56
Barrels & Exceptions in the Building & Fire Codes Scott Moore, Architect, NCARB with Colleen Moore, Interpreter Dalkita reserves all rights to the material presented. Recording and/or reproduction and display of this presentation without the express written consent of Dalkita Construction, Inc. is strictly prohibited.

Barrels Exceptions in the Building Fire Codes

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Barrels Exceptions in the Building Fire Codes

Barrels & Exceptionsin the Building & Fire Codes

Scott Moore, Architect, NCARBwith Colleen Moore, Interpreter

Dalkita reserves all rights to the material presented. Recording and/or reproduction and display of this presentation without the express written consent of Dalkita Construction, Inc. is strictly prohibited.

Page 2: Barrels Exceptions in the Building Fire Codes

Colleen Moore

Introductions

University of Florida – Journalism and Sports Management Reporting, graphic design, marketing, business management

Olympic Committee, NBA, IHL, Radio, Television, Commercial Real Estate Only 20 years of experience!

Dalkita reserves all rights to the material presented. Recording and/or reproduction and display of this presentation without the express written consent of Dalkita Construction, Inc. is strictly prohibited.

Page 3: Barrels Exceptions in the Building Fire Codes

Scott Moore

Introductions

Master of Architecture from the University of Illinois Urbana‐Champaign Nationally Certified Architect through NCARB Currently licensed in CO, KY, MA, MN, MO and UT

Over 25 years of experience in the design & building industry Over 10 years of experience in distillery design and construction

Over 15 years of experience as a general contractor, Class ‘A’ Supervisor

Dalkita reserves all rights to the material presented. Recording and/or reproduction and display of this presentation without the express written consent of Dalkita Construction, Inc. is strictly prohibited.

Page 4: Barrels Exceptions in the Building Fire Codes

A. Codes A (very) Brief HistoryB. Code HierarchyC. What do wooden cask or barrel 

exceptions actually mean?D. H‐3 Requirements 

‐ Basic & Barrel ExceptionsE. The Ventilation ExceptionF. Other Related Issues

‐ Specialty Codes‐ High Piled Storage‐New Threats to Cask Storage

Overview

* Fine print is often critical in understanding the meaning of Codes. This presentation is based on the 2015 ICC Codes and the 2015 NFPA.

Page 5: Barrels Exceptions in the Building Fire Codes

CODES: A BRIEF HISTORY

Page 6: Barrels Exceptions in the Building Fire Codes

So we're back to courting the Fire Marshall's approval. Local code allows massive amounts of bulk liquor to be stored in wooden casks at distilleries, or in individual glass containers at retail locations, but not in individual glass 

containers at distilleries.

We want our boys to be safe if they respond to a distillery fire, but the inconsistencies in the code are really frustrating.

Page 7: Barrels Exceptions in the Building Fire Codes

CODES: A ROADMAP

OR

Page 8: Barrels Exceptions in the Building Fire Codes

Abbrev. Short for This

AHJ Authority Having Jurisdiction (city, county, fire district)

ICC International Code Council

IBC International Building Code

IFC International Fire Code

IMC International Mechanical Code

NFPA National Fire Protection Association

CFM Cubic Foot per Minute

SF Square Foot or Square Feet

MAQ Maximum Allowable Quantity

LFL Lower Flammable Limit

CODES: THE LINGO (VOCAB)

Page 9: Barrels Exceptions in the Building Fire Codes

Term Means

Performance Language

Indicates an intended result and requires a design that performs to result in the code intention.

Prescriptive Language

giving exact rules, directions, or instructions about how you should do something

Commentary Not code but published to help determine the reasoning behind the rules.

CODES: THE LINGO (VOCAB)

Page 10: Barrels Exceptions in the Building Fire Codes

…but, barrels are exempt from all this… 

RIGHT?!

Page 11: Barrels Exceptions in the Building Fire Codes

When do the IFC Exceptions Apply to create Modified H‐3?

