Upload
others
View
4
Download
0
Embed Size (px)
Citation preview
BENDING BEHAVIOR OF COMPOSITE FERRO-
CEMENT SLABS IN COLD FORMED STEEL FLOORS
By
Adham Elsayed Zakaria Tonsy
A Thesis Submitted to the
Faculty of Engineering at Cairo University
in Partial Fulfillment of the Requirements for the degree of
MASTER OF SCIENCE
In
Structural Engineering
FACULTY OF ENGINEERING, CAIRO UNIVERSITY
GIZA, EGYPT
2018
BENDING BEHAVIOR OF COMPOSITE FERROCEMENT
SLABS IN COLD FORMED STEEL FLOORS
By
Adham Elsayed Zakaria Tonsy
A Thesis Submitted to the
Faculty of Engineering at Cairo University
in Partial Fulfillment of the Requirements for the degree of
MASTER OF SCIENCE
In
Structural Engineering
Under the Supervision of
Prof. Dr. Metwally Abu-Hamd
…………………………..
Professor of Steel Structures and Bridges
Structural Engineering Department
Faculty of Engineering
Cairo University
Prof. Dr. Sameh Youssef Mahfouz
Yassin
…………………………
Associate Professor of Steel Structures
Head of Construction and Building
Engineering Department
Arab Academy for Science, Technology
and Maritime Transport
FACULTY OF ENGINEERING, CAIRO UNIVERSITY
GIZA, EGYPT
2018
BENDING BEHAVIOR OF COMPOSITE FERROCEMENT
SLABS IN COLD FORMED STEEL FLOORS
By
Adham Elsayed Zakaria Tonsy
A Thesis Submitted to the
Faculty of Engineering at Cairo University
in Partial Fulfillment of the Requirements for the degree of
MASTER OF SCIENCE
In
Structural Engineering
Approved by the
Examining Committee:
Prof. Dr.
Prof. Dr.
Prof. Dr.
FACULTY OF ENGINEERING, CAIRO UNIVERSITY
GIZA, EGYPT
2018
Engineer`s Name:
Date of Birth:
Nationality:
E-mail:
Phone:
Address:
Registration date:
Awarding date:
Degree:
Department:
Supervisors:
Examiners:
Adham Elsayed Zakaria Tonsy
20/07/1991
Egyptian
+201007140019
508 Nargess buildings, 5th settlement
01/03/2014
.../…/2018
Master of Science
Structural engineering
Prof. Dr. Metwally Abu-hamd
Prof. Dr. Sameh Youssef Mahfouz Yassin
Prof. Dr.
Prof. Dr.
Prof. Dr.
Title of Thesis:
Bending behavior of composite Ferro-cement slabs in cold formed steel floors
Keywords:
Ferro-cement slabs, shear connector, CFS section, and wire mesh
i
ACKNOWLEDGEMENTS
First and foremost I would like express my thanks to Almighty ALLAH on successful
completion of this research work and thesis
I hereby, express my sincere and profound gratitude to my supervisors Professor Dr.
Metwally Abu-hamd and professor Dr. Sameh Youssef Mahfouz for their continuing
assistance, support, guidance, and understanding throughout my graduate studies. Their trust,
patience, knowledge, great insight, modesty and friendly personality have always been an
inspiration for me and will deeply influence my career and future life.
The author is grateful Faculty of Civil Engineering, Cairo University for their support,
assistance and friendly treatment that not only facilitated the work, but also made it pleasant.
I also wish to express my deep gratitude to my friends in Egypt and for their invaluable
support and encouragement through the years. Special thanks are due to last but not the least
my heartiest appreciation goes to my parents for their endless patience and understanding
towards my work and everlasting love.
ii
TABLE OF CONTENTS
ACKNOWLEDGEMENT………………...……..….………...…….……..……………….I
TABLE OF CONTENTS ………...……………….…….....….………….………….........II
LIST OF FIGURES …………..……………………..……….………………....…......…V
LIST OF TABLES ……………………..……………………….……….…..................VII
ABSTRACT……………………………….………………………..………..………VIII
Chapter One: Introduction .................................................................................... 1
1.1 General Appraisal: ...................................................................................... 1
1.2 Problem Statement ...................................................................................... 3
1.3 Aim and Objectives .................................................................................... 3
1.4 CFS-Ferro-cement Composite Slab Tests .................................................... 4
1.5 Thesis Layout ............................................................................................. 4
Chapter Two: Literature Review .......................................................................... 6
2.1 Introduction ................................................................................................ 6
2.2 Ferro-cement............................................................................................... 6
2.2.1 Ferro-cement Versus Reinforced Concrete (Distinct Characteristics).... 6
2.2.2 Ferro-cement as a Laminated Composite .............................................. 7
2.2.3 Mechanical Properties of Ferro-cement ................................................ 8
2.2.4 Durability ........................................................................................... 14
2.3 Cold-Formed Steel Structures ................................................................... 15
2.3.1 Cold-Formed Steel Beams .................................................................. 15
2.3.2 Structural Behavior - Modes of Failure Due To Bending Buckling ..... 16
2.4 Shear Connectors ...................................................................................... 20
2.5 Review of Previous Investigations on Ferro-cement slab .......................... 21
2.6 Summary .................................................................................................. 23
Chapter Three: Experimental Work .................................................................... 24
iii
3.1 General Research Outline ......................................................................... 24
3.2 Materials ................................................................................................... 24
3.2.1 Cement ............................................................................................... 24
3.2.2 Fine aggregate .................................................................................... 24
3.2.3 Water ................................................................................................. 26
3.2.4 Wire Meshes ...................................................................................... 26
3.2.5 Mortar ................................................................................................ 26
3.2.6 Cold formed steel section ................................................................... 27
3.2.7 Shear connector .................................................................................. 27
3.2.8 Mortar Compressive Strength Test ..................................................... 27
3.3 Full-Scale Flexural Test ............................................................................ 29
3.4 Test Specimens and Arrangement ............................................................. 30
3.5 Test Procedures......................................................................................... 35
Chapter Four: Results and Discussion ................................................................ 37
4.1 Introduction .............................................................................................. 37
4.2 CFS-Ferro-cement composite slab behavior .............................................. 37
4.2.1 Group 1 .............................................................................................. 38
4.2.2 Group 2 .............................................................................................. 46
4.2.3 Strain analysis .................................................................................... 56
4.3 Parameters Studied ................................................................................... 66
4.3.1 Effect of Increasing the Slab Thickness .............................................. 66
4.3.2 Effect of increasing the number of Bolts Connecting the Ferro-cement
slab with the CFS-Section ................................................................................. 71
Chapter Five: Conclusions and Recommendations ............................................. 74
5.1 Strength and Stiffness of Composite Slabs ................................................ 74
iv
5.2 Recommendations ..................................................................................... 75
References……………………………………….……………………………….76
v
LIST OF FIGURES
Figure 1-1: Typical CFS sections ............................................................................... 2
Figure 2-1: Ferro-cement versus reinforced concrete (cross sections) (Naaman, 2000)
................................................................................................................................... 7
Figure 2-2: Ferro-cement as laminated composite (Naaman, 2000) ........................... 8
Figure 2-3: Schematic load-elongation curve of reinforcement concrete and Ferro-
cement in tension (Naaman, 2000) .............................................................................. 9
Figure 2-4: Typical qualitative influence of specific surface of reinforcement on
properties of Ferro-cement (Naaman, 2000) ............................................................. 10
Figure 2-5: Typical load deflection response of Ferro-cement illustrating various
stages of behavior (Naaman, 2000) .......................................................................... 12
Figure 2-6: Load versus various mesh layers of Ferro-cement in flexure (Arif et al.,
1999) ........................................................................................................................ 13
Figure 2-7: Cold-formed symmetrical I-sections: (a) two channels using bolts: (b)
Section using clamps (Hsu et al., 2003) .................................................................... 16
Figure 2-8: Modes of buckling of lipped channel in bending (Yu, 2001) ................... 17
Figure 2-9: Lateral buckling of an I-section beam (Rhodes, 1991) ........................... 20
Figure 2-10: Deflection history of I beam due to lateral buckling (Yu, 2001) ........... 20
Figure 3-1 Fine aggregate grading curve ................................................................. 25
Figure 3-2 the photographic view of wire mesh ........................................................ 26
Figure 3-3 Cold- formed lipped channel steel sections ............................................. 27
Figure 3-4 the cube compressive strength testing set up. .......................................... 28
Figure 3-5 layout of CFS-Ferro-cement composite slab specimen ........................... 32
Figure 3-6 Preparation of the composite Ferro-cement slab specimen ..................... 34
Figure 3-7 Dial gauges arrangement in the specimen ............................................... 34
Figure 3-8 testing up of the tests for all specimens ................................................... 35
Figure 3-9 Restrain the CFS sections at both ends to prevent lateral bucking .......... 36
Figure 4-1 CFS Ferro-cement composite slab .......................................................... 37
Figure 4-2 Load versus mid span deflection for Group 1 specimens ......................... 44
vi
Figure 4-3 Large deflection at the middle of the beam .............................................. 45
Figure 4-4 Transverse and longitudinal cracks ......................................................... 46
Figure 4-5 Load versus mid span deflection for Group 2 specimens ......................... 54
Figure 4-6 Large deflection at the middle of the beam .............................................. 55
Figure 4-7 Transverse and longitudinal cracks ......................................................... 55
Figure 4-8 load against strain at critical cross-section of the composite slabs for all
CFS-Ferro-cement composite slab specimens ........................................................... 65
Figure 4-9 mid span load-deflection curves of Ferro-cement slab for partially
composite specimens................................................................................................. 66
Figure 4-10 mid span load-deflection curves of CFS beams for partially composite
specimens ................................................................................................................. 68
Figure 4-11 mid span load-deflection curves of Ferro-cement slab for fully composite
specimens ................................................................................................................. 68
Figure 4-12 mid span load-deflection curves of CFS beams for fully composite
specimens ................................................................................................................. 70
vii
LIST OF TABLES
Table 3-1 Initial and final settings of cement ............................................................ 24
Table 3-2 Sieve analysis test results .......................................................................... 25
Table 3-3 Fineness modulus, moisture content and % of clay and fine materials ...... 25
Table 3-4 the results of the material test of mortar ................................................... 29
Table 3-5 Details description of composite slabs specimens ..................................... 31
Table 4-1 Experimental results of full scale composite slab testing ........................... 38
Table 4-2 the values of strain at ultimate load for all CFS sections .......................... 56
Table 4-3 the mid span ultimate strain values for CFS beams ................................... 70
Table 4-3 the ultimate loads of tested specimens ....................................................... 71
Table 4-4 the mid span deflections for CFS beams and Ferro-cement slab ............... 72
Table 4-5 the mid span strain values for CFS beams ................................................ 73
viii
ABSTRACT
This study investigates the structural behavior of continuously supported composite
Ferro-cement slabs, in which a Ferro-cement slab is connected together with cold-formed
steel (CFS) beam by means of shear connectors. This system, called a Precast Cold- Formed
Steel-Ferro-cement Composite Slab System, is designed to produce the composite action
between the CFS structure and Ferro-cement slab where shear forces are transmitted between
the beam and slab through shear connectors or studs. Ferro-cement slabs can be defined as a
thin reinforced concrete structure in which a brittle mortar is reinforced with layers of thin
wire mesh, uniformly dispersed throughout the matrix of the composite section. This research
is based on Experimental works involved full-scale testing of laboratory tests consisted of a
total of nine full-scale continuously supported composite Ferro-cement slabs with different
parameters and tested to fracture. One type of shear connectors (bolts) was tested and one
layer of wire mesh in Ferro-cement cold formed was proposed. The main variables
considered in the study are thickness (30mm, 40mm) of the Ferro-cement slab and different
spacing between bolts (450mm, 150mm).Uniform load bending system was used to test the
specimens. The results confirmed that increasing the thickness of Ferro-cement slab has not
significantly increased the load capacity of the composite slab. However, the increase in slab
thickness has delayed the formation of cracks at an early stage. Also, using spacing between
bolts (150 mm) has increased the capacity load of the fully composite section by almost one
third the capacity load of the partially composite section (Spacing 450 mm).
