ETA ENGlhlEERIMG PRIVATE LIMITED 503-504, Prakash Deep Building, 7, Tolstoy Marg, New Delhi - 110001 Ph. : 01 1-26451115/6/7/8,43743800,41520840/43 Fax : 0 11-43743866,41520844 Email : [email protected] Ref: ETA/ICMLl9MWlBClSClKW078 Date: August 11, 2011 DGM-BUSINESS DEVELOPMENT (POWER) MIS CESC LIMITED CESC House Chowringhee Square Kolkata - 700001 West Bengal KIND ATTN: MR ADRlT PALCHOUDHURY SUB: ICML, 9MWp SOLAR POWER PROJECT AT PRATAPGARH, DIST. KUTCH, GUJARAT - SUBMISSION OF BASIC DESIGN FOR FIRE PROTECTION SYSTEM. Dear Sir, This is in reference to the subject project. We are pleased to attach herewith documents of Basic Design for Fire Protection System. We hope the above is in line with your requirements and would request you to kindly let us have your kind approval for the same to enable us to proceed further in the interest of the project. Thanking you and assuring you of our best services at all times. Yours faithfully, for ETA ENGINEERING PVT LTD. ,WAURABH CHAUHAN GENERAL MANAGER Encl: as above Regd. Office : 5, Moores Road, Chennai - 600 006 Tamil Nadu, India Branches (Tel.) - Bangalore : 41802300, Chennai : 28297626, Hyderabad : 27763529130, Mumbai : 67742700, Pune : 26051310, Kolkata : 24864329

Basic Design for Fire Protection System

Embed Size (px)

DESCRIPTION

Basic Design for FP system

Citation preview

Page 1: Basic Design for Fire Protection System

ETA ENGlhlEERIMG PRIVATE LIMITED 503-504, Prakash Deep Building, 7, Tolstoy Marg, New Delhi - 110001 Ph. : 01 1-26451115/6/7/8,43743800,41520840/43 Fax : 01 1-43743866,41520844 Email : [email protected]

Ref: ETA/ICMLl9MWlBClSClKW078 Date: August 11, 201 1

DGM-BUSINESS DEVELOPMENT (POWER) MIS CESC LIMITED CESC House Chowringhee Square Kolkata - 700001 West Bengal

KIND ATTN: MR ADRlT PALCHOUDHURY

SUB: ICML, 9MWp SOLAR POWER PROJECT AT PRATAPGARH, DIST. KUTCH, GUJARAT - SUBMISSION OF BASIC DESIGN FOR FIRE PROTECTION SYSTEM.

Dear Sir,

This is in reference to the subject project. We are pleased to attach herewith documents of Basic Design for Fire Protection System.

We hope the above is in line with your requirements and would request you to kindly let us have your kind approval for the same to enable us to proceed further in the interest of the project.

Thanking you and assuring you of our best services at all times.

Yours faithfully, for ETA ENGINEERING PVT LTD.

,WAURABH CHAUHAN GENERAL MANAGER

Encl: as above

Regd. Office : 5, Moores Road, Chennai - 600 006 Tamil Nadu, India

Branches (Tel.) - Bangalore : 41802300, Chennai : 28297626, Hyderabad : 27763529130, Mumbai : 67742700, Pune : 26051310, Kolkata : 24864329

Page 2: Basic Design for Fire Protection System

SUBMISSION TRANSMITTAL FORM

m e - 1 n w . t c r w ~ c - , I C?r*a~ ICI vrs l r ly -

~A.,..*u <.'I

Prepared By

Gaurav

Details

Approved By

PROJECT : 9MWp GRID INTERACTIVE SOLAR PV POWER PROJECT

CUSTOMER : INTEGRATED COAL MINING LIMITED - GUJARAT

CONTRACTOR : ETA ENGINEERING PVT LTD

Submission Phase:

I DRAWINGS I DOCUMENT

VENDOR & TECHNICAL SUBMITTAL

CONSTRUCTION DOCUMENTS

REPORTS

RECORDS

Submission Number: I First Second Third Fourth

Submission Contents.

