B30 Presentation Examples Universal Relay Universal Relay Family Family

B30 Presentation Examples Universal Relay Family

Embed Size (px)

Citation preview

Page 1: B30 Presentation Examples Universal Relay Family

B30 Presentation

Examples

Universal Relay FamilyUniversal Relay Family

Page 2: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: RTDS Testing EnvironmentRTDS Testing Environment

Real Time Digital SimulatorPSCAD graphical user interface

Real Time DigitalReal Time DigitalSimulatorSimulator

(RTDS)(RTDS)

Real Time DigitalReal Time DigitalSimulatorSimulator

(RTDS)(RTDS)

•Final product validation•Customer requested tests

Used for:

Page 3: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: RTDS Testing EnvironmentRTDS Testing Environment

Page 4: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: RTDS Applications and UsersRTDS Applications and Users

RTDS ApplicationsRTDS ApplicationsGEC Alsthom T&D (UK)

Asea Brown Boveri (Sweden) Siemens (Germany)

Hitachi Corp. (Japan)Toshiba Corp. (Japan)

Furnas Centrais Electricas (Brazil)Ontario Hydro Technologies Inc (Canada)

Chugoku Electric (Japan) Korea Electric Power Co. (S. Korea)

Nanjing Automation Research Institute (China) Electric Power Research Institute (China)

Manitoba Hydro (Canada)University of Manitoba (Canada)

LG Systems (S. Korea)Nanyang Technical University (Singapore)

Chanwang University (S. Korea) Kinkei Systems (Japan)

Toshiba Engineering (Japan)University of Canterbury (New Zealand)

RTDS UsersRTDS Users• Conventional TNA type studies • AC System breaker sequences • Power swings due to disturbance • DC Transmission systems with various short circuit ratios • DC System controls studies • Relay test studies • AC & DC System interactions • SVS Applications and controls studies

Page 5: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Contents...Contents...

Case 1: External SLG Fault

Case 2: External SLG Fault

Case 3: External LLG Fault

Case 4: External 3P Fault

Case 5: External 3P Fault

Case 6: External SLG Fault

Case 7: External LLG Fault

Case 8: Internal SLG Fault

Case 9: Internal SLG Fault next page

Page 6: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Contents...Contents...

Case 10: Internal LLG Fault

Case 11: Internal 3P Fault

Case 12: Internal SLG Fault (weak infeed)

Case 13: Internal SLG Fault (weak infeed)

Case 14: Closing onto Internal SLG Fault

Case 15: Closing onto Internal SLG Fault

Case 16: Closing onto Internal 3P Fault

Case 17: Closing onto External SLG Fault

Case 18: Closing onto External... next page

Page 7: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Contents...Contents...

Case 19: External SLG Fault (autorecl.)

Case 20: External 3P Fault (autorecl.)

Page 8: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 1 (External Fault)Case 1 (External Fault)

• External AG fault on circuit #4

• Point on Wave = 0 deg

• All six circuits connected

• Circuit #4 CT saturates after about 2 ms

• The B30 remains stable

COMTRADE File: B30_case_01

Page 9: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 1 (External Fault)Case 1 (External Fault)

AG, pow=0o

Page 10: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 1 (External Fault)Case 1 (External Fault)

Page 11: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 2 (External Fault)Case 2 (External Fault)

• External AG fault on circuit #4

• Point on Wave = 90 deg

• All six circuits connected

• Circuit #4 CT saturates after about 1.6 ms

• The B30 remains stable

COMTRADE File: B30_case_02

Page 12: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 2 (External Fault)Case 2 (External Fault)

AG, pow=90o

Page 13: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 2 (External Fault)Case 2 (External Fault)

Page 14: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 3 (External Fault)Case 3 (External Fault)

• External ABG fault on circuit #4

• Point on Wave = 0 deg

• All six circuits connected

• Circuit #4 CT saturates after about 2.6 ms

• The B30 remains stable

COMTRADE File: B30_case_03

Page 15: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 3 (External Fault)Case 3 (External Fault)

ABG, pow=0o

Page 16: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 3 (External Fault)Case 3 (External Fault)

Page 17: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 4 (External Fault)Case 4 (External Fault)

• External ABCG fault on circuit #4

• Point on Wave = 0 deg

• All six circuits connected

• Circuit #4 CT saturates after about 2.6 ms

• The B30 remains stable

COMTRADE File: B30_case_04

Page 18: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 4 (External Fault)Case 4 (External Fault)

ABCG, pow=0o

Page 19: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 4 (External Fault)Case 4 (External Fault)

Page 20: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 5 (External Fault)Case 5 (External Fault)

• External ABCG fault on circuit #4

• Point on Wave = 90 deg

• All six circuits connected

• Circuit #4 CT saturates after about 2.3 ms

• The B30 remains stable

COMTRADE File: B30_case_05

Page 21: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 5 (External Fault)Case 5 (External Fault)

ABCG, pow=90o

Page 22: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 5 (External Fault)Case 5 (External Fault)