1
Chapter One: Introduction
1.1 General Appraisal:
Using composite slabs, to improve the stiffness and the load capacity of the slab, become
more popular in the building industry. The composite slab has resulted in great savings in the
weight of steel structure and reduction in beam depth. For more economical section, cold-
formed steel sections interact with the Ferro-cement slab through shear connectors.
(Deierlein, 1988; Viestetet al., 1997)
The advantages of composite construction have been widely spread due to the use of
Ferro-cement as a pre-cast composite slab. Composite action depends on interactive behavior
between steel section and concrete components designed together to be more efficient in
resisting the applied loads.
The interaction between steel and concrete in the composite structure was as following;
the upper compressive force was carried by the concrete slab and the lower tensile force was
carried through the tensile resistance of the steel section. The interaction between the
concrete slab and the steel beam is provided through shear studs to resist the shear flow at the
interface of the two materials.
Welding of shear studs is not applicable due to the relatively small thickness of the cold
formed sections (Hanaor, 2008); so, the shear connection between CFS and concrete must be
investigated and need more research.
The manufacturing of cold formed steel section is carried out at room temperature,
through rolling up a steel sheet of thickness from 1.5 mm to 4 mm. The use of CFS section in
the building industry started in the 1850s in both the United States of America (USA) and
Great Britain (UK). The CFS structural sections have many advantages than hot-rolled
sections, such as small thickness, lightness, ease of prefabrication, fast erection, and
installation.
One of the established commercial applications between CFS and concrete is the
composite slab system, where a concrete layer is placed on top of CFS section. However, the
structural use of CFS sections began in the mid of 20th century especially for industrial and
commercial buildings (Hancock et al., 2001). The typical sections widely used as purlins and
truss members are "Z" and "lipped C" sections (Figure 1.1).
2
Figure 1-1: Typical CFS sections
Composite construction of CFS sections and concrete began in Europe since 1940 and
was mainly used for roof systems, where a metal deck made from CFS was used to act
compositely with concrete (Sabnis, 1979).
Ferro-cement slabs can be defined as a thin reinforced concrete structure in which a
brittle mortar is reinforced with layers of thin wire mesh, uniformly dispersed throughout the
matrix of the composite section (Naaman, 2000). Ferro-cement slabs have taken a significant
place between the construction elements for its mechanical and durability properties which
recommend it the most suitable system for lightweight structures. Ferro-cement slabs
consider being an economic and suitable alternative material for roofing; however flat or
corrugated roofing system is quite popular.
This study investigated the structural behavior of composite slab system with CFS as
beam and Ferro-cement as slab. This type of system could solve the problem of a low rupture
bending capacity of the Ferro-cement slab. The proposed composite slab system improves the
rupture bending capacity and reduces the deflection due to the composite action and also
speeds up the construction time as the proposed Ferro-cement slab acts as permanent
formwork.
3
1.2 Problem Statement
Over the years, Ferro-cement slabs applications have widely increased due to its
mechanical and durability properties such as strength, toughness, lightness, and ductility. The
wide spread of Ferro-cement slab in the construction industry is due to relatively low cost,
weight and the ease of the production.
Although CFS slabs system is considered one of the most important construction element
as a sustainable structures in the developed countries have been recognized as an important
contributor to sustainable structures in the developed countries (Yu et al., 2005), its
application is limited to roofing systems and non-structural applications (Shaari & Ismail,
2003). This can be attributed to the small thickness of its cross-section that makes it easily
subjected to torsion failure, distortional, lateral torsional, lateral distortional and local
buckling
Pre- fabricated Ferro-cement slabs is widely used in the developed countries as mention
before. It considered one of the best alternatives in the construction industry to overcome the
high cost of the other building systems, and ease of erection which reduce the time of the
construction period and to get better quality control.
In this study, a type of composite slab comprised of CFS section with Ferro-cement
called Precast Cold–Formed Steel-Ferro-cement Composite slab System is proposed to
reduce the weight as well as to improve the strength of the composite system. One of the
main advantages of this system is its light weight compared to normal reinforced concrete
slab which results in the reduction of loads transmitted to supported elements.
1.3 Aim and Objectives
The aim of this research is to the properties of a precast proposed Ferro-cement-CFS
composite slab structural system. To achieve this aim, the following objectives are studied:
1. To investigate the different parameters that controls the performance of the
proposed composite slab system.
2. To study the behavior and performance of proposed Ferro-cement slab CFS as
composite slab system.
4
1.4 CFS-Ferro-cement Composite Slab Tests
The beam section consists of one lipped channel. The flanges were connected with Ferro-
cement panel by one type of shear connector (Bolts). The proposed CFS-Ferro-cement
composite slabs were tested as full scale and their results were used to evaluate the behavior and
performance of Ferro-cement slab connected to CFS By means of shear connector. There were
nine specimens with different configurations prepared for full-scale testing. A full-scale of
continuously supported slab specimens was tested using uniform load system.
Hence, the ultimate flexural capacity of the proposed composite slabs can be established.
Details of specimen’s description and parameters studied are discussed in Chapter 3. The
results and discussion of the experimental tests are discussed in chapter 4.
The finding from this research may eventually lead to the development or improvement
of the existing system on the welding problem of shear studs on CFS due to its thinness.
Therefore, this research is to investigate the possibility of using CFS-Ferro-cement composite
slabs for structures.
The outcome of this research contributes to promote the proposed composite slab
construction method as possible industry implementation and also the use of CFS as one of
the alternative materials for small to medium size building construction. Also this research
provides important technical knowledge which can be used as a design guideline for the
proposed composite slab of CFS and Ferro-cement structures.
1.5 Thesis Layout
Chapter one presents the general introduction, background of the study, problem
statement, aims and objectives and scope of this research. Significance of the study and thesis
layout is also described in this chapter.
Chapter two carries a comprehensive literature review on the area of study and all
published works related to current study.
Chapter three describes the specimen, test setup and full-scale flexural test of CFS-
Ferro-cement composite slabs.
5
Chapter four describes the results and analysis of the full-scale flexural test of CFS-
Ferro-cement composite slabs.
Chapter five presents the discussion and comparison of all the test results, conclusions
and the recommendations.
6
Chapter Two: Literature Review
2.1 Introduction
In this chapter, a review on composite slab with CFS section and the advantages of
Ferro-cement are presented. The importance and advantages of composite construction
are also highlighted. Three main components of composite slab i.e. Ferro-cement slab,
steel beam and shear connectors or studs are illustrated. Previous works related to
composite slab with CFS section and Ferro-cement member are presented.
2.2 Ferro-cement
Ferro-cement slabs can be considered one of the react innovated construction
building systems. Ferro-cement slabs is characterized of its thin thickness i.e. nearly 3
or 4 mm and its cross-section composed of light weight cement mortar and reinforced
with a densely wired mesh (Naaman, 2000). One of the main advantages of Ferro-
cement slabs that it can be easily molded in any shape due to its highly mold ability.
Due to the high magnitude of the specific surface of reinforcement in Ferro-cement
slabs, a higher bond between the mesh reinforcement and the cement matrix was
offered (Naaman, 2000).
The close spacing of the wire meshes in cement mortar improves ductility, and
leads to a better crack pattern mechanism in Ferro-cement (Kumar, 2005). The
applications of Ferro-cement are huge including low-cost roofing on short spans
(Kumar, 2005), repair and rehabilitation of deteriorated structures (Wang et al., 2004;
Ibrahim, 2011).
2.2.1 Ferro-cement Versus Reinforced Concrete (Distinct
Characteristics)
Ferro-cement is a kind of reinforced concrete construction, however, it is quite
different based on some significant factors which are adequately enough to elucidate
the variance. Compared to reinforced concrete, Ferro-cement (Figure 2.1):
7
More thin. Distributed reinforcement.
doubly reinforced in both longitudinal and transverse directions
Consists of fine mortar or paste matrix compared to concrete
with longer aggregates.
Figure 2-1: Ferro-cement versus reinforced concrete (cross sections) (Naaman, 2000)
2.2.2 Ferro-cement as a Laminated Composite
A lamina is assumed to be a composite made of single layer of mesh embedded in a
layer of cement mortar. Thus Ferro-cement can be considered as a laminated composite.
A lamina has orthotropic properties, i.e., its mechanical properties are different in the
three principal directions. In Ferro-cement if it is reinforced with square mesh, it will
have identical properties in the two principal directions. Figure 2.2 shows Ferro-cement
viewed as a laminated composite.
8
Figure 2-2: Ferro-cement as laminated composite (Naaman, 2000)
2.2.3 Mechanical Properties of Ferro-cement
The distinctive properties of Ferro-cement emanate from the substantial quantity of
two-way reinforcement which consists of smaller members having bigger surface area
than normal reinforcement. The term Ferro-cement was firstly used by Nervi (ACI
549R, 1997). According to him, the most notable features of Ferro-cement are “greater
resistance to cracking and elasticity”.
2.2.3.1 Tensile Strength
Ferro-cement is a material with a variety of unique properties. It is a miniature
model of a high performance reinforced concrete; when it cracks under service loads,
the crack is visible. Figure 2.3 (a) illustrates the load-deflection curve of a typical
reinforced concrete testing prism. The tensile stress-strain response of the reinforcing
steel is assumed to be elastic perfectly plastic (Naaman, 2000). Several stages of
behavior can be identified:
I. Stage I corresponds to the ascending linear static portion of the curve (OA);
this portion leads to a small plateau region which corresponds to cracking
of the prism.
9
II. Stage II corresponds to the portion of the curve (AB) where cracking starts
and during which crack formation stabilizes; generally, most cracks are
formed within a relatively small increment of load beyond first structural
cracking.
III. Stage III (BC) where the load-elongation response is most linear elastic and
crack widths increase with an increase in applied load; because of cracking,
the slope of this portion of the curve is smaller than that of the initial
portion. Stage III extends until the reinforcing steel yields.
