Upload
doantu
View
219
Download
3
Embed Size (px)
Citation preview
presented by:John Siegenthaler, P.E.
Appropriate DesignsHolland Patent, NY
www.hydronicpros.com © Copyright 2014, J. Siegenthaler, all rights reserved. The contents of this file shall not be copied or transmitted in any form without written permission of the author. All diagrams shown in this file on conceptual and not intended as fully detailed installation drawings. No warranty is made as the the suitability of any drawings or data for a particular application.
TRV
TRV
TRV
TRV
TRV
TRV
thermal storage
tank
thermostatic radiator valves!on each panel radiator
pressure-regulated!variable speed
circulator1/2" PEX or
PEX-AL-PEX tubing
panel radiator
manifold station
"Best Practices in Modern Hydronic Heating - AN OVERVIEW
2014
This Morning’s topics...• Why hydronics• High efficiency gas-fired boilers• Low temperature heat emitter options• High efficiency circulators• Homerun distribution systems• Zoning options
"Best Practices in Modern Hydronic Heating - AN OVERVIEW
What are the advantages of using hydronic heating in these houses?Water vs. air: Itʼs hardly fair...
14" x 8" duct
this cut would destroy the load-carrying ability of the floor joists
2 x
12 jo
ist
3/4" tube
Water is vastly superior to air for conveying heat
A given volume of water can absorb almost 3500 times as much heat as the same volume of air, when both undergo the same temperature change
Gas-firedboilers
Oil-firedboilers
wood-firedboilers
pellet-firedboilers
CONVENTIONALBOILERS
CONDENSINGBOILERS
Gas-firedboilers
Oil-firedboilers
RENEWABLE HEAT SOURCES
solarthermal
collectors
water-to-water(geothermal)
heatpumps
air-to-watervapor comp.
water-to-water(geothermal)air-to-water
absorp.cycle
Conventional boilers are not intended to operate with sustained flue gas condensation. Allowing them to operate with such condensation will damage both the boiler and flue.
High efficiency gas-fired boilersHydronic heat source options
gas-firedcast-iron sectionalatmospheric draft
oil-firedcast-iron sectionalatmospheric draft
oil-firedsteel fire tube
atmospheric draft
oil-firedsteel fire tube
atmospheric draft
gas-firedcopper water tubeatmospheric draft
Conventional boilersConventional boilers are not intended to operate with sustained flue gas condensation
For conventional gas-fired boilers, sustained inlet water temperatures of 130 ºF or more are recommended to prevent sustained flue gas condensation.
oil-firedsteel fire tube
atmospheric draft
“EVERY BOILER can be a condensing boiler...”Conventional boilers
oil-firedsteel fire tube
atmospheric draft
The system must be designed to maintain the boiler inlet temperature above dewpoint of flue gases.
VENT
boiler inlet temperature!
sensor
mixed supply temperature!
sensor
mixing!assembly
conventional boiler
boiler loop
distribution system
Conventional boilers
The only way to ensure that a conventional boiler is protected against sustained flue gas condensation is to measure boiler inlet temperature and provide a mixing assembly that reacts to this temperature.
oil-firedsteel fire tube
atmospheric draft
An intelligent mixing assembly that can sense boiler inlet water temperature and react to it WILL protect the boiler from sustained flue gas condensation.
Protecting conventional boilers from sustained flue gas condensation
The only way to ensure that a conventional boiler is protected against sustained flue gas condensation is to measure boiler inlet temperature and provide a mixing assembly that reacts to this temperature.
50,000 Btu/hr!heat input rate!
to water
135.4 ºF!20 gpm
130 ºF!20 gpm
6 floor circuits!300 ft x 1/2" PEX!
12" spacing bare slab
mixing valve!controller !
set for 125ºF
50,000 Btu/hr!heat output rate
111.4 ºF!5.5 gpm
93 ºF!5.5 gpm
thermal equilibrium
93 ºF!2.39 gpm
bypass flow through!closely spaced tees
14.5 gpm!135.4 ºF
135.4 ºF!2.39 gpm
bypass!circulator
130 ºF
135.4 ºF
∆T=5
.1ºF130 ºF
dewpoint
boiler inlet temperature sensor
93 ºF3.11gpm
Conventional boilers
oil-firedsteel fire tube
atmospheric draft
These boilers use stainless steel or aluminum heat exchangers that can withstand the corrosive nature of condensed flue gases. (pH ≤ 4.0)
Mod/con boilers use a variable speed combustion air blower and proportional gas valve to regulate the rate of combustion. Typical range of modulation (20 - 100%).