OVERVIEW: BARREL EXCEPTIONS

IBC IFC414.3 1 CFM/SFVentilation See IFC & IMC Barrel Exception

414.5.1 Explosion Control See IFC Barrel Exception

414.5.3 Spill Control See IFC Barrel Exception

414.5.3 Secondary Containment See IFC Barrel Exception

415.5 Emergency Alarm Same

415.4 Sprinklers Same

415.6 25% Ext.Wall Same

508.3.3 ex.1 Min. 1 hr. Separation Same

2015 ICC Code References

Page 12: Barrels Exceptions in the Building Fire Codes

SECTION 307 HIGH‐HAZARD GROUP HFLAMMABLE AND COMBUSTIBLE LIQUIDS

[F] 307.1 High‐hazard Group H. High‐hazard Group H occupancy includes, among others, the use of a building or structure, or a portion thereof, that involves the manufacturing, processing, generation or storage of materials that constitute a physical or health hazard in quantities in excess of those allowed in control areas complying with Section 414, based on the maximum allowable quantity limits for control areas set forth in Tables 307.1(1) and 307.1(2).

If quantities exceedMAQs, occupancy is H‐3 

for barrel storage.

WHAT IS H‐3?

Page 13: Barrels Exceptions in the Building Fire Codes

IBC 307.5

You are considered an H‐3 Occupancy if ANY of the following apply to Class 1, 2, or 3A flammable or combustible liquids :

Stored/used in normally closed containers or systems

Liquids are pressurized at < 15 PSI

Primary Added requirements of H‐3 Occupancy:

25% perimeter on exterior wall(if over 500 SF dispensing or  1000 SF Storage per 415.5 – exceptions #1 & 2)

Must be Sprinklered 

Spill Control

Secondary Containment

1 cfm/sf Continuous Ventilation & Mechanical Code w/ Uninterruptable Power Source (UPS)

Deflagration Control2012 Fire Code 911.3 refers to NFPA 69: “Explosion control by prevention.”Table 414.5.1 Footnote e Open Use and Dispensing Only

Emergency Alarms

Mandatory Minimum 1 hr Fire Separation from other Occupancies

WHAT DO I NEED FOR H‐3?

Page 14: Barrels Exceptions in the Building Fire Codes

BARRELS & MAQs

MATERIAL CLASSGROUP WHENMAX. 

ALLOW. QTY. EXCEEDED

STORAGE b USE‐CLOSED SYSTEMS b USE‐OPEN SYSTEMS b

SOLID POUNDS

(CUBIC FEET)LIQUID GALLONS

(POUNDS)

GAS(CUBIC FEET AT NTP)

SOLIDPOUNDS 

(CUBIC FEET(LIQUID GALLONS

(POUNDS)

GAS(CUBICFEET AT NTP)

SOLID POINDS(CUBIC FEET)

LIQUID GALLONS(POUNDS)

Combustible Dust

N/A H‐2 Note q N/A N/A Note q N/A N/A Note q N/A

Combustible Liquid c, i

23A3B

H‐2 or H‐3H‐2 or H‐3

N/AN/A

120 d,e

330 d,e

13,200 e,fN/A N/A

120d

330d

13,200fN/A N/A

30d

80d

3,300f

Flammable Liquid c

1A1B and 1C

H‐2or H‐3

N/A30 d,e

120 d,eN/A N/A

30d

120d N/A N/A10d

30d

Excerpted from TABLE 307.1 (1), 2015 International Building Code and TABLE 5003.1.1(1) in 2015 International Fire Code

“MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIALS POSING A PHYSICAL HAZARD”

c. “alcoholic beverages in retail and wholesale occupancies provided that the liquids are packaged in individual containers not exceeding 1.3 gallons.” 

d. “(MAQs)… increased 100 percent … with… automatic sprinkler system ... Where Note e also applies, the increase for both notes shall be applied accumulatively.”

e. “(MAQs) … increased 100 percent when stored in approved storage cabinets, day boxes, gas cabinets or exhausted enclosures or in listed safety cans… both notes shall be applied accumulatively.”

f. “The permitted quantities shall not be limited in a building equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1”

q. “…(Combustible Dust in 2012 code) … manufactured, generated in a manner that the concentration and conditions create a fire or explosion hazard…”

Page 15: Barrels Exceptions in the Building Fire Codes

Table 2‐1.1Flash and Fire Points of Alcohol‐Water Solutions (DISCUS)

Alcohol(Vol. %)

Tag Closed Cup Flash Point2

Tag Open Cup Flash Point3

Fire Point4

Class IB Liquids

95% 63˚F (17˚C) 70˚F (21˚C) 70˚F(21˚C)

90% 65˚F (18˚C) 72˚F (22˚C) 72˚F(22˚C)