Beyond yielding, represented by point C, the curve is essentially similar to that of
the reinforcing steel and failure will occur when it fails. Figure 2.3 (b) illustrates the
load elongation curve of a typical Ferro-cement tensile prism. The stages identified in
Figure 2.3 (a) for reinforced concrete are also observed here; however, the main
difference is in stage II. In Ferro-cement, stage II (AB) can be so extensive so as to
completely take over stage III. In particular, after first cracking, cracks keep forming
with increasing load. If the reinforcing parameters are appropriate, multiple cracking
can be extensive and at the end of multiple cracking, i.e., when the numbers of cracks
stabilize, they can be near to the yielding point of the steel.
Figure 2-3: Schematic load-elongation curve of reinforcement concrete and Ferro-cement in
tension (Naaman, 2000)
10
The main point when comparing between Ferro-cement and reinforced concrete is
its high specific surface area of reinforcement compared to the traditional
reinforcement.
The high specific surface area of reinforcement for Ferro-cement results in a
different tensile and flexural behavior, as was indicated by the experimental studies. It
was found that the tensile strength of Ferro-cement at first crack is directly proportional
to the specific surface of reinforcement (Swamy and Shaheen, 1990; Arif et al., 1999;
Somayaji and Naaman 1981; Naaman, 2000).
This can also be observed in Figure 2.5 which shows the effect of the specific
surface area of reinforcement on the stress at first crack, the stress at crack saturation,
the ultimate strain of the composite, and the crack width. The tensile strength of Ferro-
cement varies with the orientation of the mesh and the nature of applied loading
(Abdullah and Mansur, 2001; Arif et al., 1999).
Figure 2-4: Typical qualitative influence of specific surface of reinforcement on properties of
Ferro-cement (Naaman, 2000)
11
2.2.3.2 Compressive Strength
The compressive strength of Ferro-cement is controlled by the properties of the
cement mortar mix. Typical compression test results of Ferro-cement cubes suggest that
the compressive strength of Ferro-cement is smaller than that of the matrix alone due to
splitting transverse tensile stresses and buckling of the mesh reinforcement in
compression (Al-Noury and Haq, 1988; Mansur and Abdullah, 1998; Naaman, 2000).
Under normal circumstances, the type of mesh and its orientation also affect the
compressive strength. The performance of expanded and hexagonal metal meshes with
orientation in the direction of loading are lower to that of square wire meshes in the
same orientation. Wire meshes at 45 degrees orientation are also with lesser efficient
compared to meshes aligned along the loading direction (Hossain and Inoue, 2000).
In general, strain-stress plots of Ferro-cement are non-linear; Ferro-cement shows
linearity at 50-60% of the maximum strength while there is non-linearity at initial, in
between and final part of the plot (Hossain and Inoue, 2000; Rao, 1992; Rao and Rao,
1986).
2.2.3.3 Bending (Flexure)
Bending replicates the joint effect of parameters dictating both the tensile and
compression characteristic features, like mortar compressive strength, mesh type, mesh
properties and mesh orientation. However, it is generally presumed that the two way
composition of mesh reinforcement contributes extra strength and safety to one
directional bending.
Analogous to the case of tension, Ferro-cement displays typical features in bending
also. Figure 2.8 typifies load versus deflection response of Ferro-cement in bending.
12
Figure 2-5: Typical load deflection response of Ferro-cement illustrating various stages of
behavior (Naaman, 2000)
Several portions of the curve can be identified:
a) An early part where structural cracking does not occur.
b) A multiple cracking portion where cracks emanate and their width increases
with increasing load.
c) A portion where steady yielding of the steel reinforcement takes place;
gradual yielding occurs even when the steel mesh has a definite yield point,
because several layers of mesh, placed at different depths of the section,
undergo yielding at different loading levels.
d) A post-yielding plastic or strain-hardening region during which the
maximum or ultimate load is attained.
e) A post-peak portion where failure happens due to either mortar failure in
compression or failure of the extreme layer of mesh.
In general, the bending resistance and the flexural moment capacity increase with
the increase in mesh layers. Figure 2.9 shows the load carrying capacity of Ferro-
cement with varying number of mesh layers. However, it is not directly proportional to
the volume fraction of reinforcement.
13
This is because even if intermediate meshes placed near the Centre of the section
undergo yielding, they do not contribute as much as meshes placed near the outer
surfaces (Mansur and Paramasivam, 1986; Mansur, 1988; Bhatacharyya et al., 2003;
Montesinos and Naaman, 2004; Suksawang et al., 2006)
The behavior of plain mortar under bending is replicated by Ferro-cement with
bundled mesh layer at cross-sectional Centre. The most effective stratum of mesh is the
one nearest to the farthest fiber or the face of the element in Ferro-cement bending
elements same as in reinforced concrete (Paramasivam and Ravindarajah, 1988). Unlike
in tension, the particular surface of reinforcement does not have a great control on the
cracking pattern in bending. The average crack width is basically dependent on tensile
strain in the farthest stratum of wire mesh and the spacing of wire mesh in transverse
(Naaman, 2000).
Under normal circumstances, square shaped welded mesh attains better behavioral
performance in bending than mesh of other shapes. This emanates from transverse
wires in welded wire meshes provision of higher anchorage for bond zone through
which the matrix are supported via biaxial confinement. The least performance is from
the hexagonal shaped wire meshes.
The same applies to tension; 45 degree orientation provides the least configuration
in bending (Naaman, 2000; Arif et al., 2001). The influence of mesh orientation on load
carrying capacity of Ferro-cement subjected to bending is shown in Figure 2.9.
Figure 2-6: Load versus various mesh layers of Ferro-cement in flexure (Arif et al., 1999)
14
2.2.3.4 Shear
There is relatively little information on the shear properties of Ferro-cement. This
because Ferro-cement is primarily used in the form of thin elements where the span-to-
depth ratio is large enough that one-way shear does not control the failure mode.
Moreover, parallel longitudinal alignment of the reinforcing layers, and a high volume
fraction of mesh which contributes to the dowel action resistance in shear. Thus, in case
of Ferro-cement beams the behavior is controlled by the bending (Naaman, 2000).
Irrespective of the content and type of used mesh or strength of mortar, it has been
reported that an approximate 32 percent of bending strength is the shear strength
(Mansur and Ong, 1987). In contrast, flexural capacity of Ferro-cement is reached first
before shear failure occurs (Mansur and Ong, 1991). In addition, cracking shear
strength of Ferro-cement varies inversely with the span-to-depth ratio and
proportionally with layers of mesh and strength of mortar (Al-Kubaisy and Nedwell,
1999).
Apart from its exhibition of excellent crack control characteristics in shear, Ferro-
cement slabs behavior is comparable to that of conventional concrete slab. However, in
contrast to the failure of slabs in flexure, the failure of slabs in shear shows only a small
signal of impending failure, except for the creation of a great number of diagonal cracks
and an insignificant plastic behavior after the multiple cracking (Mansur and
Kiritharan,2001; Alsulaimani and Basunbal,1991).
The punching shear strength of slabs subjected to central load, increase with the
increase in width of punching area, volume fraction of mesh reinforcement, depth of
slab, and mortar compressive strength while it decreases with the increase in effective
span and the size of loading area (Paramasivam and Tan, 1993; Ahmed and
Nimityongskul, 1998; Mansur et al., 2001).
2.2.4 Durability
Durability is the ability of Ferro-cement to withstand deteriorations when exposed
to different loading and environmental exposures. There are two unique factors which
determine durability of Ferro-cement apart from those of the normal reinforced
concrete:
15
I. The cover to the mesh reinforcement is comparatively small and
accordingly it is more convenient for corrosive liquids to penetrate to the
reinforcement (Nedwell, 2000; Mansur et. al., 1996).
II. The surface area of the reinforcement is unusually high; so that the contact
area available for corrosion and its subsequent rate are potentially high
(Naaman, 2000).
However, each factor differs in affecting the durability of the Ferro-cement
depending on condition of exposure. Therefore it is very important to provide sufficient
cover to Ferro-cement elements. The armature cover in compressed regions can be as
high as 6 mm, while a minimum of 10 mm has been suggested for medium aggressive
environments (Mansur et al., 1996; Liborio and Hanai, 1992).
For a simulated load-marine corrosion environment, an OPC mortar cover of 5 mm
have been shown to supply adequate barrier for the galvanized weld mesh against
corrosion (Xiong and Singh, 1997).
2.3 Cold-Formed Steel Structures
The contemporary needs of high strength materials for structural purposes brought
about substantial use of CFS manufactured through the bending of horizontal level steel
sheets at controlled temperature. The thickness of CFS sections ranged from 1.2 to
3.2mm (Yu et al., 2005); and they are highly regarded for their roles in sustainable
construction as a green technological material. They were utilized for the erection of
commercial and residential structures as roof trusses and for other non-structural
purposes.
2.3.1 Cold-Formed Steel Beams
Beam is defined as a structural member that acts laterally in response to
longitudinally loads by bending or deflecting along its axis. Upon being loaded, strain
and stresses occurs which leads to determination of shear force and bending moment
capacity.
16
The usual shapes of the CFS section used in structural beams are C-section with or
without lips, Z-sections and I-sections. CFS I-sections are usually formed when two C-
lipped channel sections are oriented back-to-back so that higher moment stability and
bearing performance could be achieved as shown in (Figure 2.10 a). Hsu et al., (2003),
proposed the I-shaped closed loops thin-walled plates into the preferred double
symmetrical geometry that form closed loops. This design philosophy was achieved by
forming the I-section with plate edges clamped at the flange location, (Figure 2.10 b).
However, this type of beam is difficult to form and not practical to be used in
construction.
Figure 2-7: Cold-formed symmetrical I-sections: (a) two channels using bolts: (b) Section
using clamps (Hsu et al., 2003)
2.3.2 Structural Behavior - Modes of Failure Due To Bending
Buckling
There are three basic buckling modes for CFS members such as local buckling,
distortional buckling and lateral or flexural torsional buckling, as shown in Figure 2.11
(Hancock et al.,2001; Cheng and Benjamm, 2003; Hancock, 2003). The transverse
deformation of plate flexure which encompasses distortion of the line of intersection is
known to be local buckling.
17
Lateral torsional buckling happened when the bending members bend or twist from
lateral plan view and remain in the same cross sectional shape. Local shear buckling
takes place in slender webs with bending members in the wide flanges of sheeting
profiles subject to diaphragm action. Global shear buckling occurs only in lightweight
sheeting profiles subjected to diaphragm action.
Figure 2-8: Modes of buckling of lipped channel in bending (Yu, 2001)
2.3.2.1 Local Buckling and Post-Buckling Strength of Thin Plate Elements
CFS sections have low width to thickness ratio which leads to local buckling when
subjected to compression, shear, bending, or bearing stress below yield stress. For the
CFS I-beam, the thin flange which is subjected to load is possible to buckle locally too.
Hence, a major design consideration for such elements is local buckling.
Although, occurring of local buckling for CFS does not mean that the loading
capacity has been reached when its buckling stress has already arrived, but in many
cases they still withstand additional load in excess of the load at local buckling. Hence,
it still has greater strength called post-buckling strength.
18
Local buckling is common in most CFS cross-sections, this guarantee superior
economy than a heavier section without local buckling (Yu and Schafer, 2003). (Dundu
and Kemp, 2005) Carried out a research and observed stress concentrations, shear lag
and bearing deformations caused by back-to-back channels with a bolted connection
made local buckling more critical. They recommended a factor of 0.8 to the yield
moment and the buckling moment of resistance to take care of stress concentrations,
shear lag and bearing deformations of back-to-back channels.
