-L2 Module BASICS Flow Monitor10
All claims for damages due to incorrectuse are excluded.
2.3 Special precautionsThe following section lists residualrisks that might arise from the device.
To reduce health risks and preventdangerous conditions, observe thesafety instructions listed here as wellas the safety instruction in the otherchapters of these Operating Instruc-tions.
DANGER!
Employment of the device inexplosion-hazard zonesrequires the observance of theOperating Instructions for"RVM/U-L2 Module ATEX"including all hazard statementsand warnings, therein.
These Operating Instructionscannot cover all conceivable dan-gers because many dangers arise,not from the device itself, but fromthe respective media flowingthrough it. Always observe theappropriate safety data sheetswhen using hazardous media!
2.3.1 Hazards from elec-trical current
Electrical current
DANGER!
Danger to life from electricalcurrent!There is an immediate risk to lifefrom electrocution on touching liveparts. Damaged electrical insula-tion or components can beextremely dangerous.
– Only qualified electriciansshall work on the electricalsystem.
– If the insulation is damaged,immediately switch off andhave repairs performed.
– Before commencing work onlive parts of the electrical sys-tems and operating equip-ment, disconnect the equip-ment and ensure that itremains disconnected for theduration of the work. Observethese 5 safety rules whendoing so:– Isolate (disconnect)– Secure against switching
back on– Check for absence of
voltage– Ground and short– Cover or cordon off other
live parts in the vicinity
SafetySpecial precautions > Hazards from electrical current
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 11
– Never bridge fuses or putthem out of operation. Alwaysobserve the correct currentratings when replacing fuses
– Keep moisture away from liveparts. This can result in short-circuit
2.3.2 Mechanical hazards
WARNING!
Risk of injury due to fracturedhousing and leakage!Unauthorized temperatures orexcessive pressure may cause theflow monitor body or the processconnections to burst. Injury may becaused by flying debris andescaping media.
– Keep within the stipulatedoperating limits
– Wear personal protectiveequipment
– Avoid severe temperature fluc-tuations
– Avoid pressure surges
CAUTION!
Risk of injury on sharp edgesand pointed corners!Sharp edges and pointed cornerscan cause abrasions and skincuts.
– Proceed with caution whenworking near sharp edges andpointed corners
– If in doubt, wear protectivegloves
SafetySpecial precautions > Mechanical hazards
19.02.2016RVM/U-L2 Module BASICS Flow Monitor12
2.3.3 Hazards from highor low temperatures
Hot or cold surfaces
WARNING!
Risk of injury from hot or coldsurfaces!Surfaces of components may heatup/cool down dramatically due tothe media flowing through them.Skin contact with hot or cold sur-faces may cause severe skin burnor frostbite.
– Always wear temperature-resistant protective workclothing and protective gloveswhen working near hot/coldsurfaces
– Before commencing work,make sure that all surfaceshave been cooled down orwarmed up to ambient temper-ature
2.3.4 Radiation hazardsStrong magnetic fields
WARNING!
Danger to life from strong mag-netic fields!Strong magnetic fields may causesevere injury or even be fatal, aswell as cause considerabledamage to property.
– Persons with pacemakersmust not be located in thevicinity of the device. Thiscould impair the function of thepacemaker
– Persons with metal implantsmust not be located in thevicinity of the device. Implantscan heat up or be attractedmagnetically
– Keep ferromagnetic materialsand electromagnets awayfrom the magnetic source.These materials could beattracted and fly through theroom, thereby injuring or evenkilling persons. Minimumclearance: 3 m
– Remove and put away metalobjects before maintenancework (jewelry, watches, writingimplements, etc.)
– Do not place any electronicdevices within the vicinity ofthe magnetic source. Thesecould be damaged
SafetySpecial precautions > Radiation hazards
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 13
– Do not place any electronicstorage media, credit cards,etc. within the vicinity of themagnetic source. Data couldbe deleted
2.3.5 Hazards caused bymedia
Hazardous media
WARNING!
Risk of injury from hazardousmedia!If the flow monitor is used for toxic,corrosive or very hot/cold media,there is a risk of serious injury fromescaping media.
– Observe details in the safetydata sheet of the media
– Comply with the safety, acci-dent prevention and environ-mental protection regulationsappropriate to the media used
– Wear personal protectiveequipment in accordance withthe safety data sheet
2.4 Personnel require-ments
WARNING!
Risk of injury due to insuffi-ciently trained and qualified per-sonnel!If unqualified personnel work onthe device or are located within itshazard zone, dangers arise whichmay result in serious injury andconsiderable damage to property.
– All work must be performed byqualified personnel only.
– Keep unqualified personnelaway from hazard zones.
Authorized personnel is to be restrictedto those persons who can be expectedto perform their work reliably. Personswhose ability to respond is influenced,e.g. by drugs, alcohol or medication,are not authorized.
Observe the age and occupational reg-ulations at the site when choosing per-sonnel.
SafetyPersonnel requirements
19.02.2016RVM/U-L2 Module BASICS Flow Monitor14
The following lists the personnel quali-fications for the various areas ofactivity:
Qualified electricianDue to specialized training, knowledgeand experience as well as knowledgeof the relevant standards and regula-tions, the qualified electrician is able toindependently perform work on theelectrical systems as well as to detectand avoid possible risks and dangers.
Additionally, the electrician must pro-vide proof of his/her professional quali-fication that certifies his/her ability toperform work on electrical systems.
The qualified electrician must fulfill therequirements contained in the validlegal accident-prevention regulations.
Qualified personnelDue to their specialized training, knowl-edge and experience as well as theirknowledge of the relevant standardsand regulations, qualified personnelare able to independently perform thework assigned to them as well as todetect and avoid possible risks anddangers.
2.5 Personal safetyequipment
Personal safety equipment is used toprotect personnel from hazards/dan-gers that might impair their safety orhealth during work.
When performing the various tasks at,and with the device, personnel mustwear personal safety equipment. Spe-cial reference is made of this in theindividual chapters within these Oper-ating Instructions. The following pro-vides a description of the personalsafety equipment:
n Always wear appropriate personalsafety equipment required in thevarious chapters of these Oper-ating Instructions before com-mencing work.
n Comply with the personal safetyequipment instructions postedwithin the work area.
Description of personal safetyequipment
Goggles
The goggles are used to protect theeyes from flying debris and splashingfluid.
Protective gloves
SafetyPersonal safety equipment
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 15
Protective gloves protect the handsfrom friction, burns, grazing, abrasion,surface cuts or deeper injuries, as wellas from direct contact with hot or coldsurfaces.
With hazardous media, the protec-tive equipment specified in theSafety Data Sheet of the mediummust be worn. In addition, the speci-fications of the system operatormust be followed. If no protectiveequipment is specified, suitable pro-tective gloves and goggles must beworn.The protective equipment is used toprotect against hazardous media leaksand hazardous media residue in thedevice.
2.6 Protective systemsIntegration within an emergency-stop concept is required
The device is designed for use as apart of a machine or system. It doesnot have its own controller and doesnot have an autonomous emergency-stop function.
Before starting up the device, installthe emergency-stop equipment andincorporate it into the safety chain ofthe machine or system.
Connect the emergency-stop equip-ment so that if there is an interruptionin the power supply or in the activationof the power supply after an interrup-tion, dangerous conditions areexcluded for persons and valuables.
The emergency-stop equipment mustalways be freely accessible.
2.7 Replacement parts
WARNING!