Checked By

Saurabh Tripathi

Name

Sr.No. 1.

Reviewed By

Kapil

For Information W For Approval As Built

ETA:

ICML: j

DOCUMENT TRAIVSMZTTAL. REF. DOC

ETA-SOLAR-TRANS-46 ..

System Description FIRE PROTECTION

SYSTEM

Description of the Document BASIC DESIGN- SYSTEM 6 FIRE

PROTECTION SYSTEM

Approved By

f S a u r q h Chauhan u

Designation

Rev No 00

Sign

Page 3: Basic Design for Fire Protection System

FIRE PROTECTION SYSTEM

PURPOSE:

An automatic fire alarm system is designed to detect the unwanted presence offire by

monitoring environmental changes associated with combustion. In general, a fire alarm system is

classified as either automatically actuated, manually actuated, or both. Automatic fire alarm

systems are intended to notify the building occupants to evacuate in the event of a fire or other

emergency, report the event to an off-premises location in order to summon emergency services,

and to prepare the structure and associated systems to control the spread of fire and smoke.

DESTGN:

After the fire protection goals are established - usually by referencing the minimum levels of

protection mandated by the appropriate model building code, insurance agencies, and other

authorities - the fire alarm designer undertakes to detail specific components, arrangements, and

interfaces necessary to accomplish these goals. Equipment specifically manufactured for tl~ese

purposes are selected and standardized installation methods are anticipated during the design

Fundamental Configuration

a) Initiating Devices

Manually actuated devices; Break glass stations, Buttons and manual fire alarm

activation are constructed to be readily located (near the exits), identified, and operated.

Automatically actuated devices can take many forms intended to respond to any number

of detectable physical changes associated with fire: convicted thermal energy; heat

detector, products of combustion; smoke detector, radiant energy; flame detector,

combustion gasses; carbon monoxide detector and release of extinguishing agents; water-

flow detector. The newest innovations can use cameras and computer algorithms to

analyze the visible effects of fire and movement in applications inappropriate for or

hostile to other detection methods.

b) Notification Appliances

Audible, visible, tactile, textual or even olfactory stimuli (odorizer) to alert the occupants

Evacuation signals may consist of audible or visible appliances with a distinct audible

tone or speakers to deliver live or pre-recorded instructions to the occupants.

Page 4: Basic Design for Fire Protection System

FIRE PROTECTION SYSTEM FOR 9 MWp GRID INTERACTIVE SOLAR PV PLANT

a) In each of the nine PCU rooms there is one number of optical smoke detector to detect the presence of any fire condition and flasher are installed outside the PCU room which will indicates the fire condition in their respective PCU rooms. As PLC's are located in each of the PCU room so a smoke detector acts as digital input to that PLC and flasher outside the PCU room acts as a digital output to that PLC. In case of any fire condition i.e. smoke a digital input is received by plc which switches on the flasher outside the PCU room to indicate the emergency condition. Plc is mounted with acknowledgement button to acknowledge the fire condition.

b) Any fire condition inside the main control room is communicated through main PLC panel located in PCU room number five through seven detectors placed inside the Main Control Room.

c) Manual call points are installed outside each PCU room, three numbers in main control room at the exit and entrance, and one number inside the guard room to activate the alarm condition in case required.

d) Guard room is equipped with one PLC looped with main plc through a fiber optic cable and connected to an alarm annunciator panel inside the guard room to visualize the alarm condition in any of the PCU rooms and main control room.

e) Hooters are installed inside the guard room and are activated in case of any fire condition in any of the rooms.

f ) Any of the fire condition in the plant installed with detectors will be indicated in the SCADA.

g) The PLC's used for Fire Protection System and SCADA are same.

NOTE: Please refer to the system architecture of Fire Protection System.