Chu el al., (2005) investigated about the buckling behavior of CFS channel section
beams when subjected to uniformly distributed load. Their study emphasized on local
and distortional buckling, sections subjected to pure compression or bending have the
only prevalent result. The CFS member was under the effect of uniformly distributed
transverse load, the outcome of their study showed that for local buckling; there is no
practical difference in critical loads between the two loading systems.
However, significant differences exist for distortional buckling. For a uniformly
distributed loading, the critical load is higher than that of pure bending. The difference
in the critical loads of both cases has been proved to decrease with the beam length for
most practical cases.
Through computational and experimental study by (Cheng and Benjamm, 2003),
the developed testing plan and details have been shown to adequately restrict
distortional buckling and provided a simple repeatable test that generates the local
buckling flexural capacity for C and Z sections.
However, the overall agreement is slightly skewed by a number of quite
conservative predictions for non-slender members that had observable inelastic reserve
capacity (Mutest /My > 1).
Through all the previous researches, the direct strength method had a main
advantage in which it can predict the ratio for both slender and non-slender specimens.
For direct strength method, its concept based on determination of all elastic instabilities
for the gross section (i.e., local, distortional, and global buckling) and the load or
moment that drives the cross-section to yield. The test results indicated that many
improvements in the elastic buckling and effective width calculation of C and Z cross-
sections are still available.
19
2.3.2.2 Lateral Buckling and Deflection of CFS Beams
Lateral buckling or lateral-torsional buckling, occurs when a beam which is
subjected to bending stress about its major axis acquires a tendency to displace
laterally or vertically, for Instance displace at right angle to the direction of
loading, and twist, if not properly braced. This behavior of an I-section beam is
shown in Figure 2.12. In addition with this, the deflection history due to lateral-
torsional buckling of the I-beam is shown in Figure 2.13. Based on the Figure, the
beam deflects in the y direction or displace vertically, at distance of (v) from its
original location before the lateral buckling occurred. This type of vertical
deflection is considered as in-plane bending. Later, whenever the buckling load
reached, the beam buckles laterally, at a distance of (u), and the section rotates
about the Centre of rotation CLB at a degree of rotation, (ø) (Stone and Laboube,
2005).
Furthermore, most of the CFS beams are restrained against lateral movement,
either by the remaining members joined to the beam or by bracing such as anti-
sag bars. Such restraints reduce the potentiality of lateral buckling, but do not
necessarily eliminate this problem (Rhodes, 1991).
In cases of members with continuous restraint the lateral torsional buckling
capacity reaches a minimum value over a finite length of beam, whereas in the
absence of restraint the buckling capacity decreases indefinitely with length. Most
of the design standards for CFS provide criteria for the design of CFS I beams
against their lateral buckling behavior.
20
Figure 2-9: Lateral buckling of an I-section beam (Rhodes, 1991)
Figure 2-10: Deflection history of I beam due to lateral buckling (Yu, 2001)
2.4 Shear Connectors
The mechanism of composite action between steel cross-section and concrete slab
depends on the shear flow, therefore the design and execution of shear connector
elements need to be carefully conducted.
Adhesion, friction, and bearing are some of the mechanisms that shear connectors
provide for stresses transmission (Viest et al, 1997). Various types of shear connectors
have been studied and introduced. In this study the steel CFS beam is connected to
Ferro-cement slab using bolts as a shear connector.
21
2.5 Review of Previous Investigations on Ferro-cement slab
(Shannag and Tareq) (2007) had studied the combined effect of reinforcing steel
meshes and discontinuous fibers as a single reinforcement in the thin mortar specimens
on the flexural behavior of Ferro-cement slabs. The researchers used 72 Ferro-cement
slabs with woven steel square wire mesh loaded with a point load in the center of the
slabs. Many parameters were studied in this research; mesh geometry, number of mesh
layers, using discontinuous glass and brass coated steel fiber. The results indicated that
as the wire mesh layers increased, the flexural strength of the Ferro-cement slabs
improved. While as the smallest spacing obtained in the wire mesh, the improved
flexural behavior obtained.in addition to, using fibers in the cement matrix improved
the flexural strength and energy absorption of Ferro-cement slabs.
(Al-Rifaie and Joma'ah) (2010) had studied the structure and the ultimate strength
of square Ferro-cement slabs of 50 x 50 cm in dimensions rested on I-beam cross-
section through attaching two Ferro-cement channel cross-sections back to back. The
flexural test carried out through subjecting the specimens to a point load. Four
specimens were tested; S1 and S2 were 2 cm thickness while S3 and S4 were 3 cm
thickness. For the reinforcement; S1 and S3 have two mesh layers while S2 and S4
have four mesh layers. The results indicated that all the slabs regardless the thickness or
the reinforcement was cracked in the middle. For S2, S3, and S1 the failure was through
the slabs, while for S4, the failure was through the beam at failure load 64 N.
(Wafa and Fukuzawa) (2010) investigated the characteristics features of thin
composite Ferro-cement elements using different reinforcement meshes in flexure. The
parameters observed in their study included: the consequence of different types of
reinforcement meshes (stainless steel meshes and E-fiberglass meshes); amount of
mesh layers and different mesh diameters with opening size and also different types of
mortar materials as matrix (cement grout mortar and polymer–cement grout mortar) on
the first crack load; bending stiffness; ultimate flexural load; load–deflection behavior;
crack characteristics; energy absorption capacity; and ductility index. The test results
elucidate that the utilization of stainless steel meshes as reinforcement system in the
Ferro-cement thin composite elements greatly influenced the improvement of bending
characteristics such as first crack load, bending stiffness, ultimate flexural load, energy
22
absorption to failure, and numerous fine and well-distributed cracks with a smaller
width than while utilizing fiberglass meshes.
(Ibrahim) (2011) had studied the punching capacity of Ferro-cement square slabs
supported on the four edges. The Ferro-cement slabs were provided with a 8 mm
diameter steel bar on the perimeter of the slab to support the spacing of the steel mesh.
The studied parameters in this research are wire mesh volume fraction, slab thickness,
and the patch load pattern. The results indicated that as the volume fraction increased,
the punching behavior of the Ferro-cement increased. In addition to, the ductility and
the stiffness of the tested slab had increased by increasing the loaded area sizes.
(Shri and Thenmozhi) (2012) had studied the ductility properties of hybrid fiber
reinforced rectangular Ferro-cement slabs with dimensions of 30 x 70 cm. the studied
parameters were; modulus of rupture and deflection at ultimate load, service load, crack
width, and moment curvature. The results indicated that as the slab thickness increased,
the ductility increased. In addition to, increasing the fiber content from 0% to 0.3% had
increased the load carrying capacity.
(Ramliand and Tabassi) (2012) investigated the mechanical performance of
polymer-modified Ferro-cement in different exposure conditions. In the study, they
assessed the load-deflection characteristics, first crack strength, crack width and crack
spacing of three commercial polymer-modified Ferro-cement; styrene-butadiene rubber
(SBR), poly-acrylic ester (PAE) and vinyl acetate-ethylene (VAE), and unmodified
Ferro-cement elements cured in air and saltwater exposure conditions. The outcome of
the tests showed that continuous saltwater exposure greatly influence the performance
of polymer modified Ferro-cement in flexure by displaying higher experimental values
of the first crack load and ultimate strength of all the specimens. Polymer modified
Ferro-cement also exhibited lower average crack width compared to the unmodified
Ferro-cement, irrespective of the exposure conditions.
(Randhir and Darshan) (2014) had studied the effect of inclusion of steel fibers
to the cement mortar of Ferro-cement slabs reinforced with different number of wire
mesh layers. Also, the researchers studied the impact of using different number of wire
mesh layers on the flexural behavior of Ferro-cement slabs. The results obtained
showed that increasing the number of wire mesh layers had increased the flexural
strength and reduced the deflection occurred. In addition to, using steel fibers had a
23
positive impact on the flexural strength of the Ferro-cement slab comparing to the one
without steel fibers.
(Alhajri and Tahrir) (2016) had studied the composite behavior of Ferro-cement
slabs supported over u-shaped cold formed steel sections. The composite action
between the steel u-shaped beam and the Ferro-cement slab was through bolts. The
results indicated that increasing both the cold formed steel section thickness and the
number of wire mesh layers had improved the flexural behavior of the studied structure.
2.6 Summary
From the previous studies it can be observed that the use of CFS, concrete and
Ferro-cement are reported on beams and slabs. It is also observed that Ferro-cement
causes less or no deterioration on the structural elements compared with the
conventional concrete. The Ferro-cement-concrete composites studied which are
reported proves improving the performance of the structural elements in terms of
flexural and impact strengths, ultimate capacity, reduced crack width, fire resistance,
insulation resistance, energy absorption, ductility, shear resistance, etc.
Also, the CFS is light weight steel section and high efficiency as flexure members.
However, Cold-Formed-Ferro-cement Composites has more tendency of improving the
overall performances that are required of the structural elements. Therefore, it is highly
recommended that investigations using CFS-Ferro-cement Composites is essential.
24
Chapter Three: Experimental Work
3.1 General Research Outline
The study investigates experimentally the structural behavior of cold formed-Ferro-
cement composite slabs. Experimental work involved on full-scale testing on the
proposed composite slab test specimens. Nine full-scale CFS-Ferro-cement composite
beam specimens were tested in this program.
Full scale tests representing the actual behavior of CFS Ferro-cement composite
slabs under flexural load were carried out. Two major parameters were studied the
thickness of Ferro-cement slab and the spacing between bolts (shear connector)
connecting the Ferro-cement slab with the CFS section to perform a composite slab.
3.2 Materials
3.2.1 Cement
Ordinary Portland Cement (OPC) of ‘Tourah’ brand was used during the study.
The (OPC) used complied with the Type I Portland Cement as in Egyptian Standard
2008/2253. Initial and final settings of cement are shown in table 3.1.
Type of
cement
Specific
gravity
Initial setting
time
Final setting
time
CEMI 42.5 R 3.15 60 min 5h
Table 3-1 Initial and final settings of cement
3.2.2 Fine aggregate
Sand passing through 4.75 mm sieve was used as fine aggregate in mortar for
Ferro-cement. Sieve analysis test results and gradation curve are shown in table 3.2 and
figure 3.1. Fineness modulus, moisture content and the percentage of clay and fine
materials are also shown in table 3.3.
25
Sieve
size
(mm)
Weight
Retained
(gm.)
Cumulative
Weight
Retained
(gm.)
