Upload
kienhou
View
218
Download
0
Embed Size (px)
Citation preview
8/13/2019 B Science 1 Report
1/40
8/13/2019 B Science 1 Report
2/40
8/13/2019 B Science 1 Report
3/40
3
INTRODUCTION
PURPOSE OF STUDY
One of the main purposes of this study is to get an understanding of the general principle of
heat transfer. Factors such as the effect of the sun of the thermal performance of the building,
thermal mass, insulation and air movement will be recorded in this report.
Furthermore, this assignment will increase our knowledge on how different building materials
thermal conductivity (k-value), measure of heat loss (u-value), thermal resistance (r-value) hasdifferent effects on heat gain or thermal environment in a particular space.
Lastly, we will be able to identify the environmental conditions related to the site conditions,
climate and human factor.
LIMITATIONS OF THE STUDY
Since the process of data logging the temperature readings and humidity only last for 72 hours,it might not be an accurate representation of the areas condition. Being placed in a small room,
the data logger might also be affected by the daily activities in the room by the fellow resident.
The room also has a huge sliding door made out of glass which will be an external weather
factor that affects the readings when the curtains are not closed.
PREVIEW
In this report, we will be presenting details about the experimented room, architectural
drawings of the house, results of the data logger, thermal analysis, wind analysis, solar analysis
and a discussion on ways to improve the thermal comfort of the house.
8/13/2019 B Science 1 Report
4/40
4
METHODOLOGY
DATA LOGGER
This data logger is called a thermal hygrometer. It is a device that records data over time with a
built-in instrument or either an external instrument and sensor. The main purpose of this
hygrometer is to record both temperature and humidity simultaneously for a given period of
time. In this project, the data is recorded for 3 days and saved up.
To prevent the data from being plagued with errors, the data logger was placed on a table
which is located in the middle of the room. The table is 1.0 meter above the ground floor. Thetemperature and humidity was recorded every 60 minutes and the device was not exposed to
any external source of heat that might disturb the reading.
The thermo hygrometer.
8/13/2019 B Science 1 Report
5/40
5
SITE PLAN
Satellite map of the site plan.
The room with the data logger is located on the ground floor of 61, Jalan SS15/2D, Subang Jaya,
47500, Selangor which is a double-storey terrace house. Since the site is located right in themiddle of a housing area, there wont be any activities that affect the readings of the data
logger.
8/13/2019 B Science 1 Report
6/40
6
FLOOR PLAN
The selected room in the house is located in the south west corner of the ground floor. The
room is a little cramped and certain appliances such as the laptop and lights will emit heat that
can affect the readings of the data logger.
Room plan. Ground floor plan.
8/13/2019 B Science 1 Report
7/40
7
ELEVATION
Since the house is located in between two other terrace houses, only the front elevation of this
house is visible. Based on the elevation and the floor plan, the room has a huge sliding door
that can be opened for ventilation and lighting. When not in use, there are curtains to block the
sunlight from entering the room and providing unnecessary heat.
Front elevation.
8/13/2019 B Science 1 Report
8/40
8
SECTION
With the section of the house, the length and height of doors, windows, openings and furniture
can be seen clearly.
Section A-A
8/13/2019 B Science 1 Report
9/40
9
LOCATION OF DATA LOGGER
The data logger was placed on a table in the middle of the room which is 1 meter above the
ground level of the first floor. This specific location was chosen so that it would be away from
any other heat sources in the room.
DETAILS OF THE ROOM (CONSTRUCTION & BUILDING MATERIALS)
The room chosen is a bedroom located inside a double-storey terrace house. This room is
3500mm wide, 4500mm long, and 3000mm in height. The bricks walls are cover by concrete
cement and a layer of white paint. The floor of the room is cover by tiles. The entrance to the
room is a single wooden hinged door. The room also has sliding doors with three normal glass
panels, which are facing the north. The room is only furnished with two fluorescent lights and
two ceiling fans.
8/13/2019 B Science 1 Report
10/40
8/13/2019 B Science 1 Report
11/40
11
HUMAN ADJUSTMENTS
On a hot day, the occupant usually turns the fan on maximum speed and directs it towards
himself. He might also slide the sliding door wide open for more air circulation. If the heat is
really unbearable, hell have to wear a singlet andprepare a cold drink to cool himself down.