• Wall hung• Free standing on floor• Sealed combustion• Requires condensate drain
Mod/con (e.g., modulating / condensing) boilers are built with the intent that fluid gases will condense within the boiler.
High efficiency gas-fired boilers
oil-firedsteel fire tube
atmospheric draft
modulating / condensing boilers, plenty to choose from...
These are all “low mass” mod/con boilers
High efficiency gas-fired boilers
oil-firedsteel fire tube
atmospheric draft
modulating / condensing combi-units (space heat + DHW)
Triangle Tube
hot water
cold water
to / from!space!
heating
internal!circulator
motorized!diverter!valve
stainless steel!brazed plate!
heat exchanger
anti-scald!valve
flow!switch
combi-boiler
LAARS
Designed for “on-demand” DHW. 30-45 seconds from cold start to rated DHW delivery temperature.
High efficiency gas-fired boilers
oil-firedsteel fire tube
atmospheric draft
To prevent short cycling - these boilers are often installed with a buffer tank.
High efficiency gas-fired boilers
buffer tank
mod/con boiler!(low mass)
to /
from
!he
atin
g lo
adtemperature!sensor
HIGH THERMAL MASS mod/con heating appliancesHigh efficiency gas-fired boilers
• “Self-buffering” heat source. No buffer tank required.
• Low pressure drop - no separate circulator required
HTP, Inc “Pioneer” heating appliance
APPLIANCE!for space heating!
and DHW
panel radiator TRV
cold
DHW
European approach to combined space heating & DHW
ACVRotex
High efficiency gas-fired boilers
Do you notice anything in common among these products?• None of them look like a boiler or water heater...
• They all look like an “appliance.”
• They all have sufficient water volume to stabilize against short cycling the burner under light loading.
This is what some North American systems look like.
European approach to combined space heating & DHW
High efficiency gas-fired boilers
oil-firedsteel fire tube
atmospheric draft
DESIGN ISSUE: To obtain high efficiency ( 88 to 97%), the water temperature supplied to the mod/con boiler must be lower than the dewpoint of the exhaust gases.
Condensing mode operation begins at inlet water temperatures of about 130 ºF, and corresponding thermal efficiency of about 87.5%.
Thermal efficiency climbs as inlet water temperature decreases.
Inlet water temperature is a function of system design.
Applying mod/con boilers in higher temperature systems is generally not recommended.
LOW WATER TEMPERATURE ARE CRUCIAL TO HIGH PERFORMANCEHigh efficiency gas-fired boilers
oil-firedsteel fire tube
atmospheric draft
Many mod/con boilers have compact heat exchangers:
Whatʼs good about this: Very low metal and water content.Whatʼs bad about this: Very low metal and water content.
DESIGN ISSUE: Low thermal mass boilers combined with highly zoned distribution systems will cause “short cycling.”
TYPICAL SOLUTION: add thermal mass in the form of a buffer tank.
heating load
(Btu/hr)
time (hr)
minimum modulation = 20% of full output
20%
100%
heating load profileheating load profile
heat source must cycle on/off to supply loads!under 20% of full output
10%
on at 30%, then stabilizeramp downhold at 20%, then off
High efficiency gas-fired boilers
oil-firedsteel fire tube
atmospheric draft
DESIGN ISSUE: The very low pressure drop associated with cast-iron sectional boilers, and most fire tube boilers allows full system flow to pass through boiler.
0
5
10
15
20
25
0 2 4 6 8 10 12
pres
sure
dro
p (p
si)
flow rate (gpm)
100,000 Btu/hr !compact mod/con
100,000 Btu/hr !cast-iron sectional
VENT
conventional boiler!with low flow resistance
Conventional boilers
oil-firedsteel fire tube
atmospheric draft
DESIGN ISSUE: Compact boiler heat exchangers also create significantly higher pressure drop as fluid flows through them.
0
5
10
15
20
25
0 2 4 6 8 10 12
pres
sure
dro
p (p
si)
flow rate (gpm)
100,000 Btu/hr !compact mod/con
100,000 Btu/hr !cast-iron sectionalTYPICAL SOLUTION: Use a dedicated
boiler circulator to create flow through boiler, in combination with some form of hydraulic separation.