Page 23: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 6 (External Fault)Case 6 (External Fault)

• External AG fault on circuit #1

• Point on Wave = 0 deg

• All six circuits connected

• Circuit #1 CT saturates after about 6 ms

• The B30 remains stable

COMTRADE File: B30_case_06

Page 24: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 6 (External Fault)Case 6 (External Fault)

AG, pow=0o

Page 25: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 6 (External Fault)Case 6 (External Fault)

Page 26: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 7 (External Fault)Case 7 (External Fault)

• External ABG fault on circuit #1

• Point on Wave = 0 deg

• All six circuits connected

• Circuit #1 CT saturates after about 5.5 ms

• The B30 remains stable

COMTRADE File: B30_case_07

Page 27: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 7 (External Fault)Case 7 (External Fault)

ABG, pow=0o

Page 28: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 7 (External Fault)Case 7 (External Fault)

Page 29: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 8 (Internal Fault)Case 8 (Internal Fault)

• Internal AG fault

• Point on Wave = 0 deg

• All six circuits connected

• The B30 operates in 10.0 msec (fast form-C)

COMTRADE File: B30_case_08

Page 30: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 8 (Internal Fault)Case 8 (Internal Fault)

AG, pow=0o

Page 31: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 8 (Internal Fault)Case 8 (Internal Fault)

Phase A operates in 10.0 msec

Phase A operates in 10.0 msec

Page 32: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 9 (Internal Fault)Case 9 (Internal Fault)

• Internal AG fault

• Point on Wave = 90 deg

• All six circuits connected

• The B30 operates in 10.7 msec (fast form-C)

COMTRADE File: B30_case_09

Page 33: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 9 (Internal Fault)Case 9 (Internal Fault)

AG, pow=90o

Page 34: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 9 (Internal Fault)Case 9 (Internal Fault)

Phase A operates in 10.7 msec

Phase A operates in 10.7 msec

Page 35: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 10 (Internal Fault)Case 10 (Internal Fault)

• Internal ABG fault

• Point on Wave = 0 deg

• All six circuits connected

• The B30 operates in 9.3 msec (fast form-C)

COMTRADE File: B30_case_10a,b

Page 36: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 10 (Internal Fault)Case 10 (Internal Fault)

ABG, pow=0o

Page 37: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 10 (Internal Fault)Case 10 (Internal Fault)

Phase A operates in 9.3 msec

Phase A operates in 9.3 msec

Page 38: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 10 (Internal Fault)Case 10 (Internal Fault)

Phase B operates in 10.5 msec

Phase B operates in 10.5 msec

Page 39: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 11 (Internal Fault)Case 11 (Internal Fault)

• Internal ABCG fault

• Point on Wave = 0 deg

• All six circuits connected

• The B30 operates in 8.8 msec (fast form-C)

COMTRADE File: B30_case_11a,b,c

Page 40: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 11 (Internal Fault)Case 11 (Internal Fault)

ABCG, pow=0o

Page 41: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 11 (Internal Fault)Case 11 (Internal Fault)

Phase A operates in 11.4 msec

Phase A operates in 11.4 msec

Page 42: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 11 (Internal Fault)Case 11 (Internal Fault)

Phase B operates in 8.8 msec

Phase B operates in 8.8 msec

Page 43: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 11 (Internal Fault)Case 11 (Internal Fault)

Phase C operates in 13.8 msec

Phase C operates in 13.8 msec

Page 44: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 12 (Internal Fault - Weak Infeed)Case 12 (Internal Fault - Weak Infeed)

• Internal AG fault

• Point on Wave = 0 deg

• Circuits 3 (wye winding of the transformer: zero-sequence infeed), 4 (weak infeed) and 5 (load) connected

• The B30 operates in 17.7 msec (fast form-C)

COMTRADE File: B30_case_12

Page 45: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 12 (Internal Fault - Weak Infeed)Case 12 (Internal Fault - Weak Infeed)

AG, pow=0o

Page 46: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 12 (Internal Fault - Weak Infeed)Case 12 (Internal Fault - Weak Infeed)

Phase A operates in 17.7 msec

Phase A operates in 17.7 msec

Page 47: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 13 (Internal Fault - Weak Infeed)Case 13 (Internal Fault - Weak Infeed)

• Internal AG fault

• Point on Wave = 90 deg

• Circuits 3 (wye winding of the transformer: zero-sequence infeed), 4 (weak infeed) and 5 (load) connected

• The B30 operates in 13.5 msec (fast form-C)

COMTRADE File: B30_case_13

Page 48: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 13 (Internal Fault - Weak Infeed)Case 13 (Internal Fault - Weak Infeed)

AG, pow=90o

Page 49: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 13 (Internal Fault - Weak Infeed)Case 13 (Internal Fault - Weak Infeed)

Phase A operates in 13.5 msec

Phase A operates in 13.5 msec

Page 50: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 14 (Closing onto Internal Fault)Case 14 (Closing onto Internal Fault)

