43
1 BABCOCK BOILER UAN WEST 1 TO 6 Operation Manual Prepared By Ashek Ullah

BABCOCK BOILER 1 - 6 Instruction Manual

Embed Size (px)

Citation preview

Page 1: BABCOCK BOILER 1 - 6 Instruction Manual

1

BABCOCK BOILER UAN WEST 1 TO 6

Operation Manual

Prepared By Ashek Ullah

Page 2: BABCOCK BOILER 1 - 6 Instruction Manual

2

Table of Contents

A. BOILER 1 TO 6 :

1. TECHNICAL DATA 2. START UP PROCEDURE

i. COLD ii. WARM iii. HOT

3. FIRING SYSTEM

i. NATURAL GAS ii. CRUDE OIL

4. SHUT DOWN PROCEDURES

i. NORMAL ii. EMERGENCY SHUT DOWN

5. OPERATION OF SOOT BLOWING SYS. 6. INTER LOCKS

7. ALARMS & PROTECTIONS 8. ISOLATION BOILER MAJOR AUXILIARY EQUIPMENTS

i. BOILER FEED WATER PUMPS ii. BOILER F.D. FANS iii. COOLING AIR FANS iv. LP GAS REDUCING STATIONS v. CRUDE OIL TRANSFER PUMPS vi. BURNER CRUDE OIL PUMPS vii. BOILER GAS / CRUDE OIL BURNER viii. BOILER FW CONTROL VALVES ix. DEAERATOR STEAM REDUCING STATION x. SH ATTAMPERATER SPRAY WATER xi. BOILER WASTE DRAIN PUMS. xii. MAJOR OVERHOLING xiii. BOILER TUBE LEAK

Page 3: BABCOCK BOILER 1 - 6 Instruction Manual

3

A - 1.BOILER TECHNICAL DATA: (For individual unit only)

BOILER (1 – 6) TECHNICAL DATA:

DESIGN DATA OPERATING DATA PRESENT DATA

A. BOILER - :

Max. Continuous loading = 365 t /h

Min. stable loading = 73 t / h

Design pressure = 86,4 bar

Drum pressure = 80,8 bar

Super Heater Outlet temp .=490 0 C

Super heater Outlet press = 66.7 bar

Feed water Inlet temp. = 140 0 C

B) FIRING EQUIPMENTS -:

Note- it is possible to operate the Boiler either with N. Gas or Crude oil or N. Gas and Crude oil during the same time : but not in same burner.

1. Natural Gas Burner -:

Type of Burner =6 multi speed lances

Number of Burner= 9 nos.

Design net calorific values -:

a) 10450 K.cal / Nm3

b) 11000 K. cal / Nm3

Cap. Of burner Nozzle 3083 Nm3 / h

Min. Gas press. Before burner 0.05 bar

Max. Gas press. Before burner 1 . 2 bar

Turn down ratio of burner 1 to 4

2. Type of Burner = Swirl parallel flow

Type of Nozzle = 15 / 10 YELN 385243 100

Number of Burners 9 nos.

Design net calorific value= 9989 K. cal/ kg

Cap. of burner Nozzle =3253 kg / h

Min. Crude oil flow before burner= 5.0 bar

Max. Crude oil flow before burner= 16.0 bar

at 100 % load = 1 %

at 50 % load = 1 % Excess Air ( O2 )

at 20 % load = 3 ,4 %

Turn down ratio of burners = 1 to 4

Note- to be able to start the boiler from cold with crude oil burner 7, 8 & 9 with atomizing Air.

Atomizing air press. before burner = 6.0 bar

Auto. steam press. outlet Red. station 13.5 bar

Auto steam temp. before burner 225 o C

3. Ignition burner -:

Type = High voltage ignito. Drug. 400 - 43 Ex / D - 2L 400

NO. of Burner 9 nos.

4. LP Gas Station - :

Inlet Press. 6 to 8 bar

Out Let press. 4.0 bar

Capacity of each station 30 ,00 Nm3

Number of Station 2 nos.

Page 4: BABCOCK BOILER 1 - 6 Instruction Manual

4

C. Pumps & Fans

Flow 200 m3 / h

Nor. Head 1120 m WC

Req. Power 803 kW

Speed 2980 r.p.m.

NO. of Pump 3 nos.

1. Boiler Feed water Pump: - (RL111A1,RL12A1 & RL13A1)

Max. Amps. 120 A

Flow 270 t / h Nor. Head 110 m WC

Req. Power 104.85 kW

Speed 1450 r.p.m.

Max. Amps. 240 A

2. Clean drain pump (RU11A1 & RU12A1)

NO. of Pump 2 nos.

Flow 70 m3 / h

Nor. Head 49.6 m WC

Req. Power 14.86 kW

Speed 2900 r.p.m.

3. Service water pump ( VG

NO. of pump 2 nos.

Flow 100 t / h Nor. Head 50 m WC

Speed 2900 r.p.m.

4. Make up water pump ( UA

NO. of pump 3 nos.

Flow 90 to 110 t / h Nor. Head 8 to 10 m WC

Speed 1450 r.p.m.

5. Waste drain pump ( RT

NO. of pump 2 nos.

6. Waste drain pit over flow pump ( ?

Flow 36.9 m3 / h

Nor. Head 18.3 bar

Req. Power 47 kW

Speed 2960 r.p.m.

7. Crude oil burner pump (NM21A1 & NM22A1)

NO. of Pump 2 nos.

Flow 62 Nm3 /sec (223700 Nm3 / h)

Nor. Head 827 m WC

Req. Power 578 kW

Speed 1490 r.p.m.

NO. of Fan 2 nos.

8. FD Fan (NG11A & NG12A1)

Max. Amps. 80 A

Flow 1073 Nm3 / h Nor. Head 106.5 m WC

Req. Power 25 kW

Speed 2965 r.p.m.

9. Cooling Air Fan ( NK51A1 & NK52A1)

NO. of fan 2 nos.

Page 5: BABCOCK BOILER 1 - 6 Instruction Manual

5

A – 2, BOILER START UP: -

According to the boiler temperature, distinguish three start- up modes: -

i. Cold Start : it may be classified either boiler evaporator & superheater temperature as environment level or start up after periodical inspection or overhauling.

ii. Warm Start : after down time of 24 hours, the boiler pressure of approx. 10 bars and

evaporator & superheater temperature approx. 180 oC. iii. Hot Start : after a downtime of 8 hours, the boiler pressure approx. 40 bars and

evaporator & superheater temperature approx. 300 oC. If necessary, boiler will be re-fed as low water level. The FW temperature amounts to approx. 100 o C.

2 – 1. a. PREPARATION TO START UP: -

Before start up the boiler check that the following items are fulfilled: -

i. All maintenance or inspection works at boiler or auxiliaries has to be completed and all work permits must be cancelled.

ii. Combustion chamber, flue gas passes and flue gas ducts are cleaned and all manholes are closed.

iii. Boiler drum cleaned and both manholes are properly tied. Level indicators are cleaned. iv. The soot blowers should be in their retracted position. v. All auxiliaries of the unit must be ready for operation e.g. all oil levels at pumps, motors and

gears are checked and topped up. vi. All dampers, vanes etc. are greased. vii. All safety instructions have to be checked about proper and exact functioning e.g. safety &

relief valves. viii. All by pass valves in regulating loops should be closed and all regulating valves checked

about proper working conditions. ix. All chemical analysis has to be in working order, cation filters are regenerated etc. x. The isolating valves of all indications or transmitters impulse line must be open. xi. All electric breakers should be in working place.

xii. The T.V. cameras for boiler furnace and drum level indication are ready for service but the furnace camera kept in operation before 1st burner fire.( N / A )

xiii. Check waste water drain pumps and grease pots are filled xiv. Check service water pumps; related water basin & over head tank. xv. Check instrument air compressors , dryers & reserve tank. xvi. Check service air compressors & reserve tank. xvii. Check emergency diesel air compressors. xviii. Check make up water pumps xix. Check instrument air supplied all consumers. xx. Power supplied to burners cubicle HB1-4 switch ON.

Page 6: BABCOCK BOILER 1 - 6 Instruction Manual

6

2 – 1. . PREPARATION TO START UP: -

a. CONDITION OF THE MOTERIZE VALVE

Circuit breakers of the motorized valve Valve position

FW Stop valve - 1 RL41G201 Working position Closed

FW Stop valve - 2 RL42G201 Working position Closed

FW Stop valve - 3 RL43G201 Working position Opened

FW Control valve - 1 RL41G401 Working position Closed

FW Control valve - 2 RL42G401 Working position Closed

FW by pass valve - 3 RL43G401 Working position Closed

FW inter Connection valve RL70G201 Working position Closed

Main FW stop valve to boiler NA 1G201 Rack out Closed

Start up stop valve NA70G201 Working position opened

Start up Control valve NA70G401 Working position Opened 50 %

Attamp. spray water valve - 1 NA51G401 Working position Closed

Attamp. spray water valve - 2 NA52G401 Working position Closed

Drum drain valve NC15G401 Working position Closed

SH - 1 drain valve NC

33G401 Working position opened

SH - 2 drain valve NC

40G401 Working position opened

SH - 3 drain valve NC

49G401 Working position opened

Boiler HP steam stop valve & by pass valve

NA49G201 Working position Closed

Boiler blow down valve RZ16G401 Working position Closed

Spray water inter connection valve RL73G401 Working position Closed

Page 7: BABCOCK BOILER 1 - 6 Instruction Manual

7

b. CONDITION OF THE HAND OPERATED VALVE

HAND OPERATED & MOTOR OPERATED VALVE POSITION

Remarks

Supporting tube outlet header drain valve ( SH – 1)

NC 33 G 1 Open

Super Heater - 2 drain valve NC 40 G1 Open

HP steam line SH – 3 outlet drain valve NC 49 G 1 open

Evaporator drain valves NC 23 G11 upto NC23 G 71

Open

Evaporator header drain valves NC 91 G 81 / 82 Closed

Economizer drain valves NC 6 G 1 / G2 Closed

Boiler drum drain valve NC 15 G 1 Closed

Saturated steam header vent valve NC 28 G1 / G2 2 turns open

Economizer inlet vent valves NC 2 G1 / G2 2 turns open

Attamp. - 1 vent valve NC 38 G 1 / G 2 2 turns open

Superheater – 3 vent valve NC 46 G 1 / G 2 2 turns open

Feed water supply line to Distiller valve RL 80 G 1 Closed RL 72 G 1 Closed RL 73 G 1 Closed RL 53 G 1 Closed

RL 53 G1 Closed

NA 54 G1 Closed

NA 55 G1 / G2 Closed

NA 56 G1 Closed

Isolating valves of Spray water control valves

NA 56 G2 Closed NA 51 G1 / G2 Open Isolating valves of Spray water control

valves NA56 G1 / G2 Open

RL- 70 G1

RL - 30 G8 Vent FW line up to FW control station RL - 40G7

Open slowly , after venting over, valves closed

FW Stop valve ( by pass station) RL 43 G201 Open fully

FW control valve ( by pass station) RL43G401 Open stepwise upto 15 %

Vent FW line before Eco. 1 inlet ( direct vent)

RL 60 G5 / G6 Open partially.

