Upload
others
View
7
Download
0
Embed Size (px)
Citation preview
Intrusion Alarm Systems | B426 Ethernet Communication Module
B426 Ethernet Communication Module
www.boschsecurity.com
u Full two-way IP event reporting with remote controlpanel programming support
u 10/100 Base-T Ethernet communication for IPv6 andIPv4 networks
u NIST-FIPS197 Certified for 128-bit to 256-bit AESEncrypted Line Security
u Plug and Play installation, including UPnP service toenable remote programming behind firewalls
u Advanced configuration by browser or RPS withcompatible Bosch control panels
The B426 Conettix Ethernet Communication Module isa four-wire powered SDI, SDI2, or Option bus devicethat provides two-way communication with compatiblecontrol panels over IPv4 or IPv6 Ethernet networks.Typical applications include:
• Reporting and path supervision to a ConettixCommunications Receiver/Gateway.
• Remote administration and control with RemoteProgramming Software (RPS) or our Remote SecurityControl application for handheld devices.
• Connection to building automation and integrationapplications.
The B426 is built for a wide variety of securecommercial and industrial applications. Flexible end-to-end path supervision, AES encryption, and anti-substitution features make B426 desirable for highsecurity and fire monitoring applications. It is capableas a stand-alone path or it can be used in conjunctionwith another communication technology. For FireMonitoring applications, the B426 meets UL864 andNFPA72 standards for Single CommunicationTechnology with approved Bosch control panels.
System overview
Use the B426 for bi-directional communication over anEthernet network.
1
4
5
6
3
2
7
8
9
11
10
12
B426 system connections overview
Callout ᅳ Description Callout ᅳ Description
1 ᅳ Compatible Boschcontrol panel
7 ᅳ Conettix D6100i CommunicationsReceiver/Gateway and/or ConettixD6600 Communications Receiver/Gateway (Conettix D6600Communications Receiver/Gatewayrequires 8, 9, and 10)
2 ᅳ Data bus connectionbetween the control paneland the module
8 ᅳ Ethernet network connection tothe Ethernet adapter (D6680/ITS-D6682/ITS-D6686) (ITS-D6682shown) Ethernet Network Adapter
3 ᅳ B426 9 ᅳ Conettix Ethernet NetworkAdapter (ITS-D6682 shown)
4 ᅳ Ethernet connectionbetween module andEthernet network
10 ᅳ Connection from ITS-D6682 tothe COM4 Port on the Conettix D6600Communications Receiver/Gateway
5 ᅳ Ethernet network,Local Area Network (LAN),Metropolitan AreaNetwork(MAN), Wide Area Network(WAN), or Internet
11 ᅳ Ethernet network connectionbetween the host computer Ethernetnetwork interface card (NIC) and theEthernet network
6 ᅳ Ethernet networkconnection to the D6100iCommunications Receiver(D6100i/D6100IPv6)
12 ᅳ Host PC running RemoteProgramming Software, Automation, orthe Conettix D6200 Programming/Administration Software
Functions
Conettix IP communicationThe B426 uses Conettix IP protocol which supports:
• Full event code reporting and administration• Flexible supervision intervals• Resistance to Denial of Service attacks• 128, 192 or 256-bit AES encryption• Anti-replay and anti-substitution
Switch addressingUse the address switch to easily assign a bus addressor setup for web configuration.
IP network supportSupports DHCP, UPnP, and Auto IP addressing bydefault, but can also be configured for Static IPnetworks. The B426 Conettix Ethernet CommunicationModule is compatible with IPv6 or IPv4 networks. Withcompatible control panels, it supports reporting toreceivers with Domain Name System (DNS) hostnamesfor automatic disaster recovery.
Easy configurationFor most installations, the default B426 settings allowinstallation with no computer required. An addressswitch allows easy bus address selection. UniversalPlug and Play (UPnP) supports automatic UDP portmapping for remote programming systems whenbehind a firewall, as well as HTTP port mapping forB426 web configuration. Auto IP enables a direct PCconnection without changing any PC network settings.For customized network settings, the B426 supports afull web configuration menu. B Series and GV4 Seriescontrol panels support keypad and RPS programmingof B426 settings.
LEDsThree LEDs provide status and troubleshootinginformation about the module and its connection.
LED Description
Heartbeat Indicates the system status of the B426 and itsconnection to the panel.
RX Indicates when an inbound packet is received on thebus.
TX Indicates when an outbound packet is transmitted onthe bus.
Certifications and approvals
The following table lists regulatory approvals byregion.
