Upload
nelly-isabel-narvaez-pacheco
View
234
Download
0
Embed Size (px)
Citation preview
8/14/2019 B1. Fan Laws and Fan Control - Robinson
1/74
Robinson Industries Fansfor You
8/14/2019 B1. Fan Laws and Fan Control - Robinson
2/74
The Beginning - 1892
8/14/2019 B1. Fan Laws and Fan Control - Robinson
3/74
Robinson IndustriesToday
Heavy Duty Fan Manufacturer
Global Support Capability w/ Intl. Representation
113 Years in Fan Industry(1892 - Present)
Four Locations:
4 Fabrication Facilities
1 Service Center
Corporate HQ
Zelienople, PA, USA
Abilene, TX
8/14/2019 B1. Fan Laws and Fan Control - Robinson
4/74
Robinson ProductRange
Custom Built Special Purpose Centrifugal Fans
Industries Served: Power, Cement , Paper, Chemical,
Ceramic, Steel, Aluminum, Mining, Fertilizer
Combustion Air Blowers
Baghouse I.D. Fans
Material Handling Exhausters
Repair/Rebuild/Retrofit
8/14/2019 B1. Fan Laws and Fan Control - Robinson
5/74
Gas Density Calculation
Density = f (Temperature, Pressure, MolecularWeight)
One Calculation Method Is:D = 0.075 x (460+70)/(460+T) x {(407-k*FASL+PI) / 407} x
MW/28.96
D = Density, lb./cu.ft. (note: standard air = .075 lbs/ft3)T = Temp at fan inlet, F (note: standard temp = 70 F)
MW = Molecular Weight (note: dry air = 28.96)k = Altitude correction (note: =.013)PI= Fan inlet pressure, in-H2O gage( could be + or -)
(Ref. Page 1 of Robinsons Fan Performance and Design Manual)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
6/74
8/14/2019 B1. Fan Laws and Fan Control - Robinson
7/74
8/14/2019 B1. Fan Laws and Fan Control - Robinson
8/74
43 oF wb2
60 oF db
0.002 lb H2O/lb da3
1
Example: Tdry = 60 degF; Twet= 43 deg F; what is the
absolute humidity ratio? What is the density?
1. Enter the chart at the bottom at 60 oF dry bulb.
2. Find 43 oF wet bulb along the saturation line and read down
and to the right along 43
o
F until it intersects 60
o
F db.3. Plot this point, then read horizontally to the right to the
read absolute humidity ratio W which is in pounds of
water per pound of dry air (= .002 lb H2O /lb dry air)
4. Read specific volume = 13.14 ft3per lb of dry gas
5. Determine density = (1 + .002)/(13.14) = .076 lbs/ft3
8/14/2019 B1. Fan Laws and Fan Control - Robinson
9/74
Fan System Assessment Tool(FSAT)
This tool developed by the US
Department of Defense and the Air Movingand Control Association, International
helps evaluate fan and system efficiency.
It also includes a segment that is helpful indetermining gas density.
8/14/2019 B1. Fan Laws and Fan Control - Robinson
10/74
System Resistance
Volume (CFM x 1000)
500450400350300250200150100500
StaticPressure(InH20)
60
50
40
30
20
40
0BHP
ROBINSON INDUSTRIES
FAN : 83" x 14.38" FRD
FOR : Basic Fan Laws I
FAN SPEED : 1180
TEMP. : 70
DENSITY : 0.075
SYSTEM RESISTANCE
150,000 CFM
40 SP
Every system has
resistance to flow.
Most gas systems
can be approximated
by an equivalent
orifice. The flow is
turbulent and the
pressure (P) requiredvaries as a function
of the square of the
volume flow-rate (Q).
P = kQ2 (k is a
system resistance
constant.)
(Ref. Page 16)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
11/74
Fan and System Curves
Volume (CFM) x 1000
300250200150100500
Pressure(InH20)
50
40
30
20
10
0
ROBINSON INDUSTRIES, INC.
FAN : 83" x 14.38" FRDFOR : Basic Fan Laws I
FAN SPEED : 1180
TEMP. : 70DENSITY : 0.075
SP
SYSTEM RESISTANCE
150,000 CFM
40 SP
The actual
operating
point will
be the
intersection
of the
system
resistance
curve and
the fancurve.
