Basic Understanding on Current Transformer

Embed Size (px)

Citation preview

  • 8/4/2019 Basic Understanding on Current Transformer

    1/29

    CURRENT TRANSFORMER

  • 8/4/2019 Basic Understanding on Current Transformer

    2/29

    CURRENT TRANSFORMER

    Definitions

    A device used to step down current from high value (primary current)to a low value (secondary current).

    Low value current is easy to measure, no need to develop highcurrent measuring equipment.

    The current ratio (primary current/secondary current) is substantiallyconstant for a given range of primary current.

    The phase angle error (secondary current compared to primarycurrent) is within specified limit.

  • 8/4/2019 Basic Understanding on Current Transformer

    3/29

    Function

    1. ProtectionCurrent transformer connected to protection equipment(protection relay). The protection relay can be set to identifywhether the input current (current transformers secondarycurrent) indicate that fault occur in the system.

    2. MeasurementCurrent transformer connected to measurement equipment(ammeter, energy meter). Measure the current flow in the circuit.

    CURRENT TRANSFORMER

  • 8/4/2019 Basic Understanding on Current Transformer

    4/29

    Construction Type

    1. Ring or WindowThe popular type is ring shape, rectangular shape and ovalshape.

    CURRENT TRANSFORMER

  • 8/4/2019 Basic Understanding on Current Transformer

    5/29

    Construction Type

    2. Split CoreThe shape similar to ring or window construction, the core aresplit into two part.

    CURRENT TRANSFORMER

  • 8/4/2019 Basic Understanding on Current Transformer

    6/29

    Construction Type

    3. Primary Wound (Block)For low current rating. both primary and secondary are Woundover the core.

    CURRENT TRANSFORMER

  • 8/4/2019 Basic Understanding on Current Transformer

    7/29

    Schematic Diagram

    1. Single Ratio

    CURRENT TRANSFORMER

  • 8/4/2019 Basic Understanding on Current Transformer

    8/29

    CURRENT TRANSFORMER

    Schematic Diagram

    2. Double RatioTransformer with an intermediate tapping on secondary winding.(terminal S1, S2 & S3) Ratio of tapping as per designrequirement. During service, unused tapping remain open.

  • 8/4/2019 Basic Understanding on Current Transformer

    9/29

    CURRENT TRANSFORMER

    Schematic Diagram

    3. Multi Ratio

  • 8/4/2019 Basic Understanding on Current Transformer

    10/29

    CURRENT TRANSFORMER

    Location In The Single Line Diagram

  • 8/4/2019 Basic Understanding on Current Transformer

    11/29

    Connection to Measurement or Protection Devices

    Measurement or protective devices are load to the currenttransformer. The circuit connection shall be in series.

    Current transformer not connected to the load when installed to theswitchgear shall be shorted to ground (secondary terminal connectedto ground).

    Open circuit is a condition when the current transformer is not

    connected to its load. Open circuit during availability of primarycurrent will result of high voltage appear at the secondary terminal(>1kV A.C).

    CURRENT TRANSFORMER

  • 8/4/2019 Basic Understanding on Current Transformer

    12/29

    CURRENT TRANSFORMER

    Connection to Measurement or Protection Devices

  • 8/4/2019 Basic Understanding on Current Transformer

    13/29

    Typical Current Transformer Description

    3000/1A - Current RatioCL.: 0.2 - Accuracy Class15VA - Rated Burden

    3000/1A - Current RatioCL.: 5P20 - Accuracy Class & Accuracy Limit Factor30VA - Rated Burden

    3000/1A - Current RatioCL.: X - Accuracy ClassVkp: 300V - Knee Point VoltageRct: 12 - Burden (Resistance)

    CURRENT TRANSFORMER

  • 8/4/2019 Basic Understanding on Current Transformer

    14/29

    Term & Definitions

    Rated Primary CurrentThe value of primary current which specified by manufacturer (shallbe based on customer/purchaser requirements). E.g. 3000A, 1600A,450A, etc.

    Secondary CurrentThe value of secondary current which specified by manufacturer (hasbeen standardized). E.g. 1A or 5a.

