48
1262-IN-015-0-02 December 1997 Instruction Manual Model 7ES DG

Barber Colman 7ES

Embed Size (px)

Citation preview

Page 1: Barber Colman 7ES

1262-IN-015-0-02December 1997

Instruction Manual

Model 7ES

DG

Page 2: Barber Colman 7ES

2

1/8 DIN, Four Digit DisplayTemperature Controller with Actuator Output

MODEL: 0 7 E S - 9 3 2 1 - 3 0 0 - 0 - 0 0Field No. 1 2 3 4 5 6 7 8 9 10 1112 13 14 15

Fields 1 through 4. BASE07ES - Controller

Fields 5 through 8. INPUT/OUTPUT9321 -TC types B, J, K, L, N, R, S and T;

Pt 100, 3 wire RTD;0 to 20 mAdc and 4 to 20 mAdc;0 to 60 mVdc and 12 to 60 mVdc;0 to 5 Vdc and 1 to 5 Vdc;0 to 10 Vdc and 2 to 10 Vdc.Note: All inputs are factory calibratedand selectable by keys. Factory setat type K.

Output 1/2: Two interlocked relays(open/close), SPST, NO relayprogrammable as actuator controloutput or time proportioning relayoutput;Output 3: SPST relay programmableas time proportioning output whenoutput 1 configured as relay output, oralarm 1

Field 9. OPTIONS2 - Output 4 (alarm 3)3 - RS-485, plus output 4 (alarm 3)

Field 10. POWER SUPPLY3 - 100 to 240 Vac

Fields 11 through 15. RESERVED

Page 3: Barber Colman 7ES

3

Congratulations

. . . on your purchase of one of the easiest toconfigure controllers on the market. After a fourstep configuration procedure, your process willbe up and running.

If for any reason you encounter difficulty withthe controller set-up, please call your supplier.

Guide to simple set-up

Only four steps are required to set up your con-troller:1. Wire the Instrument.2. Configure the instrument.3. Check the operating mode parameters.4. Check the autotune (Smart AT) process.

Un p ac k t he In st ru m e nt

W iring

C o nf ig u ra tio n

O p erating Pa ra m et ers

Au to tu ning

S V

Page 4: Barber Colman 7ES

4

CAUTION:USE WIRE SUITABLEFOR 75°C MINIMUM.

NOTES

• For supply connections use No 16 AWG or largerwires rated for at least 75 °C.

• Use copper conductors only.• Class 2 wiring must be separated a minimum of 1/4

inch from any Class 1 conductors.

ContentsWiring Guidelines............................................. 7

Terminal board .......................................... 7Measuring inputs ....................................... 8Logic inputs ............................................... 9Relay outputs .......................................... 10Inductive loads ........................................ 11Servomotor Output/Input ........................ 12Serial interface ........................................ 12Power Line Wiring ................................... 13

Configuration ................................................. 14Preliminary Hardware Settings ................ 14Configuration Procedure ......................... 15Advanced Configuration Procedure ....... 19Default Configuration Parameters .......... 23

Operating Mode............................................. 25Feedback Potentiometer Calibration ...... 26Enable/Disable Control Output ............... 27Manual Mode .......................................... 27Direct Access to Setpoints ..................... 28Serial Link ................................................ 28Autotuning (Smart AT) ............................. 29Lamp Test ................................................ 29Operating Parameters ............................. 29Error Messages ....................................... 32Default Operating Parameters ................ 34

Specifications ................................................ 36Calibration ..................................................... 40

Calibration Parameters ........................... 41Procedure ................................................ 41

Maintenance .................................................. 47

Page 5: Barber Colman 7ES

5

Mounting Requirements

Select a mounting location with the followingcharacteristics:1) Minimum vibration.2) Ambient temperature range between 0

and 50°C (32 and 122°F).3) Easy access to the rear of the instrument.4) No corrosive gases (sulfuric gas, ammo-

nia, etc.).5) No water or other fluid (i.e. condensation).6) Relative humidity of 20 to 85% non

condensing.

The instrument can be mounted on a panel upto 15 mm (0.591 in) thick with a square cutoutof 45 x 92 mm (1.772 x 3.662 in). For outlinerefer to Dimensions and Panel Cutout.

Panel surface texture must be smoother than248 microinches. The instrument is shipped witha rubber panel gasket (50 to 60 Sh). To assureIP65 and NEMA 4 protection, insert the panelgasket between the instrument and the panelas shown below.

Install the instrument as follows:

1) Insert the instrument case in the gasket.2) Insert the instrument in the panel cutout.3) Pushing the instrument against the panel,

insert the mounting bracket.4) Torque the mounting bracket screws

between 0.3 and 0.4 Nm (0.021 and 0.027lbft).

5) Make sure the instrument will not movewithin the cutout to insure NEMA 4X/IP65protection.

Br a c ke t

P a n e l

G a sk et

Page 6: Barber Colman 7ES

6

Dimensions and Panel Cutout

(116 m m )4 .567 in

(6 0 m m )2 .362 in

(125 m m)4 .92 1 in

(45 m m , - 0, +0 .6 m m )1 .772 in , - 0, +0 .024 in

(9 2 m m , - 0 , +0 .8 mm )3 .622 in , - 0 , + 0. 03 1 in

(48 m m ) 1 .890 in

(9 6 m m )3 .780 in

(10 m m ) 0 .394 in

Page 7: Barber Colman 7ES

7

WIRING GUIDELINES

Terminal board

When a relay output is used to drive an induc-tive load, connect an external snubber network(RC) across the terminals:

CR

NOTE: Control outputs 1 and 2 are protectedby varistor against an inductive load up to 0.5Amps. For the other outputs or external con-tacts in series with the instrument outputs, con-nect an external snubber network (RC) acrossthe terminals in accordance with the followingtable:Load C(µ) R(ohms) P(W) R & C V<40 mA 0.047 100 1/2 260 Vac<150 mA 0.1 22 2 260 Vac<0.5 A 0.33 47 2 260 Vac

1 0 0 /2 4 0 Vac PW R L IN E

1 2

1 3

1 5

1 4

D IG 1

D IG 2

D IG 3

1 6

1 7

1 8

1 9

2 1

2 2 1 1

1 0

9

8

7

6

5

4

3

T C

1

2 0

LI N E AR I N P U T S

RTD

R S 4 8 5

A /A ’

B /B ’

C

N O O U T 3

C OU T 3 & 4

N O O U T 4

A CM OT O R

A CF EED BA C K

M03

79-0

1

Page 8: Barber Colman 7ES

8

Measuring inputsAny external components (like zener diodes,etc.) connected between the sensor and inputterminals may cause measurement errors (ex-cessive or unbalanced line resistance or pos-sible leakage currents).

TC input

S hie ld

S hie ld

1

3

1

3

+

-

+

-

NOTE:1) Do not run input wires with power cables.2) For TC wiring use proper compensating

cable, preferably shielded (see Thermo-couple Compensating Cable ColorCodes).

3) Shielded cable should be grounded at oneend only.

4) High line resistance can cause measure-ment errors.

Linear input

1

3

m A , m V o r V

S hie ld

-

+

1

3

m A , m V o r V

S hie ld

-

G

+

+

+

-

-

Note:1) Do not run input wires with power cables.2) High line resistance can cause measure-

ment errors.3) When shielded cable is used, ground it at

one end only to avoid ground loopcurrents.

4) The input impedance is equal to:Less than 5 ohms for 20 mA inputGreater than 1 megohms for 60 mV inputGreater than 200 kilo-ohms for 5 V inputGreater than 400 kilo-ohms for 10 V input.

Page 9: Barber Colman 7ES

9

RTD input

4 3

R T D

1 4 3

R T D

1

NOTE:1) Do not run RTD wires with power cables.2) Pay attention to line resistance: high line

resistance may cause measurementerrors.

3) Shielded cable should be grounded at oneend only.

4) The resistance of the three wires must bethe same.

Any external components (like zener diodes,etc.) connected between the sensor and inputterminals can cause measurement errors (ex-cessive or unbalanced line resistance or pos-sible leakage currents).

Logic inputs

SAFETY NOTE:• Do not run logic input wiring with AC

power cables.• Use an external dry contact capable of

switching 0.5 mA, 5V dc.• The instrument needs 100 ms to recognize

a contact status variation.• Logic inputs are not isolated by measuring

input.

7L og ic in p ut 2

6

8

L og ic in p ut 1

L og ic in p ut 3

5L o gic inp u t co m m o n

The combination of logic input 1 and logic input3 allows to select the operating setpoint as fol-lows:Input 3 Input 1 Op. Setpointopen open SPopen close SP2close open SP3close close Sp4

Logic input 2 function is programmed by pa-rameter P24.

Page 10: Barber Colman 7ES

10

Relay outputs

ThermocoupleMaterial

CopperT Constantan

IronJ/L Constantan

Nickel ChromiumK Nickel Aluminum

Platinum/PlatinumR 13% Rhodium

Platinum/PlatinumS 10% Rhodium

ChromelE Constantan

Platinum 30% RhB Platinum 6 % Rh

N Nicrosil / Nisil

BritishBS 1843

+ White- Blue

Blue+ Yellow- Blue

Black+ Brown- Blue

Red+ White- Blue

Green+ White- Blue

Green+ Brown- Blue

Brown------

AmericanANSI MC 96.1+ Blue- Red

Blue+ White- Red

Black+ Yellow- Red

Yellow+ Black- Red

Green+ Black- Red

Green+ Violet- Red

Violet+ Grey- Red

Grey+ Orange- Red

Orange

GermanDIN 43710+ Red- Brown

Brown+ Red- Blue

Blue+ Red- Green

Green+ Red- White

White+ Red- White

White+ Red- Black

Black+ Red- Grey

Grey---

FrenchNFE 18-001+ Yellow- Blue

Blue+ Yellow- Black

Black+ Yellow- Purple

Yellow+ White- Green

Green+ White- Green

Green+ Yellow- Violet

Violet------

Thermocouple compensating cable color codes

14

15

16

NO - OUT 3

C - OUT 3/4

NO - OUT 4

OUT 3

OUT 418

C

NO17

O U T 1

NOTE: OUT 1 can be used either as servomotoroutput or as time proportional relay output; bythe P5 parameter it is possible to set the de-sired output

Page 11: Barber Colman 7ES

11

Relay output: Protected by varistor againstinductive load with inductive component upto 0.5A.OUT 1: Contact rating of 3A/250 Vac on resis-tive load; contact rating of OUT 2 is 2A/250 Vacon resistive load.OUT 3: Contact rating of 2Amp/250 Vacresistive load.OUT 4: Contact rating of 2Amp/250 Vacresistive load. Number of operations: 1 x 105 atspecified rating.