Region Certification
Australia C-Tick
Belgium Incert B-509-0065
Europe EN 50130-4, EN 60950, EN 61000-6-3
USA UL 365 - Police Station Connected Burglar Alarm Unitsand Systems
UL 609 - Local Burglar Alarm Units and Systems
UL 864 - Control Units and Accessories for Fire AlarmSystems (Commercial Fire)
UL 985 - Household Fire Warning System Units
UL 1023 - Household Burglar Alarm System Units
UL 1076 - Proprietary Burglar Alarm Units and Systems
UL 1610 - Central Station Burglar Alarm Units
CSFM - California Office of The State Fire Marshall
FCC Part 15 Class B, NIST FIPS-197 AES Certification(IP Communications)
Canada CAN/ULC S303 - Local Burglar Alarm Units and Systems
CAN/ULC S304 - Signal Receiving Centre and Premise
ICES-003 - Information Technology Equipment (ITE)
ULC-ORD C1023 - Household Burglar Alarm SystemUnits
The following table lists the certificates available fordownload from the Product Page atwww.boschsecurity.com.
Region Certification
USA CSFM see our website
FDNY-CoA
#6174 UL 864 9th Edition
Installation/configuration notes
Compatible control panelsAMAX 2000/2100/3000/4000B9512G/B9512G-EB8512G/B8512G-EB5512/B5512E
2 | B426 Ethernet Communication Module
B4512/B4512EB3512/B3512ED9412GV4/D7412GV4/D7212GV4D9412GV3/D7412GV3/D7212GV3D9412GV2/D7412GV2/7212GV2D9412G/D7412G/D7212G Version 6.3 or higherD9412/D7412/D7212D9112DS7220 Version 2.10 or higherDS7240 Version 2.10 or higherDS7400XiV4 Version 4.10 or higherEasy Series V3+FPD-7024Solution 2000/3000
Compatible applications• A-Link Plus. Supported on all compatible control
panels.• RPS/RPS Lite. Supported on all compatible control
panels.• PC9000. Supported on v6.3 or higher of D9412/
D7412/D7212, D9412G/D7412G/D7212G,D9412GV2/D7412GV2/7212GV2 , and D9412GV3/D7412GV3/D7212GV3 (version 8.05 or v8.13 orhigher only).
• IS2000. Supported on v6.3 or higher of D9412G/D7412G/D7212G, D9412GV2/D7412GV2/7212GV2 ,and D9412GV3/D7412GV3/D7212GV3 (version 8.05or v8.13 or higher only).
• Remote Security Control. Supported on GV4,B9512G/B8512G, B9512G-E/B8512G-E, B5512/B4512/B3512, B5512E/B4512E/B3512E, and Solution2000/3000.
Mounting considerationsMount the B426 into the enclosure’s 3-hole mountingpattern using the supplied mounting screws andmounting bracket.
Wiring considerationsThe B426 connects to a control panel using a data busconnection and to an Ethernet network using astandard Category 5 or above Ethernet cable with anRJ-45 plug.
Browser supportMicrosoft Internet ExplorerMozilla Firefox
Parts included
Quantity Component
1 B426 Conettix EthernetCommunication Module
1 Hardware pack
1 Interconnect cable wiring
1 Quick Start Guide (hardcopy)
1 Literature (mini-CD)
Technical specifications
Environmental considerations
Relative humidity Up to 93% non-condensing
Temperature(operating)
0° - +49°C (+32° - +120°F)
Properties
Board dimensions 59.5 mm x 108 mm x 16 mm (2.19 in x 4.25 in x0.629 in)
Power requirements
Current(maximum)
90 mA
Voltage(operating)
12 VDC nominal
Connectors
LAN/WAN RJ-45 modular port (Ethernet)
Cabling
Ethernet cable Category 5 or better unshielded twisted pair
Ethernet cablelength
100 m (328 ft) max length
Wiring
Data bus wiregauge
18 AWG or 22 AWG
Data bus wirelength
Maximum distance – Wire size:150 m (500 ft) - 0.65 mm (22 AWG)300 m (1000 ft) - 1.02 mm (18 AWG)
Ordering information
B426 Ethernet Communication ModuleSupports two-way communications over Ethernetnetworks for compatible control panels.Order number B426
3 | B426 Ethernet Communication Module
4 | B426 Ethernet Communication Module
Represented by:
Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:Bosch Security Systems, Inc.130 Perinton ParkwayFairport, New York, 14450, USAPhone: +1 800 289 0096Fax: +1 585 223 [email protected]
Bosch Security Systems B.V.P.O. Box 800025617 BA Eindhoven, The NetherlandsPhone: + 31 40 2577 284Fax: +31 40 2577 [email protected]
Robert Bosch (SEA) Pte Ltd, SecuritySystems11 Bishan Street 21Singapore 573943Phone: +65 6571 2808Fax: +65 6571 [email protected]
Bosch (Shanghai) Security Systems Ltd.203 Building, No. 333 Fuquan RoadNorth IBPChangning District, Shanghai200335 ChinaPhone +86 21 22181111Fax: +86 21 22182398www.boschsecurity.com.cn
Robert Bosch Ltda Security Systems DivisionVia Anhanguera, Km 98CEP 13065-900Campinas, Sao Paulo, BrazilPhone: +55 19 2103 2860Fax: +55 19 2103 [email protected]
© Bosch Security Systems 2015 | Data subject to change without notice7665963531 | en, V25, 25. Jun 2015