Risk of injury due to use ofincorrect replacement parts!Use of incorrect or faulty replace-ment parts may result in dangersto personnel as well as damages,malfunctions or total failure.
– Only use original replacementparts from the manufacturer orapproved by the manufacturer.
– Always contact the manufac-turer in case of doubt.
SafetyReplacement parts
19.02.2016RVM/U-L2 Module BASICS Flow Monitor16
Always purchase replacement partsfrom an authorized dealer or directlyfrom the manufacturer (For contactdetails, see Page 2).
The replacement parts list is in theannex.
2.8 Environmental pro-tection
NOTICE!
Risk to the environment due toimproper handling of environ-mentally hazardous substances!Serious environmental damagemay result if substances harmful tothe environment are handled incor-rectly, especially if they are dis-posed of improperly.
– Always observe the instruc-tions listed below on the han-dling and disposal of sub-stances harmful to theenvironment.
– If harmful substances arereleased into the environment,take immediate countermeas-ures. If there is doubt, contactthe local authorities, informthem of the damage andrequest information on suit-able countermeasures to betaken.
Cleaning fluids
Solvent-based cleaning fluids containtoxic substances. They must never bereleased into the environment andmust be disposed of by a waste man-agement company.
Lubricants
Lubricants such as greases and oilscontain toxic substances. They mustnever be released into the environmentand must be disposed of by a wastemanagement company.
2.9 Responsibility of theowner
Owner
The owner is the person who operatesthe device himself for business or com-mercial purposes or who cedes suchuse/application to a third-party andwho, during operation of the device,has full legal product stewardship forprotection of the user, the personnel orthird-parties.
Duties of the owner
The device is used in the commercialsector. The owner of the device istherefore subject to legal obligationspertaining to work safety.
SafetyResponsibility of the owner
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 17
In addition to the safety instructionscontained in these Operating Instruc-tions, the safety, accident preventionand environmental protection regula-tions applicable to the field of applica-tion of the device must be observed.
In particular, this includes:
n The owner must inform himselfregarding the valid health andsafety regulations and must per-form a risk assessment to addition-ally determine the risks resultingfrom the special work conditionsarising at the location at which thedevice is used, especially in regardto the media used. He must thenimplement these within OperatingInstructions for use of the device.
n The "Occupational Health andSafety Act" of 1970 stipulates thatit is the duty of the owner to pro-vide a safe workplace. He musthereby ensure that the device isoperated and maintained com-pliant to valid commercial, indus-trial, local, federal and state laws,standards and regulations.
n Appropriate to the working condi-tions and the media used, theowner must affix signs within theworking area that inform the userof the hazards and dangerspresent.
n During the entire period of use ofthe device, the owner must checkperiodically to ensure that theOperating Instructions correspondto the current state of regulations,and he must make adjustments asnecessary.
n The owner must clearly regulateand determine responsibilities forinstallation, operation, trouble-shooting, maintenance andcleaning.
n The owner must fit/retrofit suitablesafety equipment within the com-plete plant/system.
n The owner must ensure that allstaff/personnel have thoroughlyread and understand these instruc-tions before handling the device.Additionally, he must train the per-sonnel at regular intervals andwarn them of dangers.
n The owner must provide the per-sonnel with the required safetyequipment and must instruct themthat its wear is mandatory.
Additionally, the owner is responsiblefor ensuring that the device is alwayskept in a technically perfect condition.The following therefore applies:
n The owner must implement suit-able safety measures, appropriateto the media used.
n Different media have differentseverities of influence on thesoiling and wear of/to the device.The owner must set suitable main-tenance intervals, depending onthe media flowing through thedevice.
SafetyResponsibility of the owner
19.02.2016RVM/U-L2 Module BASICS Flow Monitor18
n The owner must ensure that themaintenance intervals described inthese Operating Instructions areadhered to at all times.
n The owner must ensure that thedevice is completely free of allresidual media before disposal.Remains of corrosive or toxicmaterials must be neutralized.
SafetyResponsibility of the owner
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 19
3 Design and function3.1 Overview
Fig. 2: Overview
1 Device housing2 Switch contact and female socket
or switch contact with cable3 Switch point adjustment scale
3.2 Device descriptionRVM/U-L2 flow monitors workaccording to the functional principle ofthe variable area flow meter. The flowmonitor is installed into a pipe systemand measures the flow rate of themedium flowing through the pipesystem.
A float inside the flow monitor is movedby the flowing medium. A magneticfield is generated by the magnetsinside the float. The position of the floatis detected by a switch contact. Thedesired switch point can be set on theswitch point adjustment scale bymoving the switch contact.
Applications for RVM/U-L2 flow moni-tors are, for example, supply circuitstransporting gaseous media. Thedevice monitors the volume flow of thesupply medium to ensure proper oper-ation. If the flow drops below thethreshold preset by the operator, theswitch contact (change-over contact)switches or opens (normally open con-tact).
Design and functionDevice description
19.02.2016RVM/U-L2 Module BASICS Flow Monitor20
3.3 Component descrip-tion
Switch contact
Fig. 3: Switch contact and femalesocket
A potential-free Reed contact is castinto the switch contact ( Fig. 3/1). Thedevice is supplied with a connector (Fig. 3/2).
Switch point adjustment scale
Fig. 4: Switch point adjustment scale
A scale is applied to the device body,to which the desired switch point canbe adjusted.
Design and functionComponent description
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 21
4 Transport, packaging and storage4.1 Safety instructions
for transport
Improper transport
NOTICE!
The device could be damaged iftransported improperly!Objects to be transported may fallor overturn if transported improp-erly. This may result in damage tothe device and/or property.
– Proceed carefully whenunloading transported pack-ages, both on delivery andwhen transporting in-house.Observe the symbols andinstructions on the shippingbox
– Remove packaging materialjust prior to assembly
4.2 Transport inspec-tion
On delivery, make an immediate checkfor completeness and check for trans-port damages.
If there are any visible external trans-port damages, proceed as follows:
n Do not accept the deliveryn Note the damage in the shipping
documents or on the delivery noteof the transporter and have thedriver confirm by signature
n Initiate a claim for damages
Make a claim for each fault assoon as it is detected. Claims fordamages can only be invokedwithin the valid claim periods.
4.3 PackagingAbout packaging
The packaging serves to protect theindividual components from transportdamages, corrosion and other dam-ages until they are installed. Do notdiscard the packaging and only removethe device from the shipping boximmediately before installation.
Transport, packaging and storagePackaging
19.02.2016RVM/U-L2 Module BASICS Flow Monitor22
Handling packaging materials
Dispose of packaging material inaccordance with the valid legal regula-tions and local ordinances.
NOTICE!
Danger to the environment dueto incorrect disposal!Packaging is made of valuable rawmaterials and can be reused inmany cases or usefully processedand recycled. Improper disposal ofpackaging materials may pose adanger to the environment.
– Dispose of packaging materialin an environmentally safemanner
– Comply with the local disposalregulations. If necessary, havethe packaging disposed of byapproved specialists.
4.4 Symbols on theshipping box
Top
The arrows indicate the top side of thepackage. They must always pointupwards, otherwise the content may bedamaged.
Fragile
Designates packages with breakableor damageable contents.
Handle the package carefully and donot allow it to fall or be subjected to jar-ring or severe vibration.
4.5 StorageStoring the packages
Store the packages under the followingconditions:
n Do not store in the openn Store dry and dust-freen Do not subject to any aggressive
median Protect from direct sunlightn Avoid mechanical vibrations and
shocksn Storage temperature: 0 to 35 °Cn Relative humidity: max. 60 %n Do not stackn If storing for longer than 3 months,
regularly check the general condi-tion of all parts as well as of thepackaging.