On a cold and rainy day, the occupant will only leave the sliding door slightly open and put the
fan at its lowest speed. He will also put on a jacket if the temperature gets even lower. Warm-up exercises are also another option to keep the body warm.
8/13/2019 B Science 1 Report
12/40
12
RESULTS AND ANALYSIS
The monitoring of the data logger started at 12:28am on the 12th
of September 2013 until
12.28am on the 15th
of September 2013 for a total amount of 3 days. The temperature and
relative humidity was constantly recorded after every hour. The recorded values are then
placed in a table and plotted on a graph for further analysis. Studies and researches on thermal
comfort were then carried out after collecting all the data of temperature and humidity.
The tables shown in the next pages will show all the data we collected and also several factors
that will change the readings were included such as whether the room door or sliding door
were left open. The few graphs included will further explain the analysis of the data wecollected throughout this experiment.
8/13/2019 B Science 1 Report
13/40
13
TABLES
12th
September 2013
Time Relative Humidity (%) Temperature (C) Door
Sliding
Door Desktop
0:28:20 68.5 29.9 x / /
1:28:23 71.4 30 x / /
2:28:26 72.4 29.9 x / x
3:28:29 72.9 29.8 x / x
4:28:32 73.1 29.7 x / x
5:28:35 73.7 29.6 x / x
6:28:38 73.7 29.5 x / x
7:28:41 73.9 29.5 x / x
8:28:44 73.8 29.5 x / x
9:28:47 73.9 29.7 x / x
10:28:50 73.4 29.7 x / x
11:28:53 72.4 29.8 / / x
12:28:56 71.1 29.8 / / x
13:28:59 70.4 30.1 x / x
14:29:03 70.3 30.2 x / x
15:29:06 70.3 30.3 x / x
16:29:09 71 30.2 / / x
17:29:12 70.6 30.1 x / x
18:29:15 70.4 30.2 x / /
19:29:18 70.1 30.3 x / /
20:29:21 69.5 30.4 x / /
21:29:24 69.5 30.4 x / /
22:29:27 69.3 30.4 x / /
23:29:30 69.1 30.4 x / /
Highest temperature : 30.4C / = open/on
Lowest temperature : 29.5C x = closed/off
Highest RH value : 73.9
Lowest RH value : 68.5
8/13/2019 B Science 1 Report
14/40
14
13th
September 2013
Time Relative Humidity (%) Temperature (C) Door
Sliding
Door Desktop0:29:33 69.1 30.4 x / /
1:29:33 71.1 30.6 x / /
2:29:33 71.4 30.4 x / /
3:29:33 72 30.3 x / x
4:29:33 72.6 30.1 x / x
5:29:33 72.8 30.1 x / x
6:29:33 72.8 29.9 x / x
7:29:33 73.1 29.8 x / x
8:29:33 72.9 29.9 x / x
9:29:33 72.5 30.1 x / x
10:29:33 70.9 30.2 x / x
11:29:33 68.6 30.2 x / x
12:29:33 67.7 30.4 x / x
13:29:33 65.9 30.6 / / x
14:29:33 67.8 30.6 x / x
15:29:33 68.1 30.4 x / x
16:29:33 68.3 30.2 x / x
17:29:33 68.6 30.4 x / x
18:29:33 68.4 30.1 x / x19:29:33 68.2 30.2 x / /
20:29:33 68.4 30.2 x / /
21:29:33 68.4 30.4 x / /
22:29:33 68.6 30.5 x / /
23:29:33 69.4 30.6 x / /
Highest temperature : 30.6C / = open/on
Lowest temperature : 29.8C x = closed/off
Highest RH value : 73.1
Lowest RH value : 67.7
8/13/2019 B Science 1 Report
15/40
15
14th
September 2013
Time Relative Humidity (%) Temperature (C) Door Sliding Door Desktop0:30:47 70.1 30.6 x / /
1:30:50 70.5 30.5 x / /
2:30:53 71.1 30.4 / / x
3:30:56 70.9 30.3 x / x
4:30:59 70.6 30.3 x / x
5:31:02 70.6 30.2 x / x
6:31:05 71 29.9 x / x
7:31:08 71.2 29.8 x / x
8:31:11 71.4 29.8 x / x
9:31:14 71.3 29.9 x / x
10:31:17 70.8 30 x / x
11:31:20 70.6 30.1 x / x
12:31:23 69.6 30.2 x / x
13:31:27 69.9 30.4 x / x
14:31:30 70.2 30.6 x / x
15:31:33 69.6 30.4 x / x
16:31:36 69.2 30.3 x / x
17:42:51 69 30.2 x / x
18:42:54 69.5 30.4 x / x
19:42:57 70.4 30.1 x / /
20:21:02 70 30.2 x / /
20:28:07 68.2 30.3 x / /
21:28:10 68.2 30.2 x / /
22:28:14 68.1 30.1 x / /
23:28:17 68.1 30 x / /
0:28:20 68.1 30 x / /
Highest temperature : 30.6C / = open/on
Lowest temperature : 29.8C x = closed/off
Highest RH value : 71.4
Lowest RH value : 68.1
8/13/2019 B Science 1 Report
16/40
16
Total data accumulated in 3 days in a single graph.