80% 68˚F (20˚C) 76˚F (24˚C) 76˚F(24˚C)

70% 70˚F (21˚C) 80˚F (27˚C) 80˚F(27˚C)

60% 72˚F (22˚C) 86˚F (30˚C) 87˚F(30˚C)

Class IC Liquids (below 55%)

50% 75˚F (24˚C) 90˚F (32˚C) 94˚F(34˚C)

40% 79˚F (26˚C) 96˚F (36˚C) 102˚F(39˚C)

30% 85˚F (29˚C) 104˚F (40˚C) 113˚F(45˚C)

20% 97˚F (36˚C) 119˚F (48˚C) 136˚F(58˚C)

Non‐flammable liquid (below 20%)

10% 120˚F (49˚C) 150˚F (66˚C) ‐‐‐

FLAMMABLE LIQUID. A liquid having a closed cup flash point below 100˚F(38 ˚C). Flammable liquids are further categorized into a group known as Class 1liquids. The Class 1category is subdivided as follows:

Class 1A. Liquids having a flash point below 73˚F(23˚C) and a boiling point below 100 ˚ F(38˚C).

Class 1B. Liquids having a flash point below 73˚F(23˚C) and a boiling point at or above 100˚F(38˚C).

Class 1C. Liquids having a flash point at or above 73˚F(23˚C) and below 100˚F(38˚C).

WHAT’S IN THE BARRELS?

Page 16: Barrels Exceptions in the Building Fire Codes

BARRELS

MATERIAL CLASSGROUP WHENMAX. 

ALLOW. QTY. EXCEEDED

STORAGE b USE‐CLOSED SYSTEMS b USE‐OPEN SYSTEMS b

SOLID POUNDS

(CUBIC FEET)LIQUID GALLONS

(POUNDS)

GAS(CUBIC FEET AT NTP)

SOLIDPOUNDS 

(CUBIC FEET(LIQUID GALLONS

(POUNDS)

GAS(CUBICFEET AT NTP)

SOLID POINDS(CUBIC FEET)

LIQUID GALLONS(POUNDS)

Combustible Dust

N/A H‐2 Note q N/A N/A Note q N/A N/A Note q N/A

Combustible Liquid c, i

23A3B

H‐2 or H‐3H‐2 or H‐3

N/AN/A

120 d,e

330 d,e

13,200 e,fN/A N/A

120d

330d

13,200fN/A N/A

30d

80d

3,300f

Flammable Liquid c

1A1B and 1C

H‐2or H‐3

N/A30 d,e

120 d,eN/A N/A

30d

120d N/A N/A10d

30d

Excerpted from TABLE 307.1 (1), 2015 International Building Code and TABLE 5003.1.1(1) in 2015 International Fire Code

“MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIALS POSING A PHYSICAL HAZARD”

MAQs are 120/30(240/60 sprinkled)

d. “(MAQs)… increased 100 percent … with… automatic sprinkler system ... Where Note e also applies, the increase for both notes shall be applied accumulatively.”

53 +  53  +  53  = over limit(6 barrels in a sprinkled space)

Page 17: Barrels Exceptions in the Building Fire Codes

SECTION 414 SPECIAL REQUIREMENTS – HAZARDOUS MATERIALS

[F] 414.3 Ventilation. Rooms, areas or spaces in which explosive, corrosive, combustible, flammable or highly toxic dusts, mists, fumes, vapors or gases are or may be emitted due to the processing, use, handling or storage of materials shall be mechanically ventilated where required by this code, the International Fire Code or the International Mechanical Code.

VentilationNOT EXHAUSTSee Fire Code

See Mechanical Code

BARRELS

Page 18: Barrels Exceptions in the Building Fire Codes

VENTILATION…

Page 19: Barrels Exceptions in the Building Fire Codes

CHAPTER 50HAZARDOUS MATERIALS –GENERAL PROVISIONSSECTION 5001GENERAL5001.1 Scope. “… This chapter shall apply to all hazardous materials, including those materials regulated elsewhere in this code, except that where specific requirements are provided in other chapters… [in the case of] multiple hazards, all hazards shall be addressed.”

Exceptions:10. “The storage of distilled spirits and wines in wooden 

barrels and casks.”

