Issue: 5 9 th July 2019 BA564G Two Input General Purpose Counter Issue 5

BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

Issue: 59th July 2019

BA564GTwo Input

General PurposeCounter

Issue 5

Page 2: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

1. Description

2. Operation2.1 Initialisation2.2 Controls2.3 Displays

3. System Design3.1 Power supply3.2 Pulse input

3.2.1 Input switching thresholds3.2.2 Switch contact input3.2.3 2-wire proximity detector input3.2.4 Open collector3.2.5 Magnetic pick-off input3.2.6 Voltage pulse input

3.3 Remote reset

4. Installation4.1 Location4.2 Installation procedure4.3 EMC4.4 Units of measurement and tag marking

on scale card.

5. Configuration and Calibration5.1 Calibration structure5.2 Accessing configuration functions5.3 Summary of configuration functions5.4 Input A: input-a

5.5 Input A type: inp.type

5.6 Input A debounce: debounce

5.7 Input b: input-b

5.8 Input b type: inp.type

5.9 Input b debounce: inp.type

5.10 Input A pulse counting edge: cntedg-a

5.11 Input b pulse counting edge: cntedg-b

5.12 Display update interval: update

5.13 Counting function: count

5.14 Upper display: di5p-1

5.15 Lower display: di5p-2

5.16 Position of decimal points: dp

5.17 Total scale factor: 5cale.t

5.18 Rate scale factor 5cale.r

5.19 Timebase: t-ba5e

5.20 Display filter: filter

5.21 Direction of count: up or dn

5.22 Reset value: clr val

5.23 Local reset: loc clr

5.24 Local total reset: clr tot

5.25 Local grand total reset: clr gtot

5.26 Reset grand total from configurationmenu: clr gtot

5.27 Security code: code

5.28 Reset configuration to factory defaults:r5et def

5.29 Display overflow

6. Pulse Output6.1 System design6.2 Configuration6.3 Access pulse output sub-menu:

pul5e op

6.4 Enable pulse output: enbl

6.5 Source of output pulse: 5ource

6.6 Divide output pulse frequency: divide

6.7 Output pulse width: duration

7. Configuration example

2222222222222222222222222

CONTENTS

The BA564G is CE marked to show compliance with the European EMC Directive 2014/30/EU

Page 3: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

8. Maintenance8.1 Fault finding during commissioning8.2 Fault finding after commissioning8.3 Servicing8.4 Routine maintenance8.5 Guarantee8.6 Customer comments

9. Accessories9.1 Units of measurement and instrument

identification.

9.2 Legend plate

9.3 Backlight

9.4 Alarms9.4.1 Solid state output9.4.2 Summary of configuration

functions.9.4.3 Alarm enable: enbl

9.4.4 Type of alarm: type

9.4.5 Setpoint adjustment: 5p1x9.4.6 Alarm function: hi.lo

9.4.7 Alarm output status: ni.nc

9.4.8 Hysteresis: h5tr

9.4.9 Alarm delay: dela

9.4.10 Alarm silence time: 5il

9.4.11 Flash display when alarmoccurs: fl5h

9.4.12 Access setpoint: ac5p

9.4.13 Adjusting alarm setpoints from display mode .

9.5 4/20mA output9.5.1 System design9,5,2 Configuration and calibration9.5.3 Access 4/20mA output sub-menu:

4-20 op

9.5.4 Enable 4/20mA output: enble

9.5.5 Select rate or total source:4-20type

9.5.6 Define display for 4mA output:4.000

9.5.7 Define display for 20mA output: 20.000

3

Page 4: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

1. DESCRIPTIONThe BA564G is a general purpose, field mounting twoinput Counter which can accept pulses on one or bothinputs. The Counter may be configured to show totaland rate for one of the following in engineering units:

Input A + Input b

Input A - Input b

Input A count direction controlled by Input b

Quadrature decoder (Input A and Input b electrically 90o apart)

A smaller six digit display may be activated to showthe composite pulse rate in engineering units persecond, minute or per hour.

In addition to counting applications, the BA564G candisplay the position, direction of movement and speedof a shaft or cable using the instruments quadraturedecoder.

The optically-isolated pulse output may be configuredto synchronously retransmit either of the two pulseinputs or a scaled output when the least significantdigit of the total display is incremented.

This instruction manual supplements the abbreviatedinstruction sheet supplied with each instrument.

2. OPERATIONFig 1 shows a simplified block diagram of theBA564G Counter. The instrument has two inputs,A and b, which can be individually configured toaccept pulses from most types of sensor. TheBA564G can display the total number of pulsesreceived from each input, or their sum ordifference, together with associated rates on aseparate display.

Fig 1 BA564G block diagram

The BA564G can be supplied with any of thefollowing factory fitted accessories:

Internally powered display backlight

Dual isolated alarms

Isolated 4/20mA output

4

Page 5: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

2.1 InitialisationEach time power is applied to a BA564G Counterinitialisation is performed. After a short delay thefollowing display sequence occurs:

All segments of the display are activated.

Counter starts functioning, using theconfiguration information stored in theinstrument’s permanent memory. Unless totaland grand total displays have been reset, newpulses will be added to the existing totals.

2.2 ControlsThe BA564G Counter is controlled and configured viafour front panel push buttons. In the display modei.e. when the instrument is counting the push buttonfunctions are:

Push Button Functions

) + & Grand total - shows Lo followed by leastsignificant 8 digits of the 16 digit grandtotal.

) + * Grand total - shows Hi followed by themost significant 8 digits of the 16 digitgrand total.If Local Grand Total Reset CLr Gtot inthe instrument configuration menu hasbeen activated, operating the ) and* buttons simultaneously for tenseconds will result in Clr . no beingdisplayed with the no flashing. Operatingthe * or & button will change thedisplay to Clr . YE5, the ) button willthen reset the grand total to zero whichwill be confirmed by a brief display ofGt Clrd. See 5.25

& + * If Local Total Reset CLr tot in theinstrument configuration menu has beenactivated, operating the & and *

buttons simultaneously for three secondswill reset the total display to zero andclear any pulses stored in the optionalpulse output.See 5.24

( + & Shows in succession firmware versionnumber, instrument function 2ch cntr

and any output accessories that arefitted:

-A Dual alarm outputs-P Pulse output (always fitted)-C 4/20mA output

( + ) Access to configuration menu

Note: When optional alarms are fitted, theBA564G Counter may be configured to providedirect access to the alarm setpoints from thedisplay mode when the ( and * buttons areoperated simultaneously.See 9.4.12 and 9.4.13

2.3 DisplaysThe BA564G Counter has two digital displays andassociated annunciators, plus a pulse inputindicator as shown on the front cover of thismanual.

Total Shows the total pulse count on thedisplay upper eight digit display. May be

reset via front panel push buttonsor by a remote reset switch.

Rate Shows the pulse rate on the lowerDisplay six digit display. Total and rate

displays may be reversed.

Pulse input This disc in the lower left handindicator corner of the display 'rotates' for

two seconds each time an inputpulse is received on either input.Appears to rotate continuouslywhen input frequency on eitherinput exceeds 0.5Hz.

Reset Activated while the total displayannunciator is being reset via the front panel

push buttons, or the external resetterminals.

Rate Identifies rate displayannunciator

Total Identifies total displayannunciator

RTx Retransmitted pulse annunciator annunciator.

Depends upon the setting of5ource in the pulse outputconfiguration menu.

5caled:

Annunciator activated eachtime pulse output open collectoris on, i.e. Ron is less than60Ω + 3V.

direct:

Annunciator continuously activated.

5

Page 6: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

3. SYSTEM DESIGN

Fig 2 illustrates the basic circuit that is used for allBA584G installations. For simplicity, the pulse outputis described sparately in section 6 and the optionalalarms and 4/20mA output are described in section 9of this manual.

Fig 2 Basic BA564G System

When designing a system using a BA564G Counter, itis important to remember that terminals 2, 6, 10 andRS2 are interconnected within the instrument. SeeFig 1.

3.1 Power supplyThe BA564G Counter requires a minimum of 10Vbetween terminal 1 & 2 and consumes:

10mA without optional backlightplus 6mA when terminals 3 & 4 are linkedplus 6mA when terminals 7 & 8 are linkedplus 16mA with optional backlight

3.2 Pulse inputsThe BA564G can display the total number ofpulses received and their rate from a wide varietyof pulse output sensors connected to either input.

When designing a system it is important toremember that terminals 2, 6, 10 and RS2 of theBA564G Counter are internally connected together.

3.2.1 Input switching thresholdsFor reliable operation the Counter pulse inputsmust fall below the lower threshold and rise abovethe upper thresholds shown in the following table.

Input transducerSwitching thresholds

Lower UpperOpen collector 2kΩ 10kΩ

Voltage pulse low 1.0V 3.0VVoltage pulse high 3.0V 10.0VMagnetic pick-off 0mV 40mV peakProximity detector 1.2mA 2.1mA

Switch 100Ω 1000Ω

Switch contact, proximity detector and opencollector sensors require energising to determinetheir state which is achieved by linking Counterterminals 3 and 4 for input A and terminals 7 and 8for input b.

3.2.2 Switch contact input

Any switch contact may be directly connected topulse input terminals 5 and 6 and to terminals 7and 8. The BA564G contains a configurabledebounce circuit to prevent contact bounce beingcounted. See sections 5.6 and 5.9.

3.2.3 2-wire Proximity detectorMost NAMUR 2-wire proximity detectors may bedirectly connected to a BA564G input, providingthe minimum operating voltage of the proximitydetector is less than 7.5V. The BA564G containsa configurable de-bounce circuit to prevent falsetriggering. Three levels of debounce protection areindependently available for each input. Seesections 5.6 and 5.9.