Alarm 2 and alarm 3 are in OR condition on theOUT 4.

The following recommendations avoid seriousproblems which may occur when using relayoutput for driving inductive loads.

Inductive loads

L O A D

RC

P O W ERLIN E

Values of capacitor (C) and resistor (R) are:Load C(µF) R (ohms) P(W) R & C V<40 mA 0.047 100 1/2 260 Vac<150 mA 0.1 22 2 260 Vac<0.5 A 0.33 47 2 260 Vac<1 A 0.47 47 2 260 Vac

Relay output wiring must be as far away as pos-sible from input wiring and communicationcables.

High voltage errors may occur switching induc-tive loads. Through the internal contacts, thesetransients may introduce disturbances whichcan affect instrument performance. For all out-puts, the internal protection (varistor) assurescorrect protection up to 0.5 Amps of inductivecomponent.

The same problem may occur when a switch isused in series with the internal contacts asshown bellow. In this case it is good practiceto install an additional RC network across theexternal contact as shown.

Page 12: Barber Colman 7ES

12

Servomotor Output/Input

o pen v a lve

1 7

1 8

1 9 c lo s e va lv e

P o we r L ineS er vo m o to r

2 0

2 1

2 2

Feed

back

P

oten

tiom

eter

S h ie ld

The two relay outputs are interlocked.1) Before connecting the instrument to the

power line, make sure the line voltage andload current are in accordance with thecontact rating (3A/250 Vac on resistiveload).

2) To avoid electric shock, connect powerline at the end of wiring procedure.

3) For servomotor connections, use No. 16AWG or larger wires rated for at least75°C.

4) Use copper conductors only.

5) Do not run input wires together withpower cables.

6) For feedback potentiometer, use shieldedcable with the shield connected to theearth at one point only.

7) Relay outputs are protected by varistoragainst inductive load with inductivecomponent up to 0.5 A.

Serial interface

The RS-485 interface can connect up to 30 in-struments with the remote master unit

1 1

1 0

9

A /A ’ A ’ /A

B /B ’ B’/B

C o m m o n

M A S T E R

Maximum cable length: 1.5 km (9/10 mile) at 9600 BAUD.

NOTE: According to EIA specification for RS-485.a) The "A" terminal of the generator shall be

negative with respect to the "B" terminalfor a binary 1 (MARK or OFF) state.

b) The "A" terminal of the generator shall bepositive with respect to the "B" terminalfor a binary 0 (SPACE or ON) state.

Connect the instrument (maximum of 30) to themaster unit by interface communication typeRS-485.

Page 13: Barber Colman 7ES

13

1 1

1 0

9

A /A ’ A ’ /A

B /B ’ B’/B

C o m m o n

1 1

1 0

9

M A S T E R

Power Line Wiring

1 3

1 2

Pow e r S up ply 10 0 to 240 Va c rm s (50/60 Hz )

or 24 Va c/Vd c

N

NR (S, T )

R (S, T )

NOTE:1) Before connecting the power line, check

that the voltage is correct (see ModelNumber).

2) To avoid electric shock, connect powerline at the end of the wiring procedure.

3) For supply connections use 16 AWG orlarger wires rated for at least 75 °C.

4) Use copper conductors only.

5) Do not run input wires with power cables.6) Polarity does not matter for 24 Vdc wiring.7) The power supply input is fuse protected

by a sub-miniature rated T, 1 A, 250 V.When the fuse is damaged the instrumentshould be returned to your supplier tocheck the power supply.

8) Safety requirements for permanentlyconnected equipment:• Include a switch or circuit-breaker in

the installation.• Place it in close proximity to the

equipment and within easy reach ofthe operator. Mark it as the discon-necting device for the equipment.

NOTE: A single switch or circuit-breakercan drive more than one instrument.

9) When the NEUTRAL line is present,connect it to terminal 13.

Page 14: Barber Colman 7ES

14

Figure 1.

V2

1 3 5 7 9

2 4 6 8 10

J1

CONFIGURATION

Preliminary Hardware Settings1) Remove the instrument from its case.2) Set J1 according to the desired input type

as shown in the following table.INPUT J1TYPE 1-2 3-4 5-6 7-8 9-10TC-RTD open close open open open60 mV open close open open open5 V close open close open open10 V open open close open open20 mA open open open close close

When a jumper is not used, it can be placed onpins 7 and 9.

Open input circuitThis instrument is able to identify an open cir-cuit for TC and RTD inputs. The open circuitcondition for RTD input is shown by an“overrange” indication. For TC input, either anoverrange indication (standard) or an underrangeindication can be selected as follows:Overrange (std): CH2 = close; SH2 = openUnderrange: CH2 = open; SH2 = close

Both pads are located on the solder side of theCPU card.

Configuration Key FunctionsFUNC = The new setting of the selected

parameter is stored and the nextparameter is displayed (in increasingorder).

MAN = Scrolls back through the parameterswithout storing the new setting.

s = Increases the setting of the selectedparameter.

t = Decreases the setting of the selectedparameter.

SH2CH2

Caution:Solder carefully toavoid damage toPCB or othercomponents.

Page 15: Barber Colman 7ES

15

Configuration Procedure

1) Remove the instrument from its case.2) Open switch V2 (see Figure 1, in Prelimi-

nary Hardware Settings).3) Re-insert the instrument in its case.4) Switch on power to the instrument. The

display will show COnF. (If "CAL" isdisplayed, press the s key and return tothe configuration procedure).

5) Press the FUNC key.

Note: The default setting of each parameter inthe following listing is underscored.

SEr1 = Serial interface protocolOFF = No serial interface.Ero = Poll/select using proprietary protocol.nbUS = ModbusjbUS = Jbus

SEr2 = Serial link device addressNot available when SEr1 = OFF.From 1 to 95 for proprietary protocol.From 1 to 255 for all the other protocols.Note: RS-485 serial interface allows 30 devicesmaximum.

SEr3 = Baud rate for serial linkNot available when SEr1 = OFF.From 600 to 19200 baud.Note: 19200 baud displays as 19.2.

SEr4 = Byte format for serial linkNot available when SEr1 = OFF.7E = 7 bits + even parity (For proprietary

protocol only.)7O =7 bits + odd parity (For proprietary

protocol only.)8E = 8 bits + even parity.8O = 8 bits + odd parity.8 = 8 bits without parity.

P1 = Input type and standard range0 = TC type L 0 to +400.0 °C1 = TC type L 0 to +900 °C2 = TC type J -100.0 to +400.0 °C3 = TC type J -100 to +1000 °C4 = TC type K -100.0 to +400.0 °C5 = TC type K -100 to +1370 °C6 = TC type T -199.9 to +400.0 °C7 = TC type N -100 to +1400 °C8 = TC type R 0 to +1760 °C9 = TC type S 0 to +1760 °C10 = TC type B 0 to +1820 °C11 = RTD, Pt 100 -199.9 to +400.0 °C12 = RTD, Pt 100 -200 to +800 °C13 = mV Linear 0 to 60 mV14 = mV Linear 12 to 60 mV15 = mA Linear 0 to 20 mA16 = mA Linear 4 to 20 mA17 = V Linear 0 to 5 V18 = V Linear 1 to 5 V19 = V Linear 0 to 10 V20 = V Linear 2 to 10 V21 = TC type L 0 to +1650 °F22 = TC type J -150 to +1830 °F23 = TC type K -150 to +2500 °F24 = TC type T -330 to +750 °F

Page 16: Barber Colman 7ES

16

25 = TC type N -150 to +2550 °F26 = TC type R 0 to +3200 °F27 = TC type S 0 to +3200 °F28 = TC type B 0 to + 3310 °F29 = RTD, Pt 100 -199.9 to +400.0 °F30 = RTD, Pt 100 -330 to +1470 °F

Note: When P1 = 0, 2, 4, 6, 10, 11, 28 or 29,then P43 = FLtr. For all other ranges P43 =nOFL.

P2 = Decimal point positionThis parameter is available only when a linearinput is selected (P1 = 13, 14, 15, 16, 17, 18, 19or 20).

_ _ _ _ . = No decimal._ _ _ . _ = One decimal place._ _ . _ _ = Two decimal places._ . _ _ _ = Three decimal places.

P3 = Initial scale valueCan be set with keys from -1999 to 4000 forlinear inputs. Can be set with keys within theinput range for TC and RTD. When this param-eter is modified, rL will change. Default = 0.

P4 = Full scale valueFor linear inputs, programmable from -1999to 4000. For TC and RTD inputs, programmablewithin the input range. When this parameter ismodified, rH will change. The initial and full scalevalues determine the input span used by thePID algorithm, autotuning (Smart AT), and thealarm functions. Default = 2190.

Note: Minimum input span in absolute value(S = P4 - P3) is as follows:For linear inputs, S > 100 units.For TC input with °C readout, S > 300 °C.For TC input with °F readout, S > 550 °F.For RTD input with °C readout, S > 100 °C.For RTD input with °F readout, S > 200 °F.

P5 = Output 1Sn.OL = Servomotor open loop.Sn.CL = Servomotor close loop.rEv = Reverse acting time proportional

control.dir = Direct acting time proportional control.

t

t

Inpu

tO

utp

ut

D irect A ct ion

t

t

Inpu

tO

utp

ut

R eve rse A c tio n

Notes:1) If P5 is changed to "Sn.OL" or it is

changed from "Sn.OL" to anotherselection, P41 = 0.

2) If P5 is changed to "rEv" the cycle time(Cy1) = 15 seconds.