Transport, packaging and storageStorage
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 23
Storage instructions in addition tothe instructions listed here may belisted on the packages. Followthese instructions also.
Transport, packaging and storageStorage
19.02.2016RVM/U-L2 Module BASICS Flow Monitor24
5 Installation and initial startup5.1 SafetyIncorrect installation and initialstartup
WARNING!
Risk of injury due to incorrectinstallation and initial startup!Incorrect installation and initialstartup may result in severe injuryand considerable damage to prop-erty.
– Ensure that the site is suffi-ciently cleared of obstructionsbefore commencing work
– Handle open or sharp edgedcomponents carefully
– Ensure that the assemblylocation is orderly and clean!Parts and tools lying about oron top of each other arepotential causes for accidents
– Assemble components prop-erly. Observe the stipulatedtightening torque of screws
– Before initial startup, makesure that all installation workhas been performed and com-pleted in compliance with thespecifications and instructionsin these Operating Instructions
Safeguard against restart
WARNING!
Danger to life due to unauthor-ized restart!There is a risk of severe or evenfatal injury due to unauthorizedrestart of the power supply duringinstallation.
– Before commencing work,switch off the power supply tothe entire system/plant andsecure against restart
5.2 Requirements at theplace of installation
The place of installation must meet thefollowing requirements
n The device must not be underwater.
n The surrounding area must be suf-ficiently illuminated.
n There must be sufficient space toprevent accumulation of trappedheat.
n The device must not be installedas a supporting part in a pipe con-struction.
n The device may not have anythingaffixed to, or suspended from it.
Installation and initial startupRequirements at the place of installation
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 25
n The flow monitor must be installedin such a way as to precludedamage by outside force. It mustbe ensured that the flow monitorcannot be damaged. If necessary,install an appropriate impact pro-tection device.
n External magnetic fields will influ-ence the switch contact. Keep suf-ficient distance to magnetic fields(e.g. electric motors).
n Piping, process connections orsupports made from ferromagneticmaterial influence the magneticfield of the device. Keep a spaceof minimum 100mm to those mate-rials (e.g. steel).
5.3 Preparatory workThe following criteria must be metduring installation to ensure correctfunctioning of the flow monitor:
WARNING!
Danger due to incorrect installa-tion!If the criteria listed above are notmet when installing the flow mon-itor, dangerous/hazardous condi-tions may arise.
– Do not install the flow monitoras a load bearing part in apipe system
– Do not use the flow monitorwith quick-acting valves
– Do not use the flow monitorwith solenoid valves
Installation position/direction offlow
Fig. 5: Installation position/direction offlow
Installation and initial startupPreparatory work
19.02.2016RVM/U-L2 Module BASICS Flow Monitor26
Only install the flow monitor in one ofthe positions displayed in the drawing.The medium must flow in the directionof the arrow (from a low to a high scalevalue).
Unimpeded flow sections
NOTICE!
Measuring inaccuracy due toincorrect installation!The measuring accuracy of theflow monitor is influenced by itsposition within the pipe system.Changes in cross-section, branch-offs or bends in the pipe systemimpair measuring accuracy.
– Ensure that the unimpededflow sections are maintained
– Never reduce the pipe diam-eter immediately before thedevice
We recommend Type BS-228unimpeded flow sections.
Installation and initial startupPreparatory work
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 27
Fig. 6: Unimpeded flow sections
1 10x DN2 5x DN
n There must be an unimpeded flowsection of 10xDN (rated width)before the device.
n There must be an unimpeded flowsection of 5xDN (rated width) afterthe device.
Unimpeded outlet
If the pipe system ends at an unim-peded outlet, the flow monitor must notbe installed directly in front of theopening. The device must always becompletely filled with media to ensuremeasuring accuracy.
Strainer
Fig. 7: Strainer
1 min. 10x DN2 min. 5x DN
If the medium is contaminated bysolids, a strainer must be installedbefore the device ( Fig. 7).
We recommend a Type SF, SFDor SFM strainer.
Installation and initial startupPreparatory work
19.02.2016RVM/U-L2 Module BASICS Flow Monitor28
Prepare the device
NOTICE!
Risk of damage to property dueto contamination!Contamination and deposits mayimpair the free movement of thefloat, thereby damaging thedevice.
– Ensure that there are no for-eign particles in the device.
– Ensure that the device is notsoiled .
– Do not use any media con-taining solids.
1. Unpack the device and visuallyinspect the device to ensure thatit is free of packaging materials.
2. Check the device for soiling andflush with clean medium, if nec-essary.
5.4 Installation in thepipe system
WARNING!
Risk of injury from pressurizedpipes!If the pipe system is under pres-sure when installing the device,severe injuries may result.
– Depressurize the pipe systembefore installing the device.
Installation and initial startupInstallation in the pipe system
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 29
WARNING!
Risk of injury from hot or coldsurfaces!Pipelines can heat up/cool downdramatically due to the mediaflowing through them. Skin contactwith hot or cold surfaces maycause severe skin burn or frostbite.
– Before commencing work,ensure that the system hasbeen controlled to a tempera-ture range between 0 und 40°C
– Do not touch any parts of thesystem that are either very hotor very cold.
– Always wear heat-resistant/cold-resistant protectiveclothing and protective gloveswhen working near hot/coldsurfaces.
WARNING!
Risk of injury from media in thepipe system!If the pipe system contains haz-ardous media, severe injuries maybe caused by escaping media.
– Before installation, ensure thatthe pipe system is empty anddoes not contain any mediaresidue
– Always wear personal protec-tive equipment during installa-tion
– Provide suitable drainingdevices (collection tanks, etc.)
NOTICE!
Risk of damage to the devicedue to contamination in the pipesystem!Dirt and foreign particles enteringthe device can damage the deviceand impair its operation.
– Ensure that the pipe system isclean before installing thedevice
– If necessary, flush the pipesystem with clean mediumbefore installation
Installation and initial startupInstallation in the pipe system
19.02.2016RVM/U-L2 Module BASICS Flow Monitor30
A suitable sealant must beselected depending on the condi-tion/composition of the pipe lines,the medium and the operating andenvironmental conditions. Thesealing method described here isonly an example and cannot beused in all cases.
Sealing the pipe connections
Personnel:n Qualified personnel
1. Nap the thread.
Fig. 8: Apply sealing thread
Installation and initial startupInstallation in the pipe system
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 31
2. Apply sealing thread ( Fig. 8/1)to the napped area in thethreaded direction. Observe thequantity recommended by thesealant manufacturer.
Fig. 9: Pipe connection with sealingthread
ð The pipe line is now readyfor installation ( Fig. 9)
Install device in pipe system
Personnel:n Qualified personnel
Protective equipment:n Protective gloves
Tools:n Fixed spanner
CAUTION!
Do not hold the device by itsthreads. These are sharp edgedand may cause injury.
1. Start the threaded end of thedevice onto the thread of theconnecting pipe.
Fig. 10: Screw in the device
2. Fasten the adapter union of thepipeline with an appropriatespanner ( Fig. 10/2). Whendoing so, lock the process con-nector in place to prevent slip,using a suitable spanner (Fig. 10/1).
Installation and initial startupInstallation in the pipe system
19.02.2016RVM/U-L2 Module BASICS Flow Monitor32
Fig. 11: Screw in the device
3. Keep turning in the adapterunion ( Fig. 11/2) while holdingthe process connection of thedevice locked ( Fig. 11/1) untilthe connection is tight.