(Ref. page 17)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
12/74
Fan BHP Curve
Volume (CFM) x 1000
30025020015010050
0
BHP
2000
1600
1200
800
400
0
1,257 BHP
150000 CFM
ROBINSON INDUSTRIES, INC.
FAN : 83" x 14.38" FRD
FOR : Basic Fan Laws I
FAN SPEED : 1180
TEMP. : 70
DENSITY : 0.075
BHP
This shows thepower required
to drive the fan.For mostcentrifugal fansthe BHPincreases as
CFM increases.A Non-overloading fan
has a BHP curvethat peaks and
then drops off athigher flow.
(Ref. page 17)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
13/74
Fan CurvesConsiderations for a Good Operating Point
Volume (CFM) x 1000300250200150100500
Pressure(InH20)
50
40
30
20
10
BHP
2000
1600
1200
800
400
40 SP
1257 BHP
150000 CFM
ROBINSON INDUSTRIES, INC.
FAN : 83" x 14.38" FRD
FOR : Basic Fan Laws I
FAN SPEED : 1180
TEMP. : 70
DENSITY : 0.075
Efficiency%
100
80
40
20
0
SP
BHP
Eff.
Efficiency
Stability
Sound
Size
8/14/2019 B1. Fan Laws and Fan Control - Robinson
14/74
Lab Test Arrangement
8/14/2019 B1. Fan Laws and Fan Control - Robinson
15/74
Laboratory AirPerformance Test
Test Fan
8/14/2019 B1. Fan Laws and Fan Control - Robinson
16/74
Laboratory AirPerformance Test
Test Fan
Orifice Plate (Throttling Device)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
17/74
Pitot Traverse in Outlet Duct
8/14/2019 B1. Fan Laws and Fan Control - Robinson
18/74
Fan Laws
Static Pressure, Velocity Pressure
(Dynamic Pressure), Total Pressure
Density Change
Speed Change
Size Change
8/14/2019 B1. Fan Laws and Fan Control - Robinson
19/74
Static, Velocity, and TotalPressure
Pt = Ps + Pv Consider two planes
1. fan inlet
2. fan discharge (after evase)
Fan Total Pressure: Ptdischarge- Ptinlet
Fan Static Pressure:
Psfan= Psdischarge- Ptinlet or,
Psfan = Psdischarge- (Psinlet + Pvinlet) Fan Static Pressure Rise (or, Differential Static
Pressure):
PStatic Rise= PsdischargePsinlet
8/14/2019 B1. Fan Laws and Fan Control - Robinson
20/74
Density Change
VolumeCFM2= CFM1
Static Pressure
SP2= SP1x (Density2/Density1)Horsepower
HP2= HP1x (Density2/Density1)
Sound Power
Lw2= Lw1+ 20 log x (Density2/Density1)
(Ref. Page 25)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
21/74
Density Change Example
Problem:Find the new performance at 600F and
0.0375 lbs/ft3 given the performance at
70F and 0.075 lbs/ft3:
Given: 880 RPM
Flow = 125,000 cfmDensity = 0.075 lbs/ft3 @ 70F
SP = 20 in-H2O
BHP = 525 hp
SolutionCFM2=CFM1=125,000 cfm; (Constant Volume Machine)
SP2 = (20 in-H2O) x (0.0375/0.075) = 10 in-H2O
HP2 = (525 hp) x (0.0375/0.075) = 262 hp
(Ref. Page 25)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
22/74
Density Change Example Curve
Volume (CFM) x 1000
25020015010050
Pressure(InH20)
25
20
15
10
5
0
BHP
1000
800
600
400
200
10
20
262 BHP
525 BHP
125000CFM
ROBINSON INDUSTRIES, INC.