3) If P5 is changed to "dir" the cycle time(Cy1) will be:10 seconds when P25 = Air4 seconds when P25 = OIL2 seconds when P25 = H2O

Page 17: Barber Colman 7ES

17

P6 = Valve position indicationThis parameter is available only whenP5 = Sn.OLFb = The valve position will be displayed.no.Fb =The valve position will not be

displayed (the feedback potentiometer isnot used.)

P7 = Output 3nonE = Output not used.AL1.P = Used as Alarm 1 output and alarm 1

is programmed as a process alarm.AL1.b = Used as Alarm 1 output and alarm 1

is programmed as a band alarm.AL1.d = Used as Alarm 1 output and alarm 1

is programmed as a deviation alarm.rEv = Used as second time proportional

control output with reverse action.dir = Used as second time proportional

control output with direct action.

Notes:1) If P7 is changed to "rEv" then cycle time

forced (Cy3) = 15 seconds.2) If P7 is changed to "dir" then cycle time

(Cy3) will be forced:10 seconds when P25 = Air.4 seconds when P25 = OIL.2 seconds when P25 = H2O.

3) Only one of the two outputs (see P5 andP7) can be configured as "rEv" controloutput.

4) Only one of the two outputs (see P5 andP7) can be configured as "dir" controloutput.

5) If the servomotor output is selected (P5="Sn.OL" or "Sn.CL") then OUT 3 can beset as alarm output only (P7 = "AL1.P" or"AL1.b" or "AL1.d").

P8 = Alarm 1 operating modeAvailable only when P7 is equal to AL1.P,

AL1.b or AL1.d.H.A.= High alarm (outside of the band) with

automatic reset.L.A.= Low alarm (inside the band) with

automatic reset.H.L.= High alarm (outside of the band) with

manual reset.L.L.= Low alarm (inside the band) with manual

reset.

P9 = Alarm 2 Function (OUT 4)nonE = Output not used.AL2.P = Used as Alarm 2 output and alarm 2

is programmed as a process alarm.AL2.b = Used as Alarm 2 output and alarm 2

is programmed as a band alarm.AL2.d = Used as Alarm 2 output and alarm 2

is programmed as a deviation alarm.

P10 = Alarm 2 Operating ModeNot available when P9 = "nonE."H.A.= High alarm (outside of the band) with

automatic reset.L.A. = Low alarm (inside the band) with

automatic reset.H.L. = High alarm (outside of the band) with

manual reset.L.L. = Low alarm (inside the band) with

manual reset.

Page 18: Barber Colman 7ES

18

P11 = Alarm 3 function (OUT 4)nonE = Output not used.AL3.P = Used as Alarm 3 output and alarm 3

is programmed as a process alarm.AL3.b = Used as Alarm 3 output and alarm 3

is programmed as a band alarm.AL3.d =Used as Alarm 3 output and alarm 3 is

programmed as a deviation alarm.Note: Output 4 operates as a logic OR betweenalarm 2 and alarm 3.

P12 = Alarm 3 operating modeNot available when P11 = "nonE."H.A.= High alarm (outside of the band) with

automatic reset.L.A.= Low alarm (inside the band) with

automatic reset.H.L.= High alarm (outside of the band) with

manual reset.L.L.=Low alarm (inside the band) with manual

reset.

P13 = Alarm 3 programmabilityNot available when P11 = "nonE."OPrt = Alarm 3 setpoint and hysteresis are

programmable in operating mode.COnF = Alarm 3 setpoint and hysteresis are

programmable in configuration mode.SPEC = During configuration, alarm 3 is

assigned a hysteresis value and twosetpoints. Either the first or secondsetpoint can be specified as the operatingsetpoint value.

P14 = Alarm 3 first setpoint valueNot available when P11 =• "nonE" and P13 ="COnF" or "SPEC." Default = 1380. Range:• For process alarm: Within the range limits.• For band alarm: 0 to 500 units.• For deviation alarm: -500 to 500 units.

P15 = Alarm 3 second setpoint valueNot available when P11 = "nonE" and P13 ="SPEC." Default = 1560. Range:• For process alarm:Within the range limits.• For band alarm: From 0 to 500 units.• For deviation alarm: -500 to 500 units.

P16 = Alarm 3 hysteresis valueNot available when P11 =• "nonE" and P13 ="COnF" or "SPEC." Range: From 0.1 to 10.0%of the span selected with P3 and P4 param-eters.

P17 = Setpoint of the �Soft Start� functionAvailable only when P5 not = • "Sn.0L" or "SnCL"Setpoint setting (in engineering units), to initiatethe “Soft start” function (output power limiting)at start-up. Range: Within the readout span.This setpoint setting is not used when tOL =InF. Default = 0.

P18 = Safety lockWhen P18 is selected, the display will show:• "0" if P18 = 0• "1" if P18 = 1• "SFt.A" if P18 is within 2 to 4999• "SFt.B" if P18 is within 5000 to 9999.

Page 19: Barber Colman 7ES

19

Using the s and t keys set P18 according tothe following conditions:0 = Unlocked. The device is always unlocked

and all parameters can be modified.1 = Locked. None of the parameters (except

SP, SP2, SP3, SP4 and alarm manualreset) can be modified. (For autotuningstatus see P33 parameter).

2 to 4999 = This number is a password usedin run time (see nnn parameter) to lock/unlock the device. This has no effect onthe setpoint or manual reset of the alarms.(For autotuning status see P33).

5000 to 9999 = This number is a passwordused in run time (see nnn parameter) tolock/unlock the device. This has no effecton the setpoint, manual reset of thealarms or the AL1/ AL2/ AL3 setpoints (forautotuning status see P33).

The configuration procedure is complete. Theinstrument should show "-.-.-.-." on both dis-plays. Press the FUNC key; the instrument willreturn to the beginning of the configuration pro-cedure. To continue with controller set-up goto the operating mode found in the next sec-tion. To access the advanced configurationparameters proceed as follows:1) Using the s and t keys enter 275.2) Press the FUNC key.

Advanced Configuration Procedure

P19, P20, P21, P22 and P23 are not used.

P24 = Logic Input 2 (Contact)nonE = Logic input 2 is not used.AU.nA = Logic input 2 selects AUTO/MAN

control mode.Open = AUTOClosed = MANUALrE.dr = Logic input 2 selects REVERSE/

DIRECT control mode.Open = REVERSEClosed = DIRECTNote: This selection is available only whenP5 = "Sn.OL" or "Sn.CL".

P25 = Cooling media.Available only when configured with two con-trol outputs.AIr = Air OIL = Oil H2O = waterChanging P25 forces the cycle time and rela-tive cooling gain parameter to the default valueof the selected cooling media. When:• P25 = AIr, CYx = 10 seconds and rC = 1.00• P25 = OIL, CYx = 4 seconds and rC = 0.80• P25 = H2O, CYx = 2 seconds and rC = 0.40

Page 20: Barber Colman 7ES

20

P26 = Alarm 1 actionAvailable only when P7 = "AL1.P" or "AL1.b" or"AL1.d."dir = Direct (relay energized in alarm condi-

tion).rEV = Reverse (relay de-energized in alarm

condition).

P27 = Alarm 1 standby functionAvailable only when P7 = "AL1.P" or "AL1.b" orAL1.d"OFF = Standby disabled.ON = Standby enabled.

Note: If band or deviation alarm, the alarmis masked after a setpoint change or atstart-up until the process variable reachesthe alarm setpoint plus or minus hyster-esis. If the alarm is a process alarm, thecondition is masked at start-up until theprocess variable reaches the alarmsetpoint plus or minus hysteresis.

P28 = Alarm 2 and 3 actionNot available when P9 or P11 = "nonE."dir = Direct (relay energized in alarm condi-

tion).rEV =Reverse (relay de-energized in alarm

condition).

P29 = Alarm 2 standby functionNot available when P9 = "nonE."OFF = Standby disabled.On = Standby enabled.

P30 = Alarm 3 standby functionNot available when P11 = "nonE."

OFF = Standby disabled.On = Standby enabled.

P31 = OFFSET applied to the measured valueSets a constant OFFSET throughout thereadout range. Skipped for linear inputs.For readout ranges with a decimal, P31can be set with keys from -19.9 to 19.9.For readout ranges without a decimal, P31can be set with keys from -199 to 199.Default = 0.

R e ad o ut

P3 1

R e a l C u rv e

A d ju s ted C ur ve

Inp u t

P32 = Display protected parametersSkipped when P18 = 0.

OFF = Protected parameters cannot bedisplayed.

On = Protected parameters can be displayed.

P33 = Autotuning (Smart AT)0 = Autotuning disabled.1 = Autotuning is NOT protected by a safety

lock password.2 = Autotuning is protected by a safety lock

password.

Page 21: Barber Colman 7ES

21

P34 = Maximum value of the proportionalband calculated by the autotuningalgorithm. Skipped if P33 = 0. Program-mable from P35 value to 200.0%.Default = 30.0.

P35 = Minimum Value of the ProportionalBand Calculated by the AutotuningAlgorithm. Skipped if P33 = 0. Program-mable from 1.0% to P34 value.

P36 = Minimum Value of the Integral TimeCalculated by the Autotuning Algorithm.Skipped if P33 = 0. Programmable from 1second (00.01) to 2 minutes (02.00).Default = 00.20.

P37 = Relative Cooling Gain Calculated byAutotuning Function. Available only whentwo control outputs are configured andP33 not = 0.

OFF = Autotuning algorithm does notcalculate the rC parameter value.

On = Autotuning algorithm calculates the rCparameter value.

P38 = MANUAL FunctionOFF = Manual is disabled.ON = Manual can be enabled/disabled by the

MAN key or by contact closure on logicinput 2.

P39 =Device Status at Instrument Start-upSkipped when P38 = OFF.

0 = Starts in AUTO mode.1 = Starts in manual mode:

If the time proportioning output is con-figured, the power output will be set to 0.If servomotor control is configured, theinstrument will not modify the valveposition.

2 = Starts with the settings it had prior topower shut down:If the time proportioning output isconfigured and the instrument was inmanual mode, the power output will beset to 0.If servomotor control is configured and theinstrument was in manual mode, theinstrument will not modify the valveposition.

3 = Starts with the settings it had prior topower shut down:If the time proportioning output isconfigured and the instrument was inmanual mode, the power output will besame the as it was prior to power shutdown.

