Upload
lykhuong
View
215
Download
0
Embed Size (px)
Citation preview
www.dynamicratings.com
B100 Series Technical Specification
Rev 4
B100 SERIES TECHNICAL SPECIFICATION Rev. 4
Page 2 of 15
© 2017 Dynamic Ratings Specifications and information is subject to change without notice.
Revision History
REVISION DATE
(yymmdd) PUBLISHED BY DESCRIPTION
1 160129 S. Allan, T. Foren Original Release
2 160323 A. Zuehlke, T. Foren,
S. Allan Technical Updates
3 160418 S. Allan Technical Updates
4 170228 M. Morey Updated for Production Release
Contacts
Asia / Africa / Oceania +61 3 9574 7722 [email protected]
Americas / Europe +1 262 746-1230 [email protected]
B100 SERIES TECHNICAL SPECIFICATION Rev. 4
Page 3 of 15
© 2017 Dynamic Ratings Specifications and information is subject to change without notice.
CONTENTS
REVISION HISTORY ..................................................................................................... 2
CONTACTS ................................................................................................................... 2
PURPOSE AND SCOPE ................................................................................................ 4
DEFINITIONS ................................................................................................................ 4
NOTICES, CAUTIONS OR WARNINGS ........................................................................ 5
INTRODUCTION ............................................................................................................ 6
HARDWARE FEATURES AND SPECIFICATIONS ....................................................... 6
ENCLOSURE FEATURES ............................................................................................. 7
MECHANICAL DIMENSIONS ........................................................................................ 7
HARDWARE IO OVERVIEW ......................................................................................... 8
BASE MODEL ............................................................................................................ 8
REAL TIME CLOCK (RTC) BATTERY ....................................................................... 8
ETHERNET COMMUNICATIONS OPTIONS ............................................................ 8
SERIAL COMMUNICATIONS OPTIONS ................................................................... 9
IBRIDGE COMMUNICATIONS OPTION ................................................................... 9
POWER SUPPLY ...................................................................................................... 9
I/O TYPE ELECTRICAL DATA .................................................................................... 10
DIGITAL INPUT ....................................................................................................... 10
DIGITAL OUTPUT ................................................................................................... 10
ANALOG OUTPUT – AO ......................................................................................... 11
RESISTANCE TEMPERATURE DETECTOR INPUT – RTD .................................. 11
CURRENT TRANSFORMER INPUT - CT ............................................................... 12
CLIMATIC CONDITIONS ............................................................................................. 13
MECHANICAL CONDITIONS FOR STORAGE AND USE .......................................... 13
MOUNTING .................................................................................................................. 13
HARDWARE STANDARDS COMPLIANCE ................................................................. 14
IEC 61010-1 PART 1: GENERAL REQUIREMENTS............................................... 14
IEC 60870 TELECONTROL EQUIPMENT AND SYSTEMS .................................... 14
IEC 61850 ................................................................................................................ 14
IEC 1613-2003 ......................................................................................................... 14
IEEE C37.90 ............................................................................................................ 14
IEEE C57.12.10-1997 .............................................................................................. 14
FCC PART 15 .......................................................................................................... 14
SALES CONTACTS ..................................................................................................... 15
B100 SERIES TECHNICAL SPECIFICATION Rev. 4
Page 4 of 15
© 2017 Dynamic Ratings Specifications and information is subject to change without notice.
FIGURES
FIGURE 1: B100 ............................................................................................................ 6
FIGURE 2: B100 MECHANICAL DIMENSIONS ............................................................ 7
FIGURE 3: VIBRATION MOUNT ASSEMBLY ............................................................. 13
Purpose and Scope
The purpose of this document is to provide a summary of the technical characteristics of the B100 Series Electronic Temperature Monitor (ETM). This information will assist users in understanding B100 I/O and communications, and implementing a B100 series monitor.
Definitions
CT: Current Transformer
DIP: Dual In-Line Package
Form B: Normally closed (NC), single-pole, single-throw (SPST) contacts
Form C: Change over (break-before-make), single-pole, double-throw (SPDT) contacts
I/O: Input / Output
OLTC: On-Load Tap Changer
LCD: Liquid Crystal Display
RNDIS: Remote Network Driver Interface Specification
RS-232: Serial communications link complying with EIA-232
RS-422: Serial communications link complying with EIA-422
RS-485: Serial communications link complying with EIA-485
RTC: Real Time Clock
RTD: Resistance Temperature Detector
WTI: Winding Temperature Indicator/Indication
B100 SERIES TECHNICAL SPECIFICATION Rev. 4
Page 5 of 15
© 2017 Dynamic Ratings Specifications and information is subject to change without notice.