Boiler filling valves at ‘0’ meter level NC 1 G1/ G2 Open slowly Control FW flow through control valve RL 43 G401 Flow approx. 30 t / h

Watch FW tank level Maintain normal level.

Watch economizer venting NC 2 G1 / 2

after venting completed closed vent valves

Watch boiler drum level locally & TCR When low level alarm disappeared ( > 100 mm) closed RL43 G401 & filling valves NC1 G1 / 2

Closed evaporator drain valves NC 23 G11 up-to NC23 G 71

Closed

FW Stop valve ( by pass station) RL 43 G201 Closed fully

FW control valve ( by pass station) RL43G401 Closed fully

FW main stop valve to boiler NC 1G201 Elec. CB rack in & open

Fill up the boiler drum up to > HH RL 43 G201 Open full

RL 43G401 Open stepwise up to 15 %

Open the boiler drain valve kept operation level ( - 200 mm)

Page 8: BABCOCK BOILER 1 - 6 Instruction Manual

8

A – 2. 2. BOILER FEED WATER TANK FILLING UP : -

2.2.1 Inform Lab. boiler start up program , & prepared to fill the boiler feed water tank up to normal level ~ 2.6 m:-

� Before filling the FW tank, check the following valves are in their correct position or not.

• drain valve of FW tank closed,

• vent valve of deaerator 1 turn opened.

• over flow valve must be closed & Selection in ‘AUTO’ position.

• all isolating valves of level transmitters etc. must be opened. � It may fill FW tank either with the direct make up water filling valve (UA2G201) or with turbine

condensate pumps if the condensate water conductivity as usable condition.

2 – 2. 1. FEED WATER PUMP START UP: -

After FW tank level filled: - �

2.3. Prepared to start any one FW pumps ( RL 11, 12 & 13A1): - i. FW pumps suction, lubricating oil & gland sealing water filters should be cleaned & installed. ii. Checked all filters ∆P iii. pump & suction filter drain valves closed iv. Suction filters & sealing water filters properly vented. v. Pumps suction side manual valves (RL11, 12,13G1) are fully opened. vi. Isolating valves of all pressure switches & pressure transmitters opened. vii. Pumps discharge by pass manual valves (RL21G2/G3, 22G2/G3, 23G2/G3) Closed. viii. Pumps motorize discharge isolating valves (RL 21, 22 & 23G201) Closed. ix. Pumps balancing water isolating valves (RL24, 26,28G2) opened. x. Pumps minimum flow manual isolating valves (RL25, 27,29G2) opened. xi. Sealing water isolating valve open. xii. Oil levels in the lube oil tanks are normal. xiii. Lub. Oil pumps oil discharge line isolating valve opened.

Page 9: BABCOCK BOILER 1 - 6 Instruction Manual

9

xiv. A/C & D/C Lube oil pumps, FW pumps & discharge valves Elec. Circuit breakers are in working position.

xv. Start a / c lube oil pump from TCR xvi. Check lube oil pressure & flow each for bearing. xvii. Lube oil coolers cooling service water isolating valves opened & check cooling water flow through the lube oil coolers. xviii. EM push buttons of the FW pumps released. xix. FW pumps Selector switch in TCR. xx. Start one of the FW pumps, watch amp. meter xxi. FW pump discharge by pass valve (RL21G2/3, 22G2/3, and 23G 2/3 gradually open; wait for pressure

equalization ~ 130 bars. xxii. Pumps discharge valves (RL21, 22 & 23G201) open step by step. xxiii. Pumps discharge by pass valves (RL21G2/G3, 22G2/G3, 23G2/ G3) closed. xxiv. Start one of the reserve pump’s a/c lube oil pump & Select the FW pump in ‘AUTO’.

Page 10: BABCOCK BOILER 1 - 6 Instruction Manual

10

A - 2. 3. PREPARE TO FILL UP BOILER: - PRE – CONDITIONS: ONE FW PUMP INSERVICE & THE FOLLOWING MOTORIZED VALVES C.V ARE IN WORKING POSITION.

1. FW stop valves 1, 2 & 3 ( RL41,42 & 43G201). 2. FW control valves RL41, 42 & 43G401. 3. Start up stop valve NA70G201 4. Start up Control valve NA70G401 5. Spray water Valve (attempt.)NO.1 & NO.2 NA51 & 52G401 6. Drum drain valve NC15G401 7. SH NO. 1,2 & 3 drain valves NC33/40G401,NC49G401. 8. HP steam stop valve of boiler and by pass valve 9. Boiler blow down valve RZ16G201. 10. Spray water valves RL72, 73G401.

• Open slowly vent valves RL70G1 & RL30G8 in the FW control station, if water continuously flowing out, close vent valves.

11. open fully FW stop valve RL43G201 12. Open step wise FW control valve RL43G401~ 15 % 13. Open FW vent line valves RL60G5 & G6.

• before economizer NO.1 , when water continuously flowing out, close vent valves. 14. Open stepwise boiler filling valves NC1G1 & G2 15. Control FW flow approx. 30 t / h through RL43G401. 16. Watch FW tank level, maintain its normal level by feed valve.

• Check economizer vent valve NC2G1 & G2, if water continuously flowing out, close vent valves. 17. watch boiler drum level indicator, when low level signal disappeared, ( - 100 mm) *

• some times it was observed that, drum filled upto HH level for hydraulic test & later drain excess water .

• closed FW line valve RL43G401

• Close filling valve NC1G1 & G2 18. Close evaporator drain valves , NC23G11 to NC23G72 19. Boiler FW main stop valve RL60G201 C.B. rack in & open 20. Maintain drum level - 200 mm; open RL43G201 fully & throttle FW flow approx. 30 t / h through valve

RL43G401.

Page 11: BABCOCK BOILER 1 - 6 Instruction Manual

11

BOILER FILLING UP FLOW DIAGRAM

Page 12: BABCOCK BOILER 1 - 6 Instruction Manual

12

A – 2. 4. Cold Start-up of the Boiler I. by NATURAL GAS -:

Conditions:-

• boiler filled starting level ( - 200 mm)

• Main Gas Red. Station in operation ( HP Gas .Red. station)

• One Condensate pump in service.

• One Feed Water pump in service.

1. Check all manholes on boiler and air ducts are closed. 2. Check instrument air supplied to all consumers. 3. power supplied to burners cubicle HB1-4 switch ON. 4. HP Gas Red. Station outlet press. ~ 7.00 bar.

Page 13: BABCOCK BOILER 1 - 6 Instruction Manual

13

LP GAS RED. STATION

5. Open inlet valve of both LP gas red. station NN2G1 & NN7G1. 6. Closed valve in nitrogen and vent lines. 7. Fill LP gas red. Station and waiting for press. equalization ~ 6.0 bar,

• by opening the by pass valve NN3G4 and NN8G4. 8. Open natural gas quick closing valve (NN8G401, NN3G401) by pressing the hand levers.

• An switch ON the Stop valve 9. Check proper function of LP gas red. Station valves.

• by opening the vent valve ( NN5G1, NN10G1) pressure drop,

• and watch press. after red. Station valve at ~ 3.9 bar and 4.0 bars respectively;

• then close the vent valves. 10. Open outlet valve of LP gas red. Station (NN3G1, NN8G1). 11. Check the position of natural gas control valve (NN20G401.

• It must be close position. 12. Open the natural gas relief valve, NN34G801 from TCR desk.

13. Circuit breakers of Cooling air fans working position.

• and EM. Push button released & Select Switches in TCR position. 14. Check all cooling air valves to photo cell are opened. 15. Start one of the cooling air fan. NK51A1 or NK52A1 from TCR desk.

• cool Air press. Low signal ‘ disappear ‘ 16. Select 2

nd Cooling air Fan NK52A1 to ‘AUTO’ position.

17. Tripped the running fan by pressing EM. Push button from local , Sel. ‘Auto’ stand by will take place 18. Release EM. Push button & Sel. he Fan NO. in AUTO position ;

• Press EM button of the 2nd

running fan, after tripped 1st one will take place.

19. Prepare the FD Fan NO.1 & NO.2.

� Check the oil level. � Check the function of the fans dampers and vanes. � put circuit breakers in working position. � Make sure that, hand operated dampers in the air ducts are opened. � Released EM. Push buttons of the both Fans. � Sel. Switch of both Fans in TCR position.

20. Start of the FD fans from TCR desk on ‘AUTO’ program or ‘MAN’ Selection for purging.

21. Purging Program: - (Time Setting 160 Seconds & rate of air volume 2950 m

3 / min or 177,000 m

3 / hr.)

[ Boiler purging means, clear the boiler furnace & down stream flue gas paths upto chimney inlet by a sufficient volume of air to get rid ( make free) of undesirable elements in order to safe guard the equipment against any explosion]

PRECONDITIONS:-

Connecting the interlock setting of the boiler main protection & firing interlocks systems established.

• i. Emergency push buttons released.

• ii. Control air pressure > min.

• iii. Boiler release existing means that the following interlocks are fulfilled �. a) Furnace pressure < min. b) Drum level between < HH & > LL c) Fuel air ratio < HH d) F.D. Fan 1 or 2 in operation. e) All oil quick closing valves are closed. f) All natural quick closing valves are closed. g) No purge program existing or any burner in service.

Page 14: BABCOCK BOILER 1 - 6 Instruction Manual

14

� Press push button “ Preventing ON’ � Air dumpers of all burners will open.

22. when all burner dampers are in open position ; � start to open FD Fan vane � and bring the air flow to ~ 200,000 nm

3 / h.

� signal “Preventing running ' appears. � after 160 seconds signal ‘Preventing finish ‘will appears &

“ Ready for ignition” period will start . TIME SETTING 10 minutes. � reducing the air flow by closing FD fan vane to 15 %; with air flow of approx. 45,000 nm

3 / h,

� and burners ‘Ready for Ignition ‘signal will appears at each of the nine burners. 25. Open the natural gas Main Stop valve.

� Open natural gas isolating valves infront each burners. � and check gas press. before burners must be at ~ 0.11 to 0.15 bars.

23. Starting the first burner from bottom row with natural gas burner. PRECONDITIONS: -

To get “Burner Ready” signal the following interlocks have to be fulfilled: a. Boiler Release existing when the below conditions ‘a to g’ are fulfilled.