FAN : 83" x 14.38" FRD
FOR : Basic Fan Laws I
FAN SPEED : 880
TEMP. : See Below
SP
BHP
T1 = 70 F
D1 = 0.075
T2 = 600 F
D2 = 0.0375
8/14/2019 B1. Fan Laws and Fan Control - Robinson
23/74
Speed Change(incompressible flow)
Volume
CFM2= (RPM2/ RPM1) x (CFM1)
Static Pressure
SP2= (RPM2/ RPM1)2x (SP1)
Horsepower
BHP2
= (RPM2/ RPM
1)3x (BHP
1)
Sound Power
Lw2= Lw1+ 50 log (RPM2/ RPM1)(Ref. Page 23)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
24/74
Speed Change Example
Question: Customer will change speed from 1180 rpm to 880
rpm. What will be the new performance?
Given:The existing fan has the following performance.
1180 rpm
100,000 acfm
20 in-H2O Static Pressure @ 70 degF
432 bhp
Solution:
acfm2= (100,000) x (880/1180)1= 74,576 acfm
Ps2 = (20.0) x (880/1180)2= 11.1 in-H2O
bhp2= (432) x (880/1180)3= 179 bhp
Note: The new performance is still on the original system resistance curve.The original efficiency is maintained.
(Ref. Page 23 of Robinson Fan Performance and Design Manual)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
25/74
Speed Change Example Curve
Volume (CFM)1601208040
Pressure
InH20
30
25
20
15
10
5
0
BHP
1200
1000
800
600
400
200
11.1 SP
20 SP
179 BHP
432 BHP
74576 CFM 100000 CFM
ROBINSON INDUSTRIES, INC.
FAN : 64" x 12.94" FRD
FOR : Basic Fan Laws I
FAN SPEED : 1180 & 880
TEMP. : 70
DENSITY : 0.075
SP
BHP
SYSTEM RESISTANCE
8/14/2019 B1. Fan Laws and Fan Control - Robinson
26/74
Size Change Fan Law
VolumeCFM2= (Size2/ Size1)
3x (CFM1)
Static Pressure
SP2= (Size2/ Size1)2x (SP1)Horsepower
BHP2= (Size2/ Size1)5x (BHP1)
Sound PowerLw2= Lw1 + 70 log (Size2/ Size1)Note: All fan dimensions change in proportion to the wheel
diameter. Used to size fans from lab prototype tests.
(Ref. Page 24)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
27/74
Size Change Example
Fans with Geometric Similarity What is the performance of a 90 inch dia radial
bladed fan, based on a 40 inch dia geometricallysimilar test fan (at the same speed and density)?
Given: 40 inch diameter radial bladed fan
9,000 cfm20 SP @ 70F, 0.075 lb/ft339 BHP
Solution: for 90 inch diameter geometrically similarfan
CFM2 = (90/40)3x (9,000) = 102,516 CFMSP2 = (90/40)2x (20) = 101.3 H2OBHP2 = (90/40)5x (39) = 2249 HP
(Ref. Page 24)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
28/74
Repairs and tip-outsA worn out wheel can be not only be refurbished, but also tipped-
out to achieve a slightly higher volume and pressure capability.
8/14/2019 B1. Fan Laws and Fan Control - Robinson
29/74
Size Change: Tip-Out or De-Tip
VolumeCFMMod= (Diamod/ Diaorig)
2x (CFMorig)
Static Pressure
SPMod= (Diamod/ Diaorig)2
x (SPorig)Horsepower
BHPMod= (Diamod/ Diaorig)4x (BHPorig)
Sound PowerLwmod> Lw + 70 log (Diamod/Diaorig)
(Ref. Page 24 of Robinsons Fan Performance and Design Manual)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
30/74
Tipped-out RB Wheel
8/14/2019 B1. Fan Laws and Fan Control - Robinson
31/74
Tipped-out RT Wheel
8/14/2019 B1. Fan Laws and Fan Control - Robinson
32/74
Tip-out and De-Tip Notes
Only the wheel diameterchanges.
Normal Tip-Out or De-Tip
is up to 5%Maximum is around 10%for some fan types
Increased Noise
Cannot De-Tip an AirfoilWheel
(Ref. Page 24)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
33/74
Tip-Out Example
Problem: Customer ABC has a 100 diameter wheel and they wouldlike to tip it out by 5%, (new wheel diameter is 105). What would bethe new performance?