Cumulative
Retained
(%)
Passing
(%)
4.75 17 17 1.8 98.2
2.36 29 46 4.7 95.3
1.18 109 155 15.7 84.3
0.6 389 544 54.9 45.1
0.3 332 876 88.4 11.6
0.15 101 977 98.5 1.5
pan 15 992 100 0
Table 3-2 Sieve analysis test results
Grading Type: Well Graded
Figure 3-1 Fine aggregate grading curve
Type of
aggregate
Fineness
modulus
specific
gravity
moisture
content
% of clay and
fine
Natural sand 2.63 2.67 0.60% 1.20%
Table 3-3 Fineness modulus, moisture content and % of clay and fine materials
0
10
20
30
40
50
60
70
80
90
100
0 1 2 3 4 5
Passing %
Seive Size (mm)
26
3.2.3 Water
The water cement (W/C) ratio is an essential factor to determine the concrete
strength. It should not contain any substance, which can be harmful to the process of
hydration of cement and durability of concrete. In general, water, which is acceptable
for drinking, is suitable for the concrete mixing. In this study tap water was used for the
manufacture of the concrete.
3.2.4 Wire Meshes
Expanded steel wire mesh (1.5mm diameter) locally available in the market, was
used as the reinforcement of slab. Figure 3.2 depicts the photographic view of wire
mesh used. The dimensions of wire mesh are 20mm x 20mm.
Figure 3-2 the photographic view of wire mesh
3.2.5 Mortar
Mortar mix was conducted by mixer (electrically operated). Cement and natural
sand were used in making the Ferro-cement concrete in the ratio of 1:2.25 with a
water/cement ratio of 0.4.
27
3.2.6 Cold formed steel section
The CFS sections used in this study are supplied by one of the steel manufacturers
in Egypt. Cold- formed lipped channel steel sections with depth of 140mm and
thickness of 1.5mm were used as shown in figure 3.3.
Figure 3-3 Cold- formed lipped channel steel sections
3.2.7 Shear connector
Self-drilling screws of 6 mm in diameter, 60 mm in length and steel grade 4.6 were
used.
3.2.8 Mortar Compressive Strength Test
Along with this study, mortar cubes of 70mm size were used to determine the
compressive strength of mortar. Three cubes were used to determine the mortar
compressive strength at 7 and 28 days. The compressive strength of mortar was
obtained using cube compression test.
28
The cube compressive strength testing set up is shown in Figure 3.4. The results of
the material test of mortar are given in Table 3.4. It was observed that the average
compressive strength after 7 days is 29.1 MPA, while the average compressive strength
after 28 days is 38.3 MPA.
Figure 3-4 the cube compressive strength testing set up.
29
7 DAYS 28 days
Test
Compressive
strength
(MPA)
Average
comp.
strength
(MPA)
Compressive
strength
(MPA)
Average
comp.
strength
(MPA)
1
33
31.4
35.3
36 16.7 36.5
29.8 36.1
2
23.3
26.5
38.6
36.3 26.9 33.9
26 17.6
3
29.2
28.6
34.3
33.5 29.5 31.8
27.1 32.7
4
25.7
28.5
36.7
38 31.2 42.4
20.2 34.7
5
24.7
29.5
36.8
39.2 14.3 39.6
34.5 41.3
6
22.2
27.4
44.1
41.9 25.4 39.6
34.7 41.9
Table 3-4 the results of the material test of mortar
3.3 Full-Scale Flexural Test
Full scale testing of continuously supported composite slab was set up in this
research. The purpose of full-scale tests was to evaluate and determine the flexural
strength and behavior of CFS-Ferro-cement assembled together as composite slab. The
specimens were tested by using simply supported beam specimens of 2100mm length
between supports with uniformly loading system as shown in figure 3.8.
Hence, the ultimate flexural capacity of the proposed composite was determined.
The experimental work focused on the ultimate strength of the CFS-Ferro-cement
composite slabs which was obtained from their load-deflection curve and will be
discussed later in Chapter 4.
30
3.4 Test Specimens and Arrangement
A total of nine composite slab specimens were tested for full-scale testing and
details description of each specimen are summarized in Table 3.5. Figure 3.5 shows
layout of CFS-Ferro-cement composite slab specimen where the actual length of the
beam was 2400mm.
However, an excess of 150mm at the each end of the beam to the support was
purposely done to ensure that the beam was simply support with an effective length of
2100mm between the supports. The test was set-up in such a way that the beams should
fail in flexural. Hydraulic jack with load cell having a capacity of 10 tons was used.
The width of Ferro- cement slab was 1200 mm with thickness (30-40) mm. A
lipped C Channel section was formed with top flange attached to the Ferro-cement slab.
Self-drilling bolts of 6 mm in diameter, 60 mm in length and steel grade 4.6 was used to
connect the CFS-Ferro-cement slab. Two different spacing between bolts were used
(450mm and 150mm). One layer of expanded steel wire mesh (2400mm x 1200mm)
was used with spacing (20mm x 20mm).
The casting of slabs for all composite slabs utilized the same batch of mortar. This
was to ensure that the mortar properties remained similar in all specimens. Figure 3.6
shows the formwork, casting work and the composite slab test specimen respectively.
The test specimens were supported with a pin at one end and a roller at the other end to
indicate that the test was a simple supported beam structure. Deflections at the bottom
flange of the steel section and at the bottom of slab were monitored at the center-points
using dial gauges.
Figure 3.7 shows dial gauges arrangement in the specimen. The strain gauges were
installed in the mid-span section of the bottom flanges of CFS beam to measure strains
in the CFS beam and to monitor yielding of the beam. The strains were measured using
linear strain gauges with the length of 100mm. The strain gauges were placed
longitudinally in the direction of the span so as to measure the longitudinal (flexural)
stresses. Figure 3.8 shows the setting up of the tests for all specimens.
31
Group
no. Slab
Slab
Thickness
Spacing between
bolts Type of CFS Ferro-cement slab
1
FC1
3 cm 450 mm Partially composite FC2
FC3
FC4 150 mm Fully composite
2
FC5
4 cm
450 mm Partially composite FC6
FC7
150 mm Fully composite FC8
FC9
Table 3-5 Details description of composite slabs specimens
a) Layout of CFS-Ferro-cement composite slab specimen for group 1 (All dimensions in m
32
b) Layout of CFS-Ferro-cement composite slab specimen for group 1 (All dimensions in m)
Figure 3-5 layout of CFS-Ferro-cement composite slab specimen
33
a) Formwork of full-scale Ferro-cement slab
b) Casting and finishing process
34
c) CFS composite Ferro-cement slab test specimen
Figure 3-6 Preparation of the composite Ferro-cement slab specimen
Figure 3-7 Dial gauges arrangement in the specimen
35
Figure 3-8 testing up of the tests for all specimens
3.5 Test Procedures
After the instrumentation system had been set-up, the specimen was loaded up to
15% of the predicted value. After reaching the 15% of predicted load capacity, the
specimen was unloaded back. This procedure was carried out so as to enable the
specimen to be in equilibrium state. An increment of about 2 KN was adopted so that a
uniform data and gradual failure of the specimen was monitored.
The specimen was loaded until large deflection of the middle beam can be
observed. At this point, the loading sequence was controlled by the increasing of
deflection as a small increment of load has resulted. This procedure was continued until
the specimen had reached its failure state. The composite system was supposed to fail
when there was a large reduction in the applied load or when a large deformation
occurred at the middle beam of the tested specimen.
36
An important precaution was to restrain the composite Ferro-cement slab specimen
laterally at both ends of the beam so as to prevent lateral buckling of the CFS section
during loading as shown in Figure 3.9.
Figure 3-9 Restrain the CFS sections at both ends to prevent lateral bucking
37
Chapter Four: Results and Discussion
4.1 Introduction
The results of the full-scale test specimens are illustrated and discussed in this
chapter. The relationship between the load and maximum deflection of the tested
specimens are plotted. Discussion includes flexural behavior and ultimate bending
capacities. Nine full-scale continuously supported CFS Ferro-cement composite slabs
with variable parameters were tested until failure under uniformly loading system. The
main variables considered in the study are the thickness of Ferro-cement and the
spacing between bolts. The test program was conducted in Structural Laboratory at the
Cairo University in Egypt.
4.2 CFS-Ferro-cement composite slab behavior
The purpose of the flexural test is to study the moment capacity, the mode of
failure, deflection behavior, and strain distribution along the section of the tested
specimens. The tests present the result of single C-channel specimens composite with
Ferro-cement slab as shown in figure 4.1. The details of the specimens are illustrated in
Chapter 3. The results are summarized in Table 4.1.
Figure 4-1 CFS Ferro-cement composite slab
38
Group
no.
Slab
no.
First
Crack
Load
(KN)
Ultimate
Load
(KN)
Maximum Deflection (mm)
Point 1 Point 2 Point 3 Point 4 Point 5
1
FCS1 27 53 14.8 14.1 14 20.3 14.2
FCS2 22 55 17.1 17.6 15.5 20.5 15.5
FCS3 20 45 17.6 17.9 18.3 23 18.7
FCS4 23 68 22 21.9 18.9 30 19.2
2
FCS5 22 48 18.8 18.4 17.1 20.3 17.1
FCS6 37 57 17.2 16.7 17.4 20.6 17.1
FCS7 35 64 20.9 21.1 18.2 28.7 17.8
FCS8 31 64 20.6 21.1 18.1 28.5 18.1
FCS9 38 70 22.5 22.2 22.1 32 22.4
Table 4-1 Experimental results of full scale composite slab testing
4.2.1 Group 1
The load (KN) versus mid-span deflection (mm) for Group 1 specimens is shown
in figure 4.2. In this case, failure was due to sudden torsional buckling of CFS lipped
channel. All specimens in this group exhibited a similar mode of failure, which started
by formation of transverse cracks in the Ferro-cement slab followed by a sudden
torsional buckling of steel beam at a region of maximum bending moment due to large
deflection of the beams. The failure mode occurred at the middle of the beam due to
large deflection at maximum bending moment and torsional buckling of steel beam as
shown in figure 4.3. The longitudinal cracks are located at the Centre and extended
along the length of the Ferro-cement slab as shown in figure 4.4.