If the servomotor control is configured, theinstrument was in manual mode and P40= "bUnP" the instrument will not modifythe valve position.

If the servomotor control is configured, theinstrument was in manual mode and P40is different from "bUnP," instrument willmodify the valve position to P40.

Page 22: Barber Colman 7ES

22

P40 = Switching from AUTO to MANUALSkipped if P38 = OFF. When P5 ="Sn.OL" and P6 = "no.Fb," then P40 ="bUnP" and cannot be modified.When configured for one control output,P40 can be set from 0 to 100.When configured for two control outputs,P40 can be set from -100 to 100. Above100 the instrument will show "bUnP" andthe transfer will be bumpless (the manualmode starts with an output value equal tothe last value in the auto mode).Note: If P40 is not "bUnP" and an openloop servomotor control with feedbackpotentiometer is programmed, theinstrument will reach P40 using thefeedback indication.

P41 = Conditions for Output Safety ValueWhen P5 not ="Sn.OL" P41 isconfigurable as:

0 = No safety value (default).1 = Safety value applied when overrange or

underrange is detected.2 = Safety value applied when overrange is

detected.3 = Safety value applied when underrange is

detected.

When P5 = "Sn.OL" P41 is configurable as:0 = No safety value (default).4 = When overrange or underrange is

detected the instrument will close theOUT 1 (s) relay contact.

5 = When overrange or underrange isdetected the instrument will close theOUT 2 (t) relay contact.

6 = When overrange or underrange isdetected the instrument will revert to the"standard" effect.Note: For "Standard effect" see "Errormessages."

P42 = Output Safety ValueSkipped when P41 = 0, 4, 5 or 6. Thisvalue can be set from 0 to 100% whenone control output is configured; from -100 to 100% when two control outputsare configured. Default = 0.

P43 = Digital Filter on the Displayed ValuenoFL. = No filter.FLtr = Filter enabled. Applies a digital filter of

the first order to the displayed value witha time constant equal to 4 seconds for TCand RTD inputs, 2 seconds for linearinputs.

P44 = Control Action TypePid = Operates with a PID algorithm.Pi =Operates with a PI algorithm.

P45 = Operating Setpoint Alignment atInstrument Start-up

0 = SP, SP2, SP3 or SP4 according to logicinputs 1 and 3 status.

1 = From the measured value to the selectedsetpoint with a programmable ramp (seeGrd1 and Grd2 operating parameters).

Page 23: Barber Colman 7ES

23

Note: If the instrument detects an out ofrange or an error condition on themeasured value, then P45 = 0.

P46 = Timeout SelectionSets the timeout for the operating mode.tn10 = 10 secondstn 30 = 30 seconds

P47 = Servo Behavior When PID is Limitedby "Sn.LL" and "Sn.HL"

Available only when P5 = "Sn.CL".0 = When PID is higher than "Sn.HL" or lower

than "Sn.LL" the instrument will reach therespective limit value and the outputrelays will remain open.

1 = When PID is higher than "Sn.HL" the OUT1 (s) relay contact stays closed. WhenPID is lower than "Sn.LL" the OUT 2 (t)relay contact stays closed.

P48 = Setpoint IndicationFn.SP =During ramping, the final setpoint will

be displayed.OP.SP = During ramping, the operating

setpoint will be displayed.

P49 = Anti-Reset-Windup ExtensionRange: From -30 to +30% of the propor-tional band. A positive value increasesthe high limit of the anti-reset-windup(over setpoint) while a negative valuedecreases the low limit of the anti-reset-windup (under setpoint). Default = 10.

P50 = Setpoint Access0 = only SP is accessible1 = only SP and SP2 are accessible2 = All four setpoints accessible

Note: Cycle time (Cy1/Cy3) will be updated withthe default value. See notes at P5, P7 and P25in accordance with the last setting.

This completes the advanced configuration pro-cedure. The instrument will show "COnF."

Default Configuration ParametersThe configuration parameters can be loadedwith predetermined default values. These arethe settings loaded into the instrument prior toshipment from the factory. To load the defaultvalues proceed as follows:

a) Open switch V2 (see Figure 1, preliminaryhardware settings).

b) The upper display will show:

c) Press the t key; the lower display willshow the firmware version:

d) Holding the t key press the s key; the

Page 24: Barber Colman 7ES

24

display will show:

e) Press the s key to select table 1(European) or table 2 (American) defaultparameters; the display will show:

f) Press FUNC key; the display will show:

This indicates the loading procedure has beeninitiated. After about 3 seconds the loading pro-cedure is complete and the instrument revertsto "COnF." The following is a list of the defaultconfiguration parameters loaded during the pro-cedure:

PARA. TABLE 1 (European) TABLE 2 (USA)SEr 1 Ero EroSEr 2 1 1SEr 3 19200 19200SEr 4 7E 7EP1 5 23P2 ----. ----.P3 0 0P4 1200 2190P5 SnOL SnOLP6 Fb FbP7 nonE nonEP8 H.A. H.A.P9 nonE nonEP10 H.A. H.A.P11 nonE nonEP12 H.A. H.A.P13 SPEC OPrtP14 750 1380P15 850 1560P16 0.1 0.1P17 0 0P18 0 0P24 nonE nonEP25 AIr AirP26 rEv rEvP27 OFF OFFP28 rEv rEvP29 OFF OFFP30 OFF OFFP31 0 0P32 ON ONP33 2 2P34 30.0 30.0P35 1.0 1.0P36 00.20 00.20P37 OFF OFFP38 ON ONP39 3 3P40 bUnP bUnPP41 0 0P42 0 0P43 nO.FL nO.FLP44 Pid PidP45 0 0P46 10 30P47 0 0P48 Fn.SP Fn.SPP49 10 10P50 0 0

Page 25: Barber Colman 7ES

25

OPERATING MODE

1) Remove the instrument from its case.2) Close switch V2 (see Figure 1, in the

Configuration section.3) Re-insert the instrument in its case.4) Switch on power to the instrument.

DisplaysThe upper display shows the measured valuewhile the lower display shows the programmedsetpoint (this is the normal display mode). Whenthe rate of change (Grd1, Grd2) is used, the dis-played setpoint may be different from the oper-ating setpoint (see P48).

It is possible to change the information on thelower display as follows:• Press and hold the FUNC key for 3

seconds, but not more than 10 seconds.The lower display will show "P." followedby the valve position.

• Press the "FUNC" key again. The lowerdisplay will show " r. " followed by the"rEv" acting (from 0 to 100%) powervalue.

• Press the "FUNC" key again. The lowerdisplay will show " d. " followed by the"dir" acting (from 0 to 100%) power value.

• Press the "FUNC" key again. The displaywill return in "normal display mode."

The information will appear only if the respec-tive function is configured. If no keys arepressed within the timeout period (see P46), the

display will automatically return to the normaldisplay mode.

In order to keep the desired information con-tinuously on the lower display, press the s ort key to stop the timeout. To return to the nor-mal display mode, press the FUNC key again.

Indicators°C Lit when the process variable is

shown in degrees Celsius.°F Lit when the process variable is

shown in degrees Fahrenheit.AT Flashes during autotuning (Smart AT).

Lit steadily when autotuning is active.s Lit when OUT 1 (s) is closed (the

instrument is opening the valve) or isused as a time proportioning controloutput and is in the ON condition.

t Lit when OUT 2 (t) is closed (theinstrument is closing the valve).

OUT3 Lit when alarm 1 is on or OUT 3 isused as a time proportioning controloutput and is ON.

OUT4 Lit when alarm 2 is on. Flashing at aslow rate when alarm 3 is on.Flashing at a high rate when alarms 2and 3 are on.

RMT Lit when the instrument is in REMOTEcondition (functions and parametersare controlled via serial link).

SPX Lit when SP2, SP3 or SP4 is used.Flashes when a temporary setpointfrom a serial link is used.

MAN Lit when the instrument is in theMANUAL mode.

Page 26: Barber Colman 7ES

26

Operating KeysFUNC = When in the normal display mode:

1) Press for less than 3 seconds toenter the parameter modificationmode.2) Press for 3 to 10 seconds tochange the lower display (see"Displays").3) Press for more than 10 seconds tostart a lamp test.During parameter modification, thenew setting of the selected parameteris stored and the next parameter isdisplayed (in increasing order).

MAN =Pressing and holding for more than 1second enables/disables the manualfunction.During parameter modification itscrolls the parameters back withoutstoring the new setting.

s = During AUTO mode, it increases thevalue of the selected parameter.During MANUAL mode, it closes theOUT 1 (s) relay contact.

t = During AUTO mode, it decreases thevalue of the selected parameter.During MANUAL mode, it closes theOUT 2 (t) relay contact.

s+MAN = During parameter modification theyenter the maximum programmablevalue.

t+MAN = During parameter modification theyenter the minimum programmablevalue.

A 10 or 30 second timeout (see P46) can beselected for parameter modification. If no keysare pressed during this time period, the instru-ment goes automatically to the normal displaymode and the last parameter is NOT stored.

Feedback Potentiometer CalibrationThis function is available only if closed loop ser-vomotor control (P5 = "Sn.CL") or a servomotorcontrol open loop with feedback indication(P5="Sn.OL" and P6 = "Fb.") has been selectedduring configuration procedure:

1) Switch On the instrument.2) Press the MAN key for more than one

second. The MAN LED will light and theinstrument will change to MANUAL mode.

3) Repeatedly press the FUNC key until"F.CAL" appears on the lower display.

4) Press the s or t key to select "ON" andpress the FUNC key. The upper displaywill show the valve position (in percent)and the lower display will show themessage "POS.L."

5) Repeatedly press the s or t key to setthe servomotor to the beginning of itsstroke.

6) Press the FUNC key. The display willshow "Fb.LC" (feedback low limitcalibration).

7) Press the s or t key to select "ON" andpress the FUNC key. The upper displaywill show the valve position (in percent)and the lower display will show themessage "POS.H."

Page 27: Barber Colman 7ES

27

8) Repeatedly press the s or t key to setthe servomotor to the end of its stroke.

9) Press the FUNC key. The display willshow "Fb.HC" (feedback high limitcalibration).

