26
FEMININE NAPKIN DISPOSAL TOILET STALL ELEVATION FLUSH VALVE HANDLE WALL MTD. W.C. ADA ACCESSIBLE TOILET PAPER DISPENSER 44" Max 2' - 10" Max 1' - 0" 3' - 0" 39" - 41" 4' - 6" ADA ACCESSIBLE TOILET STALL PLAN 4" 2' - 8" Clr Typ. 1' - 6" 5' - 0" Clear 1' - 0" 2' - 0" (if floor mounted) 4'-11" Min (if wall mounted) 4' - 8" Min 3' - 6" Max 1' - 0" ADA ACCESSIBLE SINK 3' - 4" Max 2' - 10" Max 2' - 5" Min 2' - 3" 9" 8" Min 6" min toe clearance ADA GUIDELINES 1' - 6" 48" Max 33" - 36" 38" Max CONTROL AREA ADA ACCESSIBLE SHOWER SOAP DISPENSER PAPER TOWEL DISP. ELECTRIC WATER COOLER WORK SURFACE CONFIGURE EXPOSED HOT WATER & DRAIN PIPES AGAINST CONTACT SINK & MIRROR/ URINAL DISTANCE TO HIGHEST PART OF PHONE ESSENTIAL TO BASIC OPERATION TELEPHONE TILTED MIRROR @ HC LOCATIONS ONLY VARIOUS SIGNS ALL OPERATING DEVICES (I.E.LIGHT SWITCHES, ETC.) 4' - 0" Max 3' - 8" Max Min 1' - 5" 3' - 4" Max 2' - 5" Min 2' - 10" Max 5' - 0" Max 4' - 6" Max Bubbler 36" Max 4' - 0" Max 4' - 0" Max ACCESSORY MOUNTING HEIGHTS 48" Max 42" Min FIRE ALARM PULL STATIONS Bubbler 39" Min - 43" Max High Low 7" 3' - 3" Clr. 1' - 3" Partition Screen NORTH 1 A101 SIM A101 1 SIM SCALE: A B 2/A4.1 1'-0" = 1'-0" M4 DETAIL BUBBLE: AS DESCRIBED IN THE PROJECT IDENTIFIES ROOM NAME & NUMBER ROOM NAME/ NO. TAG: "ROOM FINISH SCHEDULE" IDENTIFIES LOCATION OF CHANGES REVISION TAG/ CLOUD: ON ALL WORKING DRAWINGS IDENTIFIES THE LOCATION OF THE ELEVATION TAG: WORKING DRAWINGS SET ELEVATION INDICATED WITHIN THE WALL SECTION TAG: WALL SECTION INDICATED WITHIN THE WORKING DRAWINGS SET IDENTIFIES THE LOCATION OF THE THE ENLARGED DETAIL FOR THE AREA INDICATED WITHIN THE WORKING DRAWINGS SET IDENTIFIES THE LOCATION OF KEYNOTE TAG: ALL ARCHITECTURAL DRAWINGS IDENTIFIES PROPOSED WORK ON PARTITION TAG: PLAN TITLE & NO. ARROW: IDENTIFIES THE PLAN NAME, NUMBER, SCALE, & ORIENTATION ON THE SITE IDENTIFIES THE NAME, NUMBER, & SCALE OF THE DETAIL DETAIL TITLE: DOOR TAG: "DOOR & HARDWARE SCHEDULE" AS DESCRIBED IN THE PROJECT IDENTIFIES DOOR & FRAME TYPES AS DESCRIBED IN THE PROJECT "PARTITION TYPE LEGEND" IDENTIFIES PARTITION TYPES IDENTIFIES WINDOW OR FRAME TYPES. WINDOW/ FRAME TAG: OF THE ITEM INDICATED IDENTIFIES THE VERTICAL ELEVATION ELEVATION TARGET: IDENTIFIES THE PROPOSED STRUCTURAL GRID STRUCTURAL GRID LINES (PROPOSED) 2 PREFERRED ROOM NAME INCREMENTAL ROOM NUMBER INCREMENTAL REVISION NUMBER ELEVATION NUMBER SHEET NUMBER SPECIFICATION SECTION SHEET NUMBER NO TAIL = BUILDING SECTION DETAIL NUMBER BOXED TAIL = WALL SECTION INCREMENTAL NOTE NUMBER SHEET NUMBER DETAIL NUMBER INCREMENTAL DOOR & FRAME IDENTIFIER INCREMENTAL WINDOW OR FRAME IDENTIFIER WALL TYPE DESIGNATION INCREMENTAL NOTE NUMBER 2 T.O. SLAB EL. 100'-0' 101A ROOM NAME 101 CW-X 10000-1 1 TITLE SCALE: 1/8" = 1'-0" TITLE 2 1 3 SHEET TITLE DATE PROJECT All concepts, ideas, designs, plans and details as shown on this document are the sole property of Design Collaborative, Inc., and shall not be used for any purpose without their expressed written consent. The owner shall be permitted to retain copies for information and reference. CERTIFICATION 200 East Main Street - Suite 600 Fort Wayne, Indiana 46802 260.422.4241 260.422.4847 designcollaborative.com 04/19/2017 2017.0036 BETHANY SEMINARY RENOVATIONS RICHMOND, INDIANA a p f w 4/19/2017 4:25:14 PM G0.1 Project Cover Sheet P1.1 Plumbing Plans - Basement & Main Level M1.1 Mechanical Plans - Lower and Main Level E0.0 General Electrical ED1.1 Electrical Demolition Plan - Main & Second Levels E1.1 Power Plan - Lower, Main, & Second Levels E2.1 Lighting Plan - Lower, Main, & Second Levels E4.1 Electrical Schedules E6.1 Electrical Specifications G0.1 Project Cover Sheet G1.1 Project Phases A1.0 Floor Plan - Lower Level A1.1 Floor Plan - Main Level A1.2 Floor Plan - Second Level A9.0 Reflected Ceiling Plan - Lower Level A9.1 Reflected Ceiling Plan - Main Level A9.2 Reflected Ceiling Plan - Second Level A10.1 Casework, Interior & Frame Elevations A10.2 Casework Sections A11.0 Floor Finish Plan - Lower Level A11.1 Floor Finish Plan - Main Level A11.2 Floor Finish Plan - Second Level AD1.0 Demolition Floor Plan - Lower Level AD1.1 Demolition Floor Plan - Main Level AD1.2 Demolition Floor Plan - Second Level AD9.1 Demolition Ceiling Plan - Main Level AD9.2 Demolition Ceiling Plan - Second Level Owner Bethany Theological Seminary 615 National Rd W. Richmond, IN 47374 Voice:765-983-1800 Contact: Jeff Carter, President email: [email protected] Contact: Brenda Reish, Executive Director of Business Services & Treasurer email: [email protected] Architect, M&E Engineers Design Collaborative, Inc. 200 East Main Street Suite 600 Fort Wayne, Indiana 46802 Voice: 260-422-4241 Fax: 260-422-4847 Contacts: Tim Terman - Project Manager email: [email protected] Emily Larason - Interior Designer email: [email protected] Eric Sank email: [email protected] Terry Wagner email: [email protected] Acoustic Consultant Haverstick Designs Voice: 317-373-0023 Contact: Gavin Haverstick, email: [email protected] ABBREVIATIONS PROJECT TEAM WORKING DRAWING INDEX RM ROOM RO ROUGH OPENING ROW RIGHT OF WAY RPC REINFORCED CONCRETE PIPE RRD RELIEF ROOF DRAIN S SOUTH S-___ SINK SA SUPPLY AIR SC SEALED CONCRETE SD STORM DRAIN SEC SECTION SHT SHEET SIM SIMILAR SL SLATE SMC SHEET METAL CONTRACTOR SPC SPECIFICATION (S) SPKR SPEAKER SQ SQUARE SS SOLID SURFACE STA STATION STC STAIR COMPONENT STD STANDARD STO STORAGE STR STRUCTURAL STS STAINLESS STEEL SV SHEET VINYL SYM SYMMETRY (ICAL) SYS SYSTEM T&G TONGUE AND GROOVE TB TERMINAL BOX TCC TEMPERATURE CONTROL CONTRACTOR TCP TEMPERATURE CONTROL PANEL TEL TELEPHONE THK THICK (NESS) TOS TOP OF STEEL TOW TOP OF WALL TSP TOTAL STATIC PRESSURE TTB TELEPHONE TERMINAL BOARD TV TELEVISION TYP TYPICAL U-___ URINAL UNO UNLESS NOTED OTHERWISE VB VAPOR BARRIER VCT VINYL COMPOSITE TILE VERT VERTICAL VFD VARIABLE FREQUENCY DRIVE VP VINYL PLANK VT VINYL TILE VTR VENT THRU ROOF VWC VINYL WALL COVERING W WEST WC-__ _ WATER CLOSET WD WOOD WH WATER HEATER WM WIRE MESH WMV WATER MIXING VALVE WO WITHOUT WOM WALK OFF MAT WPT WORKING POINT WWF WELDED WIRE FABRIC LVR LOUVER LVT LUXURY VINYL TILE LWT LEAVING WATER TEMPERATURE M METER (S) MAS MASONRY MAT MIXED AIR TEMPERATURE MATL MATERIALS MB-___ MOP BASIN MBH 1000 BTU PER HOUR MBM METAL BUILDING MANUFACTURER MC MECHANICAL CONTRACTOR MD MANUAL DAMPER MECH MECHANICAL MFGR MANUFACTURE (ER) MFR MANUFACTURING MH MANHOLE MIN MINIMUM MISC MISCELLANEOUS MM MILLIMETER (S) MO MASONRY OPENING MOD MOTOR OPERATED DAMPER MT MOUNT (ED), (ING) MTL METAL MTLS METALS N NORTH NIC NOT IN CONTRACT NOM NOMINAL NRC NOISE REDUCTION COEFFICIENT NTS NOT TO SCALE OA OUTSIDE AIR OAL OUTSIDE AIR LOUVER OC ON CENTER (S) OD OUTSIDE DIAMETER OH OVERHEAD OJ OPEN-WEB JOIST OPG OPENING OPH OPPOSITE HAND OPP OPPOSITE PCF POUNDS PER CUBIC FOOT PERF PERFERATE (D) PKG PARKING PL PLASTIC LAMINATE PLF POUNDS PER LINEAR FOOT PNL PANEL PNT PAINT (ED) PRL PROPERTY LINE PSF POUNDS PER SQUARE FOOT PSI POUNDS PER SQUARE INCH PT PORCELAIN TILE PTD PRESSURE TREATED PVC POLYVINYL CHLORIDE PVMT PAVEMENT PWD PLYWOOD QT QUARRY TILE RA RETURN AIR RAD RADIUS RB RUBBER BASE RD ROOF DRAIN REF REFERENCE REINF REINFORCING REV REVISION (S), REVISED RG RETURN REGISTER RH RIGHT HAND EQUIP EQUIPMENT ESP EXTERNAL STATIC PRESSURE EWC ELECTRIC WATER COOLER EWT ENTERING WATER TEMPERATURE EXH EXHAUST EXIST EXISTING EXP EXPOSED EXT EXTERIOR F.C. FORWARD CURVED FAN FA FIRE ALARM FAV FIELD APPLIED VINYL FD FIRE DAMPER FD-___ FLOOR DRAIN FDC FIRE DEPARTMENT CONNECTION FDN FOUNDATION FE FIRE EXTINGUISHER FEC FIRE EXTINGUISHER CABINET FF FINISH FLOOR FFE FINISH FLOOR ELEVATION FFL FINISH FLOOR LINE FIN FINISH FLR FLOOR (ING) FPC FIRE PROTECTION CONTRACTOR FPF FINS PER FOOT FTG FOOTING GA GAGE, GAUGE GALV GALVANIZED GC GENERAL CONTRACT (ORS) GD GARAGE DOOR GPM GALLONS PER MINUTE GYB GYPSUM BOARD GYP GYPSUM HB-___ HOSE BIBB HDR HEADER HDW HARDWARE HDWR HARDWARE HGHT HEIGHT HM HOLLOW METAL HOR HORIZONTAL HORIZ HORIZONTAL HP HEAT PUMP HT HEIGHT HTG HEATING HVAC HEATING/VENTILATION/AIR CONDITIONG ID INSIDE DIAMETER INC INCLUDE (D), (ING) INS INSULATE (D), (ING) INSUL INSULATION INT INTERIOR INV INVERT JC JANITOR'S CLOSET JT JOINT KIT KITCHEN L LENGHT (LONG) L- LAVATORY LAM LAMINATE (D) LAT LEAVING AIR TEMPERATURE LAV LAVATORY LH LEFT HAND LL LIVE LOAD LT LIGHT A/C AIR CONDITIONING AB ANCHOR BOLT ADD ADDENDUM ADJ ADJACENT AFF ABOVE FINISH FLOOR AFS ABOVE FINISH SLAB ALT ALTERNATE ALUM ALUMINUM ANOD ANODIZED AP ACCESS PANEL APD AIR PRESSURE DROP ARCH ARCHITECT (URAL) AT ACOUSTICAL TILE AUTO AUTOMATIC BD BOARD BDD BACKDRAFT DAMPER BLDG BUILDING BLKG BLOCKING BM BENCH MARK BOM BOTTOM OF MASONRY BOS BOTTOM OF STEEL BOT BOTTOM BRG BEARING BSMT BASEMENT CAB CABINET CB CATCH BASIN CFM CUBIC FEET PER MINUTE CFT CUBIC FOOT (C.F.) CG CORNER GUARD CJ CONTROL JOINT CL CLOSET CLG CEILING CLR CLEAR (ANCE) CMU CONCRETE MASONRY UNIT CO CLEAR OUT COL COLUMN CONC CONCRETE CONST CONSTRUCTION CONT CONTINUOS (CONTINUE) CONTR CONTRACT (OR) CT CERAMIC TILE CYD CUBIC YARD (C.Y.) DF DRINKING FOUNTAIN DIA DIAMETER (DIA.) DIAG DIAGONAL DIM DIMENSION DIV DIVISION DR DOOR DS DOWN SPOUT DTL DETAIL DWG DRAWING E EAST EA EACH EAL EXHAUST AIR LOUVER EAT ENTERING AIR TEMPERATURE EC ELECTRICAL CONTRACTOR EF EACH FACE EFA EXHAUST FAN EG EXHAUST GRILLE EJ EXPANSION JOINT EL ELEVATION ELEC ELECTRIC (AL) ELEV ELEVATOR EMER EMERGENCY EQ EQUAL GRAPHIC SYMBOLS LEGEND BETHANY SEMINARY RENOVATIONS CONSTRUCTION DOCUMENT SET April 19, 2017 RICHMOND, IN No. Description Date

BETHANY SEMINARY RENOVATIONS - Thor …thor-construction.net/wp-content/uploads/2014/08/2017-04-19... · hb-___ hose bibb hdr header hdw hardware hdwr hardware hght height hm hollow

Embed Size (px)

Citation preview

FEMININENAPKINDISPOSAL

TOILET STALL ELEVATION

FLUSHVALVEHANDLE

WALL MTD.W.C.

ADA ACCESSIBLE

TOILETPAPERDISPENSER

44" M

ax

2' - 1

0"

Max1' - 0"

3' - 0"

39" - 41"4' - 6"

ADA ACCESSIBLE TOILET STALL PLAN

4"2'

- 8" C

lr

Typ.

1' - 6

" 5' - 0

" Clea

r

1' - 0

"2'

- 0"

(if floor mounted)4'-11" Min

(if wall mounted)4' - 8" Min

3' - 6"Max

1' - 0"

ADA ACCESSIBLE SINK

3' - 4

" Max

2' - 1

0" M

ax

2' - 5

" Min

2' - 3

"

9"

8" Min 6" min toe clearance

ADA GUIDELINES

1' - 6"

48" M

ax

33" -

36"

38" M

ax

CONTROLAREA

ADA ACCESSIBLE SHOWER

SOAPDISPENSER

PAPERTOWEL DISP.

ELECTRICWATER COOLERWORK SURFACE

CONFIGUREEXPOSEDHOT WATER& DRAINPIPESAGAINSTCONTACT

SINK & MIRROR/URINAL

DISTANCE TOHIGHEST PART OFPHONE ESSENTIALTO BASICOPERATION

TELEPHONE

TILTEDMIRROR@ HCLOCATIONSONLY

VARIOUSSIGNS

ALL OPERATINGDEVICES (I.E.LIGHTSWITCHES, ETC.)

4' - 0

" Max

3' - 8

" Max

Min

1' - 5

"

3' - 4

" Max

2' - 5

" Min

2' - 1

0" M

ax

5' - 0

" Max

4' - 6

" Max

Bubb

ler36

" Max

4' - 0

" Max

4' - 0

" Max

ACCESSORY MOUNTING HEIGHTS

48"

Max

42" M

in

FIRE ALARMPULL STATIONS

Bubb

ler39

" Min

- 43"

Max

High Low7"3'

- 3"

Clr.1' - 3"

Parti

tion

Scre

en

NORTH

1A101

SIM A1011

SIM

SCALE:

A

B

2/A4.1

1'-0" = 1'-0"

M4

DETAIL BUBBLE:AS DESCRIBED IN THE PROJECTIDENTIFIES ROOM NAME & NUMBERROOM NAME/ NO. TAG:

"ROOM FINISH SCHEDULE"

IDENTIFIES LOCATION OF CHANGESREVISION TAG/ CLOUD:ON ALL WORKING DRAWINGS

IDENTIFIES THE LOCATION OF THEELEVATION TAG:

WORKING DRAWINGS SETELEVATION INDICATED WITHIN THE

WALL SECTION TAG:WALL SECTION INDICATED WITHINTHE WORKING DRAWINGS SET

IDENTIFIES THE LOCATION OF THE

THE ENLARGED DETAIL FOR THEAREA INDICATED WITHIN THEWORKING DRAWINGS SET

IDENTIFIES THE LOCATION OF

KEYNOTE TAG:ALL ARCHITECTURAL DRAWINGSIDENTIFIES PROPOSED WORK ON

PARTITION TAG: PLAN TITLE & NO. ARROW:IDENTIFIES THE PLAN NAME, NUMBER, SCALE, &ORIENTATION ON THE SITE

IDENTIFIES THE NAME, NUMBER,& SCALE OF THE DETAIL

DETAIL TITLE:

DOOR TAG:

"DOOR & HARDWARE SCHEDULE"AS DESCRIBED IN THE PROJECTIDENTIFIES DOOR & FRAME TYPES

AS DESCRIBED IN THE PROJECT"PARTITION TYPE LEGEND"

IDENTIFIES PARTITION TYPES

IDENTIFIES WINDOW OR FRAME TYPES.WINDOW/ FRAME TAG:

OF THE ITEM INDICATEDIDENTIFIES THE VERTICAL ELEVATIONELEVATION TARGET:

IDENTIFIES THE PROPOSED STRUCTURAL GRIDSTRUCTURAL GRID LINES (PROPOSED)

2

PREFERREDROOM NAME

INCREMENTAL ROOMNUMBER

INCREMENTALREVISIONNUMBER

ELEVATIONNUMBER

SHEETNUMBER

SPECIFICATIONSECTION

SHEETNUMBER

NO TAIL = BUILDING SECTION

DETAILNUMBER

BOXED TAIL = WALL SECTION

INCREMENTALNOTE NUMBER

SHEET NUMBER

DETAIL NUMBER

INCREMENTALDOOR & FRAMEIDENTIFIER

INCREMENTAL WINDOW ORFRAME IDENTIFIER

WALL TYPEDESIGNATION

INCREMENTAL NOTENUMBER

2

T.O. SLABEL. 100'-0'

101AROOM NAME

101

CW-X10000-1 1 TITLE

SCALE: 1/8" = 1'-0"

TITLE

2 13SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/19

/201

7 4:

25:1

4 PM

G0.1

Project Cover Sheet

P1.1 Plumbing Plans - Basement & Main Level

M1.1 Mechanical Plans - Lower and Main Level

E0.0 General Electrical

ED1.1 Electrical Demolition Plan - Main &Second Levels

E1.1 Power Plan - Lower, Main, & SecondLevels

E2.1 Lighting Plan - Lower, Main, & SecondLevels

E4.1 Electrical Schedules

E6.1 Electrical Specifications

G0.1 Project Cover Sheet

G1.1 Project Phases

A1.0 Floor Plan - Lower LevelA1.1 Floor Plan - Main LevelA1.2 Floor Plan - Second Level

A9.0 Reflected Ceiling Plan - Lower LevelA9.1 Reflected Ceiling Plan - Main LevelA9.2 Reflected Ceiling Plan - Second Level

A10.1 Casework, Interior & Frame ElevationsA10.2 Casework Sections

A11.0 Floor Finish Plan - Lower LevelA11.1 Floor Finish Plan - Main LevelA11.2 Floor Finish Plan - Second Level

AD1.0 Demolition Floor Plan - Lower LevelAD1.1 Demolition Floor Plan - Main LevelAD1.2 Demolition Floor Plan - Second Level

AD9.1 Demolition Ceiling Plan - Main LevelAD9.2 Demolition Ceiling Plan - Second Level

OwnerBethany Theological Seminary

615 National Rd W.Richmond, IN 47374Voice:765-983-1800

Contact:Jeff Carter, President

email: [email protected]

Contact:Brenda Reish, Executive Director of

Business Services & Treasureremail: [email protected]

Architect, M&E EngineersDesign Collaborative, Inc.

200 East Main StreetSuite 600

Fort Wayne, Indiana 46802Voice: 260-422-4241 Fax: 260-422-4847

Contacts:

Tim Terman - Project Manageremail: [email protected]

Emily Larason - Interior Designeremail: [email protected]

Eric Sankemail: [email protected]

Terry Wagneremail: [email protected]

Acoustic ConsultantHaverstick Designs

Voice: 317-373-0023

Contact:Gavin Haverstick,

email: [email protected]

ABBREVIATIONS PROJECT TEAMWORKING DRAWING INDEX

RM ROOMRO ROUGH OPENINGROW RIGHT OF WAYRPC REINFORCED CONCRETE

PIPERRD RELIEF ROOF DRAINS SOUTHS-___ SINKSA SUPPLY AIRSC SEALED CONCRETESD STORM DRAINSEC SECTIONSHT SHEETSIM SIMILARSL SLATESMC SHEET METAL CONTRACTORSPC SPECIFICATION (S)SPKR SPEAKERSQ SQUARESS SOLID SURFACESTA STATIONSTC STAIR COMPONENTSTD STANDARDSTO STORAGESTR STRUCTURALSTS STAINLESS STEELSV SHEET VINYLSYM SYMMETRY (ICAL)SYS SYSTEMT&G TONGUE AND GROOVETB TERMINAL BOXTCC TEMPERATURE CONTROL

CONTRACTORTCP TEMPERATURE CONTROL

PANELTEL TELEPHONETHK THICK (NESS)TOS TOP OF STEELTOW TOP OF WALLTSP TOTAL STATIC PRESSURETTB TELEPHONE TERMINAL

BOARDTV TELEVISIONTYP TYPICALU-___ URINALUNO UNLESS NOTED OTHERWISEVB VAPOR BARRIERVCT VINYL COMPOSITE TILEVERT VERTICALVFD VARIABLE FREQUENCY

DRIVEVP VINYL PLANKVT VINYL TILEVTR VENT THRU ROOFVWC VINYL WALL COVERINGW WESTWC-___

WATER CLOSET

WD WOODWH WATER HEATERWM WIRE MESHWMV WATER MIXING VALVEWO WITHOUTWOM WALK OFF MATWPT WORKING POINTWWF WELDED WIRE FABRIC

LVR LOUVERLVT LUXURY VINYL TILELWT LEAVING WATER

TEMPERATUREM METER (S)MAS MASONRYMAT MIXED AIR TEMPERATUREMATL MATERIALSMB-___ MOP BASINMBH 1000 BTU PER HOURMBM METAL BUILDING

MANUFACTURERMC MECHANICAL CONTRACTORMD MANUAL DAMPERMECH MECHANICALMFGR MANUFACTURE (ER)MFR MANUFACTURINGMH MANHOLEMIN MINIMUMMISC MISCELLANEOUSMM MILLIMETER (S)MO MASONRY OPENINGMOD MOTOR OPERATED DAMPERMT MOUNT (ED), (ING)MTL METALMTLS METALSN NORTHNIC NOT IN CONTRACTNOM NOMINALNRC NOISE REDUCTION

COEFFICIENTNTS NOT TO SCALEOA OUTSIDE AIROAL OUTSIDE AIR LOUVEROC ON CENTER (S)OD OUTSIDE DIAMETEROH OVERHEADOJ OPEN-WEB JOISTOPG OPENINGOPH OPPOSITE HANDOPP OPPOSITEPCF POUNDS PER CUBIC FOOTPERF PERFERATE (D)PKG PARKINGPL PLASTIC LAMINATEPLF POUNDS PER LINEAR FOOTPNL PANELPNT PAINT (ED)PRL PROPERTY LINEPSF POUNDS PER SQUARE FOOTPSI POUNDS PER SQUARE INCHPT PORCELAIN TILEPTD PRESSURE TREATEDPVC POLYVINYL CHLORIDEPVMT PAVEMENTPWD PLYWOODQT QUARRY TILERA RETURN AIRRAD RADIUSRB RUBBER BASERD ROOF DRAINREF REFERENCEREINF REINFORCINGREV REVISION (S), REVISEDRG RETURN REGISTERRH RIGHT HAND

EQUIP EQUIPMENTESP EXTERNAL STATIC

PRESSUREEWC ELECTRIC WATER COOLEREWT ENTERING WATER

TEMPERATUREEXH EXHAUSTEXIST EXISTINGEXP EXPOSEDEXT EXTERIORF.C. FORWARD CURVED FANFA FIRE ALARMFAV FIELD APPLIED VINYLFD FIRE DAMPERFD-___ FLOOR DRAINFDC FIRE DEPARTMENT

CONNECTIONFDN FOUNDATIONFE FIRE EXTINGUISHERFEC FIRE EXTINGUISHER

CABINETFF FINISH FLOORFFE FINISH FLOOR ELEVATIONFFL FINISH FLOOR LINEFIN FINISHFLR FLOOR (ING)FPC FIRE PROTECTION

CONTRACTORFPF FINS PER FOOTFTG FOOTINGGA GAGE, GAUGEGALV GALVANIZEDGC GENERAL CONTRACT (ORS)GD GARAGE DOORGPM GALLONS PER MINUTEGYB GYPSUM BOARDGYP GYPSUMHB-___ HOSE BIBBHDR HEADERHDW HARDWAREHDWR HARDWAREHGHT HEIGHTHM HOLLOW METALHOR HORIZONTALHORIZ HORIZONTALHP HEAT PUMPHT HEIGHTHTG HEATINGHVAC HEATING/VENTILATION/AIR

CONDITIONGID INSIDE DIAMETERINC INCLUDE (D), (ING)INS INSULATE (D), (ING)INSUL INSULATIONINT INTERIORINV INVERTJC JANITOR'S CLOSETJT JOINTKIT KITCHENL LENGHT (LONG)L- LAVATORYLAM LAMINATE (D)LAT LEAVING AIR TEMPERATURELAV LAVATORYLH LEFT HANDLL LIVE LOADLT LIGHT

A/C AIR CONDITIONINGAB ANCHOR BOLTADD ADDENDUMADJ ADJACENTAFF ABOVE FINISH FLOORAFS ABOVE FINISH SLABALT ALTERNATEALUM ALUMINUMANOD ANODIZEDAP ACCESS PANELAPD AIR PRESSURE DROPARCH ARCHITECT (URAL)AT ACOUSTICAL TILEAUTO AUTOMATICBD BOARDBDD BACKDRAFT DAMPERBLDG BUILDINGBLKG BLOCKINGBM BENCH MARKBOM BOTTOM OF MASONRYBOS BOTTOM OF STEELBOT BOTTOMBRG BEARINGBSMT BASEMENTCAB CABINETCB CATCH BASINCFM CUBIC FEET PER MINUTECFT CUBIC FOOT (C.F.)CG CORNER GUARDCJ CONTROL JOINTCL CLOSETCLG CEILINGCLR CLEAR (ANCE)CMU CONCRETE MASONRY UNITCO CLEAR OUTCOL COLUMNCONC CONCRETECONST CONSTRUCTIONCONT CONTINUOS (CONTINUE)CONTR CONTRACT (OR)CT CERAMIC TILECYD CUBIC YARD (C.Y.)DF DRINKING FOUNTAINDIA DIAMETER (DIA.)DIAG DIAGONALDIM DIMENSIONDIV DIVISIONDR DOORDS DOWN SPOUTDTL DETAILDWG DRAWINGE EASTEA EACHEAL EXHAUST AIR LOUVEREAT ENTERING AIR

TEMPERATUREEC ELECTRICAL CONTRACTOREF EACH FACEEFA EXHAUST FANEG EXHAUST GRILLEEJ EXPANSION JOINTEL ELEVATIONELEC ELECTRIC (AL)ELEV ELEVATOREMER EMERGENCYEQ EQUAL

GRAPHIC SYMBOLS LEGEND

BETHANY SEMINARYRENOVATIONS

CONSTRUCTION DOCUMENT SETApril 19, 2017

RICHMOND, IN

No. Description Date

UP

UP

UP

UP

UP

DN

DN

DN

DN

RECORD STORAGEB01

ELEV.EQUIP

B02

ELEC.B05

MECH.B06

STAIRST-B5

CORR.B04

STORAGE/MECH.B10

OFFICEB03

COMMON OFFICEB02

STORAGE/MECH.B12

CLASSROOMB01

CLASSROOMB08

OFFICEB05

LOBBYB06

CORR.B09

STORAGEB11

R.R.B13

ServerB14

PROJECT 5

PROJECT 6

VEST.122

LOBBY100

VEST.130

RECEPTION104

COORIDOR103

STAIRST-1

CORRIDOR117

OFFICE119

OFFICE118

OFFICE116

OFFICE115

OFFICE114

OFFICE109

PRESIDENT107

OFFICE106

STORAGE131

GATHERING ROOM127

CONG. LIFE RESOURCECENTER

123

STORAGE124

STAIRST-4

RECEIVING/STORAGE126

WOMEN121

MEN102

ADMIN.112

ADMIN.110

MEETING HOUSE132

CHOIR ROOM133

ELEV.EL-1

ALCOVE101

STAIRST-5

OFFICE134

WORK ROOM00

KITCHEN129

PROJECT 1

PROJECT 3

PROJECT 2

OFFICE221

OFFICE220

OFFICE216

OFFICE215

ACADEMIC COOR.214

DEAN FACULTY209

CORRIDOR217

ELEV.EL-9

MEN202

WOMEN219

WORKROOM218

ADMIN.212

ADMIN.210

OFFICE204OFFICE

205OFFICE

206OFFICE

207

MECHANICAL229

STUDY ROOM228

CLASSROOM/SEMINAR227

CLASSROOM224

CLASSROOM223

CLOSET225

STAIRST-4

CORRIDOR226

STAIRST-2

LOBBY200

CORRIDOR203

ALCOVE201

MEETING HOUSE132

ORGAN CHAMBER

PROJECT 2

PROJECT 4

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/19

/201

7 3:

52:4

2 PM

G1.1

Project Phases

SCALE: 1/8" = 1'-0"3 Floor Plan - Lower Level

SCALE: 1/8" = 1'-0"1 Floor Plan - Main LevelSCALE: 1/8" = 1'-0"2 Floor Plan - Second Level

FOR FUNDING PURPOSES THE OWNER MAY CHOOSE TO AWARD THE ENTIRE SCOPE OF WORK OR SELECT PORTIONS OF THE WORK. ACCORDINGLY, THE PROJECTHAS BEEN BROKEN INTO A SERIES OF "PROJECTS." ALL WORK INDICATED THROUGHOUT THE CONSTRUCTION DRAWINGS (DEMOLITION, NEW CONSTRUCTION,FINISHES, PLUMBING, MECHANICAL, ELECTRICAL, ETC.) FOR THESE AREAS SHALL BE INCLUDED WITH THE "PROJECT" COST FOR THAT AREA AND IDENTIFIEDSEPARATELY ON THE BID FORM.

NOTE: PER THE "BID SOLICITATION" SECTION 000025 IT IS THE OWNER'S DESIRE TO PERFORM THIS WORK OVER THE SUMMER OF 2017. IN THE EVENT THERE ARECOST SAVINGS TO PERFORM THE WORK IN THE FALL/WINTER OF 2017-2018 SPACE HAS BEEN PROVIDED ON THE BID FORM TO INDICATE THE SAVINGS, IF ANY.

PROJECT #1: ALL WORK IDENTIFIED WITHIN THE GATHERING ROOM / CONGREGATIONAL LIFE RESOURCE CENTER / KITCHEN / STORAGE PORTION OF THE BUILDING, INCLUDING THE DEMOLITION WORK ON THE WEST WALL OF GATHERING ROOM 127 ADJOINING LOBBY 100.

PROJECT #2: ALL WORK IDENTIFIED WITHIN THE CHAPEL / MEETING ROOM 132 PORTION OF THE BUILDING.

PROJECT #3: ALL WORK IDENTIFIED WITHIN THE FIRST FLOOR LOBBY, RECEPTION AREA, CORRIDOR 103/117 AND OFFICE 106/107/134 AREAS.

PROJECT #4: ALL WORK IDENTIFIED WITHIN THE SECOND LOBBY, CORRIDOR 203/217 AND CLASSROOMS.

PROJECT #5: ALL WORK IDENTIFIED TO CREATE THE NEW LOWER LEVEL RESTROOM.

PROJECT #6: ALL WORK IDENTIFIED TO ENCLOSE A NEW LOWER LEVEL SERVER ROOM.

No. Description Date

H.5

F.1

G

GF.7 F.9

H

H

I

I

J

J

K

K

F

FE

E.1

D

D

.8.8

11

1.4

2 2

2.3

2.6

33

4

3.7

4.6

55

F.6 G.6

K.1

K.1

RECORD STORAGEB01

ELEC.B05

OFFICEB05

STORAGEB11

CLASSROOMB08

STAIRST-B5

LOBBYB06

ELEV.EQUIP

B02

STORAGE/MECH.B12

COMMON OFFICEB02

OFFICEB03 STORAGE/MECH.

B10MECH.