39
4.2.1.1 Ferro-cement slab 1
Load-deflection curve at point 1 Load-deflection curve at point 2
Load-deflection curve at point 3 Load-deflection curve at point 4
0
10
20
30
40
50
60
0 10 200
10
20
30
40
50
60
0 10 20
0
10
20
30
40
50
60
0 10 20
0
10
20
30
40
50
60
0 20 40
40
Load-deflection curve at point 5
a) Load versus mid span deflection for FCS1
4.2.1.2 Ferro-cement slab 2
Load-deflection curve at point 1 Load-deflection curve at point 2
0
10
20
30
40
50
60
0 5 10 15
0
10
20
30
40
50
60
0 10 20
0
10
20
30
40
50
60
0 10 20
41
Load-deflection curve at point 3 Load-deflection curve at point 4
Load-deflection curve at point 5
b) Load versus mid span deflection for FCS2
0
10
20
30
40
50
60
0 10 20
0
10
20
30
40
50
60
0 20 40
0
10
20
30
40
50
60
0 10 20
42
4.2.1.3 Ferro-cement slab 3
Load-deflection curve at point 1 Load-deflection curve at point 2
Load-deflection curve at point 3 Load-deflection curve at point 4
0
5
10
15
20
25
30
35
40
45
50
0 10 20
0
5
10
15
20
25
30
35
40
45
50
0 10 20
0
5
10
15
20
25
30
35
40
45
50
0 10 20
0
5
10
15
20
25
30
35
40
45
50
0 20 40
43
Load-deflection curve at point 5
c) Load versus mid span deflection for FCS3
4.2.1.4 Ferro-cement slab 4
Load-deflection curve at point 1 Load-deflection curve at point 2
0
5
10
15
20
25
30
35
40
45
50
0 10 20
0
10
20
30
40
50
60
70
80
0 20 40
0
10
20
30
40
50
60
70
80
0 20 40
44
Load-deflection curve at point 3 Load-deflection curve at point 4
Load-deflection curve at point 5
d) Load versus mid span deflection for FCS4
Figure 4-2 Load versus mid span deflection for Group 1 specimens
0
10
20
30
40
50
60
70
80
0 10 20
0
10
20
30
40
50
60
70
80
0 20 40
0
10
20
30
40
50
60
70
80
0 10 20
45
a) Large deflection at the middle of the beam
b) Large deflection at the middle of the beam
Figure 4-3 Large deflection at the middle of the beam
46
Figure 4-4 Transverse and longitudinal cracks
4.2.2 Group 2
The load (KN) versus mid-span deflection (mm) for Group 2 specimens is shown
in Fig 4.5. In this case, failure was due to sudden torsional buckling of CFS lipped
channel. All specimens in this group exhibited a similar mode of failure, which started
by formation of transverse cracks in the Ferro-cement slab followed by a sudden
torsional buckling of steel beam at a region of maximum bending moment due to large
deflection of the beams. The failure mode occurred at the middle of the beam due to
large deflection at maximum bending moment and torsional buckling of steel beam as
shown in figure 4.6. The longitudinal cracks are located at the Centre and extended
along the length of the Ferro-cement slab as shown in figure 4.7.
47
4.2.2.1 Ferro-cement slab 5
Load-deflection curve at point 1 Load-deflection curve at point 2
Load-deflection curve at point 3 Load-deflection curve at point 4
0
10
20
30
40
50
60
0 10 200
10
20
30
40
50
60
0 10 20
0
10
20
30
40
50
60
0 10 20
0
10
20
30
40
50
60
0 10 20 30
48
Load-deflection curve at point 5
a) Load versus mid span deflection for FCS5
4.2.2.2 Ferro-cement slab 6
Load-deflection curve at point 1 Load-deflection curve at point 2
0
10
20
30
40
50
60
0 5 10 15 20
0
10
20
30
40
50
60
0 10 20
0
10
20
30
40
50
60
0 10 20
49
Load-deflection curve at point 3 Load-deflection curve at point 4
Load-deflection curve at point 5
b) Load versus mid span deflection for FCS6
0
10
20
30
40
50
60
0 10 20
0
10
20
30
40
50
60
0 10 20 30
0
10
20
30
40
50
60
0 10 20
50
4.2.2.3 Ferro-cement slab 7
Load-deflection curve at point 1 Load-deflection curve at point 2
Load-deflection curve at point 3 Load-deflection curve at point 4
0
10
20
30
40
50
60
70
0 20 40
0
10
20
30
40
50
60
70
0 20 40
0
10
20
30
40
50
60
70
0 10 20
0
10
20
30
40
50
60
70
0 20 40
51
Load-deflection curve at point 5
c) Load versus mid span deflection for FCS7
4.2.2.4 Ferro-cement slab 8
Load-deflection curve at point 1 Load-deflection curve at point 2
0
10
20
30
40
50
60
70
0 10 20
0
10
20
30
40
50
60
70
0 10 20 300
10
20
30
40
50
60
70
0 10 20 30
52
Load-deflection curve at point 3 Load-deflection curve at point 4
Load-deflection curve at point 5
d) Load versus mid span deflection for FCS8
0
10
20
30
40
50
60
70
0 10 200
10
20
30
40
50
60
70
0 20 40
0
10
20
30
40
50
60
70
0 10 20
53
4.2.2.5 Ferro-cement slab 9
Load-deflection curve at point 1 Load-deflection curve at point 2
Load-deflection curve at point 3 Load-deflection curve at point 4
0
10
20
30
40
50
60
70
80
0 10 20 30
0
10
20
30
40
50
60
70
80
0 10 20 30
0
10
20
30
40
50
60
70
80
0 10 20 300
10
20
30
40
50
60
70
80
0 10 20 30 40
54
Load-deflection curve at point 5
e) Load versus mid span deflection for FCS9
Figure 4-5 Load versus mid span deflection for Group 2 specimens
a) Large deflection at the middle of the beam
0
10
20
30
40
50
60
70
80
0 10 20 30
55
b) Large deflection at the middle of the beam
Figure 4-6 Large deflection at the middle of the beam
Figure 4-7 Transverse and longitudinal cracks
56
4.2.3 Strain analysis
Graphs of load (KN) against strain at critical cross-section of the composite slabs
for all CFS-Ferro-cement composite slab specimens are given in Figure 4.8. In this
analysis, a critical cross-section is defined as the cross-section that has the earliest
yielding of the CFS beam, as the yielding represents the attainment of the rectangular
stress block. In, all beams, the critical cross-section was found at mid-span of the
beams.
Based on the graphs of load against strain at the critical cross-section for all CFS
beams, it can be seen that the highest tensile strain was measured at the mid of the
lower flange of CFS sections. The yielding of the CFS was caused by average load as
shown in Table 4.1 that gave strain reading which was placed at the lower flange of
CFS. The values of strain at ultimate load are tabulated in Table 4.2.
Group
no. Slab no.
Ultimate strain at mid span of CFS sections (10^-6)
Point 3 Point 4 Point 5
1
FCS1 515 918 515
FCS2 805 1208 837
FCS3 773 1240 725
FCS4 1014 1530 998
2
FCS5 644 1127 644
FCS6 564 966 515
FCS7 821 1304 885
FCS8 644 1079 676
FCS9 950 1610 982
Table 4-2 the values of strain at ultimate load for all CFS sections
57
4.2.3.1 Ferro-cement slab 1
Load strain curve at point 3 Load strain curve at point 4
Load strain curve at point 5
a) Load versus mid span strain for FCS1
0
10
20
30
40
50
60
0 500 1000
Strain
0
10
20
30
40
50
60
0 500 1000
0
10
20
30
40
50
60
0 200 400 600
58
4.2.3.2 Ferro-cement slab 2
Load strain curve at point 3 Load strain curve at point 4
Load strain curve at point 5
b) Load versus mid span strain for FCS2
0
10
20
30
40
50
60
0 500 1000
0
10
20
30
40
50
60
0 1000 2000
0
10
20
30
40
50
60
0 500 1000
59
4.2.3.3 Ferro-cement slab 3
Load strain curve at point 3 Load strain curve at point 4
Load strain curve at point 5
c) Load versus mid span strain for FCS3
0
5
10
15
20
25
30
35
40
45
50
0 500 1000
0
5
10
15
20
25
30
35
40
45
50
0 1000 2000
0
5
10
15
20
25
30
35
40
45
50
0 500 1000
60
4.2.3.4 Ferro-cement slab 4
Load strain curve at point 3 Load strain curve at point 4
Load strain curve at point 5
d) Load versus mid span strain for FCS4
0
10
20
30
40
50
60
70
80
0 1000 20000
10
20
30
40
50
60
70
80
0 1000 2000
0
10
20
30
40
50
60
70
80
0 1000 2000
61
4.2.3.5 Ferro-cement slab 5
Load strain curve at point 3 Load strain curve at point 4
Load strain curve at point 5
e) Load versus mid span strain for FCS5
0
10
20
30
40
50
60
0 200 400 600 8000
10
20
30
40
50
60
0 500 1000 1500
0
10
20
30
40
50
60
0 200 400 600 800
62
4.2.3.6 Ferro-cement slab 6
Load strain curve at point 3 Load strain curve at point 4
Load strain curve at point 5
f) Load versus mid span strain for FCS6
0
10
20
30
40
50
60
0 200 400 6000
10
20
30
40
50
60
0 500 1000 1500
0
10
20
30
40
50
60
0 200 400 600
63
4.2.3.7 Ferro-cement slab 7
Load strain curve at point 3 Load strain curve at point 4
Load strain curve at point 5
g) Load versus mid span strain for FCS7
0
10
20
30
40
50
60
70
0 500 10000
10
20
30
40
50
60
70
0 500 1000 1500
0
10
20
30
40
50
60
70
0 500 1000
64
4.2.3.8 Ferro-cement slab 8
Load strain curve at point 3 Load strain curve at point 4
Load strain curve at point 5
h) Load versus mid span strain for FCS8
0
10
20
30
40
50
60
70
0 500 10000
10
20
30
40
50
60
70
0 1000 2000
0
10
20
30
40
50
60
70
0 500 1000
65
4.2.3.9 Ferro-cement slab 9
Load strain curve at point 3 Load strain curve at point 4
Load strain curve at point 5
i) Load versus mid span strain for FCS9
Figure 4-8 load against strain at critical cross-section of the composite slabs for all CFS-
Ferro-cement composite slab specimens
0
10
20
30
40
50
60
70
80
0 500 1000
0
10
20
30
40
50
60
70
80
0 500 1000 1500 2000
0
10
20
30
40
50
60
70
80
0 500 1000 1500
66
4.3 Parameters Studied
4.3.1 Effect of Increasing the Slab Thickness
The thickness of the Ferro-cement slab is one of the variable parameters considered
in this full scale experimental program. Figure 4.9 and Figure 4.10 shows the mid span
deflection curves for the Ferro-cement slab and CFS beams in partially composite CFS
Ferro-cement slabs. It is noted that increasing the Ferro-cement slab thickness has not
significantly increased the maximum mid span deflection values.
Figure 4.11 and figure 4.12 shows the mid span load-deflection curves for the
Ferro-cement slab and CFS beams in fully composite CFS Ferro-cement slabs. It is
noted that increasing the Ferro-cement slab thickness has not significantly increased the
maximum mid span deflection values.
Table 4.3 shows the mid span ultimate strain values for CFS beams in both cases
partially and fully composite CFS Ferro-cement slab. It is noted that as the Ferro-
cement slab thickness has increased, the mid span strain has decreased due to reduction
in tensile stresses at the bottom flange of CFS section.
Figure 4-9 mid span load-deflection curves of Ferro-cement slab for partially composite
specimens
0
10
20
30
40
50
60
0 5 10 15 20
FC5
FC6
FC1
FC2
FC3
67
a) mid span load-deflection curves of right edge CFS beam
b) mid span load-deflection curves of middle CFS beam
0
10
20
30
40
50
60
0 5 10 15 20
FC5
FC6
FC1
FC2
FC3
0
10
20
30
40
50
60
0 5 10 15 20 25
FC5
FC6
FC1
FC2
FC3
68
c) mid span load-deflection curves of left edge CFS beam
Figure 4-10 mid span load-deflection curves of CFS beams for partially composite
specimens
Figure 4-11 mid span load-deflection curves of Ferro-cement slab for fully composite
specimens
0
10
20
30
40
50
60
0 5 10 15 20
FC5
FC6
FC1
FC2
FC3
0
10
20
30
40
50
60
70
80
0 5 10 15 20 25
FC4
FC7
FC8
FC9
69
a) mid span load-deflection curves of right edge CFS beam
b) mid span load-deflection curves of middle CFS beam
0
10
20
30
40
50
60
70
80
0 5 10 15 20 25
FC4
FC7
FC8
FC9
0
10
20
30
40
50
60
70
80
0 5 10 15 20 25 30 35
FC4
FC7
FC8
FC9
70
c) mid span load-deflection curves of left edge CFS beam
Figure 4-12 mid span load-deflection curves of CFS beams for fully composite specimens
Є reduction
%
Ultimate Strain at right edge beam,
Є (10^-6)
Type of CFS Ferro-
cement slab
Group
no.
