Beginning of an era of remote I/O solutions in India Messung Systems is certified for ISO 9001:2000 (Standard for Quality Management System) ISO 9001 : 2000 Certificate:04100 20047173-E3 TM A U T O M AT I O N P E O P L E Remote I/Os

Beginning of an era of remote I/O solutions in India · Beginning of an era of remote I/O solutions in India ... 1 A, Relay Output, 24 VDC/ 110 VAC/ 220 VAC Potential free Contact

Embed Size (px)

Citation preview

Beginning of an era of remote I/O solutions in India

Messung Systems is certified for ISO 9001:2000(Standard for Quality Management System)

ISO 9001 : 2000

Certificate:04100 20047173-E3

TM

A U T O M A T I O N P E O P L E

R e m o t e I / O s

Smart AccessoriesEasy Mounting Efficient I/O Wiring Arm

Same as 20 terminals size.No change required in junction box design.

Compact

Base Unit + 3 expansion units. Each unit handles64 I/O points per remote node

16 I/O points

Expansion2 Expansion3Expansion1BaseNode ID n

64 I/O Points Per Node

Afte

r

Remote I/O System

CP-5232-BO

Standard Features:

Built in CANopen Master Functionality via CANopen Interface Port

High Speed Processing

- Bit/ Byte/ Word Execution - 0.6 to 0.8 µs

2 K Inputs & 2 K Output Points (Local + RiX)

Diagnostics Status LEDs on NG523X CPU:

- Common Error Indication (I/O error)

- Application Interlocking on error via System Variables

Modbus RTU Protocol (Master/ Slave) on serial ports

Huge Memory

- 324 KB Application Program (Flash) - 1 MB Source Code (Flash)

- 32 KB Marker (Battery Back-up) - 64 KB Data (Battery Back-up)

- 64 KB File Marker (Battery Back-up)

Easy I/O Configuration through CoDeSys Programming Software

Master CPU CP 523X Series

PLC System

Messung Systems:Your Partner In Technological Excellence

At a Glance

Standard 5-pinNetwork Connector

Simple Rotary Switches for Node ID Settings

Onboard I/O Status LED Indications

Onboard Network Status LED Indications

I/O connection LabelAvailable for guidance

Easy Push Type Terminal

DIN Mounting Clip

Test Point forMultimeter

I/O Cable Connection1 sq.mm

Remote I/O System

For Your Automation Needs

Presenting

Promoted by international organization

CAN technology is based on International Standard

ISO 11898

Most secured control network:

- Self reliant, error detection & self correction

- Undetected network error possibility 1 in a 1000 yrs

Carrier Sense Multiple Access Non Destructive Arbitration

(CSMA-NDA) Technology

- Offers maximum thoroughput

- Best Real time response even at a lower baud rate

Powerful network diagnostics:

- Node failure detection

- Missing node detection

- Supports hot replacement

Very robust EMC behaviour

Lower cost of networking, simple two shielded

twisted cable

CANopen Features

Centralised I/O System

Cluttered Machine Wiring

Complex Panel Wiring

Befo

re

Limitations BenefitsReducedMachineWiring

ReducedNo. of Joints

IncreasesReliability

MinimumPanelSpace

Required

LowersInstallation &

CommissioningCosts

ReducedMaintenance

Time

In an industrial scenario, sensors & actuators are key elements embedded in the machine & process control. These sensors &

actuators are generally spread over a distance. Discrete wiring to each of these devices has always been cumbersome, time

consuming & error prone. Remote I/Os connected on the field bus are designed as an intelligent alternative. They are placed near

these field elements & are wired locally.

Messung Systems introduces RiX series Remote I/O units based on highly reliable CANopen field bus technology. RiX Remote I/O

units are designed to be mounted near these field elements (e.g. in junction boxes & in push button panels) for individual I/O

connections. Further RiX units are connected to the master CPU using a two shielded twisted pair network cable.

What is Remote I/O?

ClutteredMachineWiring

HighMaintenance

Time

HighInstallation &

CommissioningCosts

ExcessPanelSpace

Required

AdditionalJoints

ReduceReliability

RiX FRC 6940/6941cable betweenbase / expansionunit

T Junction 6930 - for connecting eachdevice on a trunk line with drop lines

RiX I/OWiring Arm 6920

UnplugMounting Clip

Panel Mount clips areplugged on the bottom sidewhen the product is delivered.

2 or 3 wire sensors can be connecteddirectly. Sink/Source selectable input.

Input Signal

24 V DC

0 V DC

ProxySwitch

Cross

Horizontal

Powerpacked Features

· Auto Network Baud Rate Detected by RiX Base

Units

· Programmable Pulse Catch

· Data Transmission on I/O Status Change to

Reduce Network Traffic

· Replacement of the Faulty Unit Without

Disturbing the Live Network

· I/O Error Indication on CPU if Expansion Unit

Gets Disconnected

· Diagnostics Status LEDs on Each module:

- Status of Base Unit

- Status of Expansion Module

Highlighting Features

R e m o t e I / O s

Messung Systems is the pioneer of indigenous PLC technology and has given the world many new-age automation products. The

backbone of Messung Systems is its R & D division that is fiercely dedicated to creating automation products that can completely

transform factory working.