10) Press the s or t key to select "ON" andpress the FUNC key. This sets the newfeedback potentiometer calibration andreturns to the MANUAL mode.

Notes:1) The minimum span (Fb.LC - FbHC) for the

instrument is equal to 20% of thepotentiometer stroke.

2) The instrument is able to assure a 1%resolution for the potentiometer indicationonly if the calibrated span is greater than50% of the potentiometer stroke.

Enable/Disable Control OutputWhen the instrument is programmed for servo-motor control, this function is not available.

To disable the control outputs when the instru-ment is in the normal display mode, press andhold (for more than five seconds) the s andFUNC keys. In this open loop mode the devicewill function as an indicator, the lower displaywill show the word OFF and all control outputsand alarms will be OFF. The alarms output con-dition depends on the alarm action type (seeP26 thru P28).

To restore the control outputs, press and hold(for more than five seconds) the s and FUNCkeys. The alarm standby function, if configured,will be activated as if a power-up condition oc-curred. If a shut down occurs when the controloutput is disabled, the control output will re-main disabled at instrument power-up.

Manual ModeMANUAL mode can be accessed (only if P38 =On) by pressing the MAN key for more than onesecond or by closing external contact 2 (seeP24). The key command is accepted and ex-ecuted only if the display is in the normal dis-play mode. Commands from external contactsare always accepted.

When in MANUAL mode the MAN LED will belit. The lower display will show the valve posi-tion (if configured) or power output value if atime proportioning control output is configured.When time proportioning control output is con-figured, the power of the "rEv" output is shownin the two most significant digits while the powerof the "dir" output (if present) is shown in thetwo least significant digits. The decimal pointbetween the two values will be flashing to indi-cate the instrument is in MANUAL mode.

Note: The instrument shows "rEv" output = 100with the graphic symbol " ." The instru-ment shows "dir" output = 100 with the graphicsymbol " ."

Page 28: Barber Colman 7ES

28

Power output can be modified by using the sand t keys. By pressing the MAN key for morethan one second, or by opening contact 2, theinstrument returns to AUTO mode. The trans-fer from AUTO to MANUAL will be in accordancewith the P40 parameter set. The transfer fromMANUAL to AUTO will be bumpless (this func-tion is not provided if integral action is excluded).If the transfer from AUTO to MANUAL is per-formed during the first part of autotuning, (TUNE)when returning to AUTO the instrument will beforced automatically to the second part ofautotuning (ADAPTIVE).

At power-up the instrument will start as deter-mined by P39. When configured for two con-trol outputs and start-up occurs in MANUALmode with power output set to 0, the outputsignal will be in accordance with the formula:

"rEv" output - "dir" output = 0.

When AUTO/MANUAL control is selected bylogic input and P39 = 0 or 1, the instrument startsin accordance to the logic input status and, forMANUAL mode, it will start with a power outputequal to zero.

Direct Access to SetpointsWhen the instrument is in AUTO mode and inthe normal display mode, it is possible to di-rectly modify the selected setpoint (SP, SP2, SP3or SP4). Pressing s or t for more than twoseconds, the setpoint will begin changing. Thenew setpoint value becomes operative at theend of a two second timeout as long as no keysare pressed.

Setpoint SelectionYou can select the operating setpoints only bythe binary combination of logic inputs 1 and 3:Input 3 Input 1 Operating Setpointopen open SPopen close SP2close open SP3close close SP4

With P50, you can limit the number of setpointsavailable.

Serial LinkThe instrument can be connected to a host com-puter by a serial link. The host can put the in-strument in LOCAL (functions and parametersare controlled via keys) or REMOTE (functionsand parameters are controlled via serial link)mode. REMOTE status is signalled by an LEDlabeled RMT. Instrument configuration can bedownloaded through the serial link when the fol-lowing conditions are met:1) Serial parameters from SEr1 to SEr4 are

properly configured.2) The instrument is in OPERATING mode.

During downloading of configuration, theinstrument goes in open loop with alloutputs in OFF state.

Note: It is not possible to perform the feed-back potentiometer calibration or the action per-formed by logic input 2 (Cnt 2) from the seriallink.

At the end of the configuration procedure, theinstrument performs an automatic reset and re-turns to closed loop control.

Page 29: Barber Colman 7ES

29

Autotuning (Smart AT)Autotuning is used to automatically optimize thecontrol action. At instrument power-up, ifautotuning is ON, the second autotuning algo-rithm will be enabled.

When ON/OFF control is programmed (Pb = 0),autotuning is disabled. Autotuning enabling/dis-abling can be protected by a safety key pass-word (see P33).

To enable autotuning, repeatedly press theFUNC key until "Snrt" is shown. Press the sor t key to change the display to "On" andpress the FUNC key. The AT LED will turn on orcontinuously flash according to the selected al-gorithm. When autotuning is enabled, it is pos-sible to display but not to modify the controlparameters (Pb, ti, td, and rC).

To disable autotuning, repeatedly press theFUNC key until "Snrt" is shown. Press the s ort key to change the display to "OFF" and pressthe FUNC key. The AT LED will turn off. Theinstrument will maintain the control parametersand will enable parameter modification.

Lamp TestTo test the display LEDs, press the FUNC keyfor more than 10 seconds. All LEDs will turn onwith a 50% duty cycle. No timeout is appliedto the lamp test. Press the FUNC key again toreturn to the normal display mode. During thelamp test, the instrument continues to controlthe process but no keyboard functions, exceptFUNC, are available.

Operating ParametersPress the FUNC key, the lower display will showthe code while the upper display shows thevalue or status (ON or OFF) of the selected pa-rameter. The s or t key sets the desired valueor status. Press the FUNC key to store the newvalue (or status) and continue to the next pa-rameter.

Some of the following parameters may beskipped depending on the instrument configu-ration.

Param. DescriptionSP Setpoint (in engineering units).

Range from rL to rH. Operative whenlogic inputs 1 and 3 are open.

Snrt Autotuning (Smart AT) status.ON or OFF shows the status ofautotuning (enabled or disabledrespectively).Set to ON to enable autotuning.Set to OFF to disable autotuning.

n.RSt Manual reset of the alarms. Skippedif none of the alarms have manualreset function. Set ON and press theFUNC key to reset the alarms.

SP2 Setpoint 2 (in eng. units). Range fromrL to rH. Operative when logic input3 is open and logic input 1 is closed;and P50 is not 0.

SP3 Setpoint 3 (in eng. units). Range fromrL to rH. Operative when logic input3 is closed and logic input 1 is open;and P50 = 2.

Page 30: Barber Colman 7ES

30

SP4 Setpoint 4 (in eng. units). Range fromrL to rH. Operative when logic input3 is closed and logic input 1 isclosed; and P50 = 2.

nnn Software key for parameter protec-tion. Skipped if P18 = 0 or 1.Set to ON to LOCK the instrument.Set to OFF to UNLOCK the instru-ment.To UNLOCK the instrument, enter theP18 value. To LOCK the instrument,enter a value that is not P18.

AL1 Alarm 1 setpoint (in engineering units).Available only if P7 = AL1.P, AL1.b orAL1.d. Ranges: span limits for processalarm; 0 to 500 for band alarm; -500 to500 for deviation alarm.

HSA1 Alarm 1 hysteresis (in % of P4 - P3 span).Available only if P7 = AL1.P, AL1.b, orAL1.d. Range from 0.1% to 10.0% ofinput span, or 1 LSD. If the hyster-esis of a band alarm is larger than thealarm band, the instrument will use ahysteresis value equal to theprogrammed band minus 1 digit.

AL2 Alarm 2 setpoint (in engineering units).Available only if P9 = AL2.P, AL2.b orAL2.d. Ranges: span limits for processalarm; 0 to 500 for band alarm; -500 to500 for deviation alarm.

HSA2 Alarm 2 hysteresis (in % of P4 - P3 span).Available only if P9 = AL2.P, AL2.b, orAL2.d. Range from 0.1% to 10.0% ofinput span, or one LSD. If thehysteresis of a band alarm is largerthan the alarm band, the instrument

will use a hysteresis value equal tothe programmed band minus 1 digit.

AL3 Alarm 3 setpoint (in engineering units).Available only if P11 = AL3.P, AL3.b orAL3.d; and P13 = OPrt or SPEC.Ranges: span limits for process alarm; 0to 500 for band alarm; -500 to 500 fordeviation alarm. When P13 = SPEC, itallows to select one of the two valuesprogrammed by P14 and P15.

HSA3 Alarm 3 hysteresis. Available only ifP11 = AL3.P, AL3.b, or AL3.d; andP13 = OPrt. Range from 0.1% to10.0% of input span, or 1 LSD. If thehysteresis of a band alarm is largerthan the alarm band, the instrumentwill use a hysteresis value equal tothe programmed band minus 1 digit.Note: alarm 2 and 3 are in ORcondition on the OUT 4.

Pb Proportional band. Range from 1.0% to200.0% of input span. When Pb is set tozero, control action becomes on-off.When instrument is working with SmartAT, Pb value will be limited by P34 andP35.

hyS Hysteresis for on-off control action.Available only when Pb = 0. Rangefrom 0.1% to 10.0% of input span.

ti Integral time (in minutes and seconds[mm.ss]). Skipped if Pb = 0. Rangefrom 0.0 to 10.0 (mm.ss). Above thisvalue the display blanks and integralaction is excluded. When instrumentis working with Smart AT, minimumtime of integral value will be limited

Page 31: Barber Colman 7ES

31

by P36.td Derivative time (in minutes and

seconds [mm.ss]). Skipped if Pb = 0.Range from 00.0 to 10.00. Wheninstrument is working with Smart AT,td will be equal to 1/4 of ti value.When P44 = PI, derivative action isalways excluded.

IP Integral pre-load (in % of the outputspan). Skipped if Pb = 0. Rangesfrom 0.0 to 100.0% of the output ifinstrument is configured with onecontrol output; from -100.0% to100.0% if configured with two controloutputs.

Sn.tt Servomotor travel time (in minutesand seconds [mm.ss]). Available onlywhen P5 = Sn.OL. Range from 0.06to 3.00.