� i. Furnace pressure < min. ii. Drum level between < HH & > LL iii. Fuel air ratio < HH iv. F.D. Fan 1 or 2 in operation. v. All oil quick closing valves are closed. vi. All natural quick closing valves are closed. vii. No purge program existing or any burner in service.

b. Boiler air purge terminated. c. Ignition air flow > min ( 45,000 Nm

3 / h )either one burner in operation ( min. air flow signal is taken from

FD Fan vane position) b. Gas regulating valve in close position. c. One flare in operation. d. Burner natural gas pressure before burner, > min.min. ( 0.02 bar) [ NN18P2] e. Burner natural gas pressure before burner < max. max. ( 0.3 bar) [ NN18P4] f. Gas relief valve open. g. Photocell is not picking up any stray light.

� wait until “Flame ‘signal appears; � observe the air damper is moving to open position, � then close natural gas relief valve from TCR.

[Note: - incase of some disturbance:

• air dampers of all burners open automatically;

• and purging has to be repeated, by increasing the air flow to ~ 200,000 Nm 3 / h.]

27. Increase air flow to > 45,000 Nm 3 / h, ( FD fan guide vane must be > 18 % open)

� start burner No.9.

• after flam appeared

• Check the stability and brightness of the flame by the flame intensity indicator and TV combustion monitor screen, also locally through furnace side glass.

� Increase the combustion air flow to 50,000 Nm3 / h. in preparation to start 2

nd burner.

� Start burner No. 7, observe the firing sequence, gas flow will be double i.e. 2200 Nm3 / h.

Immediately increase air flow upto 50,000 Nm3 / h.

� and gas pressure by opening the gas control valve.

• In case fails to start 2nd

burner or any other one, wait for at least 5 min. before making further attempts to start the burner & continuously observe the flame in side the combustion chamber.

• Observe the 02 flue gas in recorder.

Page 15: BABCOCK BOILER 1 - 6 Instruction Manual

15

• Watch all figure ( drum metal , super heaters temperature, flow and pressure rate; 28. When the drum pressure reached � 2 ~ 3 bars;

• Close the vent valves of super heaters and drum.

• Increase the press. & temp. of the boiler by corresponding controlling air flow and gas press. gas flow respectively the number of burners in operation.

Note:

• While fire rate increase, always increase air flow first before increasing gas.

• While decrease firing rate, gas flow reduce first later air flow reduce.

• During start up time maintain 20Nm3 of air flow for each 1Nm

3 of natural gas.

• Firing rate will be increase when steam temp. tends to be steady.

• During start up stage always maintain continuous feed water flow through economizer coils.

• Watch waste drain basin level & temperature should not exceed > 60 oC.

29. When SH NO.1 steam out let temperature app. ~ 300 o C press. about 5 bar,

• Then close step by step throttle all Super heaters drain valves according their metal temperature.

• Keep an eye super heaters multi point metal temperature.

• After 30 min. 30. Increase the combustion air flow to 70,000 Nm

3 / h also increase N.G. pressure to 0.7 bars, gas flow

approx. 4,000 Nm3 / h. 31. After 40 min. increase air flow 80, 00 Nm

3 / h & gas press. to 0.8 bar (gas flow around 4300Nm

3 /h).

32. 3 rd burner ‘8’ start : -

• before start 3rd

burner, prepare the attemperators station for service to maintain required temperature.( drain valves close , isolating valves opened & properly vented).

33. Air flow increase to 90,000Nm3 / h, adjust gas pressure to 0.6 bars, corresponding gas flow about 5,000

Nm3 / h.

• The fire rate must be kept in a limit, press. not more than & press. 1.5 bars / min.

• The super heater metal temp. normal increasing rate 5 oC / min,

34. When boiler outlet steam press. reach 10 bar :-

� Start heating up the HP line RA-1 by gradually opening motorize by pass valve NA50G201. � As required, open by pass valves to Turbine (RA2G202) & Distiller (RA4G2) also deaerator � When press. Equalized. � Start opening HP steam main valve NA49G201 and close by pass valve RA50G201.

• As soon as steam consumption increase steam pressure tends to come down. � Gradually close start up control valve NA70G401 & observe boiler load not be < 72 t / h at any

time. � Firing rate increase according steam consumption (turbine & distiller).

35. Start opening the FW tank HP Red. Station.( isolating valves are opened)

• and spray water control valves for heating up FW tank.( isolating valves are opened)

• monitor continuously for the proper fuel – air ratio,

• when gas pressure reaches 0.9 bar put one more gas burner in service. 36. when drum press. reach 30 ~ 35 bars :-

� as require, start turbine Hogging Ejector. � to start falling up vacuum in condenser, � main steam valve to turbine RA2G201 slowly open; � open steam valve RH32G1 to deaerator.

37. when boiler steam pressure about � 40 bar

• adjust FW flow to 50 ~ 70 t / h.

• increase press. and temp. and steam flow to turbine and distiller as required. 38. when boiler load reached 80 t / h.

• Change-over the FW control valve, by pass RL43G401 to � main control RL41G401 or RL42G401.

� Open FW controller stop valve behind the main control valve;

• Open main Control valve slowly and close the by pass valve; observe FW flow & drum level.

Page 16: BABCOCK BOILER 1 - 6 Instruction Manual

16

39. when boiler load reach approx. 100 t / h;

• bring boiler steam parameters to 50 bars and temp. 420 o

C,

• Proceed to put into AUTOMATIC CONTROL LOOP of the boiler as per following sequence:

� FFED WATER CONTROL LOOP � COMBUSTION CONTROL LOOP ( FUEL) � COMBUSTION CONTROL LOOP ( AIR) � BOILER LOAD CONTROL LOOP � SPRAY WATER CONTROL LOOP

• FW and combustion control valves to ‘AUTO ‘(Gas, contr. valve & FD Fan vane). 40. when boiler load reach approx. 180 t / h,

� start the 2nd

FW pump. 41. when air flow reach approx. 170,000 Nm

3 / h ,

� start the 2nd

FD Fan; � then open 2

nd FD fan vane until, both fans are equalized,

� select the 2nd

FD Fan vane control to automatic position 42. Bring steam parameters of boiler up to operating values;

• press. 65 bars & temp. 490 o C,

• by increasing the number of burners firing respectively with load.

Page 17: BABCOCK BOILER 1 - 6 Instruction Manual

17

A – 3.2. COLD START UP OF THE BOILER

II. BY CRUDE OIL WITH ATOMIZING AIR & ATOMIZING STEAM: - CONDITIONS: -

i. At least one crude tank filled. ii. One crude oil transfer pump running. iii. one transfer pump selected to ‘AUTO’ start iv. one service air compressor running v. Boiler filled up to normal starting level. vi. condensate pump running for mechanical sealing of the FW pump vii. One feed water pump running.

1. Open hand isolating vale OUS 70G1 from service air main ring line to boiler. 2. Open hand isolating valve OUS70 G2 service air to atomizing air.

� indication ‘Atomizing air pressure Low signal disappears. 3. Bring anti – vibration rings into oil position on burner 7, 8 & 9. 4. Preparations before start of the 1st burner

i. All manholes on the boiler and air ducts closed. ii. Instrument air connected to all consumers. iii. Power supply to the burner cubicles switch ON iv. Circuit breakers of cooling air fan (NK51, NK52A1) working position. v. Both cooling air fans emergency push buttons released. vi. All cooling air valves to the fotocell are open. vii. Start one cooling air fan

� Cooling air pressure Low signal disappears viii. Check cooling air fans performance one by one. ix. Both FD fans Circuit breakers in working position & Selector switches are TCR position. x. Dampers & vanes circuit breakers are in working position.

5. Circuit breakers of crude oil booster pumps (NM21A1 & NM22A1) are working position. 6. One oil filter in normal position, other one cleaned & properly filled. 7. Open suction, discharge and minimum flow valves at each pump : -

(NM1G1,NM21G1,NM22G1NM23G1,NM24G1,NM25G1,NM26G1, NM34G1,NM34G2) 8. open hand valves ( NM27G1 & NM27G2) before & after relief valve 9. Close by pass valve (NM27G1) of the pressure relief valve. 10. Close crude oil control valve ( NM32G401 11. Open controller’s hand isolating valves (NM32G1 & NM32G2). 12. Close crude oil by pass valve (NM33G1). 13. Open hand isolating valve (NM31G1 & NM31G2) before & after crude oil start up valve. 14. Open crude oil flow meter isolating valves (NM34G1 & NM34G2). 15. Close by pass valve (NM35G1) of crude oil flow meter. 16. Close hand isolating valves (NM41G1 – 49G1) before each burner. 17. Close oil return valve (NM51G801). 18. Through by pass valve (NM52G1) throttled oil flow approx. 6 t / h. 19. open 2 turn by pass valve (NM92G1) of the atomizing steam trap. 20. open atomizing steam control station outlet valve (NM62G4). 21. close by pass valve (NM63G1 & G2) of the atomizing steam control valve 22. open 2 turn by pass valve (NM94G1) of the atomizing steam trap. 23. open slowly to 100 % isolating valve (NM62G1) infront reducing station.

� watch pressure & temperature. � temperature after reducing station approx. 200

OC.

� open fully atomizing steam control station inlet & outlet valves (NM62G1 & G2 ) � pressure approx. 13.5 bars.

24. Open steam trap isolating valves (NM91G1 & G3).

Page 18: BABCOCK BOILER 1 - 6 Instruction Manual

18

25. close atomizing steam trap by pass valves (NM92G1 & NM94G1). 26. Start crude oil booster pump ( NM21A1 or NM22A1) : -

� Release EM. Push buttons both pumps (BM21& 22A1). � Selections are in TCR. � Start one pump � deliver pressure approx. 23 bars. � Both pumps performance test will be carry out one by one. � Physically check that all oil & atomizing steam hoses are properly connected. � Open hand isolating valves at each burner. � After opening the atomizing steam hand isolating valves on burner 7, 8 , & 9 ‘Atomizing medium

Low ‘ signal must disappear. � Close by pass valve to oil return, watch oil flow will be 0 t / h. � Watch oil pressure before oil QCV of burner, approx. ~ 6.0 bar.

27. Both FD fans dampers & vanes check function by opening & closing.

i. Both FD fans oil level check. ii. Open all hand operated dampers (NG30, 31,40,41,50 & 51G1) in the air ducks. iii. EM push buttons released. iv. Start one of the FD Fan from TCR on AUTO program � Select ‘AUTO’ program > Press release button & ON button of the fan > when running up time of the starting FD Fan is over > damper will open automatically. v. Press push button ‘ Preventing ON’

� air dampers of the all burners will open, if they are not yet open. vi. When above air dampers are open position �

� open air vane and check air flow. � Air flow > 200,000 Nm

3 / h.

� Signal ‘Preventing Running’ appears. � After 160 seconds signal ‘Preventing Finish’ will appear.