Given: 100 inch diameter wheel
100,000 CFM
20 H2O @ 70F393 BHP
Solution:
CFMmod= (105/100)2x (100,000) = 110,250 cfm
SPmod= (105/100)2x (20) = 22.05 in. H2O
BHPmod= (105/100)4x (393) = 478 bhp
(Ref. Page 24 of Robinsons Fan Performance and Design Manual)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
34/74
Fan Laws Summary
Q2= (Q1)(D2/D1)3(N2/N1)1(1)(Kp2/Kp1)-1
P2= (P1)(D2/D1)2(N2/N1)2(2/1)1(Kp2/Kp1)-1
HP2= (HP1)(D2/D1)5(N2/N1)3(2/1)1(Kp2/Kp1)-1
Lw2= (Lw1)+70log(D2/D1)+50log(N2/N1)+20log(2/1)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
35/74
Fan Curves
See reference document titled:
Modified Fan Performance Curve Calculator
8/14/2019 B1. Fan Laws and Fan Control - Robinson
36/74
Fan Control
Outlet Damper
Inlet Damper (various types)
Speed Adjustment
ConsiderationsInitial Cost
Energy Cost
Mechanical & Electrical Maintenance &Reliability
8/14/2019 B1. Fan Laws and Fan Control - Robinson
37/74
Outlet Damper Control
Volume (CFM) x 1000
30025020015010050
Pressure(InH20)
50
40
30
20
10
0
BHP
2000
1600
1200
800
400
42.5 SP
1000 BHP
105000 CFM
ROBINSON INDUSTRIES, INC.
FAN : 83" x 14.38" FRD
FOR : Basic Fan Laws I
FAN SPEED : 1180
TEMP. : 70
DENSITY : 0.075
: .
: .
:
SP
BHP
Turndown can
be achieved bypartially closinga fan outletdamper. In thisexample, thepressure drop
across the outletdamper is 22.5in-H2O (= 42.5-20). Thesystemperformance is20 in-H2O at105,000 CFM.
(Ref. page 19)
Rated at
150,000 acfm
and 40 in-H2O
Pressure loss= 22.5 in-H2O
Inlet Louvered Damper Control
8/14/2019 B1. Fan Laws and Fan Control - Robinson
38/74
Inlet Louvered Damper Control
The same
operatingpoint canbeachievedbythrottling
an inletlouvereddamper to20 degreesopen. TheBHP is
reduced to880 due topre-spin.(Ref. pages20-21)
Volume (CFM x 1000)
3002752502252001751501251007550250
50
45
40
35
30
25
20
15
10
5
0
BHP
4000
3600
3200
2800
2400
2000
1600
1200
800
400
0
Robinson Industries, Inc.Fan : 83" x 14.38" FRD SWSI
For : Basic Fan Laws I
Fan Speed : 1180 RPMTemperature : 70F
Dens ity : 0.075 LB/FT
Date : 02/02/1999Quote Number : 123456
RII FO # : 123456
EF :1SE :1TF :1
Note: Louvered damperedcurves are approximate
SP
20 4060
BHP20
4060
Note: InletP(s) Ratio = 0
880 BHP
105000 CFM
20 in. H20
8/14/2019 B1. Fan Laws and Fan Control - Robinson
39/74
Louvered Damper
15% leakage (typical).
Parallel blade operation.
Lower efficiency when dampered.Good for dirty airstream.
Synchronized operation forDWDI.
(Ref: Page 68)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
40/74
Louvered Inlet Damper
8/14/2019 B1. Fan Laws and Fan Control - Robinson
41/74
Radial Inlet Damper Control The same
operating
point can beachieved bythrottling aradial inletdamper to25 degreesopen. TheBHP isreducedfurther to700 due tothe moreeffectivepre-spinthan thelouveredinlet damper
(Ref. pages20-21)
Volume (CFM x 1000)
3002752502252001751501251007550250
50
45
40
35
30
25
20
15
10
5
0
BHP
4000
3600
3200
2800
2400
2000
1600
1200
800
400
0
Robinson Indus tries, Inc.