B06

CORR.B09

CORR.B04

CLASSROOMB01

D 504

D 104

DASHED SYMBOLS WITH DARKER LINEWEIGHTSINDICATE EXISTING WALL(S), PARTITION(S),DOOR(S), WINDOW(S), OTHER STRUCTURE ORAPPLIANCES, FIXTURES TO BE DEMOLISHED,REMOVED, OR RELOCATED (TYPICAL UNLESSNOTED OTHERWISE) ON THE DEMOLITION PLAN.

SYMBOLS WITH LIGHTER LINEWEIGHTS OR WITHPOCHE, AS SHOWN AT LEFT, INDICATE EXISTINGWALL(S), PARTITION(S), DOOR(S), WINDOW(S),OTHER STRUCTURE OR APPLIANCES, FIXTURESTO REMAIN (TYPICAL UNLESS NOTEDOTHERWISE) ON THE DEMOLITION PLAN.

SOLID SYMBOLS INDICATE NEW WALL(S),PARTITION(S), DOOR(S), WINDOW(S), OTHERSTRUCTURE OR APPLIANCES, FIXTURES TO BECONSTRUCTED. SEE PARTITION TYPES FORWALL MAKE UP.

DOTTED SYMBOLS WITH HATCHED INFILLINDICATES TEMPORARY WALL(S), PARTITION(S),DOOR(S), WINDOW(S), OTHER STRUCTURE.PARTITIONS TO RECEIVE 5/8" GYPSUM BOARDBOTH SIDES, TAPED. EXTEND TO DECK ABOVE.

PLAN LEGEND

ROOMS WITH POCHE, AS SHOWN AT LEFT,INDICATE EXISTING CONDITIONS/ROOMS NOT INSCOPE.

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/19

/201

7 3:

34:0

7 PM

AD1.0

Demolition Floor Plan -Lower Level

SCALE: 1/8" = 1'-0"1 Demolition Floor Plan - Lower Level

GENERAL DEMOLITION NOTES1 CONTRACTOR RESPONSIBLE FOR KEEPING BUILDING AND SITE

SECURE AND ALL OPENINGS COVERED DURING ALL STAGES OFDEMOLITION / CONSTRUCTION PROCESS TO PREVENT ANYUNAUTHORIZED ACCESS/ WEATHER DAMAGE.

2 CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SHORING ANDGENERAL BUILDING STABILITY DURING REMOVAL OF ANY WALLS,FLOOR,WINDOWS, DOORS, ETC., DURING DEMOLITION /CONSTRUCTION PROCESS.

3 DEMOLITION PLAN NOTES ARE GENERAL DESCRIPTION. PATCH /REPAIR ALL EXISTING SURFACES, WALLS, ETC. FROM REMOVAL OFDESCRIBED ITEMS. PATCHING AND REPAIRS SHALL MATCHEXISTING ADJACENT MATERIALS AND FINISH.

4 REMOVAL OF DOORS AND WINDOWS SHALL INCLUDE ALLHARDWARE, ANCHORS, SHIMS, SEALANT, AND ALL ASSOCIATEDDEVICES FOR DESCRIBED ITEMS, UNLESS OTHERWISE NOTED.EXISTING OPENINGS TO REMAIN SHALL BE CLEANED ANDPREPARED FOR NEW CONSTRUCTION

5 REMOVAL OF GENERAL ITEMS DESCRIBED SHALL INCLUDE ALLANCHORS, SCREWS, BOLTS, ETC. AFTER REMOVING SUCH ITEMS,PREPARE REMAINING WALLS, STRUCTURE, ETC. FOR NEWCONSTRUCTION.

6 REFER TO PLUMBING, MECHANICAL, AND ELECTRICAL DRAWINGSFOR SPECIFIC INFORMATION FOR REMOVAL OF ALL EQUIPMENT,PIPING, WIRING, DEVICES, ETC. COORDINATE REMOVAL OFDESCRIBED ITEMS WITH APPLICABLE TRADES.

7 SAW CUT AND REMOVE EXISTING CONCRETE SLAB AS REQUIREDFOR REMOVAL AND / OR INSTALLATION OF NEW UNDERGROUNDPIPING OR CONDUIT PER PLUMBING AND ELECTRICAL DRAWINGS.REFER TO STRUCTURAL DRAWINGS FOR TYPICAL SLABREPLACEMENT DETAIL.

8 PROVIDE ANY NECESSARY TEMPORARY PROTECTION TO MAINTAINWATERTIGHT EXTERIOR.

9 REMOVE ANY REMAINING CLIPS, ANCHORS, MISC. DEVICES, ANDFASTENERS FROM EXISTING SURFACES THAT ARE NOTSPECIFICALLY USED FOR REMAINING CONSTRUCTION. PATCH AND /OR REPAIR EXISTING SURFACES FOR NEW CONSTRUCTION ANDFINISHES.

PLAN CONSTRUCTION KEYNOTESD 104 SAWCUT & REMOVE PORTION OF SLAB AS

REQUIRED FOR INSTALLATION OF NEWPLUMBING.

D 504 REMOVE PORTION OF WALL FOR NEW WINDOW /DOOR/ EQUIPMENT OPENING AS SHOWN, SEERENOVATION PLAN. PROVIDE NEW LINTEL ASREQUIRED, SEE STRUCTURAL.

No. Description Date

6.5 6.5

H.5

F.1

G

GF.7 F.9

H

H

I

I

J

J

K

K

F

FE

E.1E.2

E.2

D.7

D.7

D

D

C

B

BA

A

.8.8

11

1.4

2 2

2.3

2.6

33

2.7

3.3

4

3.7

4.6

55

66

7 7

7.57.5

8 8

8.5 8.5

99

9.2 9.2

5.55.5

F.6 G.6

K.1

K.1

MEETING HOUSE132

CHOIR ROOM133

STORAGE131

LOBBY100

ALCOVE101

ELEV.EL-1

VEST.122

CONG. LIFE RESOURCECENTER

123

RECEIVING/STORAGE126

STAIRST-5

STAIRST-4

GATHERING ROOM127

KITCHEN129

STORAGE124

OFFICE119

OFFICE118

OFFICE116

OFFICE115

OFFICE114

STAIRST-1

OFFICE109

ADMIN.110

ADMIN.112

WORK ROOM00

WOMEN121

MEN102

PRESIDENT107

OFFICE106

RECEPTION104

VEST.130

D 101D 101

D 105

D 801D 507

D 507

D 501

D 801

D 801

D 801

D 501

D 501

D 501D 501

D 501

D 702

D 808D 808

P01

D 802 D 802

D 101D 101

D 106

LOCKERS125

D 803D 803

D 101D 101

D 10

1

D 101D 101 D 101D 101

D 501D 801

D 501

D 801

D 105D 105

D 105

D 807

D 501

D 501P01

D 107D 107

D 802D 802

D 501

D 10

7D

107

D 10

6D

106

D 106D 106

D 101D 101

D 105

D 10

7

D 101D 101

UP

DN

D 105

D 101D 101

UP

DN

D 10

7

D 106

D 809D 809

D 801

D 809D 809

7/A10.1

DASHED SYMBOLS WITH DARKER LINEWEIGHTSINDICATE EXISTING WALL(S), PARTITION(S),DOOR(S), WINDOW(S), OTHER STRUCTURE ORAPPLIANCES, FIXTURES TO BE DEMOLISHED,REMOVED, OR RELOCATED (TYPICAL UNLESSNOTED OTHERWISE) ON THE DEMOLITION PLAN.

SYMBOLS WITH LIGHTER LINEWEIGHTS OR WITHPOCHE, AS SHOWN AT LEFT, INDICATE EXISTINGWALL(S), PARTITION(S), DOOR(S), WINDOW(S),OTHER STRUCTURE OR APPLIANCES, FIXTURESTO REMAIN (TYPICAL UNLESS NOTEDOTHERWISE) ON THE DEMOLITION PLAN.

SOLID SYMBOLS INDICATE NEW WALL(S),PARTITION(S), DOOR(S), WINDOW(S), OTHERSTRUCTURE OR APPLIANCES, FIXTURES TO BECONSTRUCTED. SEE PARTITION TYPES FORWALL MAKE UP.

DOTTED SYMBOLS WITH HATCHED INFILLINDICATES TEMPORARY WALL(S), PARTITION(S),DOOR(S), WINDOW(S), OTHER STRUCTURE.PARTITIONS TO RECEIVE 5/8" GYPSUM BOARDBOTH SIDES, TAPED. EXTEND TO DECK ABOVE.

PLAN LEGEND

ROOMS WITH POCHE, AS SHOWN AT LEFT,INDICATE EXISTING CONDITIONS/ROOMS NOT INSCOPE.

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/19

/201

7 3:

34:3

0 PM

AD1.1

Demolition Floor Plan -Main Level

North

SCALE: 1/8" = 1'-0"1 Demolition Floor Plan - Main Level

GENERAL DEMOLITION NOTES1 CONTRACTOR RESPONSIBLE FOR KEEPING BUILDING AND SITE

SECURE AND ALL OPENINGS COVERED DURING ALL STAGES OFDEMOLITION / CONSTRUCTION PROCESS TO PREVENT ANYUNAUTHORIZED ACCESS/ WEATHER DAMAGE.

2 CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SHORING ANDGENERAL BUILDING STABILITY DURING REMOVAL OF ANY WALLS,FLOOR,WINDOWS, DOORS, ETC., DURING DEMOLITION /CONSTRUCTION PROCESS.

3 DEMOLITION PLAN NOTES ARE GENERAL DESCRIPTION. PATCH /REPAIR ALL EXISTING SURFACES, WALLS, ETC. FROM REMOVAL OFDESCRIBED ITEMS. PATCHING AND REPAIRS SHALL MATCHEXISTING ADJACENT MATERIALS AND FINISH.

4 REMOVAL OF DOORS AND WINDOWS SHALL INCLUDE ALLHARDWARE, ANCHORS, SHIMS, SEALANT, AND ALL ASSOCIATEDDEVICES FOR DESCRIBED ITEMS, UNLESS OTHERWISE NOTED.EXISTING OPENINGS TO REMAIN SHALL BE CLEANED ANDPREPARED FOR NEW CONSTRUCTION

5 REMOVAL OF GENERAL ITEMS DESCRIBED SHALL INCLUDE ALLANCHORS, SCREWS, BOLTS, ETC. AFTER REMOVING SUCH ITEMS,PREPARE REMAINING WALLS, STRUCTURE, ETC. FOR NEWCONSTRUCTION.

6 REFER TO PLUMBING, MECHANICAL, AND ELECTRICAL DRAWINGSFOR SPECIFIC INFORMATION FOR REMOVAL OF ALL EQUIPMENT,PIPING, WIRING, DEVICES, ETC. COORDINATE REMOVAL OFDESCRIBED ITEMS WITH APPLICABLE TRADES.

7 SAW CUT AND REMOVE EXISTING CONCRETE SLAB AS REQUIREDFOR REMOVAL AND / OR INSTALLATION OF NEW UNDERGROUNDPIPING OR CONDUIT PER PLUMBING AND ELECTRICAL DRAWINGS.REFER TO STRUCTURAL DRAWINGS FOR TYPICAL SLABREPLACEMENT DETAIL.

8 PROVIDE ANY NECESSARY TEMPORARY PROTECTION TO MAINTAINWATERTIGHT EXTERIOR.

9 REMOVE ANY REMAINING CLIPS, ANCHORS, MISC. DEVICES, ANDFASTENERS FROM EXISTING SURFACES THAT ARE NOTSPECIFICALLY USED FOR REMAINING CONSTRUCTION. PATCH AND /OR REPAIR EXISTING SURFACES FOR NEW CONSTRUCTION ANDFINISHES.

DEMOLITION KEYNOTESD 101 REMOVE VCT/CARPET FLOORING AND BASE COMPLETE.

PREPARE SUBSTRATE FOR NEW FINISHES INDICATED.D 105 REMOVE BRICK PAVERS AND BASE COMPLETE. PREPARE

SUBSTRATE FOR NEW FINISHES AS INDICATED.D 106 REMOVE HARDWOOD AND BASE COMPLETE. PREPARE

SUBSTRATE FOR NEW FINISHES AS INDICATEDD 107 REMOVE STAIR VINYL FINISH COMPLETE. CONTRACTOR TO

PREPARE SURFACES FOR NEW FINISHES. (SEE FINISHSCHEDULE).

D 501 REMOVE GYPSUM BOARD AND STUD WALL PARTITION(S)COMPLETE (OR PORTION AS INDICATED)

D 507 REMOVE BRICK VENEER COMPLETE (OR PORTION ASINDICATED). CONTRACTOR TO PREPARE SURFACES FOR NEWFINISH - SEE FINISH SCHEDULE.

D 702 REMOVE WINDOW AND FRAME COMPLETED 801 REMOVE CASEWORK/ CABINETRY/ COUNTER IN ITS ENTIRETY

(OR PORTION AS INDICATED). PATCH AND REPAIR WALLSURFACE AS REQUIRED TO MATCH EXISTING.

D 802 EXISTING CASEWORK/ CABINETRY/ COUNTER TO REMAIN.D 803 REMOVE METAL LOCKERS AND TRIM COMPLETE.D 807 REMOVE EXISTING FIREPLACE BRICK VENEER AND STRUCTURE

COMPLETE.D 808 REMOVE CASEWORK/ CABINETRY/ COUNTER IN ITS ENTIRETY

(OR PORTION AS INDICATED). PATCH AND REPAIR WALLSURFACE AS REQUIRED TO MATCH EXISTING. RELOCATECABINETS TO NEW LOCATION, COORDINATE WITH OWNER.

D 809 REMOVE WOOD CHAIRAIL COMPLETE, CONTRACTOR TOPREPARE SURFACES FOR NEW FINISH - SEE FINISH SCHEDULE.

P01 REMOVE PLUMBING FIXTURES AND RELATED ACCESSORIES.COORDINATE WITH PLUMBING.

No. Description Date

UP

6.5 6.5

H.5

F.1

G

GF.7 F.9

H

H

I

I

J

J

K

K

F

FE

E.1E.2

E.2

D.7

D.7

D

D

C

B

BA

A

.8.8

11

1.4

2 2

2.3

2.6

33

2.7

3.3

4

3.7

4.6

55

66

7 7

7.57.5

8 8

8.5 8.5

99

9.2 9.2

5.55.5

F.6 G.6

K.1

K.1

CLASSROOM223

CLASSROOM224

CLOSET225

STAIRST-4

CLASSROOM/SEMINAR227

STUDY ROOM228

LOBBY200

STAIRST-2

OFFICE221

OFFICE220

OFFICE216

OFFICE215

ACADEMIC COOR.214

DEAN FACULTY209

OFFICE207

OFFICE206

OFFICE205

OFFICE204

MEETING HOUSE132

MECHANICAL229

CORRIDOR203

CORRIDOR217

WORKROOM218

WOMEN219

MEN202

ADMIN.210

ADMIN.212

D 101D 101

D 101D 101

D 108D 108

D 101D 101

D 107

D 101D 101 D 101D 101

D 101D 101

D 107

D 101

D 107

ELEV.EL-9

ALCOVE201

D 10

7

DN

DN

(OPEN TO BELOW)

DASHED SYMBOLS WITH DARKER LINEWEIGHTSINDICATE EXISTING WALL(S), PARTITION(S),DOOR(S), WINDOW(S), OTHER STRUCTURE ORAPPLIANCES, FIXTURES TO BE DEMOLISHED,REMOVED, OR RELOCATED (TYPICAL UNLESSNOTED OTHERWISE) ON THE DEMOLITION PLAN.

SYMBOLS WITH LIGHTER LINEWEIGHTS OR WITHPOCHE, AS SHOWN AT LEFT, INDICATE EXISTINGWALL(S), PARTITION(S), DOOR(S), WINDOW(S),OTHER STRUCTURE OR APPLIANCES, FIXTURESTO REMAIN (TYPICAL UNLESS NOTEDOTHERWISE) ON THE DEMOLITION PLAN.

SOLID SYMBOLS INDICATE NEW WALL(S),PARTITION(S), DOOR(S), WINDOW(S), OTHERSTRUCTURE OR APPLIANCES, FIXTURES TO BECONSTRUCTED. SEE PARTITION TYPES FORWALL MAKE UP.

DOTTED SYMBOLS WITH HATCHED INFILLINDICATES TEMPORARY WALL(S), PARTITION(S),DOOR(S), WINDOW(S), OTHER STRUCTURE.PARTITIONS TO RECEIVE 5/8" GYPSUM BOARDBOTH SIDES, TAPED. EXTEND TO DECK ABOVE.

PLAN LEGEND

ROOMS WITH POCHE, AS SHOWN AT LEFT,INDICATE EXISTING CONDITIONS/ROOMS NOT INSCOPE.

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/19

/201

7 3:

34:5

3 PM

AD1.2

Demolition Floor Plan -Second Level

SCALE: 1/8" = 1'-0"1 Demolition Floor Plan - Second Level

GENERAL DEMOLITION NOTES1 CONTRACTOR RESPONSIBLE FOR KEEPING BUILDING AND SITE

SECURE AND ALL OPENINGS COVERED DURING ALL STAGES OFDEMOLITION / CONSTRUCTION PROCESS TO PREVENT ANYUNAUTHORIZED ACCESS/ WEATHER DAMAGE.

2 CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SHORING ANDGENERAL BUILDING STABILITY DURING REMOVAL OF ANY WALLS,FLOOR,WINDOWS, DOORS, ETC., DURING DEMOLITION /CONSTRUCTION PROCESS.

3 DEMOLITION PLAN NOTES ARE GENERAL DESCRIPTION. PATCH /REPAIR ALL EXISTING SURFACES, WALLS, ETC. FROM REMOVAL OFDESCRIBED ITEMS. PATCHING AND REPAIRS SHALL MATCHEXISTING ADJACENT MATERIALS AND FINISH.

4 REMOVAL OF DOORS AND WINDOWS SHALL INCLUDE ALLHARDWARE, ANCHORS, SHIMS, SEALANT, AND ALL ASSOCIATEDDEVICES FOR DESCRIBED ITEMS, UNLESS OTHERWISE NOTED.EXISTING OPENINGS TO REMAIN SHALL BE CLEANED ANDPREPARED FOR NEW CONSTRUCTION

5 REMOVAL OF GENERAL ITEMS DESCRIBED SHALL INCLUDE ALLANCHORS, SCREWS, BOLTS, ETC. AFTER REMOVING SUCH ITEMS,PREPARE REMAINING WALLS, STRUCTURE, ETC. FOR NEWCONSTRUCTION.

6 REFER TO PLUMBING, MECHANICAL, AND ELECTRICAL DRAWINGSFOR SPECIFIC INFORMATION FOR REMOVAL OF ALL EQUIPMENT,PIPING, WIRING, DEVICES, ETC. COORDINATE REMOVAL OFDESCRIBED ITEMS WITH APPLICABLE TRADES.

7 SAW CUT AND REMOVE EXISTING CONCRETE SLAB AS REQUIREDFOR REMOVAL AND / OR INSTALLATION OF NEW UNDERGROUNDPIPING OR CONDUIT PER PLUMBING AND ELECTRICAL DRAWINGS.REFER TO STRUCTURAL DRAWINGS FOR TYPICAL SLABREPLACEMENT DETAIL.

8 PROVIDE ANY NECESSARY TEMPORARY PROTECTION TO MAINTAINWATERTIGHT EXTERIOR.

9 REMOVE ANY REMAINING CLIPS, ANCHORS, MISC. DEVICES, ANDFASTENERS FROM EXISTING SURFACES THAT ARE NOTSPECIFICALLY USED FOR REMAINING CONSTRUCTION. PATCH AND /OR REPAIR EXISTING SURFACES FOR NEW CONSTRUCTION ANDFINISHES.

DEMOLITION KEYNOTESD 101 REMOVE VCT/CARPET FLOORING AND BASE COMPLETE.

PREPARE SUBSTRATE FOR NEW FINISHES INDICATED.D 107 REMOVE STAIR VINYL FINISH COMPLETE. CONTRACTOR TO

PREPARE SURFACES FOR NEW FINISHES. (SEE FINISHSCHEDULE).

D 108 REMOVE CARPET FLOORING COMPLETE, EXISTING WOOD BASETO REMAIN. PREPARE SUBSTRATE FOR NEW FLOORINGINDICATED.

No. Description Date

6.5 6.5

H.5

F.1 GF.7 F.9

H

H

I

I

J

J

K

K

F

FE

E.1E.2

E.2

D.7

D.7

D

D

C

B

BA

A

.8.8

11

1.4

2 2

2.3

2.6

33

2.7

3.3

4

3.7

4.6

55

66

7 7

7.57.5

8 8

8.5 8.5

99

9.2 9.2

5.55.5

F.6 G.6

K.1

K.1

CONG. LIFE RESOURCECENTER

123

RECEIVING/STORAGE126

STAIRST-5

STAIRST-4

KITCHEN129GATHERING ROOM

127

STORAGE124

LOBBY100

VEST.122

OFFICE119OFFICE

118OFFICE

116OFFICE

115

OFFICE114

STAIRST-1

OFFICE109

PRESIDENT107

OFFICE106

RECEPTION104

STORAGE131

MEETING HOUSE132

CHOIR ROOM133

ELEV.EL-1

WOMEN121

MEN102

ALCOVE101

WORK ROOM00

ADMIN.112

ADMIN.110

COORIDOR103

CORRIDOR117

D 904

D 904

D 904

D 904

D 903D 904

D 901D 906

D 901D 901

D 901D 901D 904

D 901D 901

D 901D 901D 901D 906

D 901D 906

D 906D 906 D 906D 906

D 901D 906

D 901D 906D 901D 901D 901D 906

D 901D 906

D 901D 906

D 905

D 906

D 904

2'x2' SUSPENDED ACOUSTICAL CEILING TILE ANDGRID SYSTEM. SEE FINISH LEGEND &SPECIFICATIONS FOR PANEL TYPE.

GYP. BD. CEILING. SEE FINISH LEGEND &SPECIFICATIONS FOR PAINT COLOR.

WALL SCONCE LIGHT FIXTURE

CAN OR PENDANT LIGHT FIXTURE

SLOPE ARROW - INDICATES SLOPE OF CEILING

LIGHT FIXTURE

2' - 0

"

NOTE:SOME SYMBOLS MAY NOT BE USED. SYMBOLS SHOWN ON PLANARE FOR REFERENCE ONLY. SEE MECHANICAL AND ELECTRICALDRAWINGS FOR ADDITIONAL INFORMATION.

2' - 0"

LIGHT FIXTURE NIGHT LIGHT.

EXPOSED STRUCTURE ABOVE. SEE GENERALREFLECTED CEILING PLAN NOTES FOR FINISHREQUIREMENTS.

2' - 0

"

2' - 0"

X'-X" / X'-X"

SLOPE

RCP SYMBOLS LEGEND

2'x2' SUSPENDED ACOUSTICAL CEILING TILEON EXISTING GRID SYSTEM. SEE FINISHLEGEND & SPECIFICATIONS FOR PANEL TYPE.

EXISTING WOOD CEILING SYSTEMS.

OS

TRACK LIGHT FIXTURES

OCCUPANCY SENSOR

EMERGENCY LIGHT FIXTURE

EMERGENCY EXIT FIXTURE

SUPPLY AIR DIFFUSER

RETURN AIR DIFFUSER

LINEAR SLOT AIR DIFFUSER

CEILING FAN UNIT

2'x2' EXISTING SUSPENDEDACOUSTICAL CEILING TILE AND GRIDSYSTEM TO REMAIN

2' - 0"

2' - 0

"

EXISTING GYP. BD. CEILING. PATCH ANDREPAIR AS NEEDED. SEE FINISH LEGEND& SPECIFICATIONS FOR PAINT COLOR.

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/19

/201

7 3:

35:1

9 PM

AD9.1

Demolition Ceiling Plan- Main Level

SCALE: 1/8" = 1'-0"1 Demolition Reflected Ceiling Plan - Main Level

GENERAL DEMOLITION NOTES1 CONTRACTOR RESPONSIBLE FOR KEEPING BUILDING AND SITE

SECURE AND ALL OPENINGS COVERED DURING ALL STAGES OFDEMOLITION / CONSTRUCTION PROCESS TO PREVENT ANYUNAUTHORIZED ACCESS/ WEATHER DAMAGE.

2 CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SHORING ANDGENERAL BUILDING STABILITY DURING REMOVAL OF ANY WALLS,FLOOR,WINDOWS, DOORS, ETC., DURING DEMOLITION /CONSTRUCTION PROCESS.

3 DEMOLITION PLAN NOTES ARE GENERAL DESCRIPTION. PATCH /REPAIR ALL EXISTING SURFACES, WALLS, ETC. FROM REMOVAL OFDESCRIBED ITEMS. PATCHING AND REPAIRS SHALL MATCHEXISTING ADJACENT MATERIALS AND FINISH.

4 REMOVAL OF DOORS AND WINDOWS SHALL INCLUDE ALLHARDWARE, ANCHORS, SHIMS, SEALANT, AND ALL ASSOCIATEDDEVICES FOR DESCRIBED ITEMS, UNLESS OTHERWISE NOTED.EXISTING OPENINGS TO REMAIN SHALL BE CLEANED ANDPREPARED FOR NEW CONSTRUCTION

5 REMOVAL OF GENERAL ITEMS DESCRIBED SHALL INCLUDE ALLANCHORS, SCREWS, BOLTS, ETC. AFTER REMOVING SUCH ITEMS,PREPARE REMAINING WALLS, STRUCTURE, ETC. FOR NEWCONSTRUCTION.

6 REFER TO PLUMBING, MECHANICAL, AND ELECTRICAL DRAWINGSFOR SPECIFIC INFORMATION FOR REMOVAL OF ALL EQUIPMENT,PIPING, WIRING, DEVICES, ETC. COORDINATE REMOVAL OFDESCRIBED ITEMS WITH APPLICABLE TRADES.

7 SAW CUT AND REMOVE EXISTING CONCRETE SLAB AS REQUIREDFOR REMOVAL AND / OR INSTALLATION OF NEW UNDERGROUNDPIPING OR CONDUIT PER PLUMBING AND ELECTRICAL DRAWINGS.REFER TO STRUCTURAL DRAWINGS FOR TYPICAL SLABREPLACEMENT DETAIL.

8 PROVIDE ANY NECESSARY TEMPORARY PROTECTION TO MAINTAINWATERTIGHT EXTERIOR.

9 REMOVE ANY REMAINING CLIPS, ANCHORS, MISC. DEVICES, ANDFASTENERS FROM EXISTING SURFACES THAT ARE NOTSPECIFICALLY USED FOR REMAINING CONSTRUCTION. PATCH AND /OR REPAIR EXISTING SURFACES FOR NEW CONSTRUCTION ANDFINISHES.

DEMOLITION KEYNOTESD 901 REMOVE SUSPENDED ACOUSTICAL TILE CEILING PADS,

GRID, AND ACCESSORIES COMPLETE.D 903 REMOVE PORTION OF BULKHEAD AS INDICATEDD 904 EXISTING HARD CEILING TO REMAIN - PREPARE FOR NEW

PAINT AND PATCH AS REQUIRED.D 905 REMOVE PORTION OF BRICK VENEER AS INDICATED.

PATCH GYP BULKHEAD AS SHOWN AND PREPARE FOR NEWFINISH.

D 906 EXISTING GRID TO REMAIN. CEILING TILES TO BEREPLACED COMPLETE.

NOTE: REFER TO MECHANICAL AND ELECTRICALDRAWINGS FOR CEILING MOUNTED DIFFUSERSAND LIGHT FIXTURES TO BE REMOVED.

No. Description Date

6.5 6.5

H.5

F.1

G

GF.7 F.9

H

H

I

I

J

J

K

K

F

FE

E.1E.2

E.2

D.7

D.7

D

D

C

B

BA

A

.8.8

11

1.4

2 2

2.3

2.6

33

2.7

3.3

4

3.7

4.6

55

66

7 7

7.57.5

8 8

8.5 8.5

99

9.2 9.2

5.55.5

F.6 G.6

K.1

K.1

CLASSROOM223

CLASSROOM224

CLOSET225

STAIRST-4

CORRIDOR226

CLASSROOM/SEMINAR227

STUDY ROOM228

LOBBY200

STAIRST-2

OFFICE221

OFFICE220

OFFICE216

OFFICE215

ACADEMIC COOR.214

DEAN FACULTY209

OFFICE207

OFFICE206

OFFICE205

OFFICE204

MEN202

WOMEN219

ELEV.EL-9

ALCOVE201

WORKROOM218

ADMIN.212

ADMIN.210

CORRIDOR203

CORRIDOR217

D 906D 906

D 906D 906

D 906D 906

D 906D 906D 906D 906

D 906

MEETING HOUSE132

MECHANICAL229

2'x2' SUSPENDED ACOUSTICAL CEILING TILE ANDGRID SYSTEM. SEE FINISH LEGEND &SPECIFICATIONS FOR PANEL TYPE.

GYP. BD. CEILING. SEE FINISH LEGEND &SPECIFICATIONS FOR PAINT COLOR.

WALL SCONCE LIGHT FIXTURE

CAN OR PENDANT LIGHT FIXTURE

SLOPE ARROW - INDICATES SLOPE OF CEILING

LIGHT FIXTURE

2' - 0

"

NOTE:SOME SYMBOLS MAY NOT BE USED. SYMBOLS SHOWN ON PLANARE FOR REFERENCE ONLY. SEE MECHANICAL AND ELECTRICALDRAWINGS FOR ADDITIONAL INFORMATION.

2' - 0"

LIGHT FIXTURE NIGHT LIGHT.

EXPOSED STRUCTURE ABOVE. SEE GENERALREFLECTED CEILING PLAN NOTES FOR FINISHREQUIREMENTS.

2' - 0

"

2' - 0"

X'-X" / X'-X"

SLOPE

RCP SYMBOLS LEGEND

2'x2' SUSPENDED ACOUSTICAL CEILING TILEON EXISTING GRID SYSTEM. SEE FINISHLEGEND & SPECIFICATIONS FOR PANEL TYPE.

EXISTING WOOD CEILING SYSTEMS.

OS

TRACK LIGHT FIXTURES

OCCUPANCY SENSOR

EMERGENCY LIGHT FIXTURE

EMERGENCY EXIT FIXTURE

SUPPLY AIR DIFFUSER

RETURN AIR DIFFUSER

LINEAR SLOT AIR DIFFUSER

CEILING FAN UNIT

2'x2' EXISTING SUSPENDEDACOUSTICAL CEILING TILE AND GRIDSYSTEM TO REMAIN

2' - 0"

2' - 0

"

EXISTING GYP. BD. CEILING. PATCH ANDREPAIR AS NEEDED. SEE FINISH LEGEND& SPECIFICATIONS FOR PAINT COLOR.

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/19

/201

7 3:

36:2

1 PM

AD9.2

Demolition Ceiling Plan- Second Level

SCALE: 1/8" = 1'-0"1 Demolition Reflected Ceiling Plan - Second Level

DEMOLITION KEYNOTESD 906 EXISTING GRID TO REMAIN. CEILING TILES TO BE REPLACED

COMPLETE.

GENERAL DEMOLITION NOTES1 CONTRACTOR RESPONSIBLE FOR KEEPING BUILDING AND SITE

SECURE AND ALL OPENINGS COVERED DURING ALL STAGES OFDEMOLITION / CONSTRUCTION PROCESS TO PREVENT ANYUNAUTHORIZED ACCESS/ WEATHER DAMAGE.

2 CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SHORING ANDGENERAL BUILDING STABILITY DURING REMOVAL OF ANY WALLS,FLOOR,WINDOWS, DOORS, ETC., DURING DEMOLITION /CONSTRUCTION PROCESS.

3 DEMOLITION PLAN NOTES ARE GENERAL DESCRIPTION. PATCH /REPAIR ALL EXISTING SURFACES, WALLS, ETC. FROM REMOVAL OFDESCRIBED ITEMS. PATCHING AND REPAIRS SHALL MATCHEXISTING ADJACENT MATERIALS AND FINISH.

4 REMOVAL OF DOORS AND WINDOWS SHALL INCLUDE ALLHARDWARE, ANCHORS, SHIMS, SEALANT, AND ALL ASSOCIATEDDEVICES FOR DESCRIBED ITEMS, UNLESS OTHERWISE NOTED.EXISTING OPENINGS TO REMAIN SHALL BE CLEANED ANDPREPARED FOR NEW CONSTRUCTION

5 REMOVAL OF GENERAL ITEMS DESCRIBED SHALL INCLUDE ALLANCHORS, SCREWS, BOLTS, ETC. AFTER REMOVING SUCH ITEMS,PREPARE REMAINING WALLS, STRUCTURE, ETC. FOR NEWCONSTRUCTION.

6 REFER TO PLUMBING, MECHANICAL, AND ELECTRICAL DRAWINGSFOR SPECIFIC INFORMATION FOR REMOVAL OF ALL EQUIPMENT,PIPING, WIRING, DEVICES, ETC. COORDINATE REMOVAL OFDESCRIBED ITEMS WITH APPLICABLE TRADES.

7 SAW CUT AND REMOVE EXISTING CONCRETE SLAB AS REQUIREDFOR REMOVAL AND / OR INSTALLATION OF NEW UNDERGROUNDPIPING OR CONDUIT PER PLUMBING AND ELECTRICAL DRAWINGS.REFER TO STRUCTURAL DRAWINGS FOR TYPICAL SLABREPLACEMENT DETAIL.

8 PROVIDE ANY NECESSARY TEMPORARY PROTECTION TO MAINTAINWATERTIGHT EXTERIOR.

9 REMOVE ANY REMAINING CLIPS, ANCHORS, MISC. DEVICES, ANDFASTENERS FROM EXISTING SURFACES THAT ARE NOTSPECIFICALLY USED FOR REMAINING CONSTRUCTION. PATCH AND /OR REPAIR EXISTING SURFACES FOR NEW CONSTRUCTION ANDFINISHES.

NOTE: REFER TO MECHANICAL AND ELECTRICALDRAWINGS FOR CEILING MOUNTED DIFFUSERSAND LIGHT FIXTURES TO BE REMOVED.

No. Description Date

UP

UP

DASHED SYMBOLS WITH DARKER LINEWEIGHTSINDICATE EXISTING WALL(S), PARTITION(S),DOOR(S), WINDOW(S), OTHER STRUCTURE ORAPPLIANCES, FIXTURES TO BE DEMOLISHED,REMOVED, OR RELOCATED (TYPICAL UNLESSNOTED OTHERWISE) ON THE DEMOLITION PLAN.