4. Repeat these steps at the otherend of the device.
5.5 Initial startupThe following steps must be takenbefore initial startup and any subse-quent startup (e.g. after removal andinstallation during maintenance).
1.
WARNING!
Make sure that the plant isoperating vibration-free.Vibrations could destroy thedevice. This could result in aserious risk of injury to theuser.
2.
WARNING!
Make sure that the mediumis flowing continuously.Pulse-like staggered loadscould destroy the device.This could result in a seriousrisk of injury to the user.
3.
NOTICE!
Flush the pipe system care-fully and ensure that thereare no solids or other for-eign matter in the system.These could impair the func-tion, or even damage thedevice.
Installation and initial startupInitial startup
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 33
5.6 Electrical connec-tion
The electrical connection of the flowmonitor is accomplished through theconnector plug or the cast on powercable leading from the switch housing.The switch contacts employed in thesedevices are potential free and do notrequire a power source. Switch con-tacts and flow monitor have been opti-mally harmonized. After replacement ofa switch contact, the switch point mustbe readjusted.
DANGER!
Danger to life from electricalcurrentThere is an immediate risk to lifefrom electrocution on touching liveparts. Damage to the electricalinsulation or single componentscan be extremely dangerous.
– Only qualified electriciansshall work on the electricalsystem
– If the insulation is damagedthen immediately switch offand have repairs carried out
– Before commencing work onlive parts of electrical systemsand components, disconnectthe equipment and ensure thatit remains disconnected for theduration of the work. Observethese 5 safety rules whendoing so:– Isolate (disconnect)
– Secure against switchingback on
– Check for absence ofvoltage
– Ground and short– Cover or cordon off other
live parts in the vicinity– Never bridge fuses or put
them out of operation. Alwaysobserve the correct currentratings when replacing fuses
– Keep moisture away from liveparts. This can result in short-circuit
5.6.1 Switch contactSG-15 with con-nector in compli-ance withEN175301-803
Wiring diagram of the suppliedsocket (EN 175301-803, Form C)front view.
Wiring diagram
normally open:
Fig. 12: Switch position under no-flowcondition
Installation and initial startupElectrical connection > Switch contact SG-15 with connector in compliance with EN175301-803
19.02.2016RVM/U-L2 Module BASICS Flow Monitor34
Fig. 13: Pin assignment, plug socket,normally-open contact. The ground-pinis not used.
change over:
Fig. 14: Switch position under no-flowcondition
Fig. 15: Pin assignment, plug socket,change-over contact. The ground-pin isnot used.
5.6.2 Plug connectorM12x1
Wiring diagram, connector M12x1
Installation and initial startupElectrical connection > Plug connector M12x1
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 35
Fig. 16: Pin assignment, connectorM12x1 (Form 15x50)
Wiring diagram
Normally open:
Fig. 17: Switch position under no-flowcondition
Change-over:
Fig. 18: Switch position under no-flowcondition
5.6.3 CableThe individual cores of the cable arenumbered according to the followingconnection diagram.
Wiring diagram
normally open:
Fig. 19: Switch position under no-flowcondition
Installation and initial startupElectrical connection > Cable
19.02.2016RVM/U-L2 Module BASICS Flow Monitor36
5.6.4 Degree of protection(IP-Code)
The specified degree of protection (IP)is only ensured if approved connectionmaterial is used (see following table).
Deviceconnec-tion
Specifi-cationof con-nectionmaterial
Degree ofprotection
EN175301-803withgland
Diameterof con-nectioncable: 5–6mm
IP65
M12x1 Plugcon-nectorM12x1
IP65
Cable - IP67
5.7 Grounding thedevice
When installing the device in a pipesystem, ensure that the device isgrounded to the pipe system to avoid adangerous electrical potential differ-ence.
5.8 Plug connectionPersonnel:n Qualified electrician
Tools:n Flat-bladed screwdriver
Fig. 20: Detach socket
1. Release the fixing screw (Fig. 20/1) from the socket
Fig. 21: Remove socket
2. Remove socket ( Fig. 21/1)
Installation and initial startupPlug connection
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 37
Fig. 22: Loosen inner section
3. Remove the inner section fromthe socket by inserting a flat-bladed screwdriver into the slot (Fig. 22/1) and carefully pry outthe inner section.
Fig. 23: Loosen the screw connection
4. Loosen the screw connection (Fig. 23/1) by turning it to the left
5. Guide the connecting cablethrough the screw connectioninto the socket
6. Make the connections as shownin the connecting diagram (Fig. 24 Fig. 25)
7. Place the inner section ( Fig. 22)back into the socket and pushuntil it locks on
8. Retighten the screw connection (Fig. 23/1) by turning it to theright until tight
Installation and initial startupPlug connection
19.02.2016RVM/U-L2 Module BASICS Flow Monitor38
9. Place the female socket onto theconnecting plug and tighten thefixing screw ( Fig. 20/1).
Fig. 24: Pin assignment, plug socket,Normally Open Contact (Form 15x50)
Fig. 25: Pin assignment, plug socket,Change-Over-Contact (Form 15x50)
5.9 Contact protectionmeasures
The Reed-switches used in the switchcontacts are designed to be very sensi-tive to overload. To prevent destructionof the switch contact, the values speci-fied on the rating plate of the switchcontact must never be exceeded (noteven temporarily).
There is a risk of overload from:
n inductive loadsn capacitive loadsn ohmic loads.
Suitable measures must be taken toprotect against overload (see followingexamples):
Installation and initial startupContact protection measures
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 39
Inductive load
There is danger of voltage peaks frominductive loads when switching off (upto 10 times the rated voltage). Induc-tive loads are caused by, e.g.:
n Contactors, relaysn Solenoid valvesn Electric motors
Examples of protective measures:
Fig. 26: Example 1
Fig. 27: Example 2
Capacitive loads
There is a danger of high currentpeaks from capacitive loads whenswitching-on the switch contact(exceeding rated current). Capacitiveloads are caused by, e.g.:
n Long connecting cablesn Capacitive consumers
Example of protective measure:
Fig. 28: Protective measure againstcapacitive loads
Ohmic loads
There is a danger of high currentpeaks from ohmic loads whenswitching-on the switch contact. Thereason for this is that the glow filamenthas a low resistance at low tempera-tures. Ohmic loads are caused by, e.g.:
n Filament bulbsn Motors during startup
Examples of protective measures:
Fig. 29: Example 1
Fig. 30: Example 2
Installation and initial startupContact protection measures
19.02.2016RVM/U-L2 Module BASICS Flow Monitor40
Protection against ohmic loads can beachieved through installation of aresistor in the circuit, or by heating theglow filament. For connection to high-impedance consumers (ex. PLC), aprotective circuit is not needed.
Installation and initial startupContact protection measures
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 41
6 Operation6.1 Switch point adjust-
mentSetting the switch point of aninstalled device
The following instructions describethe procedure for a Normally OpenContact (NOC). The actual state(open or closed), can be deter-mined using a continuity meter.
Personnel:n Qualified personnel
Tools:n Hex screwdriver
Fig. 31: Loosen set screw
1. Loosen the set screw of theswitch contact ( Fig. 31/1) usinga Hex screwdriver.
2. Slide the switch contact to theflow value to be monitored.Make sure that the arrow on theswitch contact data plate is inexact alignment with the desiredflow rate on the switchpointadjustment scale.
3. Re-tighten the set screw of theswitch contact ( Fig. 31/1) usinga Hex screwdriver. When doingso, observe the correct tight-ening torque of the screw.
