WIRING DIAGRAMS B.E.G. L LUXOMAT ® Schematics for electricians and consultants Awiring diagrams for outdoor and ceiling-mounted motion detectors 2 Wiring diagrams for wall-mounted motion detectors 3 Wiring diagrams for outdoor, wall and ceiling-mounted motion detectors 4 - 5 Wiring diagrams for Master 1-channel ceiling-mounted occupancy detectors 6 - 7 Wiring diagrams for Master 2-channel and 3-channel wall and ceiling-moun- ted occupancy detectors 8 Wiring diagrams for Master DIM 1-channel and 2-channel ceiling- mounted occupancy detectors 9 Wiring diagrams for MASTER DIM 3-channel ceiling-mounted occupancy detectors 10 Wiring diagrams for Master DALI ceiling-mounted occupancy detectors 11 - 12 Wiring diagrams for 24V ceiling- mounted occupancy detectors 13 Wiring diagrams for 24V wall-mounted occupancy detectors 14 Wiring diagrams for outdoor lamps and floodlights 15 - 16 Wiring diagrams for photo electric switches 17 Index Page

B.E.G.LUXOMATluxomat.com/en/pdf/en/Schaltbild_GB.pdf · 2013-08-27 · Standard mode with Master 3-channel TRIO occupancy detectors ... wiring diagrams for master dim 1-channel and

  • Upload
    vodat

  • View
    216

  • Download
    0

Embed Size (px)

Citation preview

wir

ing

dia

gra

ms

B.E.G. LUXOMAT®

LUXOMAT® Schematics forelectricians and consultants

Awiring diagrams for outdoor and ceiling-mounted motion detectors 2

Wiring diagrams for wall-mounted motion detectors

3

Wiring diagrams for outdoor, wall and ceiling-mounted motion detectors

4 - 5

Wiring diagrams for Master 1-channel ceiling-mounted occupancy detectors

6 - 7

Wiring diagrams for Master 2-channel and 3-channel wall and ceiling-moun-ted occupancy detectors

8

Wiring diagrams for Master DIM 1-channel and 2-channel ceiling- mounted occupancy detectors

9

Wiring diagrams for MASTER DIM 3-channel ceiling-mounted occupancy detectors

10

Wiring diagrams for Master DALI ceiling-mounted occupancy detectors

11 - 12

Wiring diagrams for 24V ceiling- mounted occupancy detectors

13

Wiring diagrams for 24V wall-mounted occupancy detectors

14

Wiring diagrams for outdoor lamps and floodlights

15 - 16

Wiring diagrams for photo electric switches

17

Index Page

B.E.G. LUXOMAT®

2

wir

ing

dia

gra

ms

wiring diagrams for outdoor and ceiling-mounted motion detectors

Standard mode with 1-channel motion detector with permanent light function

Standard mode with 1-channel motion detector

Standard mode with 1-channel motion detector with NC pushbutton

Wiring diagram for• RC-plusnext• LC-plus• LC-Click-N• LC-Mini

• PD3N-1C• PD4N-1C• PD9-1C

• HF-MD1• HF-H-MD1Standard

optional:S1=switchforpermanentlightRC=RC-suppressionkitifrequired

Wiring diagram for• RC-plusnext• LC-plus• LC-Click-N• LC-Mini

• PD3N-1C• PD4N-1C

• PD9-1C• HF-MD1• HF-H-MD1Standard

Wiring diagram for• RC-plusnext• LC-plus• LC-Click-N• LC-Mini

• PD3N-1C• PD4N-1C• PD9-1C

T1 = nC buttonManualswitchingadditionallypossible(pressopenerapprox.2 sec.).Thepositionofthepotentiometersshouldnotbeon“test”or“sun”.Ifso,thepre-settimeandsafetyvaluesgetlost.