Notices, Cautions or Warnings
This document may contain; Notices, Cautions or Warnings using ANSI Z535.5 definitions below.
Alert Symbol ANSI Z535.5 definition
NOTICE: Indicates recommended practices not related to personal injury.
CAUTION: Caution without symbol is used to alert against unsafe practices that can result in property damage only.
CAUTION with symbol: Caution with a symbol indicates a hazardous situation, which, if not avoided could result in minor or moderate injury.
WARNING with symbol: Indicates a potentially hazardous situation, which, if not avoided, can result in injury or serious damage to property.
A notice, caution or warning symbol and its associated message in this document will inform readers of Notices, Cautions or Warnings.
B100 SERIES TECHNICAL SPECIFICATION Rev. 4
Page 6 of 15
© 2017 Dynamic Ratings Specifications and information is subject to change without notice.
Introduction Dynamic Ratings is a leading supplier of monitoring and control products to the electrical power industry. The B100 extends the company’s product range and provides a reliable and cost-effective electronic temperature monitor (ETM) and controller with numerous communications options.
Figure 1: B100
Hardware Features and Specifications
The B100 is a single unit housed in an aluminium enclosure, with a day and night readable LCD screen and four external user interface buttons.
The design life of the B100 is 20 years. It is expected to last much longer.
The electrical connections are made using screw terminal blocks, and the unit has multiple cable entry ports at the base of the enclosure. The internal operating system contains many functions to make sure the control system is in a healthy operating condition.
The permitted operating temperature range is -40°C to +70°C (-40°F to 158°F).
B100 SERIES TECHNICAL SPECIFICATION Rev. 4
Page 7 of 15
© 2017 Dynamic Ratings Specifications and information is subject to change without notice.
Enclosure Features
The B100 is supplied in a robust cast aluminium enclosure that is rated to IP66 ingress protection (NEMA 4 equivalent). Mounting is via four mounting holes (with supplied vibration mounts) on the sides of the housing. Cable entry is via multiple M20 (3/4 inch) and M25 (1 inch) ports in the bottom of the unit – spare ports are to be sealed to maintain the ingress protection. Additional enclosure features include a Gore® air vent for pressure and temperature compensation, and a padlock loop for locking of the enclosure.
Mechanical Dimensions
Figure 2: B100 Mechanical Dimensions
B100 SERIES TECHNICAL SPECIFICATION Rev. 4
Page 8 of 15
© 2017 Dynamic Ratings Specifications and information is subject to change without notice.
Hardware IO Overview Base Model The base model provides the following I/O ports:
1 x USB 2.0 Type B device with USB Ethernet (RNDIS) for configuration and data download
1 GB of on-board memory for configuration and data logging
1 x Form B relay for System Alarm output
6 x Form C relays for alarm outputs
1 x RTD input for main tank temperature input
1 x RTD input for LTC temperature or ambient temperature
3 x CT inputs for load current input and WTI calculation
1 x Digital input for dual winding gradient function
2 x Analog outputs for remote indication
Real Time Clock (RTC) Battery The system contains a user-replaceable “½ AA” 3.6V Lithium Thionyl Chloride real time clock (RTC) battery with an estimated life of ten years. A Tadiran TL-2150 is approved for use.
Ethernet Communications Options The B100 can be supplied with one of the following Ethernet communications options. The ordering option by model number letter is referenced in the parenthesis below:
No Ethernet communications (default selection)
100Base-FX Fiber Ethernet port with SC connectors (compatible with 50/125, 62.5/125, and 100/140 micron glass core multimode fiber)
100Base-FX Fiber Ethernet port with ST connectors (compatible with 50/125, 62.5/125, and 100/140 micron glass core multimode fiber)
100Base-T RS45 Copper Ethernet port
Integrated iBridge communications system (see below).