SYMBOLS WITH LIGHTER LINEWEIGHTS OR WITHPOCHE, AS SHOWN AT LEFT, INDICATE EXISTINGWALL(S), PARTITION(S), DOOR(S), WINDOW(S),OTHER STRUCTURE OR APPLIANCES, FIXTURESTO REMAIN (TYPICAL UNLESS NOTEDOTHERWISE) ON THE DEMOLITION PLAN.

SOLID SYMBOLS INDICATE NEW WALL(S),PARTITION(S), DOOR(S), WINDOW(S), OTHERSTRUCTURE OR APPLIANCES, FIXTURES TO BECONSTRUCTED. SEE PARTITION TYPES FORWALL MAKE UP.

DOTTED SYMBOLS WITH HATCHED INFILLINDICATES TEMPORARY WALL(S), PARTITION(S),DOOR(S), WINDOW(S), OTHER STRUCTURE.PARTITIONS TO RECEIVE 5/8" GYPSUM BOARDBOTH SIDES, TAPED. EXTEND TO DECK ABOVE.

PLAN LEGEND

ROOMS WITH POCHE, AS SHOWN AT LEFT,INDICATE EXISTING CONDITIONS/ROOMS NOT INSCOPE.

H.5

F.1

G

GF.7 F.9

H

H

I

I

J

J

K

K

F

FE

E.1

D

D

.8.8

11

1.4

2 2

2.3

2.6

33

4

3.7

4.6

55

F.6 G.6

K.1

K.1

RECORD STORAGEB01

ELEV.EQUIP

B02

ELEC.B05

MECH.B06

STAIRST-B5

CORR.B04

STORAGE/MECH.B10

OFFICEB03

COMMON OFFICEB02

STORAGE/MECH.B12

CLASSROOMB01

CLASSROOMB08

OFFICEB05

LOBBYB06

CORR.B09

STORAGEB11

R.R.B13

ServerB14

6' - 4 7/8"

8' - 6

"9'

- 8"

M4

M4

B14A

B13A

2A1.0

M6.1

M4

R.R.B13

1' - 3

1/4"

5' - 3

7/8"

1' - 6

"

2

4

56

7

8

M6.1 M4

M4

6' - 0"

1,3

2/A1

1.0

Mx - METAL STUD

PARTITION TYPE LEGEND

1' - 4"

3-5/8" (20GA) METAL STUDS @ 16" O.C. TODECK ABOVE W/ ONE (1) LAYER OF 5/8"TYPE "X" FIRECODE GYP. WALLBOARDEACH SIDE TO DECK ABOVE.

M4

M4-aGYP. BD. TO 6" MIN. ABOVE ADJ. CEILING.

M4-1HR(U.L. DES. #U419; NON-BRG. WALL RATING= 1 HR).

M4-bINC. BATT INSULATION WITHIN CAVITY

M4-abITEMS a+b ABOVE

6" (20GA) METAL STUDS @ 16" O.C. TODECK ABOVE W/ ONE (1) LAYER OF 5/8"TYPE "X" FIRECODE GYP. WALLBOARDEACH SIDE TO DECK ABOVE.

M6.1

M6.1-aGYP. BD. TO 6" MIN. ABOVE ADJ. CEILING.

M6.1-bINC. BATT INSULATION WITHIN CAVITY

M6.1-abITEMS a+b ABOVE

1' - 4"

1' - 4"

6" (20GA) METAL STUDS @ 16" O.C. TODECK ABOVE W/ ONE (1) LAYER OF 5/8"TYPE "X" FIRECODE GYP. WALLBOARDEACH SIDE TO DECK ABOVE.

M6

M6-1HR(U.L. DES. #U425; BRG. WALL RATING = 1HR).

M6-aGYP. BD. TO 6" MIN. ABOVE ADJ. CEILING.

M6-bINC. BATT INSULATION WITHIN CAVITY

M6-abITEMS a+b ABOVE

3-5/8" (20GA) METAL STUDS @ 16" O.C. TODECK ABOVE W/ ONE (1) LAYER OF 5/8"TYPE "X" FIRECODE GYP. WALLBOARDEACH SIDE TO DECK ABOVE.

M4.1

M4.1-aGYP. BD. TO 6" MIN. ABOVE ADJ. CEILING.

M4.1-bINC. BATT INSULATION WITHIN CAVITY

M4.1-abITEMS a+b ABOVE

1' - 4"

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/19

/201

7 3:

10:1

2 PM

A1.0

Floor Plan - LowerLevel

GENERAL NOTES1 CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND

CONDITIONS RELATIVE TO THE PROJECT PRIOR TO MATERIALFABRICATION AND INSTALLATION. CONFLICTS, OMISSIONS AND/ORDISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THEARCHITECT/ENGINEER IMMEDIATELY FOR RESOLUTION PRIOR TOPROCEEDING WITH THE WORK.

2 THIS PROJECT CONSISTS OF FIVE (5) INDIVIDUAL PROJECTS THAT,BASED ON BUDGET AND FUNDRAISING, MAY OR MAY NOT ALL BEAPROOVED AT THE SAME TIME.

3 ALL NEW WALL PARTITIONS SHALL BE M4b UNLESS NOTEDOTHERWISE. REFER TO PARTITION TYPE LEGEND FOR WALLPARTITION CONSTRUCTION INFORMATION.

North

SCALE: 1/8" = 1'-0"1 Floor Plan - Lower Level

PLAN CONSTRUCTION KEYNOTES

TOILET ACCESSORY SCHEDULEITEM NAME MANUFACTURER MODEL NUMBER

1 GRAB BAR, 18" LONG (VERTICAL) BOBRICK B-5806 X 182 GRAB BAR, 36" LONG BOBRICK B-5806 X 363 GRAB BAR, 42" LONG BOBRICK B-5806 X 424 PAPER TOWEL DISPENSER, SURFACE-MOUNTED BOBRICK B-2625 TOILET TISSUE HOLDER, SURFACE-MOUNTED BOBRICK B-28886 SANITARY NAPKIN DISPOSAL, SURFACE MOUNTED BOBRICK B-2547 24"x36" MIRROR BOBRICK B-165 24368 SOAP DISPENSOR OWNER PROVIDED

SCALE: 1/4" = 1'-0"2 Restroom - B13

No. Description Date

VEST.122

LOBBY100

VEST.130

RECEPTION104

COORIDOR103

STAIRST-1

CORRIDOR117

OFFICE119

OFFICE118

OFFICE116

OFFICE115

OFFICE114

OFFICE109

PRESIDENT107

OFFICE106

STORAGE131

GATHERING ROOM127

CONG. LIFE RESOURCECENTER

123

STORAGE124

STAIRST-4

RECEIVING/STORAGE126

WOMEN121

MEN102

ADMIN.112

ADMIN.110

MEETING HOUSE132

CHOIR ROOM133

ELEV.EL-1

ALCOVE101

STAIRST-5

6.5 6.5

H.5

F.1 GF.7 F.9

H

H

I

I

J

J

K

K

F

FE

E.1E.2

E.2

D.7

D.7

D

D

C

B

BA

A

.8.8

11

1.4

2 2

2.3

2.6

33

2.7

3.3

4

3.7

4.6

55

66

7 7

7.57.5

8 8

8.5 8.5

99

9.2 9.2

5.55.5

F.6 G.6

K.1

OFFICE134

20' - 3" 15' - 8" 12' - 0 1/2"

4/A1

0.1

6/A1

0.1

3' - 3

3/4"

1' - 1

0"5'

- 7"

9' - 6

1/2"

4' - 5

1/2" 4' - 0" 5' - 5 3/4"

5/A1

0.1

9/A10.1

14/A10.1

11/A

10.1

WORK ROOM00

KITCHEN129

5' - 6

"8'

- 4"

4' - 1

3/4"

2' - 8

"6'

- 6"

2A1.1

12/A

10.1

13/A

10.1

10/A10.1

4' - 9"

15/A

10.1

AG-1

18A10.1

120000-3

134A

M4b

M4

M4

M4

M4

2' - 7

"12

' - 9"

M6

M4a

M4b

M4b

UP

DN

64116-3

123661-7

64116-3

64116-3

105113-2

5A1.1

64116-4

8 1/4" 7 1/4"

UP

DN

UP

DN

12' - 5 3/8"

115200-1

115200-1 7/A10.1

REF.

64116-6

M4a

DASHED SYMBOLS WITH DARKER LINEWEIGHTSINDICATE EXISTING WALL(S), PARTITION(S),DOOR(S), WINDOW(S), OTHER STRUCTURE ORAPPLIANCES, FIXTURES TO BE DEMOLISHED,REMOVED, OR RELOCATED (TYPICAL UNLESSNOTED OTHERWISE) ON THE DEMOLITION PLAN.

SYMBOLS WITH LIGHTER LINEWEIGHTS OR WITHPOCHE, AS SHOWN AT LEFT, INDICATE EXISTINGWALL(S), PARTITION(S), DOOR(S), WINDOW(S),OTHER STRUCTURE OR APPLIANCES, FIXTURESTO REMAIN (TYPICAL UNLESS NOTEDOTHERWISE) ON THE DEMOLITION PLAN.

SOLID SYMBOLS INDICATE NEW WALL(S),PARTITION(S), DOOR(S), WINDOW(S), OTHERSTRUCTURE OR APPLIANCES, FIXTURES TO BECONSTRUCTED. SEE PARTITION TYPES FORWALL MAKE UP.

DOTTED SYMBOLS WITH HATCHED INFILLINDICATES TEMPORARY WALL(S), PARTITION(S),DOOR(S), WINDOW(S), OTHER STRUCTURE.PARTITIONS TO RECEIVE 5/8" GYPSUM BOARDBOTH SIDES, TAPED. EXTEND TO DECK ABOVE.

PLAN LEGEND

ROOMS WITH POCHE, AS SHOWN AT LEFT,INDICATE EXISTING CONDITIONS/ROOMS NOT INSCOPE.

F

F

4

55

1/A1

0.1

2/A1

0.1

8/A10.1

3/A10.1

1' - 0 1/4" 64116-5

64116-3

64116-3

R 8' - 0"

R 7' - 4"

123661-1

2"4"

2"

8"

2' - 1"

1' - 1 3/8"

R 7' - 11"

8"2'

- 6"

2" 4" 2"SS-1

PL-3

RB-1

PLASTICLAMINATE FACEDPLYWOOD, PL-3.

SOLID SURFACECOUNTERTOP WITH

BULLNOSE EDGE.

PRINTERPROVIDEDBY OWNER

COORDINATEPOWER OUTLETINSTALLATION

RB-1

PLAM BASE CABINET, PL-1

PROVIDEOPENING FORPOWER & DATACABLES

BASIS OF DESIGN: DOUGMOCKETT DP128-6-11/16"

ROUND TOP PULL6 1/2"

1' - 5

3/4"

4"

PLASTIC LAMINATE ON3/4" PARTICLE BOARD

WITH SELF EDGE, PL-2.

PROVIDE HARDWAREFOR PULL OUT PRINTER

DRAWER 2"

92900-4

2' - 1" 5 7/8"

NOTE:1. PLASTIC LAMINATE ALLEXPOSED SURFACES.3. SEE CASEWORK ELEVATIONFOR MOUNTING HEIGHT

2' - 1" 6 7/8"

RB-1

PLASTIC LAMINATE ON3/4 PARTICLE BOARD

WITH SELF EDGE, PL-2

PLAM BASE CABINET, PL-1

2' - 6

"

PROVIDE HARDWAREFOR FILE DRAWER

CABINETS

BASIS OF DESIGN:DOUG MOCKETT

DP128-6-11/16" ROUNDTOP PULL

RB-1

EQEQ

1"

PLASTICLAMINATE FACEDPLYWOOD, PL-3.

NOTE:1. PLASTIC LAMINATE ALLEXPOSED SURFACES.3. SEE CASEWORK ELEVATIONFOR MOUNTING HEIGHT

Mx - METAL STUD

PARTITION TYPE LEGEND

1' - 4"

3-5/8" (20GA) METAL STUDS @ 16" O.C. TODECK ABOVE W/ ONE (1) LAYER OF 5/8"TYPE "X" FIRECODE GYP. WALLBOARDEACH SIDE TO DECK ABOVE.

M4

M4-aGYP. BD. TO 6" MIN. ABOVE ADJ. CEILING.

M4-1HR(U.L. DES. #U419; NON-BRG. WALL RATING= 1 HR).

M4-bINC. BATT INSULATION WITHIN CAVITY

M4-abITEMS a+b ABOVE

6" (20GA) METAL STUDS @ 16" O.C. TODECK ABOVE W/ ONE (1) LAYER OF 5/8"TYPE "X" FIRECODE GYP. WALLBOARDEACH SIDE TO DECK ABOVE.

M6.1

M6.1-aGYP. BD. TO 6" MIN. ABOVE ADJ. CEILING.

M6.1-bINC. BATT INSULATION WITHIN CAVITY

M6.1-abITEMS a+b ABOVE

1' - 4"

1' - 4"

6" (20GA) METAL STUDS @ 16" O.C. TODECK ABOVE W/ ONE (1) LAYER OF 5/8"TYPE "X" FIRECODE GYP. WALLBOARDEACH SIDE TO DECK ABOVE.

M6

M6-1HR(U.L. DES. #U425; BRG. WALL RATING = 1HR).

M6-aGYP. BD. TO 6" MIN. ABOVE ADJ. CEILING.

M6-bINC. BATT INSULATION WITHIN CAVITY

M6-abITEMS a+b ABOVE

3-5/8" (20GA) METAL STUDS @ 16" O.C. TODECK ABOVE W/ ONE (1) LAYER OF 5/8"TYPE "X" FIRECODE GYP. WALLBOARDEACH SIDE TO DECK ABOVE.

M4.1

M4.1-aGYP. BD. TO 6" MIN. ABOVE ADJ. CEILING.

M4.1-bINC. BATT INSULATION WITHIN CAVITY

M4.1-abITEMS a+b ABOVE

1' - 4"

J

J

3.73.7

M4.

1aM

4.1a

1' - 5 1/2"

1' - 1 1/2"

1' - 5"

1' - 6

"1'

- 0"

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/19

/201

7 3:

10:3

7 PM

A1.1

Floor Plan - Main Level

North

SCALE: 1/8" = 1'-0"1 Floor Plan - Main Level

PLAN CONSTRUCTION KEYNOTES64116-3 SHOP FABRICATED PLASTIC LAMINATED COUNTERTOP AND

BACKSPLASH. PROVIDE BRACKET SUPPORTS FOR TOP. SEEA9. DRAWINGS FOR HEIGHT OF COUNTERTOPS.

64116-4 EXISTING CASEWORK TO REMAIN. EXISTING PLASTICLAMINATE COUNTERTOP TO BE REMOVED. PREPARESUBSTRATE FOR NEW FINISHES. REFER TO A9 DRAWINGS &FLOOR FINISH SCHEDULE FOR ADDITIONAL FINISHINFORMATION.

64116-5 PROVIDE 3" GROMMET, EQUAL TO DOUG MOCKETT XG- FLIPTOP SERIES - 3" HOLE

64116-692900-4 1/2" DRYWALL REVEAL. BASIS OF DESIGN - FRY REGLET

DRM-50-50, CLEAR ALUMINUM FINISH.105113-2 METAL LOCKERS EQUAL TO SALSBURY INDUSTRIES BOX

STYLE STANDARD LOCKER - 3 WIDE, MODEL #65352, FINISH:GRAY. SEE A10 SERIES FOR LOCATIONS.

115200-1 LG ELECTRONICS 65UH7700 65" 4K ULTRA SMART LED TV WITHECHOGEAR FULL MOTION ARTICULATING WALL MOUNTEGLF1-BK. SEE ELECTRICAL DRAWINGS FOR POWER ANDDATA.

120000-3 RECYCLING SYSTEM, EQUAL TO BUSCH SYSTEMS SPECTRUMSERIES - SPECTRUM CUBE SLIM & SPECTRUM ELLIPSE.VARIATION TO BE ELLIPSE-SLIM CUBE-ELLIPSE. BODY FINISH:GREY, LID FINISH: GREY - POWDER COAT FINISH, PROVIDE CANFOR PAPER, PLASTIC, AND CANS. OPENINGS: PAPER-SLOT,CANS-CIRCLE, PLASTIC - FULL.

123661-1 SOLID SURFACE COUNTERTOP. SEE FINISH PLANS &SCHEDULE FOR LOCATIONS & TYPES. SEE A10. SERIESSHEETS FOR COUNTER HEIGHTS.

123661-7 SOLID SURFACE COUNTERTOP WITH WATERFALL EDGEWRAPPING DOWN EXPOSED SIDES OF CASEWORK. SEE FINISHPLANS & SCHEDULE FOR LOCATIONS AND TYPE. SEE A10SERIES FOR COUNTER HEIGHTS.

SCALE: 1/4" = 1'-0"2 Reception Desk Enlarged Plan

SCALE: 1" = 1'-0"3 Reception File Storage

SCALE: 1" = 1'-0"4 Reception Printer Cabinet

SCALE: 1/4" = 1'-0"5 Kitchen Column Enlarged Detail

GENERAL NOTES1 CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND

CONDITIONS RELATIVE TO THE PROJECT PRIOR TO MATERIALFABRICATION AND INSTALLATION. CONFLICTS, OMISSIONS AND/ORDISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THEARCHITECT/ENGINEER IMMEDIATELY FOR RESOLUTION PRIOR TOPROCEEDING WITH THE WORK.

2 THIS PROJECT CONSISTS OF FIVE (5) INDIVIDUAL PROJECTS THAT,BASED ON BUDGET AND FUNDRAISING, MAY OR MAY NOT ALL BEAPROOVED AT THE SAME TIME.

3 ALL NEW WALL PARTITIONS SHALL BE M4b UNLESS NOTEDOTHERWISE. REFER TO PARTITION TYPE LEGEND FOR WALLPARTITION CONSTRUCTION INFORMATION.

No. Description Date

DN

DN

DN

DASHED SYMBOLS WITH DARKER LINEWEIGHTSINDICATE EXISTING WALL(S), PARTITION(S),DOOR(S), WINDOW(S), OTHER STRUCTURE ORAPPLIANCES, FIXTURES TO BE DEMOLISHED,REMOVED, OR RELOCATED (TYPICAL UNLESSNOTED OTHERWISE) ON THE DEMOLITION PLAN.

SYMBOLS WITH LIGHTER LINEWEIGHTS OR WITHPOCHE, AS SHOWN AT LEFT, INDICATE EXISTINGWALL(S), PARTITION(S), DOOR(S), WINDOW(S),OTHER STRUCTURE OR APPLIANCES, FIXTURESTO REMAIN (TYPICAL UNLESS NOTEDOTHERWISE) ON THE DEMOLITION PLAN.

SOLID SYMBOLS INDICATE NEW WALL(S),PARTITION(S), DOOR(S), WINDOW(S), OTHERSTRUCTURE OR APPLIANCES, FIXTURES TO BECONSTRUCTED. SEE PARTITION TYPES FORWALL MAKE UP.

DOTTED SYMBOLS WITH HATCHED INFILLINDICATES TEMPORARY WALL(S), PARTITION(S),DOOR(S), WINDOW(S), OTHER STRUCTURE.PARTITIONS TO RECEIVE 5/8" GYPSUM BOARDBOTH SIDES, TAPED. EXTEND TO DECK ABOVE.

PLAN LEGEND

ROOMS WITH POCHE, AS SHOWN AT LEFT,INDICATE EXISTING CONDITIONS/ROOMS NOT INSCOPE.

6.5

H.5

F.1 GF.7 F.9

H

H

I

I

J

J

K

K

F

FE

E.1E.2

E.2

D.7

D.7

D

D

C

B

BA

A

.8.8

11

1.4

2 2

2.3

2.6

33

2.7

3.3

4

3.7

4.6

55

66

7 7

7.57.5

8 8

8.5 8.5

99

9.2 9.2

5.5

F.6 G.6

K.1

K.1

OFFICE221

OFFICE220

OFFICE216

OFFICE215

ACADEMIC COOR.214

DEAN FACULTY209

CORRIDOR217

ELEV.EL-9

MEN202

WOMEN219

WORKROOM218

ADMIN.212

ADMIN.210

OFFICE204OFFICE

205OFFICE

206OFFICE

207

MECHANICAL229

STUDY ROOM228 CLASSROOM/SEMINAR

227

CLASSROOM224

CLASSROOM223

CLOSET225

STAIRST-4

CORRIDOR226

STAIRST-2

LOBBY200

CORRIDOR203

ALCOVE201

MEETING HOUSE132

ORGAN CHAMBER

83513-1

122416-1

122416-1

122416-1

122416-1

122416-1

122416-1

260000-2260000-2 260000-2260000-2

260000-2

260000-2

260000-2

260000-2

Mx - METAL STUD

PARTITION TYPE LEGEND

1' - 4"

3-5/8" (20GA) METAL STUDS @ 16" O.C. TODECK ABOVE W/ ONE (1) LAYER OF 5/8"TYPE "X" FIRECODE GYP. WALLBOARDEACH SIDE TO DECK ABOVE.

M4

M4-aGYP. BD. TO 6" MIN. ABOVE ADJ. CEILING.

M4-1HR(U.L. DES. #U419; NON-BRG. WALL RATING= 1 HR).

M4-bINC. BATT INSULATION WITHIN CAVITY

M4-abITEMS a+b ABOVE

6" (20GA) METAL STUDS @ 16" O.C. TODECK ABOVE W/ ONE (1) LAYER OF 5/8"TYPE "X" FIRECODE GYP. WALLBOARDEACH SIDE TO DECK ABOVE.

M6.1

M6.1-aGYP. BD. TO 6" MIN. ABOVE ADJ. CEILING.

M6.1-bINC. BATT INSULATION WITHIN CAVITY

M6.1-abITEMS a+b ABOVE

1' - 4"

1' - 4"

6" (20GA) METAL STUDS @ 16" O.C. TODECK ABOVE W/ ONE (1) LAYER OF 5/8"TYPE "X" FIRECODE GYP. WALLBOARDEACH SIDE TO DECK ABOVE.

M6

M6-1HR(U.L. DES. #U425; BRG. WALL RATING = 1HR).

M6-aGYP. BD. TO 6" MIN. ABOVE ADJ. CEILING.

M6-bINC. BATT INSULATION WITHIN CAVITY

M6-abITEMS a+b ABOVE

3-5/8" (20GA) METAL STUDS @ 16" O.C. TODECK ABOVE W/ ONE (1) LAYER OF 5/8"TYPE "X" FIRECODE GYP. WALLBOARDEACH SIDE TO DECK ABOVE.

M4.1

M4.1-aGYP. BD. TO 6" MIN. ABOVE ADJ. CEILING.

M4.1-bINC. BATT INSULATION WITHIN CAVITY

M4.1-abITEMS a+b ABOVE

1' - 4"

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/19

/201

7 3:

15:3

4 PM

A1.2

Floor Plan - SecondLevel

North

SCALE: 1/8" = 1'-0"1 Floor Plan - Second Level

PLAN CONSTRUCTION KEYNOTES83513-1 REPLACE EXISTING ACCORDION FOLDING DOOR. PANELFOLD

SONICWALL88 ACOUSTICAL PARTITION, STC 44, OR EQUAL.PROVIDE WITH TRACK, CARRIERS, & SWEEPSEALS FOR DOUBLEDOORS WITH DOUBLE END POSTS, LATCHING AT BOTH ENDS ANDAT CENTER. FINISH: TO BE SELECTED FROM COLOR GROUP C.

122416-1 MECHO SYSTEMS - ELECTRO SHADE: ELECTRO/3 - SEESPECIFICATIONS FOR DETAILS.

260000-2 REFER TO ELECTRICAL DRAWINGS FOR NEW FLOOR POWERBOXES TO BE INSTALLED IN THIS ROOM.

GENERAL NOTES1 CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND

CONDITIONS RELATIVE TO THE PROJECT PRIOR TO MATERIALFABRICATION AND INSTALLATION. CONFLICTS, OMISSIONS AND/ORDISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THEARCHITECT/ENGINEER IMMEDIATELY FOR RESOLUTION PRIOR TOPROCEEDING WITH THE WORK.

2 THIS PROJECT CONSISTS OF FIVE (5) INDIVIDUAL PROJECTS THAT,BASED ON BUDGET AND FUNDRAISING, MAY OR MAY NOT ALL BEAPROOVED AT THE SAME TIME.

3 ALL NEW WALL PARTITIONS SHALL BE M4b UNLESS NOTEDOTHERWISE. REFER TO PARTITION TYPE LEGEND FOR WALLPARTITION CONSTRUCTION INFORMATION.

No. Description Date

2'x2' SUSPENDED ACOUSTICAL CEILING TILE ANDGRID SYSTEM. SEE FINISH LEGEND &SPECIFICATIONS FOR PANEL TYPE.

GYP. BD. CEILING. SEE FINISH LEGEND &SPECIFICATIONS FOR PAINT COLOR.

WALL SCONCE LIGHT FIXTURE

CAN OR PENDANT LIGHT FIXTURE

SLOPE ARROW - INDICATES SLOPE OF CEILING

LIGHT FIXTURE

2' - 0

"

NOTE:SOME SYMBOLS MAY NOT BE USED. SYMBOLS SHOWN ON PLANARE FOR REFERENCE ONLY. SEE MECHANICAL AND ELECTRICALDRAWINGS FOR ADDITIONAL INFORMATION.

2' - 0"

LIGHT FIXTURE NIGHT LIGHT.

EXPOSED STRUCTURE ABOVE. SEE GENERALREFLECTED CEILING PLAN NOTES FOR FINISHREQUIREMENTS.

2' - 0

"

2' - 0"

X'-X" / X'-X"

SLOPE

RCP SYMBOLS LEGEND

2'x2' SUSPENDED ACOUSTICAL CEILING TILEON EXISTING GRID SYSTEM. SEE FINISHLEGEND & SPECIFICATIONS FOR PANEL TYPE.

EXISTING WOOD CEILING SYSTEMS.

OS

TRACK LIGHT FIXTURES

OCCUPANCY SENSOR

EMERGENCY LIGHT FIXTURE

EMERGENCY EXIT FIXTURE

SUPPLY AIR DIFFUSER

RETURN AIR DIFFUSER

LINEAR SLOT AIR DIFFUSER

CEILING FAN UNIT

2'x2' EXISTING SUSPENDEDACOUSTICAL CEILING TILE AND GRIDSYSTEM TO REMAIN

2' - 0"

2' - 0

"

EXISTING GYP. BD. CEILING. PATCH ANDREPAIR AS NEEDED. SEE FINISH LEGEND& SPECIFICATIONS FOR PAINT COLOR.

H.5

F.1

G

GF.7 F.9

H

H

I

I

J

J

K

K

F

FE

E.1

D

D

.8.8

11

1.4

2 2

2.3

2.6

33

4

3.7

4.6

55

F.6 G.6

K.1

K.1

RECORD STORAGEB01

LOBBYB06

CORR.B04

CORR.B09

CLASSROOMB08

OFFICEB05

ELEC.B05

STORAGEB11

STAIRST-B5

MECH.B06

STORAGE/MECH.B10

ServerB14

OFFICEB03

R.R.B13

COMMON OFFICEB02

CLASSROOMB01

ELEV.EQUIP

B02

STORAGE/MECH.B12

8' - 0" A.F.F.

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/19

/201

7 3:

16:0

4 PM

A9.0

Reflected Ceiling Plan -Lower Level

North

SCALE: 1/8" = 1'-0"1 Reflected Ceiling Plan - Lower Level

REFLECTED CEILING PLAN KEYNOTES

GENERAL RCP NOTES1 ALL ELEVATION MARKS MEASURED FROM DESIGNATED FLOOR TO

CEILING SURFACE.2 PAINT ALL VERTICAL & HORIZONTAL GYP. BD. BULKHEADS PNT-6,

UNLESS NOTED OTHERWISE3 PAINT ALL VERTICAL & HORIZONTAL HARD CEILINGS IN STAIRS PNT-6.

No. Description Date

OSA

OSA

OSA

OSA

OSA

OSA

OS

OS OS

6.5 6.5

H.5

F.1 GF.7 F.9

H

H

I

I

J

J

K

K

F

FE

E.1E.2

E.2

D.7

D.7

D

D

C

B

BA

A

.8.8

11

1.4

2 2

2.3

2.6

33

2.7

3.3

4

3.7

4.6

55

66

7 7

7.57.5

8 8

8.5 8.5

99

9.2 9.2

5.55.5

F.6 G.6

K.1

K.1

CONG. LIFE RESOURCECENTER

123

RECEIVING/STORAGE126

STAIRST-5

STAIRST-4

KITCHEN129

STORAGE124

LOBBY100

VEST.122

OFFICE119OFFICE

118OFFICE

116OFFICE

115

OFFICE114

STAIRST-1

OFFICE109

PRESIDENT107 OFFICE

106OFFICE

134

RECEPTION104

STORAGE131

MEETING HOUSE132

MEETING HOUSE132

CHOIR ROOM133

ELEV.EL-1

WOMEN121

MEN102

ALCOVE101

WORK ROOM00

ADMIN.112

ADMIN.110

COORIDOR103

CORRIDOR117

9' - 0" A.F.F.

7' - 10" A.F.F.

8' - 0" A.F.F.

9' - 0" A.F.F.

8' - 0" A.F.F.

8' - 0" A.F.F.

9' - 0" A.F.F.

8' - 0" A.F.F.

9' - 0" A.F.F.

8' - 0" A.F.F.

9' - 0" A.F.F.8' - 0" A.F.F.

8' - 0" A.F.F.

3' - 6"

1' - 1

0"

2' - 6 3/4"

8' - 0" A.F.F.

8' - 0" A.F.F.

8' - 0" A.F.F.

92900-8

92900-8

8' - 0" A.F.F.92900-7

95110-4

95110-495110-495110-495110-4

95110-4

95110-5

95110-4

95110-5

95110-5

9511

0-5

95110-5

95110-5

95110-4

95110-5 95110-4

95110-5

95110-5

95110-5

95110-5

95110-4

95110-5

95110-5

95110-4

95110-4

95110-4

95110-4

95110-6 95110-6

PNT-6ALL

SIDES

PNT-6ALL SIDES

8' - 0" A.F.F.

8' - 0" A.F.F.8' - 0" A.F.F.

95110-4 95110-4

95110-4

95110-4

95110-4

PNT-6ALL

SIDES

ALLSIDES

PNT-695110-6

95110-5

92900-8

VEST.130

95110-5

PNT-3ALL

SIDES

GATHERING ROOM127

LOBBY100

PNT-6

PNT-6

PNT-1

PNT-6

5 1/4"

5 1/2"

95110-5

2'x2' SUSPENDED ACOUSTICAL CEILING TILE ANDGRID SYSTEM. SEE FINISH LEGEND &SPECIFICATIONS FOR PANEL TYPE.

GYP. BD. CEILING. SEE FINISH LEGEND &SPECIFICATIONS FOR PAINT COLOR.

WALL SCONCE LIGHT FIXTURE

CAN OR PENDANT LIGHT FIXTURE

SLOPE ARROW - INDICATES SLOPE OF CEILING

LIGHT FIXTURE

2' - 0

"

NOTE:SOME SYMBOLS MAY NOT BE USED. SYMBOLS SHOWN ON PLANARE FOR REFERENCE ONLY. SEE MECHANICAL AND ELECTRICALDRAWINGS FOR ADDITIONAL INFORMATION.

2' - 0"

LIGHT FIXTURE NIGHT LIGHT.

EXPOSED STRUCTURE ABOVE. SEE GENERALREFLECTED CEILING PLAN NOTES FOR FINISHREQUIREMENTS.

2' - 0

"

2' - 0"

X'-X" / X'-X"

SLOPE

RCP SYMBOLS LEGEND

2'x2' SUSPENDED ACOUSTICAL CEILING TILEON EXISTING GRID SYSTEM. SEE FINISHLEGEND & SPECIFICATIONS FOR PANEL TYPE.

EXISTING WOOD CEILING SYSTEMS.

OS

TRACK LIGHT FIXTURES

OCCUPANCY SENSOR

EMERGENCY LIGHT FIXTURE

EMERGENCY EXIT FIXTURE

SUPPLY AIR DIFFUSER

RETURN AIR DIFFUSER

LINEAR SLOT AIR DIFFUSER

CEILING FAN UNIT

2'x2' EXISTING SUSPENDEDACOUSTICAL CEILING TILE AND GRIDSYSTEM TO REMAIN

2' - 0"

2' - 0

"

EXISTING GYP. BD. CEILING. PATCH ANDREPAIR AS NEEDED. SEE FINISH LEGEND& SPECIFICATIONS FOR PAINT COLOR.

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/19

/201

7 3:

16:2

6 PM

A9.1

Reflected Ceiling Plan -Main Level

North

SCALE: 1/8" = 1'-0"1 Reflected Ceiling Plan - Main Level

REFLECTED CEILING PLAN KEYNOTES92900-7 SUSPENDED GYPSUM BOARD CEILING SYSTEM. SEE

REFLECTED CEILING PLAN FOR LOCATIONS.92900-8 PATCH IN BULKHEAD WHERE EXISTING

WALLS/FIREPLACE/LIGHTS WERE REMOVED.95110-4 EXISTING CEILING TO REMAIN.95110-5 EXISTING CEILING GRID TO REMAIN. MODIFY AS NEEDED

WHERE EXISTING WALLS ARE DEMOLISHED. REPLACE TILESCOMPLETE.

95110-6 NEW CEILING GRID AND TILE.

GENERAL RCP NOTES1 ALL ELEVATION MARKS MEASURED FROM DESIGNATED FLOOR TO

CEILING SURFACE.2 PAINT ALL VERTICAL & HORIZONTAL GYP. BD. BULKHEADS PNT-6,

UNLESS NOTED OTHERWISE3 PAINT ALL VERTICAL & HORIZONTAL HARD CEILINGS IN STAIRS PNT-6.

No. Description Date

OSA OS

AOS

A

OSA

OSA

2'x2' SUSPENDED ACOUSTICAL CEILING TILE ANDGRID SYSTEM. SEE FINISH LEGEND &SPECIFICATIONS FOR PANEL TYPE.

GYP. BD. CEILING. SEE FINISH LEGEND &SPECIFICATIONS FOR PAINT COLOR.