Today Messung Systems boasts of 35,000 successful PLC installations in diverse industries like automobile, pharmaceutical, plastic,

textile, printing and food processing. With an enviable turnover and a string of delighted customers behind it, Messung Systems is

moving ahead, creating landmark products in automaton.

RiX CANopen Remote I/O Solutions: A new era begins...

Salient Features

Network upto 31 NodesMaximum Network Length 500 mtrsCANopen Master CPU (CP 523X) sets Baudrate for Total Network

Replacement of the Faulty Unit without Disturbing the LiveNetworkI/O Error Indication on CPU if Expansion Unit gets Disconnected

01. Automotive / Automobile

- SPM (Special Purpose Machine)

- Production Control System

- Material Handling System - Conveyor

- ANDON Display System on Assembly Line

- Electroplating Plant - POWER RAIL

or MONORAIL

- Ultrasonic Cleaning System

- Press

- Transfer Line

- Intelligent Hydraulic & Pneumatics Panel

- Production Monitoring

02. Process

04. HVAC - Aircon

05. Utility Sector

- Water Treatment Plant- Asbestos Sheet Making Plant

- Climate Control- AC Automation

- Fire Control at Power Stations- Lift / Escalator - Residential or Commercial- Furnace / Boiler

03. Intelligent MCC Panel

06. Food & Beverage

07. Supervisory system for DG set/Furnace/Boiler/ Compressor etc.

- Filling & Bottling Line- Biscuit Mfg. Line- Ovens for Bread making Machine- Edible Oil Processing Plant

Vast Application Areas

Baudra

tein

Kbps

Distance in Mtrs.

Distance V/s Baudrate

25 100 250 500

125

250

500

1,000

Network upto 31 nodes

Expansion3

Node ID 2

Node ID 31

Base Expansion1 Expansion2 Expansion3

Expansion2Expansion1Base

4110 4632 4632 4532

CA

NO

pen

Netw

ork

4110

4632

4632

4532

Node ID 2

Node ID 3

RiX Expansion

Node ID 31

CANopen Master PLC SystemCP523X Series

CoDeSys Software

TerminatingResistor

TerminatingResistor

RiX Base

RiX Expansion

RiX Base

RiX Expansion

RiX Base

RiX Base

+24 VDCNetwork Power Supply

IBM PCCompatible

RiX Expansion

RiX Expansion

24 V Power SupplyTrunk Line Drop Line Expansion CableFRC T Junction

+24 VDCNetwork Power Supply

Node ID 4

Typical Remote I/O Scheme

Configuration Elements

���

System with CP 523X Series CPU

RiX Remote I/O Units

Network Power Supplies of Suitable

Current Rating

����

Network Cable - Two shielded Twisted Pair

Terminating Resistor

T - Junction

CoDeSys Software

Technical Specifications

CANopen Slave,RiX Remote I/O Units

Ordering Code Item Description

CP 5230-B0 Basic CPU with 1 PG Port, 1 CANopen Port

CP 5231-B0 Basic CPU with 1 PG Port,1 CANopen Port & 1 Auxiliary Port

CP 5232-B0 Basic CPU with 1 PG Port,1 CANopen Port & 2 Auxiliary Ports

CP 5232-P4 CPU with 2 HSC + 2 PTO, 1 PG Port,1 CANopen Port & 2 Auxiliary Ports

4110 Power Supply - Input: 220 VAC

4112 Power Supply - Input: 24 VDC

4113 Power Supply - Input: 90 - 260 VAC,Output: 24 VDC, 0.4 A

5900 Basic Plate without I/O

4930 Basic Plate with 3 I/O

4932 Basic Plate with 5 I/O

4906 Basic Plate with 8 I/O

*For more details please refer to the installation manual

PWR

RUN ERR

STS 0 1 2 3 4 5 6 7

10 11 12 13 14 1715 16

Base Unit : 16pt. 24 VDC InputC6616

Node Idx10 x1

Inputs

Inputs

140

5046

50

54

Ordering Code Item Description

C6616 RiX CANopen Base Unit 16 Point, 24 VDC sink/source Input

C6709 Base Unit 8 Point,1 A, Relay Output, 24 VDC/ 110 VAC/ 220 VAC Potential free Contact Type

C6710 Base Unit 8 Point, 24 VDC Source, 1.5 A Output

C6716 Base Unit 16 Point, 24 VDC Source, 250 mA Output

C6418 Base Unit 8 Point, 24 VDC sink/source Input + 8 Point,24 VDC Source, 250 mA Output

C6417 Base Unit 8 Point, 24 VDC sink/source Input + 6 Point,500 mA, Relay Output, 24 VDC/ 110 VAC/ 220 VAC