28. Air flow approx. 55,000 Nm3 / h.: Start oil burner 8 from TCR and wait until the flame signal appears and damper is moving in the open position.

29. Watch all figures (drum level, feed water tank level, temperature, flow, pressure, also feed water flow through economizer.

30. when drum pressure reaches 2.5 to 3 bar - close vent valves of the drum & super heater. 31. increase air flow to 65,000 Nm3 / h.:

Start oil burner NO.7, after start burner NO.7, � increase air flow to 80,000 Nm3 / h.

32. Start burner NO.9, After the signal flame appears and the air damper open stop burner NO.8. � After stopping burner NO.8, reduce air flow to 65,000 Nm

3 / h.

33. When drum pressure 10 – 15 bar start heating up steam lines. 34. Watch atomizing steam pressure & temperature before burner 7, 8 & 9. 35. Burner atomizing medium change over from air to atomizing steam : - When atomizing steam pressure is higher than atomizing air pressure the non-return valves in atomizing lines will be closed automatically by the atomizing steam pressure and the change over period starts. Closing all atomizing air valves starts within 10 minutes time delay. After the 10 minutes the atomizing air valves will be closed automatically and the signal ‘Atomizing steam press Low Low ‘ disappears. 36. Start other burners and & watch all parameters , increase pressure and temperature of boiler by

correspondingly controlling oil flow and air flow respectively the number of burners in operation.

Working sequences of the oil system: - After pressing ‘ON ‘ button start the burner the “Ready “ signal �disappearing �oil lance will be inserted �air damper is moving into ignition position. When the oil lance is inserted the atomizing steam valve is opening for heat up the oil lance and pushes the accumulated condensate out of the atomizing steam system. When the pre-purging or pre-heat time is over and the air damper is in ignition position the power for the electric igniter is switch on and the igniter starts move into the operation position. After igniter established the safety ignition time starts ( 5 second) and the oil valve opens if the following criterias are fulfilled : -

Page 19: BABCOCK BOILER 1 - 6 Instruction Manual

19

i. air damper ignition position. ii. Oil operation released iii. No order ‘OFF’ appeared iv. Air flow > min. v. Atomizing steam valve open vi. Oil lance inserted.

The fuel air mixture will ignite on the sparks of the igniter and fotocell must pick up the flame within the safety ignition time. If this done, then the signal “Flame” will appear and the air damper is moving into operation. After the expiry of the safety ignition time the igniter is retracted and the power switched off. If the fotocell is not picking up the flame within the safety time the oil quick closing valve will close again and the signal oil burner distur-bance and oil burner purge will be appearing. The oil lance will be retracted. The burner ‘OFF’ or disturbance signal has to be cancelled by pressing the burner ‘OFF’ push button. Is no other gas or oil burner in operation the automatic furnace purge will start as soon as air flow is above 200,000 n

3m /

h. When the preventing of the boiler is finished the burner may be re-started or steam purge. If you want to start oil burner, press oil ‘ON’ button, if you want to steam purge the burner press the ‘OFF’ button. STEAM PURGE SEQUENCE OF AN OIL BURNER: -

Steam purge with igniter

• May be oil valve opened & photocell did not pickup the flame, with pressing the ‘OFF’ push button the steam purge can be started �

• The signal ‘purge of lance ‘ is indicating that the steam purge is taking place.

• The air damper is moving into ignition position and the power for the ignition will be ON when the photocell criterias are fulfilled:�

i. Stem purge release exists ii. Steam purge memory is set. iii. No flame is existing iv. Oil valve is closed v. No burner in ‘ON’ or ‘OFF’ program vi. When the push button ‘ burner off’ was pressed vii. When the return signal of the open position of atomizing steam and purge steam is there, the first purge

program starts. The oil which was remaining in the oil lance will be blown out and ignited at the sparking igniter. When the time for the 1 purge program is over the air damper is closing, the igniter retracting, the power for igniter switch off.

• Is no burner in operation, the boiler has to be air purged before ignite the next burner.

• If the preventing finished, the signal ‘Ready’ for ignition is appearing & required criterias are fulfilled.

• if the second steam purge will not be interrupted with give a new ‘ON’ signal, the steam purge valve stays open until also the time of second purge will be over.

Steam purge with out igniter: -

• If one oil burner will be switched off during normal operation by pressing the ‘OFF’ push button, the atomizing steam valve is closing the steam purge valve will open too and till remaining oil is burnt with the existing flame.

Page 20: BABCOCK BOILER 1 - 6 Instruction Manual

20

Page 21: BABCOCK BOILER 1 - 6 Instruction Manual

21

A – 3. 1. Boiler 1 to 6 FIRING SYSTEM CHANGE OVER I. NATURAL GAS TO CRUDE OIL

Conditions:

� at least one crude oil tank is filled. � one transfer pump is running � and one transfer pump selected to ‘AUTO’ position. � Crude oil line properly vented & an oil flow 5 to 10 t / h is circulating each boiler ( which

prevent that wax or other part of the oil can settle in the pipe & choke the strainers and oil gun nozzles.

� All valves should be in their normal operation condition. � All oil lances installed in the retracted position and atomizing steam hoses are

connected. � The nitrogen buffer system has to be filled with nitrogen, during normal operation the

pressure should be > 21 bars. Preparation of crude oil sys. -

1. circuit breaker of the booster pump in working position;

� NM21A1 - crude oil booster pump No.1 � NM22A1 - crude oil booster pump No.2

2. one filter in normal and other stand by one cleaned & filled (NM1B10). 3. open the following suction, discharge & minimum flow valves of both crude oil booster pumps:

NM1G1 NM3G1 NM25G1 NM21G1 NM13G2 NM2G1 NM22G1 NM23G1 NM24G1

4. Hand valve before and after press. relief valves, NM27G1 – open, NM27G2 – open, � by pass valve of pressure relief valve NM28G1 – closed.

5. crude oil control valve NM32G401 open; and hand isolating valve NM32G2 open. � Crude oil control valve, by pass valve NM33G1 - close.

6. Hand operated isolating valve before and after the crude oil start-up valve NM31G1 and NM31G2 – open. 7. crude oil flow meter before and after isolating valve NM34G1 and NM34G2 – open.

� by pass valve NM35G1 of the flow meter – close. 8. Hand isolating valve before each burner NM41 to NM49G1 – close. 9. oil return pneumatic valve NM51G801 – close.

� by pass valve NM52G1 to oil return –:� throttle crude oil flow approx. 6 t / h. 10. by pass valve of steam trap of atomizing steam valve NM92G1 – open 2 turns. 11. Hand operated isolating valves before and after steam trap NM91G1 & G3 – open. 12. Atomizing steam control station outlet valve NM62G4 - open. 13. By pass valve of atomizing steam control valve NM63G1 & G2 – close.

� by pass valve of the steam trap NM94G1 open 2 turns � isolating valve NM62G1, in front Red. Station –– open slowly to full. � isolating valve NM62G2 before Red. Station – open slowly. � and watch pressure and temp.

14. Temperature reaches after Red. Station approx. ~ 200 o C. � stepwise open valve NM62G2 fully and watch press. approx. 13.5 bar.

15. by pass valve of steam trap of atomizing Red. Station drain valve NM94 & 92G1 – close. � and watch temp. after Red. Station approx. 245 o C.

16. Release EM. Push buttons of both crude oil booster pumps.

Page 22: BABCOCK BOILER 1 - 6 Instruction Manual

22

� Select booster pumps NM21, NM22A1 in the TCR position. 17. start one of the booster pumps from TCR.

� and watch the crude oil control valve approx. 23 .00 bar. 18. Select stand by crude oil booster pump to ‘AUTO’, and check ‘AUTO’ start up.

� trip the running pump by EM. push button. � stand by pump start automatically.

19. Repeat the same other crude oil booster pump. 20. make sure that, all oil and atomizing steam hoses are connected,

� and open the oil hand isolating valve in front of each burner. 21. close by pass valve to oil return valve.

� and watch oil flow, 0.0 t / h. � watch press. before oil quick stop valve of burners approx. 6 ~ 7 bar.

Note: -Start-up oil pressure is 7.0 bars.

Page 23: BABCOCK BOILER 1 - 6 Instruction Manual

23

A – 3. 1. BOILER FIRING SYSTEM CHANGE OVER

II. CRUDE OIL TO NATURAL GAS

Conditions: - :

� Boiler load 200 t / h, with 9 burners in operation. � HP Gas Red. Station in service. � LP Gas Red. Station in service.

1. Set flue gas 02 % vol. to 3 %.

• by increasing the fuel / air ratio set point, in TCR Desk. 2. check LP gas Red. Station, if already in operation. 3. open the main gas stop valve NN17G801.

• and gas relief valve from TCR desk 4. open full the gas hand operated isolating valve in front of the burners. 5. check natural gas press. before the burners, 0.11 ~ 0.15 bar. 6. stop crude oil burner NO. 7 by pressing ‘OFF ‘push button in TCR desk.

� after steam purge of the burner has taken placed- : � and oil lance retracted,- � start gas burner NO. 7 , when ‘ FLAME’ � signal appears , - � Close the natural gas relief valve. � And increase the gas pressure to approx. 0.7 bars, by opening the gas control valve

manually. Note: boiler combustion and load control remain in ‘AUTO’ mode.

7. stop crude oil burner NO. 9 , after purge time over & oil lance retracted :- � start gas burner NO. 9 , when ‘ FLAME’ signal appears, � increase the gas press. to approx. 0.6 bar ~ 0.7 bar, by opening gas control valve.

8. stop oil burner NO. 8, after purge time over & oil lance retracted :- � start gas burner NO. 8, when ‘FLAME’ signal appears, increase gas press. � Kept Natural gas Contr. Valve ‘AUTO’

9. stop oil burner NO. 5, after purge time over & oil lace retracted :- � start gas burner NO. 5, when ‘FLAME’ signal appears, increase gas press. � repeat the steps for next all other burners.

10. when the oil control valve NN32G401 has reach 20% opening position,- � change the control valve from ‘AUTO’ to ‘MANUAL’ position.

11. stop the next oil burner, after purging time over & oil lance retracted:-. � start the gas burner

12. when last oil burner remain in service, - � close the oil control valve manually, � and keep one oil burner on oil start – up valve; - � and keep one oil burner on oil start – up valve; - � watch the gas press. , not more than 1.0 bar.

13. stop the last oil burner ;- � when purge time over and oil lance retracted , - � the firing is completely changed to gas firing.

14. change 1st the position of stand by oil pump , which in ‘AUTO’ to ‘ Manual’ selection,- � then stop the crude oil running pump.

15. open the oil return valve. 16. close the atomizing steam valve. 17. close the hand isolating oil valves before each burner.