B100 SERIES TECHNICAL SPECIFICATION Rev. 4
Page 9 of 15
© 2017 Dynamic Ratings Specifications and information is subject to change without notice.
Serial Communications Options
The B100 can be supplied with one of the following serial communications options. The ordering option by model number letter is referenced in the parenthesis below:
No serial communications (default selection)
RS-485/RS-422 copper serial port
Serial over fiber port with ST connectors (compatible with 50/125, 62.5/125, and 100/140 micron glass core multimode fiber)
iBridge Communications Option
The iBridge is an affordable communications system utilizing existing conductors that enables rapid installation and data communications to IED communications.
When the B100 is ordered with the iBridge option, the Ethernet and serial ports are replaced with an internal connection to an iBridge module. For more information about the iBridge technical specification, please refer to the Dynamic Ratings iBridge Technical Specifications Manual.
Power Supply
The B100 features a universal wide-input power supply. The power supplies electrical characteristics and input ranges are in the table below.
Standard With iBridge*
AC Frequency 50 – 60 Hz 50 – 60 Hz
AC Input Range 110 – 240 VAC 100 – 240 VAC
DC Input Range 48 – 240 VDC 48 – 240 VDC
Rated Power 28 W 35 W
Table 1: B100 Power Input Ranges
*B100 with iBridge option draws an additional 7W.
B100 SERIES TECHNICAL SPECIFICATION Rev. 4
Page 10 of 15
© 2017 Dynamic Ratings Specifications and information is subject to change without notice.
I/O Type Electrical Data
The following I/O types are used in the B100, described here in detail.
Digital Input
The electrical characteristics of digital inputs are:
Absolute maximum voltage input range: ±390 V (276 VAC)
DC voltage range 15 – 390 VDC
AC voltage range 30 – 276 VAC
AC voltage frequency range: 47 to 63 Hz
Each digital input provides the following internal protection:
A self-resetting protection against over current conditions
Protection against over voltage transients and surges
Over voltage protection
Current limiting protection
Digital Output
Digital outputs are hardware relays that are configured in one of two ways:
1 x Form B (Fixed mapping for system alarm)
6 x Form C (User configurable outputs)
Digital outputs do not share any common pins and are electrically isolated. The digital outputs are electrically rated to the following:
Maximum AC carrying capacity: 10 A @ 250 VAC
Maximum DC carrying capacity: 10 A @ 30 VDC, 1 A @ 125 VDC resistive
Maximum making capacity: 30 A
Maximum AC breaking capacity: 3 A @ 120 VAC, 1.5 A @ 240 VAC
Maximum DC breaking capacity: 0.75 A @ 24 VDC, 0.4 A @ 125 VDC, 0.2 A @ 250 VDC
Each digital output provides internal protection against voltage spikes caused by inductive loads.
B100 SERIES TECHNICAL SPECIFICATION Rev. 4
Page 11 of 15
© 2017 Dynamic Ratings Specifications and information is subject to change without notice.
Analog Output – AO
Analog outputs do not share any pins and are electrically isolated. Analog outputs may be of either a current sink or voltage output type. Two DIP switches located on the board directly above the outputs are used to switch between volts and milliamps (mA). When the switch is in the up position, volts will be used. When the switch is in the down position, mA will be used. The electrical characteristics of each are:
Analog Current Output
Current range: 0 mA to 24 mA
Current resolution: 24 uA (0.1% of range)
Current accuracy: ±240 uA (±1% of range)
Maximum loop resistance 450 Ω
Analog Voltage Output
Voltage range: 0 V to 10 V
Voltage resolution: 10 mV (0.1% of range)
Voltage accuracy: ±100 mV (±1% of range)
Maximum output current: 5 mA
Each analog output provides protection against over voltage conditions.
Resistance Temperature Detector Input – RTD
An RTD input provides a three conductor connection that is intended to be used with a 3-wire, Pt100 (Platinum 100Ω) RTD. Each RTD input possesses an RTD+, RTD-, and common connection. The electrical characteristics are:
Temperature range: -50°C to +200°C
Temperature accuracy when using IEC 60751 Class A sensors: o ± 0.5°C between 0°C to 100°C o ± 1.0°C between -50°C to 0°C and 100°C to 200°C
Temperature resolution: 0.0625°C
Nominal measuring current: 1mA
Maximum cable resistance per wire 2Ω
Minimum sampling rate: 10 sample per second
Each RTD input provides protection against over voltage conditions.