3.2.4 Open collector inputSensors with an open collector output to inputterminals 5 & 6 or to 7 & 8. Input polarity shouldbe onserved The BA564G contains a configurabledebounce circuit to prevent false triggering. Seesections 5.6 and 5.9.

6

Page 7: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

3.2.5 Magnetic pick-off input Sensors incorporating a magnetic pick-off will usuallyhave a low level ac voltage output which a BA564GCounter can sense when configured for a CoiL input.The BA564G contains a configurable debounce circuitto prevent false triggering. See sections 5.6 and 5.9.

3.2.6 Voltage pulse inputTwo voltage pulse input ranges are selectable in theBA564G Counters configuration menu, VoLt5 L andVoLt5 H. The BA564G contains a configurabledebounce circuit to prevent false triggering. Seesections 5.6 and 5.9.

3.3 Remote resetThe BA564G Counter's total display may beremotely reset by connecting terminals RS1 andRS2 together. Permanent interconnection inhibitscounting. Remote resetting may be accomplishedby any switch contact.

The BA564G total display may also be reset whenthe & and * push buttons are operatedsimultaneously in the operating mode i.e. when theinstrument is counting. See 5.24

7

Page 8: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

4. INSTALLATION

5.1 LocationThe BA564G Counter is housed in a robust IP66glass reinforced polyester (GRP) enclosureincorporating an armoured glass window andstainless steel fittings making it suitable for exteriormounting in most industrial on-shore and off-shoreinstallations. The Counter should be positionedwhere the display is not in continuous direct sunlight.

Field wiring terminals are located on the rear of theCounter assembly as shown in Fig 4.

To ensure electrical continuity between the twoconduit or cable entries, the enclosure back-box isfitted with a bonding plate which includes an M4 earthstud. This bonding plate may be mounted on theinside or outside of the enclosure. If the carbonloaded GRP enclosure is not bolted to an earthedpost or structure, this earth stud should be connectedto a local earth or the plant potential equalisingconductor.

An insulated M4 stud is provided in the bottom righthand corner of the back-box for interconnecting cablescreens.

Alternatively the BA564G Counter may be pipe orpanel mounted using a BA393G pipe mounting kit ora BA394 or BA395 panel mounting kit which areavailable as accessories.

4.2 Installation ProcedureFig 3 illustrates the instrument installation procedure.

A. Remove the Counter assembly by unscrewingthe four captive 'A' screws.

B. Mount the enclosure back-box on a flat surfaceand secure with screws or bolts through the four'B' holes. Alternatively use one of the pipe orpanel mounting kits which are available asaccessories.

C. Remove the temporary hole plug and install anappropriate IP and temperature rated M20 x1.5mm cable gland or conduit fitting. If twoentries are required, the supplied IP66 stoppingplug should be replaced with an appropriate IPand temperature rated M20 x 1.5mm cable glandor conduit fitting.

D. Feed the field wiring through the cable entry inthe back-box and connect the wires to theterminals on the rear of the instrument assemblyas shown in Fig 4. Tighten cable glands toensure they are sealed and replace theinstrument assembly on the back-box. Finallyevenly tighten the four 'A' screws.

Fig 3 BA564G installation procedure

Fig 4 Dimensions and terminal connections

8

Page 9: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

4.3 EMCThe BA564G complies with the requirements of theEuropean EMC Directive 2014/30/EU. For specifiedimmunity all wiring should be in screened twistedpairs, with the screens earthed at a common point.

4.4 Units of measurement and tag markingon scale card.

The Counter's units of measurement and taginformation are shown on a scale card which slidesinto the instrument.

New Counters are supplied with a printed scale cardshowing the requested units of measurement and taginformation. If this information is not supplied whenthe instrument is ordered, a blank scale card will befitted which can easily be marked on-site with a drytransfer or a permanent marker. Custom printedscale cards are available from BEKA associates as anaccessory.

To remove the scale card from a Counter carefully pullthe transparent tab at the rear of the instrumentassembly away from the assembly as shown inFig 5a.

Fig 5a Removing scale card

To replace the scale card carefully insert it into theslot on the right hand side of the input terminals asshown in Fig 5b. Force should be applied evenly toboth sides of the scale card to prevent it twisting.The card should be inserted until about 2mm of thetransparent tab remains protruding.

Fig 5b Inserting scale card into the instrument assembly.

9

Page 10: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

5.0 CONFIGURATION & CALIBRATIONThe BA564G Counter is configured and calibrated viafour front panel push buttons. All the configurationfunctions are contained in an easy to use intuitivemenu that is shown diagrammatically in Fig 7.

Each menu function is summarised in section 5.3 ofthis manual and each summary includes a referenceto more detailed information.

The isolated pulse output, including configuration, isdescribed in section 6 of this manual. When factoryfitted optional alarms and the optional 4/20mA outputare included, additional functions appear in theconfiguration menu which are described in section 9of this manual.

All new BA564G Counters are supplied calibrated asrequested at the time of ordering. If calibration is notrequested, Counters will have factory defaultconfiguration as shown in the following table, but caneasily be re-configured on-site.

Function Display DefaultInput A inP . tYPE oP . CoL

Debounce dEbounCE dEFAuLt

Input b inP . tYPE oP . CoL

Debounce dEbounCE dEFAuLt

Counting edge A CntEdG-A EdGE 1

Counting edge b CntEdG-b EdGE 1

Update uPdAtE 0.5

Count Count A:b

Upper display di5p-1 totAL

Lower display di5P-2 on

Decimal point dP Rate 00000 . 0

Total 00000000

Total scale factor 5CALE . t 001 . 00

Rate scale factor 5CALE . r 001 . 00

Timebase t-bA5E tb-01

Filter FiLter 24

Counter direction uP or dn uP

Clear value clr val 00000000

Local clear loc clr

Local total reset Clr tot oFF

Local grand total reset Clr Gtot oFF

Security code CodE 0000

Note: While the instrument is being configuredcounting continues so that any input pulses occurringduring this time are recorded.

5.1 Calibration structureFig 6 shows the calibration structure of the BA564GCounter. The two pulse inputs are processed by thecount function to produce a single output having theselected arithmetic function, such as the sum of pulseinput A and pulse input b. This output is passed tothe 5cALE . R and 5CALE . T functions allowing the rateand total displays to have different engineering units.

5CALE . t is a dividing factor that converts the outputfrom the Counter function into the required totaldisplay in engineering units. e.g. if the output fromthe Counter function is two pulses per pump strokeand a total display of thousands of pump strokes isrequired, 5CALE . t should be set to 2000.

5CALE . r is a dividing factor that converts the outputfrom the Counter function into a rate display withthe required engineering units. e.g. if the outputfrom the Counter function is two pulses per pumpstroke and it is required to display the pump strokerate, 5CALE . r should be set to 2.

The timebase t-bA5E is a multiplying factor thatdetermines if the instrument displays rate persecond, per minute or per hour.

The BA564G uses ‘real’ decimal points. Moving theposition of a decimal point in a scale factor willaffect the instrument calibration.

Fig 6 Calibration structure

10

Page 11: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

5.2 Accessing configuration functionsThroughout this manual the instrument front panelpush buttons are shown as &, *, ( and ) andlegends displayed by the instrument are shown in aseven segment font as displayed by the Counter e.g.FiLtEr and 5CALE . r.

Access to the configuration menu is obtained byoperating the ( and ) push buttonssimultaneously. If the instrument is not protected bya security code the first parameter inPut-A will bedisplayed. If a security code other than the defaultcode 0000 has already been entered, the instrumentwill display CodE. Press ( to clear this prompt andenter the security code for the instrument using the& or * push button to adjust the flashing digit, andthe ( push button to transfer control to the next digit.If the correct code has been entered pressing ) willcause the first parameter inPut-A to be displayed. Ifan incorrect code is entered, or a push button is notoperated within ten seconds, the instrument willautomatically return to the display mode.

All configuration functions and prompts are shown onthe upper eight digit display.

Once within the configuration menu the requiredfunction can be selected by scrolling through themenu using the & and * push buttons. Theconfiguration menu is shown diagrammatically inFig 7.

When returning to the display mode followingreconfiguration, the BA564G Counter will displaydAtA followed by 5AVE while the new information isstored in permanent memory.

If after accessing the configuration menu the intervalbetween operating any front panel push buttonexceeds one minute, the BA564G will automaticallyreturn to the display mode and any configurationchanges will not be stored in permanent memory.When making changes to multiple configurationfunctions, it is therefore sensible to occasionallyreturn to the display mode to save the changes thathave already been made.

5.3 Summary of configuration functionsThis section summarises all the configurationfunctions. When read in conjunction with Fig 7 itprovides a quick aid for configuring the Counter. Ifmore detail is required, each summary contains areference to a full description of the function.