Many compact modulating / condensing boilers create high pressure drop
compactmod/con
heat exchanger
cast-ironsectional boiler
High efficiency gas-fired boilers
oil-firedsteel fire tube
atmospheric draft
closely spaced tees
very low flow resistance!common piping!
high flow ! resistance boiler
size headers for max flow velocity of 2 ft/sec
DESIGN ISSUE: Compact boiler heat exchangers also create significantly higher pressure drop as fluid flows through them.
TYPICAL SOLUTION: Use a dedicated boiler circulator to create flow through boiler, in combination with some form of hydraulic separation.
Hydraulic separation using closely spaced tees.
High efficiency gas-fired boilers
oil-firedsteel fire tube
atmospheric draft
buffer!tank
very low flow resistance!common piping!
size headers for max flow velocity of 2 ft/sec
boiler!circulator
high flow resistance boiler
DESIGN ISSUE: Compact boiler heat exchangers also create significantly higher pressure drop as fluid flows through them.
TYPICAL SOLUTION: Use a dedicated boiler circulator to create flow through boiler, in combination with some form of hydraulic separation.
Hydraulic separation using buffer tank.
High efficiency gas-fired boilers
oil-firedsteel fire tube
atmospheric draft
DESIGN ISSUE: Compact boiler heat exchangers also create significantly higher pressure drop as fluid flows through them.
TYPICAL SOLUTION: Use a dedicated boiler circulator to create flow through boiler, in combination with some form of hydraulic separation.
hydraulic separator
very low flow resistance!common piping!
high flow ! resistance boiler
size headers for max flow velocity of 2 ft/sec
Hydraulic separation using hydraulic separator.
High efficiency gas-fired boilers
solar
collec
tor ar
rayin
itial
lift
hea
d
thermal!storage!
tank
pressure regulated!variable speed circulator
3-way motorized mixing valve!(provides outdoor reset control)
zoned radiant ceiling panels
manifold valve actuators
variable speed!collector circulator
modulating / condensing
boiler
outdoor!temperature!
sensor
air return tube
air return tubedrainback /!
expansion space
temperature sensor mounted to absorber plate, or well within collector
DHW
Solar combisystem with drainback freeze
protection
Top of tank maintained at
minimum of 120 ºF
2
2.5
3
3.5
4
4.5
5
5.5
6
6.5
-10 0 10 20 30 40 50 60 70CO
POutdoor air temperature (ºF)
leaving load water temp = 86 ºF
leaving load water temp = 104 ºFleaving load water temp = 122 ºF
Heat sources such as condensing boilers, geothermal & ATW heat pumps, and solar collectors all benefit from low water temperature operation.
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
60 80 100 120 140 160 180 200
ther
mal
effi
cien
cy (d
ecim
al %
)
inlet fluid temperature (ºF)
ambient air temp. = 30ºF!solar radiation = 250 Btu/hr/ft2)
3.5
3.7
3.9
4.1
4.3
4.5
4.7
4.9
5.1
100 105 110 115 120 125
Coef
ficie
nt O
f Per
form
ance
(CO
P)
Entering water temperature (ºF)
Consider a 2,000 square foot well insulated home with a design heat loss of 18,000 Btu/hr. Assume that 90 percent of the floor area in this house is heated (1800 square feet). The required upward heat flux from the floor at design load conditions is:
heat flux= design loadfloor area
= 18,000 Btu/hr1,800 square feet
=10 Btuhr•ft2
To deliver 10 Btu/hr/ft2 the floor only has to exceed the room temperature by 5 degrees F. Thus, for a room at 68 degrees F the average floor surface temperature is only about 73 degrees F. ?This is not going to deliver "barefoot friendly floors" - as so many ads for floor heating promote.
Is radiant floor heating always the answer?
Tf = average floor surface temperature (ºF)Tr= room air temperature (ºF)q=heat flux (Btu/hr/ft2)
Why radiant floor heating ISN'T always the best choice…Direct gain passive solar buildings…
Initial concept: Since the insulated floor slab is already there- why not add tubing to keep it warm on cloudy days?
The passive solar concept relies on the floor mass giving up it’s heat at night.
If maintained at an elevated temperature with auxiliary heat ensuing solar gains cannot be absorbed.
The space quickly overheats.
A comparison of THERMAL MASS for several heat emitters:All heat emitters sized to provide 1000 Btu/hr at 110 ºF average water temperature, and 70 ºF room temperature:
Low thermal mass allows the heat emitters to quickly respond to changing internal loads
Notice where the tubing is in this 6” heated concrete slab