Ä Chapter 11.1 “Tighteningtorque” on page 70
ð The set switch point corre-sponds to the switch-offpoint of the switch contactby decreasing flow.
OperationSwitch point adjustment
19.02.2016RVM/U-L2 Module BASICS Flow Monitor42
Setting the switch point of a non-installed device
Fig. 32: Loosen the set screw
1. Loosen the set screw of theswitch contact ( Fig. 32/1)usinga Hex-Screwdriver screwdriver.
2. Slide the switch contact to theflow value to be monitored.Make sure that the arrow on theswitch contact data plate is inexact alignment with the desiredflow rate on the switch pointadjustment scale.
3. Re-tighten the set screw of theswitch contact ( Fig. 32/1) usinga Hex-Screwdriver. When doingso, observe the correct tight-ening torque of the screw.
Ä Chapter 11.1 “Tighteningtorque” on page 70
ð The set switch point corre-sponds to the switch-offpoint of the switch contactby decreasing flow.
OperationSwitch point adjustment
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 43
6.2 Checking the flowReading-off the switch value
Personnel:n Qualified personnel
Protective equipment:n Goggles
Fig. 33: Reading-off the switch pointvalue (example scale)
1. Make sure that the setting arrowand the scale mark on theswitchpoint adjustment scale arein alignment ( Fig. 33).
2. To obtain the greatest readingaccuracy, look straight-on. Theread-off value can be falsified byviewing at an angle from aboveor below (parallax error).
3. Read-off the switch value fromthe adjustment scale.
OperationChecking the flow
19.02.2016RVM/U-L2 Module BASICS Flow Monitor44
7 TroubleshootingThis chapter describes possible mal-functions of the device, their causesand repair.
If malfunctions persist or increase,shorten the maintenance interval tomeet the actual operating conditions.
For malfunctions not described in thischapter, please contact the manufac-turer (see service address on page 2).
7.1 SafetyWork performed incorrectly toremedy a malfunction
WARNING!
Risk of injury due to incorrectrepair of malfunction!Work performed incorrectly mayresult in severe injury and consid-erable damage to property.
– Ensure that the site is suffi-ciently cleared before com-mencing work
– Ensure that the repair locationis orderly and clean! Compo-nents and tools that are lyingabout or on top of each otherare potential causes of acci-dents
– If components have beenremoved, observe correctassembly procedures. Rein-stall all fixing/fastening ele-ments and observe the pre-scribed tightening torque forthe screwsÄ Chapter 11.1 “Tighteningtorque” on page 70
– Before placing the device backinto operation, ensure that allwork has been performed andcompleted in compliance withthe specifications and instruc-tions in these OperatingInstructions
TroubleshootingSafety
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 45
Conduct in case of malfunction
The complete machine or system maybe unsafe if there is a defect at the flowmonitor (e.g. fractured housing).
The following always applies:
1. In case of malfunctions thatpresent an immediate danger topersons or valuables, proceedaccording to the valid emer-gency plans for the system
2. Determine the cause of the mal-function
3. Before repair, ensure that thereis no danger to persons fromescaping media
4. If necessary, allow the pipelineand device to cool down or towarm up before commencingwork
5. Malfunctions must be correctedby qualified personnel
The following troubleshootingguide provides an indication ofwho is qualified to repair the fault .
TroubleshootingSafety
19.02.2016RVM/U-L2 Module BASICS Flow Monitor46
7.2 Troubleshooting guideFault description Cause Remedy Personnel
The switch contactdoes not switch.
No mediumflowing throughflow monitor
Check that medium isflowing through the pipe-line
Qualifiedpersonnel
Flow is too low orthe switch con-tact is set toohigh
n Adjust the switchcontact to a lowerflow rate
n Use the device atanother measuringrange
n Increase the flowrate
Qualifiedpersonnel
Incorrect reduc-tion fitting or pipediameter is toosmall
n Correct pipe diam-eter
Qualifiedpersonnel
Float is stuck Disassemble and cleanthe device
Qualifiedpersonnel
Switch contact isdefective.
n Remedy the cause ofthe defect (short-cir-cuit, overload)
n Replace the switchcontact
Qualifiedpersonnel
Switch contact ispermanentlyswitched.
Flow is too highor the switchcontact is set toolow
n Reduce the flown Adjust the switch
contact to a higherflow rate
n Use the device atanother measuringrange
Qualifiedpersonnel
TroubleshootingTroubleshooting guide
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 47
Fault description Cause Remedy Personnel
Float is stuck Disassemble and cleanthe device
Qualifiedpersonnel
Switch contact isdefective
n Remedy the cause ofthe defect (short-cir-cuit, overload)
n Replace the switchcontact
Qualifiedpersonnel
The switch point isnot the same asthe actual flow rate.
Improper scaleinstalled formedia used
Request proper conver-sion table or scale formedia used
Qualifiedpersonnel
Incorrect reduc-tion fitting or pipediameter is toosmall
n Correct pipe diam-eter
Qualifiedpersonnel
Device is dirty Disassemble and cleanthe device
Qualifiedpersonnel
Device is defec-tive
Remove device fromsystem and contact themanufacturer
Qualifiedpersonnel
TroubleshootingTroubleshooting guide
19.02.2016RVM/U-L2 Module BASICS Flow Monitor48
8 Maintenance8.1 SafetyMaintenance work performed incor-rectly
WARNING!
Risk of injury due to mainte-nance work performed incor-rectly!Maintenance work performedincorrectly may result in severeinjury and considerable damage toproperty.
– Ensure that the site is suffi-ciently cleared before com-mencing work.
– Ensure that the repair locationis orderly and clean! Compo-nents and tools that are lyingabout or on top of each otherare potential causes for acci-dents.
– If components have beenremoved, observe correctassembly procedure. Reinstallall fixing/fastening elementsand observe the prescribedtightening torque for thescrews (see Chapter 11.1).
– Before placing the device backinto operation ensure that allwork has been performed andcompleted in compliance withthe specifications and instruc-tions in these OperatingInstructions.
8.2 Maintenance planIntervals for replacement of wearparts
RVM/U-L2 type flow monitors requirevery little maintenance due to the smallnumber of moving parts. The intervalsfor the replacement of wear partsdepends significantly on the operatingconditions as well as on the composi-tion of the medium flowing through thedevice. For this reason, no intervalshave been set by the manufacturer.The operator must determine suitableintervals based on the local conditionand circumstances.
MaintenanceMaintenance plan
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 49
Interval Maintenance work Personnel
Visual inspection for dirt/soiling Qualified personnel
Visual inspection for free-movement of float Qualified personnel
Visual inspection for leaks from the device Qualified personnel
Check function of switch contact Qualified personnel
8.3 Removal from thepipe system
The flow monitor must first be removedfrom the pipe system before per-forming maintenance.
WARNING!
Risk of injury from pressurizedlines!Severe injury may result if the pipesystem is under pressure whenremoving the device.
– Depressurize the systembefore removing the device
WARNING!
Risk of injury from hot or coldsurfaces!Pipelines can heat up/cool downdramatically due to the mediaflowing through them. Skin contactwith hot or cold surfaces causessevere skin burn or frostbite.
– Before removing the device,ensure that the machine orsystem and the flow monitorhave been controlled to a tem-perature range between 0 and40°C
– Do not touch any part of themachine or system that iseither very hot or very cold
– Always wear heat-resistant/cold-resistant protective workclothing and protective gloveswhen working near hot/coldsurfaces
MaintenanceRemoval from the pipe system
19.02.2016RVM/U-L2 Module BASICS Flow Monitor50
WARNING!