BARRELS

Barrels ExemptIFC requires no ventilation

Page 20: Barrels Exceptions in the Building Fire Codes

CHAPTER 50HAZARDOUS MATERIALS –GENERAL PROVISIONSSECTION 5001GENERAL5001.1 Scope. …

BARRELS

The Commentary tells us barrels and casks are NOT exempt from 

IBC H‐3

Commentary is NOT code, but IS a guide to interpreting the code.

FROM THE COMMENTARY…Exception 10 covers the storage of distilled spirits and wines in wooden barrels and casks. This statement may appear to exempt all requirements for these products from being Group H occupancy. However, the IBC will still classify the storage area as a Group H occupancy if the amounts exceed the maximum allowable quantities (MAQs) per control area listed in Table 307.1(1) of that code for flammable or combustible liquids. All requirements for a Group H occupancy in the IBC are still applicable; however, any requirements from the code are not.…

Page 21: Barrels Exceptions in the Building Fire Codes

CHAPTER 57FLAMMABLE AND COMBUSTIBLE LIQUIDSSECTION 5701GENERAL5701.2 Nonapplicability. …This chapter shall not apply to liquids as otherwise provided in other laws or regulations or chapters of this code, including:…10. The storage of distilled spirits and wines in wooden barrels and casks.

BARRELS

Barrels and casks are Nonapplicable to this 

chapter.

IFC requires no ventilation

Page 22: Barrels Exceptions in the Building Fire Codes

COMMENTARY ON CHAPTER 57FLAMMABLE AND COMBUSTIBLE LIQUIDSSECTION 5701GENERAL5701.2 Nonapplicability. …Item 10 makes the storage of distilled spirits and wines in wooden barrels and casks exempt from this chapter. Although their contents are classified as flammable liquids, the containers do not pose the rupture hazard as do other containers. Barrels and casks will leak their contents and contribute to the fire as the metal bands that secure the staves expand and loosen. Even this hazard is generally mitigated by the operation of automatic sprinklers that prevent the fire from progressing to the point where the metal bands get hot enough to expand. A similar exception also appears in Section 5001.1

BARRELS

Barrels do not ruptureSprinklers greatly mitigate risk

Commentary is NOT code but IS a guide to interpreting the code.

Page 23: Barrels Exceptions in the Building Fire Codes

CODE: NFPA 1NFPA 1

Chapter 66 Flammable and Combustible Liquids66.1.2 Where the provisions of this chapter or NFPA 30 conflict with the provisions of Chapter 60, the provisions of this chapter and NFPA 30 shall apply.

66.9 Storage of Liquids in Containers —General Requirements.

66.9.1 Scope.

66.9.1.4 This section shall not apply to the following:(7) Distilled spirits and wines in wooden barrels or casks[30:9.1.4]

Page 24: Barrels Exceptions in the Building Fire Codes

CODE: NFPA 30NFPA 30

Chapter 9 Storage of Liquids in Containers —General Requirements

9.1 Scope.

9.1.4 This chapter shall not apply to the following:(7) Distilled spirits and wines in wooden barrels or casks

Page 25: Barrels Exceptions in the Building Fire Codes

SECTION 403MECHANICAL VENTILATION… 403.2 Outdoor  air required. “…Ventilation supply systems shall be designed to deliver the required rate of outdoor airflow to the breathing zone within each occupiable space.”

“Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants … the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.”

…510.2 Hazardous Exhaust where required.1. Flammable liquid vapor in excess of 25% of the LFL

We will come back to ventilation and deal with 

IMC

BARRELS

Page 26: Barrels Exceptions in the Building Fire Codes

CHAPTER 4[F] 414.5.1 Explosion Control. Explosion control shall be provided in accordance with the International Fire Code as required by Table 414.5.1 where quantities of hazardous materials specified in that table exceed the maximum allowable quantities in Table 307.1.(1) or where a structure, room or space is occupied for purposes involving explosion hazards as required by Section 415 or the International Fire Code.

[F] 414.5.2 Emergency or standby power.Where required by the International Fire Code or this code, mechanical ventilation, treatment systems, temperature control, alarm, detection or other electrically operated systems shall be provided with emergency or standby power in accordance with Section 2702. For storage and use areas for highly toxic or toxic materials, see Sections 6004.2.2.8 and 6004.3.4.5 of the International Fire Code.