LN

L΄́́́LNC1

E1 S1

LN

L΄́́́LNC1

E1

LN

L΄́́́LNC1

E1T1

B.E.G. LUXOMAT®

3

wir

ing

dia

gra

ms

wiring diagrams for wall-mounted motion detectors

Standard mode with 1-channel motion detector

Parallel connection with 1-channel motion detectors

Parallel connection with 1-channel motion detectors

Wiring diagram for• Indoor180-R

optional:S1=switchforpermanentlightT1=NObutton,manualswitching

additionallypossibleRC=RC-suppressionkitifrequired

Wiring diagram for• RC-plusnext max.5parallel• LC-plus max.5parallel• LC-Click-N max.2parallel• LC-Mini max.2parallel

• PD3N-1C max.8parallel• PD4N-1C max.8parallel• PD9-1C max.8parallel

Wiring diagram for• Indoor180-Rmax.8parallel

optionalT1=NObutton,manualswitching

additionallypossible

LN

L΄́́́LNC1

E1 S1

R

T1

LN

L΄́́́LNC1

E1

L΄́́́LNC1

LN

L΄́́́LNC1

E1

L΄́́́LNC1

R R

T1

B.E.G. LUXOMAT®

4

wir

ing

dia

gra

ms

wiring diagrams for outdoor, wall and ceiling-mounted motion detectors

Standard mode with 1-channel motion detector (e.g. stairs)

Standard mode with 1-channel motion detector (e.g. stairs)

Wiring diagram for• RC-plusnext• LC-plus• LC-Click-N• LC-Mini

• PD3N-1C• PD4N-1C• PD9-1C

Wiring diagram for• Indoor180-SC+SCT1max.10Indoor-SC

LN

L΄́́́LNC1

E1

LN

34

T1 T230 sec. 10min.

LN

L΄́́́LC1

E1

L΄́́́LC1

LN

34

30sec. 10min.

B.E.G. LUXOMAT®

5

wir

ing

dia

gra

ms

wiring diagrams for outdoor, wall and ceiling-mounted motion detectors

Standard mode with 2-channel motion detector

Standard mode with 2-wire technology, triac

Standard mode with 2-wire technology, relay

Wiring diagram for• PD3N-2C

M1=HVACfunction

Wiring diagram for• Indoor180-T

optionalS1=switchforpermanentlight

Wiring diagram for• Indoor180-R/2W-UK• Indoor180-R-2D

optionalS1=switchforpermanentlight

LN

NOL΄́́́LNC1

NOC2

E1 M1

LN

L΄́́́LC1

E1 S1

LN

L΄́́́LC1

E1 S1

B.E.G. LUXOMAT®

6

wir

ing

dia

gra

ms

wiring diagrams for master 1-channel ceiling-mounted occupancy detectors

Standard mode with Master 1-channel occupancy detectors with R terminal

Wiring diagram for• PD5-M-1C

optionalT1=NObuttonforsemi-automaticmodeSlaveforenlargementofdetectionarea

LN

L΄́́́LNC1

N LRR

T1 E1

Standard mode with Master 1-channel occupancy detectors with R and S terminal

Wiring diagram for• PD9-M-1C

optionalT1=NObuttonforsemi-automaticmodeSlaveforenlargementofdetectionarea

LN

L΄́́́LNC1

N LRS

T1 E1

R

Standard mode with Master 1-channel occupancy detectors (NO)

Wiring diagram for• PD9-M-1C-SDB

B.E.G. LUXOMAT®

7

wir

ing

dia

gra

ms

wiring diagrams for master 1-channel ceiling-mounted occupancy detectors

Standard mode with Master 1-channel occupancy detectors PS with R and S terminal

Wiring diagram for• PD4-M-1C-C-PS

optionalT1=NObuttonforsemi-automaticmodeSlaveforenlargementofdetectionarea

Standard mode with Master 1-channel occupancy detectors (NO) with R and S terminal

Wiring diagram for• PD2-M-1C• PD4-M-1C

optionalT1=NObuttonforsemi-automaticmodeSlaveforenlargementofdetectionarea

B.E.G. LUXOMAT®

8

wir

ing

dia

gra

ms

wiring diagrams for master 2-channel and 3-channel wall and ceiling-mounted occupancy detectors