• Internal AG fault pre-exists on the bus

• The bus is energized from the circuit #1

• Closing onto the fault at the Point on Wave = 0 deg

• The B30 operates in 7.6 msec (fast form-C)

COMTRADE File: B30_case_14

Page 51: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 14 (Closing onto Internal Fault)Case 14 (Closing onto Internal Fault)

AG, pow=0o

Page 52: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 14 (Closing onto Internal Fault)Case 14 (Closing onto Internal Fault)

Phase A operates in 7.6 msec

Phase A operates in 7.6 msec

Page 53: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 15 (Closing onto Internal Fault)Case 15 (Closing onto Internal Fault)

• Internal AG fault pre-exists on the bus

• The bus is energized from the circuit #1

• Closing onto the fault at the Point on Wave = 90 deg

• The B30 operates in 7.9 msec (fast form-C)

COMTRADE File: B30_case_15

Page 54: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 15 (Closing onto Internal Fault)Case 15 (Closing onto Internal Fault)

AG, pow=90o

Page 55: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 15 (Closing onto Internal Fault)Case 15 (Closing onto Internal Fault)

Phase A operates in 7.9 msec

Phase A operates in 7.9 msec

Page 56: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 16 (Closing onto Internal Fault)Case 16 (Closing onto Internal Fault)

• Internal ABCG fault pre-exists on the bus

• The bus is energized from the circuit #1

• Closing onto the fault at the Point on Wave = 0 deg

• The B30 operates in 6.4 msec (fast form-C)

COMTRADE File: B30_case_16a,b,c

Page 57: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 16 (Closing onto Internal Fault)Case 16 (Closing onto Internal Fault)

ABCG, pow=0o

Page 58: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 16 (Closing onto Internal Fault)Case 16 (Closing onto Internal Fault)

Phase A operates in 8.8 msec

Phase A operates in 8.8 msec

Page 59: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 16 (Closing onto Internal Fault)Case 16 (Closing onto Internal Fault)

Phase B operates in 6.4 msec

Phase B operates in 6.4 msec

Page 60: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 16 (Closing onto Internal Fault)Case 16 (Closing onto Internal Fault)

Phase C operates in 8.8 msec

Phase C operates in 8.8 msec

Page 61: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 17 (Closing onto External Fault)Case 17 (Closing onto External Fault)

• Internal ABCG fault pre-exists on the circuit #4

• The circuit #4 is connected to the de-energized bus

• The bus is energized from the circuit #1

• Closing onto the fault at the Point on Wave = 0 deg

• The B30 remains stable

COMTRADE File: B30_case_17

Page 62: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 17 (Closing onto External Fault)Case 17 (Closing onto External Fault)

ABCG, pow=0o

Page 63: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 17 (Closing onto External Fault)Case 17 (Closing onto External Fault)

Page 64: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 18 (Closing onto External Fault)Case 18 (Closing onto External Fault)

• Internal AG fault pre-exists on the circuit #4

• The circuit #4 is connected to the de-energized bus

• The bus is energized from the circuit #1

• Closing onto the fault at the Point on Wave = 0 deg

• The B30 remains stable

COMTRADE File: B30_case_18

Page 65: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 18 (Closing onto External Fault)Case 18 (Closing onto External Fault)

AG, pow=0o

Page 66: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 18 (Closing onto External Fault)Case 18 (Closing onto External Fault)

Page 67: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 19 (External Fault – Autoreclosure)Case 19 (External Fault – Autoreclosure)

• External AG fault on the circuit #4

• The fault is cleared in 100 msec

• Two AR shots are executed with the dead-time of 0.5 sec

• The AR fails - the breaker opens after 70 msec during each shot

• The B30 remains stable

COMTRADE File: B30_case_19

Page 68: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 19 (External Fault – Autoreclosure)Case 19 (External Fault – Autoreclosure)

AG, pow=0o

Page 69: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 19 (External Fault – Autoreclosure)Case 19 (External Fault – Autoreclosure)

Fault InceptionFault Inception 2nd AR shot2nd AR shot

Page 70: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 19 (External Fault – Autoreclosure)Case 19 (External Fault – Autoreclosure)

Page 71: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 20 (External Fault – Autoreclosure)Case 20 (External Fault – Autoreclosure)

• External ABCG fault on the circuit #4

• The fault is cleared in 100 msec

• Two AR shots are executed with a dead-time of 0.5 sec

• The AR fails - the breaker opens after 70 msec during each shot

• The B30 remains stable

COMTRADE File: B30_case_20

Page 72: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 20 (External Fault – Autoreclosure)Case 20 (External Fault – Autoreclosure)

ABCG, pow=0o

Page 73: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 20 (External Fault – Autoreclosure)Case 20 (External Fault – Autoreclosure)

Fault InceptionFault Inception 2nd AR shot2nd AR shot

Page 74: B30 Presentation Examples Universal Relay Family

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 20 (External Fault – Autoreclosure)Case 20 (External Fault – Autoreclosure)