Risk of injury from media in thepipe system!If the pipe system contains haz-ardous media, severe injury maybe caused by escaping media.
– Before removing the device,ensure that the pipe system isempty and does not containmedia residue
– Always wear personal protec-tive equipment when removingthe device
WARNING!
Risk of injury from media res-idue in the device!After the pipe system has beenemptied, media residue may stillbe present inside the device. In thecase of hazardous media, thiscould result in serious injury.
– When removing (de-installingthe device from the pipesystem), always wear per-sonal protective equipment.
– All requirements specified inthe media safety data sheetmust be observed in accom-plishing the work task.
– Residue of hazardous mediain the device can result inserious injury.
Removing the device from the pipesystem
Personnel:n Qualified personnel
Protective equipment:n With hazardous media, the protec-
tive equipment specified in theSafety Data Sheet of the mediummust be worn. In addition, thespecifications of the system oper-ator must be followed. If no protec-tive equipment is specified, suit-able protective gloves and gogglesmust be worn.
Tools:n Fixed spanner
1. Loosen the adapter union of thepipe line using a suitablespanner. When doing so, lockthe process connection ordevice body in place with asecond spanner.
2. Secure the device against fallingand repeat Step 1 at the otherprocess connection.
8.4 DisassemblyTo replace wear parts or to clean thedevice, the flow monitor must first bedisassembled.
MaintenanceDisassembly
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 51
WARNING!
Risk of injury due to incorrectdisassembly!– The device may still contain
media residue– Wear personal protective
equipment when working withdangerous media
– Improper disassembly maycause serious injuries if dan-gerous media is still presentinside the device
CAUTION!
Risk of injury due to incorrectdisassembly!Incorrect disassembly may resultin injuries.
– Before disassembling, ensurethat the flow monitor hascooled down/warmed up to atemperature range between 0and 40° C
– Wear personal protectiveequipment to protect againsthazardous media which maystill be present inside thedevice
Protective equipment:n With hazardous media, the protec-
tive equipment specified in theSafety Data Sheet of the mediummust be worn. In addition, thespecifications of the system oper-ator must be followed. If no protec-tive equipment is specified, suit-able protective gloves and gogglesmust be worn.
Personnel:n Qualified personnel
Protective equipment:n Gogglesn Protective gloves
Tools:n Fixed spannern Socket wrench
Special tools:n Threaded ring insertion tool
MaintenanceDisassembly
19.02.2016RVM/U-L2 Module BASICS Flow Monitor52
Fig. 34: Insert threaded ring insertiontool (outlet)
1. Insert threaded ring insertiontool (outlet) ( Fig. 34) and turnuntil it rest in the keyway of thethreaded ring
Fig. 35: Loosen threaded ring (outlet)
2. Insert socket wrench into thethreaded ring insertion tool andloosen the threaded ring (Fig. 35). Hold the device body inplace using a proper sizedspanner wrench.
MaintenanceDisassembly
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 53
Fig. 36: Remove threaded ring (outlet)
3. Unscrew the threaded ring(outlet) from the device body (Fig. 36)
Fig. 37: Remove inner parts
4. Carefully turn the device body180° and remove the inner parts(float and spring). ( Fig. 37)
Fig. 38: Spring and float
5. The inner parts of the flow mon-itor consist of the spring (Fig. 38/1) and float ( Fig. 38/2).
8.5 Maintenance
8.5.1 CleaningIt is the responsibility of the operator toestablish appropriate intervals and pro-cedures for cleaning the individualparts of the device. It must be ensuredthat the parts are not damaged duringthe cleaning process. When usingcleaning agents, it must be ensuredthat these are not aggressive to theparts and that there will be no dan-gerous reactions with media residue.Damaged parts must be replaced.
MaintenanceMaintenance > Cleaning
19.02.2016RVM/U-L2 Module BASICS Flow Monitor54
WARNING!
Risk of injury due to impropercleaning!The device may still contain mediaresidue.
– To protect against hazardousmedia residue in the device,wear personal protectiveequipment.
– Do not use cleaning agentswhich may lead to dangerousreactions with media residue.
– All requirements specified inthe safety data sheet must beobserved when handling orotherwise using the medium.
– Residue of hazardous mediainside the device can causeserious injury.
CAUTION!
Risk of injury due to damagedparts!If parts of the device are broken ordamaged, they may cause injurydue to sharp edges or splintersduring the cleaning process.
– Damaged parts must bereplaced
– Carefully clean the parts of thedevice, so as not to causedamage.
– When cleaning, always wearappropriate personal protec-tive equipment.
– Incorrect disassembly canresult in injuries.
MaintenanceMaintenance > Cleaning
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 55
Protective equipment:n With hazardous media, the protec-
tive equipment specified in theSafety Data Sheet of the mediummust be worn. In addition, thespecifications of the system oper-ator must be followed. If no protec-tive equipment is specified, suit-able protective gloves and gogglesmust be worn.
8.5.2 Parts replacementDepending on the operating conditions,wear parts such as float or spring mayhave to be replaced. Steps required toreplace these parts correspond tothose used when assembling thedevice. Ä Chapter 8.5.3 “Assembly”on page 56.
8.5.3 AssemblyAfter cleaning the individual compo-nents, the flow monitor must be reas-sembled.
Personnel:n Qualified personnel
Tools:n Fixed spannern Socket wrenchn Torque wrench
Special tools:n Threaded ring insertion tooln Test rod
Fig. 39: Insert inner parts
1. Insert the float and spring intothe device Fig. 39)
MaintenanceMaintenance > Assembly
19.02.2016RVM/U-L2 Module BASICS Flow Monitor56
Fig. 40: Insert threaded ring (outlet)
2. Insert the threaded ring (outlet)into the device body (outlet) (Fig. 40)
Fig. 41: Seat threaded ring (outlet)
3. Lightly seat the threaded ring(outlet) with the aid of thethreaded ring insertion tool andtighten with a torque wrench (Fig. 41), observing the propertorque ( Ä Chapter 11.1 “Tight-ening torque” on page 70). Ifnecessary, hold the device bodyin place with an apropriate fixedspanner.
MaintenanceMaintenance > Assembly
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 57
Fig. 42: Check for smooth operation
4. Check the float for ease ofmovement ( Fig. 42) by applyinglight pressure with the test rod
ð If the float moves sluggishly,then disassemble the deviceÄ Chapter 9.2 “Disas-sembly” on page 61 andclean the float and devicebody bore
If the float is still sluggish afterhaving been cleaned severaltimes, contact the manufacturer.
8.5.4 Switch contactreplacement
Tools:n Flat-bladed screwdrivern Hex screwdriver
Fig. 43: Loosen female socket
1. Loosen the fixing screw of thefemale socket ( Fig. 43/1) with aflat-bladed screwdriver.
Fig. 44: Remove female socket
2. Remove the female socket andgasket ( Fig. 44/1) by pullingupwards.
MaintenanceMaintenance > Switch contact replacement
19.02.2016RVM/U-L2 Module BASICS Flow Monitor58
Fig. 45: Loosen set screw
3. Using a hex screwdriver (Fig. 45/1), loosen the set screwof the switch contact, so that theswitch contact can be removed.