Page 24: BABCOCK BOILER 1 - 6 Instruction Manual

24

A – 3. 2. BOILER HOT START UP: -

CONDITIONS: - I. The boiler pressure is approx. 40 bar II. All unit auxiliaries still are in service

1. Prepare to start feed water pump after fulfilled pre-conditions.

• if the feed water temperature is 100 0C and FW tank pressure less, fed make up water to FW tank to get the feed water temperature down or take steam through inter-connection steam line from other unit � before that arrange spray water for reducing stations.

2. Pressurized feed water line, if it was already pressure less upto boiler main feed water valve NA01 GG201.

3. Prepare the natural gas system as cold start up process. 4. Start FD Fan with auto program 5. Start feeding the boiler until drum level reach – 200 mm. 6. Open hand isolating valves of drain & super heater drains. 7. open the motorized valve some steps until steam is coming out of the drains , watch the

change of the flowing noise. 8. When steam is coming, close motorized valves again, approx. after 2 to 5 minutes. 9. The feeding through the economizer is important because , steam bubbles get out of the

economizer. Therefore feed with a flow of about 50 t/ h for at least about 10 mins. 10. If drum level higher than – 200 mm, it will be equalized by using after the start of the 1st burner

the drum drain valve. 11. When the boiler furnace is air purged , drum level at start up position , start – up stop valve

open . 12. Hand isolating valve before burner open 13. Burner ready for ignition signal appeared , then boiler is ready to start the 1st burner 14. After burner fired, open start up regulating valve approx. 15 %. 15. Open super heater drain valves 10 steps. 16. When the temperature is approx. 300 o C close the drain of 2nd super heater completely. 17. And the drain of the 3rd one to 5 steps . 18. Watch the temperature of the feed water after economizer 3 outlet. Keep the temperature

below the saturated steam temperature. 19. Regulate the feed water flow accordingly. 20. As soon as the steam temperature respectively the super heaters metal temperature. 21. Start the 2nd burner. 22. This means 7 & 9 in service and NO.8 out of service. 23. Further procedure are same as cold start up .

Page 25: BABCOCK BOILER 1 - 6 Instruction Manual

25

A - 3.3. BOILER WARM START UP:

Page 26: BABCOCK BOILER 1 - 6 Instruction Manual

26

A – 4. 1. BOILER NORMAL SHUT DOWN PRCEDURES: -

1. Reduce the boiler load by reducing turbine or distiller to minimum. � keep turbine load on 25 MW, � then either start shut down distiller or transfers to other available unit. � after shut down distiller, close following valves :

• RA04G1, HP steam valve to distiller.

• RL80G1 , spray water valve to distiller

• RM90G201, return condensate water valve from distiller to FW tank. 2. Inform Lab. About boiler shut down program. 3. when boiler load reduced to approx.~ 100 t / h,

Change all boiler close loop ‘AUTO’ control to manual mode.

• FW control valve RL41 / 42 G401.

• Fuel gas control valve.

• Boiler (load) Master control.

• FD fan 1 & 2 vane control.

• Stop one FW pump. 4. when boiler load reduce to < 90 t / h,

� change FW main controller to by pass control valve, � check the gas pressure, � stop some burner, if needed, � to keep 0.5 bar gas press. by reducing the firing rate, ( at 3 burners remain in

service), � keep air flow at 90,000 nm 3 /h.

5. when attempt. Spray water valve have reached to 5 % opening position, � change the control valves to manual position.

6. when boiler load reduce further 70 ~ 80 t / h:

� start opening the start up regulating valve approx. 25 %. � And keep FW flow about 50 ~ 70 t / h through economizer.

7. when turbine load ~ 5 MW, � trip the turbine, � the quick transformer will work in the moment, when the generator breaker is open. � Open direct drain valve of the steam strainer, before turbine Q.C.valve

(RA2G10&G11). 8. when 3 burners are remain in service ( 7,8 & 9) ,

� reducing the firing rate stepwise by closing the natural gas regulating valve until the :-

� start up regulating valve will take over at 0.15 bar gauge pressure. 9. close continuous blow down valve to increase boiler drum level up to + 200 mm. 10. stop burner NO.9.

� and close the natural gas regulating valve, � as by pass regulating valve taking over,( which is capable of taking 2 burners in

service), � keep burners 7 & 8 in operation, � and adjust the air flow to 75,000 Nm 3 / h.

11. open by pass valve of the boiler HP steam � and close HP steam valve of the boiler.

12. Stop the last two burners 7 & 8 one by one , � which close in parallel the main natural gas stop valve. � Then open the gas relief valve.

Page 27: BABCOCK BOILER 1 - 6 Instruction Manual

27

13. when boiler drum level in + 200 mm,

� close the FW controller by pass valve, RL43G401. 14. stop the remaining FW pump.

� then close the HP by pass valve of the boiler. 15. close make up water valve to condenser. 16. Change the cold. condenser level control valve RM30G401 and RM35G410 to manual; and

close both valves. 17. wait up to Shaft turning gear start. 18. stop the running condensate pump 19. start purging the boiler furnace :

� by increasing the air flow to ~ 200,000 nm 3 / h, � by opening the FD fans vane control for approx. 3 min. � as purge finish signal appears.

20. stop the FD fan one by one, � by closing the vanes and air dampers respectively, and stop the motor. � Keep cooling air fan in service, until boiler is cold.

21. close the boiler main natural gas valve. 22. close all the hand isolating valves in front of the burners. 23. close the gas auto shut off valves of each LP gas Red. stations from local :

• by opening the hand lever. 24. close hand operated isolating valves of the sample points at SH and drum drains. 25. when boiler press. drop to 10 bar :

� open the drum and SH drains.

26. when boiler press. drop to 2. 5 – 3.0 bar : � open the drum and SH vents.

Page 28: BABCOCK BOILER 1 - 6 Instruction Manual

28

A - 4. 2. BOILER EMERGENCY SHUT DOWN:

Page 29: BABCOCK BOILER 1 - 6 Instruction Manual

29

A – 5. BOILER SOOT – BLOWE SYTEM: -

. Preparation to start –up: - Check which to be carried out prior to operation of the soot blowers.

i. drain by pass valve NV41G1 open ii. contact thermometer set point 200

o C

iii. the following sealing & cooling air valves must be open at all soot blowers � NV61G1, NV71G1, NV62G1, NV72G1, NV63G1, NV73G1, NV69G1, NV74G1, NV65G1, NV75G1, NV66G1, NV67G1. SOOT BLOWER 7 TO 10 NV53G1, NV54G1, NV55G1, NV56G1

iv. Steam hand isolating valves should be open at each soot-blower NV21G1 to NV26g1 & NV31G1 to NV34G1 v. all soot blowers have to be in their retracted position, if not pull them into the retraced position with

the hand lever. [indication in TCR – panel ‘OFF’ when the control voltage is switched ‘ON’ and the soot blowers are pre-select.]

vi. impulse lines of pressure switch NV1P3 & NV1P and pressure indication must be open. vii. The safety valve should not be blocked viii. Steam pressure > 40 bar. ix. Main switch of the cubicle HC 01 is switch ON

b. OPERATION OF THE SOOT BLOWER SYSTEM: -

The following criterias have to be fulfilled either Manual or Automatic operation : -

i. control voltage switch ON ( key switch at soot blower panel in TCR) ii. drain valve ( NV4G201) closed iii. main hand isolating valve ( NV1G1) closed. iv. Motorized isolating valve ( NV1G201) closed.

Page 30: BABCOCK BOILER 1 - 6 Instruction Manual

30

v. All soot blowers in their retracted position vi. All soot blowers are pre-selected to operate in the correct sequence. vii. No fault indication appeared of soot blowers 1 - 9 & main valve or drain valve. viii. When the boiler is in operation the key switch in the control cubicle has to be selected to the position ‘

with pressure’

• If during the ‘COLD’ boiler the function of the soot blower system has to be tested the key switch has to be selected to the position ‘ without pressure’.

a. AUTOMATIC OPERATION OF THE SOOT BLOWERS:

[ all remote control operating switches are arranged in TCR Cont. Panel, from where Selection ‘AUTO’ /’ MAN’ / LOCAL’ & Operation will be carry out] Sequence of the operation: - � ix. Open the drain valve manually from TCR Contr. Panel x. Open main valve main valve from TCR Contr. Panel xi. Open the main isolating valve , for heating up the line. xii. Cancelled the ‘PRESSURE LOW’ indication by pressing the button.

• If the temperature is above 200 oC the drain valve is close automatically.

xiii. Close main valve manually. xiv. When closed indication appeared of the main valve � xv. Pre- select ‘ AUTOMATIC ( Soot blower panel) xvi. Press Automatic Start button. xvii. Main drain valve will open (Flush light during the operation, steady light , when the valves are in open position) xviii. When open signal appeared, open main hand isolating valve NV1G1 slowly to heat up the steam

lines. xix. When the steam pressure is > 8 bars , the signal ‘Pressure Low in TCR can be cancelled by pressing

the ‘Alarm OFF’ push button. xx. The steam lines automatic vent valves ( NV1G4 & NV3G1) are closing in the moment , when the line

pressure is > 0.5 bar. xxi. When the steam temperature is > 200 oC the drain valve is closing automatically ( warm up time is

app.1 hr.) xxii. When drain valve closing indication appeared, the soot blowers are starting according to sequence 7

�10 & 1 � 6. xxiii. Flushing signal ‘ON’ is appearing during inserting and retracting. xxiv. When soot blower is back in the retracted position the signal ‘ON’ & ‘OFF’ is appearing. xxv. When the last soot blower has reached again the retracted position the signal ‘END’ appears and

main steam valve closes automatically. xxvi. With operating the push button ‘END’ signal ‘END’ and ‘START’ and ‘ON’ will be cancelled at each

blower. xxvii. The drain valve kept closed. xxviii. The soot blower system is ready to be started again. xxix. After completed of the soot blower, close again the hand operated isolating valve NV1G1. xxx. When soot blowing line is nearly 1 bar the vent valves NV1G4 & NV1G3 open automatically.

b. MANUAL OPERATION OF THE SOOT BLOWERS: FROM TCR SELECTION

� SOOT BLOWERS SELECTION FROM TCR, Sequence of the operation procedures: - � i. Open the drain valve by pressing the push button ‘OPEN’ in TCR ii. When drain valve opened full, iii. Open main steam valve also . iv. Open steam hand isolating valve , heat up the steam line. v. Cancelled ‘PRESSURE LOW” signal vi. If the temperature is > 200 oC , the drain valve closing automatically. vii. When drain valve closed, start 1

st shoot blower manually with pressing the push button ‘ON’.

viii. The 2nd

blower should only be started after the 1st one has reached its retraced position.

ix. By this way complete other

Page 31: BABCOCK BOILER 1 - 6 Instruction Manual

31

c. MANUAL OPERATION OF THE SOOT BLOWERS: FROM LOCAL SELECTION

� Select soot blowers in LOCAL , now it is able to operate the system from Locally by ‘ON ‘ button

• during local operation it is not possible to open the drain valve from TCR.