BARRELS

Explosion control, emergency power, spill control, drainage, and containment all refer to the IFC where barrels are exempt. Therefore these items are not required for cask storage.

Note: explosion control is inherently provided with the 0.06cfm/sf of ventilation.

Page 27: Barrels Exceptions in the Building Fire Codes

[F] 414.5.3 Spill control, drainage and containment. Rooms, buildings or areas occupied for the storage of solid and liquid hazardous materials shall be provided with a means to control spillage and to contain or drain off spillage and fire protection water discharged in the storage area where required in the International Fire Code.The methods of spill control shall be in accordance with the International Fire Code.

BARRELS

Explosion control, emergency power, spill control, drainage, and containment all refer to the IFC where barrels are exempt. Therefore these items are not required for cask storage.

Note: explosion control is inherently provided with the 0.06cfm/sf of ventilation.

Page 28: Barrels Exceptions in the Building Fire Codes

[F] 415.4 Automatic sprinkler system. Group H occupancies shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.2.5

[F] 415.5 Emergency alarms. Emergency alarms for the detection and notification of an emergency condition in Group H occupancies shall be provided as set forth herein.

[F]  415.5.1 Storage. An approved manual emergency alarm system shall be provided in buildings, rooms or areas used for storage of hazardous materials. Emergency alarm‐initiating devices shall be installed outside of each interior exit or exit access door of storage buildings, rooms or areas. Activation of an emergency alarm‐initiating device shall sound a local alarm to alert occupants of an emergency situation involving hazardous materials.

BARRELS

Sprinklers, emergency alarm are required.

IFC?

Page 29: Barrels Exceptions in the Building Fire Codes

[F] 415.6.1.3 Groups H‐2 and H‐3. Group H‐2 and H‐3 occupancies shall be set back not less than 50 feet (15 240 mm) where a detachedbuilding is required (see Table 415.6.2).

BARRELS

The detached building is never required for H‐3 spirits in casks

Page 30: Barrels Exceptions in the Building Fire Codes

508.3.3 Separation. No separation is required between nonseparatedoccupancies.

Exceptions:1. Group H‐2, H‐3, H‐4 and H‐5 occupancies shall be separated from all 

other occupancies in accordance with Section 508.4.…

BARRELS

H‐3Barrel Storage

F‐1 Distillery

A‐2 Tasting Room

Barrels Mixed with Distillery

A‐2 Tasting Room

Page 31: Barrels Exceptions in the Building Fire Codes

PEOPLE NEED TO SEE THE BARRELS!

Page 32: Barrels Exceptions in the Building Fire Codes

508.3.3 Separation. No separation is required between nonseparatedoccupancies.

Exceptions:1. Group H‐2, H‐3, H‐4 and H‐5 occupancies shall be separated from all 

other occupancies in accordance with Section 508.4.…

BARRELS

A minimum of 1 hour separation from other occupancies is required.

The IFC is not referenced. Therefore, the barrel exceptions do not apply.

Typically, in smaller buildings, the entire distillery (except the H‐3 barrel room) is a non‐separated mixed use with either F‐1 or A‐2 being the most restrictive and the H‐3 room barrel separated 

accordingly.

Page 33: Barrels Exceptions in the Building Fire Codes

Excerpted from: TABLE 508.4REQUIRED SEPARATION OF OCCUPANCIES (HOURS)

BARRELS

Occupancy H‐3…

S NS

A, E 2 3

Ra 2 NP

F‐2, S‐2b, U 2 3

Be, F‐1, M, S‐1 1 2

H‐1 NP NP

H‐2 1 NP

H‐3, H‐4 1d NP

S = sprinkledNS = not sprinkledN = No separation requirementNP = Not Permitteda. See Section 420b. Required separation from areas used only 

for private or pleasure vehicles shall be reduced by 1 hour but not less than 1/2 hour.

d. Separation is not required between occupancies of the same classification.

e. See Section 422.2 for ambulatory care facilities.

Page 34: Barrels Exceptions in the Building Fire Codes

When do the IFC Exceptions Apply to create Modified H‐3?