- 676 Partially composite 1
17% 579.5 Partially composite 2
- 998 Fully composite 1
20% 829 Fully composite 2
Є reduction
%
Ultimate Strain at middle beam, Є
(10^-6)
Type of CFS Ferro-
cement slab
Group
no.
- 1079 Partially composite 1
3% 1046.5 Partially composite 2
- 1530 Fully composite 1
5% 1457 Fully composite 2
Є reduction
%
Ultimate Strain at left edge beam, Є
(10^-6)
Type of CFS Ferro-
cement slab
Group
no.
- 660 Partially composite 1
10% 604 Partially composite 2
- 1014 Fully composite 1
15% 885.5 Fully composite 2
Table 4-3 the mid span ultimate strain values for CFS beams
0
10
20
30
40
50
60
70
80
0 5 10 15 20 25
FC4
FC7
FC8
FC9
71
4.3.2 Effect of increasing the number of Bolts Connecting the Ferro-
cement slab with the CFS-Section
The number of bolts connecting the Ferro-cement slab with CFS section is one of
the variable parameters considered in this full scale experimental program. Table 4.4
indicates that using spacing between bolts (150 mm) has increased the capacity load of the
fully composite section by almost one third the capacity load of the partially composite
section. This is due to an increase in the number of bolts connecting Ferro-cement slab with
CFS section while the Ferro-cement section is the same area.
Table 4.5 shows the maximum mid span deflections for Ferro-cement slab and CFS
beams in both cases partially and fully composite CFS Ferro-cement slab. It is noted
that as the number of bolts has increased in CFS Ferro-cement slab, the mid span
deflection has also increased.
Table 4.6 shows the ultimate mid span strain values for CFS beams in both cases
partially and fully composite CFS Ferro-cement slab. It is noted that as the number of
bolts has increased in CFS Ferro-cement slab, the mid span strain has also increased.
Pu increment % Ultimate Load, Pu, KN Type of CFS Ferro-cement slab Group no.
- 50 Partially composite 1
36% 68 Fully composite
- 52 Partially composite 2
30% 67 Fully composite
Table 4-4 the ultimate loads of tested specimens
72
δ increment % Maximum Deflection at right edge
beam, δ, mm
Type of CFS Ferro-
cement slab Group no.
- 16.45 Partially composite 1
17% 19.2 Fully composite
- 17.1 Partially composite 2
17.50% 20.1 Fully composite
δ increment % Maximum Deflection at middle beam,
δ, mm
Type of CFS Ferro-
cement slab
Group
no.
- 20.4 Partially composite 1
47.00% 30 Fully composite
- 20.45 Partially composite 2
48% 30.25 Fully composite
δ increment % Maximum Deflection at left edge beam,
δ, mm
Type of CFS Ferro-
cement slab
Group
no.
- 16.15 Partially composite 1
17% 18.9 Fully composite
- 17.25 Partially composite 2
16.50% 20.1 Fully composite
δ increment % Maximum Deflection at Ferro-
cement slab, δ, mm
Type of CFS Ferro-
cement slab
Group
no.
- 17.55 Partially composite 1
25.00% 21.95 Fully composite
- 17.78 Partially composite 2
26% 22.35 Fully composite
Table 4-5 the mid span deflections for CFS beams and Ferro-cement slab
73
Є increment % Ultimate Strain at right edge beam,
Є (10^-6)
Type of CFS Ferro-
cement slab
Group
no.
- 676 Partially composite 1
48% 998 Fully composite
- 579.5 Partially composite 2
43% 829 Fully composite
Є increment %
Ultimate Strain at middle beam, Є
(10^-6)
Type of CFS Ferro-
cement slab
Group
no.
- 1079 Partially composite 1
42% 1530 Fully composite
- 1046.5 Partially composite 2
39% 1457 Fully composite
Є increment %
Ultimate Strain at left edge beam, Є
(10^-6)
Type of CFS Ferro-
cement slab
Group
no.
- 660 Partially composite 1
54% 1014 Fully composite
- 604 Partially composite 2
47% 885.5 Fully composite
Table 4-6 the mid span strain values for CFS beams
74
Chapter Five: Conclusions and Recommendations
5.1 Strength and Stiffness of Composite Slabs
The results of experimental tests on nine full-scale composite slab
specimens were presented and discussed in Chapter 4. All full-scale specimens
were continuously supported slabs with an effective length of 2100 mm. CFS
lipped C-section and Profiled Ferro-cement slab of (30-40) mm thickness and
1200 mm effective width were incorporated. The main variables considered in
the study are the thickness of Ferro-cement slab and the number of bolts
connecting Ferro-cement slab with CFS section. Based on the test results and
observations, it was conducted to a meet the objectives of the thesis as listed in
Chapter 1 earlier. The following conclusions can be made:
1. The proposed Ferro-cement slabs with the proposed shear connector
provided sufficient restrain to the flange of CFS beam and eliminate its
local buckling problem.
2. For all specimens, Most of the cracks were first developed
longitudinally parallel to the beam due to shear flow between the Ferro-
cement and steel section. The cracks developed transversely at the
middle cross section of the span as large deformation of the specimens
occurred.
3. In all specimens, the mode of failure was due to a sudden
local/distortional buckling of CFS beam.
4. As the number of bolts connecting the CFS section with Ferro-cement
slab has increased, the mid span deflection for Ferro-cement slab and
CFS sections has also increased.
5. The effect of increasing the thickness of Ferro-cement slab has not
significantly increased the load capacity of the composite slab. However,
the increase in slab thickness has delayed the formation of cracks at an
early stage.
6. As the thickness of Ferro-cement slab has increased, the mid span strain
for CFS sections has decreased due to reduction in tensile stresses at the
bottom flange of CFS section.
75
7. As the number of bolts connecting the CFS section with Ferro-cement
slab has increased, the mid span strain for CFS sections has also
increased.
8. Using spacing between bolts (150 mm) has increased the capacity load of
the fully composite section by almost one third the capacity load of the
partially composite section.
5.2 Recommendations
This study has showed very promising results in terms of strength, stiffness and
structural behavior. Therefore, the following suggestions and recommendations for
future investigations and development are drawn:
1. This work investigated the effects of two variables on the composite action
between profiled Ferro-cement slab and steel beam. Therefore, other
parameters could be considered in future work. For example, different CFS
sections (different web depth and flange width), different grade and type of
mortar. In addition, the thickness of CFS section and the number of layers
of wire mesh in Ferro-cement slab can be investigated.
2. Other types of shear connector may be investigated.
3. A study is needed on the behavior of CFS-Ferro-cement composite beam-
column connections. For a continuous composite construction, it is very
important to develop an understanding at the beam-column connection.
76
References
ACI Committee 549R (1997). State-of-the-Art Report on Ferrocement, Manual of
Concrete Practice, ACI, Farmington Hills, Michigan ACI 549R-97.
Ahmed, S.F.U. and Nimityogsku,l P. (1998). Improvement of Punching Shear
Resistance in Ferrocement Slabs. Journal of Ferrocement, 28(4): 325-336.
Al-Kubaisy, M.A. and Nedwell, P.J. (1999). Behavior and Strength of Ferrocement
Rectangular Beams in Shear. Journal of Ferrocement. 29(1): 1-16.
Al-Noury, S.I and Haq S. (1988). Ferrocement in Axial Tension. Journal of
Ferrocement, 18(2): 111-137.
Al-Rifai, W.N. and Al-Shukur, A.H.K. (2001). Effects of Wetting and Drying
Cycles in Fresh Water on the Flexural Strength of Ferrocement. Journal of
Ferrocement. 31(2): 101-108.
Al-Rifaie, W.N. and Joma'ah, M.M. (2010). Structural Behaviour of Ferrocement
System. Diyala Journal of Engineering Sciences, first Engineering Scientific
Conference, College of Engineering-University of Diyala, pp. 237-248.
Al-Sulaimani, G.J and Basunbal, I.A. (1991). Behaviour of Ferrocement under
Direct Shear. Journal of Ferrocement, 21(2): 109-117.
Arif, M., Akhtar S., Masood, A., Basi, F. and Garg, M. (2001). Flexural Behaviour
of Fly Ash Mortar Ferrocement Panels for Low Cost Housing. Journal of Ferrocement,
31(2): 125-135.
Arif, M., Pamkaj and Kuasik, S.K. (1999). Mechanical Behavior of Ferrocement
Composites: An Experimental Investigation. Cement and Concrete Composites, 21(4):
301-312.
Bhatacharyya, P., Tan, K.H. and Mansur, M.A. (2003). Flexural Moment Capacity
of Ferrocement Hollow Sandwich Panel System. Journal of Ferrocement. 33(3): 183-
189.
Cheng, Y. and Benjamm, W.S.( 2003) “Local buckling test on cold-formed steel
beam,” Journal of Structural Engineering, vol. 129(12), pp. 1596–1606.
77
Chu, X.T., Ye, Z.M., Kettle, R. and Li, L.Y. (2005). Buckling behavior of cold-
formed channel sections under uniformly distributed loads. Thin-Walled Structures,
43(4): 531-542.
Deierlein, G.G. (1988). Design of Moment Connections for Composite Framed
Structures. Ph.D. Thesis, Phil M. Ferguson Structural Engineering Laboratory,
University of Texas at Austin, Austin, Texas.
Dundu, M. and Kemp, A.R. (2005). Strength requirements of single cold-formed
channels connected back-to-back. Journal of Constructional Steel Research, 62(3): 250-
261.
Fox, D. M., R. M. Schuster and M. Strickland. (2008)."Innovative Composite Cold
Formed Steel Floor System." Nineteenth International Specialty Conference on Cold-
Formed Steel Structures, St. Louis, MO.
Hancock, G.J. (2003). Cold-formed steel structures. Journal of Constructional Steel
Research.
Hancock, G.J., Murray, T.M. and Ellifritt, D.S. (2001). Cold-Formed Steel
structures to the AISI specification. USA: Marcel Dekker.
Hawalder, M.N.A, Mansur, M.A. and Rahman, M. (1990). Thermal Behaviour of
Ferrocement. Journal of Ferrocement, 20(3): 231-239.
Hossainan, M.Z. and Inoue (2000). A Comparison of the Mechanical Properties of
Ferrocement Elements under Compression for Square and Chicken Meshes. Journal of
Ferrocement. 30(4): 319-343.
Hsu, H.L. and Chi, P.S. (2003). Flexural performance of symmetrical cold-formed
thin walled members under monotonic and cyclic loading. Thin-walled structures,
41(1): 47-67.
Ibrahim, H.M. (2011). Experimental investigation of ultimate capacity of wired
mesh-reinforced cementitious slabs. Construction and Building Materials, 25(1): 251-
259.