X6616 Expansion Unit - 16 Point, 24 VDC sink/source Input

X6609 Expansion Unit - 8 Point, 110 / 220 VAC Input

X6709 Expansion Unit - 8 Point,

X6710 Expansion Unit 8 Point, 24 VDC Source, 1.5 A Output

X6716 Expansion Unit 16 Point, 24 VDC, Source, 250 mA Output

X6418 Expansion Unit 8 Point, 24 VDC sink/source Input + 8 Point,24 VDC Source, 250 mA Output

X6417 Expansion Unit 8 Point, 24 VDC sink/source Input + 6 Point,500 mA, Relay Output, 24 VDC/ 110 VAC/ 220 VAC

C6609 RiX CANopen Base Unit 8 Point, 110 VAC/ 220 VAC Input

RiX CANopen

RiX CANopen

RiX CANopen

RiX CANopen

RiX CANopen

VAC

1 A, Relay Output, 24 VDC/ 110 VAC/ 220 VAC Potential free Contact Type

Note : All Dimensions are in mm

CANopen Master,Nexgen 5000 PLC System

Dimensional Details

17

RiX Analog Input-Output UnitsConnectivity to Nexgen-2000 PLCsRiX Key Panel

Coming Prospects

MESSUNG AREA OFFICES

NEW DELHI

MESSUNG SYSTEMSTEL:+91(011)29216128 /

29226129FAX:+91(011)29226730

BARODA

MESSUNG SYSTEMSTEL:+91(0265)2314669 /

2358137FAX:+91(0265)2333307

PUNE

MESSUNG SYSTEMS91(020)27102172

FAX:+91(020)27102173

TEL:+

HYDERABAD

MESSUNG SYSTEMSTEL:+91(040)27722519 /

27720308FAX:+91(040)27722519

BANGALORE

MESSUNG SYSTEMSTEL:+91(080)25092119FAX:+91(080)25320480

MUMBAI

MESSUNG SYSTEMSTEL:+91(022)26674308 /

56949564FAX:+91(022)26674309

AREA DISTRIBUTORS

CHENNAI

C/MOS PROCESSORS91(044)26287653 /

26217942FAX:+91(044)26217943

TEL:+

KOLKATA

TTS SYSTEMATIX PVT. LTD91(033)24635645

FAX:+91(033)24635646

TEL:+

BANGALORE

LEONARDO AUTOMATION(080)23283030

FAX:+91(080)23282613

TEL:+91

ww

w.inte

ricsdesig

ns.c

om

EL-2, J BLOCK, M.I.D.C. BHOSARI,PUNE - 411 026. INDIATEL : +91(020)27102000 / 27102125FAX : +91(020)27102130email : [email protected] : www.messungautomation.com

MESSUNG SYSTEMSMANUFACTURER OF PLCs & HMIs

TM

CANopen Network Max 31 Nodes (Up to 500 mtrs)

Max. Units per Node 1 Base + 3 Expansion Units

Operating Temperature 0 to 55 C

Relative Humidity 5 to 90% Non Condensing

Noise Immunity2 KV Conductive on NetworkPower Supply1 KV Capacitiveon Network Cable

Shock IEC61131-2 Operating:15g (DIN rail & Panel Mounting)

Vibration IEC61131-2 Operating:5 to 150 Hz, 1g, 3.5mm Amplitude

Mounting DIN rail or Panel Mount

Protection IP 20

I/O Connections 20-pin 5.00 mm Pitch Push TypeFixed Terminal Block

I/O Wire Size Recommended RiX Input Wiring: 0.5 sq. mm per i/pRIX Output Wiring: 0.75 sq. mm per o/p

Network Connections 5-pin 5.08 mm Pitch Screw TypeOpen Style Connector

Network Cable R LAPP Cable LI2YCY 2 x 2 x 0.22for Network upto 100 mtrsLeoni / Belden / Helukabel ThickCAN Cable for Network Above 100 mtrs

Unit Power Supply 11 to 30 VDC Through 5-pinNetwork Connector

Network Power Supply 24 VDC, 5 A*

Power Supply Protection Reverse Polarity

Dimensions (Base / 140 mm 54 mm 46 mm (W H D)

Baud Rate Auto Baud Detection(10, 20, 50, 125, 250, 500, 1000 Kbps)

CANopen Version CIA Standard DS 301 Version 4.02

°

Operations IEC 1000-4-4

ecommended

x x x xExpansion Unit)

RiX Spares & Accessories

6929 RiX Spare Part - RiX 5 Pin Connector, for Network Connection

6920 RiX Accessory - RiX I/O Wiring Arm, 20 Pin Terminals (Push Type)

6121 RIO Network Cable 4 Core Shielded, (LAPP Make)Li2YCy(TP) 2 x 2 x 0.22 Unitronic

6930 RiX T - Junction for Easy Multidrop Connections

6931 RiX Power Junction for Easy Power

6940 RiX Spare Part - RiX Cable Between Base/ Expansion & Expansion,FRC Type, L = 70 mm

6941 RiX Spare Part - RiX Cable Between Base/ Expansion & Expansion,FRC Type, L = 350 mm

Connections

16