• When last soot blower has been operated the main steam valve can be closed from TCR , close push button.

• After close the manual hand isolating valve OPERATION STEAM PARAMETERS SETTING MINIMUM STAEM PRESSURE----------- = 8 BAR. MINIMUM STAEM TEMPERATURE---- = 200

oC.

SAFETY VALVE OPENING PRESS.-----= 40 BAR STAEM PRESS. AFTER REG. VALVE -= 20 BAR. BLOWING PRESSURE-------------------- = 10 BAR. ALARM STEAM PRESS. > HIGH --------= 30 BAR

Page 32: BABCOCK BOILER 1 - 6 Instruction Manual

32

A - 6. BOILER PRESSER SWITCHES & INTERLOCKS: -

a. PRESSURE & LIMIT SWITCHES: -

AK NO. EQUIPMENT TRIPPING VALUES

REMARKS

NG11A2 FD Fan 1 Vane Position 12%

NG12A2 FD Fan 2 Vane Position 12%

NR01P02 Furnace press. 400 mm WC

NA16L03 Drum Level Low Low - 320 mm WC

NA16L03 Drum Level High High + 320 mm

NN17F01

NM01F01

UE80P1 Control Air press. L L 3,5 bar

NK6P1 Cooling air press. 20 m. bar

NN37P1 Gas press. Torch 3 , 5 bar

NN35P1 Gas press. Torch 3 , 5 bar

NN16P03 Gas press. After LP Red. Station 3 , 0 bar

NN18P2 Burner N. Gas Press. 20 m bar

NN18P3 Start Gas press. High 0 , 3 bar

NN14P4 Burner N. Gas press. Low 0, 2 bar

US90P4 Auto. Air press. Low 4 , 0 bar

NM67P2 Auto. Steam press. Low 8 , 0 bar

NM77P3 Auto. Medium press. 4 , 0 bar

NM78P3 Auto. Medium press. 4 , 0 bar

NM79P3 Auto. Medium press. 4 , 0 bar

NM21P01 Crude oil press. before pump 1 , 5 bar

NM22P01 Crude oil press. before pump 1 , 5 bar

NM27G401 Crude oil Relief valve 23 , 0 bar �Opening Set value

NM31G401 Starting oil Reg. Valve 5. 0 bar �Opening Set value

NM19G401 Starting oil Reg. Valve 0 , 10 bar

NN3G401 LP Gas Reg. valve 4 , 0 bar

NN8G401 LP Gas Reg. valve 3 , 9 bar

NN3G401 LP Gas Quick closing valve 5 , 1 bar

NN8G401 LP Gas Quick closing valve 5 , 1 bar

NN6G101 LP Gas Red. Station safety valve 4 , 5 bar

NN11G101 LP Gas Red. Station safety valve 4 , 5 bar

b. TIME SETTINGS: -

Air purge time of Boiler Furnace & Fuel Gas press.

160 sec. with min. air flow 200,000 N m3 / h

Remarks

Ready for ignition period 10 mins.

Opening time of oil burner QCV 2 sec.

Opening time of gas burner QCV 1.5 , 2 sec

Purge time of gas burner QC v/v 30 sec.

Safety time gas burner 3 sec.

Safety time of oil burner 5 sec.

First stage burner oil purge 60 sec. Alarm Setting

2nd stage burner oil purge 90 sec.

Safety time photo Photocell 1 sec.

Closing time ( time ) QCV gas 1 sec.

Closing time QCV crude oil 1 sec.

Time delay NM21P01 3 sec.

Time delay NM22P01 3 sec.

Time delay NM16l03 ( Boiler Drum) 1 sec.

Time delay Fuel / Air ratio 10 sec.

Page 33: BABCOCK BOILER 1 - 6 Instruction Manual

33

A. - 7. : BOILER ALARMS & PROTECTIONS: -

a. FLOW MEASUREMENTS:

AK NO. DESCRIPTION ALARM INTERLOCKING / PROT.

NG11G401 Position of Comb. Air fan damper 18 %

NG12G401 Position of Comb. Air fan damper 18 %

NG20F01 combustion air flow S = 2000, 000 Nm3 / h

RL11F01 lube oil flow FW P/P NO.1 L = 40 l/min L = 40 l/min

RL12F01 lube oil flow FW P/P NO.2 L = 40 l/min L = 40 l/min

RL13F01 lube oil flow FW P/P NO.3 L = 40 l/min L = 40 l/min

RL11F02 sealing water flow FW P/P NO.1 L=7,5 l / min L=7,5 l / min

RL12F02 sealing water flow FW P/P NO.2 L=7,5 l / min L=7,5 l / min

RL13F02 sealing water flow FW P/P NO.3 L=7,5 l / min L=7,5 l / min

RL11F03 sealing water flow FW P/P NO.1 L=7,5 l / min L=7,5 l / min

RL12F03 sealing water flow FW P/P NO.2 L=7,5 l / min L=7,5 l / min

RL13F03 sealing water flow FW P/P NO.3 L=7,5 l / min L=7,5 l / min

b. LEVEL MEASUREMENTS: -

HH = +320 mm Z = HH = +320 mm

NA16L03 Boiler drum level LL = - 320 mm Z = LL = - 320 mm

H = + 100 mm NA16 L01 Boiler drum level

L = - 100 mm

RH03 L01 HH =2940 mm Z = HH =2940 mm

RH03 L05 LL = 700 mm Z = LL = 700 mm

RH03 L06 LL = 700 mm Z = LL = 700 mm

RH03 L07

Feed water tank level

LL = 700 mm Z = LL = 700 mm

H = 2800 mm RH03 L08

Feed water tank level L = 25OO MM

H = 13. 5 m. S = 10 m RM33 L02 Cold cond. storage tank level

L = 10 , 0 m. Z = 1 , 0 m.

S = 1380 mm

S = 1960 mm RT01 L01 Waste drain basin level

Z = 2160 mm

RT01 L01 Grease switch 300 sec. time delay

H = 1800 mm RU01 L01 Clean drain tank level

L = 1350 mm

RU01 L02 Clean drain tank level S = 1920 mm

RU01 L03 Clean drain tank level S = 1650 mm

RU01 L04 Clean drain tank level Z = 1420 mm

H = 1700 mm VF10,30 & 50 L01 Service water Basin unit (1 - 2 )

L = 1100 mm Z = 900 mm

VF17, 37 & 57 L01 Service water elevated tank L L = 2900 mm

RZ16L01 Continuous blow down flash vessel- L H = 130 mm

Page 34: BABCOCK BOILER 1 - 6 Instruction Manual

34

c. PRESSURE MEASUREMENTS: -

NA16 P02 Boiler drum press. HH = 84 , 8 bar

H = 82 , 8 bar

Z=73,7 bar NA49 P01 Boiler outlet press.

Z=69,0 bar

H = 70, 0 bar NA49 P03 Boiler outlet press.

L = 62, 0 bar

NG20 P01 Combustion air press. L = 10.0 mbar

NK01 P01 Cooling air press. L = 20.0 m bar

NM06 P06 Fuel oil filter ∆ P H = 0, 4 bar

NM02 P01 Fuel oil before fuel oil pump L = 2 , 0 bar

NM04 P02 Fuel oil after control valve LL = 3 , 0 bar S = 3 , 0 bar

H = 18 ,0 bar NM04 P03 Fuel oil after control valve

L = 6 , 0 bar

NM21 P01 Fuel oil before pump NO.1 LL = 1 , 5 bar Z = 1 , 5 bar S = 2.0 BAR

NM22 P01 Fuel oil before pump NO.2 LL = 1 , 5 bar Z = 1 , 5 bar S = 2.0 BAR

NM67 P02 Atomizer steam after cont. V / V LL = 8 , 0 bar Z = 8 , 0 bar

NM67 P03 Atomizer steam after cont. V / V L = 10 , 5 bar

NM77 P03 Atomizer medium before burner-7 L = 4 , 0 bar Z = 4 , 0 bar

NM78 P03 Atomizer medium before burner-8 L = 4 , 0 bar Z = 4 , 0 bar

NM79 P03 Atomizer medium before burner-9 L = 4 , 0 bar Z = 4 , 0 bar

NN02 P01 Natural gas ∆ P. filter Red.stin-1 H = 0 , 68 bar

NN07 P01 Natural gas ∆ P. filter Red.stin-2 H = 0 , 68 bar

NN16 P03 Natural gas press. after Red. station LL = 3 , 0 bar Z = 3 , 0 bar

NN18 P02 Burner N. gas press. after control valve LL = 0,02 bar Z = 0,02 bar

NN18 P03 Burner starting N. gas press. after cont. V. Z = 0 ,3 bar

NN18 P04 N. gas press. after contr. Valve HH = 2 .0 bar Z = 2 .0 bar

NN18 P05 burner starting N. gas press. after c.v HH = 0, 3 bar

H = 1 , 6 bar NN18 P06 burner starting N. gas press. after c.v

L = 0 , 3 bar

NN35 P01 Ignition gas press. for torch equipment -1 L = 3 , 5 bar Z = 3 , 5 bar

NN37 P01 Ignition gas press. for torch equipment -2 L = 3 , 5 bar Z= 3 , 5 bar

NR01 P01 Flue gas press. H =34 ,2 mbar

NR01 P02 Flue gas press. HH=39,2 mbar Z =39,2 mbar

H = 30,0 bar NV01 P03 Steam press. before soot blower

L = 8 , 0 bar Z = 8 , 0 bar

H = 3 , 0 bar RH03 P03 Deaerator steam press.