Fan : 83" x 14.38" FRD SWSIFor : Basic Fan Laws I
Fan Speed : 1180 RPM
Temperature : 70FDens ity : 0.075 LB/FT
Date : 02/03/1999
Quote Number : 123456RII FO # : 123456
EF :1SE :1TF :1
Note: Radial damperedcurves are approximate
SP
20
30 45
BHP
2030
45
Note: InletP(s) Ratio = 0
700 BHP105000 CFM
20 in. H20
8/14/2019 B1. Fan Laws and Fan Control - Robinson
42/74
Radial Inlet Damper
8/14/2019 B1. Fan Laws and Fan Control - Robinson
43/74
Radial Inlet Damper
10-15% leakage (typical).
Good dampered efficiency
Center-support or cantileverdesign.
Good for open inlet SWSI.
Operating linkage outsideairstream.
(Ref: Page 68)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
44/74
Vortex Damper
10-15% leakage (typical).
High efficiency in damperedconditions.
Mechanism outside airstream.
Conical inlet pieces preferred.
Cannot be used without inletbox.
Split design available No need to extend bearing
centers for DWDI.
(Ref: Page 68)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
45/74
Variable Inlet Vane (VIV)
10-15% leakage (typical).
Built as part of the inletpiece.
Requires cone-shaped inlet
piece design. High efficiency when
dampered.
No need to extend bearingcenters on DWDI.
Mechanism in airstreamfor clean applications only.
(Ref: Page 68)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
46/74
Variable Inlet Vane (VIV) Damper
8/14/2019 B1. Fan Laws and Fan Control - Robinson
47/74
Speed Control
Volume (CFM) x 100025020015010050
Pressure(InH
20)
25
20
15
10
5
0
BHP
1000
800
600
400
200
20 SP
450 BHP
ROBINSON INDUSTRIES, INC.
FAN : 83" x 14.38" FRD
FOR : Basic Fan Laws I
FAN SPEED : 840
TEMP. : 70
DENSITY : 0.075
SP
BHP
SYSTEM RESISTANCE
105,000 CFM
The sameoperating pointcan be achievedby reducing the
speed from 1180rpm to 840 rpm.The BHP isgreatly reducedto 450 sincepeak efficiency
is maintained.
(Ref. page 22)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
48/74
Annual Operating Cost
Outlet Damper: 1000 HP = 313,000 $USLouverd Damper: 880 HP = 275,000 $US
Radial or VIV Damper: 700 HP = 219,000 $US
Variable Speed Control: 450HP = 141,000 $US
Example Calculation (for variable speed control):
(450 HP) x (0.746 kW/HP) x (350 days/yr.) x (24 hrs/day) x (0.05 $/kWh) = $140,994/yr
Note: 1 HP costs about $313/yr
8/14/2019 B1. Fan Laws and Fan Control - Robinson
49/74
System Effects
8/14/2019 B1. Fan Laws and Fan Control - Robinson
50/74
System Effects
Fan Performancecan be affectedby the
configuration ofductworkupstream and
downstreamof the fan.