Standard mode with Master 2-channel occupancy detectors

Wiring diagram for• PD1N-M-2C• PD2-M-2C• PD4-M-2C

• Indoor180-M-2C

M1=HVACfunction

optionalT1=NObuttonforsemi-automaticmodeSlaveforenlargementofdetectionarea

LN

NOL΄́́́LNC1

N LRR NOC2

T1 E1 M1

Standard mode with Master 2-channel DUO occupancy detectors

Wiring diagram for• PD4-M-2C-DUO

optionalT1&2=NObuttonforsemi-automatic

modeSlaveforenlargementofdetectionarea

LN

NOL΄́́́LNC1

N LRSC1

RNOC2

SC2

T2T1 E1 E2

Standard mode with Master 3-channel TRIO occupancy detectors

Wiring diagram for• PD4-M-3C-TRIO

optionalT1&2=NObuttonforsemi-

automaticmodeSlaveforenlargementofdetectionarea

LN

NOL΄́́́LNC1

N LRSC1/2

NO RNOC2

NOC3

SC3

T2T1 E1 E2 E3

B.E.G. LUXOMAT®

9

wir

ing

dia

gra

ms

wiring diagrams for master dim 1-channel and 2-channel ceiling-mounted occupancy detectors

Standard mode with Master DIM occupancy detectors

Wiring diagram for• PD1N-M-DIM• PD2-M-DIM• PD4-M-DIM• PD5-M-DIM• PD9-M-DIM

LN

E1 110 V EB

NL+

RS L L΄́́́N + N LR

T1

C1

Standard mode with Master DUO DIM occupancy detectors

Wiring diagram for• PD4-M-

DUO-DIM

LN

E1 110 V EB

NL+

E2 110 V EB

NL+

RS L L΄́́́N + + N LR

T1

C1 C2

optionalT1=NObuttonforsemi-automaticmodeSlaveforenlargementofdetectionarea

B.E.G. LUXOMAT®

10

wir

ing

dia

gra

ms

wiring diagrams for master dim 3-channel ceiling-mounted occupancy detectors

Standard mode with Master TRIO DIM occupancy detectors

Wiring diagram for• PD4-M-

TRIO-DIM

LN

E1 110 V

NL+

E2 110 V

NL+

RS L L΄́́́N + + N LRSC3 C1/2C1 C2C1/2

NO NOC3

E3T1 T2

optionalT1&2=NObuttonforsemi-automaticmodeSlaveforenlargementofdetectionarea

B.E.G. LUXOMAT®

11

wir

ing

dia

gra

ms

wiring diagrams for master dali ceiling-mounted occupancy detectors

Standard mode with Master DALI occupancy detectors

Standard mode with Master DUO DALI occupancy detectors

Wiring diagram for• PD2-M-DALI/DSI• PD4-M-DALI/DSI• PD9-M-DALI/DSI

Wiring diagram for• PD4-M-

DUO-DALI

optionalT1=NObuttonforsemi-automaticmodeSlaveforenlargementofdetectionarea

B.E.G. LUXOMAT®

12

wir

ing

dia

gra

ms

wiring diagrams for master dali ceiling-mounted occupancy detectors

Standard mode with Master TRIO DALI occupancy detectors

Wiring diagram for• PD4-M-

TRIO-DALI

optionalT1&2=NObuttonforsemi-automaticmodeSlaveforenlargementofdetectionarea

B.E.G. LUXOMAT®

13

wir

ing

dia

gra

ms

wiring diagrams for 24V ceiling-mounted occupancy detectors

Standard mode with Master 2-channel 24V occupancy detectors

Standard mode with Master 2-channel 24V occupancy detectors with reed relay

Wiring diagram for• PD2-M-2C-24V-3A• PD2-M-2C-24V-RR

Wiring diagram for• PD2-M-2C-24V-RR

X1=lightsensor

~/+

NOR~/~/+ ~/+

NOC1

T1

NONOC2

~/

24V24V NOR~/~/+ ~/+

NOC1

NONOC2

24V24V

24V AC/DC

X2

X1 1k 15M