Display Summary of function

inPut-A Contains a sub-menu with twofunctions:

inP . tYPE Select Input typedEbounCE Set debounce

See section 5.4

inP . tYPE [for Input-A]Configures input-A to accept oneof six types of input:

oP . CoL Open collector *VoLt5 L Voltage pulse <1 >3VVoLt5 H Voltage pulse <3 >10VCoiL Magnetic pick-offPr . dEt Proximity detector *ContACt Switch contact *

* Link terminals 3 & 4See section 5.5

dEbounCE [[[for Input-A]Defines level of input debounceapplied to the pulse input A toprevent false counting:

dEFAuLt

HEAVY

LiGHt

See section 5.6

inPut-b Contains a sub-menu with two functions:

inP . tYPE Select Input type dEbounCE Set debounce

See section 5.7

inP . tYPE [for Input-b]Configures input-b to accept oneof six types of input:

oP . CoL Open collector *VoLt5 L Voltage pulse <1 >3VVoLt5 H Voltage pulse <3 >10VCoiL Magnetic pick-off Pr . dEt Proximity detector *ContACt Switch contact *

* Link terminals 7 & 8See section 5.8

11

Page 12: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

Display Summary of function

dEbounCE [for Input-b]Defines level of input debounceapplied to the pulse input b to preventfalse counting:

dEFAuLt

HEAVY

LiGHt

See section 5.9

CntEdG-A Input A pulse counting edgeDefines whether the Counter isincremented/decremented on theleading or trailing edge of a pulse oninput A. See section 5.10

CntEdG-b Input b pulse counting edgeDefines whether the Counter isincremented/decremented on theleading or trailing edge of a pulse oninput b.See section 5.11

updAtE Display update intervalDefines the interval between displayupdates between 0.5 and 5 seconds.See section 5.12

Count Counting functionDefines the arithmetic relationship ofthe two pulse inputs. The totaldisplay can be derived from:

A:b Input A + Input b

A:-b Input A - Input b

A con b Input A controlled by Input b.

a rel b Quadrature input (for position display)

See section 5.13

di5P-1 Upper displayDefines whether rAtE or totAL isshown on the upper display. Theother variable will be shown on thelower display, providing the lowerdisplay is on in function dI5P-2.See section 6.14

Display Summary of function

di5P-2 Lower displayTurns the lower display, whichnormally shows rate, on or oFF.See section 5.15

dP Position of decimal pointsDefines the position of the decimalpoint in both the total and ratedisplays.See section 5.16

5CALE . t Total Scale Factor5CALE . t is a dividing factor thatconverts the pulse output fromarithmetic Count function into therequired total display inengineering units. 5CALE . t maybe adjusted between. 0.0001 and99999. e.g. if one pulserepresents 1 centimetre ofdispensed cable and the totaldisplay is required in metres,5CALE . t should be set to 100.0which is the number of centimetresin a metre.The total display is independent ofthe rate display.See section 5.17

5CALE . r Rate scale factor5CALE . r is a dividing factor thatconverts the pulse output from thearithmetic Count function into therequired rate display inengineering units. 5CALE . r maybe adjusted between 0.0001 and99999. e.g. if one pulserepresents 2 pump strokes and therate display is required in pumpstrokes, 5CALE . r should be set to0.5.The rate display is independent ofthe total display.See section 5.18

t-bA5E TimebaseSelectable multiplier allowing rateto be displayed in units persecond, per minute or per hour.Select:

tb-01 for rate / secondtb-60 for rate / minute

tb-3600 for rate / hourSee section 5.19

12

Page 13: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

Display Summary of function

FiLtEr Display filterIs an adjustable digital filter to reducethe noise on the rate display. Thefilter has two parameters eachrepresented by a digit adjustablebetween 0 and 9. The first digitdefines the amount of filtering appliedto the display, the second digit thedeviation from the displayed rate atwhich the filter will be overridden andthe rate display will move rapidly tothe new value.See section 5.20

up or dn Direction of countDetermines whether pulses at inputsA and b increment or decrement thetotal display.See section 5.21

CLr VAL Reset valueDefines a preset number to which thetotal display will be set when theBA564G Counter is locally orremotely reset. Enables theinstrument to count down from apreset number. See section 5.22

LoC CLr Local resetContains sub-menu with twofunctions enabling the total and thegrand total to be reset via the frontpanel push buttons while the Counteris in the display mode.See section 5.23

Clr tot Local total resetWhen on is selected total display isreset when & and * buttons areoperated simultaneously for morethan 3 seconds in the display mode.See section 5.24

Clr Gtot Local grand total resetWhen on is selected the grand totalmay be reset when ) and *

buttons are operated simultaneouslyfor more than 10 seconds in thedisplay mode - see section 2.2 fordetails.Note: Once reset, the grand total cannot be restored.See section 5.25

Display Summary of function

Clr Gtot Resets grand total to zero fromwithin configuration menu.This function resets the grand totalto zero from within theconfiguration menu when CLr YE5

is selected.Note: Once reset, the grand totalcan not be recovered.See section 5.26

CodE Access codeDefines a four digit alphanumericcode that must be entered to gainaccess to the configuration menu.Default code 0000 disables thesecurity function and allowsunrestricted access to allconfiguration functions. See section 5.27

r5Et dEF Reset configuration to factorydefaults.Returns the BA564G Counter tothe factory defaults shown insection 6.0 To prevent accidentaluse the request must be confirmedby entering 5urE before the resetwill be executed. See section 5.28

13

Page 14: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

14

Page 15: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

15

Page 16: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

5.4 Input A: inPut-A

The Input A function contains two sub-functionsinP . tYPE and dEbounCE that define the type of inputand the amount of input noise rejection.

5.5 Input A type: inP. tYPE

inP . tYPE is a sub-menu in the inPut-A function whichdefines the type of input sensor or input pulse that theinstrument will count at Input-A. To check or changethe type of input, select inPut-A in the configurationmenu and press ( which will reveal the inP. tYPE

prompt, pressing ( again will show the existingInput-A setting. If set as required press ) twice toreturn to the configuration menu, or repeatedly pressthe & or * button until the required type of input isdisplayed and then press ) twice to return to theconfiguration menu.

One of following six types of input may be selected:

Switching thresholds Low High

oP . CoL Open collector 2 2 10kΩVoLt5L Voltage pulse low 1 1 3VVoLt5H Voltage pulse high1 3 10VCoiL Magnetic pick-off 0 40mVPr . dEt Proximity detector 2 1.2 2.1mAContACt Switch contact 2 100 1000Ω

Notes:1. Maximum voltage input +30V.

2. For sensors connected to Input-A that requireenergising to detect their state i.e. proximitydetectors, switch contacts or open collectorsensors, terminals 3 & 4 of the BA564G shouldbe linked together.

3. To count correctly, the input pulse must fallbelow the lower switching threshold and riseabove the higher switching threshold.

4. See section 5.6 for typical maximum countingfrequency.

5.6 Input A debounce: dEbouncE

dEbouncE is an adjustable sub-menu whichprevents the input miscounting when the inputpulse has noisy edges, such as those resultingfrom a mechanical contact closing and bouncing.The debounce function only applies to the input inwhich the function is located.

Three levels of protection may be independentlyselected for each input. The amount of debounceapplied depends upon the type of Counter inputthat has been selected for the input in theassociated inP . tYPE function.

Select inPut-A in the configuration menu andpress ( which will reveal the inP . tYPE prompt,press the & or * button to select dEbouncE

followed by ( to reveal the existing setting.Pressing the & or * button will scroll through thethree levels. When the required level has beenselected, pressing ) twice will enter the selectionand return the display to the configuration menu.

The following table shows the minimum time thatthe input pulse must be continuously above theupper input switching threshold and continuouslybelow the lower switching threshold to ensure thatthe Counter processes the input pulse. Inputswitching thresholds are shown in section 5.5.

debouncelevel

Min input pulse width

Type of Input

Contact All others

Default 1600µs 40µs

Heavy 3200µs 350µs

Light 400µs 5µs

The maximum counting frequency of the BA564Gdepends upon the debounce level selected, theshape of the input pulse and its amplitude. Thefollowing table assumes a square wave input andis included for guidance. The maximum countingfrequency will be lower if the input pulses havesloping edges and the pulse amplitude only slightlyexceeds the input switching thresholds.

ONLY FOR GUIDANCE

debouncelevel

Max counting frequency

Type of input

Contact All others

Default 250Hz 12kHz

Heavy 120Hz 2kHz

Light 1000Hz 100kHz

The minimum counting frequency is 0.01Hz.Below this frequency the rate display will be forcedto zero.

16

Page 17: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

5.7 Input b: inPut-b

The Input b function contains two sub-functionsinP . tYPE and dEbounCE that define the type of inputand the amount of input noise rejection.

5.8 Input b type: inP. tYPE

inP. tYPE is a sub-menu in the inPut-b function whichdefines the type of input sensor or input pulse that theinstrument will count at Input-b. To check or changethe type of input, select inPut-b in the configurationmenu and press ( which will reveal the inP. tYPE

prompt, pressing ( again will show the existingInput-b setting. If set as required press ) twice toreturn to the configuration menu, or repeatedly pressthe & or * button until the required type of input isdisplayed and then press ) twice to return to theconfiguration menu.

One of following six types of input may be selected:

Switching thresholds Low High

oP . CoL Open collector 2 2 10kΩVoLt5L Voltage pulse low 1 1 3VVoLt5H Voltage pulse high1 3 10VCoiL Magnetic pick-off 0 40mVPr . dEt Proximity detector 2 1.2 2.1mAContACt Switch contact 2 100 1000Ω

Notes:1. Maximum voltage input +30V.

2. For sensors connected to Input-b that requireenergising to detect their state i.e. proximitydetectors, switch contacts or open collectorsensors, terminals 7 & 8 of the BA564G shouldbe linked together.

3. To count correctly, the input pulse must fallbelow the lower switching threshold and riseabove the higher switching threshold.

4. See section 5.6 for the maximum countingfrequency.

5.9 Input b debounce: dEbouncE

Exactly as input A, please see section 5.6

5.10 Input A pulse counting edge: CntEdg-A

This function allows the edge on which a countoccurs to be selected. It applies to input A for allcounting modes except quadrature (A rEL b).