CIRCLE BACK: BARREL EXCEPTIONS

IBC IFC414.3 1 CFM/SFVentilation See IFC & IMC Barrel Exception

414.5.1 Explosion Control See IFC Barrel Exception

414.5.3 Spill Control See IFC Barrel Exception

414.5.3 Secondary Containment See IFC Barrel Exception

415.5 Emergency Alarm Same

415.4 Sprinklers Same

415.6 25% Ext.Wall Same

508.3.3 ex.1 Min. 1 hr. Separation Same

2015 ICC Code References

Page 35: Barrels Exceptions in the Building Fire Codes

SECTION 414Special Requirements – Hazardous Materials[F] 414.3 Ventilation. Rooms, areas or spaces in which explosive, corrosive, combustible, flammable or highly toxic dusts, mists, fumes, vapors or gases are or storage of materials shall be mechanically ventilated where required by this code, the International Fire Code or the International Mechanical Code.

BARRELS

Ventilation NOT EXHAUSTSee Fire Code

See Mechanical Code

Page 36: Barrels Exceptions in the Building Fire Codes

Excerpted from: TABLE 403.3.1.1  MINIMUM VENTILATION RATES

OCCUPANCY CLASSIFICATION

OCCUPANT DENSITY #/1000 

FT2 a

PEOPLE OUTDOOR 

AIRFLOW RATE IN BREATHING 

ZONE, Rp CFM/PERSON

AREA OUTDOOR AIRFLOW RATE IN 

BREATHING ZONE, 

Ra CFM/FT2 a

EXHAUSTAIRFLOW RATE

CFM/FT2 a

StorageRepair garages, enclosed parking garages b,d

‐‐ ‐‐ ‐‐ 0.75

Warehouses ‐‐ ‐‐ .06 ‐‐

0.06 CFM/FT2 required for barrel storage ventilation

BARRELS

Page 37: Barrels Exceptions in the Building Fire Codes

SECTION 403MECHANICAL VENTILATION403.1 Ventilation system. Mechanical ventilation shall be provided by a method of supply air and return or exhaust air except that mechanical ventilation air requirements for Group R‐2, R‐3, and R‐4 occupancies three stories and less in height above grade plane shall be provided by an exhaust system, supply system or combination thereof. The amount of supply air shall be approximately equal to the amount of return and exhaust air. The system shall not be prohibited from producing negative or positive pressure. The system to convey ventilation air shall be designed an installed in accordance with Chapter 6.

… ventilation is provided by supply air and return OR exhaust.

BARRELS

• If we used supply & return air, we still need 0.06 CFM of outdoor air. • Adding air means we have to move it out – i.e. exhaust.• We typically take exhaust from within 12” of the floor due to the 

properties of alcohol vapor being heavier than air• The remaining fumes to stay under 25% of LFL.

Page 38: Barrels Exceptions in the Building Fire Codes

SECTION 401GENERAL401.1 Scope. This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust systems, including exhaust systems serving clothes dryers and cooking appliances; hazardous exhaust systems; dust, stock and refuse conveyor systems; smoke control systems; energy recovery ventilation systems and other systems specified in Section 502 shall comply with Chapter 5.

Because we are ventilating with Mechanical Exhaust vs. 

Supply/Return Air –We must go to  Chapter 5 of the IMC.

BARRELS

Page 39: Barrels Exceptions in the Building Fire Codes

BARRELS

SECTION 401GENERAL401.1 Scope. This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust systems, including exhaust systems serving clothes dryers and cooking appliances; hazardous exhaust systems; dust, stock and refuse conveyor systems; smoke control systems; energy recovery ventilation systems and other systems specified in Section 502 shall comply with Chapter 5.

FROM COMMENTARY This section establishes the scope… Smoke control systems, smoke venting, mechanical exhaust systems and combustion air supplies are not within the scope of this chapter but are regulated by other sections of the code… Chapter 5 addresses exhaust systems…

It may be inferred, and supported by commentary, that Chapter 5 

requirements apply to cask storage.

Page 40: Barrels Exceptions in the Building Fire Codes

The following slides intend to show IMC Chapter 5 requirements 

do not exceed IMC Chapter 4’s requirement 

of 0.06 CFM/SF2 and are supplanted by the IFC exceptions.

BARRELS

Page 41: Barrels Exceptions in the Building Fire Codes

BARRELSSECTION 502REQUIRED SYSTEMS

502.1 General. An exhaust system shall be provided, maintained and operated as specifically required by this section and for all occupied areas where machines, vats, tanks, furnaces, forges, salamanders and other appliances, equipment and processes in such areas produce or throw off dust or particles sufficiently light to float in the air, or which emit heat, odors, fumes, spray, gas or smoke, in such quantities so as to be irritating or injurious to health or safety.