optionalT1=NObuttonforsemi-automaticmodeSlaveforenlargementofdetectionarea

B.E.G. LUXOMAT®wiring diagrams for 24V wall-mounted occupancy detectorsw

irin

g d

iag

ram

s

14

Standard mode with 1-channel 24V occupancy detectors

Wiring diagram for• Indoor180-R-24V-3A• Indoor180-R-24V-RR

optionalT1=NObuttonforsemi-automaticmode

Standard mode with 1-channel 24V occupancy detectors with reed relay

Wiring diagram for• Indoor180-R-24V-RR

optionalT1=NObuttonforsemi-automaticmodeSlaveforenlargementofdetectionarea

B.E.G. LUXOMAT®

15

wir

ing

dia

gra

ms

wiring diagrams for outdoor lamps and floodlights

Standard mode with 1-channel motion detector

Standard mode with 1-channel motion detector external

Wiring diagram for• HF-L1

• MD10• LT130

• EcolightAutomatic• FLC150• FLC500

Wiring diagram for• HF-L7• HF-L8• HF-L11• HF-L12

• AL1• AL4• AL21• AL20-CdS• ALC-ELU/D• AL20-280-BM• AL20-280-BM-LED• ALC-B-360• ALC-B-360-DECO• AL2-RC-plus-130/230/280

• FLC-280-LED• FL2-LED-230• AL5-RC-plusnext• AL5-LC

S1=switchforpermanentlight

HF-L1

HF-L7

HF-L8

MD10

LT130

Ecolight Automatic

FLC150

FLC500

Übersicht

LN

LN

AL20-CdS

ALC-ELU/D

AL20-280-BM

AL20-280-BM-LED

ALC-B-360

ALC-B-360-DECO

AL2-RC-plus-130/230/280

FLC-280-LED

FL2-LED-230

AL5-RC-plus next

AL5-LC

AL1

AL4

Übersicht

LN

L´LNC1

E1 S1

B.E.G. LUXOMAT®

16

wir

ing

dia

gra

ms

wiring diagrams for outdoor lamps and floodlights

Standard mode with 1-channel motion detector with NC pushbutton

Standard mode with 1-channel motion detector

Wiring diagram for• AL1• AL21• AL20-280-BM• AL20-280-BM-LED• ALC-B-360• ALC-B-360-DECO• AL2-RC-plus-130/230/280

• FLC-280-LED• FL2-LED-230• AL5-RC-plusnext• AL5-LC

T1 = nC buttonManualswitchingadditionallypossible(pressopenerapprox.2 sec.).Thepositionofthepotentiometersshouldnotbeon“test”or“sun”.Ifso,thepre-settimeandsafetyvaluesgetlost.

Wiring diagram for• AL1• AL21• AL20-CdS• ALC-ELU/D• AL20-280-BM• AL20-280-BM-LED• ALC-B-360• ALC-B-360-DECO• AL2-RC-plus-130/230/280

• FLC-280-LED• FL2-LED-230• AL5-RC-plusnext• AL5-LC

• max.5parallel

AL20-280-BM

AL20-280-BM-LED

ALC-B-360

ALC-B-360-DECO

AL2-RC-plus-130/230/280

FLC-280-LED

FL2-LED-230

AL5-RC-plus next

AL5-LC

AL1

Übersicht

LN

L´LNC1

E1T1

AL20-CdS

ALC-ELU/D

AL20-280-BM

AL20-280-BM-LED

ALC-B-360

ALC-B-360-DECO

AL2-RC-plus-130/230/280

FLC-280-LED

FL2-LED-230

AL5-RC-plus next

AL5-LC

AL1

max. 5 paralell

Übersicht

LN

L´LNC1

E1

L´LNC1

B.E.G. LUXOMAT®

17

wir

ing

dia

gra

ms

wiring diagrams for photo electric switches

Standard mode with 1-channel photo electric switch

Standard mode with 1-channel photo electric switch

Wiring diagram for• CdS-SM• CdS-T-SM• CdS-FC

S1=switchforpermanentlight

Wiring diagram for• TS-DD

Übersicht

LN

L´LNC1

E1 S1

max 100m 1,5mm²

Übersicht

LN

E165

34

Lux1

2

max. 100 m 1.5 mm2