To check or change the input A pulse edge onwhich the count occurs select CntEdG-A from theconfiguration menu and press ( which will revealEdGE 1 or EdGE 2. If required press the & or *button to change the setting, followed by the )

button to return to the configuration menu.

EdGE 1

Type of input Counting edgeVoltage Low to highSwitch contact Closed to openOpen collector Closed to openProximity detector High to low current

EdGE 2

Type of input Counting edgeVoltage High to lowSwitch contact Open to closedOpen collector Open to closedProximity detector Low to high current

Note:The counting edge function CntEdg-A is notincluded in the configuration menu when theBA564G Counter has a quadrature inputA rEL b. In quadrature mode the instrument willcount up when the rising edge of input-b leadsthe rising edge of input-A.See section 5.13.

5.11 Input b pulse counting edge: CntEdg-b

This function allows the edge on which a countoccurs to be selected. It applies to input b for allcounting modes except quadrature A rEL b andinput A controlled by input b A Con b.

To check or change the input b pulse edge onwhich the count occurs select CntEdG-b from theconfiguration menu and press ( which will revealEdGE 1 or EdGE 2. If required press the & or *button to change the setting, followed by the )button to return to the configuration menu.

EdGE 1 Type of input Counting edge

Voltage Low to highSwitch contact Closed to openOpen collector Closed to openProximity detector High to low current

EdGE 2

Type of input Counting edgeVoltage High to lowSwitch contact Open to closedOpen collector Open to closedProximity detector Low to high current

17

Page 18: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

Note:The counting edge function CntEdg-b is notincluded in the configuration menu when theBA564G Counter has a quadrature input A rEL b orwhen input A is controlled by input b A Con b. Inquadrature mode the instrument will count upwhen the rising edge of input-b leads the risingedge of input-A.See section 5.13.

5.12 Display update interval: uPdAtE

If either the rate or the total display is likely to changerapidly, a longer interval between display updatesmay simplify reading. This function allows one of sixdifferent display intervals between 0.5 and 5 secondsto be selected. The selected display update intervaldoes not affect the update time of any otherinstrument function.

To adjust the update interval select uPdAtE from theconfiguration menu and press ( to reveal thecurrent update interval. Pressing the & or *button will scroll through the six times. When therequired interval has been selected press ) to enterthe selection and return to the configuration menu.

5.13 Counting function: Count

This function defines the arithmetic relationshipbetween Inputs A and Input b. The following fourmodes may be selected:

Display Input count modeA : b Pulses at input A added to

pulses at input b.

A : -b Pulses at input bsubtracted from pulses at input A. 1

A Con b Input b controls count direction of input A. 1

Input b Input ALow Up counterHigh Down counter

A rEL b Quadrature input with sensors electrically 90o apart. 1

Note:1. The pulse output is not available with these

count modes.

Fig 8 shows the voltage waveforms at the two inputsand the resulting total display when the BA564G isconfigured to count up on a rising edge.

Fig 8 Counting waveforms

Note:1. For a quadrature input the two signals do not

require equal marks and spaces to achievereliable counting.

5.14 Upper display: di5P-1

Usually the total count is shown on the largerupper eight digit display, but this function reversesthe display locations allowing rate to be shown onthe larger upper display and total on the smallerlower display.

To check the setting for the display, select dI5P-1

from the configuration menu and press ( whichwill reveal if the display is showing rAtE or totAL.The setting can be changed by pressing the & or* button followed by the ) button to enter theselection and return to the configuration menu.

18

Page 19: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

5.15 Lower display: di5P-2

This function turns the lower display on or off. Whenturned off, the BA564G will only have one eight digitdisplay which may be configured in the di5P-1

function to show the total count or rate.

To check the setting for the lower display, selectdi5P-2 from the configuration menu and press( that will reveal if the lower display is on or oFF.The setting may be changed by pressing the & or* button followed by the ) button to enter theselection and return to the configuration menu.

5.16 Position of the decimal points: dP

The upper and lower displays have eight and sixdigits respectively. This function enables the positionof the decimal point in both displays to beindependently positioned as shown below.

Upper display Total 0 0 0.0.0.0.0.0 1 of 5 positions or absent

Rate 0.0.0.0.0 1 of 4 positions or absent

Lower display Total 0.0.0.0.0.0 1 of 5 positions or absent

Rate 0.0.0.0.0 1 of 4 positions or absent

To adjust the position of the decimal points select dP

from the configuration menu and press (. Theupper display defined as the rate or total display byfunction di5P-1 (section 5.14) will be activated andidentified by the display annunciator as Rate or Total.The decimal point, which may be positioned as shownin the table above, is moved by operating the & or* push button. The & button moves the position ofthe decimal point to the left and the * button movesthe decimal point position to the right.

When the decimal point in the upper display has beenpositioned pressing the ( button will transfer controlto the lower display variable, but it will be shown andannunciated on the larger upper display. The positionof the decimal point may be positioned in the sameway by operating the & and * push buttons. Whenboth decimal points are positioned as required, enterthe settings and return to the configuration menu byoperating the ) button.

Note:Adjustment of a decimal point position willdisable the following outputs which must be re-enabled after the adjustment is complete:

Pulse output

Optional Alarm outputs

Optional 4/20mA output

5.17 Total scale factor: 5CALE . t

5CALE . t is a dividing factor adjustable between0.0001 and 99999 that enables the total to bedisplayed in engineering units. e.g. if one pulsefrom the arithmetic count function represents 1centimetre of dispensed cable and the total displayis required in metres, 5CALE . t should be set to100.0 which is the number of centimetres in ametre. If just the total number of input pulses isrequired, 5CALE . t should be set to 1.0. The totaldisplay is independent of the rate display.

To check or change the total scale factor select5CALE . t from the configuration menu and press (which will reveal the existing value with one digitflashing. The value of the flashing digit may bechanged by pressing the & or * button. Whenthis digit has been adjusted as required, pressing( will transfer control to the next digit. When allthe digits have been adjusted pressing ( willtransfer control to the decimal point that may bepositioned between any of the digits, or may beomitted by moving it to the right of the leastsignificant digit. When the total scale factor hasbeen entered, press ( to return to the 5CALE . t

prompt in the configuration menu.

Note:Adjustment of 5cale . t will disable thefollowing ouputs which must be re-enabledafter the adjustment is complete:

Pulse output

Optional Alarm outputs

Optional 4/20mA output

5.18 Rate scale factor: 5CALE . r

5CALE . r is a dividing factor adjustable between0.0001 and 99999 that enables the rate display tobe shown in engineering units. e.g. if one pulsefrom the arithmetic count function represents 2pump strokes and the rate display is required inpump strokes, 5CALE . r should be set to 0.5. If justthe rate of input pulses is required, 5CALE . r shouldbe set to 1.0. The rate display is independent ofthe total display.

The units of the rate display are counts per unit oftime. The unit of time is the timebase of theinstrument which is determined by t-bA5E

described in section 5.19.

To check or change the rate scale factor select5CALE . r from the configuration menu and press (which will reveal the existing value with one digitflashing. The value of the flashing digit may beadjusted by pressing the & or * button.

19

Page 20: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

When this digit has been adjusted as required,pressing ( will transfer control to the next digit.When all the digits have been adjusted pressing( will transfer control to the decimal point that maybe positioned between any of the digits, or may beomitted by moving it to the right of the least significantdigit. When the required rate scale factor has beenentered, press ) to return to the 5CALE . r prompt inthe configuration menu.

Note:Adjustment of 5cale . r will disable thefollowing ouputs which must be re-enabledafter the adjustment is complete:

Pulse output

Optional Alarm outputs

Optional 4/20mA output

5.19 Timebase: t-bA5E

The timebase multiplies the rate display by 1, 60 or3,600 depending upon whether the BA564G Counteris required to display rate per second, per minute orper hour. See Fig 6.

To check or change the timebase, select t-bA5E fromthe configuration menu and press ( which willreveal the current setting. Pressing the & or *button will scroll through the three options:

tb-1 for pulses / secondtb-60 for pulses / minute

tb-3600 for pulses / hour

When the required multiplier is displayed press ) toreturn to the t-bA5E prompt in the configurationmenu.

5.20 Display filter: FiLtEr

The digital display filter has two independentadjustable parameters enabling the rate displayresponse to be tailored for optimum performance.The filter parameters are controlled by a two digitnumber. The first digit defines the amount of filteringapplied to the display as shown below.

First digit Filter time constantSeconds

0X 01X 1.32X 4.33X 6.54X 8.75X 11.36X 15.77X 20.98X 25.29X 31.5

The second digit defines the deviation from thedisplayed rate at which the filter will be overriddenand the rate display will move rapidly to the newvalue.

Seconddigit

Magnitude of stepchange which willproduce a rapid

response

X0 OffX1 1%X2 2%X3 4%X4 8%X5 12%X6 16%X7 24%X8 32%X9 64%

By careful adjustment of the two parameters astable display with an acceptable input stepresponse can be obtained for most applications.

During commissioning it is recommend that initiallythe second digit is set to 0 (off) and the first digit isadjusted to provide acceptable rate displaystability. The second digit should then be increaseduntil the selected step size is greater than thenoise on the display signal, at which setting therate display will become stable. These will be theoptimum filter parameters for acceptable ratedisplay stability and a fast response to a large ratesignal change.