WALL SCONCE LIGHT FIXTURE

CAN OR PENDANT LIGHT FIXTURE

SLOPE ARROW - INDICATES SLOPE OF CEILING

LIGHT FIXTURE

2' - 0

"

NOTE:SOME SYMBOLS MAY NOT BE USED. SYMBOLS SHOWN ON PLANARE FOR REFERENCE ONLY. SEE MECHANICAL AND ELECTRICALDRAWINGS FOR ADDITIONAL INFORMATION.

2' - 0"

LIGHT FIXTURE NIGHT LIGHT.

EXPOSED STRUCTURE ABOVE. SEE GENERALREFLECTED CEILING PLAN NOTES FOR FINISHREQUIREMENTS.

2' - 0

"

2' - 0"

X'-X" / X'-X"

SLOPE

RCP SYMBOLS LEGEND

2'x2' SUSPENDED ACOUSTICAL CEILING TILEON EXISTING GRID SYSTEM. SEE FINISHLEGEND & SPECIFICATIONS FOR PANEL TYPE.

EXISTING WOOD CEILING SYSTEMS.

OS

TRACK LIGHT FIXTURES

OCCUPANCY SENSOR

EMERGENCY LIGHT FIXTURE

EMERGENCY EXIT FIXTURE

SUPPLY AIR DIFFUSER

RETURN AIR DIFFUSER

LINEAR SLOT AIR DIFFUSER

CEILING FAN UNIT

2'x2' EXISTING SUSPENDEDACOUSTICAL CEILING TILE AND GRIDSYSTEM TO REMAIN

2' - 0"

2' - 0

"

EXISTING GYP. BD. CEILING. PATCH ANDREPAIR AS NEEDED. SEE FINISH LEGEND& SPECIFICATIONS FOR PAINT COLOR.

6.5 6.5

H.5

F.1

G

GF.7 F.9

H

H

I

I

J

J

K

K

F

FE

E.1E.2

E.2

D.7

D.7

D

D

C

B

BA

A

.8.8

11

1.4

2 2

2.3

2.6

33

2.7

3.3

4

3.7

4.6

55

66

7 7

7.57.5

8 8

8.5 8.5

99

9.2 9.2

5.55.5

F.6 G.6

K.1

K.1

CLASSROOM223

CLASSROOM224

CLOSET225

STAIRST-4

CORRIDOR226

CLASSROOM/SEMINAR227

STUDY ROOM228

LOBBY200

STAIRST-2

OFFICE221

OFFICE220

OFFICE216

OFFICE215

ACADEMIC COOR.214

DEAN FACULTY209

OFFICE207

OFFICE206

OFFICE205

OFFICE204

MEN202

WOMEN219

ELEV.EL-9

ALCOVE201

WORKROOM218

ADMIN.212

ADMIN.210

CORRIDOR203

CORRIDOR217

8' - 0" A.F.F.8' - 0" A.F.F.

8' - 0" A.F.F.

8' - 0" A.F.F.

95110-5 95110-5

95110-5

95110-5

95110-5

95110-495110-495110-495110-4

95110-4

95110-4

95110-4

95110-495110-4

95110-495110-495110-4

95110-4

95110-4

95110-4

95110-4

95110-4 95110-4 95110-4 95110-4

95110-5

95110-5CLASSROOM/SEMINAR

227

8' - 0" A.F.F.

95110-4

MECHANICAL229

MEETING HOUSE132

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/19

/201

7 3:

17:0

0 PM

A9.2

Reflected Ceiling Plan -Second Level

REFLECTED CEILING PLAN KEYNOTES95110-4 EXISTING CEILING TO REMAIN.95110-5 EXISTING CEILING GRID TO REMAIN. MODIFY AS NEEDED

WHERE EXISTING WALLS ARE DEMOLISHED. REPLACE TILESCOMPLETE.

North

SCALE: 1/8" = 1'-0"1 Reflected Ceiling Plan - Second Level

GENERAL RCP NOTES1 ALL ELEVATION MARKS MEASURED FROM DESIGNATED FLOOR TO

CEILING SURFACE.2 PAINT ALL VERTICAL & HORIZONTAL GYP. BD. BULKHEADS PNT-6,

UNLESS NOTED OTHERWISE3 PAINT ALL VERTICAL & HORIZONTAL HARD CEILINGS IN STAIRS PNT-6.

No. Description Date

FILLER1/4"

1' - 3" 1" 5' - 2 1/2" 1" 1' - 6"

FILLER1/4"

SS-1

64116-3

RB-1

3

4' - 1

0"8"

2' - 6

"

4

PL-3

FILE CABINETSTO RECIEVELOCKS

44313-1444313-14

PL-3

64116-1

2" 6" 5' - 4" 2" 2' - 8" 6" 1"

9' - 5"

11 1/2"8' - 2"

11 1/4"

9' - 0

" SS-1

RB-1

PL-3

44313-14 44313-14

1' - 2

"4'

- 8"

8"2'

- 2"

4"

5' - 1

0"3'

- 2"

64116-3

10' - 0 3/4"

92900-4

92900-4

1/2"

7 1/2"

1/2"

1 1/2"

FILLER1/4"

2' - 6" 2' - 9" 2' - 9" 1' - 3"

FILLER1/4"

1 1/2"

9' - 6 1/2"

2

7' - 0 1/2" 1' - 0" 1' - 6"

SS-1

64116-1

123661-131

110000-9

3' - 6

"

FILLER1/2"

2' - 6"1' - 3"1' - 3"

FILLER3/4"

FILLER1/2"

2' - 6"2' - 6"FILLER3/4"

5' - 1 1/4"

2' - 1

0"1'

- 8"

2' - 6

"

ALL CABINETS INTHIS LOCATION

TO RECIEVELOCKS

8

64116-2

64116-3

64116-1

4

VERIFY3' - 7" 2' - 6" 2' - 9" 2' - 6" 1' - 3" 3' - 0" 2' - 2" 1' - 9"

FILLER5 3/8"

2' - 0

"2'

- 6"

1' - 8

"2'

- 10"

FILLER1"

3' - 6" 1' - 2" 6' - 7" 1' - 3" 3' - 0" 2' - 5" 1' - 6"

FILLER2 3/8"

1' - 0"1' - 0"

9' - 0

"

64116-3

8

12

6' - 0

"1'

- 0"

5

1613

110000-8 110000-7224000-1

VERIFY21' - 8 3/8"

1' - 0

"

4

1 1/2"9' - 3 1/2"

1 1/2"

9' - 6 1/2"

PNT-1

PL-3

SS-1

123661-1

3' - 2

"4"

RB-1

1' - 6" 1' - 0" 7' - 0 1/2"265100-1

PNT-6

VERIFY3' - 1"

1"1' - 4" 1' - 9"

FILLER1"

61000-6

64116-3105113-2

6' - 4"

7

3' - 3"

6' - 0

"

2' - 1

0"3'

- 0"

3/4" 1' - 0" 3/4"

1/2" 3"

3/4"

6

PL-3

RB-1

SS-1

PNT-3ALL SIDES

2' - 6

"8"

4' - 8

"1'

- 2"

9' - 0

"

44313-142"

1"PL-3

1' - 5"

92900-492900-4

6' - 5 1/2"

64116-3

61000-6

FILLER3/4"

2' - 6"2' - 6"1' - 4"

FILLER3/4"

12 9

11

8' - 0

"

64116-12' - 6

"1'

- 4"

3' - 1

"1'

- 1"

FILLER1/4"

6' - 5"

FILLER1/4"

1/2"

3 1/2"

3/4"

1' - 2 1/2"3/4"3/4"

8' - 0"

8' - 0

"

4' - 0"4' - 0"

14

1' - 1

"

1/2"

1' - 2

"

1/2"

1' - 2

"

1/2"

1' - 2

"

1/2"

1' - 2

"

1/2"

1' - 2

"

1/2"

10"

PNT-2

92900-4

RB-1

4"2'

- 11"

MIN.

1' - 2

"EQ

EQ

110000-4

115200-1

5' - 6" 8' - 3 3/4" 2' - 8" 6' - 2"

PNT-3

4' - 2"

64116-3

64116-4

PNT-1ALL SIDES 110000-5

64116-4

PNT-6

6' - 2" 2' - 8" 4' - 1 3/4" 8' - 4" 5' - 6"

PNT-3

PNT-1

1' - 0

"8'

- 0"

110000-6

64300-3

PNT-1

PNT-644313-1444313-14PNT-2

PNT-3ALL SIDES

44313-1444313-14

PL-3

PNT-1

PNT-1

RB-1

SS-1PL-2

115200-1

92900-492900-4

10"

1/2"

1' - 2

"

1/2"

1' - 2

"

1/2"

1' - 2

"

1/2"

1' - 2

"

1/2"

1' - 2

"

1/2"

9"4"

PNT-2

92900-4

PL-3

RB-1

PNT-4ALL SIDES

PNT-1ALL SIDES

PNT-6

5

SimA10.1

ALL SIDES

HEAD DETAIL

JAMB DETAIL

5/8" GYP. BDEACH SIDE

5/8" GYP. BDEACH SIDE

METAL STUDS SEEPARTITION TYPES

HOLLOW METALFRAME PAINTED

(2) METAL STUDSEACH SIDE - SEEPARTITION TYPES

HOLLOW METALFRAME PAINTED W/ (3)JAMB ANCHORS PERJAMB, TYP.

SEALANT CONT.EACH SIDE

SEALANT CONT.EACH SIDE

DOOR, SEESCHEDULE

DOOR, SEESCHEDULE

2" 1"

SEE PLAN

SEE PLAN

2" 1"

1/2" TEMPERED GLASS, SEE SPECIFICATIONS

A. ALL H.M. WINDOW FRAMES SHALL WRAP WALL ASSEMBLY UNLESS NOTED OTHERWISE, OR INDICATED IN THE DETAILS.B. ALL H.M. FRAMES ARE TO BE PAINTED, SEE ROOM FINISH SCHEDULE FOR ADDITIONAL INFORMATION.C. ALL GLAZING TO MEET REQUIREMENTS FOR CHAPTER 24, 2014 INDIANA BUILDING CODE (2012 IBC).D. ALL WINDOW FRAMES ARE TO RECEIVE SEALANT BOTH SIDES, TYP.E. WINDOW FRAME DIMENSIONS SHOWN ARE NOMINAL, SEE SPECS.

SYMBOLS LEGEND

NOTES

1

WINDOW GLAZING AND FRAME TYPES

F NL

SEE

SCHE

DUL E

DOOR

HEI

GHT

2"

2"SEE SCHEDULE

DOOR WIDTH 2"

8' - 0

"

EQ EQ EQ

8' - 4"

1 1 1

2"7'

- 8"

2"

84423-2

1/8"

EQ EQ

CONTINUOUS SEALANTFOR GLASS CONNECTION

5/8" GYP BDEACH SIDE

BATT INSULLATION

STUDS, 16' O.C.

1' - 9"

FILLER5 1/2"

2' - 6" 2' - 6" 1' - 2" 1' - 2"

FILLER1/2"

2' - 6"2' - 6"

FILLER2 1/2"

1' - 0"1' - 0"

110000-10

9' - 7"

7' - 2 1/2"

110000-9

15 8

12 9

2' - 1

0"1'

- 8"

2' - 6

"2'

- 0"

9' - 0

"

64116-3

64116-1

64116-1

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/20

/201

7 9:

06:4

9 AM

A10.1

Casework, Interior &Frame Elevations

INTERIOR ELEVATION KEYNOTES44313-14 EXISTING BRICK VENEER TO REMAIN.61000-6 ADJUSTABLE MAILBOX CUBBIES, PL-1.64116-1 SHOP FABRICATED PLASTIC LAMINATE FACED BASE CABINETS.

PROVIDE ADA COMPLIANT PROTECTION SKIRT AT ALL SINKUNITS.

64116-2 SHOP FABRICATED PLASTIC LAMINATE FACED WALL CABINETSWITH ADJUSTABLE SHELVES.

64116-3 SHOP FABRICATED PLASTIC LAMINATED COUNTERTOP ANDBACKSPLASH. PROVIDE BRACKET SUPPORTS FOR TOP. SEE A9.DRAWINGS FOR HEIGHT OF COUNTERTOPS.

64116-4 EXISTING CASEWORK TO REMAIN. EXISTING PLASTIC LAMINATECOUNTERTOP TO BE REMOVED. PREPARE SUBSTRATE FORNEW FINISHES. REFER TO A9 DRAWINGS & FLOOR FINISHSCHEDULE FOR ADDITIONAL FINISH INFORMATION.

64300-3 EXISTING RAILINGS TO REMAIN.84423-2 CONTINUOUS SEALANT FOR GLASS CONNECTION.92900-4 1/2" DRYWALL REVEAL. BASIS OF DESIGN - FRY REGLET

DRM-50-50, CLEAR ALUMINUM FINISH.105113-2 METAL LOCKERS EQUAL TO SALSBURY INDUSTRIES BOX STYLE

STANDARD LOCKER - 3 WIDE, MODEL #65352, FINISH: GRAY. SEEA10 SERIES FOR LOCATIONS.

110000-4 BASIS OF DESIG: MAJESTIC ECHELON II - ECHEL60IN - DIRECTVENT GAS FIREPLACE . INTERIOR FINISH TO BE REFLECTIVEBLACK GLASS. FRONT FINISH TO BE CLEAN FACE FRONT INBLACK. FRAMING AND BLOCKING TO MATCH MANUFACTURERSPECIFICATIONS.

110000-5 EXISTING PARTITION DOOR AND EQUIPMENT TO REMAIN.110000-6 EXISTING WATER FOUNTAIN TO BE MOVED AND MOUNTED TO

NEW WALL. PROVIDE BLOCKING AS NEEDED.110000-7 OWNER FURNISHED/CONTRACTOR INSTALLED DISHWASHER.

PROVIDE POWER AND WATER TIE-INS FOR INSTALLER.110000-8 OWNER FURNISHED/CONTRACTOR INSTALLED REFRIGERATOR.

PROVIDE POWER AND WATER TIE-INS FOR INSTALLER.110000-9 OWNER FURNISHED/CONTRACTOR INSTALLED MICROWAVE.

PROVIDE POWER TIE-INS.110000-10 OWNER FURNISHED/CONTRACTOR INSTALLED COFFEE MAKER.

PROVIDE PWER AND WATER TIE-INS FOR INSTALLER.115200-1 LG ELECTRONICS 65UH7700 65" 4K ULTRA SMART LED TV WITH

ECHOGEAR FULL MOTION ARTICULATING WALL MOUNTEGLF1-BK. SEE ELECTRICAL DRAWINGS FOR POWER AND DATA.

123661-1 SOLID SURFACE COUNTERTOP. SEE FINISH PLANS & SCHEDULEFOR LOCATIONS & TYPES. SEE A10. SERIES SHEETS FORCOUNTER HEIGHTS.

224000-1 PLUMBING FIXTURE, SEE PLUMBING.265100-1 LIGHT FIXTURE, SEE ELECTRICAL

SCALE: 1/4" = 1'-0"1 Reception EastSCALE: 1/4" = 1'-0"2 Reception West

SCALE: 1/4" = 1'-0"4 Kitchen Island East

SCALE: 1/4" = 1'-0"8 Reception Files

SCALE: 1/4" = 1'-0"6 Kitchen EastSCALE: 1/4" = 1'-0"5 Kitchen Island West

SCALE: 1/4" = 1'-0"9 Student Lockers/Mailboxes

SCALE: 1/4" = 1'-0"3 Reception South

SCALE: 1/4" = 1'-0"10 Mailboxes

SCALE: 1/4" = 1'-0"14 Fireplace Elevation

SCALE: 1/4" = 1'-0"11 Gathering West

SCALE: 1/4" = 1'-0"12 Lobby EastSCALE: 1/4" = 1'-0"13 Lobby West

SCALE: 1/4" = 1'-0"15 Gathering East

DOOR SCHEDULEDOOR FRAME HEAD/

JAMBFIRE RATING

(MIN.) COMMENTSNO. W H T MAT. ELEV. MAT. ELEV.134A 3' - 0" 7' - 0" 1 3/4" WD NL HM - 17/A10.1 - 1B13A 3' - 0" 7' - 0" 1 3/4" WD F HM - 17/A10.1 -B14A 3' - 0" 7' - 0" 1 3/4" WD F HM - 17/A10.1 -

DOOR SCHEDULE COMMENTS1 NL DOOR STYLE TO MATCH EXISTING OFFICE DOORS.

SCALE: 1 1/2" = 1'-0"17 Metal Stud - HM FrameSCALE: 1/4" = 1'-0"

Door Elevations

SCALE: 1/4" = 1'-0"

Door Frame Elevations

SCALE: 1/4" = 1'-0"16 AG-1

SCALE: 1 1/2" = 1'-0"18 Glass Wall Jamb Detail

SCALE: 1/4" = 1'-0"7 Kitchen SouthNo. Description Date

MICROWAVEBY OWNER

COORDINATE POWEROUTLET INSTALLATIONWITH E.C.

RB-1

SS-1

2' - 1

1/2"

VERI

FY1'

- 2 1/

2"2"

3' - 6

"

3/4" PLASTICLAMINATE FACEDPARTICLE BOARD,PL-3

5"

SOLID SURFACEWATERFALL EDGE

COUNTERTOP, SEEFINISH SCHEDULE

RUBBER BASE,AS SCHEDULED

PROVIDE BACK PANELIN ALL CASEWORK

NOTE:1. PLASTIC LAMINATE ALLEXPOSED SURFACES.2. WHITE MELAMINE ON ALLINTERIOR SURFACES.

PROVIDE BLOCKING INWALL AS REQUIRED, TYP.

BASIS OF DESIGN:DOUG MOCKETT

DP128-6-11/16" ROUNDTOP PULL

P-LAM BASE CABINET

PLASTIC LAMINATEON 3/4" PARTICLE

BOARD WITH SELFEDGE, PL-2.

3/4" PLASTICLAMINATE FACEDPARTICLE BOARD,PL-3

RUBBER BASE,AS SCHEDULED

PROVIDE BACK PANELIN ALL CASEWORK

NOTE:1. PLASTIC LAMINATE ALLEXPOSED SURFACES.2. WHITE MELAMINE ON ALLINTERIOR SURFACES.

PROVIDE BLOCKING INWALL AS REQUIRED, TYP.

BASIS OF DESIGN:DOUG MOCKETT

DP128-6-11/16" ROUNDTOP PULL

P-LAM BASE CABINET

PRE-DRILLED ADJ.SHELF SYSTEM

3/4" MELAMINEADJUSTABLE SHELF

REF.

TO

CASE

WOR

K EL

EVAT

ION

SS-1

SOLID SURFACEWATERFALL EDGE

COUNTERTOP, SEEFINISH SCHEDULE

RB-1

BASIS OF DESIGN:DOUG MOCKETT

DP128-6-11/16" ROUNDTOP PULL

1' - 5" 1' - 1 1/2" 1' - 5 1/2"

3' - 4

1/2"

1 1/2"

3' - 6

"

SOLID SURFACECOUNTERTOP, SEEFINISH SCHEDULE

RUBBER BASE,AS SCHEDULED

PROVIDE BACK PANELIN ALL CASEWORK

NOTE:1. PLASTIC LAMINATE ALLEXPOSED SURFACES.2. WHITE MELAMINE ONALL INTERIOR SURFACES.

PROVIDE BLOCKING INWALL AS REQUIRED, TYP.

P-LAM BASE CABINET

SS-1

3/4" PLASTIC LAMINATEFACED PARTICLE BD,PL-3.

RB-1

VERIFY1' - 6"

WALLBEYOND

WALL MOUNTEDTV SCREEN, SEE

ELECTRICAL.

1/2" DRYWALLREVEAL, BASIS

OF DESIGN: FRYREGLETT. SEE

ELEVATIONS.

MAJESTIC DIRECT VENT GASFIREPLACE - ECHELON IIECHEL60IN. INSTALL PER

MANUFACTURER'S WRITTENINSTRUCTIONS.

RUBBER BASE ASSCHEDULED

REF.

TO

ELEV

.RE

F. T

O EL

EVAT

ION

REF.

TO

ELEV

.RE

F. T

O EL

EV.

REF.

TO

ELEV

.

3/4" PLASTIC LAMINATEWRAPPED PARTICLEBOARD MAIL CUBBY,PL-1

PROVIDE BLOCKING INWALL AS REQUIRED, TYP.

LINE OF WALL

REF.

TO

CASE

WOR

K EL

EV.

REF.

TO

CASE

WOR

K EL

EV.

PLASTIC LAMINATE ON3/4" PARTICLE BOARD

PRE-DRILLED ADJ.SHELF SYSTEM

P-LAM BASE CABINET

POST FORMED,BULLNOSE EDGE

RUBBER BASE,AS SCHEDULED

3/4" MELAMINEADJUSTABLE SHELF

PROVIDE BACK PANELIN ALL CASEWORK

NOTE:1. PLASTIC LAMINATE ALLEXPOSED SURFACES.2. WHITE MELAMINE ON ALLINTERIOR SURFACES.4"

1"

PROVIDE BACK PANELIN ALL CASEWORK

1' - 3"

BASIS OF DESIGN:DOUG MOCKETT

DP128-6-11/16" ROUNDTOP PULL

1' - 1"

4"

2' - 1"PLASTIC LAMINATE ON3/4" PARTICLE BOARD

POST FORMED,BULLNOSE EDGE

RUBBER BASE,AS SCHEDULED

PROVIDE BACK PANELIN ALL CASEWORK

NOTE:1. PLASTIC LAMINATE ALLEXPOSED SURFACES.2. WHITE MELAMINE ON ALLINTERIOR SURFACES.

SEE

CASE

WOR

K EL

EVAT

ION

4"

1"PROVIDE BLOCKING INWALL AS REQUIRED, TYP.

EQEQ

EQ

P-LAM BASE CABINET

PLASTIC LAMINATE BACKSPLASH. PROVIDE ENDSPLASH AT WALLCONDITIONS, TYP.

BASIS OF DESIGN:DOUG MOCKETT

DP128-6-11/16" ROUNDTOP PULL

4"

2' - 1"PLASTIC LAMINATE ON3/4" PARTICLE BOARD

PULL OUT TRASHRECEPTICAL BASE

CABINET

POST FORMED,BULLNOSE EDGE

RUBBER BASE,AS SCHEDULED

PROVIDE BACK PANELIN ALL CASEWORK

NOTE:1. PLASTIC LAMINATE ALLEXPOSED SURFACES.2. WHITE MELAMINE ON ALLINTERIOR SURFACES.

SEE

CASE

WOR

K EL

EVAT

ION

4"

PROVIDE BLOCKING INWALL AS REQUIRED, TYP.

PLASTIC LAMINATE BACKSPLASH. PROVIDE ENDSPLASH AT WALLCONDITIONS, TYP.

2' - 0

"

BASIS OF DESIGN:DOUG MOCKETT

DP128-6-11/16" ROUNDTOP PULL

CUTOUTS IN PANELFOR STANDARD

SIZE TRASH CAN

PROVIDE DRAWERHARDWARE NEEDED.

4"

2' - 1"PLASTIC LAMINATE ON3/4" PARTICLE BOARD

PRE-DRILLED ADJ.SHELF SYSTEM

P-LAM BASE CABINET

POST FORMED,BULLNOSE EDGE

RUBBER BASE,AS SCHEDULED

3/4" MELAMINEADJUSTABLE SHELF

PROVIDE BACK PANELIN ALL CASEWORK

NOTE:1. PLASTIC LAMINATE ALLEXPOSED SURFACES.2. WHITE MELAMINE ON ALLINTERIOR SURFACES.

SEE

CASE

WOR

K EL

EVAT

ION

4"

1"PROVIDE BLOCKING INWALL AS REQUIRED, TYP.

3/4" MELAMINEADJUSTABLE SHELF

PROVIDE BLOCKING INWALL AS REQUIRED, TYP.

LINE OF WALL

P-LAM WALLCABINETS

1' - 1"

BASIS OF DESIGN:DOUG MOCKETT

DP128-6-11/16" ROUNDTOP PULL

BASIS OF DESIGN:DOUG MOCKETT

DP128-6-11/16" ROUNDTOP PULL

PLASTIC LAMINATE ON3/4" PARTICLE BOARD

P-LAM BASE CABINET

POST FORMED,BULLNOSE EDGE

RUBBER BASE,AS SCHEDULED

PROVIDE BACK PANELIN ALL CASEWORK

3/4" MELAMINEADJUSTABLE SHELF

PROVIDE BLOCKING INWALL AS REQUIRED, TYP.

LINE OF WALL

PLASTIC LAMINATE BACKSPLASH. PROVIDE ENDSPLASH AT WALLCONDITIONS, TYP.

NOTE:1. PLASTIC LAMINATE ALLEXPOSED SURFACES.2. WHITE MELAMINE ON ALLINTERIOR SURFACES.

P-LAM WALLCABINETS

2' - 1

0" T

O TO

P OF

SIN

K RI

M AT

ADA

LOCA

TION

S, T

YP.

SEE

CASE

WOR

K EL

EVAT

ION

SEE

CASE

WOR

K EL

EVAT

ION

SEE

CASE

WOR

K EL

EVAT

ION

4"

2' - 1"

1' - 1"

4"

BLANK PANEL

SINK, SEE PLUMBINGDRAWINGS

BASIS OF DESIGN:DOUG MOCKETT

DP128-6-11/16" ROUNDTOP PULL

BASIS OF DESIGN:DOUG MOCKETT

DP128-6-11/16" ROUNDTOP PULL

REF.

TO

ELEV

.

1' - 1"

PROVIDEBLOCKING INWALL ASREQUIRED, TYP.

LINE OF WALL

P-LAM WALLCABINETS

BASIS OF DESIGN:DOUG MOCKETT

DP128-6-11/16" ROUNDTOP PULL

4"

2' - 1"PLASTIC LAMINATE ON3/4" PARTICLE BOARD

PRE-DRILLED ADJ.SHELF SYSTEM

P-LAM BASE CABINET

POST FORMED,BULLNOSE EDGE

RUBBER BASE,AS SCHEDULED

3/4" MELAMINEADJUSTABLE SHELF

PROVIDE BACK PANELIN ALL CASEWORK

NOTE:1. PLASTIC LAMINATE ALLEXPOSED SURFACES.2. WHITE MELAMINE ON ALLINTERIOR SURFACES.

SEE

CASE

WOR

K EL

EVAT

ION

4"

1"PROVIDE BLOCKING INWALL AS REQUIRED, TYP.

BASIS OF DESIGN:DOUG MOCKETT

DP128-6-11/16" ROUNDTOP PULL

1"1/2" BLACKMELAMINE BOARD.

2' - 1"PLASTIC LAMINATE ON3/4" PARTICLE BOARD

PRE-DRILLED ADJ.SHELF SYSTEM

P-LAM BASE CABINET

POST FORMED,BULLNOSE EDGE

RUBBER BASE,AS SCHEDULED

3/4" MELAMINEADJUSTABLE SHELF

PROVIDE BACK PANELIN ALL CASEWORK

NOTE:1. PLASTIC LAMINATE ALLEXPOSED SURFACES.2. WHITE MELAMINE ON ALLINTERIOR SURFACES.

PROVIDE BLOCKING INWALL AS REQUIRED, TYP.BASIS OF DESIGN:

DOUG MOCKETTDP128-6-11/16" ROUND

TOP PULL

4"

TAKE COUNTER INTOWINDOW TO FILL GAPBETWEEN CABINETAND WINDOW.

1' - 3"

SEE

CASE

WOR

K EL

EVAT

ION

4"EQ

EQEQ

EQ

1"

LINE OF WALLPLASTIC LAMINATE ON3/4" PARTICLE BOARD

WITH A POST FORMED,BULLNOSE EDGE.

P-LAM BASE CABINET

RUBBER BASE,AS SCHEDULED

PROVIDE BACK PANELIN ALL CASEWORK

NOTE:1. PLASTIC LAMINATE ALLEXPOSED SURFACES.2. WHITE MELAMINE ON ALLINTERIOR SURFACES.

BASIS OF DESIGN:DOUG MOCKETT

DP128-6-11/16" ROUNDTOP PULL

PROVIDE BLOCKING INWALL AS REQUIRED, TYP.

LINE OF WALL

SEE

CASE

WOR

K EL

EVAT

ION

1/2" PLASTICLAMINATE WRAPPEDPARTICLE BOARDMAIL CUBBY, PL-1

PROVIDE BLOCKING INWALL AS REQUIRED, TYP.

PROVIDE BACK PANELIN ALL CASEWORK

1' - 1"

3 1/2"

NOTE:1. PLASTIC LAMINATE ALLEXPOSED SURFACES.3. SEE CASEWORK ELEVATIONFOR MOUNTING HEIGHT

4"

2' - 1"PLASTIC LAMINATE ON3/4" PARTICLE BOARD

DRAWER & WIREPULL, SEE

ELEVATION

P-LAM BASE CABINET

POST FORMED,BULLNOSE EDGE

RUBBER BASE,AS SCHEDULED

PROVIDE BACK PANELIN ALL CASEWORK

NOTE:1. PLASTIC LAMINATE ALLEXPOSED SURFACES.2. WHITE MELAMINE ON ALLINTERIOR SURFACES.

SEE

CASE

WOR

K EL

EVAT

ION

4"

1" PROVIDE BLOCKING INWALL AS REQUIRED, TYP.

PLASTIC LAMINATE BACKSPLASH. PROVIDE ENDSPLASH AT WALLCONDITIONS, TYP.

EQEQ

PROVIDE HARDWAREFOR FILE DRAWER

CABINETS

3/4" MELAMINEADJUSTABLE SHELF

PROVIDE BLOCKING INWALL AS REQUIRED, TYP.

LINE OF WALLP-LAM WALL

CABINETS

SEE

CASE

WOR

K EL

EVAT

ION

1' - 1"

1' - 4

"

1' - 6"

MICROWAVEBY OWNER

COORDINATE POWEROUTLET INSTALLATION

NOTE:1. PLASTIC LAMINATE ALL EXPOSED SURFACES.2. WHITE MELAMINE ON ALL INTERIOR SURFACES.3. SEE CASEWORK ELEVATION FOR MOUNTING HEIGHT

BASIS OF DESIGN:DOUG MOCKETT

DP128-6-11/16" ROUNDTOP PULL

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/20

/201

7 9:

06:2

7 AM

A10.2

Casework Sections

SCALE: 1" = 1'-0"1 Bar Under Counter MicrowaveSCALE: 1" = 1'-0"3 Typ. Bar Base Cabinet

SCALE: 1" = 1'-0"2 Bar 4-Drawer Cabinet

SCALE: 1" = 1'-0"14 Fireplace Section

SCALE: 1" = 1'-0"7 Casework - Base & Student Mailboxes

SCALE: 1" = 1'-0"12 Casework - 4 Drawer - PL

SCALE: 1" = 1'-0"5 Casework - Trash Cabinet - PLSCALE: 1" = 1'-0"8 Casework - Typ. Base w/ Drawer & Wall - PL

SCALE: 1" = 1'-0"13 Casework - Typ. Sink Base & Wall - PL

SCALE: 1" = 1'-0"16 Fridge Wall Cabinet - PL

SCALE: 1" = 1'-0"9 Casework - Typ. Base w/ Drawer - PL

SCALE: 1" = 1'-0"4 Section 2

SCALE: 1" = 1'-0"6 Casework - 4 Drawer & Student MailboxesNo. Description Date

SCALE: 1" = 1'-0"11 Casework - Wall - Mailbox Cubbies

SCALE: 1" = 1'-0"10 Casework - File Cabinet

SCALE: 1" = 1'-0"15 Casework - Wall - Micro - PL

UP

UP

OFFICEB05

CLASSROOMB08

STORAGEB11

ELEC.B05

RECORD STORAGEB01

ELEV.EQUIP

B02LOBBY

B06

STORAGE/MECH.B12

COMMON OFFICEB02

OFFICEB03 STORAGE/MECH.

B10MECH.

B06

CORR.B09

CORR.B04

CLASSROOMB01

STAIRST-B5

ServerB14

R.R.B13

PNT-1

CWT-1

7' - 0

"1'

- 0"

8' - 0

"

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/19

/201

7 3:

19:2

9 PM

A11.0

Floor Finish Plan -Lower LevelSCALE: 1/8" = 1'-0"1 Finish Floor Plan - Lower Level

FINISH LEGENDAcoustic Ceiling TileACT-1 ARMSTRONG, DUNE 1774 ANGLED TEGULAR 15/16", SIZE: 24" X 24", COLOR: WHITE, GRID: 15/16" WHITE.

CarpetCPT-1 CARPET TILE, PROVIDE $35 SF INSTALL BUDGET COST; REFER TO DETAIL 3/A11.1.CPT-2 CARPET TILE, PROVIDE $35 SF INSTALL BUDGET COST; REFER TO DETAIL 3/A11.1.

Ceramic TileCT-1 12" X 24" COLORBODY PORCELAIN TILE, PRODUCT TO BE SELECTED BY DESIGNER, INSTALLED AT 33% OFFSET, PROVIDE $7 SF MATERIAL BUDGET COST; REFER TO

DETAIL 2/A11.1.

Ceramic Tile BaseCTB-1 COLORBODY PORCELAIN TILE, COVE BASE TO COORDINATE WITH CT-1, PROVIDE $7 SF MATERIAL BUDGET COST.

Ceramic Wall TileCWT-1 12" X 24" COLORBODY PORCELAIN TILE, PRODUCT TO BE SELECTED BY DESIGNER, INSTALLED AT 33% OFFSET, PROVIDE $7 SF MATERIAL BUDGET COST.

Luxury Vinyl TileLVT-1 BASIS OF DESIGN, ARMSTRONG, NATURAL CREATIONS ARBORART DIAMOND 10; REFER TO DETAIL 4/A11.1.

PaintPNT-1 SHERWIN WILLIAMS, COLOR: TBD, FINISH: EGGSHELL (MAIN COLOR)PNT-2 SHERWIN WILLIAMS, COLOR: TBD, FINISH: EGGSHELL (MAIN COLOR)PNT-3 SHERWIN WILLIAMS, COLOR: TBD, FINISH: EGGSHELL (ACCENT COLOR)PNT-4 SHERWIN WILLIAMS, COLOR: TBD, FINISH: EGGSHELL (ACCENT COLOR)PNT-5 SHERWIN WILLIAMS, COLOR: TO MATCH RUBBER BASE, FINISH: SEMI GLOSSPNT-6 SHERWIN WILLIAMS, COLOR: TBD, FINISH: FLAT (CEILING)

Plastic LaminatePL-1 TO BE SELECTED, PROVIDE ALLOWANCE FOR PREMIUM HIGH PRESSURE LAMINATE, CASEWORK.PL-2 TO BE SELECTED, PROVIDE ALLOWANCE FOR PREMIUM HIGH PRESSURE LAMINATE, COUNTER.PL-3 TO BE SELECTED, PROVIDE ALLOWANCE FOR PREMIUM HIGH PRESSURE LAMINATE, CASEWORK.