Fig. 46: Remove switch contact
4. Remove the switch contact (Fig. 46) from the device
5. Position the new switch contact,making sure that the cylinder pinslides into the guide.
6. Insert the set screw and tightenjust enough to still allow theswitch contact to move easily.
7. Connect a continuity meter: ForNormally Open Contact (NOC),pin 1 and pin 2 are assigned; forChange Over Contact (COC),pin 1 and pin 3 are assigned.
8. Slide the switch contact in theopposite direction of flow until itstops. The switch contact mustnow be closed.
9. Slowly push the switch contactin the direction of flow, until thecontact opens. This switch pointshould be set as accurately aspossible because it affects theaccuracy of the switch pointadjustment scale values (ifneeded, repeat steps 9 and 10).
10. Tighten the set screw (Fig. 45/1) observing the propertightening torque of the screw (Ä Chapter 11.1 “Tighteningtorque” on page 70)
11. Affix the enclosed data plate tothe side of the switch contact sothat the reference arrow is inalignment with the lowest scalemark. If a reference tick mark ison the data plate (recognizableas a thinner line), it is to be usedas the alignment mark. Theadhesive surface must be dryand free of oil and grease.
12. Adjust the desired flow rate (cut-off point) on the switch pointadjustment scale.
13. Attach the female socket andgasket and tighten the fixingscrew.
MaintenanceMaintenance > Switch contact replacement
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 59
8.6 Measures to betaken after mainte-nance work
Take the following steps after comple-tion of maintenance work and beforeswitching on the device:
1. Check all previously loosened/released screw connections fortightness.
Ä Chapter 11.1 “Tighteningtorque” on page 70
2. Clean the work area and removeall residual materials, packaging,substances or spills.
MaintenanceMeasures to be taken after maintenance work
19.02.2016RVM/U-L2 Module BASICS Flow Monitor60
9 Disassembly and disposalAfter its period of useful life, the devicemust be disassembled and disposed ofin an environmentally safe manner.
9.1 Safety
WARNING!
Risk of injury if disassembledincorrectly!Media residue, sharp edged com-ponents, pointed ends and cornerson and in the device or on toolsmay cause injury.
– Ensure that the site is suffi-ciently cleared before com-mencing work
– Always wear protective equip-ment when handling haz-ardous media residue
– Handle open, or sharp-edgedcomponents carefully
– Ensure that the workplace isorderly and clean! Compo-nents and tools that are lyingabout or on top of each otherare potential causes of acci-dents
– Disassemble components pro-fessionally
– Secure components so thatthey do not fall or overturn
– If in doubt, contact the manu-facturer
9.2 Disassembly
Before starting disassembly:
n Remove operating materials andpackaging and dispose of properly
Personnel:n Qualified personnel
Protective equipment:n Protective glovesn Goggles
1. Remove the device from thepipeline ( Ä Chapter 8.3“Removal from the pipe system”on page 50)
2. Disassemble the device. (Ä Chapter 9.2 “Disassembly”on page 61)
3. Clean components properly andremove media residue.
4. Dispose in an environmentallysafe manner.
Disassembly and disposalDisassembly
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 61
9.3 Return Materials9.3.1 Return Materials
AuthorizationFor products being returned, regard-less of the reason, the currently validprovisions of the returns policy set byMEISTER will apply. Return shipmentswhich do not comply with the returnspolicy may be refused by MEISTER atthe expense of the consignor.
9.4 DisposalIf no return or disposal agreement hasbeen made, recycle disassembledcomponents:
n Scrap metalsn Recycle plastic elementsn Dispose of the remaining compo-
nents according to their materialproperties
NOTICE!
Danger to the environment dueto incorrect disposal!Potential risk to the environmentmay arise due to incorrect dis-posal.
– Have electrical scrap, elec-tronic components, lubricantsand other supplies disposed ofby approved specialists
– In case of doubt, obtain infor-mation on environmentallysafe disposal from the localauthority or special disposalexpert
Disassembly and disposalDisposal
19.02.2016RVM/U-L2 Module BASICS Flow Monitor62
10 Technical data10.1 Device data plateThe data plate is on the mechanicalpart of the flow monitor/flow meter andcontains the following information:
Fig. 47: Device data plate
10.2 Switch contactdata plate
Fig. 48: Switch contact data plate
Fig. 49: Switch contact data plate withpositioning arrow
The data plate is on the switch contactand may provide the following informa-tion:
n maximum voltagen maximum currentn maximum powern positioning arrow for cut-off point
Technical dataSwitch contact data plate
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 63
10.3 Dimension sheet
Technical dataDimension sheet
19.02.2016RVM/U-L2 Module BASICS Flow Monitor64
10.4 General specificationsType Overall dimensions (mm)
G * DN SW L1 L2 T
RVM/U-L20010
1/2 15 27 90 - 14
RVM/U-L20020
1/2 15 27 90 - 14
RVM/U-L20030
1/2 15 27 90 - 14
RVM/U-L20035
1/2 15 27 90 - 14
RVM/U-L20090
1/2 15 27 90 - 14
RVM/U-L20220
1/2 15 27 90 - 14
RVM/U-L20240
1/2 15 27 90 - 14
RVM/U-L20300
1/2 15 27 90 - 14
RVM/U-L20525
1/2 15 27 90 - 14
Type Overall dimensions (mm)
G * D1 D2 A1 A2 A3 A4 weight(g) **
RVM/U-L20010
1/2 - 31,2 - - - ca. 67 350
RVM/U-L20020
1/2 - 31,2 - - - ca. 67 350
Technical dataGeneral specifications
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 65
Type Overall dimensions (mm)
G * D1 D2 A1 A2 A3 A4 weight(g) **
RVM/U-L20030
1/2 - 31,2 - - - ca. 67 350
RVM/U-L20035
1/2 - 31,2 - - - ca. 67 350
RVM/U-L20090
1/2 - 31,2 - - - ca. 67 350
RVM/U-L20220
1/2 - 31,2 - - - ca. 67 350
RVM/U-L20240
1/2 - 31,2 - - - ca. 67 350
RVM/U-L20300
1/2 - 31,2 - - - ca. 67 350
RVM/U-L20525
1/2 - 31,2 - - - ca. 67 350
* NPT thread on request
**Connecting cable weight, 2m approx. 80g
10.5 Electrical specificationsChange-Over-Contact (COC)
Data Value Unit
Voltage 250 V
Current, maximum 1,5 A
Power, maximum 50 VA
Minimum load 3 VA
Technical dataElectrical specifications
19.02.2016RVM/U-L2 Module BASICS Flow Monitor66
Normally Open Contact (NOC)
Data Value Unit
Voltage 230 V
Current, maximum 3 A
Power, maximum 60 VA
Change-Over-Contact (COC) M12x1 (-20 °C–85 °C)
Data Value Unit
Voltage 125 V
Current, maximum 1,5 A
Power, maximum 50 VA
Minimum load 3 VA
Normally Open Contact (NOC) M12x1 (-20 °C–85 °C)
Data Value Unit
Voltage 125 V
Current, maximum 3 A
Power, maximum 60 VA
Change-Over-Contact PLC
Data Value Unit
Voltage 250 V
Current, maximum 1 A
Power, maximum 60 VA
Technical dataElectrical specifications
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 67
10.6 Measuring ranges10.6.1 Standard measuring rangesType Switch range for air at 1 bar abs. & 20 °C*
Nl/min SCFH SCFM
RVM/U-L20010 2,5 – 10 5,5 – 21,0
RVM/U-L20020 5,5 – 20 12,0 – 42,0
RVM/U-L20030 8 – 30 17,0 - 64,0
RVM/U-L20035 10 – 35 21,0 - 74,0
RVM/U-L20090 45 – 90 95,0 - 190,0
RVM/U-L20220 55 – 220 115,0 - 465,0
RVM/U-L20240 65 – 240 140,0 - 510,0
RVM/U-L20300 80 – 300 170,0 - 640,0
RVM/U-L20525 140 – 525 5,0 – 18,5
* The specified data are switch-off points (other switch ranges are available onrequest).