0
10
20
30
40
50
60
70
80
90
100
0:30:00
2:30:00
4:30:00
6:30:00
8:30:00
10:30:00
12:30:00
14:30:00
16:30:00
18:30:00
20:30:00
22:30:00
0:30:002
2:30:004
4:30:006
6:30:008
8:30:0010
10:30:0012
12:30:0014
14:30:0016
16:30:0018
18:30:0020
20:30:003
22:30:005
0:30:007
2:30:009
4:30:0011
6:30:0012
8:30:0014
10:30:0016
12:30:0018
14:30:0020
16:30:0022
18:30:0024
20:30:0026
22:30:0028
0:30:0030
Temperature and Relative Humidity from the 12/9/13 to 14/9/13
Temperature Humidity ext Temperature ext humidity
8/13/2019 B Science 1 Report
17/40
17
THERMAL ANALYSIS
INDOOR
12th September 2013
On this day, the temperature was at its lowest from 3.30am until noon. The temperature
ranged between 29 degrees and 30 degrees. It started increasing after 12pm and peaked at
30.4 degrees from 8.30pm to 11.30pm. There isnt that much change in the room temperature
but the sliding door was slightly opened the whole day for some ventilation. The door was only
opened for a few hours during the day to promote air circulation. The temperature peaking at
midnight instead of during the day was due to the rain. The level of humidity was at its highest
during the day as well.
0
10
20
30
40
50
60
70
80
0:30:00
3:30:00
6:30:00
9:30:00
12:30:00
15:30:00
18:30:00
21:30:00
0:30:002
3:30:005
6:30:008
9:30:0011
12:30:0014
15:30:0017
18:30:0020
21:30:004
0:30:007
3:30:0010
6:30:0012
9:30:0015
12:30:0018
15:30:0021
18:30:0024
21:30:0027
0:30:0030
Temperature
Humidity
8/13/2019 B Science 1 Report
18/40
8/13/2019 B Science 1 Report
19/40
19
OUTDOOR
The outdoor temperature peaks at 33C everyday around the afternoon ranging from 1.30pmto 4.30pm. The lowest temperature is 25C and only occurs during the midnight until dawn.
The highest relative humidity level can reach 94% and the lowest touches 62%.
A hypothesis that can be made from the relation of these two variables is, the higher the
temperature, the lower the relative humidity level gets.
0
10
20
30
40
50
60
70
80
90
100
0:30:00
4:30:00
8:30:00
12:30:00
16:30:00
20:30:00
0:30:002
4:30:006
8:30:0010
12:30:0014
16:30:0018
20:30:003
0:30:007
4:30:0011
8:30:0014
12:30:0018
16:30:0022
20:30:0026
0:30:0030
ext Temperature
ext humidity
8/13/2019 B Science 1 Report
20/40
8/13/2019 B Science 1 Report
21/40
21
HUMIDITY
The indoor and outdoor humidity follows the same pattern but the relative humidity changesfor the indoors do not change as drastically as compared to the humidity outdoors. Compared
to the relative humidity outdoor, the relative humidity indoor seems almost static during the 3
days of recording.