RubberRB-1 JOHNSONITE, 4" RUBBER BASE, COLOR: TBD.

Solid SurfaceSS-1 CORAIN, COLOR: TO BE SELECTED

Stair ComponentSTC-1 JOHNSONITE, VINYL STAIR TREADS & RISER WITH NOSING HMT-63-SQ, FINISH: 12" DEEP HAMMERED, COLOR: BURNT UMBER 63.STC-2 JOHNSONITE, VINYL LANDING TILE, SIZE: 12" X 12", TEXTURE: HAMMERED, COLOR: BURNT UMBER 63.

Walk-Off MatWOM-1 LEES, COLLECTION: TUFF STUFF II, STEP UP II TILE, COLOR: TBD, SIZE: 24" X 24".

GENERAL ROOM FINISH NOTES1 SEE “GENERAL” SHEETS IN THE FRONT OF THE WORKING DRAWING SET FOR DEFINITION OF ABBREVIATIONS.2 THE SCHEDULED MATERIALS AND FINISHES SHALL NOT BE ORDERED OR INSTALLED BEFORE THE CONTRACTOR’S ACTUAL COLOR SAMPLE SUBMITTALS HAVE BEEN

APPROVED AS CALLED FOR IN THE SPECIFICATIONS.3 ALL FLOOR FINISH TRANSITIONS TO OCCUR IN THE MIDDLE OF DOOR FRAME UNLESS NOTED OTHERWISE.4 PROVIDE JOHNSONITE SLIMLINE RUBBER TRANSITION STRIP WHEREVER DIFFERING FLOOR MATERIALS MEET, UNLESS NOTED OTHERWISE.5 ALL HOLLOW METAL DOOR FRAMES AND WINDOW FRAMES TO BE PAINTED PNT-1 WITH ZERO VOC ACRYLIC BASED PAINT WITH A SEMI-GLOSS FINISH.6 ALL NEW DOORS TO MATCH EXISTING, COORDINATE WITH OWNER.7 ALL STAIRS TO BE STC-1 & STC-2.8 ALL EXPOSED STRUCTURE TO REMAIN EXISTING.9 ALL COUNTER TOPS AND 4” BACKSPLASHES TO BE PL-2, UNLESS NOTED OTHERWISE.10 ALL CASEWORK TO BE PL-1, UNLESS NOTED OTHERWISE.11 ALL ELEVATOR DOORS AND FRAMES TO BE PAINTED PNT-5 WITH ZERO VOC ACRYLIC BASED PAINT WITH A SEMI-GLOSS FINISH12 WHERE CERAMIC TILE MEETS CARPET TILE, PROVIDE SCHLUTER SCHIENE TRANSITION STRIP WITH EB FINISH.13 WHERE LVT MEETS CERAMIC TILE, FEATHER UP FLOOR UP TO MEET CERAMIC TILE. PROVIDE SCHLUTER SCHIENE TRANSITION STRIP WITH EB FINISH.

FINISH COMMENTS1 ALL GYP WALLS TO BE PAINTED PNT-1 UNLESS NOTED OTHERWISE.2 EXISTING CEILING GRID TO REMAIN, REMOVE AND REPLACE TILES.3 EXPOSED CEILING TO BE LEFT UNFINISHED4 REFER TO FINISH PLAN FOR INSTALL DIRECTION.5 REFER TO DETAIL 4/A11.1 FOR STAIR FINISH.6 ROOM TO RECIEVE NEW GRID AND TILES, ACT-1.7 WHERE THERE IS CPT-1 & CPT-2, PROVIDE MIX OF 60% CPT-1 AND 40% CPT-2.8 REFER TO DETAIL 2/A11.0 FOR TYP. CWT-1 INSTALL

FINISH SCHEDULE - 00 GROUND FLOORROOM

FLOOR BASEWALLS

CEILING# NAME NORTH SOUTH EAST WEST COMMENTS

B13 R.R. CT-1 -- CWT-1, PNT-1 CWT-1, PNT-1 CWT-1, PNT-1 CWT-1, PNT-1 ACT-1 4,8B14 Server EXISTING EXISTING PNT-1 PNT-1 PNT-1 PNT-1 EXPOSED 3

No. Description Date

SCALE: 1/4" = 1'-0"2 CWT-1 INSTALL

RECEIVING/STORAGE126

STORAGE124

CONG. LIFE RESOURCECENTER

123

VEST.122

OFFICE119

OFFICE118

OFFICE116

OFFICE115

OFFICE114

STAIRST-1

OFFICE109

PRESIDENT107

OFFICE106 OFFICE

134

RECEPTION104

COORIDOR103

ADMIN.110

ADMIN.112

WOMEN121

MEN102

ALCOVE101

ELEV.EL-1

LOBBY100

KITCHEN129

STAIRST-4

STAIRST-5

WORK ROOM00

LVT-1CT-1

LVT-1CT-1

STC-

1LV

T-1

PNT-1

PNT-3

CT-1CPT-1,CPT-2

CT-1CPT-1, CPT-2

STORAGE131

MEETING HOUSE132

CHOIR ROOM133

PNT-2

PNT-2

PNT-2

PNT-2

PNT-2

PNT-4

PNT-4

PNT-4

PNT-1

PNT-1

GATHERING ROOM127

CORRIDOR117

VEST.130

PNT-1

PNT-1PNT-1

PNT-1

PNT-1

PNT-1

PNT-1

PNT-1

PNT-1

PNT-1PNT-1

PNT-1

PNT-1

EXIST.

PNT-1

EXIST.

EXIST.

EXIST.

PNT-1

EXIST. EXIST.

EXIST.

EXIST.

EXIST.

EXIST.

EXIST.

PNT-1

PNT-1

PNT-1

PNT-1

STC-

1CT

-1

DN

UP

UP

DN

CPT-1STC-1

CPT-1STC-1

PNT-1

PNT-1

CPT-1

, CPT

-2LV

T-1

PNT-1

PNT-1

PNT-1

PNT-1

PNT-1

PNT-1

7/A10.1

2A11.1

96519-1

96519-1

PNT-1

CPT-1, CPT-2LVT-1 LVT-1CPT-1, CPT-2

14' - 3" 16' - 3"

12' -

5"

VINYL STAIR TREAD& RISER, STC-1

STAIR STRINGER BEYOND,PAINTED PNT-5

LVT-1CT-1

LVT-1CT-1

CT-1CPT-1,CPT-2

CT-1CPT-1, CPT-2

8' - 0" 8' - 0" 7' - 7 1/4"

9' - 2

"10

' - 0"

10' -

0"10

' - 0"

8' - 0

"10

' - 0"

7' - 7

1/8"

93000-3

93000-3

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/20

/201

7 9:

06:0

3 AM

A11.1

Floor Finish Plan -Main Level

FINISH SCHEDULE - 01 FIRST FLOORROOM

FLOOR BASEWALLS CEILING COMMENTS# NAME NORTH SOUTH EAST WEST

100 LOBBY CT-1 EXISTING, RB-1 SEE PLANS SEE PLANS SEE PLANS SEE PLANS ACT-1, PNT-1, PNT-3, PNT-6 1, 6, 9101 ALCOVE CT-1 EXISTING, RB-1 PNT-1 PNT-1 -- PNT-1 ACT-1, PNT-6 1, 2, 9103 COORIDOR CPT-1 RB-1 PNT-1 PNT-1, PNT-2 -- PNT-1 ACT-1, PNT-6 1, 2104 RECEPTION CPT-1 RB-1 PNT-1 PNT-1 PNT-1 PNT-2 ACT-1, PNT-3, PNT-6 1, 2106 OFFICE CPT-1 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT-1 6107 PRESIDENT CPT-1 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT-1 1, 2117 CORRIDOR CPT-1 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT-1, PNT-6 1, 2122 VEST. WOM-1 EXISTING, RB-1 PNT-1 PNT-1 PNT-1 PNT-1 EXISTING 9123 CONG. LIFE RESOURCE CENTER CPT-1, CPT-2 RB-1 PNT-1 PNT-1 PNT-1, PNT-2 PNT-1 ACT-1, PNT-6 1, 2, 7124 STORAGE LVT-1 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT-1 6127 GATHERING ROOM CPT-1, CPT-2 RB-1 SEE PLANS SEE PLANS SEE PLANS SEE PLANS ACT-1, PNT-6 2, 7129 KITCHEN LVT-1 RB-1 PNT-4 PNT-1 PNT-1 -- ACT-1 1, 6130 VEST. WOM-1 EXISTING, RB-1 -- -- -- -- EXISTING 9134 OFFICE CPT-1 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT-1 6ST-1 STAIR STC1, STC-2 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT-1, PNT-6 1, 2, 5ST-4 STAIR STC1, STC-2 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT-1, PNT-6 1, 2, 5ST-5 STAIR STC1, STC-2 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT-1, PNT-6 1, 2, 5

North

SCALE: 1/8" = 1'-0"1 Finish Floor Plan - Main Level

FINISH LEGENDAcoustic Ceiling TileACT-1 ARMSTRONG, DUNE 1774 ANGLED TEGULAR 15/16", SIZE: 24" X 24", COLOR: WHITE, GRID: 15/16" WHITE.

CarpetCPT-1 CARPET TILE, PROVIDE $35 SF INSTALL BUDGET COST; REFER TO DETAIL 3/A11.1.CPT-2 CARPET TILE, PROVIDE $35 SF INSTALL BUDGET COST; REFER TO DETAIL 3/A11.1.

Ceramic TileCT-1 12" X 24" COLORBODY PORCELAIN TILE, PRODUCT TO BE SELECTED BY DESIGNER, INSTALLED AT 33% OFFSET, PROVIDE $7 SF MATERIAL BUDGET COST; REFER TO

DETAIL 2/A11.1.

Ceramic Tile BaseCTB-1 COLORBODY PORCELAIN TILE, COVE BASE TO COORDINATE WITH CT-1, PROVIDE $7 SF MATERIAL BUDGET COST.

Ceramic Wall TileCWT-1 12" X 24" COLORBODY PORCELAIN TILE, PRODUCT TO BE SELECTED BY DESIGNER, INSTALLED AT 33% OFFSET, PROVIDE $7 SF MATERIAL BUDGET COST.

Luxury Vinyl TileLVT-1 BASIS OF DESIGN, ARMSTRONG, NATURAL CREATIONS ARBORART DIAMOND 10; REFER TO DETAIL 4/A11.1.

PaintPNT-1 SHERWIN WILLIAMS, COLOR: TBD, FINISH: EGGSHELL (MAIN COLOR)PNT-2 SHERWIN WILLIAMS, COLOR: TBD, FINISH: EGGSHELL (MAIN COLOR)PNT-3 SHERWIN WILLIAMS, COLOR: TBD, FINISH: EGGSHELL (ACCENT COLOR)PNT-4 SHERWIN WILLIAMS, COLOR: TBD, FINISH: EGGSHELL (ACCENT COLOR)PNT-5 SHERWIN WILLIAMS, COLOR: TO MATCH RUBBER BASE, FINISH: SEMI GLOSSPNT-6 SHERWIN WILLIAMS, COLOR: TBD, FINISH: FLAT (CEILING)

Plastic LaminatePL-1 TO BE SELECTED, PROVIDE ALLOWANCE FOR PREMIUM HIGH PRESSURE LAMINATE, CASEWORK.PL-2 TO BE SELECTED, PROVIDE ALLOWANCE FOR PREMIUM HIGH PRESSURE LAMINATE, COUNTER.PL-3 TO BE SELECTED, PROVIDE ALLOWANCE FOR PREMIUM HIGH PRESSURE LAMINATE, CASEWORK.

RubberRB-1 JOHNSONITE, 4" RUBBER BASE, COLOR: TBD.

Solid SurfaceSS-1 CORAIN, COLOR: TO BE SELECTED

Stair ComponentSTC-1 JOHNSONITE, VINYL STAIR TREADS & RISER WITH NOSING HMT-63-SQ, FINISH: 12" DEEP HAMMERED, COLOR: BURNT UMBER 63.STC-2 JOHNSONITE, VINYL LANDING TILE, SIZE: 12" X 12", TEXTURE: HAMMERED, COLOR: BURNT UMBER 63.

Walk-Off MatWOM-1 LEES, COLLECTION: TUFF STUFF II, STEP UP II TILE, COLOR: TBD, SIZE: 24" X 24".

GENERAL ROOM FINISH NOTES1 SEE “GENERAL” SHEETS IN THE FRONT OF THE WORKING DRAWING SET FOR DEFINITION OF ABBREVIATIONS.2 THE SCHEDULED MATERIALS AND FINISHES SHALL NOT BE ORDERED OR INSTALLED BEFORE THE CONTRACTOR’S ACTUAL COLOR SAMPLE SUBMITTALS HAVE BEEN

APPROVED AS CALLED FOR IN THE SPECIFICATIONS.3 ALL FLOOR FINISH TRANSITIONS TO OCCUR IN THE MIDDLE OF DOOR FRAME UNLESS NOTED OTHERWISE.4 PROVIDE JOHNSONITE SLIMLINE RUBBER TRANSITION STRIP WHEREVER DIFFERING FLOOR MATERIALS MEET, UNLESS NOTED OTHERWISE.5 ALL HOLLOW METAL DOOR FRAMES AND WINDOW FRAMES TO BE PAINTED PNT-1 WITH ZERO VOC ACRYLIC BASED PAINT WITH A SEMI-GLOSS FINISH.6 ALL NEW DOORS TO MATCH EXISTING, COORDINATE WITH OWNER.7 ALL STAIRS TO BE STC-1 & STC-2.8 ALL EXPOSED STRUCTURE TO REMAIN EXISTING.9 ALL COUNTER TOPS AND 4” BACKSPLASHES TO BE PL-2, UNLESS NOTED OTHERWISE.10 ALL CASEWORK TO BE PL-1, UNLESS NOTED OTHERWISE.11 ALL ELEVATOR DOORS AND FRAMES TO BE PAINTED PNT-5 WITH ZERO VOC ACRYLIC BASED PAINT WITH A SEMI-GLOSS FINISH12 WHERE CERAMIC TILE MEETS CARPET TILE, PROVIDE SCHLUTER SCHIENE TRANSITION STRIP WITH EB FINISH.13 WHERE LVT MEETS CERAMIC TILE, FEATHER UP FLOOR UP TO MEET CERAMIC TILE. PROVIDE SCHLUTER SCHIENE TRANSITION STRIP WITH EB FINISH.

FINISH COMMENTS1 ALL GYP WALLS TO BE PAINTED PNT-1 UNLESS NOTED OTHERWISE.2 EXISTING CEILING GRID TO REMAIN, REMOVE AND REPLACE TILES.3 EXPOSED CEILING TO BE LEFT UNFINISHED4 REFER TO FINISH PLAN FOR INSTALL DIRECTION.5 REFER TO DETAIL 4/A11.1 FOR STAIR FINISH.6 ROOM TO RECIEVE NEW GRID AND TILES, ACT-1.7 WHERE THERE IS CPT-1 & CPT-2, PROVIDE MIX OF 60% CPT-1 AND 40% CPT-2.8 REFER TO DETAIL 2/A11.0 FOR TYP. CWT-1 INSTALL9 EXISTING BRICK VENEER TO REMAIN, RB-1 TO ONLY BE APPLIED TO GYP WALLS IN THIS SPACE.10 EXISTING WOOD BASE TO REMAIN. WHERE RUBBER BASE EXISTS, REMOVE AND REPLACE WITH SCHEDULED BASE.

SCALE: 1/2" = 1'-0"3 CT-1 Installation Direction

SCALE: 1/2" = 1'-0"5 CPT-1,2 Installation DirectionSCALE: 1/2" = 1'-0"6 LVT-1 Installation Direction

SCALE: 1 1/2" = 1'-0"4 Stair Finish Detail

SCALE: 1/4" = 1'-0"2 Lobby CT-1 Layout

FLOOR FINISH PLAN KEYNOTES93000-3 1/4" SEALANT EXPANSION JOINT. JOINT TO ALIGN WITH TILE GROUT LINE. COLOR: TO MATCH GROUT COLOR.96519-1 FEATHER UP FLOOR WHERE LVT MEETS CERAMIC FOR SMOOTH TRANSITION. PROVIDE METAL TRNSITION STRIP AS REQUIRED. BASIS OF DESIGN: SCHLUTER

SCHIENE TRANSITION STRIP WITH EB FINISH.

No. Description Date

UP

OFFICE221

OFFICE220

OFFICE216

OFFICE215

ACADEMIC COOR.214

DEAN FACULTY209

OFFICE207

OFFICE206

OFFICE205

OFFICE204

CORRIDOR203

CORRIDOR217

ADMIN.212

ADMIN.210

WORKROOM218

WOMEN219

MEN202

ALCOVE201

ELEV.EL-9

LOBBY200

MECHANICAL229

STUDY ROOM228

CLASSROOM/SEMINAR227

STAIRST-4

CLOSET225

CLASSROOM224

CLASSROOM223

CORRIDOR226

STAIRST-2

MEETING HOUSE132

STAIRST-1

CPT-1, CPT-2CPT-1

STC-

1, ST

C-2

CPT-1

STC-

1, ST

C-2

CPT-1

CPT-1STC-1, STC-2

CPT-1CPT-1, CPT-2

CPT-1CPT-1, CPT-2

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/20

/201

7 9:

05:0

4 AM

A11.2

Floor Finish Plan -Second Level

FINISH SCHEDULE - 02 SECOND FLOORROOM

FLOOR BASEWALLS

CEILING COMMENTS# NAME NORTH SOUTH EAST WEST

200 LOBBY CPT-1 EXISTING PNT-1 PNT-1 EXISTING EXISTING EXISTING 10201 ALCOVE CPT-1 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 EXISTING 10203 CORRIDOR CPT-1, CPT-2 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 EXISTING217 CORRIDOR CPT-1, CPT-2 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 EXISTING223 CLASSROOM CPT-1, CPT-2 RB-1 PNT-2 PNT-1 PNT-1 PNT-1 ACT-1 2224 CLASSROOM CPT-1, CPT-2 RB-1 PNT-2 PNT-1 PNT-1 PNT-1 ACT-1 2225 CLOSET CPT-1 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT-1 2226 CORRIDOR CPT-1, CPT-2 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT-1 2227 CLASSROOM/SEMINAR CPT-1, CPT-2 RB-1 PNT-1 PNT-2 PNT-1 PNT-1 ACT-1 2ST-1 STAIR STC1, STC-2 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 EXISTING, PNT-6ST-2 STAIR STC1, STC-2 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 EXISTING, PNT-6ST-4 STAIR STC1, STC-2 RB-1 PNT-1 PNT-1 PNT-1 PNT-1 ACT-1, PNT-6 2

FINISH LEGENDAcoustic Ceiling TileACT-1 ARMSTRONG, DUNE 1774 ANGLED TEGULAR 15/16", SIZE: 24" X 24", COLOR: WHITE, GRID: 15/16" WHITE.

CarpetCPT-1 CARPET TILE, PROVIDE $35 SF INSTALL BUDGET COST; REFER TO DETAIL 3/A11.1.CPT-2 CARPET TILE, PROVIDE $35 SF INSTALL BUDGET COST; REFER TO DETAIL 3/A11.1.

Ceramic TileCT-1 12" X 24" COLORBODY PORCELAIN TILE, PRODUCT TO BE SELECTED BY DESIGNER, INSTALLED AT 33% OFFSET, PROVIDE $7 SF MATERIAL BUDGET COST; REFER TO

DETAIL 2/A11.1.

Ceramic Tile BaseCTB-1 COLORBODY PORCELAIN TILE, COVE BASE TO COORDINATE WITH CT-1, PROVIDE $7 SF MATERIAL BUDGET COST.

Ceramic Wall TileCWT-1 12" X 24" COLORBODY PORCELAIN TILE, PRODUCT TO BE SELECTED BY DESIGNER, INSTALLED AT 33% OFFSET, PROVIDE $7 SF MATERIAL BUDGET COST.

Luxury Vinyl TileLVT-1 BASIS OF DESIGN, ARMSTRONG, NATURAL CREATIONS ARBORART DIAMOND 10; REFER TO DETAIL 4/A11.1.

PaintPNT-1 SHERWIN WILLIAMS, COLOR: TBD, FINISH: EGGSHELL (MAIN COLOR)PNT-2 SHERWIN WILLIAMS, COLOR: TBD, FINISH: EGGSHELL (MAIN COLOR)PNT-3 SHERWIN WILLIAMS, COLOR: TBD, FINISH: EGGSHELL (ACCENT COLOR)PNT-4 SHERWIN WILLIAMS, COLOR: TBD, FINISH: EGGSHELL (ACCENT COLOR)PNT-5 SHERWIN WILLIAMS, COLOR: TO MATCH RUBBER BASE, FINISH: SEMI GLOSSPNT-6 SHERWIN WILLIAMS, COLOR: TBD, FINISH: FLAT (CEILING)

Plastic LaminatePL-1 TO BE SELECTED, PROVIDE ALLOWANCE FOR PREMIUM HIGH PRESSURE LAMINATE, CASEWORK.PL-2 TO BE SELECTED, PROVIDE ALLOWANCE FOR PREMIUM HIGH PRESSURE LAMINATE, COUNTER.PL-3 TO BE SELECTED, PROVIDE ALLOWANCE FOR PREMIUM HIGH PRESSURE LAMINATE, CASEWORK.

RubberRB-1 JOHNSONITE, 4" RUBBER BASE, COLOR: TBD.

Solid SurfaceSS-1 CORAIN, COLOR: TO BE SELECTED

Stair ComponentSTC-1 JOHNSONITE, VINYL STAIR TREADS & RISER WITH NOSING HMT-63-SQ, FINISH: 12" DEEP HAMMERED, COLOR: BURNT UMBER 63.STC-2 JOHNSONITE, VINYL LANDING TILE, SIZE: 12" X 12", TEXTURE: HAMMERED, COLOR: BURNT UMBER 63.

Walk-Off MatWOM-1 LEES, COLLECTION: TUFF STUFF II, STEP UP II TILE, COLOR: TBD, SIZE: 24" X 24".

GENERAL ROOM FINISH NOTES1 SEE “GENERAL” SHEETS IN THE FRONT OF THE WORKING DRAWING SET FOR DEFINITION OF ABBREVIATIONS.2 THE SCHEDULED MATERIALS AND FINISHES SHALL NOT BE ORDERED OR INSTALLED BEFORE THE CONTRACTOR’S ACTUAL COLOR SAMPLE SUBMITTALS HAVE BEEN

APPROVED AS CALLED FOR IN THE SPECIFICATIONS.3 ALL FLOOR FINISH TRANSITIONS TO OCCUR IN THE MIDDLE OF DOOR FRAME UNLESS NOTED OTHERWISE.4 PROVIDE JOHNSONITE SLIMLINE RUBBER TRANSITION STRIP WHEREVER DIFFERING FLOOR MATERIALS MEET, UNLESS NOTED OTHERWISE.5 ALL HOLLOW METAL DOOR FRAMES AND WINDOW FRAMES TO BE PAINTED PNT-1 WITH ZERO VOC ACRYLIC BASED PAINT WITH A SEMI-GLOSS FINISH.6 ALL NEW DOORS TO MATCH EXISTING, COORDINATE WITH OWNER.7 ALL STAIRS TO BE STC-1 & STC-2.8 ALL EXPOSED STRUCTURE TO REMAIN EXISTING.9 ALL COUNTER TOPS AND 4” BACKSPLASHES TO BE PL-2, UNLESS NOTED OTHERWISE.10 ALL CASEWORK TO BE PL-1, UNLESS NOTED OTHERWISE.11 ALL ELEVATOR DOORS AND FRAMES TO BE PAINTED PNT-5 WITH ZERO VOC ACRYLIC BASED PAINT WITH A SEMI-GLOSS FINISH12 WHERE CERAMIC TILE MEETS CARPET TILE, PROVIDE SCHLUTER SCHIENE TRANSITION STRIP WITH EB FINISH.13 WHERE LVT MEETS CERAMIC TILE, FEATHER UP FLOOR UP TO MEET CERAMIC TILE. PROVIDE SCHLUTER SCHIENE TRANSITION STRIP WITH EB FINISH.

FINISH COMMENTS1 ALL GYP WALLS TO BE PAINTED PNT-1 UNLESS NOTED OTHERWISE.2 EXISTING CEILING GRID TO REMAIN, REMOVE AND REPLACE TILES.3 EXPOSED CEILING TO BE LEFT UNFINISHED4 REFER TO FINISH PLAN FOR INSTALL DIRECTION.5 REFER TO DETAIL 4/A11.1 FOR STAIR FINISH.6 ROOM TO RECIEVE NEW GRID AND TILES, ACT-1.7 WHERE THERE IS CPT-1 & CPT-2, PROVIDE MIX OF 60% CPT-1 AND 40% CPT-2.8 REFER TO DETAIL 2/A11.0 FOR TYP. CWT-1 INSTALL9 EXISTING BRICK VENEER TO REMAIN, RB-1 TO ONLY BE APPLIED TO GYP WALLS IN THIS SPACE.10 EXISTING WOOD BASE TO REMAIN. WHERE RUBBER BASE EXISTS, REMOVE AND REPLACE WITH SCHEDULED BASE.

SCALE: 1/8" = 1'-0"1 Finish Floor Plan - Second Level

No. Description Date

REF

.

REF

.

H.5

H.5

F.1

F.1

G

G

F.7

F.7

F.9

F.9

H

H

I

I

J

J

K

K

F

F

1.4 1.4

2 2

2.32.3

2.62.6

33

4 4

3.73.7

4.64.6

F.6

F.6

G.6

G.6

K.1

K.1

S-1

P1

P2

P3

P4

P5

P6

P7

P8

3/4"3/4"

HOTCO

LDV

V

P5

1 1/2"

LOBBY100

CONG. LIFERESOURCE

CENTER123

STORAGE124

EX.EWC

P9

P22

H.5

H.5

F.1

F.1

G

G

F.7

F.7

F.9

F.9

H

H

I

I

J

J

K

K

F

F

E.1

E.1

1.4 1.4

2 2

2.32.3

2.62.6

33

4 4

3.73.7

4.64.6

F.6

F.6

G.6

G.6

K.1

K.1

PD1

HOT

VCO

LD

PD2

PD3

V PD4

PD3PD4

LOBBY100

CONG. LIFERESOURCE

CENTER123

STORAGE124

KITCHEN129

CHROMEPLATED BRASS

NIPPLE

1/4 TURN, ALL BRASSCHROME PLATED ANGLE

STOPSCREW TO BLOCKING

3-EAREDDROP EAR(BRASS)

5/8" GYPSUM WALL

CHROMEPLATED

ESCUTCHEON

12" STAINLESS STEEL HOSEOR CHROME TUBE TO

FIXTURE2x WOODBLOCKINGBETWEEN STUDSFOR SUPPORT

TYPE L COPPER PIPEINSULATED WITH3/4" ARMAFLEX.

VENT FROM FURNACE

COMBUSTION AIR TO FURNACE

DOMESTIC COLD WATER

WASTE (SANITARY)

VENT (SANITARY)

STORM ABOVE CEILING

DOMESTIC HOT WATER RETURN

WASTE ABOVE CEILING (SANITARY)

DOMESTIC HOT WATER

ST

ST STORM

V

A

G

CA

COND

AIR

GAS

CONDENSATE WASTE

THERMOMETER

TAMPER SWITCH

FLOW SWITCH

PRESSURE GAUGE

FS

T

2-WAY CONTROL VALVE

3-WAY CONTROL VALVE

BALL VALVE

BUTTERFLY VALVE

ELBOW DOWN

ELBOW UP

TEE DOWN

TEE UP

PIPE END CAP

P

HARD DOMESTIC HARD WATER

FORCE SANITARY FORCE MAIN

M

M

GATE VALVE

CHECK VALVE

CLEANOUTCO

VENT THROUGH ROOFVTR

TRENCH DRAINTD-_

RELIEF ROOF DRAINRRD-_

ROOF DRAINRD-_

EXTERIOR CLEANOUTECO

FLOOR DRAINFD-_

FLOOR CLEANOUTFCO

LAVATORYL-_

URINALU-_

WATER CLOSETWC-_

SINKS-_

MOP BASINMB-_

ELEVATED CLEANOUT

GAS WATER HEATERGWH-_

BACKFLOW PREVENTERBFP

WALL CLEANOUTWCO

THERMOSTATIC MIXING VALVETMV

ELECTRIC WATER HEATEREWH-_

PIPE CONTINUATION

SAN SANITARY

GAS REGULATOR

FIRE DEPARTMENT CONNECTIONFDC

ELECTRIC WATER COOLEREWC-_

SHOWERSH-_

TUB OR TUB/SHOWERT-_

RECIRCULATING PUMPRP-_

GARBAGE DISPOSERGD-_

HOSE BIBBHB-_

WALL HYDRANTWH-_

ICE MAKER BOXIMB-_

SUMP PUMPSP-_

ENERGY FACTOREF

GALLONS PER HOURGPH

GALLONS PER MINUTEGPM

WASHING MACHINE BOXWB-_

TOTAL DYNAMIC HEADTDH

HORSEPOWERHP

CROSS-LINKED POLYETHYLENEPEX

AUTOMATIC AIR VENTAAV

POLYVINYL CHLORIDEPVC

G

G

H

H

I

I

F

F

4.64.6

OFFICEB05

CLASSROOMB08

CORR.B04

OFFICEB03

ServerB14

R.R.B13

STORAGE/MECH.B10

P10

P11

P12

P13P14

VV

HOT HOTCOLD

2"1/

2"1/

2"1/

2"

2"L-

1HW

C-1

H

CO-1

2" COLD2"

P17

1 1/2" COLD

2 1/

2" C

OLD

P19 PD5

1/2"

P20

P21

H.5

H.5

H

H

I

I

33

3.73.7

4.64.6

G.6

G.6

CORR.B04

OFFICEB03

ServerB14

STORAGE/MECH.B10

CLASSROOMB08

OFFICEB05

R.R.B13

WC

-1H

4"4"

4"4"

2"

4"

P15

P14

P13

P12

P16P18

P15

2"

1 1/4"

2"

2"

L-1H

WC-1H

CO-1 4"

4"

4"

4"

V

SAN

SAN

V P11

P18

P12

P13

P14

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/19

/201

7 4:

21:4

2 PM

P1.1

Plumbing Plans -Basement & Main Level

PLUMBING NOTES

P1 EXISTING DOMESTIC HOT WATER TO REMAIN AT THIS APPROXIMATE LOCATION. CONTRACTOR TOCONFIRM EXACT LOCATION.

P2 EXISTING VENT TO REMAIN AT THIS APPROXIMATE LOCATION. CONTRACTOR TO CONFIRM EXACTLOCATION.

P3 EXISTING DOMESTIC COLD WATER TO REMAIN AT THIS APPROXIMATE LOCATION. CONTRACTOR TOCONFIRM EXACT LOCATION.

P4 TAP INTO THE EXISTING COLD WATER LINE AT THIS LOCATION AND ROUTE OVER TO THE NEW SINK.ROUTE THE INSULATED LINES DOWN INSIDE WALL AND TO BELOW THE NEW CABINET. CONNECT TO THESINK AS REQUIRED. THE EXISTING WALL TO BE OPENED AND REPAIRED BY G.C.

P5 TAP INTO THE EXISTING VENT LINE AT THIS LOCATION AND ROUTE OVER TO THE NEW SINK. ROUTE THEVENT DOWN INSIDE WALL AND TO BELOW THE NEW CABINET. CONNECT TO THE SINK AS REQUIRED. THEEXISTING WALL TO BE OPENED AND REPAIRED BY G.C.

P6 TAP INTO THE EXISTING HOT WATER LINE AT THIS LOCATION AND ROUTE OVER TO THE NEW SINK.ROUTE THE INSULATED LINES DOWN INSIDE WALL AND TO BELOW THE NEW CABINET. CONNECT TO THESINK AS REQUIRED. THE EXISTING WALL TO BE OPENED AND REPAIRED BY G.C.

P7 NEW DRAIN LINE TO BE ROUTED BELOW FLOOR IN BASEMENT AND CONNECT TO THE EXISTINGSANITARY LINE FROM THE DEMOLISHED EXISTING FIXTURE. FIRE SEAL THE FLOOR WHERE THESANITARY LINE ROUTES TO FLOOR BELOW.

P8 TURN OVER UNDERCOUNTER SINK TO THE GC FOR INSTALLATION INTO THE SOLID SURFACE MATERIALBY THE COUNTERTOP SUPPLIER.

P9 REINSTALL THE EXISTING WATER COOLER AT THIS NEW LOCATION AND RECONNECT THE WATER ANDDRAIN AS REQUIRED.

P10 CONNECT THESE WATER LINES ONTO THE EXISTING WATER LINE LOCATED IN THE CORRIDOR AT THISAPPROXIMATE LOCATION AND INSTALL BRONZE ISOLATION BALL VALVES AS SHOWN. TYPICAL

P11 CONNECT THE VENT LINE INTO THE EXISTING AT THIS APPROXIMATE LOCATION.P12 INSTALL LAVATORY PER MANUFACTURERS RECOMMENDATIONS.P13 INSTALL WATER CLOSET PER MANUFACTURERS RECOMMENDATIONS.P14 ROUTE VENT UP INSIDE WALL AS SHOWN.P15 THIS CONTRACTOR SHALL IDENTIFY EXACT LOCATION OF THE UG SANITARY AND THEN SAWCUT THE

EXISTING SLAB TO INSTALL UNDERGROUND SANITARY LINES. REPLACE SLAB TO MATCH EXISTING. PINWITH 6" LONG #4 REBARS THAT ARE DRILLED INTO THE EXISTING SLAB 3". PINS SHALL OCCUR AT 24" OCAROUND THE PERIMETER.

P16 VERIFY THE EXISTING LOCATION OF THE SANITARY LINE. DRAWINGS INDICATE THAT THESE LINES ARELOCATED AT THIS APPROXIMATE LOCATION.