Page 42: Barrels Exceptions in the Building Fire Codes

BARRELSSECTION 502REQUIRED SYSTEMS

502.1 General. An exhaust system shall be provided, maintained and operated as specifically required by this section and for all occupied areas where machines, vats, tanks, furnaces, forges, salamanders and other appliances, equipment and processes in such areas produce or throw off dust or particles sufficiently light to float in the air, or which emit heat, odors, fumes, spray, gas or smoke, in such quantities so as to be irritating or injurious to health or safety.

FROM COMMENTARY…Exhaust systems must be designed to collect and remove the contaminants… This section is written in performance language and requires case-by-case evaluation by the designer and the code official to determine the quantity and type of contamination present, whether any action needs to be taken…

The commentary clarifies the intent is to require 

the code official and designer

to work together to design a system 

appropriate to the specific situation.

Page 43: Barrels Exceptions in the Building Fire Codes

BARRELSSECTION 502REQUIRED SYSTEMS

502.1 General. An exhaust system shall be provided, maintained and operated as specifically required by this section and for all occupied areas where machines, vats, tanks, furnaces, forges, salamanders and other appliances, equipment and processes in such areas produce or throw off dust or particles sufficiently light to float in the air, or which emit heat, odors, fumes, spray, gas or smoke, in such quantities so as to be irritating or injurious to health or safety.

FROM COMMENTARY…Exhaust systems must be designed to collect and remove the contaminants… This section is written in performance language and requires case-by-case evaluation by the designer and the code official to determine the quantity and type of contamination present, whether any action needs to be taken…

Using historic data for alcohol loss 

during time in cask(Angel’s Share) 

we can demonstrate 0.06 CFM/SF2 is 

more than adequate to exhaust the vapor 

faster than it accumulatesto 25% of the LFL. 

Thereby addressing and mitigating contaminates.

Page 44: Barrels Exceptions in the Building Fire Codes

BARRELSSECTION 502EXHAUST SYSTEMS[F]502.8.1 Storage in excess of the maximum allowable quantities. Indoor storage areas and storage buildings for hazardous materials in amounts exceeding the maximum allowable quantity per control area…

[F] 502.8.1.1 System requirements. Exhaust ventilation systems shall comply with all of the following:…

2. Mechanical ventilation shall be provided at a rate of not less than 1 cfm per square foot [0.00508 m3/(s*m2)] of floor area over the storage area.

3. The systems shall operate continuously…

4. A manual shutoff control shall be provided outside of the room…labeled: VENTILATION SYSTEM EMERGENCY SHUTOFF.

5. For fumes or vapors that are heavier than air, exhaust shall be taken from a point within 12 inches (305 mm) of the floor.

6. The location of both the exhaust and inlet air openings shall be designed to provide air movement across all portions of the floor or room to prevent the accumulation of vapors.

7. The exhaust air shall not be recirculated to occupied areas…

1 CFM/SF2required where

MAQs exceeded

Page 45: Barrels Exceptions in the Building Fire Codes

BARRELS

Page 46: Barrels Exceptions in the Building Fire Codes

BARRELSSECTION 502EXHAUST SYSTEMS[F] 502.8 Hazardous materials – general requirements. Exhaust ventilation systems for structures containing hazardous materials shall be provided as required in Sections 502.8.1 through 502.8.5.

The Commentary indicates the IFC contains the same ventilation requirements.

The IFC has no ventilation requirements for barrel storage because of the exceptions.

Therefore, ventilation (exhaust) is NOT REQUIRED by 502.8 of the IMC.

FROM COMMENTARY Chapter 50 of the IFC contains guidance for the storage, dispensing, use and handling of hazardous materials. Section 5004.3 of the IFC contains the same ventilation requirements as Sections 502.8.1 and 502.8.1.1 of the code.

Page 47: Barrels Exceptions in the Building Fire Codes

BARRELSSECTION 502EXHAUST SYSTEMS[F] 502.8 Hazardous materials – general requirements. Exhaust ventilation systems for structures containing hazardous materials shall be provided as required in Sections 502.8.1 through 502.8.5.

SECTION 102APPLICABILITY[A] 102.1 General. Where there is a conflict between a general requirement and a specific requirement, the specific requirement shall govern. Where, in a specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern.