L = 2 , 3 bar

RL11 P02 Boiler FW P/P NO. 1 suc. Filter ∆ P H = 0 , 25 bar

RL11 P05 FW P/P NO. 1 LUB.OIL Filter ∆ P H = 0.294 BAR

RL12 P02 Boiler FW P/P NO. 2 suc. Filter ∆ P H = 0 , 25 bar

RL12 P05 FW P/P NO. 2 LUB.OIL Filter ∆ P H = 0.294 BAR

RL13 P02 Boiler FW P/P NO. 3 suc. Filter ∆ P H = 0 , 25 bar

RL13 P05 FW P/P NO. 3 LUB.OIL Filter ∆ P H = 0.294 BAR

RL21P03 FW P -1, press. Between NRV & stop valve L= 70 BAR L= 70 BAR

RL22P03 FW P -2, press. Between NRV & stop valve L= 70 BAR L= 70 BAR

RL23P03 FW P -3, press. Between NRV & stop valve L= 70 BAR L= 70 BAR

US90P01 Atomizer air pressure L = 8.0 bar Z = 8. 0 bar

OVF 20,40 & 60P01

Service water line pressure L = 3.2 bar S = 3.2 bar

Page 35: BABCOCK BOILER 1 - 6 Instruction Manual

35

d. CHEMICAL MEASUREMENTS: -

NA29Q01 Saturated steam conductivity H = 0.5 µs / cm

NA49Q01 Sup. heated steam boiler outlet H = 0.5 µs / cm

NC16Q01 Drum water conductivity H = 50 µs / cm

NR01Q01 Flue gas C0 H = 0.05 µs / cm

NR01Q02 Flue gas 02 H = 3 %

RL01Q01 Feed water 02 H = 0.5 µg / l

H = 9.5 RL01Q02 Feed water pH

L = 8.5

RL01Q03 Feed water conductivity H = 0.5 µs / cm

RM30Q01 Main condensate H = 0.5 µs / cm

RM90Q01 Cond. From desalination plant H = 0.5 µs / cm

RU01Q01 Clean drain conductivity H = 1.0 µs / cm

e. TEMPERATURE MEASUREMENTS: -

NG11T03 FD fan – 1, motor Winding Temp. H = 125 O C

NG12T01 FD fan – 2, motor Winding Temp. H = 125 O C

NG12T02 FD Fan 2, motor Winding Temp. H = 125 O C

NG12T03 FD Fan 2, motor Winding Temp. H = 125 O C

NM04T01 Fuel oil Temp. H= 50 O C

NV04T01 Condensate after Soot blower S = 200 O C

RA02T01 Live steam Temp. before turbine H = 497 O C

L= 475 O C

Boiler drum Dif. Temperature H = ∆T 20O C

RA02T02 Live steam Temp. before turbine HH = 509 O C Z = HH = 509 O C , turbine trip

Del time 20 min.

RH30T02 EXTR.-3 Temp. , to FW tank H = 300 O C Z = 85 O C

RL11T03 FW Pump – 1, HP Bearing Temp H = 75 O C Z = 85 O C RL12T03 FW Pump – 2, HP Bearing Temp H = 75 O C Z = 85 O C RL13T03 FW Pump – 3, HP Bearing Temp H = 75 O C Z = 85 O C RL11T04 FW Pump – 1, LP Bearing Temp H = 75 O C Z = 85 O C RL12T04 FW Pump – 2, LP Bearing Temp H = 75 O C Z = 85 O C RL13T04 FW Pump – 3, LP Bearing Temp H = 75 O C Z = 85 O C RL11T05 FW Pump – 1, Thrust Bearing Temp H = 75 O C Z = 85 O C RL12T04 FW Pump – 2, Thrust Bearing Temp H = 75 O C Z = 85 O C RL13T04 FW Pump – 3, Thrust Bearing Temp H = 75 O C Z = 85 O C RL11T07 FWP – 1, MOTOR WINDING Temp. H = 125 O C

RL11T08 FWP – 1, MOTOR WINDING Temp. H = 125 O C

RL11T09 FWP – 1, MOTOR WINDING Temp. H = 125 O C

RL12T07 FWP – 2, MOTOR WINDING Temp. H = 125 O C

RL12T08 FWP – 2, MOTOR WINDING Temp. H = 125 O C

RL12T09 FWP – 2, MOTOR WINDING Temp. H = 125 O C

RL13T07 FWP – 3, MOTOR WINDING Temp. H = 125 O C

RL13T08 FWP – 3, MOTOR WINDING Temp. H = 125 O C

RL13T09 FWP – 3, MOTOR WINDING Temp. H = 125 O C

OVF20,40 &

60T01 Service water Temp. H = 46 O C Z = 46 O C

f. FUEL / AIR RATIO & TRANSMITTER FAULT: -

HH = 1: 0.8 = 1. 25

H = 1: 0.9 = 1. 11

Fuel / air Ratio:

L = 1 : 1.15 = 0.8696

Transmitter fault adjustment SET to ± 10 %

Minimum Load for automatic operation 100 t / h = 27.5 %

Page 36: BABCOCK BOILER 1 - 6 Instruction Manual

36

A - 8. ISOLATION OF BOILER MAJOR AUXILLIARY EQUIPMENTS.

8.I. Boiler Feed water Pump. 1. Stop the pump and emergency push button pressed in or put in SWG position in TCR. 2. The 6.0 K.V. circuit breaker is racked out or in test position and the space heater MCB is switch off & tagged. 3. Discharge motorized valve and bypass manual valve are closed, 380 volt C.B. rack out and valves are chain

locked. 4. Suction manual valve closed and chain locked and strainer drain & vent valves are open. 5. Sealing water line valve to pump is closed. 6. Balancing line valve is closed and chain locked. 7. Minimum flow line valve is closed and chain locked. 8. AC / DC lube oil pumps are stopped and C.B's. are rack out or in SWG position in TCR, their EPB are pushed in. 9. Open the pump body drain valve. 10. All instrument attachment to the pump are to be removed by IMD.

NOTE: If motor is not overhaul, space heater should be on. Boiler Feed water Pump Motor.

1. The Pump is stop and 6 K.V. C.B. is racked out and earthed. 2. AC / DC lube oil pump is off, E.P.B. is pushed in and put in SWG position in TCR. 3. Space heater MCB is switch off and tag. 4. Pump and motor to be decoupled by MMD 5. Lube oil line to motor to be removed by MMD. 6. All instrument attachment to motor to be removed by IMD. 8.2 . Force Draft Fan. 1. Stop the fan and emergency push button is pressed in or put in SWG position in TCR. 2. 6.0 K.V. circuit breaker is racked out or in test position and the space heater MCB is switch off & tagged. 3. F.D. fan air damper and vane are in closed position and their 380 volts circuit breakers racked out.

8.3. Cooling Air Fans.

1. Stop the fan and emergency push button pressed in or put in SWG position in TCR. 2. 380 volts circuit breaker is racked out or in test position and the space heater MCB switch is off & tagged. 8.4. Burner Crude Oil Pumps.

1. Stop the pump and pressed in the emergency push button or put in SWG position in TCR. 2. 380 volts circuit breaker racked out or in test position and space heater MCB switch off & tag. 3. Suction and discharge manual valves are closed and chain locked. 4. Open the pump drain and vent. 8.5. Burner Crude Oil Strainers/Filters.

1. The strainer/filter is in standby position. 2. Its vent and drain are open.

Page 37: BABCOCK BOILER 1 - 6 Instruction Manual

37

8.6 . Boiler F.W. Control Valves. 1. The feed water control valve to be isolated is in standby position. 2. Both isolating valves (inlet and outlet) are closed and chain locked. 3. Outlet isolating valve 380 volts motor, circuit breaker is racked out or in test position. 4. Drain valve before the control valve must be opened. 8.7. Deaerator Steam Reducing Station. 1. The deaerator steam reducing station to be isolated is in standby position. 2. Both isolating valves (inlet and outlet) are closed and chain locked. 3. The pressure and temperature controllers 380 volts motors circuit breakers are racked out or in test position. 4. Drain and vent valve before the control valve must be opened. 5. Spray water manual isolating valve is closed. 8.8. Superheater Attemperators Spray water. 1. The superheater attemperators spray water to be isolated is in by-pass position (by-pass valve is open). 2. Both isolating valves (inlet and outlet) are closed and chain locked. 3. The spray water control valve 380 volts motor circuit breaker is racked out or in test position. 4. Drain valve after the control valve must be opened. 8.9. Boiler Waste Drain Pump. 1. Stop the pump and pressed in the emergency push button or put in SWG position in TCR. 2. Its 380 volts circuit breaker is racked out or in test position and the space heater MCB is switch off & tagged. 3. The Discharge manual valves is closed and chain locked. BOILER OVERHAULING ISOLATION PROCEDURE: 1. Boiler is shut down, drained and vented. Boiler temperature is 50

O C

2. All feedwater pumps are out of service. Isolated according to the above isolation procedure. 3. Both F.D. fans are out of service. Isolated according to the above isolation procedure. 4. LP Gas reducing stations 1 and 2 are out of service, isolated and purge by Nitrogen gas. 5. The cooling air fans are out of service and isolated according to procedure stated above. 6. Fuel oil pumps are out of service and isolated. 7. The H.P. steam valve and its by-pass are closed, chain locked and their motors C.B’s. are switch off. 8. The H.P. steam interconnection valve and its by-pass are closed, chain locked and their motors C.B’s. are

switch off. 9. F.W. interconnection valve and its by-pass are closed, chain locked and their motors C.B’s. are switch off. 10. Make-up water valve to feed water tank is closed, chain locked and their motors C.B’s. are switch off.

Page 38: BABCOCK BOILER 1 - 6 Instruction Manual

38

A - 10. Boiler abnormal operation & Trouble –shooting: - TROUBLE SHOOTING

Process plants operate maximum days of the month to cover the overall costs. The remaining days of the month operate to make profit. If the process is down for some days, then the company cannot cover the costs and no profit has been made. So, respective persons must quickly and successfully solve any problems that occur. Sometimes the problems occur during startup, sometimes just after a maintenance turn-around, and sometimes unexpectedly during usual operation. A trouble – shooting problem is one sometimes occurs that is unexpected to such an extent that it is perceived that some corrective action may be needed. The trouble occurs somewhere in a system that consists of various pieces of interacting equipment run by the people. The corrective action requires may be:

• to initiate emergency shut- down procedures.

• to forget the situation : it will eventually correct itself,

• to return the situation to ‘safe-park’ and identify and correct the cause and try to prevent a reoccurrence,

• to identify and correct the cause while the process continues to operate under current conditions. Now a days widely use and familiar with the word ‘trouble shooting’. WHAT IS THE TROUBLE SHOOTING ? Trouble shooting is the process used to diagnose the fault safely & efficiently, decide on corrective action and prevent the fault from reoccurring. Characteristics of a Trouble – Shooting Problem: The problems share four common characteristics: the problems differ in their seriousness and when they occur. This problems share mainly the following four characteristics: a) exhibit symptoms of deviations from the expected, b) have tight time constraints, c) are constrained by the physical plant layout & d) involve people.

a) exhibit symptoms of deviations from the expected: the symptoms may suggest fault on the plant or they might be caused by trouble upstream or downstream. The symptoms may be false and misleading because they result from faulty instrument or incorrect sampling. These kinds of symptoms might not reflect the real problem.

b) the tight time constraints related to safety and economics. The symptoms indicative of a potential explosion or major leak in the system. We should initiate immediate shut-down and emergency procedure.

c) The process configuration constrains a trouble shooter. The process is fabricated in a given way. The valves, lines and instruments are in fixed locations. We may want to measure or sample, but no easy way is available We have to work within the existing process system.

d) sometimes the cause of the problem is people. Someone may not have followed the expected procedure and was unwilling to admit error. Someone may open the bypass valve in the belief that ‘the process operates better that way’. The alarm may have turn OFF. The orifice plate may have been put in backwards.