P17 THERE IS A SECTION OF THE 2" COLD WATER LINE THAT REDUCES DOWN TO 3/4" FOR NO APPARENTREASON EXCEPT IT SHOWS UP ON THE ORIGINAL DESIGN DOCUMENTS. IT IS APROX 31' LONG SECTION.THIS SECTION OF PIPE SHALL BE DISCOVERED BY THE PC AND SHALL BE REMOVED AND REPLACEDWITH 2" COPPER. THIS SHALL BE BID AS ALTERNATE M-1

P18 CONNECT TO THE SANITARY LINE AT THIS APPROXIMATE LOCATION. FIELD VERIFY PRIOR TOSAWCUTTING THE FLOOR.

P19 EXISTING 2" UP TO TOILETS ON FIRST FLOORP20 TAP INTO THE EXISTING COLD WATER LINE AT THIS LOCATION AND ROUTE UP TO THE RELOCATED

ELECTRIC WATER COOLER. ROUTE THE INSULATED LINES UP INSIDE WALL AND SEAL THE FLOOR WITHFIREPROOF CAULKING

P21 UP TO EX.EWCP22 CONTRACTOR SHALL CONNECT TO THE EXISTING COLD WATER LINE BELOW THE COUNTERTOP AND

INSTALL A 3/8" BRAIDED STAINLESS STEEL HOSE FROM THE WATER LINE, ROUTE BEHIND THE CABINET,INSTALL A GROMMET IN THE NEW COUNTERTOP AND CONNECT TO THE NEW COFFEE MAKER.

NORTH

SCALE: 1/8" = 1'-0"1 Plumbing Plan - Main Level

GENERAL PLUMBING NOTES

1. DEAD ENDS SHALL BE AVOIDED IN A DRAINAGE SYSTEM, EXCEPT WHERE NECESSARY TO EXTEND THESYSTEM TO INSTALL A CLEANOUT IN AN ACCESSIBLE LOCATION. THE DEAD ENDS INTENDED FORFUTURE CONNECTION OR CREATED BY REMOVAL OR ABANDONMENT OF PIPE; WHICH IS MORE THANTWO (2) FEET ABOVE A FLOOR OR MORE THAN TEN (10) FEET HORIZONTALLY FROM THE NEARESTVENTED CONNECTION MUST HAVE A VENTED CONNECTION TO THE OUTSIDE ATMOSPHERE.

2. PIPING LOCATIONS, INVERTS AND SIZES SHALL BE VERIFIED ON SITE TO DETERMINE EXACT LOCATIONAND SIZE.

3. PROVIDE WALL CLEANOUTS ON ALL SANITARY AND STORM LINES AT 12" AFF WHERE THEY ROUTE TOBELOW THE SLAB.

4. ALL WASTE AND VENT PIPING SHALL BE SOLID CORE PVC WITH 1/2" ARMAFLEX WRAP FOR PLENUMRETURN.

5. ALL WATER LINES SHALL BE TYPE L COPPER WITH 3/4" ARMAFLEX INSULATION.6. WHERE CEILINGS ARE NOT REMOVED IN PLAN THIS CONTRACTOR SHALL BE RESPOSIBLE TO CAREFULLY

REMOVE THE CEILING AND GRID AND REPLACE TO ALLOW ACCESS TO REWORK THE PLUMBING SYSTEMAS SHOWN.

NORTH

SCALE: 1/8" = 1'-0"2 Plumbing Demolition Plan - Main Level

PLUMBING DEMOLITION NOTES

PD1 CAREFULLY REMOVE THE EXISTING ELECTRIC WATER COOLER AND PIPING SYSTEM BACK AS FAR AS REQUIRED INPREPARATION FOR RELOCATION PER THE CONSTRUCTION PLAN AT RIGHT.

PD2 REMOVE THE EXISTING SINK AND PIPING SYSTEM AS FAR BACK AS REQUIRED IN PREPARATION FOR THE NEW SINK.CAP THE FLOOR WITH FIREPROOFING AND PREPARE PIPING FOR RECONNECTION. .

PD3 REMOVE EXISTING PIPING ON THIS FLOOR AND BELOW IN PREPARATION FOR NEW CONNECTIONS.PD4 EXISTING PIPING ASSUMED TO BE LOCAED AT THIS APPROXIMATE LOCATION. THIS CONTRACTOR TO CONFIRM

EXACT LOCATION PRIOR TO BID. TYPICALPD5 THERE IS A SECTION OF 3/4" THAT REQUIRES REMOVAL . IT IS APROX 31' LONG SECTION. THIS SECTION OF PIPE

SHALL BE DISCOVERED BY THE PC AND SHALL BE REMOVED AND REPLACED WITH 2" COPPER. THIS SHALL BE BID ASALTERNATE M-1

3 FIXTURE CONNECTION DETAIL

4 PLUMBING SYMBOLS.

PLUMBING FIXTURE SCHEDULE

TAG

FIXTURE TRIM MINIMUM CONNECTION SIZE ACCESSORIES

NOTESMFG'R MODEL EQUAL FINISHRIM

HEIGHT MFG'R MODEL EQUAL FINISH COLD HOT VENT WASTE STO

PS

TUBE

S

GRI

D DR

AIN

P-TR

AP

CO-1 ZURN ZN-1400 JOSAM,WADE

NICKELBRONZE

INTERIOR FLOOR CLEANOUT, NO HUB OUTLET,SEE DRAWINGS FOR SIZES

EX. EWC ELKAY EZS8 OASIS,HALSEYTAYLOR

STAINLESSSTEEL

31 7/8" 1/2" 1 1/4" 1 1/2" Yes Yes Yes SINGLE LEVEL, REFRIGERATED WATER COOLER,BARRIER FREE, ZURN 1225 CARRIER

L-1H AMERICANSTANDARD

0356.421 KOHLER WHITE 34" AMERICANSTANDARD

2000.100MANUALSINGLELEVER

FAUCET

KOHLER, CHICAGOFAUCET

POLISHEDCHROME

1/2" 1/2" 1 1/4" 1 1/2" Yes Yes Yes Yes CARRIER HUNG ADA LAVATORY, SINGLE HOLEFOR FAUCET, ZURN Z1231 CONCEALED ARMCARRIER

S-1 ELKAY LR3322 JUST STAINLESSSTEEL

34" KOHLER K-10412 AMERICAN STANDARD,DELTA

POLISHEDCHROME

1/2" 1/2" 1 1/2" 2" Yes Yes Yes Yes DOUBLE BOWL UNDERCOUNTER SINK, 4 FAUCETHOLES ON 4" CENTERS, SPRAY NOZZLE ONFAUCET SET, DUAL LK-35 STRAINERS

WC-1H AMERICANSTANDARD

215CA.004 KOHLER WHITE 15" 1/2" 2" 4" Yes Yes TANK TYPE WATER CLOSET WITH ELONGATEDBOWL AND TANK, CHURCH 9500CT OPEN FRONTSEAT LESS COVER, WAX RING

6. OFFSET GRID - POLISHED CHROME 17 GA. CAST BRASS SOLID TOPOPEN GRID STRAINER WITH OFFSET TAILPIECE (ADA COMPLIANT)

7. P-TRAP - PVC DWV P-TRAP WITH THREADED COMPRESSION ENDS,PVC ARM, AND ESCHUTCHEON AT WALL

8. ADA WRAP - WHITE POLYOLEFIN WRAP FOR SUPPLY TUBES, STOPS,TAILPIECE, TRAP AND ARM

3. STOPS - CHROME PLATED BRASS ANGLE STOPS WITH 1/2" F.I.P.INLET AND 3/8" OUTLET, QUARTER TURN HANDLE, CHROME PLATEDESCHUTCHEON

4. TUBES - 12" LONG BRAIDED STAINLESS STEEL HOSES5. GRID DRAIN - POLISHED CHROME 17 GA. CAST BRASS SOLID TOP

OPEN GRID STRAINER WITH TAILPIECE

1. USE MANUFACTURERS CURRENT COMPARISON CHARTS FORCROSS REFERENCE FOR FIXTURE EQUALS. SUBMIT EQUALS TOENGINEER PRIOR TO BID. SEE DRAWINGS FOR OUTLET SIZES.

2. PLUMBING ACCESSORIES SHALL BE THE FOLLOWING (ACCEPTABLEMANUFACTURERS ARE: MCQUIRE, BRASSCRAFT, ZURN, KEENEY

NORTH

SCALE: 1/8" = 1'-0"5 Plumbing Plan - Basement Level

NORTH

SCALE: 1/8" = 1'-0"6 Plumbing Plan - Basement Underground

7 Waste and Vent IsometricNo. Description Date

REF

.

REF

.

T

TT

T T

F.1

F.1

G

G

H

H

I

I

J

J

K

K

F

F

E

E

E.1

E.1

D

D

C

C

11

1.4 1.4

2 2

2.32.3

2.62.6

33

2.7 2.7

3.3 3.3

4 4

3.73.7

55

F.6

F.6

K.1

K.1

RSRL

ACC-CRAC-1

M2

M1

M4

M3

M5

3/4" G

3/4"

G

M10

M7M6

FIR

EPLA

CE

MD1

MD2

M8

GAS

M9

TB-10

TB-11

18"x12"28"x14"

6"ø

8"ø

6"ø

A150B

250

RG

-1

M11

M12

M13M13

M13

M15

EX 180

M13

RG-2

M13

M14

M15

M25

M25

H.5

H.5

F.1

F.1

G

G

F.7

F.7

F.9

F.9

H

H

I

I

J

J

K

K

F

F

E

E

E.1

E.1

D

D

C

C

11

1.4 1.4

2 2

2.32.3

2.62.6

33

2.7 2.7

3.3 3.3

4 4

3.73.7

4.64.6

F.6

F.6

G.6

G.6

K.1

K.1

CRAC-1 RLRS

M19M18

M17M16

SAN

M20M21M22

EF-1

6"ø

M23

EX. EF-5

18"x10"

M24

M25

SEE PLANS FOR REFRIGERANT SIZES

30" N

TS

BUILDING WALL

RS

RL

MOUNT A NEMA 4X WATERPROOF JUNCTION BOXAND 3/4" SEALTIGHT FROM THIS BOX TO THECONDENSING UNIT AND ROUTE CONTROL WIRINGWITHIN THE SEALTIGHT.

MOUNT REFRIGERANT LINES ON FIBERGLASS OR 316SS UNISTRUT & STAINLESS CUSH CLAMPS

4" CONCRETE HOUSEKEEPING PAD SET ON 6" OFCOMPACTED CRUSHED LIMESTONE. PAD SHALL BEROUTED TO THE WALL OF THE BUILDING AND A MINIMUMOF 6" BEYOND EACH SIDE OF THE CONDENSING UNIT.PROVIDE A SINGLE PAD.

(4) 3/4" RUBBER-SHEARISOLATION BLOCKS BELOWCONDENSING UNIT

PVC PIPE SLEEVES ATWALL. SEAL WALL 100%WATERTIGHT

POWER DISCONNECT & SEALTIGHT BY E.C.

LIQUID LINE FILTER DRYER

REFRIGERANT HP SERVICE VALVES

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/19

/201

7 4:

09:1

4 PM

M1.1

Mechanical Plans -Lower and Main Level

GENERAL MECHANICAL NOTES

1. PAINT ALL EXTERIOR GAS PIPING WITH 2 COATS LIGHT GRAYENAMAL PAINT WITH RUSTOLEUM PRIMER.

2. MECHANICAL CONTRACTOR SHALL PROVIDE ANY ADDITIONALOFFSETS AS REQUIRED TO COMPLETE THE INSTALLATION OF THEDUCT SYSTEMS. LAYOUTS ARE SCHEMATIC IN NATURE ANDPROVIDE GENERAL ROUTING SOLUTIONS. CONTRACTOR SHALLCOORDINATE ALL ROUTES ON SITE.

3. ALL DUCTS SHALL BE SEALED AND INSULATED PERSPECIFICATIONS.

4. INSTALL ALL DUCTS AND PIPING AS HIGH AS POSSIBLE TO ALLOWFOR CLEARANCE WITH CEILINGS AND OTHER TRADES.

5. SEE THE REFLECTED CEILING PLANS FOR EXACT LOCATIONS OFALL DIFFUSERS IN THE CEILINGS.

MECHANICAL NOTES

M1 INSTALL THE NEW CRAC ACC ON A NEW CONCRETE PAD PER THE DETAILSSHOWN ON THIS SHEET AND IN STRICT COMPLIANCE WITH MANUFACTURERSRECOMMENDATIONS. REFRIGERANT LINES ARE TO BE SIZED BY THEMANUFACTURER PRIOR TO BID. TYPICAL

M2 THIS CONTRACTOR TO FURNISH AND INSTALL THE 4" THICK CONCRETE SLAB.SET SLAB ON 6" OF CRUSEHD LIMESTONE, CHAMFER ALL EDGES AND TURNDOWN EDGES OF PAD TO 6" BELOW FINISH GRADE.

M3 ROUTE THE REFRIGERANT AND CONTROL LINES TIGHT TO AREAWAY WALL.SEE BASEMENT PLAN FOR CONTINUATION.

M4 SAWCUT THE EXISTING AREAWAY COVER AND COLD GALVANIZE WHERE RAWSTEEL EDGES OCCUR.

M5 EXISTING AREAWAY COVER AT THIS APPROXIMATE LOCATION.M6 EXISTING DIRECT VENT FIREPLACE FURNISHED AND INSTALLED BY OTHERS

INCLUDING FLUE AND AIR INTAKE.M7 ROUTE THE GAS LINE DOWN INSIDE WALL TO SUPPLY GAS TO THE

APPLIANCE. FINAL CONNECTION OF GAS INCLUDING AN AGA ISOLATIONVALVE BY THIS CONTRACTOR. CAREFULLY COORDINATE THIS WORK WITHALL OTHER TRADES.

M8 ROUTE A NEW GAS LINE ABOVE CEILING TO ROUTE TO THE NEW FIREPLACE.CAREFULLY REMOVE AND REPLACE THE EXISTING CEILING TILES AND GRIDAS REQUIRED TO ROUTE THIS GAS LINE.

M9 EXISTING GAS LINE AT THIS APPROXIMATE LOCATION. CONTRACTOR SHALLCONFIRM EXACT LOCATION IN FIELD.

M10 START CONNECTION AT THIS EXISTING END OF PIPING SYSTEM.M11 INSTALL A NEW DUCT TAP ON THE TOP OF THIS EXISTING DUCT AND ROUTE

OVER TOP OF THE EXISTING DUCT AS SHOWN.M12 AFTER REMOVAL OF THE DIFFUSER AND ASSOCIATED DUCT FROM

DOWNSTREAM OF THIS POINT, CONNECT TO THE EXISTING 10" DUCT ANDREDUCE TO 6" THEN ROUTE TO THE NEW DIFFUSER AS SHOWN.

M13 NEW GRILLS AND REGISTERS TO BE INSTALLED AT THIS APPROXIMATELOCATION AND AVOID NEW LIGHTS. BALANCE FOR THE SHOWN AIRFLOW TOWITHIN 10% OF SHOWN AIRFLOW

M14 EXISTING THERMOSTAT TO REMAIN OPERATIONAL.M15 RELOCATE THE EXISTING THERMOSTAT FROM THE DEMOLISHED WALL TO

THE NEW WALL AS SHOWN.M16 SEE MAIN LEVEL PLAN ABOVE FOR CONTINUATION.M17 CORE DRILL BASEMENT WALL AND SEAL 3 HOLES TO ROUTE THE NEW

REFRIGERANT AND CONTROL LINES THRU THE EXISTING CONCRETE WALL.M18 CONTRACTOR SHALL ROUTE THESE REFRIGERANT AND CONTROL LINES IN

THE AREA TO AVOID EXISTING CONDITIONS. VISIT SITE PRIOR TO BID AS THEAREA IS VERY CONGESTED. TYPICAL

M19 INSTALL CRAC UNIT IN STRICT COMPLIANCE WITH MANUFACTURERINSTRUCTIONS. AT 6' TO BOTTOM OF UNIT.

M20 CUT INTO THE EXISTING 2" SANITARY LINE AND CONNECT NEW 1-1/2"CONDENSATE DRAIN AS SHOWN.

M21 TRAP THE LINE AT THIS LOCATION WITH A MINIMUM OF A 6" TALL DEEP SEALTRAP. ROUTE CONDENSATE LINE TO THIS OPEN SIGHT DRAIN.

M22 EXISTING 2" SANITARY DRAIN FROM THE SINK TO REMAIN OPERATIONALM23 INSTALL NEW EXHAUST FAN IN COMPLIANCE WITH MANUFACTURERS

INSTRUCTIONS.M24 TAP THIS NEW EXHAUST FAN INTO THE SIDE OF THE EXISTING EXHAUST

DUCTWORK.M25 EXISTING DUCT SHOWN SLIGHTLY SHADED. TYPICAL

North

SCALE: 1/8" = 1'-0"1 Mechanical Plan - Main Level

North

SCALE: 1/8" = 1'-0"2 Mechanical Plan - Lower Level

3 CONDENSING UNIT DETAIL

AIR TERMINAL SCHEDULE

TAG MFG'R MODEL NECK SIZE FACE SIZE SYSTEMMOUNTIN

G MATERIAL FINISHA TUTTLE & BAILEY T1100-06-LT 6" DIA 24"x24" SUPPLY LAY-IN STEEL WHITEB TUTTLE & BAILEY T1100-08-LT 8" DIA 24"x24" SUPPLY LAY-IN STEEL WHITE

RG-1 TUTTLE & BAILEY CRE500 10" x 10" 12" x 12" RETURN SURFACE STEEL WHITERG-2 TUTTLE & BAILEY CRE500 22" x 22" 24" x 24" RETURN SURFACE STEEL WHITE

CONDENSING UNIT SCHEDULE

TAG MFG'R MODEL WEIGHT

COOLING ELECTRICAL

NOTESTOTAL

COOLINGSENSIBLECOOLING SEER VOLTAGE PHASE

ACC-CRAC-1 MITSUBISHI MUZ-GE24NA 119 lb 22500 Btu/h 17325 Btu/h 19.0 SEER 208 V 1 1-6

1. 5 YEAR COMPRESSOR WARRANTY2. ANTI-RECYCLE TIMERS3. LOW AMBIENT OPERATION FOR COOLING DOWN TO 0 DEGREES OUTDOOR TEMPERATURE4. EXTERNAL CRANKCASE HEATERS5. LOW PRESSURE SWITCH6. SERVICE VALVES

DATA ROOM COOLING UNIT SCHEDULE

TAG MFG'R MODEL

FAN ELECTRICAL COOLING FILTERNOTE

SCFM ESP VOLT PH TC SCTHICKNE

SS MERVCRAC-1 MITSUBISHI PKA-A24KA 420 0.1 in-wg 208 V 1 22000 Btu/h 21000 Btu/h 0' - 1" 8 1-7

1 WALL MOUNTED UNIT2 ELECTRIC COIL IN REHEAT POSTION3 ACCESS PANEL ON FRONT4 SMOKE DETECTOR5 STANDARD REMOTE THERMOSTAT SENSOR6 UNIT MOUNTED DISCONNECT ON INDOOR UNIT7 FRONT RETURN AIR GRILL

FAN SCHEDULE

TAG MFG'R MODEL

FAN MOTOR

NOTESTOTAL

CFM TSP TYPE MOUNTING DRIVE VOLTAGE PHASE HPEF-1 LOREN COOK GC-144 100 0.350 in-wg CABINET CEILING DIRECT 120 V 1 105 W 1-5

1. UNIT MOUNTED DISCONNECT2. PREWIRED SPEED CONTROLLER3. RUBBER ISOLATOR HANGERS4. WITH BACKDRAFT DAMPER5. FAN SHALL RUN THRU LIGHT SWITCH

No. Description Date

EXIT LIGHT - UNIVERSAL MOUNT - BAR DENOTES FACE/ARROWS

TELEPHONE TERMINAL BOARD - FIREPROOF PAINTED 3/4" PLYWOOD

COMBINATION MOTOR STARTER

EMERGENCY LIGHT W/ BATTERY - CONNECT TO NEAREST UNSWITCHED LTG CKT

SAFETY/DISC. SWITCH - NON FUSED, "R" DENOTES AMP RATING

SECURITY SYSTEM CARD READER

SPEAKER - WALL AND CEILING MOUNT

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

DUCT SMOKE DETECTOR

FIRE ALARM HORN W/ STROBE - WALL MOUNT

MAGNETIC DOOR HOLD-OPEN

SPRINKLER FLOW SWITCH

PHOTOELECTRIC SMOKE DETECTOR

TTB

JUNCTION BOX

MOTOR

TWIST LOCK RECEP - AS NOTED

TWO-POLE SWITCH

SINGLE POLE SWITCH - 120/277 VOLT, 20 AMP

PANELBOARD

TELECOMMUNICATIONS OUTLET - BLANK COVER U.N.O. +72" INDICATES MTG HEIGHT (REQUIRES1 1/4" CONDUIT STUB INTO ACCESSIBLE CEILING SPACE)

FACP

FAAP

MOUNTED IN OTHERS EQUIPMENT

SPECIAL RECEPTACLE - AS NOTED

SNAP SWITCH W/ PILOT LAMP

THREE-WAY SWITCH

WALL MOUNTED TIMER SWITCH

FOUR-WAY SWITCH

SINGLE POLE SWITCH - WEATHERPROOF

WALL MOUNTED DIMMER SWITCH

SPEAKER VOLUME CONTROL

KEY OPERATED SWITCH

MOTOR THERMAL OVERLAOD SWITCH WITH O.L HEATER AND PILOT LAMP

FIRE ALARM STROBE ONLY - WALL MOUNT

FIRE ALARM MANUAL PULL STATION

FIRE ALARM HORN/STROBE W/PULL STATION BELOW

IONIZATION TYPE SMOKE DETECTOR

SPRINKLER TAMPER SWITCH

F2N/L

SAFETY/DISC. SWITCH - FUSED, "S" DENOTES AMP RATING

ADDRESSABLE WALL MOUNTED OCCUPANCY SENSOR - # INDICATES DEVICE ID

ADDRESSABLE WALL SWITCH/STATION - # INDICATES NUMBER OF PROGRAMMABLE BUTTONS

STAND-ALONE, CEILING MOUNTED OCCUPANCY SENSOR W/ LINE VOLTAGE POWER PACK

CEILING MOUNTED PHOTOCELL

DRY TYPE TRANSFORMER

WIRELESS ACCESS POINT - SEE SPECIFICATIONS FOR EXACT ROUGH-IN RQMTS

PRIMARY FUSED SWITCH

GROUND

CIRCUIT BREAKER

NON-FUSED DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

TRANSFER SWITCH

A-1,3HOMERUN ARROW TO PANELBOARD. TAG INDICATES PANEL / CIRCUITS.

1E-2 DETAIL INDICATOR: TOP # DENOTES DETAIL, BOTTOM # DENOTES SHEET

MAGNETIC MOTOR STARTER

GROUND FAULT INTERRUPTER

HORIZONTAL MOUNT

DUPLEX RECEPTACLE - ELEVATION INDICATES MOUNTING HEIGHT U.N.O.

CR CARD READER / DOOR ACCESS CONTROL

+42"

GFI

FLOOR OUTLET / POKE THRU DEVICE

DEDICATED 20 AMP

SPLIT WIRED

QUAD RECEPTACLE

ISOLATED GROUND

GFI WITH WEATHER PROOF

IG

GFIWP

2

3

4

WP

V

TP

P

T

D

K

OS-D WALL BOX OCCUPANCY SENSOR AND DIMMER SWITCH TYP. - LINE VOLTAGE

OS #

F

F V

F

F F

F

I

F

FS

TS

SPRINKLER POST INDICATOR VALVEPIV

J

OS

AOS

P

ADDRESSABLE, CEILING MOUNTED OCCUPANCY SENSOR - CONNECT TO NETWORKED LIGHTING CONTROL SYSTEM

LIGHT FIXTURE - F2 INDICATES FIXTURE TYPE, N/L INDICATES NIGHTLIGHT

Z#CAN LIGHT FIXTURE - F2 INDICATES FIXTURE TYPE, Z# INDICATES CONTROL ZONEF2

aPENDANT LIGHT FIXTURE - F2 INDICATES FIXTURE TYPE, a INDICATES SWITCHING

+72"

DATA RACK LOCATION - RACK BY OTHERS U.N.O.

R

S

CR

ADA DOOR OPERATORADA

S

WAP

M

PTZ CAMERA - PTZ INDICATES PAN TILT ZOOM

SECURITY SYSTEM KEYPADKP

PUSH BUTTON

+72" SURFACE MOUNTED TELECOM OUTLET

SURFACE MOUNTED DUPLEX

VFD VARIABLE FREQUENCY DRIVE

DOOR CHIMEDC

CONTACTORC

SW DATA/NETWORK SWITCH

TV TV MONITOR ROUGH-IN LOCATION. REFER TO DETAILS FOR CONDUIT RQMTS

EP1 PLAN KEYNOTE REVERENCE

EP1 DEMOLITION PLAN KEYNOTE REVERENCE

400A WIRE SIZE TAG

CONDUIT STUB WITH CAP AND MARKER FOR EXTERIOR WORK

LINETYPE INDICATES NEW ELECTRICAL WORK

LINETYPE INDICATES EXISTING ELECTRICAL TO REMAIN

LINETYPE INDICATES ELECTRICAL DEMOLITION WORK

ELECTRICAL SYMBOLS LEGEND (DOES NOT INDICATE ALL SYMBOLS ARE USED)

WALL BOX OCCUPANCY SENSOR AND ON/OFF SWITCH TYP. - LINE VOLTAGEOS

HEAT DETECTORH

F FIRE ALARM CEILING MOUNTED HORN/STROBE

DUPLEX RECEPTACLE WITH (2) USB JACKSUSB

F FIRE ALARM CEILING MOUNTED STROBE ONLYV

A#

#

GFI

18" A.F.F. TO BOTTOMOF BOX, U.N.O.

24" A.F.F. TO TOP OFBOX, U.N.O.

IN CMU WALLS

4" ABOVE COUNTER/BACKSPLASHTO BOTTOM OF BOX, U.N.O.

ABOVE COUNTERTOPS

GFI

GFI G

FI

FGFI RECEPT. IN RESTOORMSAND JANITOR CLOSETS, U.N.O.

48" A.F.F. TO TOP OF BOX, U.N.O.

BRANCH PANEL LCP

72" A.F.F. TO TOP OF ENCLOSURE, U.N.O.

F

LESSER OF: 80" A.F.F. TO TOP OF BOX, OR6" BELOW CEILING, U.N.O.

T

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/19

/201

7 5:

04:1

4 PM

E0.0

General Electrical

GENERAL ELECTRICAL NOTES1 THE SCOPE OF THE WORK COVERED BY THESE DRAWINGS AND SPECIFICATIONS

INCLUDES LABOR, EQUIPMENT, AND MATERIALS FOR THE COMPLETE ELECTRICALSYSTEM.

2 THE ENTIRE ELECTRICAL INSTALLATION SHALL COMPLY WITH THE NEC AND ALLSTATE AND LOCAL CODES.

3 THE ENTIRE ELECTRICAL SYSTEM SHALL BE GROUNDED IN ACCORDANCE WITHTHE NATIONAL ELECTRICAL CODE

4 EACH CONDUIT RUN SHALL HAVE A SEPARATE GROUND WIRE.5 ALL BRANCH CIRCUITS SHALL HAVE SEPARATE NEUTRAL CONDUCTORS. SHARING

OF NEUTRAL WIRES IS NOT ACCEPTABLE.6 PROVIDE NEW FIRE ALARM PERIPHERAL DEVICES WHERE INDICATED ON PLAN,

AND CONNECT BACK TO EXISTING EST CONTROL PANEL. PROVIDE ALL SETUP,TESTING, AND PROGRAMMING REQUIRED FOR A COMPLETE OPERATIONALSYSTEM, PERFORMED BY A MANUFACTURER AUTHORIZED VENDOR.

7 ON LOWER LEVEL AND UPPER LEVEL, PROVIDE NEW BRANCH CIRCUITS SHOWNFROM EXISTING PANELBOARDS PP1 AND PP3. PROVIDE NEW BRANCH CIRCUITBREAKERS IN PANELS AS REQUIRED.

8 ON MAIN LEVEL, RE-USE EXISTING BRANCH CIRCUITS FROM PANEL PP2, FREED UPBY DEMOLITION WHEREEVER POSSIBLE. IF THERE IS INSUFFICIENT SPACE IN PP2FOR FOR ANY NEW BRANCH CIRCUITS SHOWN, FEED THESE CIRCUITS FROM NEWPANEL PP4 ADDED IN STORAGE ROOM #124

9 PROVIDE UPDATED, TYPED CIRCUIT DIRECTORY WITH CLEAR PROTECTIVECOVER/HOLDER INSIDE DOOR OF ALL NEW AND EXISTING PANELBOARDS.

10 MC TYPE CABLE IS ALLOWABLE IN HORIZONTAL RUNS, INSTALLED CONCEALED INSTUD WALLS BETWEEN OUTLET DEVICES, CONNECTIONS TO MOVING ORVIBRATING EQUIPMENT, AND FOR FINAL CONNECTION TO LIGHT FIXTURES (6 FT.MAX).

11 USE BOLTED CLAMP TYPE HANGERS FOR SUPPORTING CONDUITS. ONE-HOLESTRAP AND SPRING TYPE CONDUIT HANGERS ARE NOT ACCEPTABLE.

12 ELECTRICAL CONTRACTOR SHALL PROVIDE BACKBOXES, CONDUIT, ANDPATHWAYS FOR NETWORK AND A/V SYSTEMS AS INDICATED ON DRAWINGS. ALLCABLING, JACKS, TERMINATIONS, AND EQUIPMENT SHALL BE PROVIDED BYOTHERS.

GENERAL LIGHTING NOTES1 LIGHT FIXTURES IN COMMON SPACES - LOBBIES, CORRIDORS, GATHERING AREA,

ETC. ARE TO BE CONTROLLED BY TIME OF DAY FUNCTIONS AND OCCUPANCYSENSORS THROUGH NETWORKED, ADDRESSABLE LIGHTING CONTROL SYSTEM.LIGHTS SHALL COME ON AT TIME DETERMINED BY OWNER. NO OVERRIDE TO BEPROVIDED DURING NORMAL OPERATING HOURS. MOTION SENSORS SHALLFUNCTION AS PRIMARY CONTROL DURING OFF HOURS - SENSORS SHALL BRINGLIGHTS ON AFTER HOURS. VERIFY TIME DELAY OVERRIDE WITH OWNER.COORDINATE ALL SCHEDULING WITH OWNER.

2 FIXTURES NOT INDICATED TO BE CONTROLLED BY NETWORKED LIGHTINGCONTROL SYSTEM SHALL BE CONTROLLED THROUGH LINE VOLTAGE STANDALONE OCCUPANCY SENSORS, EITHER WALLBOX TYPE SENSORS FOR SMALLSPACES, OR CEILING MOUNTED SENSORS FOR LARGER AREAS.

3 CONNECT ALL EXIT SIGNS, SELF CONTAINED, BATTERY POWERED EMERGENCYLIGHTS, AND LIGHT FIXTURES LABELED AS NIGHTLIGHTS UNSWITCHED TOLIGHTING CIRCUIT IN THAT AREA, BYPASSING ALL SWITCHES OR CONTROLS.

4 LIGHT FIXTURES SHALL BE AS SCHEDULED OR APPROVED EQUAL 10 DAYS PRIORTO BID.

5 STAND ALONE OCCUPANCY SENSORS SHALL HAVE SEPARATE LINE VOLTAGERELAYS/POWER PACKS FOR CONTROL OF LIGHTING CIRCUIT AND LOW VOLTAGEWIRING CONNECTION TO SENSOR TO ALLOW FOR RELOCATION OR MULTIPLESENSORS. SENSORS SHALL BE DUAL TECHNOLOGY TYPE. APPROVEDMANUFACTURER’S FOR LINE-VOLTAGE CEILING AND WALLBOX SENSORS SHALLBE WATT STOPPER, SENSOR SWITCH, AND LEVITON.

6 OCCUPANCY SENSOR LOCATIONS ON PLANS ARE SHOWN TO INDICATE AREAS TOBE COVERED, AND LIGHTS TO BE CONTROLLED. OCCUPANCY SENSORMANUFACTURER SHALL ADJUST LOCATIONS, QUANTITIES, AND SENSOR TYPES TOENSURE PROPER COVERAGE OF ALL AREAS. PROVIDE ADDITIONAL SENSORS IFNEEDED TO COVER ENTIRE AREA. USE WALL MOUNTED, LONG THROW SENSORSFOR CORRIDORS WHERE APPLICABLE, AND CEILING MOUNTED SENSORS INOTHER AREAS.

7 WALLBOX TYPE SENSORS SHALL HAVE INTEGRAL ON/OFF OVERRIDE SWITCH,ADJUSTABLE TIME DELAY, AND PROGRAMMABLE MODES OF OPERATION (MANUALON/AUTO OFF, AUTO ON/AUTO OFF, ETC). SENSORS SHALL BE CAPABLE OF BEINGMASKED OFF TO PREVENT FALSE ON SIGNAL FROM CERTAIN AREAS OFCOVERAGE.

8 WHERE CEILING MOUNTED STAND ALONE SENSORS ARE SHOWN IN ROOMS WITHLINE VOLTAGE SWITCHES, SWITCH AND SENSOR SHALL BE WIRED IN SERIES. SEESENSOR WIRING DETAIL ON SHEET E3.1

9 IN AREAS WHERE LED OR FLUORESCENT FIXTURES ARE SHOWN TO BE DIMMED,CONTRACTOR SHALL RUN LOW VOLTAGE CONTROL CABLE TO EACH FIXTURE INADDITION TO LINE VOLTAGE WIRING. CONTROL WIRING MAY BE RUN USING OPENCABLING.

10 E.C. SHALL PROVIDE ALL REQUIRED CABLING TO INTERCONNECT ALL CONTROLDEVICES, INCLUDING RJ-45 PLUGS ON ALL CABLES

111213

GENERAL ELECTRICAL DEMOLITION NOTES1 REMOVE ELECTRICAL WORK FROM WALLS, CEILINGS AND OTHER SURFACES TO BE

REMOVED. EXISTING BOXES AND CONDUIT MAY BE RE-USED IF ALL REQUIREMENTSSHOWN ON DRAWINGS ARE SATISFIED.