BUT, this assumption could be challenged.

FROM COMMENTARY Chapter 50 of the IFC contains guidance for the storage, dispensing, use and handling of hazardous materials. Section 5004.3 of the IFC contains the same ventilation requirements as Sections 502.8.1 and 502.8.1.1 of the code.

Page 48: Barrels Exceptions in the Building Fire Codes

BARRELSSECTION 502EXHAUST SYSTEMS[F]502.9.5 Flammable and combustible liquids. Exhaust ventilation systems shall be provided as required by Sections… Unless otherwise specified this section shall apply to any quantity of flammable and combustible liquids.

Exception: This section shall not apply to flammable and combustible liquids that are exempt from the International Fire Code.

FROM COMMENTARY: Minimum requirements for mechanical exhaust ventilation for inside areas in which flammable or combustible liquids are stored are contained in Section 5004.3 of the IFC and Section 502.8.1.1 of the code. The use of natural ventilation as an alternative to mechanical ventilation is subject to approval by the code official (see commentary, Sections 502.9.5.1 through 502.9.5.5).

Page 49: Barrels Exceptions in the Building Fire Codes

IMCSECTION 510HAZARDOUS EXHAUST SYSTEMS510.2 Where required. A hazardous exhaust system shall be required wherever operations involving the handling or processing of hazardous materials, in the absence of such exhaust systems andunder normal operating conditions, have the potential to create one of the following conditions:1. A flammable vapor, gas, fume, mist or dust is present in 

concentrations exceeding 25 percent of the lower flammability limit of the substance for the expected room temperature.

BARRELS

Page 50: Barrels Exceptions in the Building Fire Codes

SECTION 502EXHAUST SYSTEMS[F]502.9.5 Flammable and combustible liquids.

Section 502.9.5 is specific to flammable and combustible liquids. Due to this specificity, it is the key article pertaining to our liquid.

It specifically exempts liquids that are exempt in the IFC.

Spirits in casks are exempt from ventilation requirements in the IFC. They are therefore exempt from exhaust requirements here in the IMC.

Only the warehouse ventilation rate requirement still applies.

BARRELS

Page 51: Barrels Exceptions in the Building Fire Codes

BARRELSSpecialty Codes

Page 52: Barrels Exceptions in the Building Fire Codes

Entire space is Modified H‐3• 25% on Exterior Wall

• Sprinklers

• Emergency Alarm

• 1 hour separation

H‐3 EXCEPTIONS

If it weren’t for the barrels in this room the whole thing could be classified F‐1

the barrels make it H‐3 Modified because they exceed the MAQs.

Page 53: Barrels Exceptions in the Building Fire Codes

DUNNAGE PALLETIZED ON END

STEEL RACKS WOOD RICKS PALLETIZED WINE RACK

END STACKED

TOTES

STACKING METHODS

Storage over 6’? High Piled Storage Requirements 

• No Exception for Barrels• High‐Hazard Commodity Class• Smoke Vents• Designated Piles & Aisles• Access Doors

Page 54: Barrels Exceptions in the Building Fire Codes

IFCCHAPTER 32HIGH‐PILED COMBUSTIBLE STORAGEBarrels are not exempt from the requirements of this chapter.

If your district is not using IFC, then similar requirements are found throughout various NFPA documents.

Barrels are High Hazard Commodity and therefore, if stacked over 6’ tall, are considered high piled

Some additional building elements that may be required for HPCS include…

‐Smoke vents or ESFR (Early Suppression Fast Response) sprinklers

‐ Fire department access every 100’.‐ Draft curtains‐ Designated aisles

Watch for our next specialty presentation or webinar on this subject.

COMING SOON…

Page 55: Barrels Exceptions in the Building Fire Codes

Factory Mutual ‐ now FM Global, an insurance provider does testing to establish standards, has embarked on a new battery of tests for alcohol aging in barrels.

Current testing points to doubling the sprinkler water volume required.

They plan to do more testing… so, if you have any spare barrels of spirit to donate to the cause – it would be appreciated. ;‐) 

More information on this as the story develops…

CURRENT RESEARCH…

Page 56: Barrels Exceptions in the Building Fire Codes

Scott & Colleen MooreDalkitaArchitecture & Construction

303‐765‐[email protected]

Thank You!