Sn.db Servomotor deadband (in % of thetravel time or of the feedbackpotentiometer span). Available onlywhen P5 = Sn.CL or Sn.OL and Pbnot =• 0. Range from 1% to 50%.

Sn.LL Servomotor low limit (in % of thetravel time or feedback potentiometerspan). Available only when P5 =Sn.CL. Range from 0 to Sn.HL.

Sn.HL Servomotor high limit (in % of thetravel time or feedback potentiometerspan). Available only when P5 =Sn.CL. Range from Sn.LL to 100.

Cy1 OUT 1 cycle time (in seconds).Available only if P5 = rEv or dir.Range from 1 to 200.

Cy3 OUT 3 cycle time (in seconds).Available only if P7 = rEv or dir.Range from 1 to 200

rC Relative Cooling gain. Available onlyif instrument is configured with twocontrol output, and Pb not = 0, orinstrument is in manual mode.Range from 0.20 to 1.00. Wheninstrument is working with Smart ATand P37 is on, rC is limited by coolingmedia: 0.85 to 1.00 when P25 = Air;0.80 to 0.90 when P25 = OIL; 0.30 to0.60 when P25 = H20.

OLAP Deadband/Overlap between H/Coutputs (in % of the proportionalband). Available only if instrument isconfigured for two control outputs,and Pb not = 0, or instrument is inmanual mode. Range from -20 to50% of the Pb. A negative OLAPvalues shows a deadband; a positivevalue shows an overlap.

rL Setpoint low limit (in engineeringunits). Range from minimum rangevalue (P3) to rH. When P3 ismodified, rL will be aligned to it.

rH Setpoint high limit (in engineeringunits). Range from rL to full scalevalue (P4). When P4 is modified, rHwill be realigned to it.

Grd1 Ramp applied to a positive setpointchange (in digits per minute). Rangefrom 1 to 100. Above this value thedisplay shows "InF" meaning that thetransfer will be done as a stepchange.

Page 32: Barber Colman 7ES

32

Grd2 Ramp applied to a negative setpointchange (in digits per minute). Rangefrom 1 to 100. Above this value thedisplay shows "InF" meaning that thetransfer will be done as a stepchange.

OLH Output high limit (in % of the output).Not available if P5 = Sn.CL or Sn.OL.Range from 0.0 to 100.0 wheninstrument is configured with onecontrol output; from -100.0 to 100.0when configured with two controloutputs.

tOL Time duration of the output powerlimiter (in minutes). Not availablewhen P5 = Sn.CL or Sn.OL. Rangefrom 1 to 540. Above this value thedisplay shows "InF" meaning that thelimiting action is always on. The tOLcan be modified, but the new valuewill become operative only at nextinstrument power up.

rnP Control output maximum rate of rise(in % of the output /second).Available when Pb not = 0. Rangefrom 0.1 to 25.0. Above this value,the display shows "InF" meaning thatno ramp limitation is imposed.

Sn.CA Servomotor control action ("rEv" forreverse control action and "dir" fordirect control action). Available whenP5 = SN.CL or Sn.OL. When P24 =nonE or AU.nA, this parameter can bemodified. When P24 = rE.dr, thisparameter can be displayed only.

The following parameters are discussed in the"Feedback Potentiometer Calibration" sectionof this manual.F.CALPOS.LFb.LCPOS.HFb.HC

Error MessagesOverrange, Underrange and Sensor BreakThe instrument can detect a fault on the pro-cess variable (OVERRANGE, UNDERRANGE orSENSOR LEAD BREAK). When the process vari-able exceeds the span limits established by P1an OVERRANGE condition will appear as:

An UNDERRANGE condition will appear as:

When P41 is not zero and an out of range con-dition is detected, the instrument operates inaccordance with P41 and P42.

When P41 = 0 (default) and time proportionaloutputs are configured, the following conditionsmay occur:• When the instrument is set for one output

only and an OVERRANGE is detected,OUT 1 turns OFF (if reverse acting) or ON(if direct acting).

• When the instrument is set for heating/cooling and an OVERRANGE is detected,OUT 1 turns OFF and OUT 3 turns ON.

Page 33: Barber Colman 7ES

33

• When the instrument is set for one outputonly and an UNDERRANGE is detected,OUT 1 turns ON (if reverse acting) or OFF(if direct acting).

• When the instrument is set for heating/cooling and an UNDERRANGE isdetected, OUT 1 turns ON and OUT 3turns OFF.

When P41 = 0 (default) and the servomotor con-trol output is configured, the following condi-tions may occur:• When the instrument detects an

OVERRANGE and reverse action isassigned to the servomotor output, OUT 1(s) turns OFF while OUT 2 (t) turns ON.

• When the instrument detects anOVERRANGE and direct action isassigned to the servomotor output, OUT 1(s) turns ON while OUT 2 (t) turns OFF.

• When the instrument detects anUNDERRANGE and reverse action isassigned to the servomotor output, OUT 1(s) turns ON while OUT 2 (t) turns OFF.

• When the instrument detects anUNDERRANGE and direct action isassigned to the servomotor output, OUT 1(s) turns OFF while OUT 2 (t) turns ON.

Sensor lead breaks can be signalled as:• for TC/mV input: OVERRANGE or

UNDERRANGE (selectedby a solder jumper)

• for RTD input: OVERRANGE• for mA/V input: UNDERRANGE

On the mA/V input the lead break can be de-tected only when the range selected has a zeroelevation (4/20 mA, 1/5 V or 2/10 V). On RTDinput a special test is provided to signalOVERRANGE, when input resistance is less than15 Ohms (short circuit sensor detection).

If the instrument appears to be malfunctioningor operating in an unexplained manner:1. Load default configuration parameters.2. Short inputs.3. Remove outputs.4. Move setpoints to room temperature and

vary the setpoints to see if the controlleroutput responds in expected manner.

Power UpOn power-up, the instrument performs a self-diagnostic test. When an error is detected, thelower display shows the “Err” indication whilethe upper display shows the code of the de-tected error.

Error ListSEr Serial interface parameter error100 EEPROM write error.150 CPU error.200 Attempt to write to protected

memory.201 - 2xx Configuration parameter error.

The two least significant digit’s showthe number of the wrong parameter(ex. 209 Err shows an Error on P9parameter).

Page 34: Barber Colman 7ES

34

299 Error on control output selection.301 Selected input calibration error.302 Feedback potentiometer calibration

error.307 RJ input calibration error.400 Control parameters error.500 Auto-zero error.502 RJ error.510 Error during calibration procedure.512 Error during feedback calibration

procedure.

Dealing With Error Messages1) When a configuration parameter error is

detected, repeat the configurationprocedure of that specific parameter.

2) If error 400 is detected, press the s andt keys to load the default parametersand then repeat the control parametersconfiguration.

3) When an error 302 is detected, press thes and t keys simultaneously to load thedefault parameters and then repeat thecontrol parameter configuration.

4) For all the other errors, contact yourcontroller supplier representative.

Default Operating ParametersThe control parameters can be loaded with pre-determined values. These are the default val-ues loaded in the instrument prior to shipmentfrom the factory. To load the default values pro-ceed as follows:a) The internal switch should be closed.b) Autotuning (Smart AT) must be disabled.c) The upper display will show the process

variable while the lower display will showthe setpoint.

d) Hold the t key and press the s key; thedisplay will show:

e) Press the s or t; the display will show:

f) Press the FUNC key; the display willshow:

This means that the loading procedure has beeninitiated. After about three seconds the loadingprocedure is complete and the instrument re-verts to the normal display mode.

Page 35: Barber Colman 7ES

35

The following is a list of the default operatingparameters loaded during the above procedure:

Param. Default ValueSP = Minimum of range.SnRT = Disabled.n.SRt = OFF.SP2, SP3, Sp4 = Minimum of range.nnn = OFF.A1, A2, A3 = Minimum of range for process

alarms. 0 for deviation or bandalarms.

HSA1, HSA2, HSA3 = 0.1%.Pb = 4.0%.hyS = 0.5%.ti = 4.00 (4 minutes).td = 1.00 (1 minute).IP = 50% for servomotor control drive.

30% for one time proportionalcontrol output.0% for two control outputs.

Sn.tt = 1 (minute).Sn.db = 5 (%).Sn. LL =0 (%).Sn.HL = 100 (%).Cy1 = 15 (seconds). When two control

outputs are configured and OUT1 hasa "dir" action, the Cy1 default valuewill be equal to:10 seconds for P25 = AIr.4 seconds for P25 = OIL.2 seconds for P25 = H2O.

Cy3 = 15 (seconds). When two controloutputs are configured and OUT3 hasa "dir" action, the Cy3 default valuewill be equal to:10 seconds for P25 = AIr.4 seconds for P25 = OIL.2 seconds for P25 = H2O.

rC = 1.00 for P25 = AIr.0.80 for P25 = OIL.0.40 for P25 = H2O.

OLAP = 0.rL = Initial scale value.rH = Full scale value.Grd 1 = Infinite (step transfer).Grd 2 = Infinite (step transfer).OLH = 100%.tOL = Infinite.rnP = 25%/second.SnCA = rEv.

Page 36: Barber Colman 7ES

36

SPECIFICATIONS

GeneralCase: PC-ABS black color; self-extinguishing

degree: V-0 according to UL 94.Front Protection: Designed and tested for

IP65 and NEMA 4X for indoor locations(when panel gasket is installed). Tests wereperformed in accordance with CEI 70-1 andNEMA 250-1991 STD.

Installation: Panel mounting.Rear Terminal Block: 21 screw terminals

(screw M3, for cables from AWG 22 toAWG 14) with connection diagrams andsafety rear cover.

Dimensions: DIN 43700;48 x 96 x 116 mm.(1.890" x 3.780" x 4.567").

Weight 450 g. (1 lb.)Power Supply: 100 to 240 Vac, 50/60 Hz,

-15% to 10% of nominal value; 24 Vac/Vdc,±10% of nominal value.