2 REMOVE ALL ABANDONED CONDUCTORS, ELECTRICAL EQUIPMENT AND ACCESSIBLERACEWAYS INCLUDING LOW-VOLTAGE, INTERCOM, AND BELLS

3 EXISTING EQUIPMENT, DEVICES, ETC. INDICATED TO REMAIN ARE INTENDED TO REMAINOPERATIONAL. EXTEND OR REROUTE CIRCUITS AS REQUIRED TO KEEP DOWN STREAMDEVICES OPERATIONAL.

4 REMOVE EXISTING LIGHT FIXTURES FROM ALL AREAS WHERE NEW LIGHTING ISINDICATED.

5 EXISTING EQUIPMENT IS INTENDED TO BE A REASONABLE APPROXIMATION AND IS FORCONVENIENCE ONLY, NOT FOR THE BASIS OF BIDDING. DETERMINE EXACT QUANTITIESAND LOCATIONS AT JOB SITE.

6 ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR DISCONNECTING AND REMOVIINGPOWER FEEDS TO ALL FIXED EQUIPMENT SHOWN TO BE REMOVED OR RELOCATED.

7 FOR CAMERAS, SECURITY SYSTEM, WAP AND OTHER SIMILAR EQUIPMENT INDICATED TOREMAIN - E.C. TO SUPPORT EQUIPMENT WHERE CEILINGS ARE SHOWN TO BE REPLACED,AND REINSTALL WHEN NEW CEILING IS IN PLACE.

ELECTRICAL DRAWING INDEXZ Export to GC

E0.0 General Electrical

ED1.1 Electrical Demolition Plan - Main & SecondLevels

E1.1 Power Plan - Lower, Main, & Second Levels

E2.1 Lighting Plan - Lower, Main, & SecondLevels

E4.1 Electrical Schedules

E6.1 Electrical Specifications

NTS1 Standard Electrical Mounting Heights

VOLTAGE DROP SCHEDULE (all sizes based on copper conductors)

LOADAMPACITY WIRE SIZE

MAX WIRE LENGTH -120/208V

MAX WIRE LENGTH -277/480V

2% DROP -FEEDERS

3% DROP -BRANCH

CKTS2% DROP -FEEDERS

3% DROP -BRANCH

CKTS50 A #8 69' 103' 158' 238'50 A #6 107' 160' 246' 370'50 A #4 160' 240' 370' 554'50 A #3 200' 300' 462' 693'50 A #2 240' 360' 554' 831'

60 A #6 89' 133' 205' 308'60 A #4 133' 200' 308' 462'60 A #3 167' 250' 385' 577'60 A #2 200' 300' 462' 693'60 A #1 250' 375' 577' 866'

80 A #4 100' 150' 231' 346'80 A #3 125' 188' 289' 433'80 A #2 150' 225' 346' 520'80 A #1 188' 281' 433' 650'80 A #1/0 231' 346' 533' 799'

100 A #3 100' 150' 231' 346'100 A #2 120' 180' 277' 416'100 A #1 150' 225' 346' 520'100 A #1/0 185' 277' 426' 640'100 A #2/0 218' 328' 504' 756'

150 A #1/0 123' 185' 284' 426'150 A #2/0 146' 218' 336' 504'150 A #3/0 170' 256' 393' 590'150 A #4/0 200' 300' 462' 693'150 A #250 219' 329' 506' 759'

200 A #3/0 128' 192' 295' 426'200 A #4/0 150' 225' 346' 520'200 A #250 165' 247' 380' 569'200 A #300 185' 277' 426' 640'200 A #350 200' 300' 462' 693'

350 A #350 114' 172' 264' 396'350 A #400 123' 184' 283' 424'350 A #500 137' 206' 317' 475'350 A #600 146' 219' 337' 505'

400 A #600 128' 192' 295' 442'

No. Description Date

T

T

T

+36"

+36"

+0"

3

3

OFFICE106

STORAGE131

MEETINGHOUSE-1

132-1

GATHERINGROOM

127

LOBBY100

COORIDOR103

CHOIRROOM

133

KITCHEN129

VEST.130

ED1

ED1

ED2

4E1.1

STUDYROOM

228CLASSROOM/SEMINAR

227

CLASSROOM223

CLASSROOM224

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/19

/201

7 5:

06:0

5 PM

ED1.1

Electrical DemolitionPlan - Main & Second

Levels

NORTH

SCALE: 1/8" = 1'-0"1 Electrical Demolition Plan - Main Level

ELECTRICAL DEMOLITION KEYNOTESED1 REUSE EXISTING BACKBOX AND CONDUIT FOR NEW LOW VOLTAGE ADDRESSABLE LIGHTING

CONTROL STATION.ED2 REPLACE EXISTING INCANDESCANT CAN LIGHTS WITH NEW RETROFIT TYPE LED CAN LIGHT

FIXTURES. SEE LIGHTING PLANS FOR ADDITIONAL INFO.

NORTH

SCALE: 1/8" = 1'-0"2 Electrical Demolition Plan - Second Level

No. Description Date

T

TT

T T

+48"

+48"

+42"GFI

+42"GFI

+42"GFI

+42"GFI

+30"

FV

TV

+78" +7

8"+7

8"

GFI

+30"

+30"

TV

+78"

+78"

TV +78"

GFI

+36"GFI

LOBBY100

RECEPTION104

OFFICE134

OFFICE106

STORAGE131

VEST.130

MEETINGHOUSE-1

132-1

GATHERINGROOM

127

KITCHEN129

LPP-4

LPP-4-4

EP3

LPP-4-3

LPP-4-6

LPP-4-15

REF

REF

LPP-4-16

EP4

LPP-4-5

LPP-4-14

ACC-CRAC-1LPP-4-20

LPP-4-21

EP7EP6EP6

LPP-4-22

LPP-4-2

LPP-4-23 LPP-4-24

LPP-4-7 LPP-4-8

LPP-4-9 LPP-4-10 LPP-4-11

LPP-4-12

LPP-4-13

R.R.B13

Mech.B14

STORAGE/MECH.B10

CRAC-1

120V/1 POWER FED FROM ACC-CRAC-1

MICROWAVERECEPTACLE

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/19

/201

7 5:

04:3

9 PM

E1.1

Power Plan - Lower,Main, & Second Levels

NORTH

SCALE: 1/8" = 1'-0"1 Power Plan - Main Level

POWER PLAN KEYNOTESEP3 NEW CEILING MOUNTED FRIE ALARM STROBE. CONNECT TO EXISTING NOTIFICATION

APPLIANCE CIRCUIT FROM FIRE ALARM PANEL.EP4 CONNECT RECEPTACLES TO NEW 20 AMP BRANCH CIRCUIT BREAKER IN EXISTING PANEL

LPP2EP6 MOUNT RECEPTACLES HORIZONTALLY TO CASEWORK.EP7 MOUNT RECEPTACLE TO CASEWORK AS SHOWN IN DETAIL 4 ON SHEET E1.1.

NORTH

SCALE: 1/8" = 1'-0"2 Power Plan - Second Level

NORTH

SCALE: 1/4" = 1'-0"3 Lower Level Power PlanNTS4 Microwave Receptacle

No. Description Date

A4

A4

A4

A4

A4

OSA

OSA

OSA

OSA

OSA

OSA

OS

OSOS

A4

OSA OS

AOS

A

OSA

OSA

A4 A4 A4

A4A4

OS

F1 , Z2 F1 , Z2

F1 , Z2F1 , Z2F1 , Z2

F1 , Z2F1 , Z2F1 , Z2

F1 , Z2F1 , Z2F1 , Z2

F1 , Z2F1 , Z2F1 , Z2

F1 , Z2F1 , Z2

F1 , Z2

F1 , Z2F1 , Z2

F1 , Z2F1 , Z2F1 , Z2

F1 , Z1

F1 , Z1

F1 , Z2F1 , Z2

F1 , Z1

F1 , Z1

MEETINGHOUSE-1

132-1

LOBBY100

RECEPTION104

VEST.130

STORAGE131

OFFICE134

OFFICE106

KITCHEN129

F1 , Z2

F1 , Z2

F1 , Z3

F1 , Z3

F1 , Z3

F1 , Z3

F1 , Z3

F1 , Z3

F1 , Z3

F1 , Z3

F1 , Z3

F1 , Z3

F1 , Z3

F1 , Z3

F1 , Z3

F1 , Z3

F1 , Z3

F1 , Z3 F1 , Z3 F1 , Z3 F1 , Z3F1 , Z3

F1 , Z4

F1 , Z4

F1 , Z4

F1 , Z4

F2

F2

F2

GATHERINGROOM

127

F3 F3

F3 F3

F3

F3 F3 F3

F3 F3

F1 , Z2 F1 , Z2

F3

F3

REF

REF

EL1

EL1

EL2

EL2

EL5

EL4(TYP)

EL3EL6

X2

X2

X1X1

X2X2

X1

X1

X1

F3 , Z5 F3 , Z5 F3 , Z5

F3 , Z5 F3 , Z5 F3 , Z5

F3 , Z5 F3 , Z5 F3 , Z5

F3 , Z6 F3 , Z6 F3 , Z6

F3 , Z6 F3 , Z6 F3 , Z6

F3 , Z6 F3 , Z6F3 , Z6

F3

F3 , Z8F3 , Z7 F3 , Z7

F3 , Z7 F3 , Z7

F3 , Z7 F3 , Z7

F3 , Z8

F3 , Z8 F3 , Z8

F3 , Z8 F3 , Z8

F3 , Z9

F3 , Z9

F3 , Z9

F3 , Z9

F3 , Z9

F3 , Z9

R.R.B13

Mech.B14

STORAGE/MECH.B10

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/19

/201

7 5:

05:0

1 PM

E2.1

Lighting Plan - Lower,Main, & Second Levels

NORTH

SCALE: 1/8" = 1'-0"1 Lighting Plan - Main Level

LIGHTING PLAN KEYNOTESEL1 CONNECT NEW LIGHTS IN LOBBY AND GATHERING SPACES TO EXISTING LIGHTING

BRANCH CIRCUITS, FREED UP AS PART OF DEMOLITION.EL2 REMOVE EXISTING LINE VOLTAGE SWITCH AND WIRING, AND RE-USE EXISTING BACKBOX

AND CONDUIT FOR NEW ADDRESSABLE LIGHTING CONTROL STATION.EL3 REMOVE EXISTING DIMMER RACK IN CHAPEL AND REPLACE WITH NEW 12 POLE DIMMER

RACK IN SAME LOCATION - ETC MODEL DR6 WITH (6) ELV DUAL DIMMER MODULES ANDPARADIGM CONTROL STATION. RECONNECT EXISTING DIMMED BRANCH CIRCUITS TONEW DIMMER MODULES.

EL4 PROVIDE ALTERNATE PRICE TO REPLACE EXISTING T4 LAMPS IN ALL CAN LIGHTS WITHNEW DIMMABLE LED REPLACEMENT LAMPS - RLED LIGHTING MODEL120-RPL-007-RP-006-E11.

EL5 REPLACE EXISTING ARCHITECTURAL CONTROL STATION WITH NEW ETC MODEL UH10005ON SAME BACKBOX. PROVIDE NEW CONTROL CABLING AS REQUIRED FROM DIMMERRACK.

EL6 PROVIDE NEW ADDITIONAL ARCHITECTURAL CONTROL STATION - ETC UH1005 ON WALLOUTSIDE OF CONTROL ROOM. FURNISH W/ INFRARED RECEIVER AND HAND HELDREMOTE TO ALLOW FOR CALL UP OF SCENE PRESETS.

NORTH

SCALE: 1/8" = 1'-0"2 Lighting Plan - Second Level

NORTH

SCALE: 1/4" = 1'-0"3 Lower Level Lighting Plan

LIGHT FIXTURE SCHEDULE

MARK MANUFACTURER MODEL NO. MOUNTING FINISHLAMPING

VOLTAGEFIXTURE

WATTAGE REMARKSWATTAGE LAMP120 V

F1 GOTHAM EVO 40/15 4WR WDLSS 120 EZ1NPS80EZ

RECESSED WHITE 33 W LED 120 V 33 W 4" CAN WITH SEMI SPECULAR DIFFUSER AND WHITETRIM

F2 BRUCK 113-920-MC--MP PENDANT BLACK 18 W LED 120 V 18 W CUSTOM PENDANT.F3 LITHONIA 2VLT4 60L ADP EZ1

LP840 NES7RECESSED WHITE 52 W LED 120 V 0 W 2X4 LAY IN TROFFER

X1 LITHONIA LQM-S-W-R-ELN UNIVERSAL WHITE/RED 4 W LED 120 V 4 W WALL MOUNTED. NICAD EMERGENCY BATTERYX2 LITHONIA ELM2-LED WALL WHITE 3 W LED 120 V 6 W

No. Description Date

LOCAL EM POWERPACK WITH RELAYFOR CONTROL OF

LIGHTING LOADEMERGENCY LINE VOLTAGE IN

TO OTHERDEVICES

(OPT.)

OCCSENSOR

(typ.)

PHOTOSENSOR

(typ.)

WALLSWITCH

(typ.)

LOCAL POWERPACK WITH RELAYFOR CONTROL OF

LIGHTING LOAD

LTG

LINE VOLTAGE IN

OCCSENSOR

(typ.)

PHOTOSENSOR

(typ.)

WALLSWITCH

(typ.)

BRIDGEMODULE

POWERSUPPLY

LINE VOLTAGE IN

LOCAL DIMMINGPOWER PACK

WITH RELAY FORCONTROL OF

LIGHTING LOADLINE VOLTAGE IN

TO OTHERDEVICES

(OPT.)

OCCSENSOR

(typ.)

PHOTOSENSOR

(typ.)

WALLSWITCH

(typ.)

LOCAL POWERPACK WITH RELAYFOR CONTROL OF

LIGHTING LOADLINE VOLTAGE IN

OCCSENSOR

(typ.)

PHOTOSENSOR

(typ.)

WALLSWITCH

(typ.)

BRIDGEMODULE

POWERSUPPLY

LINE VOLTAGE IN

GATEWAY AREACONTROLLER

POWERSUPPLY

LINE VOLTAGE IN

OWNER'S LANNETWORK

TO ADD'L BRIDGEDEVICES

WEB BASEDCONTROLSSOFTWARE

CAT5 / CAT5e CABLING

LINE VOLTAGE (120V OR 277V)

CLASS B LOW-VOLTAGE WIRING

LINETYPE LEGEND

EM. LTG

LTG

LTG

LINE VOLTAGE(SENSING ONLY)

TO ADD'L BRIDGE ORLIGHTING ZONES

TO ADD'L BRIDGE ORLIGHTING ZONES

TO ADD'L BRIDGE ORLIGHTING ZONES

TO ADD'L BRIDGE ORLIGHTING ZONES

BACNET IPINTERFACE

BACNET INTERFACEBY T.C.C. (IFAPPLICABLE)

0-10V DIMMING CONDUCTORSWHERE FIXTURE INDICATED

TO BE DIMMED

THIS DETAIL IS MEANT TO INDICATE TYPICAL WIRINGREQUIREMENTS FOR A NETWORKED LIGHTING CONTROL SYSTEMAND DOES NOT MEAN THAT ALL COMPONENTS SHOWN ARE INTHIS PROJECT. TOPOLOGY AND WIRING REQUIREMENTS MAYALSO VARY DEPENDING UPON THE MANUFACTURER AND MODELOF LIGHTING CONTROL SYSTEM.

APPROVED MANUFACTURERS FOR LIGHTING CONTROLSYSTEM ARE ACUITY NLIGHT SYSTEM AND HUBELL LIGHTINGNX SYSTEM

1' -

6"2G BOX WITH BLANKCOVER PLATE (SHOWN ASDATA RECEP. ON PLANS)

2-GANG BOX WITH BLANK COVER PLATE FORDATA/VIDEO/AUDIO. PROVIDE DUPLEX RECEPTACLEMOUNTED NEXT TO BOX. FIELD VERIFYDATA/VIDEO/AUDIO NEEDS WITH OWNER.

MO

UN

TIN

G H

GT

ASIN

DIC

ATED

ON

PLA

NS

1-1/4" EMTBETWEEN BOXES1-1/4" EMT STUBBED OUT ABOVE

ACCESSIBLE CEILING

1-1/4" EMT STUBBED OUT ABOVEACCESSIBLE CEILING

PROVIDE 120V POWER FROM CIRCUITS SHOWN ONPLANS. PROVIDE SEPARATE CONDUIT FOR 120V POWER.CONDUIT PATHWAYS SHOWN ARE FOR DATA/A.V. USEONLY.

CEILING

FLOOR

PROVIDE WOOD BLOCKING AS REQUIRED FORMOUNTING TV BRACKET TO WALL.

UTILITYXFMR

MDP

LPP-1

LPP-2

LPP-3

PP-4

LPP-4

(4) #3, #8 GRD. , 1 1/4" C.

BASEMENT

FIRST FLOOR

SECOND FLOOR

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/19

/201

7 5:

05:2

0 PM

E4.1

Electrical Schedules

MECHANICAL EQUIPMENT SCHEDULE

MARK VOLTS PHASE PNL

POWERAPPARENT

LOAD WIRE SIZE

DISCONNECTING MEANS

PROVIDED BYCRAC-1 120 V 1 0.11 kW (2) #12, #12 GRD, 1/2" C. UNIT MOUNTED DISCONNECTEF-1 120 V 1 0.12 kW (2) #12, #12 GRD, 1/2" C. UNIT MOUNTED DISCONNECTACC-CRAC-1 208 V 1 6.12 kW (3) #12, #12 GRD, 1/2" C. E.C. PROVIDED DISCONNECT

RELAY CONTROL SCHEDULE

RELAYFIXTURE

TYPEPOWER CONTROLS

CONTROLS COMMENTSPANEL CKT CONTROL CAPABILITIES CONTROL INPUTSZ1 F1 ON/OFF, DIM 1% ADDRESSABLE SWITCH, OCCUPANCY SENSORZ2 F1 ON/OFF, DIM 1% ADDRESSABLE SWITCH, TIME CLOCK, OCCUPANCY

SENSORTIME CLOCK TO TURN ON LIGHTS DURING BUSINESS HOURS. OS TO TURN LIGHTS ON TO10% WHEN AFTER HOURS. ADDRESSABLE SWITCH OVERRIDES BOTH TIME CLOCK ANDOS.

Z3 F1 ON/OFF, DIM 1% ADDRESSABLE SWITCH, OCCUPANCY SENSOR LIGHTS TO TURN ON WHEN OCCUPANCY SENSOR DETECTS MOVEMENT. ADDRESSABLESWITCH OVERRIDES OCCUPANCY SENSOR

Z4 F1 LPP-4 19 ON/OFF, DIM 1% ADDRESSABLE SWITCH, OCCUPANCY SENSOR LIGHTS TO TURN ON WHEN OCCUPANCY SENSOR DETECTS MOVEMENT. ADDRESSABLESWITCH OVERRIDES OCCUPANCY SENSOR

Z5 F3 LPP-4 17 ON/OFF, DIM 1% ADDRESSABLE SWITCH, OCCUPANCY SENSOR LIGHTS TO TURN ON WHEN OCCUPANCY SENSOR DETECTS MOVEMENT. ADDRESSABLESWITCH OVERRIDES OCCUPANCY SENSOR

Z6 F3 LPP-4 17 ON/OFF, DIM 1% ADDRESSABLE SWITCH, OCCUPANCY SENSOR LIGHTS TO TURN ON WHEN OCCUPANCY SENSOR DETECTS MOVEMENT. ADDRESSABLESWITCH OVERRIDES OCCUPANCY SENSOR

Z7 F3 LPP-4 17 ON/OFF, DIM 1% ADDRESSABLE SWITCH, OCCUPANCY SENSOR LIGHTS TO TURN ON WHEN OCCUPANCY SENSOR DETECTS MOVEMENT. ADDRESSABLESWITCH OVERRIDES OCCUPANCY SENSOR

Z8 F3 LPP-4 17 ON/OFF, DIM 1% ADDRESSABLE SWITCH, OCCUPANCY SENSOR LIGHTS TO TURN ON WHEN OCCUPANCY SENSOR DETECTS MOVEMENT. ADDRESSABLESWITCH OVERRIDES OCCUPANCY SENSOR

Z9 F3 LPP-4 17 ON/OFF, DIM 1% ADDRESSABLE SWITCH, OCCUPANCY SENSOR LIGHTS TO TURN ON WHEN OCCUPANCY SENSOR DETECTS MOVEMENT. ADDRESSABLESWITCH OVERRIDES OCCUPANCY SENSOR

NORTH

SCALE: 1/8" = 1'-0"1 Lighting Control Wiring DiagramNORTH

SCALE: 3/4" = 1'-0"2 Typical Wall Mounted Monitor Rough-In

NORTH

SCALE: 1/8" = 1'-0"3 One Line Diagram

Legend:Total Amps: 34 A 30 A 21 ATotal Load: 3.97 kW 3.42 kW 2.53 kW

29 3027 2825 2623 RECEPT 1 0.18... 0.18... 1 RECEPT 2421 RECEPT KITCHEN 129 1 0.18... 0.18... 1 RECEPT 2219 KITCHEN 129 1 0.19... 0.18... 1 RECEPT 2017 ROOM 223, 224, 227, 228 1 0.01... 0.00... 1 ROOM 127, 129, 104, 106, 134 1815 RECEPT 1 0.54... 0.54... 1 RECEPT 1613 RECEPT 1 0.90... 0.18... 1 RECEPT KITCHEN 129 1411 POWER CLASSROOM/SEMINAR 227 1 0.72... 0.90... 1 RECEPT 129 POWER STUDY ROOM 228 1 0.72... 0.72... 1 POWER CLASSROOM/SEMINAR 227 107 POWER CLASSROOM 223 1 0.72... 0.72... 1 POWER CLASSROOM 224 85 RECEPT 1 0.18... 0.36... 1 RECEPT 63 RECEPT 1 0.18... 0.36... 1 RECEPT ROOM 127 41 RECEPT 1 0.90... 0.18... 1 RECEPT 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: TYPE 1Mounting: RECESSED Wires: 4 Mains Rating: 100 A

Supply From: Phases: 3 Mains Type: MLOLocation: GATHERING ROOM 127 Volts: 120/208 A.I.C. Rating: 10000

Branch Panel: LPP-4

MDPMDP

No. Description Date

DRAWINGS AND GENERAL PROVISIONS OF CONTRACT, INCLUDING GENERAL ANDSUPPLEMENTARY CONDITIONS AND DIVISION 1 SPECIFICATION SECTIONS, APPLY TO THISAND THE OTHER SECTIONS OF DIVISION 16.

THE SCOPE OF THE WORK COVERED BY THESE SPECIFICATIONS INCLUDES LABOR,EQUIPMENT, AND MATERIALS FOR THE COMPLETE ELECTRICAL SYSTEM.

UNLESS OTHERWISE INDICATED MATERIALS AND EQUIPMENT ARE NEW, OFMANUFACTURERS STANDARD CONSTRUCTION, INSTALLED IN ACCORDANCE WITH ACCEPTEDPRACTICE. THE ENGINEER WILL GIVE NOTIFICATION UPON OBSERVATION OFUNSATISFACTORY WORK; HOWEVER, RESPONSIBILITY CONTINUES FOR CORRECTION OFDEFECTIVE MATERIAL AND WORK DISCLOSED DURING THE GUARANTEE PERIOD OR THE FIRSTOPERATING SEASON.

THE DRAWINGS AND SPECIFICATION ARE COOPERATIVE AND SUPPLEMENTARY, AND IT IS THEINTENT OF BOTH DRAWINGS AND SPECIFICATIONS TO COVER THE ELECTRICALREQUIREMENTS AS NEARLY AS POSSIBLE. CLOSELY CHECK THE DRAWINGS ANDSPECIFICATIONS FOR ANY OBVIOUS CONFLICTS, ERRORS OR OMISSION AND NOTIFY THEENGINEER OF ANY PRIOR TO THE RECEIPT OF BIDS, IN ORDER TO PERMIT CLARIFICATION BYMEANS OF WRITTEN ADDENDUM.

RELATED DOCUMENTS

COMPLY WITH OR EXCEED THE REQUIREMENTS OF THE LATEST EDITION OF THE NATIONALELECTRICAL CODE, AND APPLICABLE LOCAL, STATE, AND FEDERAL ORDINANCES.

DETERMINE THE EXISTENCE OF, AND INCLUDE AMOUNTS OF ANY FEES, LEVIES, TAXES,ASSESSMENTS AND OTHER COSTS REQUIRED BY THIS WORK.

PERMITS AND CODES

RESPONSIBILITY EXTENDS BEYOND THE INSTALLATION AND CONNECTIONS OF THE VARIOUSAPPARATUS. PROVIDE THE ELECTRICIANS TO PROPERLY ADJUST THE VARIOUS ELECTRICALDEVICES, BALANCE PHASES, MAKE THE REQUIRED TESTS, ETC., UNTIL THE ENTIRE ELECTRICALINSTALLATION FUNCTIONS PROPERLY IN EVERY DETAIL.

RESPONSIBILITY

PREPARE RECORD DOCUMENTS, IN ADDITION TO THE REQUIREMENTS SPECIFIED INDIVISION 1, INDICATE INSTALLED CONDITIONS FOR:

RECORD DOCUMENTS

1. MAJOR RACEWAY SYSTEMS, SIZE AND LOCATION, FOR BOTH EXTERIOR ANDINTERIOR; LOCATIONS OF CONTROL DEVICES; DISTRIBUTION AND BRANCHELECTRICAL CIRCUITRY; AND FUSE AND CIRCUIT BREAKER SIZE ANDARRANGEMENTS.

2. EQUIPMENT LOCATIONS (EXPOSED AND CONCEALED), DIMENSIONED FROMPROMINENT BUILDING LINES.

3. APPROVED SUBSTITUTIONS, CONTRACT MODIFICATIONS, AND ACTUALEQUIPMENT AND MATERIALS INSTALLED.

PREPARE MAINTENANCE MANUALS, IN ADDITION TO THE REQUIREMENTS SPECIFIED INDIVISION 1, INCLUDE THE FOLLOWING INFORMATION FOR EQUIPMENT ITEMS:

MAINTENANCE MANUALS

1. DESCRIPTION OF FUNCTION, NORMAL OPERATING CHARACTERISTICS ANDLIMITATIONS, PERFORMANCE CURVES, ENGINEERING DATA AND TESTS, ANDCOMPLETE NOMENCLATURE AND COMMERCIAL NUMBERS OF REPLACEMENTPARTS.

2. MANUFACTURER'S PRINTED OPERATING PROCEDURES TO INCLUDESTART_UP, BREAK_IN, AND ROUTINE AND NORMAL OPERATINGINSTRUCTIONS; REGULATION, CONTROL, STOPPING, SHUTDOWN, ANDEMERGENCY INSTRUCTIONS; AND SUMMER AND WINTER OPERATINGINSTRUCTIONS.

3. MAINTENANCE PROCEDURES FOR ROUTINE PREVENTATIVE MAINTENANCEAND TROUBLESHOOTING; DISASSEMBLY, REPAIR, AND REASSEMBLY; ALIGNINGAND ADJUSTING INSTRUCTIONS.

4. SERVICING INSTRUCTIONS AND LUBRICATION CHARTS AND SCHEDULES.5. COPIES AND DOCUMENTATION OF ALL SOFTWARE REQUIRED FOR

PROGRAMMING EQUIPMENT.

ALL WORK SHALL CONFORM TO OR EXCEED THE MINIMUM REQUIREMENTS OF THENATIONAL ELECTRIC CODE (N.E.C.) , LATEST EDITION, AND ALL FEDERAL, STATE, LOCALAND MUNICIPAL ORDINANCES. THE CONTRACTOR SHALL COMPLY WITH THEDIRECTIONS OF ALL PROPERLY APPOINTED AUTHORITIES HAVING JURISDICTION.

INSTALLATIONS SHOWN ON DRAWINGS OR REQUIRED HEREIN THAT EXCEED THEMINIMUM REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE OR OTHERREGULATIONS SHALL BE INSTALLED AS SHOWN OR SPECIFIED.

THE CONTRACTOR SHALL VISIT THE PROJECT SITE, AND FAMILIARIZE HIMSELF WITH ALLEXISTING CONDITIONS WHICH WILL AFFECT HIS WORK. HE SHALL ALSO REVIEW THEDRAWINGS AND SPECIFICATIONS OF OTHER TRADES AND TAKE NOTE OF CONDITIONSTO BE CREATED WHICH WILL ALSO AFFECT HIS WORK. ALL CONDITIONS WILL BECONSIDERED IN THE PREPARATION OF BIDS. NO ADDITIONAL MONEY WILL BE PAID TOCHANGE OR CORRECT CONDITIONS THAT WERE EVIDENT AT THE TIME OF BID.

THE CONTRACTOR SHALL ROUGH-IN FOR AND/OR MAKE FINAL CONNECTIONS ASREQUIRED TO ALL MISCELLANEOUS EQUIPMENT FURNISHED BY THE OWNER OR UNDEROTHER SECTIONS OF THESE SPECIFICATIONS. CONTRACTOR SHALL PROVIDE SAFETYDISCONNECTS AND OTHER MISCELLANEOUS PROTECTIVE DEVICES AS REQUIRED BYCODE. ALL WORK SHALL BE ROUGHED-IN AND CONNECTED IN ACCORDANCE WITHAPPROVED SHOP DRAWINGS.

THE NUMBER OF WIRES FOR LIGHTING AND RECEPTACLE BRANCH CIRCUITS ARE NOTSHOWN ON THE DRAWINGS. THE NUMBER OF WIRES IN ANY CIRCUIT SHALL BEDETERMINED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND WIRINGSHALL BE PROVIDED TO PERFORM ALL FUNCTIONS OF THE DEVICES BEING INSTALLED.ADDITIONALLY, WIRES SHALL BE PROVIDED AS REQUIRED BY THE CONTRACTDOCUMENTS, I.E., EQUIPMENT GROUNDS, ETC. PROVIDE THE NUMBER OF WIRESREQUIRED FOR A COMPLETE AND WORKABLE SYSTEM.

THE CONTRACTOR SHALL REVIEW ALL DRAWINGS, FROM ALL DISCIPLINES IN THEPREPARATION OF HIS BID. CONTRACTOR SHALL PROVIDE ROUGH-INS AND FINALEQUIPMENT CONNECTIONS TO ALL EQUIPMENT, REGARDLESS OF WHETHER ITAPPEARS ON ELECTRICAL DRAWINGS.

VERIFY FINAL LOCATIONS FOR ROUGH_INS WITH FIELD MEASUREMENTS AND WITH THEREQUIREMENTS OF THE ACTUAL EQUIPMENT TO BE CONNECTED.

REFER TO EQUIPMENT SPECIFICATIONS IN DIVISIONS 2 THROUGH 16 FOR ROUGH_INREQUIREMENTS.

EXECUTION OF WORK

SEQUENCE, COORDINATE, AND INTEGRATE THE VARIOUS ELEMENTS OF ELECTRICAL SYSTEMS,MATERIALS, AND EQUIPMENT. COMPLY WITH THE FOLLOWING REQUIREMENTS:

ELECTRICAL INSTALLATIONS

1. COORDINATE ELECTRICAL SYSTEMS, EQUIPMENT, AND MATERIALS INSTALLATIONWITH OTHER BUILDING COMPONENTS.

2. VERIFY MOUNTING HEIGHT OF ALL WALL MOUNTED LIGHT FIXTURES, INTERIOR ANDEXTERIOR PRIOR TO ROUGH-IN.

3. VERIFY ALL DIMENSIONS BY FIELD MEASUREMENTS.4. ARRANGE FOR CHASES, SLOTS, AND OPENINGS IN OTHER BUILDING COMPONENTS

DURING PROGRESS OF CONSTRUCTION, TO ALLOW FOR ELECTRICALINSTALLATIONS.

5. COORDINATE THE INSTALLATION OF REQUIRED SUPPORTING DEVICES ANDSLEEVES TO BE SET IN POURED_IN_PLACE CONCRETE AND OTHER STRUCTURALCOMPONENTS, AS THEY ARE CONSTRUCTED.

6. SEQUENCE, COORDINATE, AND INTEGRATE INSTALLATIONS OF ELECTRICALMATERIALS AND EQUIPMENT FOR EFFICIENT FLOW OF THE WORK. GIVEPARTICULAR ATTENTION TO LARGE EQUIPMENT REQUIRING POSITIONING PRIOR TOCLOSING IN THE BUILDING.

7. WHERE MOUNTING HEIGHTS ARE NOT DETAILED OR DIMENSIONED, INSTALLSYSTEMS, MATERIALS, AND EQUIPMENT TO PROVIDE THE MAXIMUM HEADROOMPOSSIBLE.

8. COORDINATE THE INSTALLATION OF ELECTRICAL MATERIALS AND EQUIPMENTABOVE CEILINGS WITH SUSPENSION SYSTEM, MECHANICAL EQUIPMENT ANDSYSTEMS, AND STRUCTURAL COMPONENTS.

9. WHERE ELECTRICAL INSTALLATION IS SHOWN MOUNTED ABOVE OR IN CASEWORK,VERIFY HEIGHT AND LOCATION WITH ARCHITECT AND CASEWORK SHOP DRAWINGSPRIOR TO ROUGH-IN.

10. COORDINATE CONNECTION OF ELECTRICAL SYSTEMS WITH EXTERIORUNDERGROUND AND OVERHEAD UTILITIES AND SERVICES. COMPLY WITHREQUIREMENTS OF GOVERNING REGULATIONS, FRANCHISED SERVICE COMPANIES,AND CONTROLLING AGENCIES. PROVIDE REQUIRED CONNECTION FOR EACHSERVICE.

11. INSTALL SYSTEMS, MATERIALS, AND EQUIPMENT TO CONFORM WITH APPROVEDSUBMITTAL DATA, INCLUDING COORDINATION DRAWINGS, TO GREATEST EXTENTPOSSIBLE. CONFORM TO ARRANGEMENTS INDICATED BY THE CONTRACTDOCUMENTS, RECOGNIZING THAT PORTIONS OF THE WORK ARE SHOWN ONLY INDIAGRAMMATIC FORM. WHERE COORDINATION REQUIREMENTS CONFLICT WITHINDIVIDUAL SYSTEM REQUIREMENTS, REFER CONFLICT TO THE ARCHITECT.