10.7 Operating dataDescription Value Unit
Max. media temperature 120 (optional 160°C) °C
Min. media temperature
It must be ensured thatthe medium does notfreeze.
-20 °C
Max. operating pressure 300
350
bar (brass)
bar (stainless steel)
Technical dataOperating data
19.02.2016RVM/U-L2 Module BASICS Flow Monitor68
Pressure loss 0,02 – 0,3 bar
Measuring accuracy ± 10 % of full scale value
Operating data for devices employed inexplosion hazard zones differs fromthe above.
Operating data for devices employed inexplosion hazard zones are specifiedin the Operating Instructions for "RVM/U-L2 Module ATEX", Chapter 4.
Technical dataOperating data
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 69
11 Appendix11.1 Tightening torqueComponent/function
Description Size Torque Qty
Threaded ring Threaded ring(outlet)
G1/2" 5 Nm 1
Switch contact Cylinder headscrew, hexsocket
M3x10 0,4 Nm 1
11.2 Replacementparts
AppendixReplacement parts
19.02.2016RVM/U-L2 Module BASICS Flow Monitor70
The following replacement parts drawing provides an example of the constructionof a RVM/U-L2 type flow monitor. The actual configuration may vary depending onthe model.
Item Qty Description
1 1 Device body
2 1 Float
3 1 Spring
4 1 Threaded ring (outlet)
5 1 Cylinder pin (switch contact)
6 1 Switch contact with male connector
7 1 Female socket and gasket
8 1 Fixing screw, female socket
9 1 Set screw, switch contact
AppendixReplacement parts
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 71
11.3 ToolsThe following tools are required:
Tools
n Fixed spanner 27 mmn Flat-bladed screwdriver, blade
width 5,5 mmn Hexagon socket key 2,5 mmn Torque screwdriver and assorted
bladesn Ratchet wrench, 1/2" and socketsn Torque wrench, 1/2"
Special tools
n Threaded ring insertion tool, RVM/U-L2
n Test rod RVM/U-L2
11.4 Sealant
Before using a sealant, ensure thatit is compatible with the mediaused and that it can be employedunder the given operating condi-tions.
n Ensure proper sealn Use a suitable sealant. Liquid seal-
ants will damage the flow monitorn Always follow the sealant manu-
facturer's instructions
AppendixSealant
19.02.2016RVM/U-L2 Module BASICS Flow Monitor72
11.5 Lubricants
Before using a lubricant, always make sure that it is compatible with the oper-ating medium.
For the proper mounting of O-rings, device-specific O-ring installation tools may bepurchased from the manufacturer.
The following lubricants are suitable to facilitate installing the O-rings:
Lubricant O-ring material
NBR EPDM FKM
Glycerine* suitable suitable suitable
Soapy water suitable suitable suitable
* Glycerine must not be used if the device is used for sulfuric acid and/or nitricacid.
AppendixLubricants
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 73
12 IndexAAssembly . . . . . . . . . . . . . . . . . . 56
CCable . . . . . . . . . . . . . . . . . . . . . 36Component groups . . . . . . . . . . . 21Connected loads
Change-Over-Contact (COC) . . 66Normally Open Contact (NOC) . 67
ConnectorM12x1 . . . . . . . . . . . . . . . . . . 35
Contact . . . . . . . . . . . . . . . . . . . . 7Contact protection measures . . . . . 39Copyright . . . . . . . . . . . . . . . . . . . 3Correct use . . . . . . . . . . . . . . . . . 10Customer service . . . . . . . . . . . . . 7
DDegree of protection
IP-Code . . . . . . . . . . . . . . . . . 37Device data plate . . . . . . . . . . . . . 63Device description . . . . . . . . . . . . 20Dimension sheet . . . . . . . . . . . . . 64Disassembly
disposal . . . . . . . . . . . . . . . . . 61Maintenance . . . . . . . . . . . . . 51
Disposal . . . . . . . . . . . . . . . . . . . 62
EElectrical connection . . . . . . . . . . 34employment . . . . . . . . . . . . . . . . 10Environmental protection . . . . . . . 17
cleaning fluids . . . . . . . . . . . . 17lubricants . . . . . . . . . . . . . . . . 17
FFault table . . . . . . . . . . . . . . . . . . 47
GGeneral
safety . . . . . . . . . . . . . . . . . . . 8
HHazard
electrical current . . . . . . . . . . . 11Hazards
mechanical . . . . . . . . . . . . . . 12media . . . . . . . . . . . . . . . . . . 14radiation . . . . . . . . . . . . . . . . 13temperature . . . . . . . . . . . . . . 13
IInitial startup . . . . . . . . . . . . . . . . 33Installation
pipe system . . . . . . . . . . . . . . 29preparatory work . . . . . . . . . . . 26
LLimitation of liability . . . . . . . . . . . . 3Lubricant . . . . . . . . . . . . . . . . . . 73
MMaintenance . . . . . . . . . . . . . . . . 54Maintenance plan . . . . . . . . . . . . 50Measuring range . . . . . . . . . . . . . 68
OOperating conditions . . . . . . . . . . 68Overview . . . . . . . . . . . . . . . . . . 20Owner . . . . . . . . . . . . . . . . . . . . 17
PPackaging . . . . . . . . . . . . . . . . . . 22Parts replacement . . . . . . . . . . . . 56Plug connection . . . . . . . . . . . . . . 37Plug connector
EN175301-803 . . . . . . . . . . . . 34
Index
19.02.2016RVM/U-L2 Module BASICS Flow Monitor74
Precautionsgeneral . . . . . . . . . . . . . . . . . 11
PreparationDevice . . . . . . . . . . . . . . . . . . 29
RRead-off . . . . . . . . . . . . . . . . . . . 44Replacement parts . . . . . . . . . 16, 70Return Materials Authorization . . . . 62
SSafety
disassembly . . . . . . . . . . . . . . 61Safety equipment . . . . . . . . . . 15, 16Safety instructions
transport . . . . . . . . . . . . . . . . 22Sealant . . . . . . . . . . . . . . . . . . . . 72Service . . . . . . . . . . . . . . . . . . . . . 7Special tools . . . . . . . . . . . . . . . . 72Storage . . . . . . . . . . . . . . . . . . . 23Strainer . . . . . . . . . . . . . . . . . . . 28Switch contact . . . . . . . . . . . . . . . 21
replacement . . . . . . . . . . . . . . 58
Switch contact data plate . . . . . . . 63Switch point adjustment scale . . . . 21Switch point setting . . . . . . . . . . . 42Switch value . . . . . . . . . . . . . . . . 44Symbols
packaging . . . . . . . . . . . . . . . 23Symbols used
in the instructions . . . . . . . . . . . 8
TTechnical data
General specifications . . . . . . . 65Tightening torque . . . . . . . . . . . . . 70Tightening torque of screws . . . . . 70Tools . . . . . . . . . . . . . . . . . . . . . 72Transport inspection . . . . . . . . . . . 22
UUnimpeded flow section . . . . . . . . 27
WWarranty and guarantee provisions . 7
Index
19.02.2016 RVM/U-L2 Module BASICS Flow Monitor 75