To check or change the filter select FiLtEr in theconfiguration menu and press ( which will revealthe current settings with the first digit flashing.Pressing the & or * button will adjust theflashing digit and ( will transfer control to thesecond digit. While making adjustments thefiltered rate display is shown on the lower displayso that stability can be assessed while adjustmentsare being made. When set as required, press the) button to enter the revised parameters andreturn to the FiLtEr prompt in the configurationmenu.

20

Page 21: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

5.21 Direction of count: uP or dn

This function defines whether input pulses incrementor decrement the total display. i.e. whether Input A isan up-counter or a down-counter.

When configured as a down-counter with a non-zeronumber entered for the reset value CLr VAL, theBA564G will count down from the re-set value to zero.

To check or change the count direction select uP or dn

from the configuration menu and press ( which willreveal the present setting. uP indicates that theinstrument is an up-counter and dn that it is a downcounter. Pressing the & or * buttons will togglethe instrument between the two settings. When setas required, press the ) button to enter the settingand return to the configuration menu.

Note:The Count function described in section 5.13also affects the direction in which the BA564Gcounts.

5.22 Reset value: CLr VAL

This function defines the value to which the totaldisplay is reset when the local or remote reset areoperated. This allows the BA564G to be used as apre-set down counter.

When the instrument is used as an up-counter,CLr VAL is normally set to zero.

To check or change the reset value select CLr VAL

from the configuration menu and press ( which willreveal the current setting with one digit flashing. Theflashing digit may be adjusted by pressing the & or* button. When this digit is correct, pressing ( willtransfer control to the next digit.

When all the digits have been adjusted press the )button to enter the revised number and return to theconfiguration menu.

5.23 Local reset: LoC CLr

The Local reset function contains two sub-functionsClr tot and Clr Gtot which when enabled allow thetotal display and grand total to be reset via theinstrument front panel push buttons while the BA564GCounter is in the display mode.

5.24 Local total reset: Clr tot

Clr tot is a sub-menu in the LoC CLr function. Whenactivated it allows an operator to reset the totaldisplay to the reset value [see section 5.22] while theBA564G Counter is in the display mode by operatingthe & and * push buttons simultaneously for morethan three seconds.

To check or change the setting select LoC CLr inthe configuration menu and press ( which willreveal the Clr tot prompt, operating ( again willshow if the local total reset is on or oFF. If set asrequired operate the ) button twice to return tothe configuration menu, or the & or * button tochange the setting followed by the ) button twiceto enter the change and return to the LoC CLr

prompt in the configuration menu.

Note:The total display may also be remotely resetto the reset value by connecting terminalsRS1 and RS2 together for more than onesecond. See section 3.3 of this manual.

5.25 Local grand total reset: Clr Gtot

The grand total is a separate sixteen digit counterwhich is incremented or decremented in parallelwith the total display, but is not reset when the totaldisplay is reset. The grand total may be viewed inthe display mode in two eight digit sections asdescribed in section 2.2 of this manual.

Clr Gtot is a sub-menu in the LoC CLr functionwhich when activated allows the operator to resetthe grand total display to zero from the displaymode by operating the ) and * pushbuttons simultaneously for more than ten seconds.

To check or change the setting select LoC CLr inthe configuration menu and press ( which willreveal Clr tot. Using the & or * button toselect Clr Gtot and press ( which will show iflocal grand total reset is on or oFF. If set asrequired operate the ) button twice to return tothe configuration menu, or the & or * button tochange the setting followed by the ) button twiceto enter the change and return to the LoC CLr

prompt in the configuration menu.

Note: Once reset, the grand total can not berecovered.

5.26 Reset grand total from configurationmenu: Clr Gtot

The grand total is a separate sixteen digit counterwhich is incremented or decremented in parallelwith the total display, but is not reset when the totaldisplay is reset. The grand total may be viewed inthe display mode in two eight digit sections asdescribed in section 2.2 of this manual.

To zero the grand total from within theconfiguration menu select CLr Gtot and press (which will cause the instrument to display Clr . no

with no flashing.

21

Page 22: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

Using the & or * push button change Clr no toclr ye5, pressing ( will result in the instrumentdisplaying 0000 with the first digit flashing. This is arequest to confirm the reset instruction by entering5urE. Using the & or * button set the first flashingdigit to 5 and press ( to transfer control to thesecond digit which should be set to u. When 5urE

has been entered pressing the ) button will resetthe grand total which will be confirmed by a briefdisplay of Gt Clrd, the instrument will automaticallyreturn to the Clr Gt prompt in the configuration menu.

Note: Once reset, the grand total can not berecovered.

5.27 Security code: CodE

Access to the instrument configuration menu may beprotected by a four digit security code which must beentered to gain access. New instruments areconfigured with the default security code 0000 whichallows unrestricted access to all configurationfunctions.

To enter a new security code select CodE from theconfiguration menu and press ( which will cause theBA564G Counter to display 0000 with one digitflashing. The flashing digit may be adjusted using the& and * push buttons, when set as requiredoperating the ( button will transfer control to thenext digit. When all the digits have been adjustedpress ) to return to the CodE prompt. The revisedsecurity code will be activated when the BA564GCounter is returned to the display mode.

Please contact BEKA associates sales department ifthe security code is lost.

5.28 Reset configuration to factory defaults r5Et dEF

This function returns the BA564G Counter to thefactory defaults shown in section 5.0. To preventaccidental use the request must be confirmed byentering 5urE before the configuration change willbe executed.

Select r5Et dEF from the configuration menu andpress (. the instrument will display 0000 with thefirst digit flashing. To confirm the instruction toreset all the configuration functions to factorydefaults 5urE must be entered. Using the & or* button set the first flashing digit to 5 and press( to transfer control to the second digit whichshould be set to u. When 5urE has been enteredpressing the ) button will reset all theconfiguration functions to the factory defaultsettings and zero both the total display and thegrand total. While resetting the BA564G Counterwill display - - - - - - - - before automaticallyreturning to the display mode when the operation iscomplete.

5.29 Display overflowThe BA564G Counter total has a maximum displayrange of -9999999 to 99999999 when shown onthe eight digit upper display. If this range isexceeded the display will be as shown below withall of the decimal points flashing:

Overrange 9.9.9.9.9.9.9.9

Underrange -9.9.9.9.9.9.9

When the total is shown on the lower six digitdisplay the maximum display range is -99999 to999999.

When a total overflow occurs the actual total maybe obtained from the instrument's grand totaldisplay which has sixteen digits - see 2.2.

To prevent future total display overflows occurringthe total scale factor 5CALE . t and the position ofthe decimal point in the total display dP should bereviewed.

22

Page 23: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

6. Pulse outputThe BA564G Counter has an opto-isolated solid statepulse output. The output is an open collector havingthe following electrical parameters:

Ron = 60 + 3VRoff = 1MImax = 10mA

The output pulse may be a synchronous duplicate ofInput A or Input b for re-transmission applications, or itmay be derived from the total display. When derivedfrom the total display the output pulse frequency maybe divided and the output pulse width defined.

The retransmitted RTx annunciator on the instrumentdisplay shows the status of the retransmitted pulseoutput. Annunciator activation depends upon thesetting of 5ource in the pulse output configurationmenu.

5caled:

Annunciator activated each time pulse outputopen collector is on, i.e. Ron is less than 60Ω+ 3V.

direct:

Annunciator continuously activated

6.1 System designThe Counter’s pulse output is a passive circuit i.e. notpowered, but it is totally isolated from all otherCounter circuits. The terminals P1 and P2 may beconnected to any other instrument with an opencollector pulse input.

Fig 9 shows how to produce a voltage pulse outputthat could be used to drive a safe area counter. Thepositive terminal of the pulse output circuit P1 isconnected to the Counter’s positive supply terminal 1.When an output pulse occurs and the open collectoroutput ‘closes’, P2 is connected to P1 and the pulsecurrent flows through resistor R1. The current flowingin the circuit is determined by R1 which should bechosen to limit the pulse output current to less than10mA. For a 24V supply R1 should be greater than2,200Ω.

Fig 9 Generating voltage pulse output

6.2 ConfigurationThe pulse output is configured via the PuL5E oP

sub-menu in the configuration menu as shown inFig 9.

This sub-menu allows the source of the outputpulse to be selected. For re-transmissionapplications the output pulse may be asynchronous duplicate of the pulse at Input A or atInput b by selecting dirECt A or dirECt b in the5ourCE sub-function.

Selecting 5CALEd derives the output pulse from thetotal display and introduces two additionalfunctions, diVidE and durAtion to the sub-menuallowing the output pulse frequency to be dividedand the output pulse width (duration) to be defined.

If the diVidE and durAtion functions areconfigured such that the output pulse frequencywith the specified pulse width can not be output inreal time, the number of pulses will be stored andtransmitted at the maximum possible speed.

When the total display is reset to zero or the powersupply to the BA564G Counter is disconnected orturned off, any stored pulses will not be retained.

23

Page 24: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

6.3 Access Pulse output sub-menu: PuL5E oP

Using the & or * push button scroll through theCounters configuration menu until PuL5E . oP isdisplayed, pressing ( will then access the pulseoutput sub-menu which is shown in Fig 10.

Fig 10 Pulse output configuration sub-menu

6.4 Enable pulse output: EnbL

This function allows the pulse output to be disabled orenabled without altering any of the pulse outputparameters. Using the & or * push button selectEnbL in the pulse output sub-menu and press (. toreveal the existing setting on or oFF. The function canbe changed by pressing the & or * push buttonfollowed by the ) button to return to EnbL prompt.

6.5 Source of output pulse: 5ourCE

The output pulse may be derived from:

dirECt A Output is duplicate of input Apulse.

dirECt b Output is duplicate of input bpulse.