12. INSTALL SYSTEMS, MATERIALS, AND EQUIPMENT LEVEL AND PLUMB, PARALLELAND PERPENDICULAR TO OTHER BUILDING SYSTEMS AND COMPONENTS, WHEREINSTALLED EXPOSED IN FINISHED SPACES.

13. INSTALL ELECTRICAL EQUIPMENT TO FACILITATE SERVICING, MAINTENANCE, ANDREPAIR OR REPLACEMENT OF EQUIPMENT COMPONENTS. AS MUCH ASPRACTICAL, CONNECT EQUIPMENT FOR EASE OF DISCONNECTING, WITH MINIMUMOF INTERFERENCE WITH OTHER INSTALLATIONS.

14. INSTALL ACCESS PANEL OR DOORS WHERE UNITS ARE CONCEALED BEHINDFINISHED SURFACES.

15. INSTALL SYSTEMS, MATERIALS, AND EQUIPMENT GIVING RIGHT_OF_WAY PRIORITYTO SYSTEMS REQUIRED TO BE INSTALLED AT A SPECIFIED SLOPE.

16. PROVIDE PERMANENT OPERATIONAL DATA NAMEPLATE ON EACH ITEM OF POWEROPERATED EQUIPMENT, INDICATING MANUFACTURER, PRODUCT NAME, MODELNUMBER, SERIAL NUMBER, CAPACITY, OPERATING AND POWER CHARACTERISTICS,LABELS OF TESTED COMPLIANCE, AND SIMILAR ESSENTIAL DATA. LOCATENAMEPLATES IN AN ACCESSIBLE LOCATION.

OUTLET BOXES SHALL BE LOCATED SO THEY ARE NOT PLACED BACK-TO-BACK IN THE SAMEWALL IN ORDER TO LIMIT SOUND TRANSMISSION FROM ROOM TO ROOM.

CONTRACTOR SHALL CHECK ALL EQUIPMENT LAYOUTS AND VERIFY EXACT MOUNTING HEIGHTS,BEFORE ROUGH-IN.

FOLLOW PAINT MANUFACTURER'S INSTRUCTIONS FOR SURFACE PREPARATION, PRODUCTAPPLICATION AND PROPER ENVIRONMENTAL CONDITIONS, PAINTING ALONG WITH ADJACENTSURFACES. EXCEPT AS OTHERWISE INDICATED, USE ENAMEL PRIME AND FINISH COATS.

FURNISH: OBTAIN, PAY FOR AND DELIVER TO THE WORK SITE. INCLUDES RECEIVING AT WORKSITE AND SUITABLY STORING IN THE ORIGINAL SHIPPING CONTAINER FOR MATERIALS ANDEQUIPMENT.

INSTALL: UNPACK, TRANSPORT FROM WORK SITE STORAGE, HOIST OR OTHERWISE MOVE INTOPOSITION, FASTEN, CONNECT SERVICES, TEST AND PLACE IN OPERATION AS INDICATED.

PROVIDE: FURNISH AND INSTALL.

INDICATED: SHOWN, NOTED, SCHEDULED, SPECIFIED OR OTHERWISE PORTRAYED BY PRINTEDOR GRAPHIC MEANS.

NRTL: NATIONALLY RECOGNIZED TESTING LABORATORY, I.E., UNITED LABORATORIES.

DEFINITIONS

PROVIDE CONDUIT, TUBING, SURFACE METAL RACEWAY AND SPECIAL WIRE WAYS OF TYPESAND SIZES INDICATED WITH FITTINGS AND ACCESSORIES FOR A COMPLETED SYSTEM. USETYPE INDICATED BELOW FOR EACH APPLICATION AND WHERE NOT INDICATED SELECT PROPERTYPE FOR THE APPLICATION. USE 3/4" TRADE SIZE MINIMUM UNLESS OTHERWISE INDICATED.

RACEWAYS

1. GALVANIZED RIGID OR INTERMEDIATE STEEL CONDUIT - FOR POURED INCONCRETE, EXPOSED OUTDOOR LOCATIONS, WET LOCATIONS, HAZARDOUSLOCATIONS, OR WHERE SUBJECT TO ABUSE.

2. ELECTRICAL METALLIC TUBING (EMT) - FOR PROTECTED, DRY LOCATIONS LIKEWALL AND CEILING CAVITIES, BRANCH CIRCUITS AND COMMUNICATIONRACEWAY. USE STEEL BODY SET SCREW OR COMPRESSION TYPECOUPLINGS AND CONNECTORS (DIE CAST IS NOT ACCEPTABLE).

3. FLEXIBLE METAL CONDUIT - FOR FINAL CONNECTIONS TO LIGHT FIXTURES,MOTORS, TRANSFORMERS, AND OTHER MOVING OR VIBRATING EQUIPMENT INDRY LOCATIONS TO ISOLATE VIBRATION AND ALLOW NECESSARY MOVEMENT.USE 1-3 FOOT LENGTHS (6 FOOT ALLOWABLE FOR LIGHT FIXTURES).

4. METAL CLAD (TYPE MC) CABLE - FOR HORIZONTAL RUNS BETWEEN DEVICEBOXES WHERE CONCEALED IN STUDWALL CAVITIES. USE ONLY FOR RUNSBETWEEN DEVICES, AND NOT FOR DROPS FROM CEILING DOWN INTO WALL, ORFOR HOMERUNS BACK TO PANELBOARDS.

5. LIQUID-TIGHT FLEXIBLE METAL CONDUIT - SIMILAR TO FLEXIBLE METALCONDUIT EXCEPT USE FOR LOCATIONS SUBJECT TO WEATHER, WASH DOWN,SPLASHING LIQUIDS, OIL, ETC.

6. NON-METALLIC CONDUIT (SCHEDULE 40 PVC) - UNLESS OTHERWISE INDICATEDLIMIT USE TO EXTERIOR OF BUILDING AND UNDERGROUND, DIRECT ORENCASED BURIAL. ENCASE IN CONCRETE WHEN UNDER PARKING LOT,ROADWAY, DRIVEWAY.

7. SURFACE METAL RACEWAY (SMR) - LIMIT USE TO APPLICATIONS/AREASINDICATED AND WHERE APPROVED BY ENGINEER.

PROVIDE INDICATED TYPE/SIZE WIRE/CABLE PRODUCTS AS MARKETED BY ALPHA,AMERICAN INSULATED, BELDEN, CLIFFORD, HI-TEMP, ESSEX, SOUTHWIRE OR TRIANGLE.USE STANDARD, NEW PRODUCTS LISTED IN CURRENT PUBLISHED INFORMATION AND OFRECENT MANUFACTURE. CONSTRUCT OF 98 PERCENT CONDUCTIVITY ANNEALED COPPERWITH FLAME RETARDANT INSULATION. USE NO. 12 AWG MINIMUM FOR POWER ANDCONTROL EXCEPT THAT FOR CONTROL CIRCUITS LESS THAN 50' IN LENGTH AND 10 AMPSCURRENT DEMAND MAY BE NO 14 AWG. SELECT APPROPRIATE UL TYPE FROM THEFOLLOWING:

WIRE AND CABLE

1. TYPE THHN/THWN FOR WET LOCATIONS WITH 75 C (167 F.) OR DRY LOCATIONSWITH 90 C (194 F) MAXIMUM OPERATING TEMPERATURE, THERMOPLASTIC HEATAND MOISTURE RESISTANT INSULATION WITH NYLON JACKET.

2. TYPE XHHW FOR DRY LOCATIONS WITH 90 C (194 F.) MAXIMUM OPERATINGTEMPERATURE. CROSS LINKED SYNTHETIC POLYMER, HEAT AND MOISTURERESISTANT INSULATION.

3. WIRE SIZES INDICATED ON DRAWINGS ARE BASED ON AMPERAGE AND LOAD OFEQUIPMENT ONLY. BASED ON ROUTING AND DISTANCE OF RUNS, CONTRACTORSHALL INCREASE WIRE SIZE AS REQUIRED TO LIMIT VOLTAGE DROP IN ALLPANEL FEEDERS TO 2% MAXIMUM, AND IN BRANCH CIRCUITS TO 3% MAXIMUM.

PROVIDE NRTL TYPE, FACTORY FABRICATED, COPPER BODY, OF SIZE, RATING AND STYLEFOR APPLICATIONS INDICATED. USE MECHANICAL SET SCREW TYPES OR COMPRESSIONTYPE LUGS. USE 2-HOLE TYPES IN AVAILABLE SIZES AND WHERE SPACE PERMITS.ACCEPTABLE MANUFACTURER: IDEAL, T & B, BUCHANAN, BURNDY, AND ILSCO.

WIRE CONNECTORS

1. SPIRAL SPRING (WIRENUT) TYPE FOR WIRE SIZE #8 AWG AND BELOW,THERMOPLASTIC FLAME RETARDANT SHELL, WITH SQUARE WIRE SPIRALSPRING.

2. USE PRE-INSULATED, POWER DISTRIBUTION TERMINAL BLOCK TYPECONNECTORS FOR #6 AWG AND LARGER - BLACKBURN AMT SERIES OR PDSSERIES

PROVIDE BOXES AND FITTINGS OF APPROPRIATE TYPE FOR EACH APPLICATION ASINDICATED BELOW AND WHERE NOT SPECIFICALLY INDICATED BELOW MAKE PROPERSELECTION. ACCEPTABLE MANUFACTURER: APPLETON, CROUSE HINDS, KILLARK, RACO,SPRING CITY, STEEL CITY, O.Z./GEDNEY, HUBBELL.

BOXES AND FITTINGS

1. INTERIOR OUTLET BOXES - 4" SQUARE OR LARGER GALVANIZED SHEET STEEL DRAWNOR FORMED TO PROPER DEPTH SINGLE PIECE, STAMPED KNOCKOUTS BACK ANDSIDES, CORROSION RESISTANT COVER SCREWS IN THREADED HOLES OR TAPPEDDEVICE MOUNTING RINGS AS REQUIRED. USE SQUARE CUT PLASTER/DEVICE RINGS(NOT DRAWN TYPE) FLUSH MOUNT IN FINISHED AREAS AND CROWN TYPE COVERSFOR SURFACE MOUNTING IN UNFINISHED AREAS.

2. EXTERIOR (WEATHERPROOF) BOXES - CAST METAL, CORROSION RESISTANT,THREADED CONDUIT ENTRY, WITH GASKETS. FOR DUPLEX/GFI EXTERIOR ANDINTERIOR WET LOCATION RECEPTACLES, USE ARLINGTON INDUSTRIES "IN-USE”RECESSED MOUNT GASKETED, LOCKING COVER OR APPROVED EQUAL.

3. JUNCTION AND PULL BOXES - PROVIDE CODE-GAGE, GALVANIZED SHEET STEELAPPROPRIATE FOR EACH APPLICATION. CONSTRUCT WITH WELDED SEAMS ANDSCREW COVERS ATTACHED WITH STAINLESS STEEL FASTENERS.

4. FLOOR BOXES - UNLESS OTHERWISE INDICATED PROVIDE FULLY IN-FLOOR BOXCOMPLETE WITH FLUSH COVER AT EACH FLOOR OUTLET LOCATION. FURNISH WITHTRIM FLANGE SUITABLE FOR FLOOR FINISH WITH RECEPTACLE/JACKS(S) IN POWERAND COMMUNICATION COMPARTMENTS. USE PRODUCTS OF HUBBELL, STEEL CITYOR APPROVED EQUAL.

5. CONDUIT BODIES - PROVIDE REQUIRED CONFIGURATION, GALVANIZED CAST METALCONDUIT BODY SIZED AS REQUIRED, COMPLETE WITH THREADED CONDUIT ENTRY,MATING COVER AND GASKET AND CORROSION RESISTANT SCREWS.

6. BUSHINGS, LOCKNUTS, KNOCKOUT CLOSURES - PROVIDE DOUBLE LOCKNUTS ANDINSULATED GROUNDING BUSHING FOR EACH CONDUIT TERMINATION AT MAIN ANDDISTRIBUTION PANELS. BOND CONDUITS TOGETHER AND TO ENCLOSURE. CLOSEANY UNUSED CONDUIT OPENINGS WITH CORROSION RESISTANT METAL CLOSURES.USE INSULATED METAL OR NON-METALLIC BUSHINGS AS INDICATED.

PROVIDE, WHERE INDICATED, WIRING DEVICES OF CONFIGURATION RATING AND TYPEREQUIRED. ACCEPTABLE MANUFACTURERS ARE COOPER, LEVITON, P & S AND HUBBELL. PARTNUMBERS BELOW INDICATE QUALITY LEVEL ONLY NOT COLOR OR CONFIGURATION. USE ONEMANUFACTURER FOR EACH TYPE DEVICE. COLOR TO MATCH EXISTING DEVICES WHENAPPLICABLE.

WIRING DEVICES

1. DUPLEX RECEPTACLE - GENERAL DUTY, 3-WIRE, 2-POLE WITH GROUND, 125 VOLT,15 AMPERE, NEMA 5-15R TYPE WITH METAL PLASTER EARS; SPRING LOADED,SCREW ACTIVATED PRESSURE PLATE TERMINALS. BACK AND SIDE WIRED WITHGROUND TERMINAL BONDED TO MOUNTING YOKE. HUBBELL "HBL CR5252" OREQUAL. USE NEMA 5-20R CONFIGURATION WHERE SHOWN CONNECTED TO ADEDICATED 20A CIRCUIT BREAKER.

2. PLUGS, CONNECTORS - 15 AMP, 125 VOLT, 3-WIRE W/GROUND, PVC/ABS/NYLONBODY, PARALLEL BLADE, U-GROUND, CORD CLAMP, DEAD FRONT, NEMA 5-15R/P.PLUG-HUBBELL #5266C OR EQUAL. CONNECTOR - HUBBELL #5269C OR EQUAL.PROVIDE SIMILAR PLUGS AND CONNECTORS OF OTHER RATINGS AND NEMACONFIGURATIONS AS INDICATED.

3. SWITCHES - QUIET TYPE, 120/277 VOLT, 20 AMP, BACK AND SIDE WIRED, SCREWTERMINALS, SWITCH HANDLE OR KEY OPERATED, SINGLE POLE, DOUBLE POLE, 3-WAY, 4-WAY, MAINTAINED OR MOMENTARY TYPES WITH PILOT LAMP OR OTHERFEATURES AS INDICATED. EQUAL TO HUBBELL #1221.

PROVIDE A SINGLE PIECE, MATCHING AND MATING COVER PLATE FOR EACH DEVICE OR GROUP(GANG) OF DEVICES. FURNISH WITH SMOOTH FACE AND MATCHING MOUNTING SCREWS. USEPRODUCTS OF ONE OF THE FOLLOWING: COOPER, LEVITON, HUBBELL OR P & S.

DEVICE COVER PLATES

1. SEMI RIGID THERMAL PLASTIC, COLOR MATCH DEVICE.

PROVIDE PROPER HP, VOLTAGE AND CURRENT RATING & NEMA TYPE DISCONNECT FOR EACHLOCATION INDICATED. FURNISH WITH OR WITHOUT OVER CURRENT PROTECTION AND OTHERACCESSORIES AS INDICATED. USE NEMA 3R ENCLOSURE IN WET LOCATIONS. ACCEPTABLEMANUFACTURERS ARE: SQUARE D, EATON/CUTLER HAMMER AND SIEMENS.

MOTOR AND CIRCUIT DISCONNECTS

1. SWITCH TYPE - HEAVY DUTY, SHEET STEEL ENCLOSED, 2, 3 OR 4 POLE, QUICKBREAK, VISIBLE BLADE, INTERLOCKED DOOR, PAD LOCK LOCKOUT PROVISION HIGHCONDUCTIVITY COPPER CURRENT CARRYING PARTS, SILVER TUNGSTEN CONTACTS,POSITIVE PRESSURE/SPRING ASSISTED FUSE CLIPS (FUSED TYPES).

PROVIDE MANUFACTURER'S STANDARD FABRICATED SUPPORT DEVICES AS REQUIREDFOR COMPLETE INSTALLATION OF THE WORK. SELECT APPROPRIATE TYPE WHERE TWOOR MORE TYPES ARE SUITABLE. USE PRODUCTS MANUFACTURED BY RACO, MINERALLAC,ELCEN, B-LINE, UNISTRUT, OR APPLETON.

SUPPORTING DEVICES

1. BOLTED CLAMP - SINGLE PIECE, ELECTRO-GALVANIZED, SINGLE CLAMP BOLT, UPTO 1-1/2" TRADE SIZE, MINERALLAC #0 THRU #4 OR EQUAL. USE FOR SINGLECONDUIT RUNS.

2. CLEVIS HANGER - 1-1/2" - 4" TRADE SIZE, GALVANIZED STEEL, FOR ROD HANGER,B-LINE FIG. B690 OR EQUAL.

3. U-CHANNEL - 12 GAGE HOT DIP GALVANIZED, 1-5/8" CROSS SECTION, 9/16"PUNCHED HOLES AT 8" O.C. OPPOSITE OPEN SIDE, WITH FITTINGS AS REQUIRED.FOR CONDUIT, PANELS, BOXES, EQUIPMENT.

4. RISER CLAMPS - 2-PIECE, BLACK STEEL, 2 CLAMP BOLTS, 4" EARS, B-LINE FIGUREB3373 OR EQUAL.

5. C-CLAMPS - BLACK MALLEABLE IRON, ½" ROD SIZE FOR TRAPEZE HANGER, 1/4"ROD SIZE FOR INDIVIDUAL CONDUIT HANGER UP TO 1-1/4" TRADE SIZE, 3/8" RODSIZE FOR INDIVIDUAL CONDUIT HANGER UP TO 2-1/2" TRADE SIZE, APPROX. 70LB/100 UNITS.

6. T-BEAM CLAMPS - BLACK STEEL, 1-1/4" X 3/16/" STOCK, 3/8" CLAMP BOLT, 2"FLANGE WIDTH, APPROX. 52 LBS/100 UNITS.

PROVIDE ANCHORS OF TYPES, SIZES AND MATERIALS INDICATED FOR EACH APPLICATION.ACCEPTABLE MANUFACTURERS ARE PHILLIPS, DIAMOND, RAWL, STAR.

ANCHORS

1. TOGGLE BOLT - SPRINGHEAD, 3/16" X 4" OR LARGER AS NEEDED FOR USE INHOLLOW WALLS.

2. EXPANSION TYPE - 2-PIECE WITH EXPANSION WEDGE, 1/4" - ½" BOLT SIZE. FORUSE IN SOLID MASONRY AND CONCRETE.

PROVIDE SLEEVES AND SEALS AS INDICATED FOR EACH APPLICATION WHERE RACEWAYPENETRATES WALL, FLOOR, ROOF, ETC. CONSTRUCTION.

SLEEVES AND SEALS

1. SLEEVES - SCHEDULE 40 GALVANIZED STEEL PIPE OR GALVANIZED SHEETMETAL W/WELDED SEAMS, 20 GAGE UP TO 3" AND 16 GAGE UP TO 4" TRADESIZE. USE FOR DRY AREAS.

2. MOISTURE SEALS - MALLEABLE IRON BODY, NEOPRENE GROMMETS AND RINGS,METAL COMPRESSION RINGS, PRESSURE CLAMPS, CAP SCREWS. ACCEPTABLEMANUFACTURERS: O.Z. GEDNEY, SPRING CITY OR APPROVED EQUAL. FORWALL/FLOOR PENETRATIONS AT OR BELOW GRADE AND OTHER LOCATIONSSUBJECT TO MOISTURE.

PROVIDE IDENTIFICATION PRODUCTS AS INDICATED INCLUDING COLOR CODES, LABELS,SIGNS AND TAGS. USE STANDARD PRODUCTS OF ONE OF THE FOLLOWINGMANUFACTURERS FOR EACH TYPE MARKER REQUIRED: W.H. BRADY, IDEAL, PANDUIT,SETON, 3M.

ELECTRICAL IDENTIFICATION

1. CABLE/CONDUCTOR MARKING - VINYL CLOTH, ADHESIVE BACKED, PREPRINTEDOR WRITE-ON WITH CLEAR PLASTIC COVER FLAP. USE FOR CIRCUITIDENTIFICATION.

2. PANEL & EQUIPMENT MARKING - BLACK WITH WHITE CORE ENGRAVING STOCK,3/8" LETTERS, STAINLESS STEEL SELF-TAPPING ATTACHMENT SCREWS ORCONTACT ADHESIVE WHERE SCREWS WOULD INJURE SUBSTRATE MATERIAL.USE ON FRONT OF PANELS, SWITCHBOARDS, SWITCHGEAR, MOTOR CONTROLCENTERS, MAGNETIC STARTERS AND EQUIPMENT CABINETS.

3. INFORMATION MARKING - EMBOSSED TYPE, WHITE LETTERS ON BLACK 3/8"WIDE TAPE, PEEL-OFF ADHESIVE BACK. USE INSIDE PANELS FOR PANEL ANDFEEDER IDENTIFICATION AND ON STARTERS, CONTACTORS, ETC. FOR CIRCUITAND LOAD IDENTIFICATION. ENGRAVED TYPE MAY BE SUBSTITUTED FOREMBOSSED TYPE AT CONTRACTOR'S OPTION.

4. LABEL INSIDE OF ALL DEVICE COVER PLATES AND EXTERIOR OF ALL JUNCTIONBOXES WITH INDELIBLE MARKER LISTING CIRCUIT NUMBERS CONTAINEDTHEREIN.

INSTALL COMPLETE RACEWAY SYSTEM IN PROGRESS WITH OTHER TRADES AND PRIOR TOPULLING WIRE/CABLE. FOLLOW NECA GUIDELINES FOR NEAT, FIRST CLASS WORKMANSHIP.MAKE FLEX TERMINATIONS VERTICAL WHERE EVER PRACTICAL TO MINIMIZE STRAIN AND ALLOWNATURAL LOOP. SELECT PROPER SUPPORTS AND ANCHORS FOR MOUNTING OF ELECTRICALWORK AND ALLOW AIR SPACE WHEN MOUNTING TO MASONRY OR CONCRETE SURFACES.SUPPORT BOXES IN STUD WALLS FROM 2 STUDS, USE MOUNTING BAR ETC. TO SPAN BETWEENSTUDS.

AVOID HORIZONTAL CONDUIT RUNS IN MASONRY WALLS; RUN PARALLEL OR PERPENDICULAR TOBUILDING LINES IN GENERAL AND ABOVE WATER AND STEAM LINES WHERE POSSIBLE. PULLWIRE AND CABLES INTO COMPLETED RACEWAY SYSTEM(S) AND MAKE CONNECTIONS ASINDICATED.

ATTACH DEVICES SOLIDLY TO OUTLET BOX USING SHIMS FOR FLUSH MOUNT. CONNECTRECEPTACLES VIA PIGTAIL SO DEVICE REMOVAL WON'T INTERRUPT CIRCUIT. INSTALL DEVICESAND COVERS AFTER PAINTING OR PROTECT OR CLEAN AS NEEDED.

INSTALL MOTOR/CIRCUIT DISCONNECT SWITCHES WITHIN SITE OF CONTROLLER UNLESSINDICATED OTHERWISE. SELECT FUSES BASED ON NAME PLATE RATING OR OTHERMANUFACTURER'S RECOMMENDATION WHEN AVAILABLE AND INSTALL IN EACH FUSIBLE DEVICE.

PLACE INTUMESCENT FILL MATERIAL IN PENETRATIONS OF FIRE RATED ASSEMBLIES; FOLLOWMANUFACTURER'S INSTRUCTIONS.

MARK PANELBOARDS WITH PANEL DESIGNATION ABOVE DOOR AND INSIDE OF DOOR WITH PANELDESIGNATION, VOLTAGE AND FEEDER DESIGNATION I.E., "PANEL 1L1, 120/208 VOLT 3 PH. 4 WIRE,FEEDER LD-1."

MARK STARTERS, DISCONNECTS, CONTACTORS, ETC. WITH UNIT DESIGNATION, EQUIPMENTSERVED, VOLTAGE AND FEED CIRCUIT I.E., "MS-1, PUMP P1, 208 V. 3 PH. 1L1-10". CLEANSURFACES OF DUST, OIL, DIRT, ETC. PRIOR TO APPLICATION OF MARKING MATERIALS. APPLYFOLLOWING FINISH PAINTING AS APPLICABLE. BLUNT ANY POINTS OF ATTACHMENT SCREWS.

PROVIDE LABEL DESIGNATING CIRCUIT NUMBER OF ALL CONDUCTORS AT ALL PANELBOARDS,JUNCTION BOXES, AND TERMINATION POINTS.

PAINT ALL FIRE ALARM JUNCTION BOXES RED.

ELECTRICAL INSTALLATION

COMPLY WITH APPLICABLE PORTIONS OF ANSI, IEEE, NEC, NEMA AND UL STANDARDS.PROVIDE NRTL LABELED PRODUCTS. SERVICE EQUIPMENT REQUIRES LISTING"SUITABLE FOR USE AS SERVICE EQUIPMENT." REFER TO OTHER SPECIFICATIONSECTIONS/DIVISIONS FOR APPLICABLE REQUIREMENTS.

GROUND THE ELECTRICAL SYSTEM USING STANDARD PRODUCTS OF THE FOLLOWINGMANUFACTURER'S: BLACKBURN, ERICO/CADWELD, THOMAS & BETTS OR APPROVEDEQUAL. PROVIDE WIRE, CABLE, FLEXIBLE BRAID, ELECTRODE PLATES, ELECTRODERODS, LUGS, CLAMPS, SURGE ARRESTERS AND RELATED PRODUCTS AS REQUIRED FORA COMPLETED GROUNDING SYSTEM.

SERVICE AND DISTRIBUTION

1. CONDUCTORS - MATCH FEEDER AND BRANCH CIRCUIT CONDUCTORS, SIZE ASINDICATED OR PER NEC WHERE NOT INDICATED. PROVIDE SEPARATE GREENINSULATED GROUND CONDUCTOR IN ALL FEEDERS AND BRANCH CIRCUITS.

2. FLEXIBLE BRAID - FLAT, FLEXIBLE 30 AWG, COPPER, 480 STRANDS, 3/4" WIDE 48,250CM. WITH CRIMPED ON BOLT HOLE ENDS (3/8" BOLT SIZE).

3. GROUND ELECTRODES - 3/4" DIAMETER, 10' LONG COPPER CLAD STEEL ROD, OREQUIVALENT COPPER PLATE OR AS OTHERWISE INDICATED.

4. CONNECTION ACCESSORIES - WELDING/BRAZING MATERIALS, HEAT SHRINK TUBING,INSULATING TAPE, BRONZE OR COPPER LUGS APPLIED ACCORDING TOMANUFACTURER'S RECOMMENDATIONS.

PROVIDE WHERE INDICATED CIRCUIT BREAKER TYPE PANELBOARDS OF SIZE, TYPEAND RATINGS INDICATED AND AS MANUFACTURED BY SIEMENS, SQUARE-D OREATON/CUTLER HAMMER. FURNISH FACTORY ASSEMBLED, DEAD FRONT, SHEET STEELENCLOSED, COMPLETE WITH BOLTED IN CIRCUIT BREAKERS AND ANCILLARYCOMPONENTS REQUIRED. SELECT PROPER VOLTAGE , LOAD CURRENT AND FAULTCURRENT INTERRUPTING RATINGS FOR EACH APPLICATION UNLESS MORE STRINGENTREQUIREMENTS ARE INDICATED. PROVIDE MANUFACTURER'S STANDARD PRODUCTSWITH FLAT FRONT, FLUSH DOOR, CONCEALED HINGES, LOCKING LATCH LATCHES KEYEDALIKE.

PANELBOARDS

1. LIGHTING AND APPLIANCE BRANCH CIRCUIT PANELS - COPPER BUSSING,THERMAL/MAGNETIC CIRCUIT BREAKERS, INTERLOCKS, SHUNT TRIPS,SPECIAL FEATURES AS INDICATED, FULL CAPACITY NEUTRAL BAR, GROUNDBAR SUITABLE LUGS TO TERMINATE CONDUCTORS INDICATED, MECHANICALTYPE MAIN LUGS.

2. POWER DISTRIBUTION PANELBOARDS - MOLDED CASE THERMAL/MAGNETICMAIN AND BRANCH CIRCUIT BREAKERS, COMPRESSION TYPE MAIN LUGS,GROUND BAR, NEUTRAL BAR, SHUNT TRIPS, INTERLOCKS AND SPECIALFEATURES AS INDICATED.

3. ENCLOSURES - GALVANIZED SHEET STEEL, 16 GAGE MINIMUM, SAME MAKEAS PANEL BOARDS, WITH FIELD CUT CONDUIT KNOCKOUTS. WITH SURFACEOR ADJUSTABLE FLUSH FRONT COVER IN GRAY ENAMEL FINISH, CONCEALEDMOUNTING HARDWARE, CIRCUIT DIRECTORY FRAME, CARD AND CLEARPROTECTIVE COVER. PROVIDE HINGED FRONT COVERS ON PANELS.

4. ACCESSORIES - INCLUDE AS INDICATED; CIRCUIT BREAKERS, GROUNDFAULT PROTECTION DEVICES, MAIN BREAKERS, SUB-FEED, OR FEED-THRUTYPE LUGS AS INDICATED ON DRAWINGS.

TOUCH-UP SCRATCHED OR DAMAGED FINISHES. SPACE SURFACE MOUNTED PANELS AWAYFROM MASONRY OR CONCRETE WALLS AT LEAST ½" USING U-CHANNEL. ISOLATETRANSFORMERS WITH EXTERNAL PADS LIKE KORFUND. PHASE BALANCE PANELBOARDSPRIOR TO TYPING DIRECTORIES. MOUNT WITH TOP AT 6' ABOVE FLOOR.

TEST GROUND RESISTANCE PRIOR TO CONNECTION TO WATER MAIN AND IF RESISTANCE ISOVER 5 OHMS, PROVIDE ADDITIONAL RODS OR SOIL TREATMENT TO OBTAIN 5 OHMS OR LESS.THEN CONNECT TO WATER MAIN. USE GROUND RESISTANCE TESTER, RECORD TEST DATAAND SUBMIT COPY TO ENGINEER. VERIFY PHASE CONDUCTORS TO BE FREE OF GROUNDSPRIOR TO ENERGIZATION.

COMPLY WITH APPLICABLE PROVISIONS OF ANSI, CBM, IES, NEC, NEMA, NESC, NFPA ANDNRTL. USE PRODUCTS BEARING UL LABEL. EXAMINE OTHER SPECIFICATIONDIVISIONS/SECTIONS FOR RELEVANT INSTRUCTIONS.

PROVIDE LIGHT FIXTURES OF TYPES, SIZES AND PHOTOMETRIC QUALITIES AS INDICATED.INCLUDE LAMP, DRIVER, MOUNTING HARDWARE, TRIM, POWER CORD/WHIP, LENS, LAMPSOCKET, LAMP STARTING AID AND OTHER REQUIRED OR INDICATED ACCESSORIES FORCOMPLETED FUNCTIONAL ASSEMBLY. SELECT FROM MANUFACTURERS LISTED ON THEDRAWINGS OR OBTAIN WRITTEN APPROVAL FROM THE ENGINEER 10 DAYS PRIOR TO BIDDATE FOR CONSIDERATION OF ALTERNATIVE MANUFACTURE.

INSTALL FIXTURES AT INDICATED HEIGHTS/LOCATIONS. COMPLY WITH MANUFACTURER'SINSTALLATION INSTRUCTIONS. SUPPORT FIXTURES FROM STRUCTURAL COMPONENTS,PLUMB RIGID PENDANTS. PROVIDE SAFETY CHAINS TO STRUCTURE FROM 2 DIAGONALLYOPPOSITE CORNERS OF BALLASTED FIXTURES INSTALLED IN LAY-IN CEILING SYSTEMS.REPLACE UNITS DAMAGED IN SHIPPING OR HANDLING. REPLACE DEFECTIVE OR BURNED OUTLAMPS. INCLUDING REPLACEMENT OF HID AND FLUORESCENT TYPES FOR ONE YEAR PERIODFROM DATE OF SUBSTANTIAL COMPLETION. CLEAN EXPOSED SURFACES, LENSES,REFLECTORS AND REFRACTORS AT PROJECT COMPLETION, REPLACE NOISY ORMALFUNCTIONING BALLASTS.

LIGHTING

PROVIDE COMPLETE RACEWAY SYSTEMS AS INDICATED FOR AUDIBLE, VISUAL, DATA AND SIGNALCOMMUNICATION SYSTEM(S). USE ONLY PLENUM RATED COMMUNICATION MEDIA INENVIRONMENTAL AIR SPACE OR INSTALL IN RACEWAY THROUGH PLENUM. MINIMUM RACEWAYREQUIREMENTS INCLUDE: DRAW THROUGH RACEWAY THROUGH NON-ACCESSIBLE AREAS,PROTECTIVE RACEWAY WHERE EXPOSED TO DAMAGE (I.E., WALLS BELOW 8' AFF) AND FROMFLUSH JACKS, OUTLETS, ETC. TO ACCESSIBLE CEILING SPACE. TRIM EACH OUTLET WITHINDICATED TYPE JACK, BUSHED COVER OR BLANK COVER TO MATCH OTHER DEVICES. COMPLYWITH APPLICABLE PORTIONS OF NEC, IEEE, EIA/TIA, FCC, ANSI, & ASTM. USE NRTL LISTEDPRODUCTS TO THE EXTENT AVAILABLE. EXAMINE OTHER SPECIFICATION SECTIONS FORAPPLICABLE REQUIREMENTS. INSTALL COMMUNICATIONS SYSTEMS WORK DURING NORMALWORKING HOURS IN COORDINATION WITH WORK OF OTHERS.

COMMUNICATIONS

SHEET

TITLE

DATE PROJECT

All concepts, ideas, designs, plans and details as shown on thisdocument are the sole property of Design Collaborative, Inc., andshall not be used for any purpose without their expressed writtenconsent. The owner shall be permitted to retain copies forinformation and reference.

CERTIFICATION

200 East Main Street - Suite 600 Fort Wayne, Indiana 46802

260.422.4241260.422.4847designcollaborative.com

04/19/2017 2017.0036

BETH

ANY

SEM

INAR

YR

ENO

VAT I

ON

SR

ICH

MO

ND

, IN

DIA

NA

a

pfw

4/19

/201

7 5:

05:3

9 PM

E6.1

Electrical Specifications

ELECTRICAL SPECIFICATIONS

No. Description Date