Power Consumption: 10 VA max.Insulation Resistance: >100 megohms

according to IEC 1010-1.Dielectric Strength: 1500 V rms according to

IEC 1010-1.Display Updating Time: 500 ms.Sampling Time: 250 ms for linear inputs; 500

ms for TC and RTD inputs.Resolution: 30000 counts.Accuracy: ±0.2% f.s.v., ±1 digit @ 25°C

ambient temperature.Common Mode Rejection: 120 dB @ 50/60

Hz.Normal Mode Rejection: 60 dB @ 50/60 Hz.

Electromagnetic Compatibility and SafetyRequirements: Conforms to councildirectives 89/336/EEC (reference harmo-nized standard EN 50081-2 and EN 50082-2) and to council directives 73/23/EEC and93/68/EEC (reference harmonized standardEN 61010-1).

Installation Category: IITemperature Drift (Reference Junction

Excluded):<200 ppm/°C of span for mV and TC ranges1, 3, 5, 7, 21, 22, 23, 25.<300 ppm/°C of span for mA/V.<400 ppm/°C of span for RTD ranges 12and 30, and TC ranges 0, 2, 4, 6, 24.<500 ppm/°C of span for RTD range 11 andTC ranges 8, 9, 26, 27.<800 ppm/°C of span for RTD range 29, andTC ranges 10 and 28.

Operating Temperature: 0 to 50°C.Storage Temperature: -20 to 70°C.Humidity: 20 to 85% rh, non-condensing.Protections: 1) Watchdog circuit for automatic

restart. 2) DIP switch for protection againsttampering of configuration and calibrationparameters.

InputsThermocoupleType: L, J, K, T, N, R, S, B. °C/°F selectable.External Resistance: 100 ohms max.;

maximum error 0.1% of span.Burnout: Shown as an overrange condition

(standard). Possible to obtain anunderrange indication by cut and short.

Page 37: Barber Colman 7ES

37

Reference Junction: Automatic compensation0 to 50°C.

Reference Junction Accuracy: 0.1°C/°C.Input Impedance: >1 megohmsCalibration: According to IEC 584-1 and DIN

43710-1977.Standard Ranges:

Type Range °C Range °F L 0 0 to 400.0L 1 0 to 900 21 0 to 1650J 2 -100.0 to 400.0J 3 -100 to 1000 22 -150 to 1830K 4 -100.0 to 400.0K 5 -100 to 1370 23 -150 to 2500T 6 -199.9 to 400.0 24 -330 to 750N 7 -100 to 1400 25 -150 to 2550R 8 0 to 1760 26 0 to 3200S 9 0 to 1760 27 0 to 3200B 10 0 to 1820 28 0 to 3110

Resistance Temperature DetectorInput: 3 wire Pt. 100 ohms.Input Circuit: Current injection°C/°F Selection: Front pushbuttons or serial

link.Line Resistance: Automatic compensation to

20 ohms/wire with no measurable error.Calibration: According to DIN 43760.Burnout: Detects open condition of one or

more wires. Also able to detect short circuitof sensor.

Standard Ranges:11 -199.9 to 400 °C12 -200 to 800 °C29 -199.9 to 400.0 °F30 -330 to 1470 °F

LinearReadout: Keyboard programmable between

-1999 and 4000.Decimal Point: Programmable in any position.Burnout: Shows as underrange condition for

4 to 20 mA, 1 to 5 V, and 2 to 10 V.Shows as underrange or overrange(selectable by soldering jumper) for 0 to 60mV, and 12 to 60 mV.No indication for 0 to 20 mA, 0 to 5 V or0 to 10 V.

Accuracy: 0.2% + 1 digit @ 25°C.Impedance:

Type13 0 to 60 mV >1 megohms14 12 to 60 mV >1 megohms15 0 to 20 mA <5 ohms16 4 to 20 mA <5 ohms17 0 to 5 V >200 kilo-ohms18 1 to 5 V >200 kilo-ohms19 0 to 10 V >400 kilo-ohms20 2 to 10 V >400 kilo-ohms

Feedback Potentiometer InputType: 100 ohms to 10 kilo-ohms.Minimum Working Stroke: 50% of the

potentiometer range in order to assure the1% display resolution.

Page 38: Barber Colman 7ES

38

Logic InputEquipped with three logic inputs. Inputs 1 and3 are used to select the operating setpoint. In-put 2 function is programmed by P24 param-eter. Use an external contact with a contactrating better than 0.5 mA, 5 Vdc. Instrumentneeds 100 ms to recognize a contact statusvariation. Logic inputs are not isolated by themeasuring input.

SetpointsAllows to use four setpoints: SP, SP2, SP3 andSP4. Selection is possible only by logic inputs1 and 3.Setpoint Transfer: Between one setpoint and

another, or between two different setpointvalues, may be realized by a step transfer orby a ramp with two different programmablerate of change (ramp up and ramp down).

Slope Value: 1 to 100 engineering units/minute or step.

Setpoints Limiter: RLO and RHI parameters,programmable.

Control ActionsControl Action: PID + ATType: One (heating or cooling), or two (heating

and cooling) control outputs.Proportional Band: Range: 1.0 to 200.0% of

the input span. When Pb = 0, control actionbecomes on-off.

Hysteresis (for on-off): 0.1% to 10.0% of inputspan.

Integral Time: From one second to 20minutes, or excluded.

Derivative Time: From one second to 10minutes. If zero is selected, derivativeaction is excluded.

Integral Pre-load: 0.0 to 100.0% for onecontrol output; -100.0 (cooling) to 100.0%(heating) for two control outputs.

Auto-Tuning: Keyboard enable/disable.Auto/Manual: Keyboard selectable.Auto/Manual Transfer: Bumpless. "MAN"

indicator off in auto mode; lit in manualmode.

OutputsThis instrument is equipped with four relay out-puts. OUT 1 can be used either as a servo-motor output (together with OUT 2, both relaysare interlocked), or as an independentrelayoutput. In this case, OUT 2 cannot be used.OUT 3 and OUT 4 are independent relay out-puts. (OUT 4 is optional).

Out 1&2 Out 3 (Relay) Out 4 (Relay)Servomotor AL1 AL2, AL3Heating AL1 AL2, AL3Cooling AL1 AL2, AL3Heating Cooling AL2, AL3Alarms 2 and 3 are in OR condition on theOUT 3 relay.

Control Outputs Updating Time: 250 ms whenlinear input is selected; 500 ms when TC orRTD input is selected.

Action: Direct/reverse, programmable by frontkeyboard.

Output Level Indication: Output 1 and output2 displayed separately.

Page 39: Barber Colman 7ES

39

Output Status Indicator: Four indicators: s,t, OUT3 and OUT4 are lit when therespective output is in the on condition.

Output Level Limiter: For one controlmedium: 0 to 100%; for two controlmediums: from -100 to 100%. This functionmay be operative at instrument start-up forprogrammable time (to avoid thermal shockand/or preheating the plant).

Outputs 1 and 2Type: Two relays, interlocked. SPST, NO

contact.Contact Rated: 3 A @ 250 Vac on resistive

load.

Output 3Type: Relay, SPST contact.Contact Rated: 2 A @ 250 Vac on resistive

load.Note: Side C of OUT 3 and OUT 4 are common.

AlarmsActions: Direct or reverse.Functions: Each alarm can be configured as

process, band or deviation.Reset: Automatic or manual programmable on

each alarm.Stand-by (mask) Alarm: Each can be config-

ured with or without stand-by function. Thisfunction allows to delete false indication atinstrument start-up and/or after a setpointchange.

Process AlarmOperating Mode: High or low programmable.Setpoint: Programmable in engineering units

within input span.Hysteresis: Programmable from 0.1% to

10.0% of input span (P4-P3).

Band AlarmOperating Mode: Inside or outside program-

mable.Setpoint: Programmable from 0 to 500 units.Hysteresis: Programmable from 0.1% to

10.0% of input span.

Deviation AlarmOperating Mode: High or low programmable.Setpoint: Programmable from -500 to 500

units.Hysteresis: Programmable from 0.1% to

10.0% of input span.

Serial Communications InterfaceType: RS-485.Protocol Type: MODBUS, JBUS, proprietary

polling/selecting.Baud: Programmable from 600 to 19200.Byte Format: 7 or 8 bit, programmable.Parity: Even, odd or none, programmable.Stop Bit: One.Address: 1 to 95 for proprietary protocol; 1 to

255 for all other protocols.Output Voltage Levels: According to EIA

standard.

Page 40: Barber Colman 7ES

40

CALIBRATION

Calibration parameters are logically divided intogroups of two parameters each – initial scalevalue and final scale value. A calibration checkis provided after entering the values of eachgroup. A calibration check can be initiated with-out making an entry: press the FUNC key toadvance to the desired calibration check. Thelower display will show the parameter code (t.,rJ., etc.) and the upper display will show “on”or “off.” Press the s or t key to select on oroff.

To go to the next parameter without modifyingthe calibration, press the FUNC key when thedisplays shows “off.” To return the previous pa-rameter without modifying the calibration, pressthe MAN key.

To set the parameter calibration, press the FUNCkey when the display shows “on.” The displaywill blank, and only the decimal point of the LSDof the lower display will be lit during the calibra-tion step.

Before beginning calibration, be sure internalswitch V2 is open (see "Preliminary HardwareSettings," Figure 1).