5CALEd Output is derived from the totaldisplay and is only functional whenthe Count function is configured forA+b. When 5CALEd is selected twoadditional functions, diVidE anddurArion, appear in the pulseoutput sub-menu.

Using the & or * push button select 5ourCE inthe pulse output sub-menu and press (. to revealthe existing pulse source. The function can bechanged by pressing the & or * push buttonfollowed by the ) button to return to 5ourCE

prompt.

6.6 Divide output pulse frequency: diVidE

When the output pulse is derived from the totaldisplay the output pulse frequency may be dividedby:

1

10

100

1000

10000

Using the & or * push button select diVidE inthe pulse output sub-menu and press ( to revealthe existing divisor. The value can be changed bypressing the & or * push button to select therequired value followed by the ) button to returnto diVidE prompt.

Note: This function only appears in the sub-menuwhen the output pulse is derived from thetotal display.

6.7 Output pulse width: durAtion

When the output pulse is derived from the totaldisplay, the pulse width is defined by this function.One of 11 pulse widths in milliseconds may beselected:

0 . 1

0 . 5

1

2 . 5

5

10

25

50

100

250

500

Using the & or * push button select durAtion inthe pulse output sub-menu and press ( to revealthe existing pulse duration. The value can bechanged by pressing the & or * push button toselect the required value followed by the ) buttonto return to durAtion prompt.

Note: This function only appears in the pulseoutput sub-menu when the output pulse isderived from the total display.

24

Page 25: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

7. CONFIGURATION EXAMPLEA BA564G Counter is required to display the positionand speed, including direction, of a cable which issensed by two proximity detectors mounted on awheel with a circumference of 1m over which thecable runs. The sensors, which produce fifteenpulses per revolution, are positioned so their outputsare electrically 90° apart. The BA564G is required todisplay the position of the cable relative to a startingpoint in metres with a resolution of 0.1m, and to showspeed of the cable in metres per second with aresolution of 1m. The total display (position) is to beresettable by an external contact, not from theBA564G Counter front panel. Similarly the grand totalis not to be resettable from the BA564G Counter frontpanel. To prevent tampering the instrumentconfiguration menu is to be protected by security code1209.

The BA564G may be configured on-site withoutdisconnection from the power supply or from the twoproximity detectors.

If after accessing the configuration menu the intervalbetween operating any front panel push buttonexceeds one minute the BA564G will automaticallyreturn to the display mode and any configurationchanges will not be stored in permanent memory.When making multiple changes it is therefore sensibleto occasionally return to the display mode to save thechanges that have already been made.

Step 1 Enter the configuration menuPut the BA564G Counter in theconfiguration mode by simultaneouslypressing ( and ) push buttons.Assuming a security code has not alreadybeen entered the instrument will respondby displaying inPut-A which is the firstparameter in the configuration menu.See Fig 7.

Step 2 Select the type of inputsWith InPut-A displayed; press ( toreveal the existing setting. Using the& or * button select Pr . dEt, the inputfor a 2-wire proximity detector, and thenreturn to the inPut-A prompt in theconfiguration menu by pressing ).

Repeat for the second input inPut-b

Step 3 Select input count modeThe two proximity detectors arepositioned so their outputs areelectrically 90° apart. From thisinformation, in the quadrature inputmode the BA564G Counter can sensethe direction and angular movement ofthe wheel to which the proximitydetectors are attached. Hence, therelative position of the cable can bedisplayed by the counter.

Select Count from the configurationmenu and press (. Using the & or* button select A rEL b the quadraturefunction and press ) to return to the‘Count’ prompt in the configurationmenu.

Step 4 Define function of upper displayIn the example the cable position (totaldisplay) is required on the eight digitupper display.Select dI5P-1 from the configurationmenu and press ( which will reveal ifthe upper display is showing rAtE ortotAL. Using the & or * buttonselect totAL followed by the ) buttonto enter the selection and return to theconfiguration menu.

Step 5 Activate lower rate displayA rate display is required so the lowerdisplay must be activated.Select di5PLAY . 2 from the main menuand press ( to show the existingsetting. Using the & or * buttonselect on followed by ) to enter theselection and return to the configurationmenu.

Step 6 Position of decimal pointIn this example the BA564G is requiredto display total (position) with aresolution of one decimal place andrate (speed) with no decimal point.

Select d . P. from the configuration menuand press (. The BA564G will showand identify the total display with all thedigits activated. Using the & or *button position the decimal pointbetween the first and second leastsignificant digits.Operating the ( button will show andidentify the rate display with all thedigits activated, Using the & or *button position the decimal point to theright of the least significant digit i.e. notvisible. Finally press ) to return tothe configuration menu.

25

Page 26: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

Step 7 Enter the total scale factorIn this example the proximity detectorsproduce fifteen pulses per one metremovement of the cable. The positiondisplay is required in metres so the total(position) scale factor 5CALE . t should beset to 15.0.

Select 5CALE . t from the configurationmenu and press ( to view the currentvalue with one digit flashing. Use the &and * buttons to adjust each digit in turnand the ( button to transfer control to thenext digit and to the decimal point. Enter15.0 and return to the 5CALE . t prompt inthe configuration menu by pressing ).

Step 8 Enter the rate scale factorIn this example the proximity detectorsproduce fifteen pulses per one metremovement of the cable. The rate displayis required in metres per second so therate (speed) scale factor 5CALE . r shouldbe set to 15.0.

Select 5CALE . r from the configurationmenu and press ( to view the currentvalue with one digit flashing. Use the &and * buttons to adjust each digit in turnand the ( button to transfer control to thenext digit and to the decimal point. Enter15.0 and return to the 5CALE . r prompt inthe configuration menu by pressing ).

Step 9 Set the display timebaseIn this example the rate display (speed) isrequired in metres per second.Select t-bA5E from the configurationmenu and press ( to reveal the currentsetting. Using the & or * button scrollthrough the three options and selecttb-01. Return to the t-bA5E prompt inthe configuration menu by pressing ).

Step 10 Adjust the rate display filter The rate display filter parametersshould be adjusted experimentally afterinstallation to provide a stable ratedisplay with an acceptable stepresponse.

During commissioning it isrecommended that initially the seconddigit of the rate parameters is set to 0(step response off) and the first digit(amount of filtering) is adjusted toprovide acceptable rate display stability.The second digit should then beincreased until acceptable rate displaystability is once again achieved.

To adjust the filter parameters selectFiLtEr from the main menu and press( to reveal the current setting. Thefirst digit will be flashing and may beadjusted using the & or * button.The ( button will transfer control tothe second digit. When both are set asrequired, return to the FiLtEr prompt inthe main menu by pressing ).

Note: While adjusting the filter, the rate isshown on the lower display so thatstability can be assessed.

Step 11 Direction of countIn this application the direction of countwill determine whether a cablemovement is shown as a positive ornegative position and rate. If input Aoccurs before input b, a positive displaywill result when the BA564G isconfigured to count up.

Select uP or dn from the main menuand press ( to reveal the existingsetting. Using the & or * buttonselect uP followed by ) to enter theselection and return to the configurationmenu.

26

Page 27: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

Step 12 Turn local clear offIn this example the operator must not beable to zero the total (cable position)display or the grand total from theinstrument front panel. Both local clearfunctions should therefore be turned off.

Select LoC CLr from the main menu andpress ( which will result in Clr tot beingdisplayed, press ( again to show if thefunction is turned on or oFF. Using the &or * button toggle the display to oFF andpress ) to return to the Clr tot promptfrom which Clr Gtot can be selected bypressing the & or * button. Turn thisfunction off in exactly the same way beforereturning to the configuration menu bypressing the ) button twice.

Step 13 Define the security codeDefining an access security code preventsunauthorised access to the configurationmenu. Select CodE in the configurationmenu and press ( which will reveal theexisting security code with the first digitflashing. Using the & and * buttonsenter the new code 1209 digit by digit.The ( button transfers control betweendigits. When the new code has beenentered, press ) to return to theconfiguration menu.

Step 14 Return to the display modeFollowing completion of configuration,return the BA564G to the display mode bypressing ). The instrument will displaydAtA followed by 5AVE while theconfiguration changes are stored inpermanent memory.

8. MAINTENANCE

8.1 Fault finding during commissioningIf a BA564G Counter fails to function duringcommissioning the following procedure should befollowed:

Symptom Cause Check:No display No power supply,

or incorrectwiring.

Note: Terminals 2,6, 10 & RS2 areinterconnected

within theinstrument.

That there isbetween 10 and

30V on terminals1 & 2 withterminal 1positive.

Counter isreceiving powerbut pulse inputindicator not

rotating.

No input pulses,incorrect inputconfiguration,

incorrect linking ofterminals 3 & 4

and terminals 7 & 8.

Inputconfiguration.

Linking ofterminals 3 & 4.

andterminals 7 & 8.

That input signalpolarity is correct.

Pulse inputindicator rotatingbut incorrect rate

display.

Incorrect ratedisplay calibration 5CALE . r

t-bA5E

Pulse inputindicator rotatingbut incorrect total

display.

Incorrect totaldisplay

calibration.

Remote resetswitch contacts

closed.

5CALE . t

That RESETannunciator ondisplay is not

activated. If it is,check reset wiring

and switch.

Pulse inputindicator rotatingbut total display

showing9.9.9.9.9.9.9.9

or-9.9.9.9.9.9.9

Or if shown onthe lower display

9.9.9.9.9.9or

-9.9.9.9.9

Total display hasoverflowed.