Kandaswamy,S.and Ramachandraiah, A. (2002). Sound Transmission Performance
on Ferrocement Panels. Journal of Ferrocement, 32(1): 59-67.
78
Kumar, A. (2005). Ferrocement box sections-viable option for floors and roof of
multi-storey buildings. Asian Journal of Civil Engineering (Building and Housing),
6(6): 569–582.
Lakkavalli, B.S. and Liu, Y. (2006). Experimental study of composite cold-formed
steel C-section floor joists. Journal of Constructional Steel Research, 62(10): 995-1006.
Lawson, R.M., Popo-Ola, S.O. and Varley, D.N. (2001). Innovative development
of light steel composites in buildings. In: Eligehausen, R. (ed.) International
Symposium on Connections between Steel and Concrete. Stuttgart, Germany RILEM
Publications SARL.
Liborio,J.B.L. and Hanai, J.B. (1992). Ferro-ement Durability: Some
Recommendations for Design and Production, Journal of Ferrocement. 22(3): 265-271.
M.jamal Shannag and Tareq Bin Ziyyad (2007). Flexural response of ferrocement
with fibrous cementitious matrices. Consruction and Building Materials, 21(6): 1198-
1205.
Mansur, M.A. and Ong, K.G.C. (1987). Shear Strength of Ferrocement Beams.
ACI Structural Journal. 84(1): 10-17.
Mansur, M.A. and Paramasivam, P. (1986). Cracking Behaviour and Ultimate
Strength of Ferrocement in Flexure. Journal of Ferrocement, 16 (4): 405-415.
Mansur, M.A., Ahmed, I. and Paramasivam, P. (2001). Punching Shear Strength of
Simply Supported Ferrocement Slabs. ASCE Journal of Materials in Civil Engineering,
13(6): 418-426.
Mansur, M.A. and. Kiritharan, T. (2001). Shear Strength of Ferrocement Structural
Sections, Journal of Ferrocement, 31(3): 195-211.
Mansur, M.A., Paramasivam, P., Wee, T.H. and Lim, H.B. (1996). Durability of
Ferrocement-a Case Study. Journal of Ferrocement, 26(1): 11-19.
Methews, M.S., Sudhakumar, J. and Thomas, A.V. (1992). Behaviour of
Ferrocement Roofing Panels under Periodic Heat Flow Conditions. Journal of
Ferrocement. 22(2): 125-133.
79
Montesinos, G.P. and Naaman, A.E. (2004). Parametric Evaluation of the Bending
Response of Ferrocement and Hybrid Composites with FRP Reinforcements. Journal of
Ferrocement. 34(2): 341-352.
Naaman, A.E. (2000). Ferrocement and Laminated Cementitious Composites. Ann
Arbor, Michigan, USA: Techno Press.
Onet, T., Magureanu, C. and Vescan, V. (1992). Aspects Concerning the Behavior
of Ferrocement in Flexure, Journal of Ferrocement, 22 (1): 1-9.
Parmasivam, P. and Tan, K.H. (1993). Punching Shear Strength of Ferrocement
Slabs. ACI Structural Journal, 90(3): 294-301.
Randhir J. Phalke and Darshan G. Gaidhankar (2014). Flexural behavior of
ferrocement slab panels using welded square mesh by incorporating steel fibers.
International Journal of Emerging Trends in Engineering and Development, 3(5): 756-
763.
Rao, P.K. (1992). Stress-Strain Behavior of Ferrocement Elements under
Compression. Journal of Ferrocement, 22(4): 343-352.
Rhodes, J. (1991). Design of CFS members. Elsevier Applied Science Publisher.
S. Deepa Shri and R. Thenmozhi (2012). Flexural behavior of hybrid ferrocement
slabs with micro-concrete and fibers. International Journal of Emerging Trends in
Engineering and Development, 4(2): 165-177.
Sabnis, G.M. (1979). Handbook of Composite Construction Engineering. Van
Nostrand Reinhold Company, New York.
Salimullah, M. (1994). Ferrocement Roofing Elements: The Solution of the Middle
and Low Income Housing-The Bangladesh Experience. Journal of Ferrocement. 24(1):
51-56.
Shaari, S.N. and Ismail E. (2003). Promoting the use of industrialised building
systems and modular coordination in the Malaysia construction industry. Board of
Engineer Malaysia. Bulletin ingénieur.
Somayaji, S. and Naaman, A.E. (1981). Stress-Strain Response and Cracking of
Ferrocement in Tension. Journal of Ferrocement, 11(2): 127-142.
80
Stone, T.A. and LaBoube, R.A. (2005) “Behavior of CFS built-up I-sections,”
Thin-Walled Structures, vol. 43, pp. 1805 – 1817.
Suksawang, N., Nassif, H.H. and Sanders, M. (2006). Analysis of Ferrocement-
Laminated Concrete Beams. Proceedings of Eight International Symposium and
Workshop on Ferrocement and Thin Reinforced cement Composites. 06 08 February,
Bangkok Thailand, IFS, 141-150.
Swamy, R.N. and Shaheen, Y.B.I. (1990). Tensile Behaviour of Thin Ferrocement
Plates. Proceedings of Thin-Section Fiber Reinforced Concrete and Ferrocement, USA.
American Concrete Institute, Detroit, MI.
M. Alhajri, M. M Tahrir, M. Azimi and J. Mirza (2016). Behavior of pre-cast u-
shaped composite beam integrating cold-formed steel with ferrocement slab. Thin
Walled Structures, 102: 18-29.
Viest, I.M., Colaco, J.P., Furlong, R.W., Griffis, L.G., Leon, R.T. and Wyllie, L.A.
Jr. (1997). Composite Construction: Design for Buildings. McGraw-Hill,
NewYork. W.W. Yu, CFS Design. 3rd Edition. USA: John Wiley & Sons, 2001
Wafa, M.A. and Fukuzawa, K. (2010). Characteristics of ferrocement thin
composite elements using various reinforcement meshes in flexure. Journal of
Reinforced Plastics and Composites.
Wang, S., Naaman, A.E. and Li, V.C. (2004). Bending response of hybrid
ferrocement plates with meshes and fibers. Journal of Ferrocement: Vol, 34 (1).
Xiong, J.G. and Singh, G. (1997). Review of the fatigue Behaviour of Ferrocement
in a Corrosive Environment, Journal of Ferrocement. 27(1): 7-18.
Yu, C. and Schafer, B.W. (2003). Local buckling tests on cold-formed steel beams.
Journal of structural engineering, 129(12): 1596-1606.
Yu, W.K., Chung, K.F. and Wong, M.F. (2005). Analysis of bolted moment
connections in cold-formed steel beam–column sub-frames. Journal of Constructional
Steel Research, 61(9): 1332-1352.
الملخص
ستقصاء السلوك الانشائى للبلاطات المستمرة المركبة من الفيروسيمنت حيث ان إيهدف البحث الى
ربطة قص. وقد أالبلاطات ترتكز على كمرات من الحديد المشكل على البارد متصله فيما بينها ب
ستغلال التاثيرالمركب بين القطاعات المشكله على البارد وبلاطات صمم هذا النظام لإ
ربطة القص. تعتبر القطاعات المشكلة أالفيروسيمنت كى تنتقل قوة القص فيما بينهم عن طريق
ستدامه عند نشائى هام فى الدول الناميه ومن مواد التشييد التى تتسم بالإإعلى البارد عنصر
على الرغم من المميزات السالف نيه والتجاريه منخفضة الارتفاع.ستخدامها فى المبانى السكإ
ذكرها إلا انه لا يوجد بيانات كافيه عن الأداء والسلوك الخاص بالقطاعات المشكله على البارد عند
إستخدامها فى الإنشاءات المركبه. بالإضافة الى ما سبق تعتبر بلاطات الفيروسيمنت منخفضة
وبناءً على ما سبق تم إستحداث .ن سريعة التشرخ نظراً لسماكتها الصغيرهالجساءة وبالتالى تكو
concrete deckنظام بلاطات من قطاعات من الحديد المشكل على البارد ليكون بديلاً عن "
systemويقوم هذا ." عند تنفيذه فى اسقف واسطح المبانى السكنيه والتجاريه منخفضة الارتفاع
ستخدام خلطه اسمنتيه مكونة من رمل واسمنت ومسلحه بشبكة معدنية النظام المستحدث على إ
ويعتمد هذا البحث على التجارب العمليه لعدد تسع نماذج بالأبعاد الحقيقيه لإختبار .خفيفة الوزن
النظام السابق من حيث سمك البلاطه الامثل والمسافات بين المسامير مع استخدام نوع موحد من
أربطة القص وشبكة معدنية واحدة لتسليح البلاطه.
زكريا تونسىادهم السيد 20/7/1991
مصري1/3/0142 / /8201
ماجستير العلوم هندسة إنشائية
أ.د. متولى ابو حمد
أ.د. سامح يوسف محفوظ
:مهندس تاريخ الميلاد:
الجنسية: تاريخ التسجيل:
تاريخ المنح: الدرجة: القسم:
المشرفون:
:الممتحنون
:الرسالة عنواند الحدي ات منلبلاطات الادوار المركبة من الفيروسيمنت مع كمرالسلوك الانحنائى المشكل على البارد
ة:الدال الكلمات شبك سلك بلاطات فيروسيمنت, رباط قص, قطاع من الحديد المشكل على البارد و
ت المركبة من الفيروسيمنت مع كمرا لبلاطاتلالانحنائى السلوك
من الحديد المشكل على البارد
إعداد ادهم السيد زكريا تونسى
جامعة القاهرة -الهندسة كلية إلى مقدمة رسالة
ماجستير العلوم كجزء من متطلبات الحصول علي درجة
في
الهندسة الإنشائية
يعتمد من لجنة الممتحنين:
أ.د.
أ.د.
أ.د.
ت المركبة من الفيروسيمنت مع كمرا لبلاطاتلالانحنائى السلوك
من الحديد المشكل على البارد
إعداد ادهم السيد زكريا تونسى
جامعة القاهرة -الهندسة كلية إلى مقدمة رسالة
ماجستير العلوم كجزء من متطلبات الحصول علي درجة
في
الهندسة الإنشائية
تحت إشراف
سامح يوسف محفوظ /الدكتور الأستاذأستاذ مساعد فى المنشات المعدنية
رئيس قسم هندسة التشييد والبناءالاكاديمية العربية للعلوم والتكنولوجيا والنقل
البحرى
متولى ابو حمد /الدكتور الأستاذ أستاذ فى المنشات المعدنية والكبارى
الهندسة الإنشائيةقسم جامعة القاهرة
جامعة القاهرة –كلية الهندسة
جمهورية مصر العربية –الجيزة 2018
ت المركبة من الفيروسيمنت مع كمرا بلاطاتلالانحنائى ل السلوك
من الحديد المشكل على البارد
إعداد ادهم السيد زكريا تونسى
جامعة القاهرة -الهندسة كلية إلى مقدمة رسالة
ماجستير العلوم كجزء من متطلبات الحصول علي درجة
في
الهندسة الإنشائية
جامعة القاهرة –كلية الهندسة
جمهورية مصر العربية –الجيزة
2018