There is also no air conditioning in the experimented room and only a fan is used to help cool
the room. Since the indoor temperature was mostly constant, the relative humidity had to
follow suit.
0
10
20
30
40
50
60
70
80
90
100
0:30:00
3:30:00
6:30:00
9:30:00
12:30:00
15:30:00
18:30:00
21:30:00
0:30:002
3:30:005
6:30:008
9:30:0011
12:30:0014
15:30:0017
18:30:0020
21:30:004
0:30:007
3:30:0010
6:30:0012
9:30:0015
12:30:0018
15:30:0021
18:30:0024
21:30:0027
0:30:0030
Humidity
ext Humidity
8/13/2019 B Science 1 Report
22/40
22
WIND ANALYSIS
Wind rose diagram.
8/13/2019 B Science 1 Report
23/40
23
SOLAR ANALYSIS
DAILY SUN PATH
Plan view of the sun path.
The Sun rising from the east.
8/13/2019 B Science 1 Report
24/40
24
The Sun nearing noon.
The Sun setting in the west.
8/13/2019 B Science 1 Report
25/40
8/13/2019 B Science 1 Report
26/40
26
July evening.
October evening.
8/13/2019 B Science 1 Report
27/40
27
SOLAR RADIATION
The recorded room will not be affected by the sunlight during the evening as it is located at the
west side of the house. Hence, the solar radiation in the evening will not be included.
ANNUAL SOLAR RADIATION IN THE MORNING
January, 10am.
April, 10am.
8/13/2019 B Science 1 Report
28/40
8/13/2019 B Science 1 Report
29/40
29
ANNUAL SOLAR RADIATION IN THE AFTERNOON
January, 1pm.
April, 1pm.
8/13/2019 B Science 1 Report
30/40
8/13/2019 B Science 1 Report
31/40
31
BIOCLIMATIC CHART
The chart above is the bioclimatic chart that has a selected comfort zone (the temperature
range within which one is comfortable following the readings from MS1525) and an average
value of the temperature and relative humidity.
The red point indicates that the indoor condition of the room is far from the comfort zone.
More wind movement is needed to lower the temperature of the room to the comfort zone.
Using shades from trees and roofs is also a way to keep the temperature lower.
8/13/2019 B Science 1 Report
32/40
32
A constant air movement is really important to keep the room temperature at comfortable
levels due to the tropical climate of Malaysia which is hot and humid. Windows must be shaded
from direct sunlight and opened for good air circulation. One of the most common ways in
Malaysia to increase the air movement in house is by using fans.
As the relative humidity of our climate is high, its difficult for our sweat to evaporate and in
turn causes us discomfort. A dryer air would benefit us much more. In order to do this, certain
houses use dehumidifiers to keep the relative humidity at the comfort level.
To achieve the comfort zone in an indoor environment, a good ventilation and dehumidification
will be needed.
8/13/2019 B Science 1 Report
33/40
8/13/2019 B Science 1 Report
34/40
34
2) Natural Ventilation
Natural ventilation is the use of the natural forces of wind and buoyancy to deliver sufficient
fresh air and air change to ventilate enclosed spaces without active temperature controls or
mechanical means.
Single-sided ventilation when one door is open. Cross ventilation when both doors
are open.
8/13/2019 B Science 1 Report
35/40
35
STACK VENTILATION
Hot air is less dense than cold air. Therefore, hot air will rise higher in the internal space while
cold air sinks lower. A good ventilation system should consider about the way to control the
movement of air to achieve the optimum air change rate. A good design that incorporates stack
ventilation will help to improve the internal ventilation.
With only one outlet as an opening, the ventilation in the room is poor. To improve this
condition and thermal comfort of the room, we would suggest to install a ventilation fan at the
wall of the sleeping area to increase the air exchange rate of the room.
The ventilation fan will help the room to perform the cross and stack ventilation and improve
the air circulation. We would also suggest the user of the room to open the sliding door fully on
hot days to increase the air change rate. This is because only one panel of the sliding door is
usually opened, which only provides 33% of ventilation efficiency.