(Ref. Page 28)
System Effects Fan Outlet
8/14/2019 B1. Fan Laws and Fan Control - Robinson
51/74
System EffectsFan Outlet
(Ref. Page 28)Reprinted from AMCA Publication 201-90
8/14/2019 B1. Fan Laws and Fan Control - Robinson
52/74
Effective Duct Length
(Ref. Page 29)Reprinted from AMCA Publication 201-90
S t Eff t F t f
8/14/2019 B1. Fan Laws and Fan Control - Robinson
53/74
System Effect Factor forOutlet Elbows
(Ref. Page 32)Reprinted from AMCA Publication 201-90
System Effects (Pressure Losses)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
54/74
System Effects (Pressure Losses)
(Ref. Page 33)Reprinted from AMCA Publication 201-90
CFD Analysis of Non Uniform
8/14/2019 B1. Fan Laws and Fan Control - Robinson
55/74
CFD Analysis of Non-UniformFlow in Fan Outlet Elbow
Forced Inlet Vortex
8/14/2019 B1. Fan Laws and Fan Control - Robinson
56/74
Forced Inlet Vortex -(Counter Rotating Swirl)
(Ref. Page 30)Reprinted from AMCA Publication 201-90
Decreased Fan
Aerodynamic Performance
Increased Fan Brake
Horsepower Requirement
Fan Aerodynamic Surge
/ Pulsation may Result
Non Uniform Flow Induced into
8/14/2019 B1. Fan Laws and Fan Control - Robinson
57/74
Non-Uniform Flow Induced intoFan Inlet by a Poorly Designed
Rectangular Inlet Duct
(Ref. Page 31)Reprinted from AMCA Publication 201-90
Most Common Cause of
Deficient Fan Performance
Fan Aerodynamic Surge
/ Pulsations may Result
Properly Designed Inlet
Box Provides a Predictable
Inlet Condition and
Maintains Stable Fan
Performance
N U if Fl i t F I l t
8/14/2019 B1. Fan Laws and Fan Control - Robinson
58/74
Non-Uniform Flow into Fan InletInduced by 90Round Section
Elbow - No Turning Vanes
(Ref. Page 31)Reprinted from AMCA Publication 201-90
System Effects (Pressure Losses)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
59/74
System Effects (Pressure Losses)
(Ref. Page 33)Reprinted from AMCA Publication 201-90
S t Eff t
8/14/2019 B1. Fan Laws and Fan Control - Robinson
60/74
System Effects
(Ref. Page 34)Reprinted from AMCA Publication 201-90
Non Uniform Flow Induced into Fan
8/14/2019 B1. Fan Laws and Fan Control - Robinson
61/74
Non-Uniform Flow Induced into FanInletCFD Analysis of Flow
8/14/2019 B1. Fan Laws and Fan Control - Robinson
62/74
Fan Stability
8/14/2019 B1. Fan Laws and Fan Control - Robinson
63/74
The Mechanics of Surging
(Ref. Page 36)
Th M h i f S i
8/14/2019 B1. Fan Laws and Fan Control - Robinson
64/74
The Mechanics of Surging
8/14/2019 B1. Fan Laws and Fan Control - Robinson
65/74
The Mechanics of Surging
(Ref. Page 36)
B
Desired Operating Point:
When operating volume
is reduced from A to B,
the fan responds bygenerating more pressure.
As a result the system
remains stable with the
flow proceeding from the
fan down the duct.
B
8/14/2019 B1. Fan Laws and Fan Control - Robinson
66/74
The Mechanics of Surging
(Ref. Page 37)
Undesirable Operating point:
When flow is reduced from
B to C, the fan responds by
generating less pressure. Then
the pressure in the downstream
duct is higher than the pressure
at the fan. The result is reverseFlow commonly called
surging .
C
The Mechanics of Surging
8/14/2019 B1. Fan Laws and Fan Control - Robinson
67/74
The Mechanics of Surging
(Ref. Page 37)
We normally only thinkAbout fan performance
in the first quadrant
i.e. positive flow and
positive pressure.
Flow reversal!
C
8/14/2019 B1. Fan Laws and Fan Control - Robinson
68/74
Inlet Damper Control
(Ref. Page 35)
Di h D
8/14/2019 B1. Fan Laws and Fan Control - Robinson
69/74
Discharge Damper
(Ref. Page 36)
Eliminates the Helmholtz
resonator effect of a largeduct or plenum,
Blow Off or Recirculation
8/14/2019 B1. Fan Laws and Fan Control - Robinson
70/74
Blow-Off or Recirculation
(Ref. Page 35)
Blow-off
RecirculationLoop
8/14/2019 B1. Fan Laws and Fan Control - Robinson
71/74
Robinson Surgeless Blower
(Ref. Page 38)
Robinson offers a
blower with special
surgeless characteristic
performance curve. The
peak pressure is at zero
volumetric flow.
8/14/2019 B1. Fan Laws and Fan Control - Robinson
72/74
Temperature Rise thru Fan
(Ref. Page 38)
8/14/2019 B1. Fan Laws and Fan Control - Robinson
73/74
Sound Considerations
Ref. Page 73
C it N i C
8/14/2019 B1. Fan Laws and Fan Control - Robinson
74/74
Community Noise Concerns