B100 SERIES TECHNICAL SPECIFICATION Rev. 4
Page 12 of 15
© 2017 Dynamic Ratings Specifications and information is subject to change without notice.
Current Transformer Input - CT
Current transformer inputs do not share any pins and are electrically isolated. The electrical characteristics of each are (note - all stated currents are RMS):
Current range: 0mA to 10mA AC
Absolute maximum input current: 15mA
Fundamental frequency range: 47 to 63Hz
Current resolution: 15uA (0.1% of range)
Current accuracy: ± 75uA (±0.5% of range)
Bandwidth: 567Hz (9th harmonic of 63Hz)
Input impedance: 50Ω ± 5%
Sampling rate: 2000 samples per second
Each current transformer input provides protection against over voltage conditions.
B100 SERIES TECHNICAL SPECIFICATION Rev. 4
Page 13 of 15
© 2017 Dynamic Ratings Specifications and information is subject to change without notice.
Climatic Conditions
All components are rated for operation at +85°C (+184°F).
System Operating Temperature Range: -40°C to +70°C (-40°F to +158°F)
Mechanical Conditions for Storage and Use
Bm
Stationary vibration, sinusoidal - Displacement amplitude (mm) - Acceleration amplitude (m/s2) - Frequency range (Hz)
3mm @ 2-9Hz 10m/s2 @ 9-200Hz 15m/s2 @ 200-500Hz
Shock - Half-sine duration (ms) - Peak acceleration (m/s2)
11ms @ 100m/s2
Table 2: Mechanical Conditions for Storage and Use
Mounting
The B100 is suitable for external mounting on the transformer, but can be installed inside an equipment cubicle if required. If externally mounted, it is recommended that it is mounted in a height and location that is easily visible and accessible.
Mounting is achieved via four mounting holes (with supplied vibration mounts) on the sides of the housing. The metal ferrules have a hole diameter of 6.4mm (0.25 in.), suited to metric M6 or imperial 1/4-28 fasteners – 316 grade stainless steel is recommended.
Figure 3: Vibration Mount Assembly
B100 SERIES TECHNICAL SPECIFICATION Rev. 4
Page 14 of 15
© 2017 Dynamic Ratings Specifications and information is subject to change without notice.
Hardware Standards Compliance IEC 61010-1 Part 1: General Requirements
Product Safety Standards for Measurement, Control, and Laboratory Products
The following versions of 61010-1 are applicable:
International: IEC 61010-1
Europe: EN 61010-1
IEC 60870 Telecontrol Equipment and Systems
IEC 60870-1 General considerations
IEC 60870-2 Operating conditions
IEC 61850
The following sections from IEC 61850:
IEC 61850-3
IEC 61850-5
IEC 61850-6
IEC 61850-7
IEC 61850-8
The B100 product is designed to comply with the relevant sections of the following:
IEC 1613-2003
IEEE Standard Environmental and Testing Requirements for Communications Networking Devices in Electric Power Substations
IEEE C37.90
Standard for Relays and Relay Systems Associated with Electric Power Apparatus
IEEE C57.12.10-1997
American National Standard for Transformers--230 kV and Below 833/958 through 8333/10 417 kVA, Single-Phase, and 750/862 through 60 000/80 000/100 000 kVA, Three-Phase without Load Tap Changing; and 3750/4687 through 60 000/80 000/100 000 kVA with Load Tap Changing--Safety Requirements.
FCC Part 15
EMC Standards for Measurement, Control, and Laboratory Products
B100 SERIES TECHNICAL SPECIFICATION Rev. 4
Page 15 of 15
© 2017 Dynamic Ratings Specifications and information is subject to change without notice.
Sales Contacts
To learn more about Dynamic Ratings, a global supplier of sensing, monitoring, controls and communication solutions which improve system reliability, provide maintenance savings and reveal additional capacity of power transformers, circuit breakers, generators, motors, switchgear and cables please contact our sales departments below.
Asia / Africa / Oceania +61 3 9574-7722 [email protected]
Americas +1 262 746-1230 [email protected]
Europe +44 1617 681111 [email protected]
www.dynamicratings.com