General Guidelinesa) The instrument should be mounted in its

case in order to keep the internaltemperature constant.

b) Ambient temperature should be stable.Avoid drift due to air conditioning or othermechanical devices.

c) Relative humidity should not exceed 70%.d) Minimum warm up time should be at least

20 minutes.e) Operate as much as possible in a noise

free environment.f) During calibration, connect one input at a

time to the rear terminal block.g) Before input calibration, the specific

preliminary hardware settings describedinthe Configuration section must be made.

h) Use calibrators with the following:AccuracyCurrent Input:

±0.025% output±0.0025% range±0.01 microamp

Voltage Input:±0.005% output±0.001% range±5 microvolt

TC Input:±0.005% output±0.001% range±5 microvolt

RTD Input:±0.02%±0.0025 ohms/decade

Reference JunctionCompensation:better than 0.1°C

mA output: better than ±0.1% of thereadout ±2 microamp

Page 41: Barber Colman 7ES

41

ResolutionCurrent Input: 0.5 microampVoltage Input: 100 microvoltTC Input: 1 microvoltRTD Input: 10 milliohmRef. Jct. Compensation: better than 0.1°CmA output 1 microamp

Calibration Parameters

Following is a complete list of calibration sym-bols:Code ParametertL TC/mV Input Minimum Range ValuetH TC/mV Input Maximum Range Valuet. TC/mV Input CheckrJ Reference Junction CompensationrJ. Reference Junction Compensation

CheckPL RTD Input Minimum Range ValuePH RTD Input Maximum Range ValueP. RTD Input ChecknAL Current Input Minimum Range Value

(0 mA)nAH Current Input Maximum Range Value

(20 mA)nA. Current Input Check5UL 5 Volt Input Min. Range Value (0 V)5UH 5 Volt Input Max Range Value (5 V)5U. 5 Volt Input Check10UL 10 Volt Input Minimum Value (0 V)10UH 10 Volt Input Maximum Value (10 V)10U. 10 Volt Input Check

ProcedureSwitch on the instrument; the upper display willshow “COnF”. Press the s key and the displaywill show “CAL”. Press the “FUNC” key to startthe calibration process. Repeatedly press theFUNC key until the desired calibration (parameter)code appears.

Use the s and t keys to select between ONand OFF. To go to the next parameter withoutmodifying the calibration, press the FUNC keywhen the display shows “OFF” .

tL TC/mV input minimum range valuea) Perform the preliminary hardware settings

described in the Configuration section;connect the calibrator and instrument asshown below. The displays show “OFF”and “tL”.

1

3

c) Set calibrator to 0.000 mV.d) Press the s key; the display changes to

“ON”.e) After a few seconds, start calibration by

pressing the FUNC key. The decimalpoint of the least significant digit will lightto indicate the instrument is performingthe calibration. When calibration iscomplete, the instrument will proceed tothe next parameter.

Page 42: Barber Colman 7ES

42

tH TC/mV input maximum range valuea) Set the calibrator to 60.000 mV.b) Press the s key; the displays will show

“ON” and “tH”.c) After a few seconds, start calibration by

pressing the FUNC key. The decimalpoint of the least significant digit will lightto indicate the instrument is performingthe calibration. When this calibration iscomplete, the instrument will proceed tothe next parameter.

t. TC/mV input checkThe display will show “t.” followed by a num-ber showing the measured value in counts.

Check the linear calibration by setting:a) 0.000 mV; the readout must be equal to

“t.0 0000” ±10 counts.b) 60.000 mV; the readout must be equal to

“t.3 0000” ±10 counts.c) 30.000 mV; the readout must be equal to

“t.1.5000” ±10 counts.d) Press the FUNC key; go to the next

parameter.

rJ Reference junction compensationNote: Make sure tL and tH are correctly cali-brated before attempting rJ calibration.

a) Measure the temperature close toterminals 1 and 3 using an appropriateinstrument, as shown below.

1

3

M ea su ring D ev ice

+

-

b) Wait a few minutes to allow temperaturestabilization of the entire system (compen-sation cable, sensor, calibrator andinstrument).

c) The displays will show “rJ” and “OFF.”Use the s and t keys to make thereadout value equal to the temperaturemeasured by the measuring device intenths of °C.

d) After a few seconds, start calibration bypressing the FUNC key. The decimalpoint of the least significant digit will lightto indicate the instrument is performingthe calibration. When this calibration iscomplete, the instrument will proceed tothe next parameter.

rJ. Reference junction compensation checkThe display will show “rJ.” and the temperaturein tenths of °C. Check that the display readoutis equal to the value read by the measuring de-vice.

Press the FUNC key; the instrument will pro-ceed to the next parameter.

Page 43: Barber Colman 7ES

43

PL RTD input minimum range valuea) Perform the preliminary hardware settings

described in the Configuration section.Connect the calibrator and instrument asshown below.

1

4

3

b) Set 0.00 ohms on the resistor box.c) Press the s key; the displays show “ON”

and “PL”.d) After a few seconds, start calibration by

pressing the FUNC key. The decimalpoint of the least significant digit will lightto indicate the instrument is performingthe calibration. When this calibration iscomplete, the instrument will proceed tothe next parameter.

PH RTD input maximum range valuea) Set resistor box to 375.00 ohms.b) Press the s key; the displays will show

“ON” and “PH”.c) After a few seconds, start calibration by

pressing the FUNC key. The decimalpoint of the least significant digit will lightto indicate the instrument is performingthe calibration. When this calibration iscomplete, the instrument will proceed tothe next parameter.

P. RTD input checkThe display shows “P.” followed by a numbershowing the measured value in counts.

Check the calibration (not linear) by setting theresistance box to:a) 0.00 ohms; the readout should be

“P. 0 0000” ±10 counts.b) 125.00 ohms; the readout should be

“P.1 0190” ±10 counts.c) 250.00 ohms; readout should be

“P. 2 0189” ±10 counts.d) 375.00 ohms; readout should be

“P. 3 0000” ±10 counts.e) Press the FUNC key and proceed to next

parameter.

nAL Current input (mA) minimum range valuea) Perform the preliminary hardware settings

described in the Configuration section;connect the calibrator and instrument asshown:

1

3

b) Set 0.000 mA on the calibrator (even if theminimum range value is 4 mA). The upperdisplay shows “OFF.”

c) Press the s key, the display will switch to“ON”.

Page 44: Barber Colman 7ES

44

d) After a few seconds, start calibration bypressing the FUNC key. The decimalpoint of the least significant digit will lightto indicate the instrument is performingthe calibration. When this calibration iscomplete, the instrument will proceed tothe next parameter.

nAH Current input (mA) maximum rangevalue

a) Set 20 mA on the calibrator.b) Press the s key, the displays will show

“nAH” and “ON”.c) After a few seconds, start calibration by

pressing the FUNC key. The decimalpoint of the least significant digit will lightto indicate the instrument is performingthe calibration. When this calibration iscomplete, the instrument will proceed tothe next parameter.

nA. Current input (mA) checkThe display will show “nA.” followed by a num-ber showing the measured value in counts.

Check the linear calibration by setting the cali-brator to:a) 0.000 mA; the readout should be

“nA. 0 0000” ±10 counts.b) 20.000 mA; readout should be

“nA. 3 0000” ±10 counts.c) 10.000 mA; readout should be

“nA. 1 5000” ± 10 counts.d) Press the FUNC key.

5UL 5 volt input-minimum range valuea) Perform the preliminary hardware settings

described in the Configuration section.Connect the calibrator and instrument asshown:

1

3

b) Set 0.000 V on the calibrator (even if theminimum range value is 1 V). The upperdisplay will show “OFF.”

c) Press the s key, the display will show“5UL” and “ON.”

d) After a few seconds, start calibration bypressing the FUNC key. The decimalpoint of the least significant digit will lightto indicate the instrument is performingthe calibration. When this calibration iscomplete, the instrument will proceed tothe next parameter.

Page 45: Barber Colman 7ES

45

5UH 5 volt input-maximum range valuea) Set 5.000 V on the calibrator.b) Press the s key, the display will show

“5UH” and “ON”.c) After a few seconds, start calibration by

pressing the FUNC key. The decimalpoint of the least significant digit will lightto indicate the instrument is performingthe calibration. When this calibration iscomplete, the instrument will proceed tothe next parameter

5U. 5 volt input checkThe display will show “5U.” followed by a num-ber showing the measured value in counts.

Check the calibration by setting the calibratorto:a) 0.000 V; the readout should be

“5U. 0 0000” ±10 counts.b) 5.000 V; readout should be

“5U. 3 0000” ±10 counts.c) 2.500 V; readout should be

“5U. 1 5000” ± 10 counts.d) Press the FUNC key to proceed to next

parameter.

10UL 10 volt input - minimum range valuea) Perform preliminary hardware settings as

described in the Configuration section.Connect the instrument to the calibratoras shown:

1

3

b) Set 0.000 V on the calibrator (even if theminimum range value is 2 V). The upperdisplay will show “OFF”.

c) Press the s key to enable calibration.The upper display will switch to “ON”.

d) Wait a few seconds until the measurementhas stabilized, then push the FUNC key.When calibration is complete, theinstrument will go to the next parameter.

10UH 10 volt input-maximum range valuea) Set 10.000 V on the calibrator.b) Press the s key, the display will show

“10UH” and “ON”.c) After a few seconds, start calibration by

pressing the FUNC key. The decimalpoint of the least significant digit will lightto indicate the instrument is performingthe calibration. When this calibration iscomplete, the instrument will proceed tothe next parameter

Page 46: Barber Colman 7ES

46

10U. 10 volt input checkThe display will show “10U.” followed by a num-ber showing the measured value in counts.

Check the calibration (linear) by setting the cali-brator to:a) 0.000 V; the readout should be

“10U.0 0000” ±10 counts.b) 10.000 V; readout should be

“10U.3 0000” ±10 counts.c) 5.000 V; readout should be

“10U.1 5000” ±10 counts.d) Press the FUNC key.

This completes the calibration procedure. Toenter the configuration procedure press the skey, the display will show “CnF”. If configura-tion and calibration are complete, switch the in-strument off and set the DIP switches accord-ing to the Configuration section.

Page 47: Barber Colman 7ES

47

MAINTENANCE1) Remove power from power supply

terminals and from relay output terminals.2) Remove instrument from its case.3) With a vacuum cleaner or compressed air

(max. 3 kg/cm2), remove all deposit ofdust and dirt on louvers and internalcircuits. Be careful not to damage internalcomponents.

4) Clean external plastic or rubber parts withcloth moistened with Ethyl Alcohol (pureor denatured) C

2H

5OH, or isopropyl

alcohol (pure or denatured) [(CH3)2CHOH],or water (H2O).

5) Verify that there are no loose terminals.6) Before re-inserting the instrument in its

case, be sure it is perfectly dry.7) Re-insert the instrument and turn it on.

Page 48: Barber Colman 7ES

Barber-Colman CompanyIndustrial Instruments Division1354 Clifford AvenueP.O. Box 2940Loves Park, IL U.S.A. 61132-2940

Telephone +1 800 232 4343Facsimile +1 815 637 5341http://www.barber-colman.com

A Siebe Group CompanyCopyright © 1997 Barber-Colman Company.