Repositiondecimal point intotal display orenter a different

5CALE . t

to reduce totaldisplay

magnitude.

Unstable ratedisplay

Noisy pulse inputsignal

Eliminate sourceof electrical noise.

Increase debounce and/or

display filter.Unable to enter

configurationmenu.

Incorrect securitycode

That the correctsecurity code is

being used.

Contact BEKA ifcode is lost.

Alarms do notfunction

Alarms have beendisabled following

calibrationchange.

Re-enable bothalarms.

27

Page 28: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

8.2 Fault finding after commissioning

ENSURE PLANT SAFETY BEFORESTARTING MAINTENANCE

If a BA564G Counter fails after it has been functioningcorrectly, the following table may help to identify thecause of the failure.

Symptom Cause Check:No display No power supply. That there is

between 10 and30V on terminals

1 & 2 Pulse inputindicator not

rotating.

No input pulses Output fromsensor.

Wiring betweensensor and

BA564G Counter.Unstable rate

displayNoisy pulse input

signalLocate source of

electrical noise, orincrease

debounce andrate display filter.

If this procedure does not reveal the cause of thefault, it is recommended that the instrument isreplaced.

8.3 ServicingWe recommend that faulty BA564G Counters arereturned to BEKA associates or to your local BEKAagent for repair.

8.4 Routine maintenanceThe mechanical and electrical condition of theinstrument should be regularly checked. Inspectionfrequency should be adjusted to suit theenvironmental conditions.

8.5 GuaranteeInstruments which fail within the guarantee periodshould be returned to BEKA associates or our localagent. It is helpful if a brief description of the faultsymptoms is provided.

8.6 Customer commentsBEKA associates is always pleased to receivecomments from customers about our products andservices. All communications are acknowledged andwhenever possible, suggestions are implemented.

28

Page 29: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

9. ACCESSORIES

9.1 Units of measurement & instrumentidentification.

New BA564G Counters are supplied with a printedscale card showing the units of measurement and taginformation specified when the instrument wasordered. If this information was not supplied a blankscale card will be fitted which can easily be markedwith a dry transfer or a permanent marker on-site.

Custom printed scale cards are available asaccessories and may be easily fitted as shown insection 4.4 of this manual.

9.2 Legend plateThe BA564G Counter can also be supplied with ablank or custom laser engraved stainless steel legendplate - see Fig 4. The plate, which after installation isvisible from the front of the instrument, is suppliedloose with two fixing screws for securing it to the rearof the instrument's back-box. This plate can typicallyaccommodate:

1 row of 5 alphanumeric characters 10mm high

or 1 row of 6 alphanumeric characters 7mm high

or 2 rows of 10 alphanumeric characters 5mm high

9.3 BacklightThe BA564G Counter can be supplied with a factoryfitted backlight that produces green illuminationenhancing display contrast and enabling it to be readat night or in poor lighting conditions. The backlight isinternally powered from the instrument power supplyso that no additional wiring or intrinsically safeinterface is required, but the supply current increasesas shown below. Maximum current consumption

Without backlight 10mAAdditional for backlight 16mA

Addition with terminals 3 & 4 linked 6mA Addition with terminals 7 & 8 linked 6mA

----------Total current 38mA max

29

Page 30: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

9.4 AlarmsThe BA564G Counter can be supplied with factoryfitted dual alarms. Each may be independentlyconfigured as a rate display or total display, high orlow alarm. with a normally open, or a normally closedsolid state output.

Configurable functions for each alarm includeadjustable setpoint, alarm delay time and alarmsilence time. Hysteresis may be applied to ratealarms.

WARNINGThese alarm outputs should not be used forcritical safety applications such as a shutdown system.

When the BA564G power supply is turned off ordisconnected, alarm outputs will open irrespective ofwhether normally open or normally closed outputshave been selected. When designing a system anopen output should therefore be chosen for the alarmcondition.

Alarm annunciators on the instrument display indicatethe status of each alarm. If an alarm delay or silencetime has been selected the annunciator will flashduring the delay or silence period.

The BA564G internal counters are up-dated andcompared with the alarm setpoint twice per second,irrespective of the display update time selected. Thismay result in an alarm being delayed for up to half asecond after the rate or total has exceeded thesetpoint.

9.4.1 Solid state output Each alarm has a galvanically isolated single polesolid state switch output as shown in Fig 11. Theoutputs are polarised and current will only flow in onedirection. Terminals A1 and A3 should be connectedto the positive side of the supply.

Ron = less than 5 + 0.7VRoff = greater than 1M

Note: Because of the series protection diode sometest meters may not detect a closed alarmoutput

Fig 11 Equivalent circuit of each alarm output

The solid state output of each alarm may be used toswitch any circuit with parameters equal or less than:

V = 30V dcI = 200mA

9.4.2 Summary of configuration functionsWhen a BA564G Counter is supplied with alarmsthe Counter configuration menu is extended asshown in Fig 12. Each alarm may be configuredto operate on the rate or total display.

For simplicity Fig 12 only shows the configurablefunctions on the rate option of alarm AL1, the totaloption is identical except that the total alarms cannot have hysteresis. Configuration of alarm AL2is identical to alarm AL1.

The following table summarises each of the alarmconfiguration functions and includes a crossreference to more detailed information. Again onlythe functions on alarm AL1 are listed.

Display Summary of function

EnbL Alarm enableEnables or disables the alarm withoutchanging the alarm parameters.See section 9.4.3

tYPE Type of alarmDefines whether the alarm operates onthe rate or total display.See section 9.4.4

5P1r Alarm setpoint 1 or Adjusts the alarm setpoint. The5P1t alarm is activated when the rate or

total display equals the setpoint.Note: 5P1r is displayed for a rate alarmand 5P1t for a total alarm.See section 9.4.5

HI. LO Alarm functionDefines whether the alarm has a highor low function.See section 9.4.6

no . nc Normally open or normally closedoutput.Determines whether the single polealarm output is open or closed in thenon-alarm condition.See section 9.4.7

H5tr HysteresisAdjusts the alarm hysteresis. Onlyavailable on a rate alarm.See section 9.4.8

dELA Alarm delay timeAdjusts the delay between the displayequaling the setpoint and the alarmoutput being activated. See section 9.4.9

30

Page 31: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

Display Summary of function

5IL Alarm silence timeDefines the time that the alarm outputremains in the non-alarm conditionfollowing acceptance of an alarm.See section 9.4.10

FL5H Flash display when alarm occursWhen enabled, alternates the rate or totaldisplay between process value and alarmreference AL1 or AL2 when an alarmoutput is activated.See section 9.4.11

AC5P Access setpointSub-menu that enables direct access tothe alarm setpoints from the display modeand defines a separate security code.

31

Page 32: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

9.4.3 Alarm enable: EnbL

This function allows the alarm to be enabled ordisabled without altering any of the alarm parameters.Using the & or * push button select AL1 or AL2

from the configuration menu and press ( to reachEnbL in the alarm sub-menu. Pressing ( will thenreveal the existing setting. The function can bechanged by pressing the & or * push buttonfollowed by the ) button to return to the alarm sub-menu.

9.4.4 Type of alarm: tYPE

Alarm 1 and Alarm 2 are totally independent, bothmay be rate or total alarms, or one may beconditioned for rate and the other for total. Using the & or * push button select tYPE fromthe selected alarm sub-menu and press ( tocheck or change the function. The & or * pushbutton will toggle the selection between rAtE andtotAL, when set as required press the ) button toreturn to the alarm sub-menu.

Note: When tYPE is changed, the alarmconfiguration is automatically reset to thedefault values and the alarm is disabled. Itmust therefore be reconfigured before use.

32

Page 33: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

9.4.5 Setpoint adjustment: 5P1x & 5P2xThe rate alarm setpoints SP1r and SP2r may bepositioned anywhere between 000000 and 999999,and the total alarm setpoint SP1t and SP2t anywherebetween 00000000 and 99999999.

All the setpoints are adjusted in the same way, forexample, to adjust the setpoint of Alarm 1 which hasbeen configured to operate on the rate display.Using the & or * push button select 5P1r in theAL1 sub-menu and press ( which will reveal theexisting setpoint with one digit flashing. The requiredsetpoint can be entered using the & or * pushbutton to adjust the flashing digit and the ( button totransfer control to the next digit. When set asrequired press ) to enter the value and return to the5P1r prompt in the alarm 1 sub-menu.

9.4.6 Alarm function: Hi. Lo

Alarm 1 and Alarm 2 are totally independent, bothmay be Hi or Lo, or one may be conditioned as a Hialarm and the other as a Lo alarm. Using the & or * push button select Hi. Lo from theselected alarm sub-menu and press ( to check orchange the function. The & or * push button willtoggle the alarm function between Hi and Lo, whenset as required, press the ) button to return to theHi. Lo prompt in the alarm sub-menu.

9.4.7 Alarm output status: no . nC

Each single pole alarm output may be open or closedin the non-alarm condition. When the BA564G powersupply is turned off or disconnected, the alarmoutput(s) will open irrespective of whether normallyopen or normally closed outputs have been selected.Therefore, when designing an alarm system normallyclosed nc should be selected so that the output openswhen an alarm occurs or if the power supply fails.

Using the & or * push button select no . nC from theselected alarm sub-menu and press ( to check orchange the function. The & or * push button willtoggle the contact status between no and nC, whenset as required, press the ) button to return to theno . nC prompt in the alarm sub-menu

9.4.8 Hysteresis: H5tr

Hysteresis is only available on rate alarms so theH5tr function only appears in the configuration sub-menu when alarm tYPE has been set to rAtE. Duringconfiguration hysteresis is shown in the units of ratepreviously configured for the rate display.