Natural air driven
into the room
8/13/2019 B Science 1 Report
36/40
36
Cold air sinking.
Hot air rises
and is driven
out by the
ventilation fan
8/13/2019 B Science 1 Report
37/40
37
3) Building Materials
Building materials is another prime factor that affects the internal environment of a building.
The only opening in this room which is the sliding door is made out of normal glass only.
This glass has a poor performance in reflecting the light and UV rays which are the main factorsthat lead to high internal temperature. Furthermore, the huge size of the sliding door makes
the situation even worse. Therefore, we suggest changing the glass sliding door to double
glazing glass or tinted glass to reflect more UV rays.
4) Shading Devices
In order to reduce the direct heat gain from the sun radiation through openings and windows,
the ground level of the house is designed with a porch and overhang to shade the openings.
However the roof of this house is oddly designed because there are no roof overhangs that
shade the windows on the first floor. Therefore, the roof should be extended slightly to provide
some shade from the sun for the upper levels.
8/13/2019 B Science 1 Report
38/40
38
5) Roof Insulation
To ensure that the thermal comfort level of a house is always optimum, the design and
construction of the roof is extremely important as it is the part which receives the most
exposure to sunlight.
An example for smart roof designs is creating a ventilated loft to allow the trapped heat within
the roof to exit. An insulated ceiling design should also be used in the house to reduce the heat
transferred into the house from the roof.
8/13/2019 B Science 1 Report
39/40
39
CONCLUSION
As a conclusion, the experimented room in this assignment is not in the thermal comfort level
for people. Even though the building has the correct orientation, the ventilation in this small
room is very poor. This leads to a high temperature indoors.
Since there is only one opening in the room which is the sliding door, cross ventilation will not
usually occur due to the entrance to the room being closed most of the time. Due to the size of
the sliding doors, curtains are usually drawn out to block out the excessive sunlight. If the
sliding door was replaced with smaller openings, the occupant will not have to on the lights in
his room so frequently.
The building materials of the house can also use a better selection to improve the thermal
comfort. For example, the glass sliding door should be replaced with glazed glass for better
insulation. Furthermore, the roof of the house should have an extended overhang to shield the
upper levels of the house from direct sunlight.
There are many ways to improve the thermal comfort of this house besides relying on
mechanical means. A well designed house should have a great energy efficiency without
constraining the creativity of the design and comfort of the occupants.
8/13/2019 B Science 1 Report
40/40
REFERENCES
1) Stein, B. & Reynolds, John S.2000. Mechanical and Electrical Equipment for Buildings.New
York. John Wiley.
2) MS 1525, Code of Practice on Energy Efficiency and Use of Renewable Energy for Non-
Residential Buildings.
3) Weather information of Subang Jaya fromhttp://weatherspark.com/averages/34046/Subang-
Jaya-Selangor-Malaysia
4) Weather information of Petaling Jaya fromhttp://www.weather-
forecast.com/locations/Petaling-Jaya/forecasts/latest
5) Site plan fromhttps://maps.google.com/
http://weatherspark.com/averages/34046/Subang-Jaya-Selangor-Malaysiahttp://weatherspark.com/averages/34046/Subang-Jaya-Selangor-Malaysiahttp://weatherspark.com/averages/34046/Subang-Jaya-Selangor-Malaysiahttp://weatherspark.com/averages/34046/Subang-Jaya-Selangor-Malaysiahttp://www.weather-forecast.com/locations/Petaling-Jaya/forecasts/latesthttp://www.weather-forecast.com/locations/Petaling-Jaya/forecasts/latesthttp://www.weather-forecast.com/locations/Petaling-Jaya/forecasts/latesthttp://www.weather-forecast.com/locations/Petaling-Jaya/forecasts/latesthttps://maps.google.com/https://maps.google.com/https://maps.google.com/https://maps.google.com/http://www.weather-forecast.com/locations/Petaling-Jaya/forecasts/latesthttp://www.weather-forecast.com/locations/Petaling-Jaya/forecasts/latesthttp://weatherspark.com/averages/34046/Subang-Jaya-Selangor-Malaysiahttp://weatherspark.com/averages/34046/Subang-Jaya-Selangor-Malaysia