    Current RatioThe ratio of Rated Primary Current to Rated Secondary Current. E.g.3000/1A, 1600/5A. etc.

    CURRENT TRANSFORMER

  • 8/4/2019 Basic Understanding on Current Transformer

    15/29

    Term & Definitions

    Rated BurdenThe burden assigned by manufacturer at which the currenttransformer performs with specified accuracy expressed in VA.Connected burden shall be less than specified rated burden.

    BurdenTotal load connected across the secondary of current transformerexpressed in VA or at rated secondary current.

    Accuracy ClassThe class assigned to the current transformer with the specifiedlimits of ratio error and phase angle error. Accuracy class specifiesby BS & IEC standard. E.g. X, 5P, 10P, 0.2, 0.5, 1,etc.Class X, 5P, 10P for protection. Class 0.2, 0.5 for measurement.

    CURRENT TRANSFORMER

  • 8/4/2019 Basic Understanding on Current Transformer

    16/29

    Term & Definitions

    Accuracy Class

    CURRENT TRANSFORMER

  • 8/4/2019 Basic Understanding on Current Transformer

    17/29

    Term & Definitions

    Accuracy Limit FactorE.g. 10, 20.

    Knee Point VoltageThe point at which C.T is saturate where 10% increase in voltagecauses a 50% increase in magnetizing current.

    CURRENT TRANSFORMER

  • 8/4/2019 Basic Understanding on Current Transformer

    18/29

    Testing

    Polarity TestTo prove that a group of C.Ts has been manufactured and installedwith the correct polarity.

    CURRENT TRANSFORMER

  • 8/4/2019 Basic Understanding on Current Transformer

    19/29

    Testing

    Magnetization CurveTo determine the secondary voltage and current at which the C.Tmagnetic core begin to saturate. The Result should be compared tomanufacturers curve.

    The point at which saturation is deemed to become significant isknown as Knee Point Voltage, where 10% increase in voltagecauses a 50% increase in magnetizing current.

    CURRENT TRANSFORMER

  • 8/4/2019 Basic Understanding on Current Transformer

    20/29

    Testing

    Magnetization Curve

    CURRENT TRANSFORMER

  • 8/4/2019 Basic Understanding on Current Transformer

    21/29

    CURRENT TRANSFORMER

    Testing

    Magnetization Curve

  • 8/4/2019 Basic Understanding on Current Transformer

    22/29

    CURRENT TRANSFORMER

    Testing

  • 8/4/2019 Basic Understanding on Current Transformer

    23/29

    Testing

    Burden CheckMeasurement of secondary resistance at terminal SI-S2 with anohmmeter. The value shall be as manufacturer specification.

    Insulation Resistance TestCarried out when the wiring between C.T and the connectedequipment completed. To measure the C.T insulation resistance. Thevalue shall be as manufacturer specification.

    Primary InjectionShould be carried out when the wiring is completed. To enablemeasurements to be made of the secondary quantities as verificationof the correct installation of the C.T, the connected wiring andequipment.

    CURRENT TRANSFORMER

  • 8/4/2019 Basic Understanding on Current Transformer

    24/29

    Typical Installation Inside The Gas Insulated Switchgear

    CURRENT TRANSFORMER

  • 8/4/2019 Basic Understanding on Current Transformer

    25/29

    Typical Installation Inside The Gas Insulated Switchgear

    CURRENT TRANSFORMER

  • 8/4/2019 Basic Understanding on Current Transformer

    26/29

    CURRENT TRANSFORMER

    Typical C.T Construction

  • 8/4/2019 Basic Understanding on Current Transformer

    27/29

    Typical complete assembly

    C.T without outer protection

    CURRENT TRANSFORMER

    Typical C.T Construction

  • 8/4/2019 Basic Understanding on Current Transformer

    28/29

    Typical C.T Construction

    CURRENT TRANSFORMER

    http://en.wikipedia.org/wiki/Image:Leistungsschalter-110KV.jpg
  • 8/4/2019 Basic Understanding on Current Transformer

    29/29

    Typical C.T winding machine

    CURRENT TRANSFORMER