Using the & or * push button select H5tr in theselected alarm sub-menu and press ( which willreveal the existing hysteresis with one digit flashing.The required hysteresis can be entered using the &or * push button to adjust the flashing digit and the( button to transfer control to the next digit. When

set as required press ) to enter the value andreturn to the H5tr prompt in the alarm sub-menu.

e.g. A BA564G Counter configured to display arate of 0 to 5000, with a high alarm set at 4000 andhysteresis of 100 will perform as follows:

High alarm will be activated when rateequals or exceeds 4000, but will not resetuntil the rate falls below 3900.

9.4.9 Alarm delay: dELA

This function enables activation of the alarm outputto be delayed for a fixed time following the alarmcondition occurring. The delay can be set in 1second increments up to 3600 seconds. If a delayis not required zero should be entered.

To adjust the delay select dELA using the & or *push button in the selected alarm sub-menu andpress ( which will reveal the existing delay timein seconds with one digit flashing. The requireddelay time can be entered using the & or *push button to adjust the flashing digit and the( button to transfer control to the next digit.When set as required press ) to enter the valueand return to the dELA prompt in the alarm sub-menu.

The alarm annunciator will start flashingimmediately an alarm condition occurs and willcontinue for the delay time, after which the alarmoutput will be activated and the alarm annunciatorwill be permanently activated.

9.4.10 Alarm silence time: 5IL

The alarm silence function is primarily intended foruse in small installations where the alarm outputdirectly operates an annunciator such as asounder. When the alarm silence time is set to anyfigure other than zero, the ( push buttonbecomes an alarm accept button.

After an alarm has occurred, operating the( button will cause the alarm output to revert tothe non-alarm condition for the alarm silence time.When an alarm is silenced the alarm annunciatorwill flash until the silence time expires.

To adjust the alarm silence time select 5iL usingthe & or * push button in the selected alarmsub-menu and press ( which will reveal theexisting alarm silence time in seconds with onedigit flashing. The required silence time can beentered using the & or * push button to adjustthe flashing digit and the ( button to transfercontrol to the next digit. When set as requiredpress ) to enter the value and return to the 5iL

prompt in the alarm sub-menu.

33

Page 34: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

9.4.11 Flash display when alarm occurs:FL5H

In addition to the two alarm annunciators on the lefthand side of the BA564G Counter display which showthe status of both alarms, this function provides aneven more conspicuous indication that an alarm hasoccurred.

When enabled, this function alternates the rate ortotal display between the numerical value and thealarm identification AL1 or AL2 when an alarm occurs.

Using the & or * push button select FL5H from theselected alarm sub-menu and press ( to check orchange the function. The & or * push button willtoggle the function between oFF and on, when set asrequired, press the ) button to return to the FL5H

prompt in the alarm sub-menu.

9.4.12 Access Setpoint: AC5P

This function activates a separate menu that providesdirect access to the alarm setpoints from the displaymode by simultaneously operating the ( and *buttons. An operator can therefore adjust the alarmsetpoints without having access to the configurationand alarm sub-menus. Protection againstunauthorised or accidental adjustment is provided bya separate security access code.

Using the & or * push button select AC5P from theconfiguration menu and press ( to reach the enablefunction EnbL. Pressing ( will reveal the existingsetting which can be toggled between on and oFF bypressing the & or * push button. When set asrequired, press the ) button to return to the EnbL

prompt from which a separate security access codecan be entered using the ACCd function which can beselected using the & or * push button.

To enter a new security code select ACCd from thesub-menu and press ( which will cause the BA564GCounter to display 0000 with one digit flashing. Theflashing digit may be adjusted using the & or *push button, when set as required operating the( button will transfer control to the next digit. Whenall the digits have been adjusted press ) to return tothe ACCd prompt. The revised security code will beactivated when the BA564G Counter is returned tothe display mode. Default security access code 0000will disable the security code allowing direct access tothe setpoints in the display mode by pressing the( and * buttons simultaneously.

Please contact BEKA associates sales department ifthe security code is lost.

9.4.13 Adjusting alarm setpoints from the display modeAccess to the two alarm setpoints from theBA564G Counter’s display mode is obtained byoperating the ( and * push buttonssimultaneously as shown in Fig 13. If the setpointsare not protected by a security code the alarmsetpoint prompt 5P1r or 5P1t will be displayeddepending upon whether a rate or total alarm hasbeen configured. If the setpoints are protected bya security code, CodE will be displayed first.Pressing ( again will allow the alarm setpointsecurity code to be entered digit by digit using the& and * buttons to adjust the flashing digit andthe ( push button to move control to the nextdigit. If the correct code is entered pressing )will then cause alarm setpoint prompt 5P1x to bedisplayed. If an incorrect security code is entered,or a button is not pressed within ten seconds, theinstrument will automatically return to the displaymode.

Once within the menu pressing the & or *buttons will toggle the display between the twoalarm setpoint prompts 5P1x and 5P2x.

Fig 13 Setpoint adjustment from the display mode

34

Page 35: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

To adjust an alarm setpoint select 5P1x or 5P2x andpress ( which will reveal the current setting. Theflashing digit of the setpoint may be adjusted usingthe & or * push button and the ( button to movecontrol to the next digit. When the required setpointhas been entered, pressing ) will return the displayto the 5P1x or 5P2x prompt from which the othersetpoint may be selected, or the instrument may bereturned to the display mode by pressing ) again.

Note: Direct access to the alarm setpoints from thedisplay mode is only available when the AC5P

menu is enabled - see section 9.4.12

35

Page 36: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

9.5 4/20mA output The BA564G Counter can be supplied with anoptional factory fitted galvanically isolated 4/20mAoutput which may be configured to represent the rateor total display.

9.5.1 System designThe Counter’s optional 4/20mA output is a passivecurrent sink i.e. not powered, but it is totally isolatedfrom all other Counter circuits. It is effectively a2-wire 4/20mA transmitter requiring a minimum supplyof 5V with the output current controlled by theCounter’s rate or total. Terminals C1 and C2 may beconnected to any other instrument with a 4/20mAtransmitter input with at least a 5V output as shown inFig 14. Terminals C2 and C4 are internally linked andmay be used for joining a return 4/20mA wire.

Fig 14 Application of 4/20mA output

9.5.2 Configuration and calibrationWhen a BA564G Counter is supplied with an optional4/20mA output the configuration menu is extended asshown in Fig 18. The 4/20mA output sub-menu isaccessed via the 4-20 oP function.

The 4/20mA output sub-menu allows the 4/20mAoutput to be controlled by the rate or the total display.

9.5.3 Access 4/20mA output sub-menu:4-20 oP

Access the BA564G Counter configuration menuas described in section 5.2. Using the & and *push buttons scroll though the menu until 4-20 oP

is displayed, pressing ( will then access the4/20mA output sub-menu which is shown in Fig 15.

Fig 15 4/20mA output configuration sub-menu

9.5.4 Enable 4/20mA output: EnbL

This function allows the 4/20mA output to beenabled or disabled without altering any of the4/20mA output parameters. Using the & or *push button select EnbL in the 4-20 oP sub-menuand press ( to reveal the existing setting on oroFF. The function can be changed by pressing the& or * push button followed by the ) button toreturn to EnbL prompt.

Note: When the 4/20mA output is disabled byselecting oFF, the output is a constant3.5mA irrespective of the instrumentdisplay.

9.5.5 Select rate or total source: 4-20tYPE

The 4/20mA output current can represent theBA564G Counter’s rate or total display and thisshould be defined before any other 4/20mA currentoutput functions are configured.

Using the & or * push button select 4-20tYPE inthe 4/20mA output sub-menu and press ( toreveal the existing setting totAL or rAtE. Thefunction can be changed by pressing the & or *push button followed by the ) button to return to4-20tYPE prompt.

36

Page 37: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

37

Page 38: BA564G Two Input General Purpose Counter1. DESCRIPTION The BA564G is a general purpose, field mounting two input Counter which can accept pulses on one or both inputs. The Counter

Note: If the controlling source of the 4/20mAoutput is changed i.e. from rate to total, the4/20mA output will be disabled and theoutput will be a constant 3.5mA irrespectiveof the instrument display.The 4/20mA output must always bere-enabled and reconfigured following thecontrolling source being changed.

9.5.6 Display which corresponds to 4mA output: 4 . 000

The BA564G Counter display which corresponds to a4.000mA output current is defined by this function.Using the & or * push button select 4 . 000 in the4/20mA output sub-menu and press ( to reveal theexisting rate or total display with one digit flashing.The required display can be entered using the& or * push button to adjust the flashing digit andthe ( button to transfer control to the next digit.When set as required press ) to enter the value andreturn to the 4 . 000 prompt in the 4/20mA output sub-menu.

9.5.7 Display which corresponds to 20mA output: 20.000

The BA564G Counter display which correspondsto 20.000mA output current is defined by thisfunction. Using the & or * push button select20 . 000 in the 4/20mA output sub-menu and press(. to reveal the existing rate or total display withone digit flashing. The required display can beentered using the & or * push button to adjustthe flashing digit and the ( button to transfercontrol to the next digit. When set as requiredpress ) to enter the value and return to the 20

000 prompt in the 4/20mA output sub-menu.

Note: If the BA564G Counter and the 4/20mAcurrent sink output are powered fromseparate supplies, the 4/20mA outputcurrent will continue to flow when theBA564G Counter supply fails or is turnedoff. Powering both from a commonsupply eliminates this effect.

38