When emergencies arise, due to logical, physical or fault causes, analyze and identify the causes, decide on the most applicable action, and proceed quickly. It is essential that an operator know the plant thoroughly to handle emergencies. Proper knowledge of the plant not only will make it possible to act wisely but also will give the operator the necessary confidence. Learn what constitutes safe practices and how they are applied to plant. Do not shut down unless it is absolutely necessary, but do not hesitate to shut down rather than resort to unsafe practices. When emergencies of this nature arise, quick and decisive action is important, and a through knowledge of the plant and a pre-considered line of action are essential. Study the various means available sources and utilize them in proper way. “When any problem arises, it might be some causes and several solutions in our hand, which one perfect and applicable it is depending on experience & broad knowledge regarding the subject.”

Page 39: BABCOCK BOILER 1 - 6 Instruction Manual

39

In the processing plant several problems & difficulties are arising, all of them are not possible to add due to our limitation; only some of them difficulties and their causes show bellows: -

Plant difficulties encountered in operation: A. Oil firing A summary of the difficulties that may encountered in operating oil fired plant are as follows:-

1. Failure of the oil to flow to the pumps due to inactive venting of the tank. 2. Clogged strainers caused by sludge deposits in the tank 3. Failure of pumps to operate due to air leaks in the suction line. 4. Vapor formation in the pump suction line as a result of too high temp. in tank. 5. Oil too heavy to flow to the pumps because of insufficient heating 6. Faulty atomizing caused by: a. too low an oil temperature.

b. carbon formation on burner trips. c. worn burner trips d. too low oil pressure. e. insufficient steam or air.

7. Smoke, poor combustion, and flames striking furnace walls caused by:

a. faulty atomization of oil. b. incorrect adjustment of air supply. c. automatic control not functioning properly.

8. Fire hazard and unsightly appearance caused by leaks in the pump discharge line. B. Boiler water level: Thought should be given to the procedure to be followed if difficulty is experienced in maintaining the water level in the boiler. Small oil / gas fired boilers equipped for automatic operation have low water fuel-cutoff devices. In the event of low water, the fuel valve automatically closed and the water level restored. However, industrial and utility plant shutdown must be avoided if at all possible. Alarms are provided, but in the event of high or low water, the operator must decide on the action to be taken. When the water level in the drum drops below the minimum required as specified by the boiler designer, stop the fuel and air supplies.

� Priming & foaming are caused by boiler water high in solids, high capacities, high water level, or a combination of these. Foaming is serious, since it makes it difficult to determine the water level. Priming can result in a mixture of steam and water in steam lines, causing water hammer, which may result in rupture of the piping system. When this trouble develops, reduce the capacity and blow the boiler down through the surface blow off, if one is provided; otherwise, use the main blow off. If the priming becomes so serious that the water level can no longer be detected, close the steam valve long enough to determine the correct level. Blow down the gauge glass and water column to make sure the water level indicated is correct. If conditions do not return to normal, take the boiler out of service.

C. Boiler tube failure: Stop the fuel feed and proceed to reduce combustion. Maintain water level unless this affects the feed water supply. This is a matter that requires instant decision on the part of operator, and the correct action depends on the size of the leak and available reserve supply of water. The pressure should be reduce as quickly as possible to prevent the blow of water and steam from cutting other tubes. Except for the fact that tube failures cause boiler outage, they are not considered serious. Operating a boiler with tube leak, escaping water or steam that can cut other tubes by impingement and cause a chain reaction of tube failures. With the loss of water or steam, a tube failure can change boiler circulation and possible cause overheating in the circuits, which can lead to further failures. Small leak can be detected at times by loss of water from the system, by the loss of chemicals from a drum type boiler or by noise that is created by the leak. Damage of boiler tubes are normally recognized by the following signs:

a. Pressure increase in combustion chamber. b. Increase of difference between water & steam flow. c. Changing in flue gas temperature without changing load.

Page 40: BABCOCK BOILER 1 - 6 Instruction Manual

40

d. Blowing noise in the boiler. e. Steam at chimney exit.

If above reason appeared, shut down the boiler normal way. If serious leaking, stop boiler by pressing emergency button. D. Incase of more then one burner tripping, put muster control immediately on Hand Control. Reduce load according to still available burner load.

8 burner up to 100 % load approx. = 360 t/h 6 burner up to 70 % load approx. = 240 t/h 3 burner up to 30 % loads approx. = 120 t/h.

When trouble is over, change Hand control to AUTO. E. If all burners are tripped, turbine will trip due to inter lock. If inter lock is not operating, trip turbine with emergency button. F. Break down of oil / air ratio control or gas/air ratio control. Change master control to Hand. Change oil / air ratio respectively gas /air ratio (air flow & fuel flow) keep the plant running. Keep sufficient air by observing 02. 4. Break down temperature control, change immediately from AUTO to Hand ( manual position) if temperature dropping too far ,quickly trip the turbine. Abnormally low steam temperatures may also produce by:

b. Insufficient excess air. c. Higher then design feed water temperature. d. Excessive moisture carries over from the boiler. e. A fouled super heater externally & internally. f. Leaking spray water valves. g. Poorly adjusted control equipment.

On the other hand following conditions can produce steam temperature abnormally high:

a. dirty furnace b. Too much excess air c. Lower than design feed water temperature. d. Irregular ignition or delayed combustion. e. Poorly adjust control equipments. If temperature exceeds maximum allowed value reduce burner load immediately.

G. Failure of the fuel supply: - low capacity, too much primary/ combustion air and disturbance from blowing soot may result in loss of ignition when fuel is burned in suspension. If the equipment is supplied with a flame detector the fuel feed will be shut off automatically. H. Safety valve leak: - even pressure lower than for which it is set, try to free it by operating the lift levers. If this fails to stop the leak, the valve must be repaired or replaced. Never attempt to stop a leaking safety valve by blocking or fighting the spring. I. Gauge glass breaks: -shut off the flow of steam and water. While the gauge glass is out of service, check the water level by using the try cock. Before inserting the new gauge glass, blow out the connections to make sure that no broken pieces remain in the fitting, and check the glass and gasket for the correct length and size. Pull up the packing slowly and not to tightly to avoid breaking the glass. When the new glass is in position, open the top or steam valve first and allow the drain valve to remain open. This permits steam to circulate through the glass, gradually heating the entire surface to a uniform temperature. Then partly open the lower valve. After the water has reached the normal level, open the lower valve. After the water has reached the normal level, open both valves all the way. When the lower valve is first opened, the glass is subjected to a vibration in temperature that may result in breakage.

Page 41: BABCOCK BOILER 1 - 6 Instruction Manual

41

BURNER NOT FIRE

Possible Causes:

1. Pilot not burning. 2. Main gas valve solenoid coil burned out. 3. Water level too low or no water in sight glass. 4. Honeywell operating pressure switch defective. 5. Broken wire in burner circuit. 6. Loose or broken probe in water column. 7. Scale build-up on probe and/or water column.

Corrective Action:

1. Check the gas supply. 2. Replace solenoid coil. 3. Replace gas valve. 4. Replace operating pressure switch. 5. Check wiring for loose or broken connection.

BURNER NOT SHUT OFF

Possible Causes:

1. Pressure switches not operating. 2. Faulty operating mechanism on gas valve. 3. Broken wire in burner circuit (shorted to ground).

Corrective Action:

1. Replace pressure switch. 2. Replace gas valve. 3. Check for electrical short circuit and repair.

PILOT BURNER NOT BURNING OR NOT STAY LITGHT

Possible Causes:

1. Pilot burner orifice plugged or dirty. 2. Ignition wire burnt or shorting out. 3. Igniter lance cracked or broken. 4. Igniter lance misaligned. 5. Ignition module defective. 6. Pilot solenoid valve not opening. 7. Pilot regulator plugged or broken.

Corrective Action:

1. Clean pilot burner orifice. 2. Replace igniter. 3. Replace pilot safety relay. 4. Re-align igniter to the center of the pilot assembly. 5. Replace ignition module. 6. Replace pilot solenoid valve.

7. Clean or replace pilot regulator.

Page 42: BABCOCK BOILER 1 - 6 Instruction Manual

42

PRE-IGNITION OR POOR LIGHT OFF

Possible Causes:

1. Pilot in wrong location in relation to main burner. 2. Dirty main burner orifices.

Corrective Action:

1. Clean pilot burner and orifice without enlarging. 2. Locate pilot burner so that top of burner is 1/2” above and 1/2” to the side of main burner. 3. Clean burner caps with drill bit. Consult factory for proper drill bit size. Caution: be careful to avoid any

increases in orifice size. 4. Adjust barometric damper in stack. Check for collapsed stack or restriction in stack.

PUMP NOT PERFORMING PROPERLY

Possible Causes:

1. No water being supplied to suction side of pump. 2. Plugged strainer screen. 3. Check valves worn or leaking. 4. Pump leaking at shaft. 5. Pump out of adjustment. 6. Air lock. 7. Vapor lock.

Corrective Action:

1. Clean lines connecting float tank to water jacket on 9.5, 10 & 15 HP models. 2. Remove and clean pump intake strainer screen. Clean lines from water jacket to pump. 3. Repair or replace check valves. 4. Replace shaft seal and “O” ring in pump. 5. Adjust pump impeller. 6. With pump running, carefully loosen hex nut on angle check valve to bleed air from system. Tighten hex

nut when water starts escaping. 7. If vapor lock is caused by leaking check valves, replace check valves. If vapor lock is caused by too

high a temperature in the return tank, check all steam traps for proper operation and repair as required.

PUMP MOTOR WILL NOT RUN

Possible Causes:

1. Starter relay defective. 2. Broken electrical connection. 3. Motor burned out. 4. Inter lock block to start the pump

Corrective Action:

1. Replace starter relay. 2. Release the pump from inter lock blocking 3. Check wiring for loose or broken connection. 4. Repair or replace motor.

Page 43: BABCOCK BOILER 1 - 6 Instruction Manual

43

POOR BOILER PERFORMANCE (Low steam pressure or slow recovery)

Possible Causes:

1. Low water condition in boiler. 2. Insufficient fuel supply to burners. 3. Defective operating pressure switch. 4. Calcium deposits, (boiler scale) in water tube assembly. 5. Soot formation on water tube assembly.

Corrective Action:

1. Clean burners. 2. Replace operating pressure switch. 3. De-scale boiler or replace plugged water tube assembly. 4. Remove soot from tubes by means of soot blowers. 5. Improper fuel air ration. 6. Fuel oil / gas caloric values are poor for improper combustion.

SIGHT GLASS GASKETS LEAK

Possible Causes:

1. Gaskets deteriorated. 2. Fittings improperly aligned.

Corrective Action:

1. Boiler shut down and allow cooling down. 2. Replace gaskets. 3. Loosen nuts, carefully align sight glass fittings and tighten nuts.